ATTACHMENT 12 - Drawings 11 of 13.pdf

PDF 17 MB Posted

Attached to
36C77623B0005 EHRM Infrastructure Upgrades - Cincinnati Project #539-21-701
Solicitation number
36C77623B0005
Issued by

About this file

This document provides details on a federal solicitation and related file. The solicitation number 36C77623B0005 is for the Construction of the EHRM Infrastructure Upgrades at the Cincinnati VAMC, Project #539-21-701. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin for an opportunity type of Solicitation. Attachment 12 - Drawings 11 of 13.pdf is the name of the related file, though its content is not specified. The solicitation is for infrastructure upgrade construction services at the Cincinnati VAMC to be provided under Project #539-21-701.

View the file

Other files

File Type Posted
36C77623B0005 0004 - Extension 3-10-23.pdf PDF
Technical Questions and Answers - Cincinnati EHRM.pdf PDF
36C77623B0005 0003.pdf PDF
36C77623B0005 0002 - EHRM Infrastructure Upgrades - Cincinnati.pdf PDF
Site Visit Sign-In Sheet - 36C77632B0005 EHRM Infrastructure Construction - Cincinnati VAMC.pdf PDF
ATTACHMENT 24 - Construction Wage Rates - Hamilton 01-13-2023.pdf PDF
36C77623B0005 0001 - EHRM Infrastructure Upgrades - Cincinnati.pdf PDF
Site Visit Memorandum.pdf PDF
ATTACHMENT 4 - Drawings 3 of 13.pdf PDF
ATTACHMENT 23 - Contractor Safety - Environmental Form.pdf PDF
ATTACHMENT 6 - Drawings 5 of 13.pdf PDF
ATTACHMENT 18 - Technology Narrative.pdf PDF
ATTACHMENT 13 - Drawings 12 of 13.pdf PDF
ATTACHMENT 15 - Plumbing Narrative.pdf PDF
ATTACHMENT 19 - Hazardous Materials Inspection Report.pdf PDF
ATTACHMENT 24 - Construction Wage Rates - Hamilton 1-13-2022.pdf PDF
ATTACHMENT 21 - COVID-19 Safety Protocols 12-14-21.pdf PDF
ATTACHMENT 14 - Drawings 13 of 13.pdf PDF
ATTACHMENT 20 - Brand Name Justification.pdf PDF
ATTACHMENT 22 - Limitations on Subcontracting - Nov 2022.pdf PDF
ATTACHMENT 9 - Drawings 8 of 13.pdf PDF
ATTACHMENT 10 - Drawings 9 of 13.pdf PDF
ATTACHMENT 16 - Mechanical Narrative.pdf PDF
ATTACHMENT 7 - Drawings 6 of 13.pdf PDF
ATTACHMENT 3 - Drawings 2 of 13.pdf PDF
ATTACHMENT 17 - Electrical Narrative.pdf PDF
ATTACHMENT 2 - Drawings 1 of 13.pdf PDF
ATTACHMENT 25 - Site Visit Instructions.pdf PDF
ATTACHMENT 8 - Drawings 7 of 13.pdf PDF
ATTACHMENT 11 - Drawings 10 of 13.pdf PDF
ATTACHMENT 5 - Drawings 4 of 13.pdf PDF
36C77623B0005 Solicitation - Cincinnati EHRM.pdf PDF
ATTACHMENT 1 - Specifications.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

UP

DN

DN

1 Bed Rm.

Tlt.

310A

1 Bed Rm.

Dining Recreation

Nour/Kit

Stor.

302A k Rm.

Stair #3 S*3*3

Mech.

311B

Tlt.

311A

Lounge/Lockers 311C

Office

Elec. Cl.

Signal

2 Bed Rm.

Tlt.

314A

2 Bed Rm.

Tlt.

316A

1 Bed Rm.

Mech.

318A

2 Bed Rm.

Tlt.

320A

2 Bed Rm.

2 Bed Rm.

Tlt.

317A

2 Bed Rm.

3 Bed Rm.

321 Tlt.

321A

2 Bed Rm.

Tlt.

328A 2 Bed Rm.

Tlt.

332A

2 Bed Rm.

2 Bed Rm.

Tlt.

334A

2 Bed Rm.

2 Bed Rm.

Tlt.

338A

2 Bed Room

Stair #5 S*3*5

Quiet Rm.

Resp. Ther.

Elec.

Equip.

343 Laun.

Mech.

341A

Signal

Bath

Congregate B.

Stair #4 S*3*4

Linen

Hac

Tlt.

Soil. Util.

Linen Rm.

Ice Machine

Stor.

339A

Linen Chute 368C

Office 313A

Elect.

339B

Elect.

M

AT

C H

L

IN

E

EXIST. NURSE

STATION

TELECOM

ROOM

M

AT

C H

L

IN

E

C

C

CC

C

KEYED NOTES

1. BACKBONE RISER CEILING PENETRATION

2. FIREWALL PENETRATION

3. 12 INCH X 4 INCH WIRE MESH CABLE TRAY

4. 18 INCH X 4 INCH WIRE MESH CABLE TRAY

5. 24 INCH X 4 INCH WIRE MESH CABLE TRAY

6. SLEEVES IN FLOOR ABOVE.

7. (2) 4" DIAMETER SLEEVES

8. (2) 2" DIAMETER SLEEVES

9. (2) 1-1/2" DIAMETER SLEEVES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TN-273-F.64.3N

BLDG. 64 - THIRD FLOOR - NORTH

TECHNOLOGY DATA OUTLET PLAN

RMJr

1 FLOOR PLAN - BLDG. 64 - THIRD FLOOR NORTH

SCALE: 1/8" = 1'-0"

1 2

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

2. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR

BEFORE BEGINNING DRILLING.

3. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY

SPARE RISER SLEEVES. REFER TO SECTION 07 84 00

FIRESTOPPING.

4. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND

CABLE TRAY PLUS 50%.

5. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE

TRAY WITHOUT DAMAGING OR DEFORMING THE CABLE.

6. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS

IN THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING

REMOVED FROM ANY WALL MOUNT EQUIPMENT UNLESS

OTHERWISE NOTED. TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES

WITH NEW CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE SPECIFICATIONS. NEW

MODULAR JACKS SHALL BE OF THE SAME MANUFACTURER AS

THE FACE PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND EXISTING

RE-TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 08 00.

KEY PLAN

04-MAY-22

DN DN

DN

Stair #1 S*3*1

Classrm./Conf.

2 Bed Rm.

Tlt.

367A

Signal 367B

2 Bed Rm.

Corridor C*3*1

Clin. Spec.

02 Stor.

2 Bed Rm.

Tlt.

363A

2 Bed Rm.

2 Bed Rm.

Tlt.

361A

2 Bed Rm.

Tlt.

357A

2 Bed Rm.

Mech.

371A

Office

Elec. Cl.

Equip.

Stair #2 S*3*2

Signal

Bath 364 Congregate

B.

Ward Supply

Clean Util.

Soil. Util.

Tlt.

Hac

Ward Supply

2 Bed Rm.

2 Bed Rm.

Tlt.

349A Mech.

347A

2 Bed Rm.

Tlt.

345A

2 Bed Rm.

Tlt.

306A

2 Bed Rm.

Tlt.

350A

3 Bed Rm.

2 Bed Rm.

Tlt.

346A

2 Bed Rm.

Corridor C*3*2

Equip.

Head Nurse

Tlt.

308A

1 Bed Rm.

1 Bed Rm.

Tl

Dining Recreation

Tlt.

302B

Nour/Kit

Nurses Station

Off.

307A

Work Rm.

Stair #3 S*3*3

Mech.

311B

T

Lounge/Loc 311C

Elect.

368B

Elect.

368A

Linen Chute 368C

M

AT

C H

L

IN

E M

AT

C

H L

IN

E

C

C

C

C

C

C

KEYED NOTES

1. BACKBONE RISER CEILING PENETRATION

2. FIREWALL PENETRATION

3. 12 INCH X 4 INCH WIRE MESH CABLE TRAY

4. 18 INCH X 4 INCH WIRE MESH CABLE TRAY

5. 24 INCH X 4 INCH WIRE MESH CABLE TRAY

6. SLEEVES IN FLOOR ABOVE.

7. (2) 4" DIAMETER SLEEVES

8. (2) 2" DIAMETER SLEEVES

9. (2) 1-1/2" DIAMETER SLEEVES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TN-273-F.64.3S

BLDG. 64 - THIRD FLOOR - SOUTH

TECHNOLOGY DATA OUTLET PLAN

RMJr

1 FLOOR PLAN - BLDG. 64 - THIRD FLOOR SOUTH

SCALE: 1/8" = 1'-0"

1 2

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

2. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR

BEFORE BEGINNING DRILLING.

3. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY

SPARE RISER SLEEVES. REFER TO SECTION 07 84 00

FIRESTOPPING.

4. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND

CABLE TRAY PLUS 50%.

5. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE

TRAY WITHOUT DAMAGING OR DEFORMING THE CABLE.

6. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS

IN THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING

REMOVED FROM ANY WALL MOUNT EQUIPMENT UNLESS

OTHERWISE NOTED. TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES

WITH NEW CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE SPECIFICATIONS. NEW

MODULAR JACKS SHALL BE OF THE SAME MANUFACTURER AS

THE FACE PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND EXISTING

RE-TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 08 00.

UP

Garage

Office

Restroom

Garage

Fuel Pump

Storage 106A

Stairs

Tools 103A

Garage

Storage

Shed

CATEGORY 6A CABLE

ROUTED THROUGH

ATTIC ON J-HOOKS

RACK WALL

MOUNTED

EXISTING DATA CABLES ROUTED TO BLDG.64-RM034

KEYED NOTES

1. BACKBONE RISER CEILING PENETRATION

2. FIREWALL PENETRATION

3. 12 INCH X 4 INCH WIRE MESH CABLE TRAY

4. 18 INCH X 4 INCH WIRE MESH CABLE TRAY

5. 24 INCH X 4 INCH WIRE MESH CABLE TRAY

6. SLEEVES IN FLOOR ABOVE.

7. (2) 4" DIAMETER SLEEVES

8. (2) 2" DIAMETER SLEEVES

9. (2) 1-1/2" DIAMETER SLEEVES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

TN-275-F.117.1

BLDG. 117 - FIRST FLOOR

TECHNOLOGY DATA OUTLET PLAN

RMJr

1 FLOOR PLAN - BLDG. 117 - FIRST FLOOR

SCALE: 1/8" = 1'-0"

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

2. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR

BEFORE BEGINNING DRILLING.

3. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY

SPARE RISER SLEEVES. REFER TO SECTION 07 84 00

FIRESTOPPING.

4. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND

CABLE TRAY PLUS 50%.

5. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE

TRAY WITHOUT DAMAGING OR DEFORMING THE CABLE.

6. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS

IN THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING

REMOVED FROM ANY WALL MOUNT EQUIPMENT UNLESS

OTHERWISE NOTED. TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES

WITH NEW CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE SPECIFICATIONS. NEW

MODULAR JACKS SHALL BE OF THE SAME MANUFACTURER AS

THE FACE PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND EXISTING

RE-TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 08 00.

CLOSET

C

LO

SE

T

TOILET

C

LO

SE

T

TELECOM

ROOM

XXX

# SF

TN-280-C.TB.1

BLDG. TB - EDUCATION TRAILER

TECHNOLOGY DEMO PLAN

RMJr

TB

1 FLOOR PLAN - BLDG. TB - EDUCATION TRAILER

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

2. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR

BEFORE BEGINNING DRILLING.

3. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY

SPARE RISER SLEEVES. REFER TO SECTION 07 84 00

FIRESTOPPING.

4. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND

CABLE TRAY PLUS 50%.

5. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE

TRAY WITHOUT DAMAGING OR DEFORMING THE CABLE.

6. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS

IN THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING

REMOVED FROM ANY WALL MOUNT EQUIPMENT UNLESS

OTHERWISE NOTED. TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES

WITH NEW CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE SPECIFICATIONS. NEW

MODULAR JACKS SHALL BE OF THE SAME MANUFACTURER AS

THE FACE PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND EXISTING

RE-TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 08 00.

KEY PLAN

KEYED NOTES

1. BACKBONE RISER CEILING PENETRATION

2. FIREWALL PENETRATION

3. 12 INCH X 4 INCH WIRE MESH CABLE TRAY

4. 18 INCH X 4 INCH WIRE MESH CABLE TRAY

5. 24 INCH X 4 INCH WIRE MESH CABLE TRAY

6. SLEEVES IN FLOOR ABOVE.

7. (2) 4" DIAMETER SLEEVES

8. (2) 2" DIAMETER SLEEVES

9. (2) 1-1/2" DIAMETER SLEEVES

CONFERENCE

TELECOM

ROOM

105A

OFFICE

OFFICE

OFFICE

C O

R R

ID

O

R

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

TOILET

TN-282-C.TE.1

BLDG. TE - RESEARCH TRAILER

TECHNOLOGY DATA OUTLET PLAN

RMJr

TE

1 FLOOR PLAN - BLDG. TE - RESEARCH TRAILER

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE

SIZE AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

2. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR

BEFORE BEGINNING DRILLING.

3. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY

SPARE RISER SLEEVES. REFER TO SECTION 07 84 00

FIRESTOPPING.

4. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE

TRAY ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR

BACKBONE CABLE SUPPORT AS INDICATED ON THE PLANS. THE

CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND

CABLE TRAY PLUS 50%.

5. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE

TRAY WITHOUT DAMAGING OR DEFORMING THE CABLE.

6. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON

EACH FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS

STRUCTURED CABLING.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS WHERE THERE IS NO

CABLE TRAY OR COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A PATCH PANELS

IN THE TELECOMMUNICATION ROOM AS INDICATED ON RACK

ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST CABLING

REMOVED FROM ANY WALL MOUNT EQUIPMENT UNLESS

OTHERWISE NOTED. TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A

TELECOMMUNICATIONS/DATA OUTLET AS INDICATED. EXISTING

COMMUNICATION OUTLET BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE WITH NEW

CATEGORY 6A CABLE UNLESS OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE COMMUNICATIONS CABLES

WITH NEW CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE SPECIFICATIONS. NEW

MODULAR JACKS SHALL BE OF THE SAME MANUFACTURER AS

THE FACE PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY 6A CABLES AND

CONNECTIVITY COMPONENTS THAT ARE OF THE SAME

MANUFACTURER, INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND EXISTING

RE-TERMINATED CABLES IN ACCORDANCE WITH THE

SPECIFICATION 27 08 00.

KEY PLAN

KEYED NOTES

1. BACKBONE RISER CEILING PENETRATION

2. FIREWALL PENETRATION

3. 12 INCH X 4 INCH WIRE MESH CABLE TRAY

4. 18 INCH X 4 INCH WIRE MESH CABLE TRAY

5. 24 INCH X 4 INCH WIRE MESH CABLE TRAY

6. SLEEVES IN FLOOR ABOVE.

7. (2) 4" DIAMETER SLEEVES

8. (2) 2" DIAMETER SLEEVES

9. (2) 1-1/2" DIAMETER SLEEVES

NORTH WALL ELEVATION - BLDG. 1 TR B021

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. 1 TR B021

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 1 TR B021

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 1 TR B021

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR B021

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR B021

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 1 TR B021

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

TN-401-C.1.B

BLDG. 1 - BASEMENT -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

DrawnCheckedIssue Date

04-MAY-2022 RMJr VV18-OCT-2022

EAST WALL ELEVATION - BLDG. 1 TR A035

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 1 TR A035

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. 1 TR A035

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 1 TR A035

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR A035

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR A035

SCALE: N.T.S.

TELECOM ROOM LAYOUT - TR A035 - BASEMENT

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

TN-402-C.1.B

BLDG. 1 - BASEMENT -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x48", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

21-OCT-22

2 WEST WALL ELEVATION - BLDG. 1 IT CLOSET A0005

SCALE: N.T.S 3 EAST WALL ELEVATION - BLDG.1 IT CLOSET A0005

SCALE: N.T.S

4 NORTH WALL ELEVATION - BLDG. 1 IT CLOSET

SCALE: N.T.S 5 SOUTH WALL ELEVATION - BLDG. 1 IT CLOSET A0005

SCALE: N.T.S

6 RACK ELEVATION - FRONT VIEW - BLDG.1 IT CLOSET A0005

SCALE: N.T.S. 7 RACK ELEVATION - REAR VIEW - BLDG.1 IT CLOSET A0005

SCALE: N.T.S.

1 IT CLOSET LAYOUT - BLDG. 1 IT CLOSET A0005

SCALE: 1/2" = 1'-0"

TN-403-C.1.B

BLDG. 1 - BASEMENT -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE RUNWAY.

8. 18" CABLE RUNWAY

9. 24" CABLE RUNWAY

10. CABLE RUNWAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS OF

HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

28-OCT-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr 8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com 21-OCT-22

SOUTH WALL ELEVATION - BLDG. 1 TR A134A

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 1 TR A134A

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 1 TR A134A

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 1 TR A134A

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR A134A

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR A134A

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 1 TR A134A

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

TN-405-C.1.1

BLDG. 1 - FIRST FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

21-OCT-22

WEST WALL ELEVATION - BLDG. 1 TR A144A

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 1 TR A144A

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. 1 TR A144A

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 1 TR A144A

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR A144A

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR A144A

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 1 TR A144A

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZ

OY

OY OYOX OX

OX

TN-406-C.1.1

BLDG. 1 - FIRST FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

21-OCT-22

NORTH WALL ELEVATION - BLDG. 1 TR C179

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. 1 TR C179

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 1 TR C179

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 1 TR C179

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR C179

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR C179

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 1 TR C179

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

TN-407-C.1.1

BLDG. 1 - FIRST FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x48", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

21-OCT-22

SOUTH WALL ELEVATION - BLDG. 1 TR B232

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 1 TR B232

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 1 TR B232

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 1 TR B232

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR B232

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR B232

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 1 TR B232

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

TN-410-C.1.2

BLDG. 1- SECOND FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE…