ATTACHMENT 13 - Drawings 12 of 13.pdf

PDF 17 MB Posted

Attached to
36C77623B0005 EHRM Infrastructure Upgrades - Cincinnati Project #539-21-701
Solicitation number
36C77623B0005
Issued by

About this file

This document provides details on a federal solicitation and related file. The solicitation number 36C77623B0005 is for the Construction of the EHRM Infrastructure Upgrades at the Cincinnati VAMC, Project #539-21-701, issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The opportunity type is a solicitation. Attachment 13 appears to include construction drawings related to the project, which involves upgrades to infrastructure at the Cincinnati VA Medical Center. The solicitation seeks construction services to complete Project 539-21-701 for infrastructure improvements at the Cincinnati VAMC.

View the file

Other files

File Type Posted
36C77623B0005 0004 - Extension 3-10-23.pdf PDF
Technical Questions and Answers - Cincinnati EHRM.pdf PDF
36C77623B0005 0003.pdf PDF
36C77623B0005 0002 - EHRM Infrastructure Upgrades - Cincinnati.pdf PDF
Site Visit Sign-In Sheet - 36C77632B0005 EHRM Infrastructure Construction - Cincinnati VAMC.pdf PDF
ATTACHMENT 24 - Construction Wage Rates - Hamilton 01-13-2023.pdf PDF
36C77623B0005 0001 - EHRM Infrastructure Upgrades - Cincinnati.pdf PDF
Site Visit Memorandum.pdf PDF
ATTACHMENT 4 - Drawings 3 of 13.pdf PDF
ATTACHMENT 23 - Contractor Safety - Environmental Form.pdf PDF
ATTACHMENT 6 - Drawings 5 of 13.pdf PDF
ATTACHMENT 18 - Technology Narrative.pdf PDF
ATTACHMENT 15 - Plumbing Narrative.pdf PDF
ATTACHMENT 19 - Hazardous Materials Inspection Report.pdf PDF
ATTACHMENT 24 - Construction Wage Rates - Hamilton 1-13-2022.pdf PDF
ATTACHMENT 21 - COVID-19 Safety Protocols 12-14-21.pdf PDF
ATTACHMENT 14 - Drawings 13 of 13.pdf PDF
ATTACHMENT 20 - Brand Name Justification.pdf PDF
ATTACHMENT 22 - Limitations on Subcontracting - Nov 2022.pdf PDF
ATTACHMENT 9 - Drawings 8 of 13.pdf PDF
ATTACHMENT 10 - Drawings 9 of 13.pdf PDF
ATTACHMENT 16 - Mechanical Narrative.pdf PDF
ATTACHMENT 7 - Drawings 6 of 13.pdf PDF
ATTACHMENT 3 - Drawings 2 of 13.pdf PDF
ATTACHMENT 17 - Electrical Narrative.pdf PDF
ATTACHMENT 2 - Drawings 1 of 13.pdf PDF
ATTACHMENT 25 - Site Visit Instructions.pdf PDF
ATTACHMENT 8 - Drawings 7 of 13.pdf PDF
ATTACHMENT 11 - Drawings 10 of 13.pdf PDF
ATTACHMENT 12 - Drawings 11 of 13.pdf PDF
ATTACHMENT 5 - Drawings 4 of 13.pdf PDF
36C77623B0005 Solicitation - Cincinnati EHRM.pdf PDF
ATTACHMENT 1 - Specifications.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WEST WALL ELEVATION - BLDG. 1 TR B312D

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 1 TR B312D

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. 1 TR B312D

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 1 TR B312D

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR B312D

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR B312D

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG.1 TR B312D

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

TN-415-C.1.3

BLDG. 1- THIRD FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

21-OCT-22

DrawnCheckedIssue Date

04-MAY-2022 RMJr VV18-OCT-2022

NORTH WALL ELEVATION - BLDG. 1 TR C305

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 1 TR C305

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. 1 TR C305

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 1 TR C305

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR C305

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR C305

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 1 TR C305

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY

OZ OZ

OZOY

OY OYOX OX

OX

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY

OZ OZ

OZOY

OY OYOX OX

OX

TN-416-C.1.3

BLDG. 1- THIRD FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

21-OCT-22

WEST WALL ELEVATION - BLDG. 1 TR C3006

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 1 TR C3006

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 1 TR C3006

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. 1 TR C3006

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR C3006

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR C3006

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 1 TR C3006

SCALE: 1/2" = 1'-0"

