ATTACHMENT 14 - Drawings 13 of 13.pdf

PDF 19 MB Posted

Attached to
36C77623B0005 EHRM Infrastructure Upgrades - Cincinnati Project #539-21-701
Solicitation number
36C77623B0005
Issued by

About this file

This document provides details on a federal solicitation opportunity and an associated file attachment. The solicitation number is 36C77623B0005 for the EHRM Infrastructure Upgrades - Cincinnati Project #539-21-701 opportunity through the Department of Veterans Affairs Technology Acquisition Center Austin. The opportunity type is a solicitation for construction services to upgrade infrastructure at the Cincinnati VAMC as outlined in Attachment 14 - Drawings 13 of 13.pdf. The description specifies infrastructure upgrades and the associated project number. No further key details are provided on response dates, pricing terms, or other requirements.

View the file

Other files

File Type Posted
36C77623B0005 0004 - Extension 3-10-23.pdf PDF
Technical Questions and Answers - Cincinnati EHRM.pdf PDF
36C77623B0005 0003.pdf PDF
36C77623B0005 0002 - EHRM Infrastructure Upgrades - Cincinnati.pdf PDF
Site Visit Sign-In Sheet - 36C77632B0005 EHRM Infrastructure Construction - Cincinnati VAMC.pdf PDF
ATTACHMENT 24 - Construction Wage Rates - Hamilton 01-13-2023.pdf PDF
36C77623B0005 0001 - EHRM Infrastructure Upgrades - Cincinnati.pdf PDF
Site Visit Memorandum.pdf PDF
ATTACHMENT 4 - Drawings 3 of 13.pdf PDF
ATTACHMENT 23 - Contractor Safety - Environmental Form.pdf PDF
ATTACHMENT 6 - Drawings 5 of 13.pdf PDF
ATTACHMENT 18 - Technology Narrative.pdf PDF
ATTACHMENT 13 - Drawings 12 of 13.pdf PDF
ATTACHMENT 15 - Plumbing Narrative.pdf PDF
ATTACHMENT 19 - Hazardous Materials Inspection Report.pdf PDF
ATTACHMENT 24 - Construction Wage Rates - Hamilton 1-13-2022.pdf PDF
ATTACHMENT 21 - COVID-19 Safety Protocols 12-14-21.pdf PDF
ATTACHMENT 20 - Brand Name Justification.pdf PDF
ATTACHMENT 22 - Limitations on Subcontracting - Nov 2022.pdf PDF
ATTACHMENT 9 - Drawings 8 of 13.pdf PDF
ATTACHMENT 10 - Drawings 9 of 13.pdf PDF
ATTACHMENT 16 - Mechanical Narrative.pdf PDF
ATTACHMENT 7 - Drawings 6 of 13.pdf PDF
ATTACHMENT 3 - Drawings 2 of 13.pdf PDF
ATTACHMENT 17 - Electrical Narrative.pdf PDF
ATTACHMENT 2 - Drawings 1 of 13.pdf PDF
ATTACHMENT 25 - Site Visit Instructions.pdf PDF
ATTACHMENT 8 - Drawings 7 of 13.pdf PDF
ATTACHMENT 11 - Drawings 10 of 13.pdf PDF
ATTACHMENT 12 - Drawings 11 of 13.pdf PDF
ATTACHMENT 5 - Drawings 4 of 13.pdf PDF
36C77623B0005 Solicitation - Cincinnati EHRM.pdf PDF
ATTACHMENT 1 - Specifications.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WEST WALL ELEVATION - BLDG. 2 - FLOOR 2

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 2 - FLOOR 2

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. 2 - FLOOR 2

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 2 - FLOOR 2

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 2 - FLOOR 2

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 2 - FLOOR 2

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 2 - FLOOR 2

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TN-472-C.2.2

BLDG. 2 - SECOND FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

DrawnCheckedIssue Date

04-MAY-2022 RMJr VV18-OCT-2022

NORTH WALL ELEVATION - BLDG. 3 - BASEMENT

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 3 - BASEMENT

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 3 - BASEMENT

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 3 - BASEMENT

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 3 - BASEMENT

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 3 - BASEMENT

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

SOUTH WALL ELEVATION - BLDG. 3 - BASEMENT

SCALE: N.T.S

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TN-473-C.3.B

BLDG. 3 - BASEMENT -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

UP

SOUTH WALL ELEVATION - BLDG. 8 - FLOOR 2

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 8 - FLOOR 2

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 8 - FLOOR 2

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 8 - FLOOR 2

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 8 - FLOOR 2

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 8 - FLOOR 2

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 8 - FLOOR 2

SCALE: 1/2" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TN-474-C.8.2

BLDG. 8 - SECOND FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

4 WEST WALL ELEVATION - BLDG. 15 - FLOOR 1

SCALE: N.T.S

2 SOUTH WALL ELEVATION - BLDG. 15 - FLOOR 1

SCALE: N.T.S 3 NORTH WALL ELEVATION - BLDG. 15 - FLOOR 1

SCALE: N.T.S

6 RACK ELEVATION - FRONT VIEW - BLDG. 15 - FLOOR 1

SCALE: N.T.S. 7 RACK ELEVATION - REAR VIEW - BLDG. 15 - FLOOR 1

SCALE: N.T.S.

1 TELECOM ROOM LAYOUT - BLDG. 15 - FLOOR 1

SCALE: 1/2" = 1'-0"

GROUP AA

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

5 EAST WALL ELEVATION - BLDG. 15 - FLOOR 1

SCALE: N.T.S

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

28-OCT-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TN-479-C.15.1

BLDG. 15 - FIRST FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x48", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

SOUTH WALL ELEVATION - BLDG. 64 - BASEMENT

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 64 - BASEMENT

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 64 - BASEMENT

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 64 - BASEMENT

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 64 - BASEMENT

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 64 - BASEMENT

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 64 - BASEMENT

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TN-480-F.64.B

BLDG. 64- BASEMENT -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

NORTH WALL ELEVATION - BLDG. 64 - FLOOR 1

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. 64 - FLOOR 1

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 64 - FLOOR 1

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 64 - FLOOR 1

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 64 - FLOOR 1

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 64 - FLOOR 1

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 64 - FLOOR 1

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TN-481-F.64.1

BLDG. 64- FIRST FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

EAST WALL ELEVATION - BLDG. 64 - TR 220

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 64 - TR 220

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. 64 - TR 220

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 64 - TR 220

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 64 - TR 220

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 64 - TR 220

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 64 - TR 220

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TN-482-F.64.2

BLDG. 64 - FIRST FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

WEST WALL ELEVATION - BLDG. 64 - FLOOR 3

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 64 - FLOOR 3

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 64 - FLOOR 3

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. 64 - FLOOR 3

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 64 - FLOOR 3

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 64 - FLOOR 3

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 64 - FLOOR 3

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TN-483-F.64.3

BLDG. 64 - THIRD FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

BLDG. 117 FIRST FLOOR TELECOM ROOM LAYOUT

SCALE: 1/2" = 1'-0"

BLDG. 117 FIRST FLOOR WEST WALL ELEVATION

SCALE: 1/2" = 1'-0"

BLDG. 117 FIRST FLOOR NORTH WALL ELEVATION

SCALE: 1/2" = 1'-0"

BLDG. 117 FIRST FLOOR EAST WALL ELEVATION

SCALE: 1/2" = 1'-0"

UP

Tools

103A

Garage

BLDG. 117 TR WALL MOUNT RACK ELEVATION

SCALE: N.T.S.

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TN-484-F.117.1

BLDG. 117 - FIRST FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x48", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

EAST WALL ELEVATION - BLDG. TB - FLOOR 1

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. TB - FLOOR 1

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. TB - FLOOR 1

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. TB - FLOOR 1

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. TB - FLOOR 1

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. TB - FLOOR 1

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. TB - FLOOR 1

SCALE: 1/2" = 1'-0"

TN-490-C.TB.1

BLDG. TB - FIRST FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

TB

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x48", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

EAST WALL ELEVATION - BLDG. TB - FLOOR 1

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. TB - FLOOR 1

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. TB - FLOOR 1

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. TB - FLOOR 1

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. TB - FLOOR 1

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. TB - FLOOR 1

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. TB - FLOOR 1

SCALE: 1/2" = 1'-0"

TN-490-C.TB.1

BLDG. TB - FIRST FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

TB

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas…