This document provides details on a federal solicitation opportunity and an associated file. The solicitation number is 36C77623B0005 for the EHRM Infrastructure Upgrades - Cincinnati Project #539-21-701. The opportunity type is a solicitation from the Department of Veterans Affairs Technology Acquisition Center Austin for construction services to upgrade the infrastructure at the Cincinnati VAMC. The associated file is a drawing attachment without further description. The solicitation is for infrastructure upgrade construction at the Cincinnati VA Medical Center for Project 539-21-701.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F1
F3
F1
F1
F
F1
F
F
DN
Service
Lobby
IRM
Storage
(Hdwr)
Stor.
A436A
Elec.
A436B
Comp. Rm.
A437C
Stor.
A444A
Corridor C*4*1
A
M
A
M
FEC
UNDERFLOOR PIPING
ABOVEFLOOR PIPING
ABOVEFLOOR NOZZLE (TYP.)
UNDERFLOOR NOZZLE (TYP.)
FEC
10 9
TO CRAC
UNITS
SEQUENCE OF OPERATIONS
THE CLEAN AGENT EXTINGUISHING FIRE EXTINGUISHING SYSTEM SHALL
OPERATE AS FOLLOWS:
1. ACTIVATION OF ANY SINGLE SMOKE DETECTOR SHALL:
A. ENERGIZE AN ALARM LED LAMP ON THE ACTIVATED DETECTOR
AND CLEAN AGENT CONTROL PANEL.
B. TRANSMIT AN ALARM SIGNAL TO THE BUILDING’S FIRE ALARM
SYSTEM.
2. ACTIVATION OF A SECOND SMOKE DETECTOR SHALL:
A. ENERGIZE AN ALARM LED LAMP ON THE ACTIVATOR DETECTOR.
B. ACTIVATE PRE-DISCHARGE BELL NOTIFICATION APPLIANCE AND
PREDISCHARGE STROBE NOTIFICATION APPLIANCE.
C. SHUT DOWN POWER TO ELECTRONIC EQUIPMENT WITHIN THE
PROTECTED SPACE, CLOSE DAMPERS, RELEASE DOOR HOLD
OPEN DEVICES, AND SHUT DOWN AIR HANDLING UNITS SERVING
THE PROTECTED SPACE.
D. INITIATE A PROGRAMMABLE 30-SECOND TIME DELAY (AGENT
RELEASE) SEQUENCE.
3. ACTIVATION OF A MANUAL ACTIVATION STATION SHALL:
A. ENERGIZE AN ALARM LED LAMP ON THE CLEAN AGENT CONTROL
PANEL.
B. ACTIVATE PRE-DISCHARGE BELL NOTIFICATION APPLIANCE AND
PRE-DISCHARGE STROBE NOTIFICATION APPLIANCE.
C. SHUT DOWN POWER TO ELECTRONIC EQUIPMENT WITHIN THE
PROTECTED SPACE, CLOSE DAMPERS, RELEASE DOOR HOLD
OPEN DEVICES, AND SHUT DOWN AIR HANDLING UNITS SERVING
THE PROTECTED SPACE.
D. TRANSMIT AN ALARM SIGNAL TO THE BUILDING’S FIRE ALARM
SYSTEM.
E. INITIATE A PROGRAMMABLE 20-SECOND TIME DELAY (AGENT
RELEASE) SEQUENCE.
4. ACTIVATION OF THE ABORT SWITCH SHALL:
A. CEASE THE TIME DELAY. ONCE THE ABORT SWITCH IS RELEASED,
THE TIME DELAY COUNTDOWN SHALL RESUME FROM WHERE IT
CEASED. THE TIME DELAY SHALL NOT RESET.
B. TRANSMIT A TROUBLE SIGNAL TO THE BUILDING’S FIRE ALARM
SYSTEM.
5. UPON COMPLETION OF THE TIME DELAY, THE SYSTEM SHALL:
A. DE-ENERGIZE THE PRE-DISCHARGE BELL AND PRE-DISCHARGE
STROBE NOTIFICATION APPLIANCE.
B. ACTIVATE A DISCHARGE STROBE NOTIFICATION APPLIANCE
INSIDE AND OUTSIDE OF THE PROTECTED AREA.
C. ENERGIZE VALVE ACTUATOR FOR AGENT CYLINDERS RELEASING
GASEOUS AGENT INTO THE PROTECTED AREA.
6. ACTIVATION OF THE LOW AGENT TANK PRESSURE SWITCH AND
MAINTENANCE LOCK-OUT SWITCH SHALL:
A. ENERGIZE A SUPERVISORY LED LAMP ON THE CLEAN AGENT
CONTROL PANEL.
B. TRANSMIT A SUPERVISORY ALARM SIGNAL TO THE BUILDING’S
FIRE ALARM SYSTEM.
7. PRESENCE OF ANY FAULT, BYPASS FUNCTION, OR REMOVAL OF THE
ELECTRIC VALVE ACTUATOR SHALL:
A. ENERGIZE A TROUBLE LED LAMP ON THE CLEAN AGENT CONTROL
PANEL.
B. TRANSMIT A TROUBLE SIGNAL TO THE BUILDING’S FIRE ALARM
SYSTEM.
8. ACTIVATION OF DUCT DETECTOR OR SMOKE DETECTOR WITHIN A
COMPUTER ROOM AIR CONDITION UNIT SHALL ENERGIZE A SUPERVISORY
SIGNAL LED LAMP ON THE CLEAN AGENT CONTROL PANEL AND
SHUTDOWN CRAC UNITS.
CLEAN AGENT GENERAL NOTES
1. NOVEC 1230 SYSTEMS SHALL BE INSTALLED AND TESTED IN
ACCORDANCE WITH NFPA 2001, CLEAN AGENT FIRE EXTINGUISHING
SYSTEMS, MANUFACTURER'S CURRENT PRINTED RECOMMENDATIONS,
CODES, AND STANDARDS ADOPTED BY THE LOCAL AUTHORITY HAVING
JURISDICTION.
2. NOVEC 1230 SYSTEM INSTALLATION SHALL BE PERFORMED OR
SUPERVISED BY THOSE SKILLED IN CLEAN AGENT FIRE EXTINGUISHING
SYSTEMS TECHNOLOGY.
3. ALL DEVICES, APPLIANCES, AND EQUIPMENT USED IN THE NOVEC 1230
EXTINGUISHING SYSTEM SHALL BE LISTED AND APPROVED BY UL AND FM
GLOBAL.
4. PIPING:
A. PIPING SHALL CONFORM WITH THE REQUIREMENTS SET FORTH IN
NFPA 2001, CLEAN AGENT FIRE EXTINGUISHING SYSTEMS.
B. PIPING SHALL BE BLACK STEEL PIPE CONFORMING TO ASTM-A-53
OR A-106, SCHEDULE 40 OR 80, WITH AN INTERNAL WORKING
PRESSURE OF 620 PSIG.
C. ORDINARY CAST-IRON PIPE, STEEL PIPE CONFORMING TO ASTM
A-120 , OR NONMETALLIC PIPE SHALL NOT BE USED.
D. EACH PIPE SECTION SHALL BE REAMED, BLOWN CLEAR, AND
CLEANED INTERNALLY AFTER PREPARATION AND BEFORE
ASSEMBLY BY MEANS OF SWABBING UTILIZING A SUITABLE,
NONFLAMMABLE CLEANER SUCH AS TRICHLORETHANE, ETC.
E. THE PIPING NETWORK SHALL BE FREE OF PARTICULATE MATTER
AND OIL RESIDUE BEFORE INSTALLATION OF DISCHARGE
NOZZLES.
F. STENCILED PIPE IDENTIFICATION SHALL NOT BE PAINTED OVER,
CONCEALED, OR REMOVED PRIOR TO APPROVAL OF THE LOCAL
AUTHORITY HAVING JURISDICTION.
G. PIPING NETWORK SHALL BE INSTALLED IN STRICT ACCORDANCE
TO SYSTEM PLANS AND PIPING ISOMETRICS PREPARED BY
CONTRACTOR. ANY PIPING CHANGES SHALL BE APPROVED BY
ROSS & BARUZZINI PRIOR TO FABRICATION OR INSTALLATION OF
MATERIALS.
5. FITTINGS
A. FITTINGS SHALL CONFORM WITH THE REQUIREMENTS SET FORTH
IN NFPA 2001, CLEAN AGENT FIRE EXTINGUISHING SYSTEMS.
B. MALLEABLE IRON FITTINGS SHALL BE 300 LB. CLASS CONFORMING
TO ASTM A-197.
C. 150 LB. CLASS, ORDINARY CAST IRON FITTINGS, AND HOLE-CUT
FITTINGS OR SIMILAR SHALL NOT BE USED. VICTAULIC TYPE
FITTINGS SHALL BE STYLE 75 OR 77.
D. UL LISTED VICTAULIC OR OTHER LISTED GROOVED PIPE FITTINGS
CAN BE USED.
E. PIPE JOINTS OTHER THAN THREADED, WELDED, BRAZED, FLARED,
COMPRESSION, OR FLANGED TYPE SHALL BE LISTED OR
APPROVED. ALL THREADS USED IN JOINTS AND FITTINGS SHALL
CONFORM TO ANSI B1.20.1
F. JOINT COMPOUND, PIPE TAPE, OR THREAD LUBRICANT SHALL BE
APPLIED ONLY TO THE MALE THREADS OF THE JOINT.
6. PIPING SUPPORT
A. PIPING SHALL BE SUPPORTED BY A COMBINATION NETWORK
COMPRISED OF PIPE HANGERS AND RIGID PIPE SUPPORT
RACKETS.
B. PIPE HANGERS SHALL BE USED TO SUPPORT THE "DEAD LOAD"
OF THE PIPING SYSTEM AND SHALL BE SPACED AT INTERVALS
NOT EXCEEDING 15 FEET.
C. RIGID PIPE SUPPORTS SHALL BE USED TO SUPPORT THE "LIVE
LOAD”OF THE PIPING SYSTEM DURING DISCHARGE. RIGID
BRACING IS REQUIRED AT EACH DIRECTIONAL CHANGE FITTING,
TEE, AND NOZZLE.
D. ALL DROPS TO 180 DEGREE NOZZLES REQUIRE BACK BRACING IN
THE OPPOSITE DIRECTION OF THE DISCHARGE.
E. EARTHQUAKE BRACING SHALL BE USED WHEN REQUIRED BY
LOCAL CODES. REFER TO ANSI B31.1, POWER PIPING CODE, FOR
FURTHER GUIDANCE ON SUPPORTING PIPING.
7. TESTING
A. THE COMPLETED SYSTEM SHALL BE REVIEWED AND TESTED BY
QUALIFIED FIELD ENGINEERING TECHNICIAN IN ACCORDANCE
WITH NFPA 2001 AND AS REQUIRED TO MEET THE APPROVAL OF
THE LOCAL AUTHORITY HAVING JURISDICTION.
B. PIPING NETWORK SHALL BE INSPECTED TO DETERMINE THAT IT IS
IN COMPLIANCE WITH THE DESIGN AND INSTALLATION
DOCUMENTS.
C. MEANS OF PIPE REDUCTION AND ATTITUDES OF TEES SHALL BE
CHECKED FOR CONFORMANCE TO THE DESIGN.
D. PIPING JOINTS, DISCHARGE NOZZLES, AND PIPING SUPPORTS
SHALL BE SECURELY FASTENED TO PREVENT UNACCEPTABLE
VERTICAL OR LATERAL MOVEMENT DURING DISCHARGE.
E. DISCHARGE NOZZLES SHALL BE INSTALLED IN SUCH A MANNER
THAT PIPING CANNOT BECOME DETACHED DURING DISCHARGE.
F. ALL AGENT STORAGE CONTAINERS SHALL BE PROPERLY
LOCATED IN ACCORDANCE WITH AN APPROVED SET OF SYSTEM
DRAWINGS.
G. ALL CONTAINERS AND MOUNTING BRACKETS SHALL BE
FASTENED SECURELY IN ACCORDANCE WITH THE
MANUFACTURER'S REQUIREMENTS.
H. THE PIPING NETWORK SHALL BE PNEUMATICALLY TESTED IN A
CLOSED CIRCUIT FOR A PERIOD OF 10 MINUTES AT 40 PSIG. AT
THE END OF 10 MINUTES, THE PRESSURE DROP SHALL NOT
EXCEED 20 PERCENT OF THE TEST PRESSURE.
I. A FLOW TEST USING COMPRESSED AIR SHALL BE PERFORMED ON
THE PIPING NETWORK TO VERIFY THAT FLOW IS CONTINUOUS,
AND THAT THE PIPING AND NOZZLES ARE UNOBSTRUCTED.
J. PROTECTED ENCLOSURE SHALL BE EXAMINED AND DOOR FAN
TESTED TO LOCATE AND THEN EFFECTIVELY SEAL ANY
SIGNIFICANT AIR LEAKS THAT COULD RESULT IN A FAILURE OF
THE ENCLOSURE TO HOLD THE SPECIFIED AGENT
CONCENTRATION LEVEL FOR THE HOLDING PERIOD. SEALING OF
THE ROOM SHALL BE BY OTHERS.
8. ALL PERSONNEL WHO WILL BE WORKING IN THE NOVEC 1230 PROTECTED
ENCLOSURE SHALL RECEIVE TRAINING REGARDING EXTINGUISHING
SYSTEM OPERATION AND AGENT SAFETY
9. COORDINATE LOCATIONS OF NOZZLES WITH HOT/COLD AISLE
CONTAINMENT TO PRODUCE THE REQUIRED CONCENTRATION
THROUGHOUT THE VOLUME SERVED.
10. COORDINATE THE SMOKE DETECTORS, INCLUDING AIR0ASPIRATING
SYSTEM WITH HOT/COLD AISLE CONTAINMENT TO PROVIDE COVERAGE IN
ACCORDANCE WITH MANFACTURER'S INSTRUCTIONS.
DEMOLITION KEYED NOTES
1. EXISTING SUPPRESSION PANEL TO BE REMOVED. CAP POWER SUPPLY
BACK TO SOURCE.
2. REMOVE EXISTING SMOKE DETECTORS AND ASSOCIATED WIRING IN
CEILING AND IN RAISED FLOOR CONNECTED TO CLEAN AGENT PANEL.
3. REMOVE EXISTING CLEAN AGENT STROBE/SPEAKERS. VIF.
4. REMOVE EXISTING CLEAN AGENT CYLINDERS, NOZZLES, PIPING, AND
SUPPORTS IN CEILING AND IN RAISED FLOOR.
5. REMOVE EXISTING ABORT SWITCH, MANUAL RELEASE AND MAINTENANCE
SWITCH IN ITS ENTIRETY.
1 5
A
M
SD
SD
SD
SD
SD SD
SD
SD
SD
SD
F
F
F
A
M
A M
CLEAN AGENT NOTES AND SYMBOLS
1. REFER TO SPECIFICATIONS SECTION 283000 FOR ADDITIONAL
INFORMATION PERTAINING TO THE FIRE ALARM SYSTEM.
2. SIGNALING LINE CIRCUITS SHALL BE ROUTED IN A CLASS B
CONFIGURATION
3. NOTIFICATION APPLIANCE CIRCUITS SHALL BE ROUTED IN A CLASS B
CONFIGURATION.
4. FIRE ALARM CIRCUITS SHALL BE ROUTED IN CONDUIT.
5. FOR VISUAL DEVICES, THE '#' WITHIN THE SYMBOL CORRESPONDS TO
THE CANDELA RATING OF THE DEVICE: 1=15cd, 3=30cd, 5=75cd, 7=177cd.
6. WALL MOUNTED NOTIFICATION DEVICES SHALL BE MOUNTED WITH THE
TOP OF THE DEVICE +90" A.F.F. OR 6" BELOW THE CEILING, WHICHEVER IS
LOWER.
7. PROVIDE ADDITIONAL APPPURTANCES AS REQUIRED TO CONNECT
CLEAN AGENT SUPPRESSION PANEL TO EXISTING FIRE ALARM CONTROL
PANEL.
A
M
CLEAN AGENT ABORT SWITCH: +48" A.F.F. TO CENTERLINE
MANUAL AGENT ABORT SWITCH: +48" A.F.F. TO CENTERLINE
WALL MOUNTED BELLF
WALL MOUNTED BELL WITH STROBEF#
CLEAN AGENT PIPING ABOVE RAISED FLOOR
CLEAN AGENT PIPING BELOW RAISED FLOOR
DUCT MOUNTED SMOKE DETECTOR : PHOTOELECTRIC TYPEDS
NEW WORK KEYED NOTES
1. NOVEC 1230 TANK LOCATION. SECURE TO WALL WITH WALL MOUNTED
TANK SUPPORTS. SYSTEM REQUIRES 740 LBS OF CLEAN AGENT FOR
APPROXIMATELY 1275 SF ROOM. ROOM DIMENSIONS SHALL BE VERIFIED IN
FIELD AND AGENT QUANITITY SHALL BE ADJUSTED BASED ON EXISTING
CONDITIONS.
2. PROVIDE NEW DOOR SEALS FOR THE DOORS IN THE ROOM.
3. CAULK BASEBOARD OPENINGS AND PENETRATIONS AROUND ROOM
PERIMETER, FLOORS, AND UNDERSIDE OF SLAB OF FLOOR ABOVE.
EXISTING OPENINGS SHALL BE SEALED AIRTIGHT WITH FIRE-RATED
SEALANT
4. AIR-ASPIRATING SMOKE DETECTOR APPARATUS. ONE SYSTEM SHALL
MONITOR THE RETURN AIR OF THE CRAC UNITS. THE OTHER SHALL
PROTECT THE RAISED FLOOR AND CEILING. SYSTEMS SHALL BE DESIGNED
AND INSTALLED BY MANUFACTURER.
5. A DUAL ACTION MANUAL PULL STATION WITH IDENTIFICATION INDICATING
AGENT RELEASE WITHIN PROTECTED ROOM, CLEAN AGENT ABORT SWITCH
AND SIGN MOUNTED 48" AFF DESCRIBING OPERATIONAL SEQUENCE OF THE
SYSTEM.
6. NEW CLEAN AGENT PANEL WITH SEPARATE MAINTENANCE KEYED SWITCH.
FIRE ALARM CONTRACTOR TO PROVIDE ALARM, SUPERVISORY, AND
TROUBLE CONTACTS FOR CLEAN AGENT SYSTEM. PROVIDE ADDITIONAL
APPPURTANCES AS REQUIRED TO CONNECT CLEAN AGENT SYSTEM TO
EXISTING FIRE ALARM CONTROL PANEL.
7. VERIFY PIPE ROUTING IN FIELD. NOZZLES SHALL BE INSTALLED WITHIN 12"
OF THE CEILING OR BOTTOM OF OBSTRUCTIONS. COORDINATE CLEAN
AGENT PIPING WITH CABLE TRAYS, RACKS, AND PLASTIC CURTAIN
SEPARATION.
8. PRESSURE RELIEF VENT TO BE INSTALLED IN A SUITABLE LOCATION TO
EQUALIZE PRESSURE IN THE ROOM UPON DISCHARGE OF AGENT. FINAL
SIZE AND LOCATION SHALL BE DETERMINED BY THE CLEAN AGENT
CONTRACTOR.
9. PROVIDE SIGNAGE FOR PREDISCHARGE STROBES AND BELLS IN
ACCORDANCE WITH SPECIFICATIONS.
10. PROVIDE SIGNAGE FOR DISCHARGE STROBES IN ACCORDANCE WITH
SPECIFICATIONS.
11. PROVIDE FM-200 FIRE EXTINGUISHER CABINET. FIRE EXTINGUISHER RATING
SHALL BE 2A:10B:C. COORDINATE WITH ARCHITECT.
12. NEW SMOKE DETECTORS TO REPLACE EXISTING AT CEILING AND RAISED
FLOOR. DETECTORS AT RAISED FLOOR ARE TO BE MOUNTED SIDEWAYS
WITH STEEL ANGLE SUPPORT. COORDINATE LOCATIONS WITH HOT AND
COLD AISLE, DUCTS, CABLE TRAY ETC.
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project TitlePhaseDrawing Title
Approved: Project Director
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784
San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
FULLY SPRINKLED
6 SOUTH OLD ORCHARD
WEBSTER GROVES, MO. 63119
T: 314.918.8383 F: 314.918.17666
/1 /2
:0
:0
P
M FP-205-C.1.4
FIRE PROTECTION FOURTH FLOOR
CLEAN AGENT PLAN
15-JUN-2022
RFJA
CINCINNATI VAMC EHRM
INFASTRUCTURE UPGRADES
539-21-701
3200 VINE ST. CINCINNATI, OH.
100% CONSTRUCTION
DOCUMENTS
1/4" = 1'-0"
CLEAN AGENT NEW WORK A437C
1/4" = 1'-0"
CLEAN AGENT DEMO WORK A437C
CLEAN AGENT PIPING DOWN TO
RAISED FLOOR
DN
796 SF
CORRIDOR
420 SF
CORRIDOR
762 SF
COURTYARD
BELOW
CRASH CART
MED CLOSET
NURSE STATION
QUIET ROOM
LINEN CLOSET
HAC
BATHROOM
248A
BATHROOM
247A
BEDROOM
BATHROOM
246A
BATHROOM
245A
BEDROOM
BEDROOM
BATHROOM
244A
BATHROOM
243A
BEDROOM
BEDROOM
BEDROOM
(NEGATIVE
PRESSURE)
BATHROOM
241A
BATHROOM
242A
BEDROOM
BEDROOM
(NEGATIVE
PRESSURE)
BATHROOM
240A
BATHROOM
239A
BEDROOM
ELECTRIC
CLOSET
BEDROOM
BATHROOM
238A
BATHROOM
237A
BEDROOM
BEDROOM
BATHROOM
236A
BATHROOM
235A
BEDROOM
BATHROOM
234A
SPECIAL CARE
BATHROOM
233A
SPECIAL CARE
RESIDENT
ROOM
68 SF
STAIR 1
S2.1
NURSE STATION
SOILED UTILITY
BATHING SUITE
COMP. CLOSET
KITCHEN
DINING ROOM
LIVING ROOM
WORK ROOM
211A
CLEAN SUPPLY
Redundant Room
CORRIDOR
229A
BEDROOM
02 STORAGE
315 SF
Room
232 SF
Room
STAFF
WOMEN'S
BEDROOM
1023 SF
CORRIDOR
STAFF MEN'S
STORAGE
STORAGE
TECH CLOSET
297 SF
LOBBY
LAUNDRY
Redundant Room
CORRIDOR
ROOF GARDEN
WORK ROOM
STORAGE
STORAGE
TECH CLOSET
297 SF
LOBBY
STORAGE
STORAGE
TECH CLOSET
297 SF
LOBBY
FP-212-C.2.2
FP-212-C.2.2
REMOVE/REWORK SPRINKLER HEADS
AND PIPING. REFER TO NEW WORK PLAN
3 ON THIS SHEET.
SPRINKLER CONTRACTOR SHALL PROVIDE
A FULLY COMPLIANT WET SPRINKLER
SYSTEM. CONTRACTOR SHALL VERIFY
EXISTING CONDITIONS AND REMOVE,
REWORK OR EXTEND EXISTING SPRINKLER
SYSTEM FOR NEW TELE ROOM. COMPLY
WITH VA AND NFPA #13 FIRE SUPPRESSION
REQUIREMENTS.
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project TitlePhaseDrawing Title
Approved: Project Director
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784
San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
FULLY SPRINKLED
6 SOUTH OLD ORCHARD
WEBSTER GROVES, MO. 63119
T: 314.918.8383 F: 314.918.17664
/2 /2
:1 :3
P
M
FP-212-C.2.2
FIRE PROTECTION SECOND FLOOR
OVERALL & ENLARGED PLANS
04-MAY-2022
DDPJA
CINCINNATI VAMC EHRM
INFASTRUCTURE UPGRADES
539-21-701
3200 VINE ST. CINCINNATI, OH.
100% CONSTRUCTION
DOCUMENTS
1/16" = 1'-0"
FIRE PROTECTION - BUILDING #2 - PARTIAL
SECOND FLOOR PLAN
1/4" = 1'-0"
STORAGE 204 - SECOND FLOOR PLAN -
DEMOLITION
1/4" = 1'-0"
STORAGE 204 - SECOND FLOOR PLAN -
NEW WORK
EQ EQ
EQ EQ
EQ EQ
36" 12"
36" 12"
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
24" X 48"
CEILING TILE
12" X 48"
CEILING TILE
12" X 12" / 24" X 24"
CEILING TILE
12" X 48"
CEILING TILE
24" X 48"
CEILING TILE
NOTE:
INDICATES CENTERLINE OF SPRINKLER HEAD
TYPICAL SPRINKLER BRANCH
LINE WITH ONE (1) INCH
OUTLET TEES
ONE (1) INCH RISER NIPPLE
LENGTH AS REQUIRED
1" X 1/2" REDUCING
COUPLING
UPRIGHT SPRINKLER HEAD
1/2" MAX.
RECESSED SPRINKLER HEAD
1" X 1/2" REDUCING
COUPLING
ONE (1) INCH
DROP - LENGTH
AS REQUIRED
ONE (1) INCH
DROP - LENGTH
AS REQUIRED
ONE (1) INCH
DROP - LENGTH
AS REQUIRED
TYP SPRINKLER
BRANCH LINE
WITH ONE (1) INCH
OUTLET TEES
S E
Q U
E N
C E
O F
O P
E R
A T
IO
N
E N
E R
G
IZ
E A
L A
R M
L E
D L
A M
P O
N D
E T
E C
T O
R
A C
T
IV
A T
E S
U P
E R
V
IS
O R
Y I N
D
IC
A T
IO
N
A C
T
IV
A T
E T
R O
U B
L E
I N
D
IC
A T
IO
N
P R
E -D
IS
C
H A
R G
E B
E L L A
N D
S T
R O
B E
S H
U T
D O
W N
P O
W E
R O
F E
L E
C T
R
IC
A L E
Q U
IP
M
E N
T
C L O
S E
D A
M P
E R
S
R E
L E
A S
E D
O O
R H
O L D
O P
E N
S H
U T
D O
W N
C R
A C
U N
IT
S
IN
IT
IA
T
E
S E
C O
N D
T
IM
E D
E L A
Y
IN
IT
IA
T
E
S E
C O
N D
T
IM
E D
E L A
Y
R E
S U
M E
C O
U N
T D
O W
N
D E
-E N
E R
G
IZ
E P
R E
-D
IS
C H
A R
G E
B E
L L A
N D
S T
R O
B E
A C
T
IV
A T
E D
IS
C
H A
R G
E S
T R
O B
E N
O T
IF
IC
A T
IO
N
A P
P L
IA
N C
E S
B U
IL
D
IN
G
S Y
S T
E M
A L A
R M
B U
IL
D
IN
G
S Y
S T
E M
T R
O U
B L E
B U
IL
D
IN
G
S Y
S T
E M
S U
P E
R V
IS
O
R Y
SYSTEM INPUT
1ST ALARM (1% OBS./FT)
2ND ALARM (4% OBS./FT)
CLEAN AGENT MANUAL RELEASE ACTIVATES
C E
A S
E T
IM
E
D E
L A
Y
ABORT ACTIVE
ABORT RELEASE
TIME DELAY COMPLETION
LOW AGENT TANK PRESSURE
SWITCH ACTIVATES
CIRCUIT TROUBLES
(FAULTS, REMOVAL OF ELECTRIC ACTUATOR)
DUCT DETECTOR OR SMOKE
DETECTOR IN DUCT ACTIVATES
A C
T
IV
A T
E A
L A
R M
I N
D
IC
A T
IO
N
E N
E R
G
IZ
E V
A L V
E A
C T
U A
T O
R F
O R
A G
E N
T C
Y L
IN
D E
R S
R E
L E
A S
E
PRE-ALARM (0.2% OBS./FT)
CLEAN AGENT
RELEASING PANEL
MAINTENANCE
DISCONNECT SWITCH
CLEAN AGENT
RELEASING SOLENOID
STROBE
SYNCHRONIZATION
MODULE
H/S H/S
HORN/STROBE
NOTIFICATION
FIRE ALARM
CONTROL
PANEL
MM
A M
ABORT SUPERVISION
MODULE
A M
ABORT SUPERVISION
MODULE
SUPERVISORY,
ACTION LEVEL
*SCHEMATIC SHOWN FOR REFERENCE ONLY.
REFER TO INSTALLATION INSTURUCTIONS FOR
DETAILED WIRING INFORMATION
MM
TROUBLE,
SUPERVISORY LEVELMM
ALARM, ACTION
LEVEL
H/S H/S H/S H/S H/S H/S
DS
AIR ASIPIRATING
DEVICE SMOKE
DETECTOR
MM
DS
MM
DS
MMMONITORING MODULE, (TYP.)
EXISTING DUCT
SMOKE DETECTORS
(TYP.)
ASD ASD
SUPERVISORY, ACTION
LEVEL (TYP. FOR
MONITORING DUCT
SMOKE DETECTORS)
MOTORIZED
DAMPER
CM
MOTORIZED
DAMPER
CM
MOTORIZED
DAMPER
CM
EMERGENCY
POWER OFF
CM CM
EMERGENCY
POWER OFF
CONTROL
MODULE
CM
EMERGENCY
POWER OFF
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project TitlePhaseDrawing Title
Approved: Project Director
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784
San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
FULLY SPRINKLED
6 SOUTH OLD ORCHARD
WEBSTER GROVES, MO. 63119
T: 314.918.8383 F: 314.918.17666
/1 /2
:3
:3
A
M FP-710
DETAILS
15-JUM-2022
RFJA
CINCINNATI VAMC EHRM
INFASTRUCTURE UPGRADES
539-21-701
3200 VINE ST. CINCINNATI, OH.
100% CONSTRUCTION
DOCUMENTS
NONE
SPRINKLER HEAD LOCATION IN NEW
CEILING PANELS
NONE
UPRIGHT SPRINKLER HEAD
NONE
RECESSED SPRINKLER HEAD
NO SCALE
CLEAN AGENT SEQUENCE OF OPERATIONS
NONE
CLEAN AGENT RELEASING PANEL
SD
F1
F1
SD
SMOKE ALARM SHALL NOT INITIATE FIRE
ALARM SYSTEM
CONNECT SPEAKER/STROBE TO EXISTING
FIRE ALARM SYSTEM
SMOKE ALARM ACTIVATED STROBE
SD
F#
FIRE ALARM SYSTEMS
SMOKE ALARM
CEILING MOUNTED SPEAKER WITH STROBE
1. REFER TO SPECIFICATIONS SECTION 283000 FOR ADDITIONAL
INFORMATION PERTAINING TO THE FIRE ALARM SYSTEM.
2. SIGNALING LINE CIRCUITS SHALL BE ROUTED IN A CLASS B
CONFIGURATION
3. NOTIFICATION APPLIANCE CIRCUITS SHALL BE ROUTED IN A CLASS B
CONFIGURATION.
4. FIRE ALARM CIRCUITS SHALL BE ROUTED IN CONDUIT.
5. FOR VISUAL DEVICES, THE '#' WITHIN THE SYMBOL CORRESPONDS TO
THE CANDELA RATING OF THE DEVICE: 1=15cd, 3=30cd, 5=75cd, 7=177cd.
6. WALL MOUNTED NOTIFICATION DEVICES SHALL BE MOUNTED WITH THE
TOP OF THE DEVICE +90" A.F.F. OR 6" BELOW THE CEILING, WHICHEVER IS
LOWER.
7. PROVIDE ADDITIONAL APPPURTANCES AS REQUIRED TO CONNECT
SMOKE DETECTOR TO EXISTING FIRE ALARM CONTROL PANEL.
