Attachment 4a_Lolomai Project_ Caterpillar Generator_ATS_MTS_specifications.docx
DOCX document 23 KB Posted
- Attached to
- GENERATOR INSTALLATION SERVICES
- Solicitation number
- 26WA159121
About this file
This is a specifications document for a Caterpillar propane generator system required for the DSW Lolamai Point Generator installation project. The primary requirement is a 30 kW standby-rated Caterpillar propane generator package that meets UL2200 standards with an electronic control panel. The generator must be 120/240-volt, single-phase, 60 hertz operation at 1800 rpm, equipped with a 100-amp LSI main circuit breaker, battery charger, lead-acid batteries, and jacket water heater. The generator will be supplied without an enclosure and must include site testing, startup, and client training services.
The specification also includes two complementary electrical components: a 200-amp ASCO automatic transfer switch (ATS) configured as open transition, NEMA 1, 3-pole unit, and a 200-amp ASCO manual transfer switch (MTS) with camlocks in NEMA 1 configuration and NEMA 3R rating, also with open transition 3-pole configuration. This equipment package is part of a broader Western Area Power Administration (WAPA) Desert Southwest Region sources sought announcement seeking vendors capable of providing generator installation and transfer switch startup and testing services across multiple DSW microwave sites.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 2 PWS - New Peak project_v2.docx | DOCX document | |
| Attachment 4 PWS - Lolomai project_v2.docx | DOCX document | |
| Attachment 3 PWS - Tower Mountain Project_v2.docx | DOCX document | |
| Attachment 1 PWS - CTP project_v2.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project: DSW Lolamai Point Generator, ATS, and MTS Startup & Testing Service Requirement: Purchase and Installation service in accordance with attachment 2 PWS
SPECIFICATIONS
Caterpillar Propane Generator
1. 30 kW standby rated
1. UL2200 package, Electronic Control Panel
1. 120/240-volt, 1 phase, 60 hertz. 1800rpm
1. Main Circuit Breakers LSI – 100A
1. No Enclosure
1. Battery charger
1. Lead Acid Batteries
1. Jacket Water Heater
1. Site testing and startup per spec, client training
ASCO Automatic Transfer Switch
1. 200A ASCO ATS
1. Open transition, Nema 1, 3-pole
ASCO Manual Transfer Switch with camlocks
1. 200A ASCO MTS (Nema 1) with camlocks (Nema 3R)
1. Open transition, 3- pole
File details come from the government source that posted it. Updated .