TN-417-C.1.3

BLDG. 1- THIRD FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

21-OCT-22

SOUTH WALL ELEVATION - BLDG. 1 TR A441

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 1 TR A441

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 1 TR A441

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 1 TR A441

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR A441

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR A441

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 1 TR A441

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

TN-420-C.1.4

BLDG. 1 - FOURTH FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

VISTA 2

VISTA 1 PHILIPS BIOMED

MISC. 3

MISC. 4

P H

IL

IP

S B

IO

M

E D

M

IS

C ,3

M

IS

C

V

IS

T A

V

IS

T A

H D

A B

GUEST

WIRELESS,

MISC. 2

CERNER 2

CERNER 1

MDA B

MDA B

GUEST WIRELESS

FIBER TREE 1

FIBER TREE 2

CERNER 2

CERNER 1

CORE SWITCH A

CORE SWITCH B

VM 1

VM 2

PACS 1

PACS 2

M

IS

C

M

IS

C

M

IS

C

V M

V M

P A

C S

P A

C S

P H

IL

IP

S B

IO

M

E D

M

IS

C ,3

M

IS

C

V

IS

T A

V

IS

T A

H D

A B

GUEST

WIRELESS,

MISC. 2

CERNER 2

CERNER 1

MDA B

MDA B

MDA

MDA A

MDA A

FIBER TREE 2

CORE SWITCH B

VM 1

VM 2

PACS 1

PACS 2

M

IS

C

M

IS

C

M

IS

C

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

3/8" = 1'-0"

TN-421-C.1.4

ENLARGED TDR PLANS CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

14-OCTOBER-2022

PR

C1

3/8" = 1'-0"

FOURTH FLOOR ENLARGED TDR PLAN - SERVER A437C -PHASE 1

3/8" = 1'-0"

FOURTH FLOOR ENLARGED TDR PLAN - SERVER A437C -PHASE 2

GENERAL NOTES:

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION AND FINAL

LOCATION WITH THE ELECTRICAL AND MECHANICAL DIVISION. REFER TO ELECTRICAL,

MECHANICAL AND PLUMBING DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP, AND ANY OTHER

FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE PATHWAY

SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE AS INDICATED

ON THE PLANS. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING AND SECTION 27 05 33 RACEWAYS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE DRILLING.

CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE RISER SLEEVES.

REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY ON THE WALL

ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE CABLE SUPPORT AS INDICATED

ON THE PLANS. THE CABLE TRAY SHALL BE SECURELY ANCHORED TO THE WALL

SUFFICIENT TO SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO SUPPORT

COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY WITHOUT DAMAGING OR

DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH FLOOR. REFER

TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED CABLING.

10. INSTALL NEW NETWORK EQUIPMENT CABINETS PRIOR TO THE DEMOLITION OF THE

NETWORK EQUIPMENT CABINETS LABELED AS DEMO. RELOCATE EXISTING RACK

MOUNTED EQUIPMENT INTO NEW NETWORK EQUIPMENT CABINETS. AFTER ALL RACK

MOUNTED EQUIPMENT IS REMOVED FROM DEMO RACKS, DISASEMBLE AND REMOVE

THE DEMO CABINETS/RACKS.

TRUE NORTH PLAN NORTH

NEW

CABINET

DEMO

CABINET

EXISTING

CABINET

LEGEND:

Description Date

ADDENDUM 1 4/29/2022

PHILIPS

BIOMED

MISC. 1,3 MISC. 4, 5 VISTA 1 VISTA 2 HDA B

GUEST

WIRELESS,

MISC. 2

CERNER 2

CERNER 1

MDA B

MDA B

VM 1 VM 2 PACS 1 PACS 2

MDA

MDA A

MDA A

2 2 2 2 2 2 2 2 7

CRAC-4

EX-CRAC-1

EX-CRAC-2

EX-CRAC-3

TN-1-A437C

TC-1-A437C

UPS1 PNL 2

NEW UPS 1

UPS1 PNL 1

UPS2 PNL 2

UPS2 PNL 1

12345678910

HDA A

3' - 4 127/128"

DETAIL NOTES:

1. 84" HIGH (45RU)

2. 24" WIDE WITH FRONT AIR DAMS

3. 48" DEEP

4. RAILS, SQUARE PUNCHED HOLES WITH CAGE NUTS, 2

SETS.

5. FRONT DOOR - DOUBLE PERFORATED, GEN 3 TERAFRAME

6. REAR DOOR - DOUBLE PERFORATED

7. LATCH/LOCK KITS - 2-POINT LATCHING, KEYED LOCK

8. COLOR - WHITE

9. TOP PANEL - 2-PIECE WITH BRUSH SEALED OPENINGS

10. BOTTOM PANEL - SOLID, GLACIER WHITE

11. SIDE PANEL - SOLID 2-PIECE WITH BRUSH SEALED CABLE

OPENINGS

12. FILLER PANEL - 1RU, GLACIER WHITE

13. FILLER PANEL - 2RU, GLACIER WHITE

14. CABLE ENTRY COVER - BRUSH SEALED

15. PDU BRACKET - STANDARD ASSEMBLY

16. CASTERS - WITH CASTERS AND LEVELER FEET

17. CABLE MANAGER - FINGER CABLE MANAGER WITH NO

COVER

18. CLICK NUT HARDWARE KIT

19. EIA-310-E COMPLIANT

20. UL LISTED 2416, NWIN, FILE #227626

2' - 0"

DETAIL NOTES:

1. 84" HIGH (45RU)

2. 30" WIDE WITH FRONT AIR DAMS

3. 48" DEEP

4. RAILS, SQUARE PUNCHED HOLES WITH CAGE NUTS, 2 SETS.

5. FRONT DOOR - DOUBLE PERFORATED, GEN 3 TERAFRAME

6. REAR DOOR - DOUBLE PERFORATED

7. LATCH/LOCK KITS - 2-POINT LATCHING, KEYED LOCK

8. COLOR - WHITE

9. TOP PANEL - 2-PIECE WITH BRUSH SEALED OPENINGS

10. BOTTOM PANEL - SOLID, GLACIER WHITE

11. SIDE PANEL - SOLID 2-PIECE WITH BRUSH SEALED CABLE

OPENINGS

12. FILLER PANEL - 1RU, GLACIER WHITE

13. FILLER PANEL - 2RU, GLACIER WHITE

14. CABLE ENTRY COVER - BRUSH SEALED

15. PDU BRACKET - STANDARD ASSEMBLY

16. CASTERS - WITH CASTERS AND LEVELER FEET

17. CABLE MANAGER - FINGER CABLE MANAGER WITH NO COVER

18. CLICK NUT HARDWARE KIT

19. EIA-310-E COMPLIANT

20. UL LISTED 2416, NWIN, FILE #227626

2' - 6"

RACK 10 RACK 9 RACK 8 RACK 7 RACK 6 RACK 5 RACK 4 RACK 3 RACK 2 RACK 1

RACK 19 RACK 18 RACK 13 RACK 12 RACK 11RACK 14RACK 15RACK 16RACK 17

DETAIL NOTES:

1. FIBER OPTIC PANELS WITH MTP

CASSETTES (1-12)

2. CATEGORY 6A, 48-PORT, 1RU, HIGH

DENSITY, ANGLED PATCH PANELS

(14-17)

3. SPACE RESERVED FOR GFCI CORE

SWITCH

DETAIL NOTES:

1. 84" HIGH (45RU)

2. 40" WIDE WITH FRONT AIR DAMS

3. 48" DEEP

4. RAILS, SQUARE PUNCHED HOLES WITH CAGE

NUTS, 2 SETS.

5. FRONT DOOR - DOUBLE PERFORATED, GEN 3

TERAFRAME

6. REAR DOOR - DOUBLE PERFORATED

7. LATCH/LOCK KITS - 2-POINT LATCHING, KEYED

LOCK

8. COLOR - WHITE

9. TOP PANEL - 2-PIECE WITH BRUSH SEALED

OPENINGS

10. BOTTOM PANEL - SOLID, GLACIER WHITE

11. SIDE PANEL - SOLID 2-PIECE WITH BRUSH

SEALED CABLE OPENINGS

12. FILLER PANEL - 1RU, GLACIER WHITE

13. FILLER PANEL - 2RU, GLACIER WHITE

14. CABLE ENTRY COVER - BRUSH SEALED

15. PDU BRACKET - STANDARD ASSEMBLY

16. CASTERS - WITH CASTERS AND LEVELER FEET

17. CABLE MANAGER - FINGER CABLE MANAGER

WITH NO COVER

18. CLICK NUT HARDWARE KIT

19. EIA-310-E COMPLIANT

20. UL LISTED 2416, NWIN, FILE #227626

3' - 4"

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

As indicated

TN-422-C.1.4

ENLARGED TDR PLANS CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

14-OCTOBER-2022

PR

C1

3/8" = 1'-0"

FOURTH FLOOR ENLARGED TDR PLAN - SERVER A437C

GENERAL NOTES:

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION AND FINAL

LOCATION WITH THE ELECTRICAL AND MECHANICAL DIVISION. REFER TO ELECTRICAL,

MECHANICAL AND PLUMBING DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP, AND ANY OTHER

FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE PATHWAY

SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE AS INDICATED

ON THE PLANS. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING AND SECTION 27 05 33 RACEWAYS AND BOXES FOR COMMUNICATIONS

SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE DRILLING.

CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE RISER SLEEVES.

REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH FLOOR. REFER

TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED CABLING.

8. PHASING OF THE WORK IN THE DATA CENTER IMPACTS WORK IN THE TRS AND

HORIZONTAL CABLING. COORDINATE WORK SCHEDULES WITH THE COR.

9. GOVERNMENT EQUIPMENT WILL BE RELOCATED BY GOVERNMENT IT PERSONNEL.

CONTRACTOR WILL HAVE TECHNICIANS AVAILABLE TO PROVIDE SUPPORT DURING

OUTAGES AND CUT-OVERS. COORDINATE WORK WITH THE COR.

10. CONTRACTOR SHALL PROVIDE CABLE MANAGEMENT FINGERS, AIR DAMS, BAYING

SEAL KITS, CABLE BRUSHES, AND GROMMETS MANUFACTURED AND COMPATIBLE

WITH CABINETS.

11. CONTRACTOR SHALL PROVIDE FACTORY TERMINATED, MTP, FIBER OPTIC TRUNK

CABLES FOR SIDE A AND SIDE B BACKBONE FROM THE DATA CENTER TO EACH

TELECOMMUNICATIONS ROOM. COORDINATE WITH COR.

12. CONTRACTOR SHALL PROVIDE FACTORY TERMINATED, FIBER OPTIC PATCH CABLES

FOR SIDE A AND SIDE B FROM THE FIBER OPTIC DISTRIBUTOR TO EQUIPMENT

CABINETS. COORDINATE WITH COR.

13. CONTRACTOR SHALL VERIFY FACTORY, PRE-TERMINATED, FIBER OPTIC CABLES

MEASUREMENTS PRIOR TO ORDERING. COORDINATE WITH COR.

14. SECONDARY UPS IS EXISTING AND IS LOCATED IN MECHANICAL ROOM A3002. SEE

ELECTRICAL PLANS FOR MORE INFORMATION.

KEYED NOTES:

1. GROUNDING BUSBAR MOUNTED AT 84" AFF, WITH TWO ROWS OF 7/16" HOLES AT 1"

SPACING EACH WAY. MAKE ALL CONNECTS WITH TWO HOLE LONG BARREL

COMPRESSION LUGS AND BOND TO BUSBAR WITH TWO 3/8" SS HEX HEAD CAP

SCREWS WITH SS LOCKING NUTS. SEE GROUNDING SPECIFICATIONS AND GROUND

BUSBAR DETAILS FOR NOTES.

2. STANDARD-DENSITY SERVER EQUIPMENT CABINET, 24" X 48" DEEP, 7' HIGH

3. 30" NETWORK EQUIPMENT CABINET, 30" X 48" DEEP, 7' HIGH

4. WIRE MESH CABLE TRAY 4" X 24" WIDE, 9' AFF. SECOND LEVEL OF FIBER CHANNEL

PATHWAY 4" X 4".

5. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH SERIES 44+ FIRE

RATED PATHWAY OR APPROVED EQUAL.

6. CONTRACTOR SHALL INSTALL A FLEXIBLE/VERTICAL AISLE CONTAINMENT SYSTEM

SEPARATING THE HOT AND COLD AISLES WITHIN THE DATA CENTER. CONTRACTOR TO

COORDINATE WITH MECHANICAL ENGINEER.

7. 40" NETWORK EQUIPMENT CABINET, 40" X 48" DEEP, 7' HIGH

TRUE NORTH PLAN NORTH

N.T.S.

TYPICAL CABINET - SERVER EQUIPMENT CABINET

N.T.S.

TYPICAL CABINET - 30" NETWORK EQUIPMENT CABINET

N.T.S.

SERVER ROOM - A437C - ROW 1 LAYOUT

N.T.S.

SERVER ROOM - A437C - ROW 2 LAYOUT

N.T.S.

NEW FIBER CORE RACK ELEVATION

Description Date

ADDENDUM 1 4/29/2022

N.T.S.

TYPICAL CABINET - 40" NETWORK EQUIPMENT CABINET

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 1

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 2

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 3

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 4

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 5

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 6

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 7

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 8

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 9

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 10

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 11

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 12

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 13

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 14

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 15

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 16

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 17

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 18

RACKED EQUIPMENT

PS1 PS2

PDU

B

PDU

A

RACK 19

TYP

ZONE PDU

LEG 1 LEG 2

ZONE PDU

LEG 1 LEG 2

ZONE PDU

LEG 1 LEG 2

ZONE PDU

LEG 1 LEG 2

ZONE PDU

LEG 1 LEG 2

ZONE PDU

LEG 1 LEG 2

ZONE PDU

LEG 1 LEG 2

ZONE PDU

LEG 1 LEG 2

ZONE PDU

LEG 1 LEG 2

J J

3 4

TYP TYP

6 7

TYP

MDA A MDA A MDA MDA B MDA BHDA A

HDA B

ED ED ED

EDEDEDEDEDEDEDEDED

12 DUPLEX LC OM4/24 CAT 6A MPO-8 - A-SIDE

12 DUPLEX LC OM4/24 CAT 6A MPO-8 - B-SIDE

MDA A MDA A MDA MDA B MDA BHDA A

HDA B

ED ED ED

EDEDEDEDEDEDEDEDED

(24) DUPLEX LC/(6) MPO-8 ((4) 24-STRAND OM4) - A-SIDE

(24) DUPLEX LC/(6) MPO-8 ((4) 24-STRAND OM4) - B-SIDE

(24) CAT 6A - A-SIDE

(24) CAT 6A - B-SIDE

(24) DUPLEX LC/(2) 24-STRAND OM4 - A-SIDE TO B-SIDE

(6) CAT 6A - A-SIDE TO B-SIDE

LOW VOLTAGE/ IT

Ross & Baruzzini Inc.

1600 Riveredge Parkway NW Suite 900 Atlanta, GA 30328

Project Number

Building Number

Drawing Number

Drawn By:Checked By:Issue Date:

Location

Project TitlePhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANT

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

100% CONSTRUCTION

DOCUMENTS

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

Scale:

FULLY SPRINKLERED

N.T.S.

TN-423-C.1.4

POWER AND NETWORK SCHEMATIC CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST. CINCINNATI, OH. 45220

539-21-701

TL

14-OCTOBER-2022

PR

C1

N.T.S.

SCHEMATIC DIAGRAM AND REDUNDANCY LEVEL -SERVER ROOM

KEYED NOTES:

1. MONITORED VERTICAL PDU, L21-20 PLUG, 3 PHASE, 120/208V, 20A, 10' INPUT POWER

CORD C13 (6) C19 OUTLETS.

2. 30 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH FOUR NEMA L21-20R

AND SIX NEMA 5-20 OUTLETS AND TWO 10' POWER CORDS TERMINATING IN NEMA

L21-30P. ZONIT ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL.

3. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, THREE-PHASE CIRCUIT,

MOUNTED BELOW RAISED FLOOR, COORDINATE INSTALLATION LOCATION WITH

CONTRACTOR. PROVIDE PLUG FOR RECEPTACLE CONNECTION FROM ZONE PDU. SEE

ELECTRICAL SHEET FOR ADDITIONAL INFORMATION.

4. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, THREE-PHASE CIRCUIT,

MOUNTED BELOW RAISED FLOOR, COORDINATE INSTALLATION LOCATION WITH

CONTRACTOR. PROVIDE PLUG FOR RECEPTACLE CONNECTION FROM ZONE PDU. SEE

ELECTRICAL SHEET FOR ADDITIONAL INFORMATION.

5. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH SIX NEMA L21-20R

OUTPUT RECEPTACLES AND TWO 10' POWER CORDS TERMINATING IN ARD-WIRED

JUNCTION BOX. ZONIT ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

6. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT TERMINATING IN A

HARD-WIRED JUNCTION BOX MOUNTED BELOW RAISED FLOOR. PROVIDE POWER

CORD WIPE FROM ZONE PDU. SEE ELECTRICAL SHEET FOR ADDITIONAL INFORMATION.

EC TO MAKE FINAL HARD CONNECTION.

7. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT TERMINATING IN A

HARD-WIRED JUNCTION BOX MOUNTED BELOW RAISED FLOOR. PROVIDE POWER

CORD WIPE FROM ZONE PDU. SEE ELECTRICAL SHEET FOR ADDITIONAL INFORMATION.

EC TO MAKE FINAL HARD CONNECTION.

Description Date

N.T.S.

DIVERSE ROUTING CABINETS (EQUIPMENT DISTRIBUTOR) TO

HORIZONTAL DISTRIBUTION AREA (STANDARD DENSITY)

N.T.S.

DIVERSE ROUTING HORIZONTAL DISTRIBUTION AREA TO MAIN

DISTRIBUTION AREA

4 NORTH WALL ELEVATION - BLDG. 1 TR A540

SCALE: N.T.S 5 SOUTH WALL ELEVATION - BLDG. 1 TR A540

SCALE: N.T.S

1 TELECOM ROOM LAYOUT - BLDG. 1 TR A540

SCALE: 1/2" = 1'-0"

4 X 4"C SLEEVES

ON LEVEL BELOW

6 RACK ELEVATION - FRONT VIEW - BLDG. 1 TR A540

SCALE: N.T.S. 7 RACK ELEVATION - REAR VIEW - BLDG. 1 TR A540

SCALE: N.T.S.

GROUP AA

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

GROUP AA

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

2 EAST WALL ELEVATION - BLDG. 1 A540

SCALE: N.T.S 3 WEST WALL ELEVATION - BLDG. 1 A540

SCALE: N.T.S

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

TN-425-C.1.5

BLDG. 1 - FIFTH FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE RUNWAY.