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project TitlePhaseDrawing Title
Approved: Project Director
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784
San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
FULLY SPRINKLED
6 SOUTH OLD ORCHARD
WEBSTER GROVES, MO. 63119
T: 314.918.8383 F: 314.918.17664
/2 /2
:1 :5
P
M
FA-206.C.1.3
FIRE ALARM THIRD FLOOR
ENLARGED PLAN
04-MAY-2022
AuthorApprover
CINCINNATI VAMC EHRM
INFASTRUCTURE UPGRADES
539-21-701
3200 VINE ST. CINCINNATI, OH.
100% CONSTRUCTION
DOCUMENTS
1/4" = 1'-0"
RESIDENT OFFICE OVERNIGHT C383A -
THIRD FLOOR PLAN - NEW WORK
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project TitlePhaseDrawing Title
Approved: Project Director
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784
San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
FULLY SPRINKLED
6 SOUTH OLD ORCHARD
WEBSTER GROVES, MO. 63119
T: 314.918.8383 F: 314.918.17664
/2 /2
:0 :3
A
M
P-000
PLUMBING SYMBOLS AND
ABBREVIATIONS
04-MAY-2022
DDPJDB
CINCINNATI VAMC EHRM
INFASTRUCTURE UPGRADES
539-21-701
3200 VINE ST. CINCINNATI, OH.
100% CONSTRUCTION
DOCUMENTS
PLUMBING GENERAL NOTES
1. THIS CONTRACTOR SHALL VISIT THE PROJECT SITE AND VERIFY LOCATIONS, ELEVATIONS
AND SIZES OF ALL UTILITIES AT SITE PRIOR TO PROCEEDING WITH WORK. EXISTING
SYSTEMS AND STRUCTURE SHALL BE INVESTIGATED FOR BEST POSSIBLE ROUTING OF
COLD WATER, HOT WATER, SANITARY WASTE AND VENT, STORM AND MEDICAL
LABORATORY GAS PIPING.
2. THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THE ONLY AVAILABLE INFORMATION
HAS BEEN OBTAINED FROM EXISTING PLANS, SPECIFICATIONS, AND FIELD SURVEYS. THE
EXACT LOCATION OF PIPING, FIXTURES AND EQUIPMENT MAY DEVIATE FROM THE
LOCATION INDICATED ON THESE DRAWINGS. EXTREME ACCURACY IS NOT GUARANTEED.
THIS CONTRACTOR SHALL BE PREPARE TO MAKE ALTERATIONS TO NEW AND/OR
EXISTING SERVICES TO FIT JOB CONDITIONS. THIS CONTRACTOR SHALL FURNISH A
COMPLETE CODE COMPLYING SYSTEM. THIS CONTRACTOR SHALL REPORT, IN WRITING,
ANY DISCREPANCIES WHICH PREVENT THE INSTALLATION OF WORK AS SHOWN.
3. IF THIS CONTRACTOR DOES NOT CLEARLY UNDERSTAND THESE PLANS OR IS NOT
COMPLETELY SURE OF THEIR MEANING, THIS CONTRACTOR SHOULD OBTAIN THE
ENGINEER'S WRITTEN EXPLANATION AND/OR INTERPRETATION PRIOR TO SUBMITTING
BIDS, SINCE THIS CONTRACTOR WILL BE HELD RIGIDLY TO THE INTERPRETATION OF THE
ENGINEER.
4. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO REPAIR THE EXISTING SURFACES TO
REMAIN WHERE THEIR WORK HAS BEEN COMPLETED. REPAIR SHALL INCLUDE, BUT NOT
LIMITED TO, ANY EXISTING WALL, CEILING OR FLOOR THAT IS SCHEDULED TO REMAIN.
REPAIR, PAINTING, AND PATCHING SHALL BE COMPLETED BY AN APPROPRIATE
CONTRACTOR QUALIFIED FOR THIS TYPE OF WORK.
5. IF HAZARDOUS MATERIALS ARE ENCOUNTERED DURING DEMOLITION OPERATIONS, THE
CONTRACTOR WILL NOTIFY BUILDING OWNER OF THE HAZARDOUS MATERIAL.
6. TEMPORARY CONNECTION SHALL BE PROVIDED BY RESPECTIVE PLUMBING
CONTRACTOR WHEN EXTENDED INTERRUPTIONS OF SERVICES AND UTILITIES SUCH AS
WATER, WASTE AND FIRE PROTECTION WHICH SERVE OTHER AREAS ARE NECESSARY.
7. COORDINATE WITH MAINTENANCE PERSONNEL AS TO SOURCE OF UTILITIES AND
TEMPORARILY DISCONNECT OR SHUT OFF SERVICES OR UTILITIES AT NEAREST MAIN.
TEMPORARY AND ACCESSIBLE ISOLATION VALVES SHALL BE INSTALLED CLOSE TO THIS
POINT OF WORK.
8. IT IS ESSENTIAL THAT BUILDING OPERATIONS CONTINUE WITH MINIMAL INTERRUPTIONS.
IT IS NECESSARY THAT OPERATION OF EXISTING SYSTEMS BE INTERFACED WITH AS
LITTLE DISRUPTION AS POSSIBLE EXCEPT IN AREAS VACATED FOR CONSTRUCTION
WORK. WORK WHICH WILL INTERFERE WITH OPERATION OF EXISTING FIRE SUPPRESSION
AND PLUMBING SYSTEMS OR WHICH REQUIRE DOWNTIME WILL BE SCHEDULED ONLY
AFTER CONSULTATION WITH AND PERMISSION GIVEN BY THE OWNER. ALLOW 10 DAYS
PRIOR TO ANTICIPATED INTERRUPTION OF SYSTEMS. WORK MAY BE REQUIRED TO BE
PERFORMED OUTSIDE NORMAL WORKING HOURS.
9. ARCHITECTURAL, TECHNOLOGY, MECHANICAL, AND ELECTRICAL DEMOLITION, AND NEW
WORK DRAWINGS AND SPECIFICATIONS SHALL BE READ IN CONJUNCTION WITH THESE
DRAWINGS.
10. ALL PIPING HANGERS AND SUPPORTS SHALL BE REMOVED ALONG WITH PIPING BEING
REMOVED.
11. THE CONTRACTOR SHALL COORDINATE DEMOLITION WORK WITH PROJECT'S PHASING
SCHEDULE PRIOR TO COMMENCEMENT OF ANY WORK.
12. USE CAUTION WHEN SAW-CUTTING THROUGH EXISTING CONCRETE FLOOR OR WALL
CONSTRUCTION FOR THE INSTALLATION OF PLUMBING SYSTEMS TO AVOID CUTTING
REBAR AT EDGE OF OPENING.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY REVISIONS, TRANSITIONS, OFFSETS,
ETC., TO AVOID DUCTWORK, PIPING, EQUIPMENT OR STRUCTURE NEW OR EXISTING AND
TO MAKE A COMPLETE AND FUNCTIONING SYSTEM.
14. REMOVE ALL PORTIONS OF THE BUILDING (CEILING TILES, WALLS, SPRINKLER HEADS,
SPRINKLER HEAD ESCUTCHEON, ECT.) AS REQUIRED TO COMPLETE THE SCOPE
INDICATED IN THE CONSTRUCTION DOCUMENTS (SEE ARCHITECTURAL, TECHNOLOGY,
MECHANICAL, ELECTRICAL, AND FIRE PROTECTION DRAWINGS). REPLACE, REINSTALL, OR
COORDINATE REINSTALLATION WITH OTHER TRADES FOR ALL ITEMS REMOVED TO
ACCOMMODATE THE INSTALLATION/ REMOVALS OF ANY PLUMBING PIPE, FIXTURE,
EQUIPMENT, OR OTHER TRADES WORK, USING WORKERS QUALIFIED IN THE
APPROPRIATE TRADE. REPLACE CEILING TILES DAMAGED WITH THIS WORK TO MATCH,
REPAIR WALLS BACK TO THE ORIGINAL FINISH.
PLUMBING ABBREVIATIONS
NOT ALL SYMBOLS ARE USED FOR THIS PROJECT
ADA
AP
BP
BT
BTC
BV
CI
CO
CSS
DCVA
DS
DW
DWH
EEW
ESEW
ESH
ET
EWC
FCO
GCO
GD
HB
HWRP
HWST
IM
IW
LA
MB
NIC
OB
RD
RPZ
S
S/S
SH
SK
SP
SS
SSK
SW
TMV
UR
V
VB
VS
VTR
W
WC
WCO
WD
WH
WHA
WM
WS
WSV
YCO
AMERICANS WITH DISABILITIES ACT
ACCESS PANEL
BOOSTER PUMP
BATHTUB
BRANCH TO CONNECTION
BALANCE VALVE
CAST IRON
CLEANOUT
CLINICAL SERVICE SINK
DOUBLE CHECK VALVE ASSEMBLY
DOWNSPOUT
DISHWASHER
DOMESTIC WATER HEATER
EMERGENCY EYE WASH
EMERGENCY SHOWER & EYE WASH
EMERGENCY SHOWER
EXPANSION TANK
ELECTRIC WATER COOLER
FLOOR CLEAN OUT
GRADE CLEANOUT
GARBAGE DISPOSAL
HOSE BIBB
HOT WATER RETURN PUMP
HOT WATER STORAGE TANK
ICE MAKER
INDIRECT WASTE
LAVATORY
MOP BASIN
NOT IN CONTRACT
OUTLET BOX
ROOF DRAIN
REDUCED PRESSURE BACKFLOW PREVENTER
SANITARY
STAINLESS STEEL
SHOWER
SINK
SUMP PUMP
SANITARY STACK
SHOP SINK
SOFT WATER
THERMOSTATIC MIXING VALVE
URINAL
VENT
VACUUM BREAKER
VENT STACK
VENT THRU ROOF
WASTE
WATER CLOSET
WALL CLEANOUT
WASHER DRAIN
WALL HYDRANT
WATER HAMMER ARRESTOR
WATER METER
WASTE STACK
WASTE STACK VENT
YARD CLEANOUT
COMMON PFP SYMBOLS & ABBREVIATIONS
NOT ALL SYMBOLS ARE USED FOR THIS PROJECT
X
P501
DIRECTION OF FLOW
BRANCH CONNECTION, BOTTOM
BRANCH CONNECTION, TOP
ELBOW, TURNED DOWN
ELBOW TURNED UP
SHUTOFF VALVE
CHECK VALVE
PRESSURE REDUCING VALVE
PRESSURE GAUGE
UNION
PIPING CAP
EXISTING PIPING TO BE REMOVED
MATCH LINE
CONNECTION TO EXISTING
DETAIL DESIGNATION
RISER DESIGNATION
KEYED NOTE
REVISION NOTE
ABOVE FINISH FLOOR
AUTHORITIES HAVING JURISDICTION
ACCESS PANEL
BOTTOM OF PIPE
DIAMETER
DOWN
EXISTING
FINISHED FLOOR ELEVATION
GALLONS PER HOUR
GALLONS PER MINUTE
HORSEPOWER
INVERT ELEVATION
NORMALLY CLOSED
NOT TO SCALE
POUNDS PER SQUARE INCH
REVOLUTIONS PER MINUTE
ROUGH-IN
SHUTOFF VALVE
TOTAL DYNAMIC HEAD
VERIFY IN FIELD
AFF
AHJ
AP
BOP
DIA
DN
EX OR EXIST
FFE
GPH
GPM
HP
IE OR INV. ELEV
NC
NTS
PSI
RPM
RI
SOV
TDH
VIF
PLUMBING SYMBOLS & ABBREVIATIONS
NOT ALL SYMBOLS ARE USED FOR THIS PROJECT
TRAPPED CONNECTION
STRAINER
BALANCING VALVE
CLEANOUT (CO)
OS & Y GATE VALVE
TEMPERATURE GAUGE
THERMOSTATIC MIXING VALVE
REDUCED PRESSURE BACKFLOW PREVENTER
HOSE BIBB/WALL HYDRANT
ACID VENT
ACID WASTE
DRAIN PIPING
DEIONIZED WATER PIPING
REVERSE OSMOSIS PIPING (RO)
DOMESTIC COLD WATER PIPING (CW)
DOMESTIC HOT WATER PIPING (HW)
DOMESTIC HOT WATER RETURN PIPING (HWR)
NON-POTABLE WATER PIPING
PUMP DISCHARGE PIPING
SANITARY PIPING
SUBSOIL DRAINAGE PIPING
STORM PIPING
OVERFLOW STORM PIPING
TEMPERED WATER
VENT PIPING
EXISTING FIXTURE TO BE REMOVED
EXISTING FIXTURE
NEW FIXTURE
FLEXIBLE CONNECTION
FLOOR DRAIN/FLOOR SINK (FD/FS)
CIRCULATION PUMP
AV
AW
D
DI
RO
NP
PD
SSD
ST
OST
TW
S
/2
8/
Mens
Restroom
Dir.
Conference
Room A102
Office A103
Office A104
Secretary
Office A105
Associate
Dir. Office A106
Director's
Office A107
Chief of
Staff A108
Sec. Chief of Staff A109
Adm Asst.
A110
HAC
A111
Adm Asst.
A112
QA
Manager A113
Sec. &
Waiting A114
Risk
Management A115
Asst Chief
Social
Work A116
S.W. Off.
A117
S.W. Off.
A118
Staff Dir.
Asst.
A119
Stor A120
Public
Affairs A118A
Adm. Asst.
A114A
Chief Soc.
Work A115A
Tele A119A
Director
Public
Affairs
Office A113A
Med Staff
Coor.
A112A
Staff Dir.
Asst.
A119C
Clos A105A
Elec.
A111A
Clos A102A
Office B105
Office B106
Exam B107
SCI
Pharmacy B108
SCI Social
Worker B109
Office B110
Toilet B111
Exam B112
Stor B113
Storage B114
Exam B115
Stair 4 S*1*4
Exam B117
Waiting
Area B118
Corridor C*1*7
Stor B114A
Tele Clos B107A
Secretary B119
Off.
B127
Off.
B128
Off.
B129
Off.
B130
Off.
B131
Occ.
Therapy B132
Kit.
Multi-Purpose B133
Off.
B134
Off.
B135
Group Rm.
B137
Group
Room B132B
Adm. Asst.
B125
Office B125A
Stor.
B127A
Stor.
B137A
Stor.
B137B
Men's
Restroom A121
Stair 2 S*1*2
Quality
Assurance A123
AACOS
A124
F. Tlt.
A125
Service
Lobby A126
KIT.
A127
Food
Service A128
Volunteer A1035
Dry Storage A127B
Walk-In
Ref.
A127C
Walk-In
Ref.
A127D
HAC
A126B
Trash
Chute A126A
Corridor C*1*2
Elec.
A126C
Dry Stor.
A127A
Pizza Shop A131
Canteen
Dining A130
HAC
A133
Retail Store B101
Mech.
B101B
Office B103
Clerical B102
Elec.
B103A Stockroom
B101ATelecom Room
A134A
Audiology
Clinic B123
F. Tlt.
B104
Tlt.
B124
Tele.
B124A
RN Intake B139
Oxygen B140
Physical
Therapy/Occupational
Therapy B143
Speech
Pathology B144
Speech
Pathology B145
Neuropsychology B146
Electrical
Closet B141
Nave B163
Vestry B163B
Stor B163C
Chancel B163A
Chap. Clin.
Pastoral
Education B163G
Chaplain
Assistant B163H
Chief B163J
Chaplain B163K
Chaplain B163L
Corridor C*1*8
Corridor C*1*6
Pharmacy
Specialist B156
Storage B157
NP / Exam B158
Social
Work B159
Physician/Exam B160
Reception B162A
Waiting B162
Storage B161
Stor.
B150A
SVC.
Officer B147
SVC.
Officer B148
SVC.
Officer B148A
SVC.
Officer B150B
SVC.
Officer B149
SVC.
Officer B149A
Waiting
Room B150
Audiology C141
Corridor C*1*5
Corridor C*1*14
Off.
C134A
Adm. Asst.
C134B
Off.
C134C
Off.
C134D
Off.
C134E
Procedure C134FReceiving
C134G
Pharmacy C140
Off.
C129
Secure
Dispensing C133
Vault C143
Waiting C125
Consult C125A
Elec.
C126
Pharmacy C140B
Dispensing C125B
Sec.
C137
Voluntary
Service
Office B162C
Storage C162D
Agent
Cashier C162E
Agent
Cashier C162F
Agent
Cashier C162G
Transport C135
Voluntary
Service C137A
Corridor C*1*1
Volunteer
Office A1039
Volunteer
Office A1038
Sig.
A141A
Stair 1 S*1*1
Decedent
Affairs A144 A144A
Nurse
Pract.
A144B
Nurse
Pract.
A144C
Eligibility
Off.
A140
Clos A139
Clos.
A140A
F. Tlt.
A139A
Personnel
Health A139B
Personal
Health C132A
Person.
Hlth.
C132B
Off.
C130D
Off.
C130C
Social
Work SVC C130
Off.
C130A
Exam C130B
Signal C128
Tele.
C127
Stair 5 S*1*5
M. Tlt.
A174 Nursing
Lounge A158
Elec.
A161A
HAC
A160
F. Tlt.
A161
Phys.
A162
Phys.
A163
Phys.
A164
Phys.
A165
Nurse
Manager A166
Chief Nurse
Office A167
Chief Office A168
Prog. Asst.
A169
Waiting A170
Physician
Office A171
Phys.
A172
Stor.
A173
Elec.
A143
Tlt.
A158A
Stair 9 S*1*9
On Call A155
Tlt.
A155A
Sig.
A147A
Cl. Stor.
A147D
Cl. Lin.
A147C
Pub. Tlt.
A147B
Emergency A147
Secl.
A154
Secl.
A152
Minor
Surgery A153
Triage C120
Chief Off.
A151
Soil. Util.
A157
PCMM
Coordinator A146A
Quality
Manager A146B
Squad Stor.
A146
Heart Exam
A148
Heart Exam
A149
Restroom A149A
Heart Exam
A150
Corridor C*1*3
M. Tlt.
C124
F. Tlt.
C123
Employee
Health C122A
Conference
Room C122
Office C121
Exam C122D
Exam C122C
Police C119
Employee
I.D.
C119A
Off.
C119B
Off.
C119C
Lkrs.
C119D
Tlt C119E
Evidence C119F
Armory C119G Stor.
C119H
Waiting C116
PEC
C116A PEC
C116B
PEC
C116C
Off.
C116D
PEC
C116E
Holding C119K
M. Tlt.
C117
F. Tlt.
C118Holding
C119I
Corridor C*1*11
Stair 6 S*1*6
Clerk C102
Waiting
Room C103
Exam
Room C104
HAC
C105
PEA
C106
Exam C107
Exam C108 Elec.
C109
Exam C110
Alcove C111
Exam C112
Exam C113
Exam C114Exam
C115
Tlt C104A
Stor C104B
Corridor C101
PIV
Registrar B156A
Pain
School B156B
Elec.
B155
Elec.
B155A
Compund C140A
Stair 7 S*1*7
Tlt.
C1012
Work Rm.
C1013
Clinical
Pharm.
C1014
RN
C1015
Exam C1018
Exam C1019
Exam C1020
Exam C1021
Exam C1022
Exam C1023
Exam C1024
Exam C1025
Exam C1026
Meds C1027
Exam C1028
Exam C1029
Exam C1030
Office C1032
Clinicians
Break Rm.
C1033
Women's
Lockers C1033A
F. Tlt.
C1033B
Men's
Lockers C1033C
M. Tlt.
C1033D
Program
Assistant C1017
Care
Coordination C1013A
Pharmacist
Counselor C1034
Changing
Room-MRI C1035
Reception C1036
Social
Worker C1037
RN
C1038
Tlt.
C1039
Office C1040
Exam C1041
Wrk. St.
C1042
HAC
C1043
Exam C1044
Neg. Press.
C1045
Exam C1046
Exam C1047
Exam C1048
Neg. Press.
C1049
Exam C1050
Exam C1051
Exam C1052
Ante C1053
Procedure C1054
Elec.
C1055
Stor.
C1057
Tele.
C1059
Neg. Press.
C1061Soiled
Utility C1063
Exam C1000
Exam C1001
Exam C1002
Exam C1003
Exam C1004
Office C1005
Exam C1006
Exam C1007
Exam C1008
Procedure C1009
Office C1010
Office C1011
Storage B153
Work Area C1038A
Pharmacist
Counselor C165
Reception C167
Clinical
Pharm.
C168
RN
C169
Nutrition C170
Office C171
Exam C172
Work St.
C173
Tlt.
C174
Exam C175
Elec.
C176
Exam C177
Exam C178
Exam C179
Exam C180
Exam C181
Exam C182
Meds C183
Elec.
C184
Exam C185
Linen C186
Procedure C187
HAC
C188
Exam C189
Tele.
C190
Exam C191
Stor.
C192
Voluntary
Service C147
Mech.
C149
ATM
C150
Break
Room C151
Office C152
Office C153
Office C154
Exam C155
Exam C156
Exam C157
Exam C158
Exam C159
Tlt.
C160
Office C161
Office C162 Exam
C163
Office C164
Work Area C164A
Clos.
C163A
Info C166A
Office C166
F. Tlt.
C146
Storage C195
Blood Draw
Rm.
C193
RN
C194
Work Area C169A
Intake C196
Exam C197
Exam C198
Exam C199
Corridor C*1*12
Waiting
Room C145
Entry C-1-10L
Corridor C*1*15
Corridor C*1*19
Corridor C*1*16
Corridor C*1*17
Corridor C*1*18
Corridor C*1*20
Vestibule C144
Stair 10 S*1*10
Kit.
B152
Corridor C*1*23
Waiting
Area C100
Waiting
Room C100D
Stair 3 S*1*3
Corridor C*1*4
Sig B124B
Storage B132A
Recreation B151
Stor.
B151L
Office B125B
Conference B163D
Blessed
Sacrament B163E
Office C122B
Interview
Room C119J
Storage C135A
Entry A158B
M. Med.
Stor.
B151E
Elec.
B151K
M. Med.
Stor.
B151D
M. Med.
Stor.
B151C
Stor.
B151B
Med. Media B151A
Toilet B151I
Storage B151F Film Room
B151G Medical
Illust.
B151H
Closet B163F
Storage C162H
Entry C151A
HAC
A1028
Stair 11 S*1*11
Stair 8 S*1*8
Clerical B102A
Decon
Trailer A147E
Water
Treatment A101B
Shared
Office A1030
Office C1005A
PEC
C116H
PEC
C116F
Closet C119L
Volunteer
Storage A1036
Trailer C148
Desk A175C
Corridor C*1*21
Corridor C*1*22
Corridor C*1*9
Corridor C*1*13
Corridor C*1*10
Pharmacist
Counselor C145
PIV
Registrar C116G
Vending A134
Telecom Room
DN
UP
UP
DN DN
DN
UP
UP
UP
UP
DN
UP
UP
DN
DN
DN
DN DN
UPDN UP
DN
DN UP
DN
UP
DN
DN
A144A
Telecom Room
Telecom Room
A134A
Vending A134
P-120-C.1.1
P-120-C.1.1
PROVIDE DRIP PAN
WITH WATER SENSOR
S 4"
2"
S S
S
EX. CW & HW PIPING
PROVIDE DRIP PAN
PROVIDE WATER
SENSOR
PROVIDE WATER
SENSOR
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project TitlePhaseDrawing Title
Approved: Project Director
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784
San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
FULLY SPRINKLED
6 SOUTH OLD ORCHARD
WEBSTER GROVES, MO. 63119
T: 314.918.8383 F: 314.918.17664
/2 /2
:0 :4
A
M
P-120-C.1.1
PLUMBING FIRST FLOOR OVERALL &
ENLARGED PLANS
04-MAY-2022
DDPJDB
CINCINNATI VAMC EHRM
INFASTRUCTURE UPGRADES
539-21-701
3200 VINE ST. CINCINNATI, OH.
100% CONSTRUCTION
DOCUMENTS
1/16" = 1'-0"
PLUMBING - BUILDING #1 - OVERALL FIRST
FLOOR PLAN
1/4" = 1'-0"
CONF. ROOM A144A - FIRST FLOOR
PLUMBING PLAN
1/4" = 1'-0"
VENDING A134 - FIRST FLOOR PLUMBING
PLAN
/2
8/
Conference
Rm.
C236
Telecom Room
B232
Telecom Room
C236A
Telecom Room
A2006A
Stair 10 S*2*10
Lab B211
Recep.
A202
Imaging
Recep.
A201
Stor.
A202ADigital
Chest Rm.
A203
Dressing
Rm.
A203A
Speech
Pathlgy.
A204
Rehab
Care Line A205
Man Rehab
Care Line A206
Staff A207
Occupational
Therapy A208
EMG Lab A209
Rehab
Exam A210
Rehab
Exam A211
Elec.
A212
HAC
A213
Staff Tlt.
A214
PT Storage A215
Hydrotheraphy A216
Exam/Treatment
/ Exercise
Room A217
Physical
Ther.
Supervisor A218
Adl. Clinic A208A
EMG Lab A209A
Elec.
A217A
Corridor C*2*2
Light Box
Room A215B
SCI Exam A215A
Stor.
A218A
Stair 2 S*2*2
Oxygen
Storage A221
Therapy
Supervisor A222
Ante Room A223
Stor.
A210A
Equip
Wash A222B
Compressor
Room A222D
Equipment
Storage and Testing A228A
Storage A228B
Eto. Room B208A
Mech A228C
Office A230
Dressing
Rm.
A227B
Office A231
LKRS.
A227A
Shower A227
Elec.
A225B
Service
Lobby A225
Trash
Chute A225A
Lounge A226Training
Room A224
HAC
A225C
Office A232
Nuclear
Med. Sec.
C200
Waiting C201
Reading C202
Work Rm.
C203
CAT Scan
Room C204
Gamma
Camera C205
Uptake
Prep Bay C204A
Uptake
Area C204B
Uptake
Prep Room C204C
PET/CT
Scanner C204D
Echo Room C252 Echo Room
C251 Echo Rm
C250
Cath Lab C216O
Stor.
C216P
I.V. Prep
Rm.
C207
Elec.
C209
Control
Room C204E
Tlt.
C204F Tele.
C208
File Rm.
C200B
Chief Off.
C200A
Reading
Rm.
C250A
Chief Off.
C200C
Break
Room A240
Stair 1 S*2*1
Signal
Closet A239
M. Tlt.
A236
Tlt.
A235
G.P.
Radiography A242
Control A243
Storage A243A
Stair 5 S*2*5
Reading
Room A245
Gamma
Camera C210
Hot Lab C212
Stor.
C213
X-Ray
Room A246
Control A246A
Clos A243B
Clos A243C
Ultrasound A266
Corridor C*2*1
Elec.
A246B
Corridor C*2*3
Viewing A256
Reading
Room A257
Reading
Room A258
Adm.
A259
Chief
Radiology A260
Adm. Asst.
A261
Off.
A262
Resident
Reading
Room A263
Reading
Room A264
Reading
Room A262A
Tlt.
A260A
Pat. Rm.
A266B
Ultrasound A265
Stor A255 Tlt.
A253B
Break Rm.
A253
Elec.
A253A
HAC
A254
Digital
Radiography A252
Control A252A
Student
Off.
A251
Office A251B
Patient
Toilet A249C
Control A249B
BE
Fluororoom A249
Storage A249A
Work Rm.
A250A
Cl. Supp.
A296
Clean
Equipment A295
Sig. Clos.
A250
Clean
Supply
Room A251A
M. Lkrs.
A270
Tlt.
A270A
Staff
Lounge A269
F. Lkrs.
A271
Tlt.
A271A
Conf.
A272
RN
Manager A273
Elec.
A275
HAC
A274
On Call A276
Tlt.
A276A
Stair 9 S*2*9
Off.
A268
Off.
A267
Pat. Room A280
Pat. Room A281
Pat. Room A282
Pat Rm.
Pressure A283
Pat Rm.
Neg.
Pressure A284
Pat Rm.
Neg.
Pressure A285
Pat. Rm.
Neg.
Pressure A286
Pat. Rm A287
Pat. Rm.
A288
Pat. Rm.
Neg.
Pressure A289
Pat. Rm.
A290
Pat. Rm.
A291
Pat. Rm.
A292
Grieve/
Consult.
A293
Off.
A298 Meds.
A277
Nurse
Station A279
Staff Tlt.
A297
Lin.
A294
G.P.
Radiography A248
Tlt.
A248A
Trans.
A248B
Soil.
A278
Stair 4 S*2*4
Anatomic
Pathology
Gross
Room B215
Cytology B216
Special
Staining B217
Histology
Processing B218
Supervisor B219
Histology B220
Sig. Clos.
B221
Tele.
B222
Off.
B223
Sec.
B224
Operatory B225
Operatory B226
Dental Lab B227
Stor.
B228
Dental
Operatory B229
Dental
Hygeine B230
Oral Surg.
B231
Off.
B233
Corridor C*2*24
Lab Office B235
TB/ MYC
Lab B210B
TB/ MYC.
Lab B210C
ISO
B210D
ISO
B210E
Tele.
B210A
Lab B211A
Cold Rm.
B211B
Ante A235A
Dispatch
Area A236A
Clean
Supplies B201
F. Tlt.
B203A
M. Lkrs.
B202
Slide Stor.
B202A
F. Lkrs.
B203
Dir. Off.
B205
Off.
B207A
Elec.
B206
Corridor C*2*17
Off.
B207BOff.
B207C
Pathology
Off.
B209
Micro
Reading B208
Break
Room B210
HAC
B204
Corridor C*2*5
Corridor C*2*4
Stair 3 S*2*3
Waiting
Rm.
B224A
Oral Surg.
B231A
Off.
B233A
Stor.
B233B
Elec.
B233C
Off.
B235A
Tele.
B221C
Office B234A
Lab B234B
Lab B234C
Off.
B234D
Cancer
Registry B234E
Chief B234F
Off.
B234G
Prep Rm.
C214
Control C215
Cardiac
Cath Lab C216
Tlt.
C217
Waiting C218 Stair 6
S*2*6
Tele.
C220
Stor.
C221
Elec.
C222
Lockers C223
Lab Lounge C224
Hemo Stor.
C225
Mech.
C226
Lkrs.
C228
Chemistry
Hemotology
Lab C229
Blood Draw C230
Blood Bank C231
Storage C232
HAC
C234Storage
C235
Off.
C237
Break Rm.
C238
HAC
C239
Off.
C240
Off.
C241
Off.
C242
Off.
C243
Off.
C244
Stor.
C245
Exam C246
EKG Rm.
C247
Tlt.
C248
Scope
Wash C216A
Soil Ut.
C216B
Clean
Linen C216C
Observ.
C216D
Transfer C216E
Radiology
Spec Rm.
C216F
Scrub Area C216G
Cath Lab C216H
Control C216I
Equip C216J
Prep Mon C216K
Sterile
Supply C216L
Vestibule C216M
Control
Rm.
C216N
Bone
Density Lab C211
Tlt.
C216Q
Tlt.
C214A
CT
Scanner C214B
Sec.
C229A
Off.
C229B
Off.
C229C
Chief Off.
C229D
Clos C229E
Files C229F
Mech.
C229I
Special
Chem.
C229J
Toxicology C229K
Tele C229L
Elec.
C229M
Stor.
C229N
Shwr C228A
Tlt.
C228B
Off.
C229G
Off.
C229H
Soiled Ut.
C229O
Cold Stor.
C229P
Stair 8 S*2*8
Womens C2001
Mens C2003
Elec.
C2004
Blood Draw C2005
Work Rm.
C2007
HAC
C2008
Exam C2009
Intake C2010
Exam C2011
Stor.
C2012
Exam C2013
Stor.
C2014
Exam C2015
Exam C2016
Exam C2017
Exam C2018
Exam C2019
Waiting
Alcove C2020
Exam C2021
Exam C2023
Exam C2025
Tlt.
C2027
Gas Stor C2029
Lin.
C2031
Supply C2033Staff Tlt.
C2035
Soil C2037
Exam C2039
Tlt.
C2041
Exam C2043
Exam C2044
Exam C2045
Exam C2047 Exam
C2048
Exam C2049
Exam C2051
Exam C2052
Exam C2053
Exam C2054
Exam C2055
Exam C2056
Signal C2057
Office C2059
Exam C2069
Exam C2071
Exam C2072
Exam C2073
Exam C2074
Exam C2075
Exam C2076
Exam C2077
Work
Alcove C2078
Work
Alcove C2079
Exam C2080
Exam C2081
Exam C2082
Lin C2036
Break Rm.
C2038
Soiled
Utility A299
Elec.
A239A
Corridor C*2*25
Corridor C*2*12
Utility
Room B229A
Office B235B
Reception C2063
Waiting C2061
Storage C2067
Mech B208B
Stair C229R
Closet C216R
CT Room
#2 A2013
Stair 11 S*2*11
Clean
Supply A2011
Storage A2010
PACS
Read A2008
S.P.
Control A2009
Special
Procedures A2015
MRI
Component A2007
MRI Room A2001A
MRI
A2001
Equipment
Storage A2023
MRI
Equipment A2001B
MRI EMS
A2025
Corridor C*2*15
Waiting A2000
Dressing
Room A2002
Chage
Area A2002A
Toilet A2002B
Elec.
A2006
Signal A2005
Men Staff A2004
Women
Staff A2003
CT Control A2014
Adm.
Equip.
A2016A
CT Room
#1 A2016
S.P.
Equipment A2021
CT Prep A2017
Toilet A2018
Storage A2020
Office A2022
IR Reading A2024
Office A208A
CT Office A2019
Toilet A2024A
Storage A2026
Mechanical C232A
A/C Shaft
A/C Shaft
A/C Shaft
UP
DN
DN
DN
DN
UP
DN
UP
UP
DN UP DN
DN UP
UP
DN
UP
UP
Telecom Room
B232
B233A Stor.
P-130-C.1.2
ST
PROVIDE DRIP PAN
WITH WATER SENSOR
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project TitlePhaseDrawing Title
Approved: Project Director
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784
San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
FULLY SPRINKLED
6 SOUTH OLD ORCHARD
WEBSTER GROVES, MO. 63119
T: 314.918.8383 F: 314.918.17664
/2 /2
:0 :4
A
M
P-130-C.1.2
PLUMBING SECCOND FLOOR
OVERALL & ENLARGED PLANS
04-MAY-2022
DDPJDB
CINCINNATI VAMC EHRM
INFASTRUCTURE UPGRADES
539-21-701
3200 VINE ST. CINCINNATI, OH.
100% CONSTRUCTION
DOCUMENTS
1/16" = 1'-0"
PLUMBING - BUILDING #1 - OVERALL
SECOND FLOOR PLAN
1/4" = 1'-0"
DENTAL ROOM B232 - SECOND FLOOR
PLUMBING PLAN
/2
8/
S
A/C Shaft
BB
CC
G
K
L
H
F
AA
A.6A.6
SD
SP
Telecom Room
B312D
Telecom Room
Telecom Room
C305
C3008
/4
1/4" / 12"
1/4" / 12"
1/4" / 12"
1/4" / 12"
/4
" / 1
/4
" / 1
/4
" / 1
/4
" / 1
DN
ABOVE
DN TYP.
Isolation
Procedure
Rm.
C3024
Fluoro
Procedure
Rm.
C3023
Corridor C*3*14
Procedure
Rm.
C3021
Wash
Room C3020
Physician
Work Room C3019
Scope
Storage C3017
Ante Rm.
C3016
Scope
Cleaning C3016A
Procedure
Rm.
C3025
Procedure
Rm.
C3026
Prep/Recovery
Rm.
C3027
Clean
Supply C3014
Isolation
Prep/Recovery
Rm.
C3013Prep/Recovery
Rm.
C3028
Prep/Recovery
Rm.
C3029
Isolation
Prep/Recovery
Rm.
C3012
Prep/Recovery
Rm.
C3011
Prep/Recovery
Rm.
C3030
Prep/Recovery
Rm.
C3010
Staff Break
Rm.
C3009
Staff Toilet C3009A
Patient
Toilet Rm.
C3008
Storage C3007A
Signal
Clos.
C3035
Patient
Toilet Rm.
C3037
Prep/Recovery
Rm.
C3038
Prep/Recovery
Rm.
C3039
Post-Op C3040
Elec.
C3036A
Consult.
C3005
Lobby C3001
Waiting C3002
Staff
Lounge C326 Stair 10
S*3*10
Staff Work
Rm.
C3007
SPD Case
Cart C3034
O.R. #7 C329
O.R.
Storage C339
Anesthesia
Work Rm.
C337
Men's
Locker C324B
O.R. 1 C354
O.R. 2 C353
O.R.
Alcove C352
O.R.
Alcove C352A
O.R.
Alcove C352B
Light Rm.
C352C
O.R. 3 C351
O.R. 4 C350
Clean Core C340
Elec.
C338A
O.R. 5 C349
O.R. 6 C348
Mech.
C342
Corridor C*3*7
Women's
Locker C322
HAC
C346
Office C330
Cysto O.R.
C332
Cysto O.R.
C347
M. Shower C324AW. Shower
C322A
Sub-Waiting C3036
Work Rm.
C3004A
Nurse
Station C3031
Sterile Core C347A
Frozen
Section C316 Utility
C320
Office C318 Elec.
C335
Tele.
C333
Corridor C*3*9
Entry C324
A/C Shaft C337A
Soiled
Utility C3032
Men's C3002A
Women's C3002B
Pat. Tlt.
C3022
Reception C3004
Dr. Office C315
Office C317
Office C319
Office C321
Office C323
Office C325
Stair 6 S*3*6
Anesthesia
Tech.
C328
Cleaning
Supply C3016B
Temp.
Control C3005A
Oxygen
Storage C369
Vestibule C322B
Vestibule C324C
HAC
C3033
Patient
Room A387A
Patient
Room A387B
Patient
Room A387C
Patient
Room A387D
Patient
Room A387E
Patient
Room A387F
Patient
Room A387G
Shower A387H
Patient
Room A387I
Patient
Room A387J
Patient
Room A387K
Nurse
Station A387
Service
Lobby A338
M. Locker A339
F. Locker A340
Corridor C*3*19
RO DI
Water A343
De-Gown A342
Gowning
Rm.
A341
De-Con B303Prep/Pack
B307C
HAC
B303A
HAC
B307D
Office B305B
Office B305A
Office B305C
Conf Rm.
B305D
Vendor
Drop Off B304
Cool Down
Cart B307B
Steam
Equip Rm.
B307A
Open
Office B305
Ante Rm/
Clean Exit B307
Elec B306
Vasc. Lab A300
Vascular
Lab A301
Chief Diet.
A302
Diet Sec.
A303
Diet Off.
A305F. Tlt.
A306A
Waiting A307
Exam A308
Exam A309
Storage A310
Lab A311
Machine A311A
Plaster A312
CAD/CAM
A313
Off.
A314
Elec.
A315
M. Tlt.
A316
Stor.
A317
HAC
A318
Asst. Chief A319
Pros. Adm.
Asst.
A320
Clos.
A320A
Chief Off.
A321
Ward Adm.
Off.
A323
Adm. Asst.
A324
Office A324A
Office A324B
Office A324C
Chief PBS A324D
Office A324E
Office A324G
Stor.
A324F
Stor.
A324H
Elec.
A331A
Pros. Stor.
A330
Pros. Off.
A332
Stair 2 S*3*2 Stor.
A335
Stor.
A336
Asst. Chief
Diet.
A337
Corridor C*3*2
F. Tlt.
A341
M. Tlt.
A342
Stair 1 S*3*1
Stor.
A344
Sig.
A345
Stor.
A344A
Tlt.
A347A
Vasc. Lab A347
Elec.
A350
Mech.
A351
Adm. Asst.
A352
Off.
A353
Conf.
A354
Chief of
Surgery A355
Off.
A356
Off.
A357
Off.
A358
Off.
A359
Off.
A360
Off.
A361
Corridor C*3*3
Off.
A355A
Physician
Review A355B
Linen Clos.
A389
Nurse Off.
A390
Soil Utility A391
Equip. Stor.
A392
HVAC
A394
Elec.
A395
Sig.
A396
Clean
Supply A397
Vasc. Lab A379
HAC
A378
HAC
A380
Lounge A382
Tlt.
A382A
M. Lock.
A382BFemale
Locker A382C
Soc. Wrk.
A383
Respiratory
Therapy A384
Conference
Room A385
Pharm.
A386
On Call A381
Tlt.
A381A
Patient
Advocate A348
Off.
A349
Stair 5 S*3*5
Off.
A350B
Off.
A350D
Off.
A350A
Off.
A350C
Corridor C*3*1
Elect.
A346
Classroom B308
Nurse
Educator B309Stor.
B310
Office B311
Office B310A
Conf.
B310B
Off.
B311A
Off.
B311B
Lounge B311C
Asst. Ch.
B311D
Asst. Ch.
B311E
Adm. Off.
B311F
Word Proc.
B311G
Off.
B311H
Chief Nurse B311I
Research
Off.
B312
Off.
B312A
Sig.
B312B
Elec.
B312C
Stair 3 S*3*3
Nursing
Conf.
B314
F. Tlt.
B315
Stor.
B316
Eq. Stor.
B317
Res. Stor.
B318
Stor.
B319
Classroom B320
Office B321
Off.
B319A
Off.
B319B
Off.
B319C
Off.
B319D
Stor.
B321A
Classroom B321B
Work Area B320A
Stor.
B320B
Stor.
B320C
HAC
B319E
Stair 4 S*3*4
Stor.
B311M
Corridor C*3*5
Learning
Exchange B322
Work Area B322A
Work Area B322B
Elec.
B322C
Pat. Dining B325
Family
Waiting B326
Reception B327
Office C300
Consult C301
Break Rm.
C302
Patient Tlt.
C303
PACU
C304
C305 Office C306
Acute Care C307
Storage C308
Corridor C*3*6
Patient Rm.
C304A
Patient Rm C304B
Patiet Rm C304C
Meds.
C304D
Clean
Supp.
C304E
Patient Rm.
C304F
Patient Rm.
C304G
Patient Rm.
C304H
Patient Rm.
C304IPatient Tlt.
C304J
Patient Rm.
C304K
Patient Rm.
C304L
Patient Rm.
C304M
Patient Rm.
C304N
Patient Rm.
C304O
EMS
C360Off.
C361
Clean
Stretcher
Stor.
C355
Anaesthetics C356
Soil C357
Storage C358
HAC
C359
Electrical C309
Family
Wtng.
C310
Tele C311
Lactation C312
Grieve
Consult C313
ICU Dir.
Off.
C314
Corridor C*3*17
Adm. Asst.
A307A
Stor.
A324I
Tlt.
A388
Stair 9 S*3*9
HAC
B301
Db. Wtr B302
Tlt.
C302A
Tr. Ch.
A338A
Stair 8 S*3*8
Elec A338B
Linen Clost.
C3015
Corridor C*3*11
Corridor C*3*12
Corridor C*3*13
Corridor C*3*16
Corridor C*3*15
Corridor C*3*18
Room B303B
Room B307E
Storage B308A
Mechanical
A3002
Areaway
AW-1
Areaway
AW-2
Stair #11
A3001
Vestibule
A3003
A3004
A/C Shaft
A/C Shaft
UP
UP
UP
UP
UP
UP
UP
UP
DN
DN
DN
DNUP
DN UP
DN
UP
UPDN
DN
UP
T
P-140-C.1.3
REMOVE EXISTING FIXTURES
AND ASSOCIATED PIPING, CAP
BACK TO AN ACTIVE MAIN
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project TitlePhaseDrawing Title
Approved: Project Director
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784
San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
FULLY SPRINKLED
6 SOUTH OLD ORCHARD
WEBSTER GROVES, MO. 63119
T: 314.918.8383 F: 314.918.17664
/2 /2
:0 :5
A
M
P-140-C.1.3
PLUMBING THIRD FLOOR OVERALL &
ENLARGED PLANS
04-MAY-2022
AuthorApprover
CINCINNATI VAMC EHRM
INFASTRUCTURE UPGRADES
539-21-701
3200 VINE ST. CINCINNATI, OH.
100% CONSTRUCTION
DOCUMENTS
1/16" = 1'-0"
PLUMBING - BUILDING #1 - OVERALL THIRD
FLOOR PLAN
1/4" = 1'-0"
FAMILY WAITING ROOM C310 -THIRD
FLOOR - PLUMBING DEMOLITON PLAN
/2
8/
A/C ShaftA/C Shaft
A/C Shaft
DN
Reception A400
Interview A401
Interview A401A
Reception A401BInterview
A402A
HAC
A403
Stor.
A404
Med Room A405
Exam Rm.
A406
Exam Rm.
A407
Exam Rm.
A408
Exam Rm.
A409
Exam Rm.
A410
Exam Rm.
A411
Exam Rm.
A412
Exam Rm.
A413
Exam Rm.
A414
Exam Rm.
A415
Exam Rm.
A416
Exam Rm.
A417
Stor.
A418
Elec.
A418A
Stor.
A420
Staff Tlt.
A421
HSRD
Office A422
Dr's
Off.
A423
HSRD
Off.
A424
Oncology
Pharmacy
Sattelite A425
Chemo
Prep.
A425A
IRM Office A427
Stair 2 S*4*2
HSRD
Off.
A424A
Comp.
Training A430
Comp.
Specialist
Off.
A431
Service
Lobby A436
IRM
Network
Operation
Center A437
Comp.
Programmer
Off.
A439
Computer
Off.
A440
A441
Res. Off.
A442
Stair 1 S*4*1
IRM
Storage
(Hdwr) A444
Elec.
A445
Toilet A446
Toilet A446A
IRM
Storage
(Comm) A445A
Infusion A449
Tlt.
A449A
Stair 5 S*4*5
Sub. Lab.
A453 Pharm.
A454
Exam A455
Elec.
A456
Stor.
A457A
S.B.
A457B
Tlt.
A457C
D.B.
A457D
Proc.
A457E
Nurse
Station A457F
Lab.
A457G
Exam A458
Exam A458A
Exam A458B
Exam A458C
Elec.
A459
Stor.
A460
Soil. Util.
A461
CL. Lin.
A462
Exam A463
Exam 2 A464
Exam 4 A465
Exam 6 A466
Exam 8 A467
Exam 10 A468
Exam 9 A469
Exam 7 A470
Exam 5 A471
Exam 3 A472
Exam 1 A473
Exam A474
KIT.
A475
Supp.
A476
HAC
A477
Waiting A478
GCRC
Corridor A457
Tlt.
A457H
Tlt.
A474A
Waiting A402B
Trash
Chute A435
Stor.
A436A
Elec.
A436B
Comp. Rm.
A437C
Stor.
A444A
Tlt.
A464A
Tlt.
A473A
Tlt.
A465A
Tlt.
A471A
Tlt.
A467A
Tlt.
A470A
Corridor C*4*2
HSRD
Off.
A424E
HSRD
Off.
A424D
Common
Area A424C
Dir.
Off.
A424B
Dr's
Off.
A423A
Social
Worker A422A
Tlt.
A406A
HSRD
Off.
A424F
HSRD
Off.
A424G
A442A
Corridor C*4*1
Elec.
A424H
Tlt.
A416A
Tlt.
A414A
Tlt.
A413A
Tlt.
A410A
Tlt.
A408A
Tlt.
A407A
Tlt.
A463A
Tlt.
A439A
Staff
Physician B403A
Neuro
Office B439
Regular
E.E.G B403B
E.E.G.
Control &
Observation B403
F. Tlt.
B406
M. Tlt.
B407
Auto-Clave
Dishwasher B408
HAC
B409
Elec.
B410
LAB.
Procedure
Rm B411
W. Lab.
B412
Ram Lab.
B412A
Tissue
Culture B412B
Office B412C
Stair 4 S*4*4
Electrophoresis
Core B413A
RAM Lab.
B413B
Corridor C*4*5
Infectious
Disease
Lab B414
Hazardous
Compounding B414B
Non-Hazardous
Compounding B414D Office
B415
Cold Rm.
B415A
Freez.
B415B
Sig. Clos.
B416
Elec.
B417
Stair 3 S*4*3
Research
Adm. Off.
B420
Adm. Off.
B420B
CFBRE Off.
B421
Conf.
B425
Clos.
B425A
Office B426A
Associate
Chief of
Staff/Research B426
Office B427
Office B428
HAC
B429
Refrig.
B430
Elec.
B431
Lab B432
Tissue
Culture B433A
Mic Rotomy B435
Microscope
Core B436
Office B437
Evoked
Potential
Lab B438
Copier
Room B437A
Corridor B429A
Director's
Office B429B
Mech
Room A456E
Hazardous
Storage B414A
Work
Station
Area B414
Ante Room B414C
Telecom Room
DN
UP DNUP
DN
UP
DN
UP
UP
DN
IRMStor.
Elec.
A436B
Comp. Rm.
A437C
Stor.
A444A
Corridor C*4*1
P-150-C.1.4
WS-1
WS-1
WS-1 WS-1
WS-1 WS-1
12' CABLE WITH WATER
SENSORS (TYP.)
WATER SENSOR (WS-1)
(TYP. 6 LOCATIONS) P.C.
TO PROVIDE AND THE
MECHANICAL CONTROLS
CONTRACTOR TO
CONNECT TO BAS.
INSTALLED BELOW
RAISED FLOOR.
CONNECT 1/2"
CW TO WATER
SUPPLY OF EWC
IN CORRIDOR.
ETP-1
SHUT OFF VALVE
1/2" CW-DN
PROVIDE AND INSTALL A 3"FD-1
FLOOR DRAIN WITH DEEP SEAL
TRAP AND P-TRAP WITH TRAP
PRIMER CONNECTION
DRAIN FROM FLOOR DRAIN TO
TERMINATE INDIRECTLY 1"
ABOVE THE RIM OF THE MOP
BASIN ON THE 3RD FLOOR
DIRECTLY BELOW.
A W
PROVIDE DRIP
PAN WITH
WATER SENSOR
(WS-1)
3" ACID WASTE
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project TitlePhaseDrawing Title
Approved: Project Director
ARCHITECT/ENGINEER OF RECORDCONSULTANT
Revisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784
San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
FULLY SPRINKLED
6 SOUTH OLD ORCHARD
WEBSTER GROVES, MO. 63119
T: 314.918.8383 F: 314.918.17664
/2 /2
:0 :5
A
M
P-150-C.1.4
PLUMBING FOURTH FLOOR OVERALL
& ENLARGED PLANS
04-MAY-2022
DDPJDB
CINCINNATI VAMC EHRM
INFASTRUCTURE UPGRADES
539-21-701
3200 VINE ST. CINCINNATI, OH.
100% CONSTRUCTION
DOCUMENTS
1/16" = 1'-0"
PLUMBING - BUILDING #1 - OVERALL
FOURTH FLOOR PLAN
1/4" = 1'-0"
COMPUTER ROOM A 437C - FOURTH FLOOR
NEW WORK PLAN - PLUMBING
PLUMBING MATERIAL SPECIFICATIONS
1. FLOOR DRAIN (FD-1) SHALL BE J.R. SMITH 2005-NB-P050 OR EQUAL.
2. WATER SENSOR (WS-1) SHALL BE A WATER ALERT DETECTOR XSS-5 WITH TWO SC-12 SENSOR CABLES AND WITH POWER
OPTION "VOLTAGE MODULE" AS MANUFACTURED BY DORLEN PRODUCTS IN. OR EQUAL.
3. ELECTRONIC TRAP PRIMER (ETP-1) SHALL BE PPP INC. ELECTRONIC TRAP PRIMER MODEL 695-ES01 OR EQUAL.
4. COLD WATER PIPING SHALL BE 1/2" TYPE "L" HARD DRAWN COPPER PIPE WITH SOLDERED FITTING. SOLDER SHALL BE LEAD-FREE LEAD FREE WATER SOLUBLE PASTE FLUX SHALL BE USED FORR JOINING FITTINGS AND COUPLINGS.
5. COLD WATER PIPING SHALL BE INSULATED WITH 1/2: THICK 25/50 ARMAFLEX OR EQUAL.
6. SHUT OFF VALVES SHALL BE APOLLO 77CLF LEAD FREE BRONZE BALL VALVE OR EQUAL.
7. WASTE PIPING SHALL BE SERVICE WEIGHT CAST IRON PIPE WITH HEAVY DUTY NO-HUB COUPLINGS.
/2
8/
| FP-203-C.1 .B THRU 3 - FIRE PROTECTION ENLARGED PLANS |
| FP-204-C.1.4 THRU 9 - FIRE PROTECTION ENLARGED PLANS |
| FP-205-C.1.4 - FIRE PROTECTION FOURTH FLOOR CLEAN AGENT PLAN |