This document is a Scope of Work specification summary prepared by the State of Colorado, Design & Construction Management for the modernization of Freight Elevator #3 located at the State Office Building, 201 East Colfax Avenue in Denver, Colorado (Project 2024-070M23). The project involves the complete modernization of a single freight elevator with a 2,500-pound capacity operating at 200 feet per minute, servicing six primary floors plus an alley entrance. The scope of work encompasses replacement of the existing Otis geared hoist machine with a new permanent magnet AC gearless hoist machine, installation of new programmable microprocessor controllers compliant with ASME A17.1-2019 standards, upgrade of power-operated front freight doors with sequential closing operation, installation of new hoistway entrances with bi-parting door panels, and replacement of all related mechanical and electrical components including hoist cables, governor equipment, door tracking systems, and counterweight adjustments. Additional work includes cab refurbishment with new aluminum diamond plate flooring, installation of new signal fixtures and pushbutton stations, pit ladder and safety devices per current code, and comprehensive fire service integration with addressable smoke detection and three interface modules for primary floor recall, alternate floor recall, and machine room notification systems.
The specification document does not provide pricing information, contract award dates, response deadlines, bidder conference details, site visit requirements, or contract term information in this summary excerpt. The document explicitly notes that this summary is a brief outline and that if any discrepancy exists between the summary and the full technical specifications, the complete technical specifications should take precedence. The project represents a significant capital improvement initiative for state elevator infrastructure modernization with emphasis on compliance with current safety and fire service codes.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
State of Colorado - State Office Building 201 East Colfax Avenue Freight Elevator #3 - Modernization Specifications Denver, CO 80203 State of Colorado - Design & Construction Management - Project: 2024-070M23 Freight Elevator #3
FREIGHT ELEVATOR #3 - Scope of Work Summary and Schedule of Equipment (1)
Description:
Quantity 1
Speed/Capacity 200 FPM / 2,500 Lbs.
Stops/Openings 6 Front & 1 Rear (Alley) (B, 1, Alley, 2, 3, 4, 5)
Operation Simplex Operation with Sequential Closing Freight Doors
Machine Room:
Machine Remove existing Otis Geared Hoist Machine and install new Permanent Magnet AC Gearless Hoist Machine with Deflector Sheave in Machine Room, Bed Plate with Main and Auxiliary Brake Assembly. Install new Hoist Cables.
Machine Room Access Expand existing 36” X 33” Machine Room accessway and install a new “Wire Fence/Gate and lock.
Controller Provide new programmable microprocessor controllers. A17.1- 2019 compliant.
Power Conversion New Variable Voltage Variable Frequency Drive
Governor and Tail Sheave
Provide new Hollister-Whitney or “preapproved equal.”
Governor Rope Provide new Governor Rope.
Hoistway:
Overhead Sheave Install Overhead Deflector Sheave in the Machine Room.
Hoistway Entrances, and Bi-Parting Door Panels
Provide new "Front" Power Operated Car Gate and Power Operated Hoistway Bi-Parting Freight Doors Panels with New Car and Hall Pushbutton Stations and Sequential Operation Controls. Provide means for Hoistway Access at each floor. (Lock Box and Pull Chain) Rear/Alley Car Gate and Bi-Parting Hoistway Door shall remain Manual Operation.
Freight Power Door Equip.
Install new Door Unlocking Devices, Interlocks, and Pull Straps.
Hoistway Door Tracks, Motors, and Guide Shoes.
Install new Freight Door Tracks, Sheaves, Chains, Motors, Interlocks, Guide Shoes, and Hoistway "Pull Chain" Access devices, and Retiring Cams..
Car & Cwt Guide Shoes Install new Inserts in existing Guide Shoes.
Wiring/Duct Provide all new wiring and duct.
Counterweight Add/Remove weight for properly balance
Car:
Car Gate & Counterweight
Install new Power Front Car Gates and Manual Rear Car Gate with Cwt assembly. “Chip” Hoistway Wall as needed to accommodate at least a 13” Pocket for Power Door
State of Colorado - State Office Building 201 East Colfax Avenue Freight Elevator #3 - Modernization Specifications Denver, CO 80203 State of Colorado - Design & Construction Management - Project: 2024-070M23 Freight Elevator #3
Retiring Cams Install new Retiring Cams for Front and Rear Door operation.
Car Sling, Platform, Safeties, and Cab
Install new "Safety Operated Switch." (SOS) Clean and rretain the existing Car Sling, and Safeties. Replace worn Safeties. Clean, lubricate, adjust, and paint.
Cab: Clean and Paint the existing Freight Elevator Cab and Ceiling. Flooring:
Install new Aluminum “Diamond Plate” flooring.
Top of Car Railing Provide per current code
Pit:
Pit Ladder Provide per current code.
Stop Switch Provide new in compliance with code.
Buffers Refurbish as needed. Clean and paint.
Signal Fixtures
Car Operating Panel Provide new Main COP w/ digital PI. A17.1 2019 compliant.
Hall Call Fixtures Provide new Innovation Industries PB-35 or approved equal Hall Push Button Stations w/ digital PI, Door Open/Close Buttons, and Top/Bottom Hoistway Access
Door Close Signal (Buzzer and Strobe Light)
Provide “Buzzer” and “Flashing Light” on Cab to alarm after a predetermined length of time when Door/Gate is closing or left open.
Hoistway Access Sws. Provide Top and Bottom Hoistway Access per code
Emergency Fire Fighters’ Service Phase
I & II
In accordance with ASME A17.1 – 2019 and NFPA 73 and ther City/County of Denver Fire Department, install new addressable Smoke or other form of “Initiating Device/s” in each Elevator Lobby, Elevator Machine Room, Pit and Hoistway. Install three (3) Fire Panel and Elevator Control Panel “Interface Modules” within 3 feet of the new Elevator Control Panel. 1.) Primary Floor Recall 2.) Alternate Floor Recall 3.) Machine Room Flashing Hat
(1) Summary is just a brief outline to give general scope of work. If a discrepancy exists between the summary and body of the technical specifications, or if an item is not included in the summary, the body of the technical specifications should take precedence.