8. 18" CABLE RUNWAY

9. 24" CABLE RUNWAY

10. CABLE RUNWAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS OF

HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

04-MAY-22

SOUTH WALL ELEVATION - BLDG. 1 A643

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 1 A643

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 1 A643

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 1 A643

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR A643

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR A643

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 1 A643

SCALE: 1/2" = 1'-0"

4 X 4"C SLEEVES

ON LEVEL ABOVE

4 X 4"C SLEEVES

ON LEVEL BELOW

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY

OZ OZ

OZOY

OY OYOX OX

OX

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY

OZ OZ

OZ

OY

OY OYOX OX

OX

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

TN-430-C.1.6

BLDG. 1 - SIXTH FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

SOUTH WALL ELEVATION - BLDG. 1 TR A732A

SCALE: N.T.S

NORTH WALL ELEVATION - BLDG. 1 TR A732A

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 1 TR A732A

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 1 TR A732A

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR A732A

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR A732A

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 1 TR A732A

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

4 X 4"C SLEEVES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

TN-435-C.1.7

BLDG. 1 - SEVENTH FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x36", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

ZPDS-208V30A -L21-4L21-20R-CR OR APPROVED EQUAL

18. SIDE A POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

19. SIDE B POWER, REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT

TERMINATING IN A HARD-WIRED JUNCTION BOX.

20. VERTICAL RACK PDU, L21-20 PLUG, 3-PHASE WYE, 20A, 208V INPUT, (24)

C13 (6) C19 (6) 5-20R OUTLETS, 208V OUTPUT. CHATSWORTH L1-1N0K4

OR APPROVED EQUAL.

21. SIDE-A POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3 PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

22. SIDE-B POWER, L21-20R TWIST-LOCK RECEPTACLE 208V, 20A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

23. SIDE-A POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

24. SIDE-B POWER, L21-30R TWIST-LOCK RECEPTACLE 208V, 30A, 3-PHASE,

8.5 FT AFF, COORDINATE LOCATION WITH CONTRACTOR.

25. 60 A, 208 V, 3-PHASE ZONE PDU BASE UNIT - REAR CIRCUITS WITH

SIX NEMA L21-20R OUTPUT RECEPTACLES AND TWO 10' POWER

CORDS TERMINATING IN HARD-WIRED JUNCTION BOX. ZONIT

ZPDS-208V60A-HW-6L21-2 OR APPROVED EQUAL.

26. TOP-MOUNTED RACK BONDING BUSBAR (RBB)

1. CONTRACTOR SHALL COORDINATE THE EQUIPMENT'S INSTALLATION

AND FINAL LOCATION WITH THE ELECTRICAL AND MECHANICAL

DIVISION. REFER TO ELECTRICAL, MECHANICAL AND PLUMBING

DRAWINGS.

2. CONTRACTOR SHALL INSTALL PATHWAY DIVIDERS, RADIUS DROP AND

ANY OTHER FITTING FOR A PROPER CABLE RUNWAY INSTALLATION.

3. CONTRACTOR SHALL COORDINATE THE EZ-PATH LOCATIONS WITH THE

PATHWAY SYSTEM LAYOUT OUTSIDE EACH TELECOM ROOM. REFER TO

FLOOR PLAN DRAWINGS.

4. CONTRACTOR SHALL INSTALL BACKBONE RISER SLEEVES OF THE SIZE

AS INDICATED ON THE PLANS. REFER TO SECTION 27 15 00

COMMUNICATIONS STRUCTURED CABLING AND SECTION 27 05 33

RACEWAYS AND BOXES FOR COMMUNICATIONS SYSTEMS.

5. CONTRACTOR SHALL X-RAY CONCRETE FLOOR BEFORE CORE

DRILLING. CONTRACTOR SHALL COORDINATE WITH THE COR BEFORE

BEGINNING DRILLING.

6. CONTRACTOR SHALL FIRESTOP RISER SLEEVES AND EMPTY SPARE

RISER SLEEVES. REFER TO SECTION 07 84 00 FIRESTOPPING.

7. CONTRACTOR SHALL INSTALL AN VERTICAL LADDER TYPE CABLE TRAY

ON THE WALL ABOVE THE VERTICAL RISER SLEEVES FOR BACKBONE

CABLE SUPPORT AS INDICATED ON THE PLANS. THE CABLE TRAY

SHALL BE SECURELY ANCHORED TO THE WALL SUFFICIENT TO

SUPPORT THE TOTAL WEIGHT OF CABLES AND CABLE TRAY PLUS 50%.

8. CONTRACTOR SHALL INSTALL CABLE SUPPORTS SUFFICIENT TO

SUPPORT COMMUNICATIONS CABLES ON THE VERTICAL CABLE TRAY

WITHOUT DAMAGING OR DEFORMING THE CABLE.

9. CONTRACTOR SHALL LABEL EACH CABLE AT 42 INCHES A.F.F. ON EACH

FLOOR. REFER TO SECTION 27 15 00 COMMUNICATIONS STRUCTURED

CABLING.

GENERAL NOTES

21-OCT-22

NORTH WALL ELEVATION - BLDG. 1 TR A838

SCALE: N.T.S

SOUTH WALL ELEVATION - BLDG. 1 TR A838

SCALE: N.T.S

EAST WALL ELEVATION - BLDG. 1 TR A838

SCALE: N.T.S

WEST WALL ELEVATION - BLDG. 1 TR A838

SCALE: N.T.S

RACK ELEVATION - FRONT VIEW - BLDG. 1 TR A838

SCALE: N.T.S.

RACK ELEVATION - REAR VIEW - BLDG. 1 TR A838

SCALE: N.T.S.

TELECOM ROOM LAYOUT - BLDG. 1 TR A838

SCALE: 1/2" = 1'-0"

GROUP A

A

B

GROUP B GROUP A GROUP B

LEG 1 LEG 2 LEG 1 LEG 2

OX

OZ

OY OZ OZ

OZOY

OY OYOX OX

OX

4 X 4"C SLEEVES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

PROJECT MANAGEMENTCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

539-21-701

04-MAY-2022

100% CONSTRUCTION

DOCUMENTS

CINCINNATI VAMC EHRM

INFRASTRUCTURE UPGRADES

3200 VINE ST., CINCINNATI, OH

RMJr

TN-440-C.1.8

BLDG. 1 - EIGHTH FLOOR -

TECHNOLOGY TELECOM ROOM PLAN

VV

KEYED NOTES

1. MIGHTY 20 Mo CHANNEL RACK WITH HEXGUARD CABLE PASSAGE, 23.75" X 30" DEEP, 7' HIGH

2. VERTICAL CABLE MANAGER, 6.45" WIDE X 10.26" DEEP.

3. FIBER OPTIC ENCLOSURE WITH DUPLEX-LC, MPO CASSETS

4. ANGLED PATCH PANEL, 48-PORT, 1U, HIGH DENSITY.

5. ETHERNET SWITCH (GFGI)

6. HORIZONTAL CABLE MANAGER, SINGLE SIDED.

7. 12" CABLE WIRE BASKET TRAY

8. 18" CABLE WIRE BASKET TRAY

9. 24" CABLE WIRE BASKET TRAY.

10. WIRE BASKET CABLE TRAY ELEVATION BRACKETS

11. 24-IN. TMGB GROUND BUS BAR

12. PROVIDE FIRE STOPPING DEVICE WITH SPLIT WALL PLATE. EZ PATH

SERIES 44+ FIRE RATED PATHWAY OR APPROVED EQUAL.

13. AC GRADE, FIRE RETARDANT PLYWOOD, PAINTED WITH TWO COATS

OF HIGH GLOSS, FIRE RETARDANT PAINT APPLIED TO ALL WALLS.

14. ELECTRICAL PANEL BOARDS. REFER TO ELECTRICAL DRAWINGS.

15. RACK-MOUNTED, 5KW, 208V, UPS WITH NEMA 20A, L21-20P INPUT AND

L21-20R OUTPUT.

16. WALL MOUNT CABINET, 24"x24"x48", WITH FAN KIT AND TWO SETS OF

RAILS, SOLID DOOR. CHATSWORTH 11840-736, FAN KIT 40972-001, 36"

CABINET RAILS 12787-524, OR APPROVED EQUAL.

17. 30 A, 208 V, 3-PHASE, ZPDU, (4) NEMA L21-20R, (6) NEMA 5-20 OUTLETS

AND 2 x 10' POWER CORDS TERMINATING IN NEMA L21-30P. ZONIT

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .