ATTACHMENT 11 - Drawings 10 of 13.pdf

PDF 12 MB Posted

Attached to
36C77623B0005 EHRM Infrastructure Upgrades - Cincinnati Project #539-21-701
Solicitation number
36C77623B0005
Issued by

About this file

This document provides details on a federal solicitation opportunity for construction services. The solicitation number is 36C77623B0005 for the EHRM Infrastructure Upgrades - Cincinnati Project #539-21-701, issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The opportunity involves construction of EHRM Infrastructure Upgrades at the Cincinnati VAMC, requiring installation and upgrade of related systems. The attached file is a drawing related to the project scope. The response deadline and award date are not specified.

View the file

Other files

File Type Posted
36C77623B0005 0004 - Extension 3-10-23.pdf PDF
Technical Questions and Answers - Cincinnati EHRM.pdf PDF
36C77623B0005 0003.pdf PDF
36C77623B0005 0002 - EHRM Infrastructure Upgrades - Cincinnati.pdf PDF
Site Visit Sign-In Sheet - 36C77632B0005 EHRM Infrastructure Construction - Cincinnati VAMC.pdf PDF
ATTACHMENT 24 - Construction Wage Rates - Hamilton 01-13-2023.pdf PDF
36C77623B0005 0001 - EHRM Infrastructure Upgrades - Cincinnati.pdf PDF
Site Visit Memorandum.pdf PDF
ATTACHMENT 4 - Drawings 3 of 13.pdf PDF
ATTACHMENT 23 - Contractor Safety - Environmental Form.pdf PDF
ATTACHMENT 6 - Drawings 5 of 13.pdf PDF
ATTACHMENT 18 - Technology Narrative.pdf PDF
ATTACHMENT 13 - Drawings 12 of 13.pdf PDF
ATTACHMENT 15 - Plumbing Narrative.pdf PDF
ATTACHMENT 19 - Hazardous Materials Inspection Report.pdf PDF
ATTACHMENT 24 - Construction Wage Rates - Hamilton 1-13-2022.pdf PDF
ATTACHMENT 21 - COVID-19 Safety Protocols 12-14-21.pdf PDF
ATTACHMENT 14 - Drawings 13 of 13.pdf PDF
ATTACHMENT 20 - Brand Name Justification.pdf PDF
ATTACHMENT 22 - Limitations on Subcontracting - Nov 2022.pdf PDF
ATTACHMENT 9 - Drawings 8 of 13.pdf PDF
ATTACHMENT 10 - Drawings 9 of 13.pdf PDF
ATTACHMENT 16 - Mechanical Narrative.pdf PDF
ATTACHMENT 7 - Drawings 6 of 13.pdf PDF
ATTACHMENT 3 - Drawings 2 of 13.pdf PDF
ATTACHMENT 17 - Electrical Narrative.pdf PDF
ATTACHMENT 2 - Drawings 1 of 13.pdf PDF
ATTACHMENT 25 - Site Visit Instructions.pdf PDF
ATTACHMENT 8 - Drawings 7 of 13.pdf PDF
ATTACHMENT 12 - Drawings 11 of 13.pdf PDF
ATTACHMENT 5 - Drawings 4 of 13.pdf PDF
36C77623B0005 Solicitation - Cincinnati EHRM.pdf PDF
ATTACHMENT 1 - Specifications.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A/C Shaft

IRM

Network

Operation

Center A437

Comp.

Programmer

Off.

A439

Computer

Tlt.

A439A

Staff

Physician B403A

Neuro

Office B439

Regular

E.E.G B403B

E.E.G.

Control &

Observation B403

F. Tlt.

B406

M. Tlt.

B407

Auto-Clave

Dishwasher B408

HAC

B409

Elec.

B410

LAB.

Procedure

Rm B411

W. Lab.

B412

Ram Lab.

B412A

Tissue

Culture B412B

Office B412C

Stair 4 S*4*4

Electrophoresis

Core B413A

RAM Lab.

B413B

Corridor C*4*5

Infectious

Disease

Lab B414

Hazardous

Compounding B414B

Non-Hazardous

Compounding B414D Office

B415

Cold Rm.

B415A

Freez.

B415B

Sig. Clos.

B416

Elec.

B417

Stair 3 S*4*3

Research

Adm. Off.

B420

Adm. Off.

B420B

CFBRE Off.

B421

Conf.

B425

Clos.

B425A

Office B426A

Associate

Chief of

Staff/Research B426

Office B427

Office B428

HAC

B429

Refrig.

B430

Elec.

B431

Lab B432

Tissue

Culture B433A

Mic Rotomy B435

Microscope

Core B436

Office B437

Evoked

Potential

Lab B438

Copier

Room B437A

Corridor B429A

Director's

Office B429B

Hazardous

Storage B414A

Work

Station

Area B414

Ante Room B414C

DN

DN

UP

UP

2 2

2 2 2

2 2

2 2

2 2

2 2

2 22

TN-421-C.1.4

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

1/8" = 1'-0"

TN-151-C.1.4

TECHNOLOGY FOURTH FLOOR

PARTIAL PLAN - A

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

04-MAY-2022

PR

C1

1/8" = 1'-0"

TECHNOLOGY FOURTH FLOOR PARTIAL PLAN - A

D

B

A

GENERAL NOTES:

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED. DATA SHOWN IN

ROOM IS AN ESTIMATE OF WHAT WILL BE REQUIRED.

TRUE NORTH PLAN NORTH

Description Date

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. ALL HORIZONTAL CABLING ON THIS FLOOR TO BE TERMINATED IN

TR-4.

3. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

4. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

5. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

6. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE

TRAY PLUS 50%.

7. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

8. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

9. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS IN

THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

11. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING REMOVED

FROM ANY WALL MOUNT EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE CONTRACTOR DURING

COMMISSIONING.

12. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

13. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

14. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES WITH

NEW CATEGORY MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW MODULAR JACKS

SHALL BE OF THE SAME MANUFACTURER AS THE FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

15. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

16. CONTRACTOR SHALL TEST ALL NEW AND EXISTING RE-TERMINATED

CABLES IN ACCORDANCE WITH THE SPECIFICATION 27 08 00.

A/C ShaftA/C Shaft

Reception A400

Interview A401

Interview A401A

Reception A401BInterview

A402A

HAC

A403

Stor.

A404

Med Room A405

Exam Rm.

A406

Exam Rm.

A407

Exam Rm.

A408

Exam Rm.

A409

Exam Rm.

A410

Exam Rm.

A411

Exam Rm.

A412

Exam Rm.

A413

Exam Rm.

A414

Exam Rm.

A415

Exam Rm.

A416

Exam Rm.

A417

Stor.

A418

Elec.

A418A

Stor.

A420

Staff Tlt.

A421

HSRD

Office A422

Dr's

Off.

A423

HSRD

Off.

A424

Oncology

Pharmacy

Sattelite A425

Chemo

Prep.

A425A

IRM Office A427

Stair 2 S*4*2

HSRD

Off.

A424A

Comp.

Training A430

Comp.

Specialist

Off.

A431

Service

Lobby A436

Computer

Off.

A440

A441

Res. Off.

A442

Stair 1 S*4*1

IRM

Storage

(Hdwr) A444

Elec.

A445

Toilet A446

Toilet A446A

IRM

Storage

(Comm) A445A

Infusion A449

Tlt.

A449A

Exam 9 A469

Exam 7 A470

Exam 5 A471

Exam 3 A472

Exam 1 A473

Exam A474

HAC

A477

Waiting A478

Waiting A402B

Trash

Chute A435

Stor.

A436A

Elec.

A436B

Comp. Rm.

A437C

Stor.

A444A

Corridor C*4*2

HSRD

Off.

A424E

HSRD

Off.

A424D

Common

Area A424C

Dir.

Off.

A424B

Dr's

Off.

A423A

Social

Worker A422A

Tlt.

A406A

HSRD

Off.

A424F

HSRD

Off.

A424G

A442A

Corridor C*4*1

Elec.

A424H

Tlt.

A416A

Tlt.

A414A

Tlt.

A413A

Tlt.

A410A

Tlt.

A408A

Tlt.

A407A

Telecom Room

UP

DN

UP

DN

TN-420-C.1.4

2 2

2 2

2 2

TR-4

SR-4

TN-421-C.1.4

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

1/8" = 1'-0"

TN-152-C.1.4

TECHNOLOGY FOURTH FLOOR

PARTIAL PLAN - B

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

04-MAY-2022

PR

C1

1/8" = 1'-0"

TECHNOLOGY FOURTH FLOOR PARTIAL PLAN - B

D B

A

GENERAL NOTES:

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED. DATA SHOWN IN

ROOM IS AN ESTIMATE OF WHAT WILL BE REQUIRED.

3. PROVIDE (4) 4" CONDUITS TO TR ON LEVEL ABOVE.

TRUE NORTH PLAN NORTH

Description Date

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. ALL HORIZONTAL CABLING ON THIS FLOOR TO BE TERMINATED IN

TR-4.

3. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

4. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

5. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

6. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE

TRAY PLUS 50%.

7. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

8. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

9. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS IN

THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

11. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING REMOVED

FROM ANY WALL MOUNT EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE CONTRACTOR DURING

COMMISSIONING.

12. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

13. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

14. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES WITH

NEW CATEGORY MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW MODULAR JACKS

SHALL BE OF THE SAME MANUFACTURER AS THE FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

15. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

Infusion A449

Stair 5 S*4*5

Sub. Lab.

A453 Pharm.

A454

Exam A455

Elec.

A456

Stor.

A457A

S.B.

A457B

Tlt.

A457C

D.B.

A457D

Proc.

A457E

Nurse

Station A457F

Lab.

A457G

Exam A458

Exam A458A

Exam A458B

Exam A458C

Elec.

A459

Stor.

A460

Soil. Util.

A461

CL. Lin.

A462

Exam A463

Exam 2 A464

Exam 4 A465

Exam 6 A466

Exam 8 A467

Exam 10 A468

Exam 9 A469

Exam 7 A470

Exam 5 A471

Exam 3 A472

Exam 1 A473

Exam A474

KIT.

A475

Supp.

A476

HAC

A477

GCRC

Corridor A457

Tlt.

A457H

Tlt.

A474A

Tlt.

A464A

Tlt.

A473A

Tlt.

A465A

Tlt.

A471A

Tlt.

A467A

Tlt.

A470A

Tlt.

A463A

DNUP

222 2

2 2

2 2

2 2

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

1/8" = 1'-0"

TN-153-C.1.4

TECHNOLOGY FOURTH FLOOR

PARTIAL PLAN - D

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

04-MAY-2022

PR

C1

1/8" = 1'-0"

TECHNOLOGY FOURTH FLOOR PARTIAL PLAN - D

D B

A

GENERAL NOTES:

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED. DATA SHOWN IN

ROOM IS AN ESTIMATE OF WHAT WILL BE REQUIRED.

TRUE NORTH PLAN NORTH

Description Date

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. ALL HORIZONTAL CABLING ON THIS FLOOR TO BE TERMINATED IN

TR-4.

3. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

4. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

5. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

6. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE

TRAY PLUS 50%.

7. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

8. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

9. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS IN

THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

11. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING REMOVED

FROM ANY WALL MOUNT EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE CONTRACTOR DURING

COMMISSIONING.

12. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

13. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

14. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES WITH

NEW CATEGORY MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW MODULAR JACKS

SHALL BE OF THE SAME MANUFACTURER AS THE FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

15. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

Telecom Room

A540

Elec.

A537A

Work Room A537F

Exam

Room 5 A555

Clos.

A556

Exam

Room 4 A557A

Surgery

Office A557B

Procedure

Room A557C

Procedure

Room A557D

Exam A558

Waiting

Area A559

Clerk A559A

Class Rm.

A564

Exam 7 A566

Exam 6 A567

Exam 5 A568

Elec.

A560

Tele A561

Soil A562

HAC

A562A

Stor.

A563A

Pain Nurse A563

Stor.

A564A

Stor.

A565A

Supp Clos A567A

Corridor C*5*4

Telesurgery

Office A554

Tlt.

A553

Skin and

Wound

Care Clinic A551

Closet A551A

Stor.

A551B

Stair 5 S*5*5

Medical

Service

Office B537

Medical

Service B538

Office B539

Chief Office B540

Adm Asst.

A541

Chief Med.

Svc.

A542

Dirty

Equipment A537B

Db. Wtr.

A539

Storage A537E

Clean

Supply A537D

Oxygen

Storage

Equipment

Room A537C

Office B537A

Med Svc B501

Office B503

Office B504

Conferece

Room B523

Cleric B524

Rolling

Storage B525

IV

Ante-Room B526

IV Prep B526A

IV Buff B526B

Closet B526C

Tlt.

B503A

Storage B506

Conference

Rm.

B507

Office B508

Office B509

Office B510

Office B511

Office B512

Office B513

Office B514

Office B515

Office B516

Office B517

Storage B515A

Closet B507A

Dispensing

Area B536

Office B535C

Stair 3 S*5*3

Storage B505H

Sig. Clos.

B505G

Office B518

Corridor C*5*5

Office B505

Tlt.

B505A

Elec.

B505B

HAC

B521E

Stor.

B518A

Staff Tlt.

B535B

Stor.

B521D

Elec.

B521B

Cart Stor.

B535

Narc. Vault B521A Chief

B522

Compound

Picking B527Unit Dose

B535A

Corridor C*5*1

Closet A554A

MICU

Penthouse B505D

Fan Room B505E

Stair 4 S*5*4

DNUP

DN

UP

DN

N

S.R.

A519

S.R.

A522

Soil. Util.

A515

Nurse Manager

A528

S.R

A512

S.R.

A511

Clean Supply

A5093

Storage

A5087

Storage

A5100

Nourishment

A508

Single Room

A504

Clean Linen

A5083

Staff Toilet

A5085

Nurse Station

A506

Single Room

- Bariatric

A5097

Single Room

- Bariatric

A5098

Single Room

- Bariatric

A5099

Single Room

- Bariatric

A5086

Single Room

- Negative Pressure

A5088Single Room

- Negative Pressure

A5089

Single Room

A5090Single Room

- Negative Pressure

A5091 Single Room

- Bariatric Negative Pressure

A5092

Signals

A5094

Elec.

A5095

HAC

A5084

Family Lounge

A578HUC

A581 Consult

A580

Staff Lounge

A510

Telem.

A509

Elec.

A514

Office

A582

Meds

A505

Physical Therapy

A579

Staff Tlt

A513

D.R.

A501

D.R.

A502

Elec.

A516

D.R.

A517D.R.

A518

D.R.

A520

D.R.

A521

D.R.

A523

Storage

A525

S.R.

A526

S.R.

A527

Bath

A511A

Bath

A512A

Bath

A521A

Bath

A520A

Bath

A522A

Bath

A519A

Corridor

C-5-1

Bath

A523A

Bath

A518A

Bath

A517A

Bath

A526A

Bath

A502A

Bath

A501A

Bath

A527A

Corridor

C-5-2

Storage

A549

Corridor

C-5-1

Corridor

C-5-1

Toilet

A5097A

Toilet

A5098A Toilet

A5099A Toilet

A5086A

Toilet

A5088A Toilet

A5089A

Toilet

A5090A

Toilet

A5091A

Toilet

A5092A

Areaway

A-1

Areaway

A-2

Corridor

C-5-4

Anteroom

A5092B

Anteroom

A5091B

Corridor

C-5-1

Clean Linen

A524

Pgm. Supp.

Asst.

A575

Tlt.

A577

Waiting Area

A550

Office

A574

Staff Physician

A573

Exam 1

A572

Exam 2

A571

Exam 3

A570

Exam 4

A569

Stair #11

A5096

Clean Supply

A503

Bath

A504B

A L

IG

N

UPUP

(2) SS04

(2) SS04

(2) SS04

(2) SS04

TR-5

(4) SS04

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

1/16" = 1'-0"

TN-160-C.1.5

TECHNOLOGY FIFTH FLOOR OVERALL

PLAN

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

04-MAY-2022

PR

C1

1/16" = 1'-0"

TECHNOLOGY FIFTH FLOOR OVERALL PLAN

GENERAL NOTES:

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. PROVIDE (4) 4" CONDUITS TO TR ON LEVEL BELOW.

3. PROVIDE (4) 4" CONDUITS TO TR ON LEVEL ABOVE.

4. 12 INCH X 4 INCH WIRE MESH CABLE TRAY

D B

A

TRUE NORTH PLAN NORTH

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. ALL HORIZONTAL CABLING ON THIS FLOOR TO BE TERMINATED IN

TR-5.

3. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

4. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

5. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

6. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE

TRAY PLUS 50%.

7. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

8. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

9. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS IN

THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

11. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING REMOVED

FROM ANY WALL MOUNT EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE CONTRACTOR DURING

COMMISSIONING.

12. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

13. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

14. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES WITH

NEW CATEGORY MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW MODULAR JACKS

SHALL BE OF THE SAME MANUFACTURER AS THE FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

15. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

16. CONTRACTOR SHALL TEST ALL NEW AND EXISTING RE-TERMINATED

CABLES IN ACCORDANCE WITH THE SPECIFICATION 27 08 00.

Description Date

ADDENDUM 1 4/29/2022

Medical

Service

Office B537

Medical

Service B538

Office B539

Chief Office

Dirty

Equipment A537B

Db. Wtr.

A539

Oxygen

Storage

Equipment

Room A537C

Office B537A

Med Svc B501

Office B503

Office B504

Conferece

Room B523

Cleric B524

Rolling

Storage B525

IV

Ante-Room B526

IV Prep B526A

IV Buff B526B

Closet B526C

Tlt.

B503A

Storage B506

Conference

Rm.

B507

Office B508

Office B509

Office B510

Office B511

Office B512

Office B513

Office B514

Office B515

Office B516

Office B517

Storage B515A

Closet B507A

Dispensing

Area B536

Office B535C

Stair 3 S*5*3

Storage B505H

Sig. Clos.

B505G

Office B518

Corridor C*5*5

Office B505

Tlt.

B505A

Elec.

B505B

HAC

B521E

Stor.

B518A

Staff Tlt.

B535B

Stor.

B521D

Elec.

B521B

Cart Stor.

B535

Narc. Vault B521A Chief

B522

Compound

Picking B527Unit Dose

B535A

MICU

Penthouse B505D

Fan Room B505E

Stair 4 S*5*4

DN

UP

DN

1 2

2 2

2 2

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

1/8" = 1'-0"

TN-161-C.1.5

TECHNOLOGY FIFTH FLOOR PARTIAL

PLAN - A

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

04-MAY-2022

PR

C1

1/8" = 1'-0"

TECHNOLOGY FIFTH FLOOR PARTIAL PLAN - A

D B

A

GENERAL NOTES:

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED. DATA SHOWN IN

ROOM IS AN ESTIMATE OF WHAT WILL BE REQUIRED.

TRUE NORTH PLAN NORTH

Description Date

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. ALL HORIZONTAL CABLING ON THIS FLOOR TO BE TERMINATED IN

TR-5.

3. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

4. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

5. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

6. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE

TRAY PLUS 50%.

7. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

8. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

9. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS IN

THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

11. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING REMOVED

FROM ANY WALL MOUNT EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE CONTRACTOR DURING

COMMISSIONING.

12. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

13. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

14. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES WITH

NEW CATEGORY MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW MODULAR JACKS

SHALL BE OF THE SAME MANUFACTURER AS THE FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

15. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

Room

A540

Elec.

A537A

Work Room A537F

Chief Office B540

Adm Asst.

A541

Chief Med.

Svc.

A542

Storage A537E

Clean

Supply A537D

Corridor C*5*1

N

S.R.

A519

S.R.

A522

Soil. Util.

A515

Nurse Manager

A528

S.R

A512

S.R.

A511

Clean Supply

A5093

Storage

A5087

Storage

A5100

Nourishment

A508

Single Room

A504

Clean Linen

A5083

Staff Toilet

A5085

Nurse Station

A506

Single Room

- Bariatric

A5097

Single Room

- Bariatric

A5098

Single Room

- Bariatric

A5099

Single Room

- Bariatric

A5086

Single Room

- Negative Pressure

A5088Single Room

- Negative Pressure

A5089

Single Room

A5090Single Room

- Negative Pressure

A5091 Single Room

- Bariatric Negative Pressure

A5092

Signals

A5094

Elec.

A5095

HAC

A5084

Family Lounge

A578HUC

A581 Consult

A580

Staff Lounge

A510

Telem.

A509

Elec.

A514

Office

A582

Meds

A505

Physical Therapy

A579

Staff Tlt

A513

D.R.

A501

D.R.

A502

Elec.

A516

D.R.

A517D.R.

A518

D.R.

A520

D.R.

A521

D.R.

A523

Storage

A525

S.R.

A526

S.R.

A527

Bath

A511A

Bath

A512A

Bath

A521A

Bath

A520A

Bath

A522A

Bath

A519A

Corridor

C-5-1

Bath

A523A

Bath

A518A

Bath

A517A

Bath

A526A

Bath

A502A

Bath

A501A

Bath

A527A

Corridor

C-5-2

Storage

A549

Corridor

C-5-1

Corridor

C-5-1

Toilet

A5097A

Toilet

A5098A Toilet

A5099A Toilet

A5086A

Toilet

A5088A Toilet

A5089A

Toilet

A5090A

Toilet

A5091A

Toilet

A5092A

Areaway

A-1

Areaway

A-2

Corridor

C-5-4

Anteroom

A5092B

Anteroom

A5091B

Corridor

C-5-1

Clean Linen

A524

Pgm. Supp.

Tlt.

A577

Physician

Exam 1

A572

Exam 2

A571

Exam 3

Exam 4

Stair #11

A5096

Clean Supply

A503

Bath

A504B

A L

IG

N

ALIGN

UPUP

2 2 2

1 1

1 1

1 1

TN-425-C.1.5

TR-5

2 2

2 2

2 2 2

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

1/8" = 1'-0"

TN-162-C.1.5

TECHNOLOGY FIFTH FLOOR PARTIAL

PLAN - B

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

04-MAY-2022

PR

C1

1/8" = 1'-0"

TECHNOLOGY FIFTH FLOOR PARTIAL PLAN - B

D B

A

GENERAL NOTES:

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED. DATA SHOWN IN

ROOM IS AN ESTIMATE OF WHAT WILL BE REQUIRED.

3. PROVIDE (4) 4" CONDUITS TO TR ON LEVEL BELOW.

4. PROVIDE (4) 4" CONDUITS TO TR ON LEVEL ABOVE.

TRUE NORTH PLAN NORTH

Description Date

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. ALL HORIZONTAL CABLING ON THIS FLOOR TO BE TERMINATED IN

TR-5.

3. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

4. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

5. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

6. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE

TRAY PLUS 50%.

7. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

8. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

9. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS IN

THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

11. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING REMOVED

FROM ANY WALL MOUNT EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE CONTRACTOR DURING

COMMISSIONING.

12. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

13. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

14. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES WITH

NEW CATEGORY MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW MODULAR JACKS

SHALL BE OF THE SAME MANUFACTURER AS THE FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

15. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

Exam

Room 5 A555

Clos.

A556

Exam

Room 4 A557A

Surgery

Office A557B

Procedure

Room A557C

Procedure

Room A557D

Exam A558

Waiting

Area A559

Clerk A559A

Class Rm.

A564

Exam 7 A566

Exam 6 A567

Exam 5 A568

Elec.

A560

Tele A561

Soil A562

HAC

A562A

Stor.

A563A

Pain Nurse A563

Stor.

A564A

Stor.

A565A

Supp Clos A567A

Corridor C*5*4

Telesurgery

Office A554

Tlt.

A553

Skin and

Wound

Care Clinic A551

Closet A551A

Stor.

A551B

Stair 5 S*5*5

Closet A554A

DNUP

Pgm. Supp.

Asst.

A575

Tlt.

A577

Waiting Area

A550

Office

A574

Staff Physician

A573

Exam 1

A572

Exam 2

A571

Exam 3

A570

Exam 4

A569

2 2

2 2

2 2

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

1/8" = 1'-0"

TN-163-C.1.5

TECHNOLOGY FIFTH FLOOR PARTIAL

PLAN - D

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

04-MAY-2022

PR

C1

1/8" = 1'-0"

TECHNOLOGY FIFTH FLOOR PARTIAL PLAN - D

D B

A

GENERAL NOTES:

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED. DATA SHOWN IN

ROOM IS AN ESTIMATE OF WHAT WILL BE REQUIRED.

TRUE NORTH PLAN NORTH

Description Date

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. ALL HORIZONTAL CABLING ON THIS FLOOR TO BE TERMINATED IN

TR-5.

3. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

4. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

5. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

6. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE

TRAY PLUS 50%.

7. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

8. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

9. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS IN

THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

11. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING REMOVED

FROM ANY WALL MOUNT EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE CONTRACTOR DURING

COMMISSIONING.

12. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

13. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

14. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES WITH

NEW CATEGORY MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW MODULAR JACKS

SHALL BE OF THE SAME MANUFACTURER AS THE FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

15. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

Room

Nurse

Station A600A603A604

A605

HAC

A606

A607

A608

A609

D.R.

A611

S.R.

A612

S.R. (Neg.

Pres.)

A614

Elec.

A615

Soiled

Utility A616

Elec.

A617

CL. Lin.

A618

D.R.

A619

S.R.

A620

S.R. (Neg.

Pres.)

A621

D.R.

A622

D.R.

A623

S.R. (Neg.

Pres.)

A624

CL. Supp.

A625

D.R.

A626

Stair 2 S*6*2

Storage A628

D.R.

A629

Nourish.

A630

D.R.

A631

Service

Lobby A632

Elec.

A632E

Medical

Conf.

A634B

Tlt.

A635

Phys.

Work Rm.

A632D

LKRS.

A637B

HAC

A637A

DB. Wtr.

A639

Research

Pulmonary

Lab.

A640

HHN Off.

A641

Chief

Medical

Res.

A642

A643

Stair 1 S*6*1

Elec.

A645

Equip. Stor.

A646

D.R.

A647

A648

D.R.

A649

Stair 5 S*6*5

A651

A652

A654 A655

A656 A657A658

A659

Elec.

A660

Elec.

A661

Soil. Util.

A662

A663

A663A

A664

A668 A669

A671A

A671

A672

CL. Lin.

A673

HAC

A674

A675A676

Tlt.

A604A

Tlt.

A607A

Tlt.

A611A

Tlt.

A612A

Tlt.

A614A

Tlt.

A619A

Tlt.

A621A

Tlt.

A620A

Tlt.

A622A

Tlt.

A623A

Tlt.

A626ATlt.

A624A

Tlt.

A629A

Tlt.

A631A

Trash

Chute A637

Medical

Conf.

A634C

Meeting

Room A634A

Sig. Clos.

A645A

Tlt.

A647A

Tlt.

A649A

Tlt.

A651A

Tlt.

A654A

Tlt.

A655A

Tlt.

A656A

Toilet A659A

Tlt.

A664A

A667A

A670

Tlt.

A675A

Tlt.

A672A

Corridor C*6*1

Off.

B601

Elec.

B619B

Soiled B619A

Echo.

B604

Storage B605

IV Tech.

Off.

B606

Conf. Rm.

B607

Stair 3 S*6*3

Exam B609

Exam B610

Office B611A

Exam B612A

Exam B612B

Exam B612C

Exam B612D

Toilet B613

Exam B614

Toilet B615

Exam B616

Exam B617

Secretary B618

Elec.

B607A

Sig. Clos.

B606A

Tlt.

B605A

Tlt.

B603

Adm. Asst.

B620

Social

Work Off.

B621

Phys.

B622

Conf.

Room B623

Chief

Admn.

Asst.

B624

Chief Phys.

B625

Phys.

B626

Phys.

B627

Phys.

B628

Phys.

B629

Clos.

B625A

Corridor C*6*5

Stor.

B632

Stor.

B633

Ward Stor.

B635

Pulmonary

Func. LAB B636

HAC

B634

Tlt.

B620A

Corridor C*6*2

Exam B611B

Closet B609A

Storage A646A

A/C Shaft A/C Shaft

A6002A

A6002

A6003AA6003A6004A

A6005

A6005A

A6006

A6006B

A6014A

A6013

A6013AA6012A

A6012

A6009

A6010

A6007B

A6007

A6007A

A6006A

A6004

A6000

A6008

C-6-6

A6001

C-6-6A

AREAWAYAREAWAY

A6011

A667

Tlt.

A666

C-6-3A

A658A

A657A

C-6-3A

A613

C-6-2A Tlt.

A608A

A602 A601

DN UP DNUP

DN UP

DN

UP

A643

(4) SS04

(4) SS04

(2) SS04 (2) SS04

(2) SS04

TR-6

4 4

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

1/16" = 1'-0"

TN-170-C.1.6

TECHNOLOGY SIXTH FLOOR OVERALL

PLAN

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

04-MAY-2022

PR

C1

1/16" = 1'-0"

TECHNOLOGY SIXTH FLOOR OVERALL PLAN

GENERAL NOTES:

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. PROVIDE (4) 4" CONDUITS TO TR ON LEVEL BELOW.

3. PROVIDE (4) 4" CONDUITS TO TR ON LEVEL ABOVE.

4. 12 INCH X 4 INCH WIRE MESH CABLE TRAY

D B

A

TRUE NORTH PLAN NORTH

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. ALL HORIZONTAL CABLING ON THIS FLOOR TO BE TERMINATED IN

TR-6.

3. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

4. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

5. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

6. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE

TRAY PLUS 50%.

7. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

8. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

9. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS IN

THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

11. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING REMOVED

FROM ANY WALL MOUNT EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE CONTRACTOR DURING

COMMISSIONING.

12. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

13. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

14. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES WITH

NEW CATEGORY MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW MODULAR JACKS

SHALL BE OF THE SAME MANUFACTURER AS THE FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

15. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

16. CONTRACTOR SHALL TEST ALL NEW AND EXISTING RE-TERMINATED

Tlt.

A635

DB. Wtr.

A639

Research

Pulmonary

Lab.

A640

Medical

Conf.

A634C

Off.

B601

Elec.

B619B

Soiled B619A

Echo.

B604

Storage B605

IV Tech.

Off.

B606

Conf. Rm.

B607

Stair 3 S*6*3

Exam B609

Exam B610

Office B611A

Exam B612A

Exam B612B

Exam B612C

Exam B612D

Toilet B613

Exam B614

Toilet B615

Exam B616

Exam B617

Secretary B618

Elec.

B607A

Sig. Clos.

B606A

Tlt.

B605A

Tlt.

B603

Adm. Asst.

B620

Social

Work Off.

B621

Phys.

B622

Conf.

Room B623

Chief

Admn.

Asst.

B624

Chief Phys.

B625

Phys.

B626

Phys.

B627

Phys.

B628

Phys.

B629

Clos.

B625A

Corridor C*6*5

Stor.

B632

Stor.

B633

Ward Stor.

B635

Pulmonary

Func. LAB B636

HAC

B634

Tlt.

B620A

Exam B611B

Closet B609A

DN

UP

2 22

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

1/8" = 1'-0"

TN-171-C.1.6

TECHNOLOGY SIXTH FLOOR PARTIAL

PLAN - A

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

04-MAY-2022

PR

C1

1/8" = 1'-0"

TECHNOLOGY SIXTH FLOOR PARTIAL PLAN - A

D B

A

GENERAL NOTES:

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED. DATA SHOWN IN

ROOM IS AN ESTIMATE OF WHAT WILL BE REQUIRED.

TRUE NORTH PLAN NORTH

Description Date

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. ALL HORIZONTAL CABLING ON THIS FLOOR TO BE TERMINATED IN

TR-6.

3. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

4. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

5. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

6. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE

TRAY PLUS 50%.

7. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

8. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

9. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS IN

THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

11. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING REMOVED

FROM ANY WALL MOUNT EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE CONTRACTOR DURING

COMMISSIONING.

12. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

13. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

14. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES WITH

NEW CATEGORY MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW MODULAR JACKS

SHALL BE OF THE SAME MANUFACTURER AS THE FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

15. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

Room

Nurse

Station A600A603A604

A605

HAC

A606

A607

A608

A609

D.R.

A611

S.R.

A612

S.R. (Neg.

Pres.)

A614

Elec.

A615

Soiled

Utility A616

Elec.

A617

CL. Lin.

A618

D.R.

A619

S.R.

A620

S.R. (Neg.

Pres.)

A621

D.R.

A622

D.R.

A623

S.R. (Neg.

Pres.)

A624

CL. Supp.

A625

D.R.

A626

Stair 2 S*6*2

Storage A628

D.R.

A629

Nourish.

A630

D.R.

A631

Service

Lobby A632

Elec.

A632E

Medical

Conf.

A634B

A635

Phys.

Work Rm.

A632D

LKRS.

A637B

HAC

A637A

HHN Off.

A641

Chief

Medical

Res.

A642

A643

Stair 1 S*6*1

Elec.

A645

Equip. Stor.

A646

D.R.

A647

A669

A671A

A675A676

Tlt.

A604A

Tlt.

A607A

Tlt.

A611A

Tlt.

A612A

Tlt.

A614A

Tlt.

A619A

Tlt.

A621A

Tlt.

A620A

Tlt.

A622A

Tlt.

A623A

Tlt.

A626ATlt.

A624A

Tlt.

A629A

Tlt.

A631A

Trash

Chute A637

Meeting

Room A634A

Sig. Clos.

A645A

Tlt.

A675A

Tlt.

A672A

Corridor C*6*1

Corridor C*6*2

Storage A646A

A/C Shaft A/C Shaft

A6002A

A6002

A6003AA6003A6004A

A6005

A6005A

A6006

A6006B

A6014A

A6013

A6013AA6012A

A6012

A6009

A6010

A6007B

A6007

A6007A

A6006A

A6004

A6000

A6008

C-6-6

A6001

C-6-6A

AREAWAYAREAWAY

A6011

A613

C-6-2A Tlt.

A608A

A602 A601

DN UP

DN UP

A643

TN-430-C.1.6

2 1

2 2 2 2

1 2

2 2 2 2

TR-6

2 2 2

2 2 2

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

1/8" = 1'-0"

TN-172-C.1.6

TECHNOLOGY SIXTH FLOOR PARTIAL

PLAN - B

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

04-MAY-2022

PR

C1

1/8" = 1'-0"

TECHNOLOGY SIXTH FLOOR PARTIAL PLAN - B

D B

A

GENERAL NOTES:

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED. DATA SHOWN IN

ROOM IS AN ESTIMATE OF WHAT WILL BE REQUIRED.

3. PROVIDE (4) 4" CONDUITS TO TR ON LEVEL BELOW.

4. PROVIDE (4) 4" CONDUITS TO TR ON LEVEL ABOVE.

TRUE NORTH PLAN NORTH

Description Date

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. ALL HORIZONTAL CABLING ON THIS FLOOR TO BE TERMINATED IN

TR-6.

3. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

4. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

5. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

6. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE

TRAY PLUS 50%.

7. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

8. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

9. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS IN

THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

11. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING REMOVED

FROM ANY WALL MOUNT EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE CONTRACTOR DURING

COMMISSIONING.

12. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

13. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

14. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES WITH

NEW CATEGORY MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW MODULAR JACKS

SHALL BE OF THE SAME MANUFACTURER AS THE FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

15. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

D.R.

A647

A648

D.R.

A649

Stair 5 S*6*5

A651

A652

A654 A655

A656 A657A658

A659

Elec.

A660

Elec.

A661

Soil. Util.

A662

A663

A663A

A664

A668 A669

A671A

A671

A672

CL. Lin.

A673

HAC

A674

Tlt.

A647A

Tlt.

A649A

Tlt.

A651A

Tlt.

A654A

Tlt.

A655A

Tlt.

A656A

Toilet A659A

Tlt.

A664A

A667A

A670

Tlt.

A675A

Tlt.

A672A

A667

Tlt.

