This document provides details on a federal solicitation opportunity and a related file attachment. The solicitation number is 36C77623B0005 for the EHRM Infrastructure Upgrades - Cincinnati Project #539-21-701 opportunity. The Department of Veterans Affairs Technology Acquisition Center Austin is seeking construction services for infrastructure upgrades at the Cincinnati VAMC, as described in the related drawing attachment file. The solicitation type is for construction of the specified upgrades at the medical center.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
UP
EXIST.
TELECOM ROOM
B312D
EXIST.
RESEARCH OFFICE
B312
EXIST.
OFFICE
B312A
EXIST.
STAIR 3
B*3*3
14'-0"±
'-1
/4
TELECOM
ROOM
C3006
EXIST.
CONSULTATION
C3005
EXIST.
LOBBY
C3001
EXIST.
POST OP
C3040
EXIST.
PREP./RECOVERY
C3039
EXIST.
STAFF WORKRM.
C3007
EXIST.
RECEPTION
C3004
EXIST.
CORRIDOR
C*3*11
15'-9 1/2"±
6' -6
2'-6"
5'-8"
EXIST.
FAMILY WAITING
C310
EXIST.
LACTATION
C312
EXIST.
GRIEVE CONSULT.
C313
EXIST.
SOCIAL WORKER
A383
EXIST.
STORAGE
C308
EXIST.
ON CALL
A381
EXIST.
CORRIDOR
C*3*17
1717B312 B312D
C3006
A383A
1 EXISTING TELECOM ROOM B312D - ROOM RENOVATION
SCALE: 1/4" = 1'-0" 3 TELECOM ROOM C3006 - ROOM RENOVATION
SCALE: 1/4" = 1'-0"
5 RESIDENT OFFICE/OVERNIGHT A383A- ROOM RENOVATION
SCALE: 1/4" = 1'-0"
X2
X2
X2
X4
X2 X2
X2
RESIDENT OFFICE/
OVERNIGHT
A383A
1 2532
'-6
12'-4"±
16'-4 3/8"±
6' -2
/4
X2
X2A
X4
X2
X4
7 TELECOM ROOM C305 - ROOM RENOVATION
SCALE: 1/4" = 1'-0"
TELECOM
ROOM
C305
EXIST.
OFFICE
C306
EXIST.
CORRIDOR
C*3*17
C305
8'-4"±
'-9
2 3
X2
X4
X2
X4
X4
EXIST.
TELECOM ROOM
B312D
EXIST.
RESEARCH OFFICE
B312
EXIST.
OFFICE
B312A
EXIST.
STAIR 3
B*3*3
EXIST.
CONSULTATION
C3005
EXIST.
LOBBY
C3001
EXIST.
POST OP
C3040
EXIST.
PREP./RECOVERY
C3039
EXIST.
STAFF WORKRM.
C3007
EXIST.
RECEPTION
C3004
EXIST.
CORRIDOR
C*3*11
EXIST.
FAMILY WAITING
C310
EXIST.
LACTATION
C312
EXIST.
GRIEVE CONSULT.
C313
EXIST.
SOCIAL WORKER
A383
EXIST.
STORAGE
C308
EXIST.
ON CALL
A381
EXIST.
CORRIDOR
C*3*17
TELECOM
ROOM
C3006
2 EXISTING TELECOM ROOM B312D - CEILING RENOVATION
SCALE: 1/4" = 1'-0" 4 TELECOM ROOM C3006 - CEILING RENOVATION
SCALE: 1/4" = 1'-0"
6 RESIDENT OFFICE/OVERNIGHT A383A - CEILING RENOVATION
SCALE: 1/4" = 1'-0"
OD
OD
RESIDENT OFFICE/
OVERNIGHT
A383A
8 TELECOM ROOM C305 - CEILING RENOVATION
SCALE: 1/4" = 1'-0"
TELECOM
ROOM
C305 EXIST.
OFFICE
C306
EXIST.
CORRIDOR
C*3*17
OD
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project Title
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
PhaseDrawing Title
Approved: Project Director
PROJECT MANAGEMENTCONSULTANTRevisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
FULLY SPRINKLERED
539-21-701
4-MAY-2022
100% CONSTRUCTION
DOCUMENTS
CINCINNATI VAMC EHRM
INFRASTRUCTURE UPGRADES
3200 VINE ST., CINCINNATI, OH
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
ETS
T
TA
GE
S
R I
E T E X
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJO
SE
P
H
7 6 22 1
5/4/22
AS-403-C.1.3
ENLARGED FLOOR PLANS -
3RD FLOOR RENOVATION
IAR
C1
1. REFERENCE GENERAL NOTES ON SHEET GI-004.
2. UNLESS NOTED OTHERWISE, ALL EXISTING WALLS
ARE 5/8" GYPSUM BOARD/3 5/8"METAL STUD FRAMED
TO UNDERSIDE OF PRIMARY BUILDING FRAMING
STRUCTURE (1 HR. FIRE RATED - CONSTRUCTION
SIMILAR TO U.l. DESIGN NO. U465). CONTRACTOR TO
VERIFY.
3. UNLESS NOTED OTHERWISE, ALL EXISTING DOOR
ASSEMBLIES ARE SOLID CORE WOOD DOORS/HOLLOW
METAL FRAME TYPICAL (3'-0" X 7'-0").
4. UNLESS NOTED OTHERWISE ALL EXISTING LAY-IN
CEILING ASSEMBLIES ARE 2' X 2' STANDARD GRID WITH
FISSURED TILES AT 8'-0" A.F.F. TYPICAL.
5. UNLESS NOTED OTHERWISE, ALL EXISTING STEEL
COLUMN FUR-OUTS ARE GYPSUM BOARD/METAL STUD
FRAMED TYPICAL.
6. PARTIAL OR ENTIRE RECONSTRUCTION OF SOME
EXISTING CEILING ASSEMBLIES THOUGH OUT THE
ENTIRE BUILDING(S), ESPECIALLY IN CORRIDORS,
WILL BE NECESSARY. REFERENCE ALL DISCIPLINE
DEMOLITION DRAWINGS. RECONSTRUCTION IS TO
INCLUDE MISCELLANEOUS PATCHING /REPAIR TO
MATCH EXISTING OR BETTER CONDITIONS.
7. EXISTING FIRE-RATED WALL IDENTIFICATION
INDICATED ONLY FOR IMMEDIATE AFFECTED ROOM
WALLS. CONTRACTOR SHALL VERIFY FULL EXTENT OF
EXISTING FIRE-RATED WALLS AT ADJACENT AREAS.
8. ALL NEW WALLS SHALL BE PARTITION TYPE '1' UNLESS
OTHERWISE NOTED.
9. UNLESS NOTED OTHERWISE AT ALL ROOMS WHERE
EXISTING LAY-IN CEILING IS REMOVED AND IS TO
BECOME A "NO CEILING" ROOM, THE EXISTING
GYPSUM BOARD ABOVE PREVIOUSLY REMOVED
CEILING IS TO BE FULLY TAPED, FLOATED, TEXTURED
AND PAINTED TO MATCH EXISTING WALLS.
GENERAL NOTES - RENOVATION
1. EXISTING DOOR/FRAME ASSEMBLY TO REMAIN.
2. PROVIDE CARD READER.
3. PROVIDE ROOM SIGNAGE.
4. PROVIDE NEW FLOORING AND BASE AS SCHEDULED.
5. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE IN THIS ROOM THAT MAY REQUIRE MINOR
DEMOLITION, PATCHING AND REPAIR OF EXISTING
FLOOR SUBSTRATE, WALL OR MISCELLANEOUS
ASSEMBLIES.
6. PROVIDE 8'x4'x3/4" 'AC' FACED FIRE-RATED PLYWOOD
VERTICALLY ON ALL WALLS AS INDICATED. PAINT WITH 2
COATS MIN. FIRE-RATED PAINT. COORDINATE EXACT
LOCATION A.F.F. WITH TECHNOLOGY AND ELECTRICAL
DRAWINGS AND EXISTING CONDITIONS.
7. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE OF EXISTING AND NEW COMPONENTS AT
CEILING LEVEL.
8. EXISTING FLOOR AND BASE TO REMAIN. REPAIR AS
NECESSARY TO MATCH EXISTING CONDITIONS OR
BETTER.
9. EXISTING VCT FLOORING AND RUBBER BASE TO REMAIN.
10. LIMITED RENOVATION TO EXISTING CEILING ASSEMBLY
PER MEP AND TECHNOLOGY DRAWINGS WORK SCOPE.
11. RELOCATED EXISTING MARKER BOARD.
12. RELOCATED EXISTING MILLWORK.
13. CEILING FUR-DOWN ABOVE.
14. NEW GYPSUM BOARD/METAL STUD FRAMED FUR-DOWN
TO MATCH EXISTING HEIGHT. NO JOINTS
UNLESS NOTED OTHERWISE.
15. RELOCATED EXISTING LIGHT FIXTURE.
16. RELOCATED EXISTING TV MONITOR.
17. EXISTING ALUMINUM FLOOR AND WALL (EACH SIDE)
EXPANSION JOINT COVERS TO REMAIN.
18. EXISTING GYPSUM BOARD/METAL STUD FRAMED
FUR-DOWN TO REMAIN.
19. RELOCATED EXISTING FIRE EXTINGUISHER.
20. EXISTING EXTERIOR WINDOW TO REMAIN.
21. REINSTALL EXISTING SALVAGED WOOD BASE AND CHAIR
RAIL. PROVIDE BALANCE OF MATERIAL AS NEEDED TO
COMPLETE JOB. PAINT ALL BASE AND CHAIR RAIL IN
ENTIRE ROOM.
22. EXISTING PLASTER ON CMU TO UNDERSIDE OF EXISTING
STRUCTURE (4" OR 8" CMU PER WALL THICKNESS
DEPICTED GRAPHICALLY). FIRE-RATED WALL.
CONTRACTOR VERIFY.
23. EXISTING ROOM SIGNAGE.
24. EXISTING CARD READER.
25. REFERENCE DOOR SCHEDULE.
26. PAINT INTERIOR SIDE OF EXISTING WINDOW GLAZING
ONLY "FLAT BLACK".
27. REINSTALLED EXISTING ROOM SIGNAGE.
28. REINSTALLED EXISTING CARD READER.
29. PLASTER ASSEMBLY INFILL AT EXISTING WALL AS
DETAILED AT EXISTING WINDOW OPENING.
30. ENSURE EXISTING WALL VENT IS SECURELY CLOSED
SHUT PRIOR TO COVER-UP.
31. PROVIDE WALL PROTECTION TO MATCH EXISTING.
32. PROVIDE NEW CEILING AS SCHEDULED.
33. PROVIDE GYPSUM BOARD/STEEL STUD FRAMED
FUR-DOWN AS DETAILED.
34. PROVIDE 2' X 2' RAISED FLOOR SYSTEM AT 10" ABOVE
THE 4TH FLOOR LEVEL.
35. ELECTRICAL CONDUITS AND MECHANICAL PIPING PER
MEP DRAWINGS.
36. PROVIDE 5/8" GYPSUM BOARD WHERE EXISTING TILE
WAINSCOT AND SUBSTRATE WAS REMOVED. TEXTURE
AND FINISH TO MATCH EXISTING ADJACENT WALLS (4'-0"±
HIGH, LOCATE AS INDICATED BY HEAVY LINE).
37. TEXTURE AND FINISH EXISTING GYPSUM BOARD
SUBSTRATE TO MATCH EXISTING ADJACENT WALLS.
38. GYPSUM BOARD ASSEMBLY INFILL AS DETAILED AT
EXISTING WINDOW OPENING.
39. PROVIDE INFILL PER KEYED NOTE 29 AT VOID LEFT BY
HEATER REMOVED.
40. PROVIDE 1" THICK MINIMUM CONCRETE INFILL FLUSH
WITH EXISTING CONCRETE TOPPING WHERE PORTIONS
OF EXISTING CMU WALLS ARE REMOVED.
41. PROVIDE PAINTED WOOD CHAIR RAIL TO MATCH
EXISTING.
42. REINSTALLED EXISTING SHELF.
43. PROVIDE GYPSUM BOARD/METAL STUD FRAMED CHASE
FROM FLOORS ABOVE . MINIMIZE SIZE AND REFERENCE
MEP DRAWINGS FOR COMPONENTS TO BE IN CHASE.
44. RAMP AND RAILS BY RAISED FLOOR SYSTEM
MANUFACTURER.
45. ROOM PERIMETER WALLS TO BE FULLY SEALED TOP
AND BOTTOM ON BOTH SIDES OF WALL. EXTERIOR WALL
SEAL INTERIOR SIDE ONLY.
KEYED NOTES - RENOVATION
46. TEMPORARY ALUMINUM RAMP BY CONTRACTOR TO BE
RETURNED TO OWNER AT END OF JOB.
47. MODULAR BRICK INFILL ON EXTERIOR TO MATCH
EXISTING. TOOTH-IN AND MATCH MORTAR.
KEYED NOTES - RENOVATION (CONT.)
EXISTING WALL TO REMAIN
NEW WALL CONSTRUCTION
EXISTING DOOR/FRAME ASSEMBLY
TO REMAIN
EXISTING WINDOW ASSEMBLY
TO REMAIN
NEW WINDOW ASSEMBLY
NEW DOOR/FRAME ASSEMBLY
1 HR. FIRE-RATED WALL (EXISTING)
2 HR. FIRE-RATED WALL (EXISTING)
LEGEND - RENOVATION
FIRE-RATED WALL (NEW OR EXISTING
1 HOUR UNLESS NOTED OTHERWISE)
TRUE NORTH PLAN
NORTH
TRUE NORTH PLAN
NORTH
TRUE NORTH PLAN
NORTH
TRUE NORTH PLAN
NORTH
TRUE NORTH PLAN
NORTH
TRUE NORTH PLAN
NORTH
TRUE NORTH PLAN
NORTHTRUE NORTH PLAN
NORTH
1 TELECOM ROOM A441 - ROOM RENOVATION
SCALE: 1/4" = 1'-0"
3 EXIST. COMPUTER A437C - ROOM RENOVATION
SCALE: 1/4" = 1'-0"
A437A
A437
A437C
15'-4"±
9' -1
2 23
A441
TELECOM
ROOM
A441
EXIST. IRM
NOC
A437
EXIST. CPU
ROOM
A437C
EXIST. SERVICE
LOBBY
A436
3'-2 1/2"
7' -0
X3B X3B
X3B X3B
'-6
13'-8"±
'-1
1"
3'-3"
17'-7 1/4"±
10'-0" (1/12 RAMP SLOPE)
4444 5
X4 X2A
X2A
X2A
X2A
X2
X2
2 28
2 TELECOM ROOM A441 - CEILING RENOVATION
SCALE: 1/4" = 1'-0"
4 EXIST. COMPUTER A437C - CEILING RENOVATION
SCALE: 1/4" = 1'-0"
OD 77
TELECOM
ROOM
A441
EXIST. IRM
NOC
A437
EXIST. CPU
ROOM
A437C
EXIST. SERVICE
LOBBY
A436
OD OD
OD
OD OD
OD
OD
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project Title
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
PhaseDrawing Title
Approved: Project Director
PROJECT MANAGEMENTCONSULTANTRevisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
FULLY SPRINKLERED
539-21-701
4-MAY-2022
100% CONSTRUCTION
DOCUMENTS
CINCINNATI VAMC EHRM
INFRASTRUCTURE UPGRADES
3200 VINE ST., CINCINNATI, OH
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
ETS
T
TA
GE
S
R I
E T E X
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJ
O
SE
P
H
7 6 22 1
5/4/22
AS-404-C.1.4
ENLARGED FLOOR PLANS -
FOURTH FLOOR - RENOVATION
IAR
IAR, JFB
1. REFERENCE GENERAL NOTES ON SHEET GI-004.
2. UNLESS NOTED OTHERWISE, ALL EXISTING WALLS
ARE 5/8" GYPSUM BOARD/3 5/8"METAL STUD FRAMED
TO UNDERSIDE OF PRIMARY BUILDING FRAMING
STRUCTURE (1 HR. FIRE RATED - CONSTRUCTION
SIMILAR TO U.l. DESIGN NO. U465). CONTRACTOR TO
VERIFY.
3. UNLESS NOTED OTHERWISE, ALL EXISTING DOOR
ASSEMBLIES ARE SOLID CORE WOOD DOORS/HOLLOW
METAL FRAME TYPICAL (3'-0" X 7'-0").
4. UNLESS NOTED OTHERWISE ALL EXISTING LAY-IN
CEILING ASSEMBLIES ARE 2' X 2' STANDARD GRID WITH
FISSURED TILES AT 8'-0" A.F.F. TYPICAL.
5. UNLESS NOTED OTHERWISE, ALL EXISTING STEEL
COLUMN FUR-OUTS ARE GYPSUM BOARD/METAL STUD
FRAMED TYPICAL.
6. PARTIAL OR ENTIRE RECONSTRUCTION OF SOME
EXISTING CEILING ASSEMBLIES THOUGH OUT THE
ENTIRE BUILDING(S), ESPECIALLY IN CORRIDORS,
WILL BE NECESSARY. REFERENCE ALL DISCIPLINE
DEMOLITION DRAWINGS. RECONSTRUCTION IS TO
INCLUDE MISCELLANEOUS PATCHING /REPAIR TO
MATCH EXISTING OR BETTER CONDITIONS.
7. EXISTING FIRE-RATED WALL IDENTIFICATION
INDICATED ONLY FOR IMMEDIATE AFFECTED ROOM
WALLS. CONTRACTOR SHALL VERIFY FULL EXTENT OF
EXISTING FIRE-RATED WALLS AT ADJACENT AREAS.
8. ALL NEW WALLS SHALL BE PARTITION TYPE '1' UNLESS
OTHERWISE NOTED.
9. UNLESS NOTED OTHERWISE AT ALL ROOMS WHERE
EXISTING LAY-IN CEILING IS REMOVED AND IS TO
BECOME A "NO CEILING" ROOM, THE EXISTING
GYPSUM BOARD ABOVE PREVIOUSLY REMOVED
CEILING IS TO BE FULLY TAPED, FLOATED, TEXTURED
AND PAINTED TO MATCH EXISTING WALLS.
GENERAL NOTES - RENOVATION
1. EXISTING DOOR/FRAME ASSEMBLY TO REMAIN.
2. PROVIDE CARD READER.
3. PROVIDE ROOM SIGNAGE.
4. PROVIDE NEW FLOORING AND BASE AS SCHEDULED.
5. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE IN THIS ROOM THAT MAY REQUIRE MINOR
DEMOLITION, PATCHING AND REPAIR OF EXISTING
FLOOR SUBSTRATE, WALL OR MISCELLANEOUS
ASSEMBLIES.
6. PROVIDE 8'x4'x3/4" 'AC' FACED FIRE-RATED PLYWOOD
VERTICALLY ON ALL WALLS AS INDICATED. PAINT WITH 2
COATS MIN. FIRE-RATED PAINT. COORDINATE EXACT
LOCATION A.F.F. WITH TECHNOLOGY AND ELECTRICAL
DRAWINGS AND EXISTING CONDITIONS.
7. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE OF EXISTING AND NEW COMPONENTS AT
CEILING LEVEL.
8. EXISTING FLOOR AND BASE TO REMAIN. REPAIR AS
NECESSARY TO MATCH EXISTING CONDITIONS OR
BETTER.
9. EXISTING VCT FLOORING AND RUBBER BASE TO REMAIN.
10. LIMITED RENOVATION TO EXISTING CEILING ASSEMBLY
PER MEP AND TECHNOLOGY DRAWINGS WORK SCOPE.
11. RELOCATED EXISTING MARKER BOARD.
12. RELOCATED EXISTING MILLWORK.
13. CEILING FUR-DOWN ABOVE.
14. NEW GYPSUM BOARD/METAL STUD FRAMED FUR-DOWN
TO MATCH EXISTING HEIGHT. NO JOINTS
UNLESS NOTED OTHERWISE.
15. RELOCATED EXISTING LIGHT FIXTURE.
16. RELOCATED EXISTING TV MONITOR.
17. EXISTING ALUMINUM FLOOR AND WALL (EACH SIDE)
EXPANSION JOINT COVERS TO REMAIN.
18. EXISTING GYPSUM BOARD/METAL STUD FRAMED
FUR-DOWN TO REMAIN.
19. RELOCATED EXISTING FIRE EXTINGUISHER.
20. EXISTING EXTERIOR WINDOW TO REMAIN.
21. REINSTALL EXISTING SALVAGED WOOD BASE AND CHAIR
RAIL. PROVIDE BALANCE OF MATERIAL AS NEEDED TO
COMPLETE JOB. PAINT ALL BASE AND CHAIR RAIL IN
ENTIRE ROOM.
22. EXISTING PLASTER ON CMU TO UNDERSIDE OF EXISTING
STRUCTURE (4" OR 8" CMU PER WALL THICKNESS
DEPICTED GRAPHICALLY). FIRE-RATED WALL.
CONTRACTOR VERIFY.
23. EXISTING ROOM SIGNAGE.
24. EXISTING CARD READER.
25. REFERENCE DOOR SCHEDULE.
26. PAINT INTERIOR SIDE OF EXISTING WINDOW GLAZING
ONLY "FLAT BLACK".
27. REINSTALLED EXISTING ROOM SIGNAGE.
28. REINSTALLED EXISTING CARD READER.
29. PLASTER ASSEMBLY INFILL AT EXISTING WALL AS
DETAILED AT EXISTING WINDOW OPENING.
30. ENSURE EXISTING WALL VENT IS SECURELY CLOSED
SHUT PRIOR TO COVER-UP.
31. PROVIDE WALL PROTECTION TO MATCH EXISTING.
32. PROVIDE NEW CEILING AS SCHEDULED.
33. PROVIDE GYPSUM BOARD/STEEL STUD FRAMED
FUR-DOWN AS DETAILED.
34. PROVIDE 2' X 2' RAISED FLOOR SYSTEM AT 10" ABOVE
THE 4TH FLOOR LEVEL.
35. ELECTRICAL CONDUITS AND MECHANICAL PIPING PER
MEP DRAWINGS.
36. PROVIDE 5/8" GYPSUM BOARD WHERE EXISTING TILE
WAINSCOT AND SUBSTRATE WAS REMOVED. TEXTURE
AND FINISH TO MATCH EXISTING ADJACENT WALLS (4'-0"±
HIGH, LOCATE AS INDICATED BY HEAVY LINE).
37. TEXTURE AND FINISH EXISTING GYPSUM BOARD
SUBSTRATE TO MATCH EXISTING ADJACENT WALLS.
38. GYPSUM BOARD ASSEMBLY INFILL AS DETAILED AT
EXISTING WINDOW OPENING.
39. PROVIDE INFILL PER KEYED NOTE 29 AT VOID LEFT BY
HEATER REMOVED.
40. PROVIDE 1" THICK MINIMUM CONCRETE INFILL FLUSH
WITH EXISTING CONCRETE TOPPING WHERE PORTIONS
OF EXISTING CMU WALLS ARE REMOVED.
41. PROVIDE PAINTED WOOD CHAIR RAIL TO MATCH
EXISTING.
42. REINSTALLED EXISTING SHELF.
43. PROVIDE GYPSUM BOARD/METAL STUD FRAMED CHASE
FROM FLOORS ABOVE . MINIMIZE SIZE AND REFERENCE
MEP DRAWINGS FOR COMPONENTS TO BE IN CHASE.
44. RAMP AND RAILS BY RAISED FLOOR SYSTEM
MANUFACTURER.
45. ROOM PERIMETER WALLS TO BE FULLY SEALED TOP
AND BOTTOM ON BOTH SIDES OF WALL. EXTERIOR WALL
SEAL INTERIOR SIDE ONLY.
KEYED NOTES - RENOVATION
46. TEMPORARY ALUMINUM RAMP BY CONTRACTOR TO BE
RETURNED TO OWNER AT END OF JOB.
47. MODULAR BRICK INFILL ON EXTERIOR TO MATCH
EXISTING. TOOTH-IN AND MATCH MORTAR.
KEYED NOTES - RENOVATION (CONT.)
EXISTING WALL TO REMAIN
NEW WALL CONSTRUCTION
EXISTING DOOR/FRAME ASSEMBLY
TO REMAIN
EXISTING WINDOW ASSEMBLY
TO REMAIN
NEW WINDOW ASSEMBLY
NEW DOOR/FRAME ASSEMBLY
1 HR. FIRE-RATED WALL (EXISTING)
2 HR. FIRE-RATED WALL (EXISTING)
LEGEND - RENOVATION
FIRE-RATED WALL (NEW OR EXISTING
1 HOUR UNLESS NOTED OTHERWISE)
TRUE NORTH PLAN
NORTH
TRUE NORTH PLAN
NORTH
TRUE NORTH PLAN
NORTH TRUE NORTH PLAN
1 TELECOM ROOM A540 - ROOM RENOVATION
A540
44 66
20 26 30
15'-8"±
9' -3
X3A
X3A X3A
TELECOM
ROOM
A540
EXIST.
CHIEF OFFICE
B540
EXIST.
CORRIDOR
C*5*1
EXIST.
ADMIN. ASST.
B541
EXIST.
CHIEF MED.
B542
2 TELECOM ROOM A540 - CEILING RENOVATION
SCALE: 1/4" = 1'-0"
OD
TELECOM
ROOM
A540
EXIST.
CHIEF OFFICE
B540
EXIST.
CORRIDOR
C*5*1
EXIST.
ADMIN. ASST.
B541
EXIST.
CHIEF MED.
B542
OD
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project Title
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
PhaseDrawing Title
Approved: Project Director
PROJECT MANAGEMENTCONSULTANTRevisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
FULLY SPRINKLERED
539-21-701
4-MAY-2022
100% CONSTRUCTION
DOCUMENTS
CINCINNATI VAMC EHRM
INFRASTRUCTURE UPGRADES
3200 VINE ST., CINCINNATI, OH
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
ETS
T
TA
GE
S
R I
E T E X
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJ
O
SE
P
H
7 6 22 1
5/4/22
AS-405-C.1.5
ENLARGED FLOOR PLAN -
FIFTH FLOOR - RENOVATION
IAR
IAR, JFB
1. REFERENCE GENERAL NOTES ON SHEET GI-004.
2. UNLESS NOTED OTHERWISE, ALL EXISTING WALLS
ARE 5/8" GYPSUM BOARD/3 5/8"METAL STUD FRAMED
TO UNDERSIDE OF PRIMARY BUILDING FRAMING
STRUCTURE (1 HR. FIRE RATED - CONSTRUCTION
SIMILAR TO U.l. DESIGN NO. U465). CONTRACTOR TO
VERIFY.
3. UNLESS NOTED OTHERWISE, ALL EXISTING DOOR
ASSEMBLIES ARE SOLID CORE WOOD DOORS/HOLLOW
METAL FRAME TYPICAL (3'-0" X 7'-0").
4. UNLESS NOTED OTHERWISE ALL EXISTING LAY-IN
CEILING ASSEMBLIES ARE 2' X 2' STANDARD GRID WITH
FISSURED TILES AT 8'-0" A.F.F. TYPICAL.
5. UNLESS NOTED OTHERWISE, ALL EXISTING STEEL
COLUMN FUR-OUTS ARE GYPSUM BOARD/METAL STUD
FRAMED TYPICAL.
6. PARTIAL OR ENTIRE RECONSTRUCTION OF SOME
EXISTING CEILING ASSEMBLIES THOUGH OUT THE
ENTIRE BUILDING(S), ESPECIALLY IN CORRIDORS,
WILL BE NECESSARY. REFERENCE ALL DISCIPLINE
DEMOLITION DRAWINGS. RECONSTRUCTION IS TO
INCLUDE MISCELLANEOUS PATCHING /REPAIR TO
MATCH EXISTING OR BETTER CONDITIONS.
7. EXISTING FIRE-RATED WALL IDENTIFICATION
INDICATED ONLY FOR IMMEDIATE AFFECTED ROOM
WALLS. CONTRACTOR SHALL VERIFY FULL EXTENT OF
EXISTING FIRE-RATED WALLS AT ADJACENT AREAS.
8. ALL NEW WALLS SHALL BE PARTITION TYPE '1' UNLESS
OTHERWISE NOTED.
9. UNLESS NOTED OTHERWISE AT ALL ROOMS WHERE
EXISTING LAY-IN CEILING IS REMOVED AND IS TO
BECOME A "NO CEILING" ROOM, THE EXISTING
GYPSUM BOARD ABOVE PREVIOUSLY REMOVED
CEILING IS TO BE FULLY TAPED, FLOATED, TEXTURED
AND PAINTED TO MATCH EXISTING WALLS.
GENERAL NOTES - RENOVATION
1. EXISTING DOOR/FRAME ASSEMBLY TO REMAIN.
2. PROVIDE CARD READER.
3. PROVIDE ROOM SIGNAGE.
4. PROVIDE NEW FLOORING AND BASE AS SCHEDULED.
5. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE IN THIS ROOM THAT MAY REQUIRE MINOR
DEMOLITION, PATCHING AND REPAIR OF EXISTING
FLOOR SUBSTRATE, WALL OR MISCELLANEOUS
ASSEMBLIES.
6. PROVIDE 8'x4'x3/4" 'AC' FACED FIRE-RATED PLYWOOD
VERTICALLY ON ALL WALLS AS INDICATED. PAINT WITH 2
COATS MIN. FIRE-RATED PAINT. COORDINATE EXACT
LOCATION A.F.F. WITH TECHNOLOGY AND ELECTRICAL
DRAWINGS AND EXISTING CONDITIONS.
7. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE OF EXISTING AND NEW COMPONENTS AT
CEILING LEVEL.
8. EXISTING FLOOR AND BASE TO REMAIN. REPAIR AS
NECESSARY TO MATCH EXISTING CONDITIONS OR
BETTER.
9. EXISTING VCT FLOORING AND RUBBER BASE TO REMAIN.
10. LIMITED RENOVATION TO EXISTING CEILING ASSEMBLY
PER MEP AND TECHNOLOGY DRAWINGS WORK SCOPE.
11. RELOCATED EXISTING MARKER BOARD.
12. RELOCATED EXISTING MILLWORK.
13. CEILING FUR-DOWN ABOVE.
14. NEW GYPSUM BOARD/METAL STUD FRAMED FUR-DOWN
TO MATCH EXISTING HEIGHT. NO JOINTS
UNLESS NOTED OTHERWISE.
15. RELOCATED EXISTING LIGHT FIXTURE.
16. RELOCATED EXISTING TV MONITOR.
17. EXISTING ALUMINUM FLOOR AND WALL (EACH SIDE)
EXPANSION JOINT COVERS TO REMAIN.
18. EXISTING GYPSUM BOARD/METAL STUD FRAMED
FUR-DOWN TO REMAIN.
19. RELOCATED EXISTING FIRE EXTINGUISHER.
20. EXISTING EXTERIOR WINDOW TO REMAIN.
21. REINSTALL EXISTING SALVAGED WOOD BASE AND CHAIR
RAIL. PROVIDE BALANCE OF MATERIAL AS NEEDED TO
COMPLETE JOB. PAINT ALL BASE AND CHAIR RAIL IN
ENTIRE ROOM.
22. EXISTING PLASTER ON CMU TO UNDERSIDE OF EXISTING
STRUCTURE (4" OR 8" CMU PER WALL THICKNESS
DEPICTED GRAPHICALLY). FIRE-RATED WALL.
CONTRACTOR VERIFY.
23. EXISTING ROOM SIGNAGE.
24. EXISTING CARD READER.
25. REFERENCE DOOR SCHEDULE.
26. PAINT INTERIOR SIDE OF EXISTING WINDOW GLAZING
ONLY "FLAT BLACK".
27. REINSTALLED EXISTING ROOM SIGNAGE.
28. REINSTALLED EXISTING CARD READER.
29. PLASTER ASSEMBLY INFILL AT EXISTING WALL AS
DETAILED AT EXISTING WINDOW OPENING.
30. ENSURE EXISTING WALL VENT IS SECURELY CLOSED
SHUT PRIOR TO COVER-UP.
31. PROVIDE WALL PROTECTION TO MATCH EXISTING.
32. PROVIDE NEW CEILING AS SCHEDULED.
33. PROVIDE GYPSUM BOARD/STEEL STUD FRAMED
FUR-DOWN AS DETAILED.
34. PROVIDE 2' X 2' RAISED FLOOR SYSTEM AT 10" ABOVE
THE 4TH FLOOR LEVEL.
35. ELECTRICAL CONDUITS AND MECHANICAL PIPING PER
MEP DRAWINGS.
36. PROVIDE 5/8" GYPSUM BOARD WHERE EXISTING TILE
WAINSCOT AND SUBSTRATE WAS REMOVED. TEXTURE
AND FINISH TO MATCH EXISTING ADJACENT WALLS (4'-0"±
HIGH, LOCATE AS INDICATED BY HEAVY LINE).
37. TEXTURE AND FINISH EXISTING GYPSUM BOARD
SUBSTRATE TO MATCH EXISTING ADJACENT WALLS.
38. GYPSUM BOARD ASSEMBLY INFILL AS DETAILED AT
EXISTING WINDOW OPENING.
39. PROVIDE INFILL PER KEYED NOTE 29 AT VOID LEFT BY
HEATER REMOVED.
40. PROVIDE 1" THICK MINIMUM CONCRETE INFILL FLUSH
WITH EXISTING CONCRETE TOPPING WHERE PORTIONS
OF EXISTING CMU WALLS ARE REMOVED.
41. PROVIDE PAINTED WOOD CHAIR RAIL TO MATCH
EXISTING.
42. REINSTALLED EXISTING SHELF.
43. PROVIDE GYPSUM BOARD/METAL STUD FRAMED CHASE
FROM FLOORS ABOVE . MINIMIZE SIZE AND REFERENCE
MEP DRAWINGS FOR COMPONENTS TO BE IN CHASE.
44. RAMP AND RAILS BY RAISED FLOOR SYSTEM
MANUFACTURER.
45. ROOM PERIMETER WALLS TO BE FULLY SEALED TOP
AND BOTTOM ON BOTH SIDES OF WALL. EXTERIOR WALL
SEAL INTERIOR SIDE ONLY.
KEYED NOTES - RENOVATION
46. TEMPORARY ALUMINUM RAMP BY CONTRACTOR TO BE
RETURNED TO OWNER AT END OF JOB.
47. MODULAR BRICK INFILL ON EXTERIOR TO MATCH
EXISTING. TOOTH-IN AND MATCH MORTAR.
KEYED NOTES - RENOVATION (CONT.)
EXISTING WALL TO REMAIN
NEW WALL CONSTRUCTION
EXISTING DOOR/FRAME ASSEMBLY
TO REMAIN
EXISTING WINDOW ASSEMBLY
TO REMAIN
NEW WINDOW ASSEMBLY
NEW DOOR/FRAME ASSEMBLY
1 HR. FIRE-RATED WALL (EXISTING)
2 HR. FIRE-RATED WALL (EXISTING)
LEGEND - RENOVATION
FIRE-RATED WALL (NEW OR EXISTING
1 HOUR UNLESS NOTED OTHERWISE)
TRUE NORTH PLAN
NORTH
TRUE NORTH PLAN
'-2
/4
TELECOM
ROOM
A643
EXIST.
MEDICAL RESIDENT
A642
EXIST.
STAIR 1
S*6*1
EXIST.
CORRIDOR
C*6*1
15'-5 7/8"±
A643
1 TELECOM ROOM A643 - ROOM RENOVATION
SCALE: 1/4" = 1'-0"
X3B
X3C
X3B
EXIST.
MEDICAL RESIDENT
A642
EXIST.
STAIR 1
S*6*1
EXIST.
CORRIDOR
C*6*1
TELECOM
ROOM
A643
2 TELECOM ROOM A643 - CEILING RENOVATION
SCALE: 1/4" = 1'-0"
OD
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project Title
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
PhaseDrawing Title
Approved: Project Director
PROJECT MANAGEMENTCONSULTANTRevisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
FULLY SPRINKLERED
539-21-701
4-MAY-2022
100% CONSTRUCTION
DOCUMENTS
CINCINNATI VAMC EHRM
INFRASTRUCTURE UPGRADES
3200 VINE ST., CINCINNATI, OH
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
ETS
T
TA
GE
S
R I
E T E X
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJO
S
EP
H
7 6 22 1
5/4/22
AS-406-C.1.6
ENLARGED FLOOR PLANS -
6TH FLOOR RENOVATION
IAR
C1
1. REFERENCE GENERAL NOTES ON SHEET GI-004.
2. UNLESS NOTED OTHERWISE, ALL EXISTING WALLS
ARE 5/8" GYPSUM BOARD/3 5/8"METAL STUD FRAMED
TO UNDERSIDE OF PRIMARY BUILDING FRAMING
STRUCTURE (1 HR. FIRE RATED - CONSTRUCTION
SIMILAR TO U.l. DESIGN NO. U465). CONTRACTOR TO
VERIFY.
3. UNLESS NOTED OTHERWISE, ALL EXISTING DOOR
ASSEMBLIES ARE SOLID CORE WOOD DOORS/HOLLOW
METAL FRAME TYPICAL (3'-0" X 7'-0").
4. UNLESS NOTED OTHERWISE ALL EXISTING LAY-IN
CEILING ASSEMBLIES ARE 2' X 2' STANDARD GRID WITH
FISSURED TILES AT 8'-0" A.F.F. TYPICAL.
5. UNLESS NOTED OTHERWISE, ALL EXISTING STEEL
COLUMN FUR-OUTS ARE GYPSUM BOARD/METAL STUD
FRAMED TYPICAL.
6. PARTIAL OR ENTIRE RECONSTRUCTION OF SOME
EXISTING CEILING ASSEMBLIES THOUGH OUT THE
ENTIRE BUILDING(S), ESPECIALLY IN CORRIDORS,
WILL BE NECESSARY. REFERENCE ALL DISCIPLINE
DEMOLITION DRAWINGS. RECONSTRUCTION IS TO
INCLUDE MISCELLANEOUS PATCHING /REPAIR TO
MATCH EXISTING OR BETTER CONDITIONS.
7. EXISTING FIRE-RATED WALL IDENTIFICATION
INDICATED ONLY FOR IMMEDIATE AFFECTED ROOM
WALLS. CONTRACTOR SHALL VERIFY FULL EXTENT OF
EXISTING FIRE-RATED WALLS AT ADJACENT AREAS.
8. ALL NEW WALLS SHALL BE PARTITION TYPE '1' UNLESS
OTHERWISE NOTED.
9. UNLESS NOTED OTHERWISE AT ALL ROOMS WHERE
EXISTING LAY-IN CEILING IS REMOVED AND IS TO
BECOME A "NO CEILING" ROOM, THE EXISTING
GYPSUM BOARD ABOVE PREVIOUSLY REMOVED
CEILING IS TO BE FULLY TAPED, FLOATED, TEXTURED
AND PAINTED TO MATCH EXISTING WALLS.
GENERAL NOTES - RENOVATION
1. EXISTING DOOR/FRAME ASSEMBLY TO REMAIN.
2. PROVIDE CARD READER.
3. PROVIDE ROOM SIGNAGE.
4. PROVIDE NEW FLOORING AND BASE AS SCHEDULED.
5. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE IN THIS ROOM THAT MAY REQUIRE MINOR
DEMOLITION, PATCHING AND REPAIR OF EXISTING
FLOOR SUBSTRATE, WALL OR MISCELLANEOUS
ASSEMBLIES.
6. PROVIDE 8'x4'x3/4" 'AC' FACED FIRE-RATED PLYWOOD
VERTICALLY ON ALL WALLS AS INDICATED. PAINT WITH 2
COATS MIN. FIRE-RATED PAINT. COORDINATE EXACT
LOCATION A.F.F. WITH TECHNOLOGY AND ELECTRICAL
DRAWINGS AND EXISTING CONDITIONS.
7. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE OF EXISTING AND NEW COMPONENTS AT
CEILING LEVEL.
8. EXISTING FLOOR AND BASE TO REMAIN. REPAIR AS
NECESSARY TO MATCH EXISTING CONDITIONS OR
BETTER.
9. EXISTING VCT FLOORING AND RUBBER BASE TO REMAIN.
10. LIMITED RENOVATION TO EXISTING CEILING ASSEMBLY
PER MEP AND TECHNOLOGY DRAWINGS WORK SCOPE.
11. RELOCATED EXISTING MARKER BOARD.
12. RELOCATED EXISTING MILLWORK.
13. CEILING FUR-DOWN ABOVE.
14. NEW GYPSUM BOARD/METAL STUD FRAMED FUR-DOWN
TO MATCH EXISTING HEIGHT. NO JOINTS
UNLESS NOTED OTHERWISE.
15. RELOCATED EXISTING LIGHT FIXTURE.
16. RELOCATED EXISTING TV MONITOR.
17. EXISTING ALUMINUM FLOOR AND WALL (EACH SIDE)
EXPANSION JOINT COVERS TO REMAIN.
18. EXISTING GYPSUM BOARD/METAL STUD FRAMED
FUR-DOWN TO REMAIN.
19. RELOCATED EXISTING FIRE EXTINGUISHER.
20. EXISTING EXTERIOR WINDOW TO REMAIN.
21. REINSTALL EXISTING SALVAGED WOOD BASE AND CHAIR
RAIL. PROVIDE BALANCE OF MATERIAL AS NEEDED TO
COMPLETE JOB. PAINT ALL BASE AND CHAIR RAIL IN
ENTIRE ROOM.
22. EXISTING PLASTER ON CMU TO UNDERSIDE OF EXISTING
STRUCTURE (4" OR 8" CMU PER WALL THICKNESS
DEPICTED GRAPHICALLY). FIRE-RATED WALL.
CONTRACTOR VERIFY.
23. EXISTING ROOM SIGNAGE.
24. EXISTING CARD READER.
25. REFERENCE DOOR SCHEDULE.
26. PAINT INTERIOR SIDE OF EXISTING WINDOW GLAZING
ONLY "FLAT BLACK".
27. REINSTALLED EXISTING ROOM SIGNAGE.
28. REINSTALLED EXISTING CARD READER.
29. PLASTER ASSEMBLY INFILL AT EXISTING WALL AS
DETAILED AT EXISTING WINDOW OPENING.
30. ENSURE EXISTING WALL VENT IS SECURELY CLOSED
SHUT PRIOR TO COVER-UP.
31. PROVIDE WALL PROTECTION TO MATCH EXISTING.
32. PROVIDE NEW CEILING AS SCHEDULED.
33. PROVIDE GYPSUM BOARD/STEEL STUD FRAMED
FUR-DOWN AS DETAILED.
34. PROVIDE 2' X 2' RAISED FLOOR SYSTEM AT 10" ABOVE
THE 4TH FLOOR LEVEL.
35. ELECTRICAL CONDUITS AND MECHANICAL PIPING PER
MEP DRAWINGS.
36. PROVIDE 5/8" GYPSUM BOARD WHERE EXISTING TILE
WAINSCOT AND SUBSTRATE WAS REMOVED. TEXTURE
AND FINISH TO MATCH EXISTING ADJACENT WALLS (4'-0"±
HIGH, LOCATE AS INDICATED BY HEAVY LINE).
37. TEXTURE AND FINISH EXISTING GYPSUM BOARD
SUBSTRATE TO MATCH EXISTING ADJACENT WALLS.
38. GYPSUM BOARD ASSEMBLY INFILL AS DETAILED AT
EXISTING WINDOW OPENING.
39. PROVIDE INFILL PER KEYED NOTE 29 AT VOID LEFT BY
HEATER REMOVED.
40. PROVIDE 1" THICK MINIMUM CONCRETE INFILL FLUSH
WITH EXISTING CONCRETE TOPPING WHERE PORTIONS
OF EXISTING CMU WALLS ARE REMOVED.
41. PROVIDE PAINTED WOOD CHAIR RAIL TO MATCH
EXISTING.
42. REINSTALLED EXISTING SHELF.
43. PROVIDE GYPSUM BOARD/METAL STUD FRAMED CHASE
FROM FLOORS ABOVE . MINIMIZE SIZE AND REFERENCE
MEP DRAWINGS FOR COMPONENTS TO BE IN CHASE.
44. RAMP AND RAILS BY RAISED FLOOR SYSTEM
MANUFACTURER.
45. ROOM PERIMETER WALLS TO BE FULLY SEALED TOP
AND BOTTOM ON BOTH SIDES OF WALL. EXTERIOR WALL
SEAL INTERIOR SIDE ONLY.
KEYED NOTES - RENOVATION
46. TEMPORARY ALUMINUM RAMP BY CONTRACTOR TO BE
RETURNED TO OWNER AT END OF JOB.
47. MODULAR BRICK INFILL ON EXTERIOR TO MATCH
EXISTING. TOOTH-IN AND MATCH MORTAR.
KEYED NOTES - RENOVATION (CONT.)
EXISTING WALL TO REMAIN
NEW WALL CONSTRUCTION
EXISTING DOOR/FRAME ASSEMBLY
TO REMAIN
EXISTING WINDOW ASSEMBLY
TO REMAIN
NEW WINDOW ASSEMBLY
NEW DOOR/FRAME ASSEMBLY
1 HR. FIRE-RATED WALL (EXISTING)
2 HR. FIRE-RATED WALL (EXISTING)
LEGEND - RENOVATION
FIRE-RATED WALL (NEW OR EXISTING
1 HOUR UNLESS NOTED OTHERWISE)
TRUE NORTH PLAN
NORTH
7' -2
1 25
8 9 8 98 9
A704A
A702A
8'-3"±
6' -2
20 26
38 30 X2B
X2C
X2B
X2B
X2C
X2B
EXIST.
INTERVIEW
A702
EXIST.
STORAGE
A704B
STORAGE
A702A
EXIST. SENSORY
THERAPY
A704
EXIST.
CORRIDOR
C*7*2
7'-4"±
STORAGE
A704A
1 STORAGE A702A & STORAGE A704A - ROOM RENOVATION
SCALE: 1/4" = 1'-0"
3 TELECOM ROOM A732A - ROOM RENOVATION
SCALE: 1/4" = 1'-0"
EXIST. OCCUPATIONAL
THERAPY
A732
EXIST.
CORRIDOR
C*7*1
15'-6"±
TELECOM
ROOM
A732A
A732A
A732
'-0
44 666
X1A
X1A
20 26 30
2 STORAGE A702A & STORAGE A704A - CEILING RENOVATION
SCALE: 1/4" = 1'-0"
EXIST.
INTERVIEW
A702
STORAGE
A702A
EXIST. SENSORY
THERAPY
A704
EXIST.
CORRIDOR
C*7*2
STORAGE
A704A
EXIST.
STORAGE
A704B
4 TELECOM ROOM A732A - CEILING RENOVATION
SCALE: 1/4" = 1'-0"
EXIST. OCCUPATIONAL
THERAPY
A732
EXIST.
CORRIDOR
C*7*1
TELECOM
ROOM
A732A
OD
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project Title
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
PhaseDrawing Title
Approved: Project Director
PROJECT MANAGEMENTCONSULTANTRevisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
FULLY SPRINKLERED
539-21-701
4-MAY-2022
100% CONSTRUCTION
DOCUMENTS
CINCINNATI VAMC EHRM
INFRASTRUCTURE UPGRADES
3200 VINE ST., CINCINNATI, OH
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
ETS
T
TA
GE
S
R I
E T E X
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJ
O
SE
P
H
7 6 22 1
5/4/22
AS-407-C.1.7
ENLARGED FLOOR PLAN -
SEVENTH FLOOR - RENOVATION
IAR
IAR, JFB
1. REFERENCE GENERAL NOTES ON SHEET GI-004.
2. UNLESS NOTED OTHERWISE, ALL EXISTING WALLS
ARE 5/8" GYPSUM BOARD/3 5/8"METAL STUD FRAMED
TO UNDERSIDE OF PRIMARY BUILDING FRAMING
STRUCTURE (1 HR. FIRE RATED - CONSTRUCTION
SIMILAR TO U.l. DESIGN NO. U465). CONTRACTOR TO
VERIFY.
3. UNLESS NOTED OTHERWISE, ALL EXISTING DOOR
ASSEMBLIES ARE SOLID CORE WOOD DOORS/HOLLOW
METAL FRAME TYPICAL (3'-0" X 7'-0").
4. UNLESS NOTED OTHERWISE ALL EXISTING LAY-IN
CEILING ASSEMBLIES ARE 2' X 2' STANDARD GRID WITH
FISSURED TILES AT 8'-0" A.F.F. TYPICAL.
5. UNLESS NOTED OTHERWISE, ALL EXISTING STEEL
COLUMN FUR-OUTS ARE GYPSUM BOARD/METAL STUD
FRAMED TYPICAL.
6. PARTIAL OR ENTIRE RECONSTRUCTION OF SOME
EXISTING CEILING ASSEMBLIES THOUGH OUT THE
ENTIRE BUILDING(S), ESPECIALLY IN CORRIDORS,
WILL BE NECESSARY. REFERENCE ALL DISCIPLINE
DEMOLITION DRAWINGS. RECONSTRUCTION IS TO
INCLUDE MISCELLANEOUS PATCHING /REPAIR TO
MATCH EXISTING OR BETTER CONDITIONS.
7. EXISTING FIRE-RATED WALL IDENTIFICATION
INDICATED ONLY FOR IMMEDIATE AFFECTED ROOM
WALLS. CONTRACTOR SHALL VERIFY FULL EXTENT OF
EXISTING FIRE-RATED WALLS AT ADJACENT AREAS.
8. ALL NEW WALLS SHALL BE PARTITION TYPE '1' UNLESS
OTHERWISE NOTED.
9. UNLESS NOTED OTHERWISE AT ALL ROOMS WHERE
EXISTING LAY-IN CEILING IS REMOVED AND IS TO
BECOME A "NO CEILING" ROOM, THE EXISTING
GYPSUM BOARD ABOVE PREVIOUSLY REMOVED
CEILING IS TO BE FULLY TAPED, FLOATED, TEXTURED
AND PAINTED TO MATCH EXISTING WALLS.
GENERAL NOTES - RENOVATION
1. EXISTING DOOR/FRAME ASSEMBLY TO REMAIN.
2. PROVIDE CARD READER.
3. PROVIDE ROOM SIGNAGE.
4. PROVIDE NEW FLOORING AND BASE AS SCHEDULED.
5. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE IN THIS ROOM THAT MAY REQUIRE MINOR
DEMOLITION, PATCHING AND REPAIR OF EXISTING
FLOOR SUBSTRATE, WALL OR MISCELLANEOUS
ASSEMBLIES.
6. PROVIDE 8'x4'x3/4" 'AC' FACED FIRE-RATED PLYWOOD
VERTICALLY ON ALL WALLS AS INDICATED. PAINT WITH 2
COATS MIN. FIRE-RATED PAINT. COORDINATE EXACT
LOCATION A.F.F. WITH TECHNOLOGY AND ELECTRICAL
DRAWINGS AND EXISTING CONDITIONS.
7. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE OF EXISTING AND NEW COMPONENTS AT
CEILING LEVEL.
8. EXISTING FLOOR AND BASE TO REMAIN. REPAIR AS
NECESSARY TO MATCH EXISTING CONDITIONS OR
BETTER.
9. EXISTING VCT FLOORING AND RUBBER BASE TO REMAIN.
10. LIMITED RENOVATION TO EXISTING CEILING ASSEMBLY
PER MEP AND TECHNOLOGY DRAWINGS WORK SCOPE.
11. RELOCATED EXISTING MARKER BOARD.
12. RELOCATED EXISTING MILLWORK.
13. CEILING FUR-DOWN ABOVE.
14. NEW GYPSUM BOARD/METAL STUD FRAMED FUR-DOWN
TO MATCH EXISTING HEIGHT. NO JOINTS
UNLESS NOTED OTHERWISE.
15. RELOCATED EXISTING LIGHT FIXTURE.
16. RELOCATED EXISTING TV MONITOR.
17. EXISTING ALUMINUM FLOOR AND WALL (EACH SIDE)
EXPANSION JOINT COVERS TO REMAIN.
18. EXISTING GYPSUM BOARD/METAL STUD FRAMED
FUR-DOWN TO REMAIN.
19. RELOCATED EXISTING FIRE EXTINGUISHER.
20. EXISTING EXTERIOR WINDOW TO REMAIN.
21. REINSTALL EXISTING SALVAGED WOOD BASE AND CHAIR
RAIL. PROVIDE BALANCE OF MATERIAL AS NEEDED TO
COMPLETE JOB. PAINT ALL BASE AND CHAIR RAIL IN
ENTIRE ROOM.
22. EXISTING PLASTER ON CMU TO UNDERSIDE OF EXISTING
STRUCTURE (4" OR 8" CMU PER WALL THICKNESS
DEPICTED GRAPHICALLY). FIRE-RATED WALL.
CONTRACTOR VERIFY.
23. EXISTING ROOM SIGNAGE.
24. EXISTING CARD READER.
25. REFERENCE DOOR SCHEDULE.
26. PAINT INTERIOR SIDE OF EXISTING WINDOW GLAZING
ONLY "FLAT BLACK".
27. REINSTALLED EXISTING ROOM SIGNAGE.
28. REINSTALLED EXISTING CARD READER.
29. PLASTER ASSEMBLY INFILL AT EXISTING WALL AS
DETAILED AT EXISTING WINDOW OPENING.
30. ENSURE EXISTING WALL VENT IS SECURELY CLOSED
SHUT PRIOR TO COVER-UP.
31. PROVIDE WALL PROTECTION TO MATCH EXISTING.
32. PROVIDE NEW CEILING AS SCHEDULED.
33. PROVIDE GYPSUM BOARD/STEEL STUD FRAMED
FUR-DOWN AS DETAILED.
34. PROVIDE 2' X 2' RAISED FLOOR SYSTEM AT 10" ABOVE
THE 4TH FLOOR LEVEL.
35. ELECTRICAL CONDUITS AND MECHANICAL PIPING PER
MEP DRAWINGS.
36. PROVIDE 5/8" GYPSUM BOARD WHERE EXISTING TILE
WAINSCOT AND SUBSTRATE WAS REMOVED. TEXTURE
AND FINISH TO MATCH EXISTING ADJACENT WALLS (4'-0"±
HIGH, LOCATE AS INDICATED BY HEAVY LINE).
37. TEXTURE AND FINISH EXISTING GYPSUM BOARD
SUBSTRATE TO MATCH EXISTING ADJACENT WALLS.
38. GYPSUM BOARD ASSEMBLY INFILL AS DETAILED AT
EXISTING WINDOW OPENING.
39. PROVIDE INFILL PER KEYED NOTE 29 AT VOID LEFT BY
HEATER REMOVED.
40. PROVIDE 1" THICK MINIMUM CONCRETE INFILL FLUSH
WITH EXISTING CONCRETE TOPPING WHERE PORTIONS
OF EXISTING CMU WALLS ARE REMOVED.
41. PROVIDE PAINTED WOOD CHAIR RAIL TO MATCH
EXISTING.
42. REINSTALLED EXISTING SHELF.
43. PROVIDE GYPSUM BOARD/METAL STUD FRAMED CHASE
FROM FLOORS ABOVE . MINIMIZE SIZE AND REFERENCE
MEP DRAWINGS FOR COMPONENTS TO BE IN CHASE.
44. RAMP AND RAILS BY RAISED FLOOR SYSTEM
MANUFACTURER.
45. ROOM PERIMETER WALLS TO BE FULLY SEALED TOP
AND BOTTOM ON BOTH SIDES OF WALL. EXTERIOR WALL
SEAL INTERIOR SIDE ONLY.
KEYED NOTES - RENOVATION
46. TEMPORARY ALUMINUM RAMP BY CONTRACTOR TO BE
RETURNED TO OWNER AT END OF JOB.
47. MODULAR BRICK INFILL ON EXTERIOR TO MATCH
EXISTING. TOOTH-IN AND MATCH MORTAR.
KEYED NOTES - RENOVATION (CONT.)
EXISTING WALL TO REMAIN
NEW WALL CONSTRUCTION
EXISTING DOOR/FRAME ASSEMBLY
TO REMAIN
EXISTING WINDOW ASSEMBLY
TO REMAIN
NEW WINDOW ASSEMBLY
NEW DOOR/FRAME ASSEMBLY
1 HR. FIRE-RATED WALL (EXISTING)
2 HR. FIRE-RATED WALL (EXISTING)
LEGEND - RENOVATION
FIRE-RATED WALL (NEW OR EXISTING
1 HOUR UNLESS NOTED OTHERWISE)
TRUE NORTH PLAN
NORTH
TRUE NORTH PLAN
NORTH
TRUE NORTH PLAN
NORTH
1 TELECOM ROOM A838 - ROOM RENOVATION
A838
15'-11"±
9' -7
8 9
20 26 30
X3B
X3B
TELECOM
ROOM
A838
EXIST.
WAITING
B801
EXIST.
CONFERENCE
A839EXIST.
CORRIDOR
C*8*1
2 TELECOM ROOM A838 - CEILING RENOVATION
SCALE: 1/4" = 1'-0"
TELECOM
ROOM
A838
EXIST.
WAITING
B801
EXIST.
CONFERENCE
A839EXIST.
CORRIDOR
C*8*1
OD OD
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project Title
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
PhaseDrawing Title
Approved: Project Director
PROJECT MANAGEMENTCONSULTANTRevisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
FULLY SPRINKLERED
539-21-701
4-MAY-2022
100% CONSTRUCTION
DOCUMENTS
CINCINNATI VAMC EHRM
INFRASTRUCTURE UPGRADES
3200 VINE ST., CINCINNATI, OH
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
ETS
T
TA
GE
S
R I
E T E X
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJ
O
SE
P
H
7 6 22 1
5/4/22
AS-408-C.1.8
ENLARGED FLOOR PLAN -
EIGHTH FLOOR - RENOVATION
IAR
IAR, JFB
1. REFERENCE GENERAL NOTES ON SHEET GI-004.
2. UNLESS NOTED OTHERWISE, ALL EXISTING WALLS
ARE 5/8" GYPSUM BOARD/3 5/8"METAL STUD FRAMED
TO UNDERSIDE OF PRIMARY BUILDING FRAMING
STRUCTURE (1 HR. FIRE RATED - CONSTRUCTION
SIMILAR TO U.l. DESIGN NO. U465). CONTRACTOR TO
VERIFY.
3. UNLESS NOTED OTHERWISE, ALL EXISTING DOOR
ASSEMBLIES ARE SOLID CORE WOOD DOORS/HOLLOW
METAL FRAME TYPICAL (3'-0" X 7'-0").
4. UNLESS NOTED OTHERWISE ALL EXISTING LAY-IN
CEILING ASSEMBLIES ARE 2' X 2' STANDARD GRID WITH
FISSURED TILES AT 8'-0" A.F.F. TYPICAL.
5. UNLESS NOTED OTHERWISE, ALL EXISTING STEEL
COLUMN FUR-OUTS ARE GYPSUM BOARD/METAL STUD
FRAMED TYPICAL.
6. PARTIAL OR ENTIRE RECONSTRUCTION OF SOME
EXISTING CEILING ASSEMBLIES THOUGH OUT THE
ENTIRE BUILDING(S), ESPECIALLY IN CORRIDORS,
WILL BE NECESSARY. REFERENCE ALL DISCIPLINE
DEMOLITION DRAWINGS. RECONSTRUCTION IS TO
INCLUDE MISCELLANEOUS PATCHING /REPAIR TO
MATCH EXISTING OR BETTER CONDITIONS.
7. EXISTING FIRE-RATED WALL IDENTIFICATION
INDICATED ONLY FOR IMMEDIATE AFFECTED ROOM
WALLS. CONTRACTOR SHALL VERIFY FULL EXTENT OF
EXISTING FIRE-RATED WALLS AT ADJACENT AREAS.
8. ALL NEW WALLS SHALL BE PARTITION TYPE '1' UNLESS
OTHERWISE NOTED.
9. UNLESS NOTED OTHERWISE AT ALL ROOMS WHERE
EXISTING LAY-IN CEILING IS REMOVED AND IS TO
BECOME A "NO CEILING" ROOM, THE EXISTING
GYPSUM BOARD ABOVE PREVIOUSLY REMOVED
CEILING IS TO BE FULLY TAPED, FLOATED, TEXTURED
AND PAINTED TO MATCH EXISTING WALLS.
GENERAL NOTES - RENOVATION
1. EXISTING DOOR/FRAME ASSEMBLY TO REMAIN.
2. PROVIDE CARD READER.
3. PROVIDE ROOM SIGNAGE.
4. PROVIDE NEW FLOORING AND BASE AS SCHEDULED.
5. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE IN THIS ROOM THAT MAY REQUIRE MINOR
DEMOLITION, PATCHING AND REPAIR OF EXISTING
FLOOR SUBSTRATE, WALL OR MISCELLANEOUS
ASSEMBLIES.
6. PROVIDE 8'x4'x3/4" 'AC' FACED FIRE-RATED PLYWOOD
VERTICALLY ON ALL WALLS AS INDICATED. PAINT WITH 2
COATS MIN. FIRE-RATED PAINT. COORDINATE EXACT
LOCATION A.F.F. WITH TECHNOLOGY AND ELECTRICAL
DRAWINGS AND EXISTING CONDITIONS.
7. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE OF EXISTING AND NEW COMPONENTS AT
CEILING LEVEL.
8. EXISTING FLOOR AND BASE TO REMAIN. REPAIR AS
NECESSARY TO MATCH EXISTING CONDITIONS OR
BETTER.
9. EXISTING VCT FLOORING AND RUBBER BASE TO REMAIN.
10. LIMITED RENOVATION TO EXISTING CEILING ASSEMBLY
PER MEP AND TECHNOLOGY DRAWINGS WORK SCOPE.
11. RELOCATED EXISTING MARKER BOARD.
12. RELOCATED EXISTING MILLWORK.
13. CEILING FUR-DOWN ABOVE.
14. NEW GYPSUM BOARD/METAL STUD FRAMED FUR-DOWN
TO MATCH EXISTING HEIGHT. NO JOINTS
UNLESS NOTED OTHERWISE.
15. RELOCATED EXISTING LIGHT FIXTURE.
16. RELOCATED EXISTING TV MONITOR.
17. EXISTING ALUMINUM FLOOR AND WALL (EACH SIDE)
EXPANSION JOINT COVERS TO REMAIN.
18. EXISTING GYPSUM BOARD/METAL STUD FRAMED
FUR-DOWN TO REMAIN.
19. RELOCATED EXISTING FIRE EXTINGUISHER.
20. EXISTING EXTERIOR WINDOW TO REMAIN.
21. REINSTALL EXISTING SALVAGED WOOD BASE AND CHAIR
RAIL. PROVIDE BALANCE OF MATERIAL AS NEEDED TO
COMPLETE JOB. PAINT ALL BASE AND CHAIR RAIL IN
ENTIRE ROOM.
22. EXISTING PLASTER ON CMU TO UNDERSIDE OF EXISTING
STRUCTURE (4" OR 8" CMU PER WALL THICKNESS
DEPICTED GRAPHICALLY). FIRE-RATED WALL.
CONTRACTOR VERIFY.
23. EXISTING ROOM SIGNAGE.
24. EXISTING CARD READER.
25. REFERENCE DOOR SCHEDULE.
26. PAINT INTERIOR SIDE OF EXISTING WINDOW GLAZING
ONLY "FLAT BLACK".
27. REINSTALLED EXISTING ROOM SIGNAGE.
28. REINSTALLED EXISTING CARD READER.
29. PLASTER ASSEMBLY INFILL AT EXISTING WALL AS
DETAILED AT EXISTING WINDOW OPENING.
30. ENSURE EXISTING WALL VENT IS SECURELY CLOSED
SHUT PRIOR TO COVER-UP.
31. PROVIDE WALL PROTECTION TO MATCH EXISTING.
32. PROVIDE NEW CEILING AS SCHEDULED.
33. PROVIDE GYPSUM BOARD/STEEL STUD FRAMED
FUR-DOWN AS DETAILED.
34. PROVIDE 2' X 2' RAISED FLOOR SYSTEM AT 10" ABOVE
THE 4TH FLOOR LEVEL.
35. ELECTRICAL CONDUITS AND MECHANICAL PIPING PER
MEP DRAWINGS.
36. PROVIDE 5/8" GYPSUM BOARD WHERE EXISTING TILE
WAINSCOT AND SUBSTRATE WAS REMOVED. TEXTURE
AND FINISH TO MATCH EXISTING ADJACENT WALLS (4'-0"±
HIGH, LOCATE AS INDICATED BY HEAVY LINE).
37. TEXTURE AND FINISH EXISTING GYPSUM BOARD
SUBSTRATE TO MATCH EXISTING ADJACENT WALLS.
38. GYPSUM BOARD ASSEMBLY INFILL AS DETAILED AT
EXISTING WINDOW OPENING.
39. PROVIDE INFILL PER KEYED NOTE 29 AT VOID LEFT BY
HEATER REMOVED.
40. PROVIDE 1" THICK MINIMUM CONCRETE INFILL FLUSH
WITH EXISTING CONCRETE TOPPING WHERE PORTIONS
OF EXISTING CMU WALLS ARE REMOVED.
41. PROVIDE PAINTED WOOD CHAIR RAIL TO MATCH
EXISTING.
42. REINSTALLED EXISTING SHELF.
43. PROVIDE GYPSUM BOARD/METAL STUD FRAMED CHASE
FROM FLOORS ABOVE . MINIMIZE SIZE AND REFERENCE
MEP DRAWINGS FOR COMPONENTS TO BE IN CHASE.
44. RAMP AND RAILS BY RAISED FLOOR SYSTEM
MANUFACTURER.
45. ROOM PERIMETER WALLS TO BE FULLY SEALED TOP
AND BOTTOM ON BOTH SIDES OF WALL. EXTERIOR WALL
SEAL INTERIOR SIDE ONLY.
KEYED NOTES - RENOVATION
46. TEMPORARY ALUMINUM RAMP BY CONTRACTOR TO BE
RETURNED TO OWNER AT END OF JOB.
47. MODULAR BRICK INFILL ON EXTERIOR TO MATCH
EXISTING. TOOTH-IN AND MATCH MORTAR.
KEYED NOTES - RENOVATION (CONT.)
EXISTING WALL TO REMAIN
NEW WALL CONSTRUCTION
EXISTING DOOR/FRAME ASSEMBLY
TO REMAIN
EXISTING WINDOW ASSEMBLY
TO REMAIN
NEW WINDOW ASSEMBLY
NEW DOOR/FRAME ASSEMBLY
1 HR. FIRE-RATED WALL (EXISTING)
2 HR. FIRE-RATED WALL (EXISTING)
LEGEND - RENOVATION
FIRE-RATED WALL (NEW OR EXISTING
1 HOUR UNLESS NOTED OTHERWISE)
TRUE NORTH PLAN
NORTH
TELECOM
ROOM
A916A
EXIST.
PSYCH. OFFICE
A919B
EXIST.
ELECTRIC
A916D
EXIST.
HAC
A915B
EXIST.
SERVICE LOBBY
A916
14'-8 1/4"±
8' -7
5'
-1 1"
8'-3 3/4"±
A916A
66 3
A916D
1 TELECOM ROOM A916A - ROOM RENOVATION
SCALE: 1/4" = 1'-0"
X1A X1
X1A
X1B X1B
EXIST.
PSYCH. OFFICE
A919B
EXIST.
ELECTRIC
A916D
EXIST.
HAC
A915B
EXIST.
SERVICE LOBBY
A916
TELECOM
ROOM
A916A
2 TELECOM ROOM A916A - CEILING RENOVATION
SCALE: 1/4" = 1'-0"
7 3332
OD
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project Title
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
PhaseDrawing Title
Approved: Project Director
PROJECT MANAGEMENTCONSULTANTRevisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
FULLY SPRINKLERED
539-21-701
4-MAY-2022
100% CONSTRUCTION
DOCUMENTS
CINCINNATI VAMC EHRM
INFRASTRUCTURE UPGRADES
3200 VINE ST., CINCINNATI, OH
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
ETS
T
TA
GE
S
R I
E T E X
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJO
S
EP
H
7 6 22 1
5/4/22
AS-409-C.1.9
ENLARGED FLOOR PLANS -
9TH FLOOR RENOVATION
IAR
C1
1. REFERENCE GENERAL NOTES ON SHEET GI-004.
2. UNLESS NOTED OTHERWISE, ALL EXISTING WALLS
ARE 5/8" GYPSUM BOARD/3 5/8"METAL STUD FRAMED
TO UNDERSIDE OF PRIMARY BUILDING FRAMING
STRUCTURE (1 HR. FIRE RATED - CONSTRUCTION
SIMILAR TO U.l. DESIGN NO. U465). CONTRACTOR TO
VERIFY.
3. UNLESS NOTED OTHERWISE, ALL EXISTING DOOR
ASSEMBLIES ARE SOLID CORE WOOD DOORS/HOLLOW
METAL FRAME TYPICAL (3'-0" X 7'-0").
4. UNLESS NOTED OTHERWISE ALL EXISTING LAY-IN
CEILING ASSEMBLIES ARE 2' X 2' STANDARD GRID WITH
FISSURED TILES AT 8'-0" A.F.F. TYPICAL.
5. UNLESS NOTED OTHERWISE, ALL EXISTING STEEL
COLUMN FUR-OUTS ARE GYPSUM BOARD/METAL STUD
FRAMED TYPICAL.
6. PARTIAL OR ENTIRE RECONSTRUCTION OF SOME
EXISTING CEILING ASSEMBLIES THOUGH OUT THE
ENTIRE BUILDING(S), ESPECIALLY IN CORRIDORS,
WILL BE NECESSARY. REFERENCE ALL DISCIPLINE
DEMOLITION DRAWINGS. RECONSTRUCTION IS TO
INCLUDE MISCELLANEOUS PATCHING /REPAIR TO
MATCH EXISTING OR BETTER CONDITIONS.
7. EXISTING FIRE-RATED WALL IDENTIFICATION
INDICATED ONLY FOR IMMEDIATE AFFECTED ROOM
WALLS. CONTRACTOR SHALL VERIFY FULL EXTENT OF
EXISTING FIRE-RATED WALLS AT ADJACENT AREAS.
8. ALL NEW WALLS SHALL BE PARTITION TYPE '1' UNLESS
OTHERWISE NOTED.
9. UNLESS NOTED OTHERWISE AT ALL ROOMS WHERE
EXISTING LAY-IN CEILING IS REMOVED AND IS TO
BECOME A "NO CEILING" ROOM, THE EXISTING
GYPSUM BOARD ABOVE PREVIOUSLY REMOVED
CEILING IS TO BE FULLY TAPED, FLOATED, TEXTURED
AND PAINTED TO MATCH EXISTING WALLS.
GENERAL NOTES - RENOVATION
1. EXISTING DOOR/FRAME ASSEMBLY TO REMAIN.
2. PROVIDE CARD READER.
3. PROVIDE ROOM SIGNAGE.
4. PROVIDE NEW FLOORING AND BASE AS SCHEDULED.
5. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE IN THIS ROOM THAT MAY REQUIRE MINOR
DEMOLITION, PATCHING AND REPAIR OF EXISTING
FLOOR SUBSTRATE, WALL OR MISCELLANEOUS
ASSEMBLIES.
6. PROVIDE 8'x4'x3/4" 'AC' FACED FIRE-RATED PLYWOOD
VERTICALLY ON ALL WALLS AS INDICATED. PAINT WITH 2
COATS MIN. FIRE-RATED PAINT. COORDINATE EXACT
LOCATION A.F.F. WITH TECHNOLOGY AND ELECTRICAL
DRAWINGS AND EXISTING CONDITIONS.
7. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE OF EXISTING AND NEW COMPONENTS AT
CEILING LEVEL.
8. EXISTING FLOOR AND BASE TO REMAIN. REPAIR AS
NECESSARY TO MATCH EXISTING CONDITIONS OR
BETTER.
9. EXISTING VCT FLOORING AND RUBBER BASE TO REMAIN.
10. LIMITED RENOVATION TO EXISTING CEILING ASSEMBLY
PER MEP AND TECHNOLOGY DRAWINGS WORK SCOPE.
11. RELOCATED EXISTING MARKER BOARD.
12. RELOCATED EXISTING MILLWORK.
13. CEILING FUR-DOWN ABOVE.
14. NEW GYPSUM BOARD/METAL STUD FRAMED FUR-DOWN
TO MATCH EXISTING HEIGHT. NO JOINTS
UNLESS NOTED OTHERWISE.
15. RELOCATED EXISTING LIGHT FIXTURE.
16. RELOCATED EXISTING TV MONITOR.
17. EXISTING ALUMINUM FLOOR AND WALL (EACH SIDE)
EXPANSION JOINT COVERS TO REMAIN.
18. EXISTING GYPSUM BOARD/METAL STUD FRAMED
FUR-DOWN TO REMAIN.
19. RELOCATED EXISTING FIRE EXTINGUISHER.
20. EXISTING EXTERIOR WINDOW TO REMAIN.
21. REINSTALL EXISTING SALVAGED WOOD BASE AND CHAIR
RAIL. PROVIDE BALANCE OF MATERIAL AS NEEDED TO
COMPLETE JOB. PAINT ALL BASE AND CHAIR RAIL IN
ENTIRE ROOM.
22. EXISTING PLASTER ON CMU TO UNDERSIDE OF EXISTING
STRUCTURE (4" OR 8" CMU PER WALL THICKNESS
DEPICTED GRAPHICALLY). FIRE-RATED WALL.
CONTRACTOR VERIFY.
23. EXISTING ROOM SIGNAGE.
24. EXISTING CARD READER.
25. REFERENCE DOOR SCHEDULE.
26. PAINT INTERIOR SIDE OF EXISTING WINDOW GLAZING
ONLY "FLAT BLACK".
27. REINSTALLED EXISTING ROOM SIGNAGE.
28. REINSTALLED EXISTING CARD READER.
29. PLASTER ASSEMBLY INFILL AT EXISTING WALL AS
DETAILED AT EXISTING WINDOW OPENING.
30. ENSURE EXISTING WALL VENT IS SECURELY CLOSED
SHUT PRIOR TO COVER-UP.
31. PROVIDE WALL PROTECTION TO MATCH EXISTING.
32. PROVIDE NEW CEILING AS SCHEDULED.
33. PROVIDE GYPSUM BOARD/STEEL STUD FRAMED
FUR-DOWN AS DETAILED.
34. PROVIDE 2' X 2' RAISED FLOOR SYSTEM AT 10" ABOVE
THE 4TH FLOOR LEVEL.
35. ELECTRICAL CONDUITS AND MECHANICAL PIPING PER
MEP DRAWINGS.
36. PROVIDE 5/8" GYPSUM BOARD WHERE EXISTING TILE
WAINSCOT AND SUBSTRATE WAS REMOVED. TEXTURE
AND FINISH TO MATCH EXISTING ADJACENT WALLS (4'-0"±
HIGH, LOCATE AS INDICATED BY HEAVY LINE).
37. TEXTURE AND FINISH EXISTING GYPSUM BOARD
SUBSTRATE TO MATCH EXISTING ADJACENT WALLS.
38. GYPSUM BOARD ASSEMBLY INFILL AS DETAILED AT
EXISTING WINDOW OPENING.
39. PROVIDE INFILL PER KEYED NOTE 29 AT VOID LEFT BY
HEATER REMOVED.
40. PROVIDE 1" THICK MINIMUM CONCRETE INFILL FLUSH
WITH EXISTING CONCRETE TOPPING WHERE PORTIONS
OF EXISTING CMU WALLS ARE REMOVED.
41. PROVIDE PAINTED WOOD CHAIR RAIL TO MATCH
EXISTING.
42. REINSTALLED EXISTING SHELF.
43. PROVIDE GYPSUM BOARD/METAL STUD FRAMED CHASE
FROM FLOORS ABOVE . MINIMIZE SIZE AND REFERENCE
MEP DRAWINGS FOR COMPONENTS TO BE IN CHASE.
44. RAMP AND RAILS BY RAISED FLOOR SYSTEM
MANUFACTURER.
45. ROOM PERIMETER WALLS TO BE FULLY SEALED TOP
AND BOTTOM ON BOTH SIDES OF WALL. EXTERIOR WALL
SEAL INTERIOR SIDE ONLY.
KEYED NOTES - RENOVATION
46. TEMPORARY ALUMINUM RAMP BY CONTRACTOR TO BE
RETURNED TO OWNER AT END OF JOB.
47. MODULAR BRICK INFILL ON EXTERIOR TO MATCH
EXISTING. TOOTH-IN AND MATCH MORTAR.
KEYED NOTES - RENOVATION (CONT.)
EXISTING WALL TO REMAIN
NEW WALL CONSTRUCTION
EXISTING DOOR/FRAME ASSEMBLY
TO REMAIN
EXISTING WINDOW ASSEMBLY
TO REMAIN
NEW WINDOW ASSEMBLY
NEW DOOR/FRAME ASSEMBLY
1 HR. FIRE-RATED WALL (EXISTING)
2 HR. FIRE-RATED WALL (EXISTING)
LEGEND - RENOVATION
FIRE-RATED WALL (NEW OR EXISTING
1 HOUR UNLESS NOTED OTHERWISE)
TRUE NORTH PLAN
NORTH
ROOM
EXIST. ELEVATOR
MACHINE ROOM
EXIST.
CORRIDOR
C*B*2
EXIST.
TELECOM
EXIST.
BREAK ROOM
EXIST.
CORRIDOR
C*B*3
12'-8 5/8"±
12'-2"±
8' -2
/4
15'-7"±
000166
1 TELECOM ROOM 0001 - ROOM RENOVATION
SCALE: 1/4" = 1'-0"
X2
X2X5
X5
2 3
EXIST. ELEVATOR
MACHINE ROOM
EXIST.
CORRIDOR
C*B*2
EXIST.
TELECOM
EXIST.
BREAK ROOM
EXIST.
CORRIDOR
C*B*3
TELECOM
ROOM
2 TELECOM ROOM 0001 - CEILING RENOVATION
SCALE: 1/4" = 1'-0"
OD
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project Title
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
PhaseDrawing Title
Approved: Project Director
PROJECT MANAGEMENTCONSULTANTRevisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
FULLY SPRINKLERED
539-21-701
4-MAY-2022
100% CONSTRUCTION
DOCUMENTS
CINCINNATI VAMC EHRM
INFRASTRUCTURE UPGRADES
3200 VINE ST., CINCINNATI, OH
8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
ETS
T
TA
GE
S
R I
E T E X
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJO
S
EP
H
7 6 22 1
5/4/22
AS-440-C.2.B
ENLARGED FLOOR PLANS -
BASEMENT FLOOR RENOVATION
IAR
C2
1. REFERENCE GENERAL NOTES ON SHEET GI-004.
2. UNLESS NOTED OTHERWISE, ALL EXISTING WALLS
ARE 5/8" GYPSUM BOARD/3 5/8"METAL STUD FRAMED
TO UNDERSIDE OF PRIMARY BUILDING FRAMING
STRUCTURE (1 HR. FIRE RATED - CONSTRUCTION
SIMILAR TO U.l. DESIGN NO. U465). CONTRACTOR TO
VERIFY.
3. UNLESS NOTED OTHERWISE, ALL EXISTING DOOR
ASSEMBLIES ARE SOLID CORE WOOD DOORS/HOLLOW
METAL FRAME TYPICAL (3'-0" X 7'-0").
4. UNLESS NOTED OTHERWISE ALL EXISTING LAY-IN
CEILING ASSEMBLIES ARE 2' X 2' STANDARD GRID WITH
FISSURED TILES AT 8'-0" A.F.F. TYPICAL.
5. UNLESS NOTED OTHERWISE, ALL EXISTING STEEL
COLUMN FUR-OUTS ARE GYPSUM BOARD/METAL STUD
FRAMED TYPICAL.
6. PARTIAL OR ENTIRE RECONSTRUCTION OF SOME
EXISTING CEILING ASSEMBLIES THOUGH OUT THE
ENTIRE BUILDING(S), ESPECIALLY IN CORRIDORS,
WILL BE NECESSARY. REFERENCE ALL DISCIPLINE
DEMOLITION DRAWINGS. RECONSTRUCTION IS TO
INCLUDE MISCELLANEOUS PATCHING /REPAIR TO
MATCH EXISTING OR BETTER CONDITIONS.
7. EXISTING FIRE-RATED WALL IDENTIFICATION
INDICATED ONLY FOR IMMEDIATE AFFECTED ROOM
WALLS. CONTRACTOR SHALL VERIFY FULL EXTENT OF
EXISTING FIRE-RATED WALLS AT ADJACENT AREAS.
8. ALL NEW WALLS SHALL BE PARTITION TYPE '1' UNLESS
OTHERWISE NOTED.
9. UNLESS NOTED OTHERWISE AT ALL ROOMS WHERE
EXISTING LAY-IN CEILING IS REMOVED AND IS TO
BECOME A "NO CEILING" ROOM, THE EXISTING
GYPSUM BOARD ABOVE PREVIOUSLY REMOVED
CEILING IS TO BE FULLY TAPED, FLOATED, TEXTURED
AND PAINTED TO MATCH EXISTING WALLS.
GENERAL NOTES - RENOVATION
1. EXISTING DOOR/FRAME ASSEMBLY TO REMAIN.
2. PROVIDE CARD READER.
3. PROVIDE ROOM SIGNAGE.
4. PROVIDE NEW FLOORING AND BASE AS SCHEDULED.
5. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE IN THIS ROOM THAT MAY REQUIRE MINOR
DEMOLITION, PATCHING AND REPAIR OF EXISTING
FLOOR SUBSTRATE, WALL OR MISCELLANEOUS
ASSEMBLIES.
6. PROVIDE 8'x4'x3/4" 'AC' FACED FIRE-RATED PLYWOOD
VERTICALLY ON ALL WALLS AS INDICATED. PAINT WITH 2
COATS MIN. FIRE-RATED PAINT. COORDINATE EXACT
LOCATION A.F.F. WITH TECHNOLOGY AND ELECTRICAL
DRAWINGS AND EXISTING CONDITIONS.
7. REFERENCE MEP AND TECHNOLOGY DRAWINGS FOR
WORK SCOPE OF EXISTING AND…