A666

C-6-3A

A658A

A657A

C-6-3A

DNUP

2 1

2 2

2 2

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

1/8" = 1'-0"

TN-173-C.1.6

TECHNOLOGY SIXTH FLOOR PARTIAL

PLAN - D

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

04-MAY-2022

PR

C1

1/8" = 1'-0"

TECHNOLOGY SIXTH FLOOR PARTIAL PLAN - D D

B

A

GENERAL NOTES:

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. EXISTING CONDITIONS WERE NOT OBSERVED. DATA SHOWN IN

ROOM IS AN ESTIMATE OF WHAT WILL BE REQUIRED.

TRUE NORTH PLAN NORTH

Description Date

1. REFER TO SHEET T-000 FOR GENERAL NOTES AND LEGENDS.

2. ALL HORIZONTAL CABLING ON THIS FLOOR TO BE TERMINATED IN

TR-6.

3. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

4. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

5. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

6. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE

TRAY PLUS 50%.

7. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

8. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

9. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS OTHERWISE

NOTED.

10. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS IN

THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

11. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING REMOVED

FROM ANY WALL MOUNT EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE CONTRACTOR DURING

COMMISSIONING.

12. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

13. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

14. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES WITH

NEW CATEGORY MODULAR JACKS TO MATCH THE COMMUNICATION

CABLE PERFORMANCE SPECIFICATIONS. NEW MODULAR JACKS

SHALL BE OF THE SAME MANUFACTURER AS THE FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

15. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

A/C Shaft

A737

Bath A711A

Soil. Util.

A712

A713

Elec.

A714

S.R.

A715

Clean

Linen A716

S.R.

A717

S.R.

A718

Bed Room A719

Ex. Group A720

Bath A719A

Bed Room A722

Q.R.

A723

T.L.T.

A723A

T.L.T.

A722A

T.L.T.

A715A

Ante A711

Dining/Group

Room A705

Nurse

Station A705A

S.R.

A706

Bath A706A

Bath A707A

T.R.

A707

T.R.

A708

Bath A708A

Bath A709B

Ante A709

Obser.

A710

S.R.

A709A

Exist.

Seclusion A711B

Stair 2 S*7*2

Nurse

Station

Meds A725A

Stor.

A724

Nurse

Station A725

Nurse

Station

Work/Conference A725B

Break

Room A726

Corridor C*7*2

Storage A740

Waiting A774

Office #14 A743

Office #13 A744

Stair 5 S*7*5

Sensory

Therapy

Room A704

Storage A704B

Storage A702A

Interview

Room A702

Nurse Off.

A701

Chief Nurse

Off.

A700

Exam Rm.

A776

Office #18 A775

Reception A773

Training (6) A746 Stor.

A747

S. Office

#11A A748

S. Office

#11A A749

Office #12 A750

Group #2

(10-12) A751Office #10

A752 Tlt.

A753 Office #9

A754 Office #8

A755 Office #7

A756 Office #6

A757

Elec.

A758

A759

HAC

A760

Ante A761

Office A762

Office #5 A763

Office #5A A764

Office #5B A765

Group #1

(12-20) A766

Office A767A

Office #2 A768

Office #3 A769

Testing A770

Vis. Bath A771

Copy Rm.

A773A

Staff Office A767

Lockers A727B

Service

Elev. Lobby A727

Laundry A728A

Trash

Chute A727A

Staff Tlt.

A736

Sig. Clos.

A734

Stair 1 S*7*1

HAC

A735

Stor.

A735A

Elec.

Occupational

Therapy A732

Corridor C*7*1

DB Wtr.

A729

Storage A728CSocial

Worker A728D

Group

Room A728

Elec.

A728B

Soc.

Worker A730

O/T Off.

A731

Tlt.

A730A

Social

Worker B733A

Psych. Res.

B734

Tlt.

B734A

Waiting B705

Stat.

B704

Nurse Man.

B703

Soc.

Worker B702

Intake

Coor.

B701

Off.

B733

Off.

B733B

HAC

B732

Stor.

B731

Stor.

B719

Reception B705C

Elec B706

Break

Room B705D

Staff Tlt.

B705E

Signal

Closet B705F

Stair 3 S*7*3

Office B708

Office B709

Office B710

Office B711A

Tobacco &

Acohol

Research

Center B712

Group Rm.

B713

Off.

B714

Off.

B715A

Off.

B716A

Off.

B717

Off.

B715B

Off.

B714A

Off.

B721

Off.

B722

Off.

B723

Off.

B724

Group

Room B725

Off.

B726

Off.

B727

Wash

Room B728

Off.

B729

KLT

B730

Adm. Asst.

B716B

Bath B721A

Tlt.

B723A

Tlt.

B722A

Elec.

B720

Group

Room B725B

Tlt.

B726A

Off.

B711

Tlt.

B729A

Closet A728E

Clos.

A772

Office A741

Office A742

Storage A704A

DN UP DNUP

DN UP

DN

UP

Telecom Room

(2) SS04 (2) SS04 (2) SS04

(2) SS04

(2) SS04

(4) SS04

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

1/16" = 1'-0"

TN-180-C.1.7

TECHNOLOGY SEVENTH FLOOR

OVERALL PLAN

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

04-MAY-2022

PR

C1

1/16" = 1'-0"

TECHNOLOGY SEVENTH FLOOR OVERALL PLAN

D B

A

GENERAL NOTES:

KEYED NOTES:

1. EXISTING TELECOMMUNICATIONS ROOM.

2. PROVIDE (4) 4" CONDUITS TO TR ON…