This document provides details on a federal contract opportunity for radiation therapy expansion at the Jamaica Plain Campus of the Department of Veterans Affairs. The solicitation number is 36C77622B0038 and seeks proposals for expanding radiation therapy services at the Jamaica Plain location. Interested parties should respond with final drawings by the specified due date. The contracting agency is the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The opportunity aims to enhance radiation therapy infrastructure and services for veterans.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JAMAICA PLAINS MASSACHUSETTS
VA MEDICAL CENTER
JAMAICA PLAIN, MA
VA PROJ. NO. 523-417
RADIATION THERAPY EXPANSION
VAMC
100% BID DOCUMENTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
100% BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
523-417
JAMAICA PLAIN, MA
RADIATION THERAPY EXPANSION
VAMC
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
B
IM
/0
V A
B o s to n
R a d ia ti o n T h e ra p y /0
V A
B o s to n
R a d ia ti o n T h e ra p y D iv
R
.r v t
/1
/2
:5
:2
A
M
09/17/2021
GI100
COVER SHEET
09/17/21 ADL JJAAllen D. Lantz, P.E.
MD License #41513
JAMAICA PLAIN, MA
NTS
ACHITECTURE / INTERIOR DESIGN
CIVIL ENGINEERING
PRIME ENGINEER - PROJECT MANAGEMENT,
MECHANICAL, ELECTRICAL, PLUMBING, FIRE
PROTECTION, TELECOM, STRUCTURAL ENGINEERING
CITP / LIFE SAFETY ENVIRONMENTAL ENGINEERING
GEOTECHNICAL ENGINEERINGESTIMATING SERVICES
DRAWING SHEET INDEX
Sheet Number Sheet Name
FP404 FIRE PROTECTION ENLARGED PLAN
FP501 FIRE PROTECTION DETAILS
P-001 PLUMBING LEGENDS, SYMBOLS, NOTES & SPECIFICATIONS
P-101 PLUMBING FLOOR PLANS
P-102 PLUMBING ROOF PLAN
P-401 PLUMBING ENLARGED PLANS
P-402 PLUMBING ENLARGED PLANS
P-501 PLUMBING DETAILS
M-001 MECHANICAL LEGENDS AND SYMBOLS
MD101 MECHANICAL - HVAC FLOOR PLAN - PRE-DEMO
MH101 MECHANICAL - HVAC FLOOR PLAN - OVERALL
MH102 MECHANICAL - HVAC ROOF PLAN - NEW
MH401 MECHANICAL ENLARGED PLAN
MH402 MECHANICAL ENLARGED PLAN
MH403 MECHANICAL ENLARGED PLAN
MH404 MECHANICAL ENLARGED PLAN
MP401 MECHANICAL ENLARGED PLAN
M-501 MECHANICAL - DETAILS
M-502 MECHANICAL - DETAILS
M-701 MECHANICAL - CONTROLS
M-801 MECHANICAL - SCHEDULES
E-001 ELECTRICAL LEGENDS AND SYMBOLS
E-002 ELECTRICAL GENERAL NOTES
E-101 ELECTRICAL - OVERALL FLOOR PLAN
E-401 ELECTRICAL ENLARGED PLANS - PHASE 1
E-402 ELECTRICAL ENLARGED PLANS - PHASE 2 AND 3
E-403 ELECTRICAL ENLARGED PLANS - PHASE 4 AND 5
E-404 ELECTRICAL ENLARGED PLANS - PHASE 6
E-501 ELECTRICAL - DETAILS
E-801 ELECTRICAL - SCHEDULES
FA001 FIRE ALARM LEGEND AND ABBREVIATIONS
FA101 FIRE ALARM OVERALL FLOOR PLAN
FA401 FIRE ALARM ENLARGED PLANS - PHASE 1
FA402 FIRE ALARM ENLARGED PLANS - PHASES 2 AND 3
FA403 FIRE ALARM ENLARGED PLANS - PHASES 4 AND 5
FA404 FIRE ALARM ENLARGED PLANS - PHASE 6
FA501 FIRE ALARM DETAILS
FA601 FIRE ALARM DIAGRAMS
T-001 TELECOM LEGEND AND ABBREVIATIONS
T-100 TELECOM CONNECTIONS PLAN
T-101 TELECOM OVERALL PLAN
T-102 TELECOM ROOF PLAN
T-401 TELECOM ENLARGED PLANS - PHASE 1
T-402 TELECOM ENLARGED PLANS - PHASE 2
T-403 TELECOM ENLARGED PLANS - PHASE 3
T-404 TELECOM ENLARGED PLANS - PHASE 4
T-405 TELECOM ENLARGED PLANS - PHASE 5
T-406 TELECOM ENLARGED PLANS - PHASE 6
T-407 TELECOM ENLARGED DATA ROOM RT004
T-501 TELECOM DETAILS
T-502 TELECOM DETAILS
T-601 TELECOM DIAGRAMS
DRAWING SHEET INDEX
Sheet Number Sheet Name
GI100 COVER SHEET
GI002 SYMBOLS AND ABBREVIATIONS
GI003 PHASING PLANS
GI004 PHASING PLANS
LS001 LIFE SAFETY BUILDING CODES ANALYSIS
LS002 LIFE SAFETY BUILDING CODES ANALYSIS
LS101 LIFE SAFETY FLOOR PLAN - EXISTING
LS102 LIFE SAFETY FLOOR PLAN - PHASING
LS103 LIFE SAFETY FLOOR PLAN - PHASING
LS104 LIFE SAFETY FLOOR PLAN - NEW
CS101 EXISTING CONDITIONS AND DEMOLITION PLAN
CS102 SITE, GRADING & UTILITY PLANS
CS103 ACCESS ROAD PLAN
CS104 CONSTRUCTION DETAILS
AD101 REMOVALS PLAN
AD102 CEILING REMOVALS PLAN
AE101 PROPOSED PLAN
AE102 PROPOSED ROOF PLAN
AE103 PROPOSED REFLECTED CEILING PLAN
AE201 BUILDING ELEVATIONS & 3D VIEW
AE202 INTERIOR ELEVATIONS
AE203 INTERIOR ELEVATIONS
AE204 INTERIOR ELEVATIONS
AE205 INTERIOR ELEVATIONS
AE301 BUILDING SECTIONS
AE302 WALL SECTIONS
AE303 WALL SECTIONS
AE501 WALL DETAILS
AE502 WALL DETAILS
AE503 ROOF DETAILS
AE504 ROOF DETAILS
AE505 MILLWORK DETAILS
AE506 MILLWORK DETAILS
AE601 DOOR AND WINDOW SCHEDULE. TYPES AND DETAILS
AE602 EXTERIOR WALL AND PARTITION TYPES AND DETAILS
AE603 ROOF TYPES AND DETAILS
AE604 FINISH SCHEDULE AND DETAILS
AF701 FINISH FLOOR PLAN
AF702 EQUIPMENT PLAN
XK301 DUCTILE STEEL STUD WALL SYSTEM
S101 GENERAL NOTES
S201 FOUNDATION PLAN
S202 STAIR & RAMP FOUNDATION PLAN
S203 ROOF FRAMING PLAN
S204 FRAME SECTION
S301 FOUNDATION DETAILS
S302 STRUCTURAL DETAILS
S303 STAIR & RAMP FOUNDATION DETAILS
FP001 FIRE PROTECTION LEGENDS, SYMBOLS, & NOTES
FP101 FIRE PROTECTION FLOOR PLAN
FP401 FIRE PROTECTION ENLARGED PLAN
FP402 FIRE PROTECTION ENLARGED PLAN
FP403 FIRE PROTECTION ENLARGED PLAN
Revisions Date
NOTE: REFER TO STRUCTURAL, MECHANICAL,
AND/OR ELECTRICAL DRAWINGS FOR
ABBREVIATIONS SPECIFIC TO EACH DISCIPLINE.
AB ANCHOR BOLT, AUGER BORING
ABI ALTERNATE BID ITEM
AC ACOUSTIC AIR CONDITIONING, ASPHALTIC CONCRETE
AD ACCESS DOOR
ADD ALT ADDITIVE ALTERNATE
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZE
AP ACCESS PANEL
APC ACOUSTIC PANEL CEILING
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASB ASBESTOS
ASPH ASPHALT
AUTO AUTOMATIC
AWP ACOUSTIC WALL PANEL
BDRM BEDROOM
BIT. CONC BITUMINOUS CONCRETE
BJ BAR JOIST
BLDG BUILDING
BLK BLOCK
BM BEAM, BENCHMARK
BOT BOTTOM
BRD BOARD
BRG BEARING
BS BOTTOM OF STEP
BSMT BASEMENT
BTWN BETWEEN
BW BOTTOM OF WALL
CAB CABINET
CAP CAPACITY
CC CENTER TO CENTER
CEM CEMENT
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CI CAST IRON
CIR CIRCULATING
CJ CONSTRUCTION JOINT, CONTROL JOINT
CLG CEILING
CLO CLOSET
CLR CLEAR
CENTERLINE
CMU CONCRETE MASONRY UNITS
CMU G1 GLAZED CMU, ONE SIDE
CMU G2 GLAZED CMU, TWO SIDES
CO CLEANOUT
COL COLUMN
COMP'T COMPARTMENT
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CS/CI CONTRACTOR SUPPLIED/ CONTRACTOR INSTALLED
CS/OI CONTRACTOR SUPPLIED/OWNER INSTALLED
CSK COUNTER SUNK
CT CERAMIC TILE
CTE CONNECT TO EXISTING
CTR CENTER
CUH CABINET UNIT HEATER
Ø DIAMETER
DF DRINKING FOUNTAIN
DFD DOOR FRAME DIMENSION
DH DOUBLE HUNG
DIA DIAMETER
DIM DIMENSION
DN DOWN
DTL DETAIL
DWG DRAWING
E EAST
EA EACH
EL, ELEV ELEVATION
ELEC ELECTRIC
EMERG EMERGENCY
EPS EXTRUDED POLYSTYRENE
EQ EQUAL
EQUIP EQUIPMENT
ETC ETCETERA
EW EACH WAY
EXG EXISTING
EXP EXPANSION, EXPOSED
EXP JT EXPANSION JOINT
EXT EXTERIOR
FBO FURNISHED BY OTHERS
FCO FLOOR CLEAN-OUT
FD FLOOR DRAIN, FOOTING DRAIN
FE FIRE EXTINGUISHER
FF FINISH FLOOR
FFE FINISHED FLOOR ELEVATION
FG FINISH GRADE, FIBERGLASS
FHC FIRE HOSE CABINET
FIG FIGURE
FIN FINISH
FO FUEL OIL
FOF FACE OF FOUNDATION
FOR FUEL OIL RETURN
FOS FACE OF STUD, FUEL OIL SUPPLY
FOUND FOUNDATION
FP FIREPROOF
FR FRAME, FIRE RETARDANT
FRT FIRE RETARDANT TREATED
FS FLOOR SINK
FT FOOT, FEET, FINNED TUBE
FTG FOOTING
FWP FABRIC WALL PANEL
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GF/GI GOVT. FURNISHED/GOVT. INSTALLED
GF/CI GOVT. FURNISHED/CONTRACTOR INSTALLED
GI GALVANIZED IRON
GOV'T GOVERNMENT
GPM GALLONS PER MINUTE
GR GRADE
GRAN GRANULAR
GRD GROUND
GWB GYPSUM WALLBOARD
GYP GYPSUM
HGT HEIGHT
H&V HEATING AND VENTILATING
HB HOSE BIB
HC HANDICAPPED
HCWD HOLLOW CORE WOOD DOOR
HDC HANDICAPPED
HDW HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HPR HIGH PERFORMANCE ROOFING
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
IN INSIDE DIAMETER
INCL INCLUSIVE
INFO INFORMATION
INSUL INSULATION, INSULATED
INT INTERIOR
IWP IMPACT RESISTANT WALL PROTECTION
JAN JANITOR CLOSET
JCT JUNCTION
KV KILOVOLT
KW KILOWATT
LAB LABORATORY
LAV LAVATORY
LBS POUNDS
LF LINEAR FEET
LFC LINOLEUM FLOOR COVERING
LGR LEDGER
LP LOW POINT
LR LIVING ROOM
LT LIGHT
LWC LIGHT WEIGHT CONCRETE
LVL LAMINATED VENEER LUMBER
MACH MACHINE
MANUF MANUFACTURER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MC MEDICINE CABINET
MCB METAL CORNER BEAD
MECH MECHANICAL
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MM MILLIMETER
MO MASONRY OPENING
MR MOISTURE RESISTANT
MS METAL STRIP
MTD MOUNTED
MTL METAL
N NORTH
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVER ALL
OB GL OBSCURE GLASS
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE
OS/CI OWNER SUPPLIED/CONTRACTOR INSTALLED
OS/OI OWNER SUPPLIED/OWNER INSTALLED
OVHD, OH OVERHEAD
P-1 PLUMBING FIXTURE TYPE
PART PARTITION
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLAST PLASTIC
PLYWD PLYWOOD
PNL PANEL
PNTD PAINTED
POL POLISHED
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT, POINT, PRESSURE TREATED
PT DISP PAPER TOWEL DISPENSER
PVC POLY VINYL CHLORIDE
PVMT PAVEMENT
QT QUARRY TILE
R RADIUS, RISER
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN, ROAD
RECEP RECEPTACLE
REF REFRIGERATOR
REINF REINFORCEMENT
REQ'D REQUIRED
REV REVISION
RF RESINOUS FLOOR
RL RAIN LEADER
RM ROOM
RO ROUGH OPENING
RS RESILIENT STAIR ACCESSORY
RT RUBBER TILE
S SOUTH
S DISP SOAP DISPENSER
S&V STAIN AND VARNISH
SCONC SEALED CONCRETE
SCWD SOLID CORE WOOD DOOR
SCH, SCHED SCHEDULE
SCR SUPPLY CEILING REGISTER
SECT SECTION
SF SQUARE FEET
SH SINGLE HUNG
SHT SHEET
SIM SIMILAR
SL SLOPE
SPECS SPECIFICATIONS
SQ SQUARE
SQ FT SQUARE FEET
SS SERVICE SINK, SANITARY SEWER, STAINLESS STEEL
SSURFACE SOLID SURFACE
ST STREET
STA STATION
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUP SUPPORT
SUSP SUSPEND
SV SHEET VINYL
SYM SYMMETRICAL
T TOP, TANGENT, THERMOMETER
TB TACK BOARD
TBA TOILET BATH ACCESSORIES
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
T.O.C. TOP OF CONCRETE
T.O.M. TOP OF MASONRY
T.O.S. TOP OF STEEL
T.O.W. TOP OF WALL
TEL TELEPHONE
TEMP TEMPERATURE, TEMPORARY
TERM TERMINAL
THK THICK
THRU THROUGH
TLT TOILET
TP TOILET PARTITION
TPH TOILET PAPER HOLDER
TRAN TRANSOM
TS TOP OF STEP, TOP OF SILL
TV TELEVISION
TYP TYPICAL
TYPE "X" UL APPROVED GWB
U&D UP AND DOWN
UC UNDERCUT
UNO UNLESS NOTED OTHERWISE
UV UNIT VENTILATOR
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VTR VENT THROUGH ROOF
W WEST
WAIN WAINSCOT
WB RESILIENT WALL BASE
WC WALL COVERING
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WIDTH, WINDOW DIMENSION, WOOD
WGL WIRE GLASS
WP WATERPROOF, WEATHERPROOF
WS WEATHERSTRIPPING
WT WEIGHT
WW WELDED WIRE FABRIC
ROWS IDENTIFIED BY LETTERS
INCREASING TOWARD THE
BOTTOM OF SHEET
DRAWING TITLE
DRAWING COORDINATE
INDICATOR
SCALE OF DRAWING
COLUMNS IDENTIFIED BY
NUMBERS INCREASING TOWARD
THE RIGHT SIDE OF SHEET.
F
E
1 2 3
C4 DRAWING BLOCK TITLE
1 1/2" = 1'-0"F1
SCALE: 1/8" = 1'-0"
4' 8'0 16'
B3
D
C
B
A
SHEET NUMBER DETAIL
IS DRAWN ON
ROOM NAME
ROOM NUMBER
BREAK LINE
GRAPHIC SCALE
REVISION NUMBER
REVISION CLOUD
ELEVATION MARKER - SECTION
ELEVATION MARKER - PLAN
DOOR
NUMBER
REFERENCE
WINDOW TYPE REFERENCE
WALL TYPE REFERENCE
COLUMN GRID REFERENCE
SHEET NUMBER ELEVATION
IS DRAWN ON
INTERIOR ELEVATION
REFERENCE
BUILDING / WALL
SECTION
NUMBER
SHEET NUMBER BUILDING /
WALL SECTION IS DRAWN
ON
BUILDING ELEVATION
NUMBER
SHEET NUMBER
ELEVATION IS DRAWN ON
MATCH LINE
4 HOUR RATED PARTITION
3 HOUR RATED PARTITION
2 HOUR RATED PARTITION
1 HOUR RATED PARTITION
DETAIL NUMBER
SYMBOLS
LINETYPES
SMOKE BARRIER
STEEL & OTHER METAL PATTERN
CONCRETE BLOCK PATTERN
STONE CUT PATTERN
TERRA COTTA
CARPET AND PAD PATTERN
TILE, ACOUSTICAL
CEILING PATTERN
WOOD FLOORING PATTERN
BRICK PATTERN, GLAZED
SAND CLAY GRAVEL PATTERN
BRICK PATTERN
EROSION AND
SEDIMENTATION
CONTROL,
FILTRATION BED PATTERN
EARTHWORK GRAVEL
PATTERN, POROUS
FILL
EARTHWORK ROCK PATTERN
EARTHWORK PATTERN,
COMPACTED FILL
PATTERN
RIPRAP PATTERN
SAND PATTERN
GLASS ELEVATION PATTERN
GYPSUM BOARD FINISH PATTERN
SEALANT AND BACKER ROD
INSULATION,
RIGID
BOARD PATTERN
INSULATION,
LOOSE
FILL PATTERN
WOOD FINISH PATTERN
PARTICLE BOARD PATTERN
ORIENTED STRAND BOARD PATTERN
WOOD, GLUED-LAMINATED PATTERN
WOOD FRAMING,
CONTINUOUS
PATTERN
WOOD BLOCKING OR SHIM PATTERN
HATCH PATTERNS
EARTH, UNDISTURBED PATTERN
EARTH, CRUSHED
ROCK
GRAVEL PATTERN
EARTH, CRUSHED
ROCK
GRAVEL PATTERN
PLYWOOD PATTERN
10'-0"
Room name
B
M2
A101
SIM
CONCRETE POURED IN
PLACE, PRECAST
ALUMINUM PATTERN
ASPHALT SHINGLE PATTERN
1/2 HOUR RATED PARTITION
KEYNOTE TAG
A101
1 1
A1
AE101
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked DrawnWWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/1
/2
:3
:2
A
M U
A u to d e s k A u to s a ve s \R e vi t\
A
G V
A J
P R
A D
IA
T
IO
N
T H
E R
A P
Y
A R
C H
R jo c e ly n
.b o o th e w b rc a e
.c o m .r v t
GI002
523-417
BLDG 1, D-WING
RADIATION THERAPY EXPANSION
VAMC
JAMAICA PLAIN, MA
JRB SHW09/17/21
100% BID DOCUMENTSSYMBOLS AND ABBREVIATIONS
FULLY SPRINKLERED
NTS
ARCHITECTURAL ABBREVIATIONS
NTS
DRAWING AREA
NTS
ARCHITECTURAL SYMBOLS
Revisions: Revision Description Date: 9/13/2021
FEC
F E
C F
E C
F E
C
F E
C
F E
C
FEC
F E
C F
E C
F E
C
F E
C
F E
C
FEC
F E
C F
E C
F E
C
F E
C
F E
C
FEC
F E
C F
E C
F E
C
F E
C
F E
C
F E
C
C L
E A
R
M
IN
PHASING 1 NOTES:
- RELOCATE 4 OFFICES TO THE SWING OFFICE SPACE, ROOM RT-002
TEMP OFFICE
TELE/DATA
RT-004
ELEC
RT-006
CLEAN UTILITY
RT-024
OFFICE
RT-025
OFFICE
RT-026
OFFICE
RT-027
OFFICE
RT-030
OFFICE
RT-029
DOSIMETRY
RT-031
C L
E A
R
M
IN
OFFICE/SWING
RT-002
PHYSICIST
RT-036
CLEAR
5' - 0" MIN
PHASING 2 NOTES:
- RELOCATE 3 OFFICES PERMANENTLY TO THE NEW ADDITION
- RELOCATE 2 OFFICES TEMPORARILY TO THE NEW ADDITION
TEMP
OFFICE
TEMP
OFFICE
OFFICE
RT-033
OFFICE
RT-032
OFFICE
RT-027
OFFICE
RT-026OFFICE
RT-025
CLEAR
5' - 0" MIN
PHASING 3 NOTES:
- RELOCATE 2 OFFICES TEMPORARILY TO THE NEW ADDITION
- RELOCATE THE PATIENT HOLDING AREA TO EXAM ROOM RT-007
- CONSTRUCTION ACTIVITIES TO REMOVE SKYLIGHT IS TO BE DONE DURING OFF HOURS AND COORDINATED WITH THE VA TO MINIMIZE DISRUPTION TO PATIENTS. TEMPORARY ROOFING TO BE INSTALLED OVER SKYLIGHT
INFILL UNTIL ENTIRE ROOF IS REPLACED
- EXISTING NURSE STATION TO REMAIN OPERATIONAL THROUGHOUT THE PHASE
TEMP PATIENT
HOLDING
NEW
DOSIMETRY
DOSIMETRIST
RT-035
PHYSICIST
RT-036
NURSE
RT-016B
FOCUS
RT-037
MED CLOSET
RT-038
TEMP
OFFICE
TEMP
OFFICE
EXAM
RT-007
CLEAR
5' - 0" MIN
PHASING 4 NOTES:
- CYBERKNIFE TO BE OFF-LINE DURING PHASE 4
- RELOCATE THE PATIENT HOLDING AREA TO EXAM ROOM RT-007
- THE CONTROL ROOM AND CYBERKNIFE ROOM CANNOT BE SHUT DOWN FOR MORE THAN A (3) WEEK PERIOD.
CONSTRUCTION ACTIVITY MUST BE CONTINUOUS. COORDINATE CONSTRUCTION SHUTDOWN PERIOD WITH
THE VA.
TEMP PATIENT
HOLDING
CONTROL ROOM
RT-017
EXAM
RT-007
NEW WALL
EXISTING WALL
LEGEND:
TEMPORARY WALL
LOCATION OF TEMPORARY PARTITIONS IS
GENERAL IN NATURE. GC TO LOCATE ALL
TEMPORARY PARTITIONS AND DOORS AS
REQUIRED TO PROTECT THE AREA UNDER
CONSTRUCTION. SEE LIFE SAFETY SHEETS
FOR NOTES ON REQUIRED FIRE RATING.
PHASING 0 NOTES:
- PHASE 0 TO BE COMPLETED PRIOR TO THE START OF PHASE 1, AND TO BE REMOVED AND RETURNED TO THE ORIGINAL CONDITION PRIOR TO THE START OF PHASE 2.
- DURING PHASE 0 AND PHASE 1, RELOCATE PHYSICIST OFFICE RT-033 TO SWING OFFICE RT-002
4' - 6"
VIF
5' - 7 3/8"
DOSIMETRY
RT-034
PHYSICIST
RT-033
FIRE-RETARDANT TREATED WOOD STAIR ON EITHER
SIDE OF NEW TEMPORARY EGRESS DOOR. STAIRS
TO HAVE 11" MIN TREAD AND 7" MAX RISER
TEMPORARY HANDRAIL / GUARD RAIL ON BOTH SIDES
OF STAIRS. AT EXTERIOR STAIR, DO NOT ATTACH
HANDRAIL TO EXISTING BUILDING.
FIRE-RETARDANT TREATED WOOD LANDING ON
EITHER SIDE OF NEW TEMPORARY EGRESS DOOR.
REMOVE EXISTING STOREFRONT SYSTEM AND
SAVE FOR RE-INSTALLATION. INSTALL NEW
TEMPORARY CFMF OR FIRE-RETARDANT
TREATED WOOD WALL WITH INTERIOR GWB AND
EXTERIOR SHEATHING AND WATER PROOFING.
NEW WALL TO BE SEALED TO EXISTING AND
WEATHER TIGHT. PROVIDE 3' WIDE TEMPORARY
EGRESS DOOR WITH PANIC HARDWARE, DOOR
CONTACT SWITCH AND EGRESS ONLY LOCK.
STAIR, LANDING AND RAIL TO BE REMOVED
AFTER THE COMPLETION OF PHASE 1 AND
STOREFRONT SYSTEM TO BE RE-INSTALLED.
PROVIDE TEMPORARY
EGRESS SIGNAGE. DOOR
TO BE OPEN DURING
OCCUPIED HOURS
V
IF
4' - 0"
1' - 0"
DOSIMETRIST
RT-032
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/1
/2
:3
:3
A
M U
A u to d e s k A u to s a ve s \R e vi t\
A
G V
A J
P R
A D
IA
T
IO
N
T H
E R
A P
Y
A R
C H
R jo c e ly n
.b o o th e w b rc a e
.c o m .r v t
GI003
523-417
BLDG 1, D-WING
RADIATION THERAPY EXPANSION
VAMC
JAMAICA PLAIN, MA
JRB SHW09/17/21
100% BID DOCUMENTSPHASING PLANS
FULLY SPRINKLERED
3/32" = 1'-0"D1 PHASE 1
3/32" = 1'-0"D3 PHASE 2
3/32" = 1'-0"D6 PHASE 3
3/32" = 1'-0"D8 PHASE 4
KEY PLAN
3/16" = 1'-0"F1 PHASE 0
Revisions: Revision Description Date:
9/13/2021
FEC
E
C F
E C
F E
C
F E
C
F E
C
FEC
F E
C F
E C
F E
C
F E
C
F E
C
FEC
F E
C F
E C
F E
C
F E
C
F E
C
PHASING 5 NOTES:
- EXAM ROOMS TO BE COMPLETED IN 2 SUB-PHASES. KEEP A TOTAL OF 2 EXAM ROOMS OPERATIONAL AT ALL TIMES.
- RELOCATE THE PATIENT HOLDING AREA TO SWING ROOM RT-002
C L
E A
R
M
IN
C L
E A
R
M
IN
PHASE 5A PHASE 5B
CLEAR
5' - 0" MIN
HOLDING
RT-016A
INTERVIEW/VITALS
RT-015
EXAM
RT-014
EXAM
RT-013 PHASE 5B
PHASE 5B
TEMP PATIENT
HOLDING
OFFICE/SWING
RT-002
PHASING 6 NOTES:
- WAITING AND REGISTRATION TO BE MOVED TO SWING ROOM RT-002 AND WAITING ROOM RT-010
- TEMPORARY ROOFING TO BE INSTALLED OVER SKYLIGHT INFILL UNTIL ENTIRE ROOF IS REPLACED
TEMP WAITING
AND
REGISTRATION
C L
E A
R
M
IN
C L
E A
R
M
IN
TEMP
WAITING
RECEPTION
RT-001A
WAITING
RT-001
WHEELCHAIR
STORAGE
RT-009
OFFICE/SWING
RT-002
GOWNED
WAITING
RT-010
PHASING 7 NOTES:
- DOUBLE DOOR IS TO BE RELOCATED AND TEMPORARY EGRESS IS TO BE PROVIDED. SEE LIFE SAFETY SHEETS
- WAITING ROOM DOOR TO BE KEPT HELD OPEN DURING CONSTRUCTION PERIOD DURING HOURS OF OPERATION
PHASING 8 NOTES:
- REPLACE THE EXISTING ROOF TO THE EXTENTS SHOWN
- THE ROOF OVER THE NEW ADDITION IS TO BE COMPLETED AS PART OF PHASE 1
NEW WALL
EXISTING WALL
LEGEND:
TEMPORARY WALL
LOCATION OF TEMPORARY PARTITIONS IS
GENERAL IN NATURE. GC TO LOCATE ALL
TEMPORARY PARTITIONS AND DOORS AS
REQUIRED TO PROTECT THE AREA UNDER
CONSTRUCTION. SEE LIFE SAFETY SHEETS
FOR NOTES ON REQUIRED FIRE RATING.
TEMPORARY WALL SHALL RESIST PASSAGE OF SMOKE PER NFPA 241 AND BE 1HR RATED.
LOCATION OF TEMPORARY PARTITIONS IS GENERAL IN NATURE. GC TO LOCATE ALL
TEMPORARY PARTITIONS AND DOORS AS REQUIRED TO PROTECT THE AREA UNDER
CONSTRUCTION. SEE LIFE SAFETY DRAWING LS001 FOR OTHER NOTES.
TEMPORARY WALL TYPE: T1
5' MIN. CLEAR
PATIENT SIDECONSTRUCTION
SIDE
EXISTING STRUCTURAL DECK
NEW RATED PARTITION
TO EXTEND THROUGH
SUSPENDED CEILING TO
DECK. SEAL ALL
PENETRATIONS.
EXISTING APC CEILING
SEAL ALL JOINTS, TYP.
NEW LAYER 5/8" GWB ON
BOTH SIDES OF PARTITION
SECURED TO CFMF STUDS.
GWB TO BE PAINTED ON
CORRIDOR SIDE.
1 HR RATED (UL U419)
WHERE NON-RATED TEMPORARY PARTITIONS ARE ALLOWED TO BE USED, TEMPORARY
PARTITION SHALL RESIST PASSAGE OF SMOKE PER NFPA 241. LOCATION OF
TEMPORARY PARTITIONS IS GENERAL IN NATURE. GC TO LOCATE ALL TEMPORARY
PARTITIONS AND DOORS AS REQUIRED TO PROTECT THE AREA UNDER CONSTRUCTION.
SEE LIFE SAFETY DRAWING LS001 FOR OTHER NOTES.
TEMPORARY WALL TYPE: T2
5' MIN. CLEAR
PATIENT SIDECONSTRUCTION
SIDE
EXISTING STRUCTURAL DECK
NEW SMOKE TIGHT
PARTITION TO STOP AT
EXISTING SUSPENDED
CEILING.
EXISTING APC CEILING
SEAL ALL JOINTS, TYP.
NEW LAYER 5/8" GWB ON
BOTH SIDES OF PARTITION
SECURED TO CFMF STUDS.
GWB TO BE PAINTED ON
CORRIDOR SIDE.
SMOKE TIGHT PARTITION
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
Project TitleDrawing Title
Approved:
Phase
Location
Issue Date
Project Number
Building Number
Drawing Number
Checked Drawn
TRUE NORTH
PROJECT NORTH
WWW.WBRCAE.COM
BANGOR, MAINE 207-947-4511
PORTLAND, MAINE 207-828-4511
SARASOTA, FLORIDA 941-556-0757
www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
/1
/2
:3
:3
A
M U
A u to d e s k A u to s a ve s \R e vi t\
A
G V
A J
P R
A D
IA
T
IO
N
T H
E R
A P
Y
A R
C H
R jo c e ly n
.b o o th e w b rc a e
.c o m .r v t
GI004
523-417
BLDG 1, D-WING
RADIATION THERAPY EXPANSION
VAMC
JAMAICA PLAIN, MA
JRB SHW09/17/21
100% BID DOCUMENTSPHASING PLANS
FULLY SPRINKLERED
3/32" = 1'-0"D1 PHASE 5A & 5B
3/32" = 1'-0"D3 PHASE 6
3/32" = 1'-0"D6 PHASE 7
3/32" = 1'-0"D8 PHASE 8 ROOF PLAN
KEY PLAN
NTSF1 TEMPORARY PARTITIONS
1FB 1FB1FB 1FB1FB
2FB 2FB2FB 2FB2FB
SP SPSP SPSP
LIFE SAFETY LEGEND
OCCUPANT LOAD
EXIT CAPACITY (PERSONS)
COMMON PATH OF TRAVEL
DEAD END PATH
TOTAL TRAVEL DISTANCE
1-HOUR FIRE RATED BARRIER
2-HOUR FIRE RATED BARRIER
SMOKE PARTITION
FIRE EXTINGUISHER CABINET LOCATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
523-417
BLDG 1, D-WING
JAMAICA PLAIN, MA
RADIATION THERAPY EXPANSION
VAMC
C U s e rs \L th o m a s .S
T A
N T
O N
\D o c u m e n ts
\4
S E
S V
A J
P R
A D
IA
T
IO
N
T H
E R
A P
Y
F
IR
E R lt h o m a s N
Q U
.r v t
/1
/2
:5
:0
A
M
LS001
LIFE SAFETY BUILDING CODES
ANALYSIS
09/17/21 D.
FUECKER
D. LITTLE
THE INTENT OF THIS PROJECT IS TO CONSOLIDATE RADIATION THERAPY FUNCTIONS TO ONE AREA OF THE VA JAMAICA PLAIN MEDICAL CENTER AND IMPROVE PATIENT TREATMENT WORKFLOW. THE PROJECT INCLUDES 690SF ADDITION WITHIN THE EXISTING EXTERIOR COURTYARD. 775SF OF SPACE WITHIN THE EXISTING RADIATION THERAPY DEPARTMENT WILL BE REPURPOSED. 1,291SF OF EXISTING
SPACES WILL BE REFRESHED.
THE RADIATION THERAPY DEPARTMENT IS IN THE BASEMENT LEVEL, WING D.
THE SCOPE OF WORK INCLUDES THE RECONSTRUCTION OF EXISTING AREAS AND AN ADDITION.
THE EXISTING BUILDING WET-PIPE SPRINKLER SYSTEM WILL BE MODIFIED THROUGHOUT ALL HEATED/CONDITIONED AREAS OF THE RECONSTRUCTED BUILDING. THE EXISTING WET-PIPE SPRINKLER SYSTEM WILL BE EXTENDED THROUGHOUT ALL
HEATED/CONDITIONED AREAS OF THE BUILDING ADDITION.
THE EXISTING FIRE ALARM SYSTEM WILL BE MODIFIED TO INCLUDE NEW DEVICES FOR THE RECONSTRUCTED AREA AND EXTENDED TO
INCLUDE NEW DEVICES FOR THE ADDITION.
1.1 SCOPE OF WORK
VA HAS ADOPTED THE NATIONAL FIRE CODES (NFC) PUBLISHED BY THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), WHICH ESTABLISH A MINIMUM ACCEPTABLE LEVEL OF LIFE SAFETY AND PROPERTY PROTECTION. LIFE SAFETY REQUIREMENTS ARE SPECIFICALLY ADDRESSED IN THE LIFE SAFETY CODE, NFPA 101. WHERE CONFLICTS EXIST BETWEEN CODES, THE DESIGNER SHALL FOLLOW THE CODE SPECIFIED IN THE TEXT UNDER THE SUBJECT SECTION OF THIS VA FIRE PROTECTION DESIGN MANUAL. FIRE PROTECTION DESIGN SHALL BE BASED ON THE LATEST EDITIONS OF THE NFC AT THE DATE OF AWARD. SEE CODES AND STANDARDS
SECTION FOR EDITIONS USED.
FIRE PROTECTION FEATURES NOT ADDRESSED BY THE NFC OR OTHERWISE ADDRESSED BY THIS DOCUMENT SHALL BE DESIGNED TO COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE INTERNATIONAL BUILDING CODE (IBC).
FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS BY NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF
THE IBC REQUIREMENTS ARE DIFFERENT).
1.2 APPLICATION
BUILDING CONSTRUCTION AND SAFETY CODE NFPA 5000, 2021
STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS NFPA 241, 2019
STANDARD ON TYPES OF BUILDING CONSTRUCTION NFPA 220, 2021
STANDARD FOR FIRE SAFETY AND EMERGENCY SYMBOLS NFPA 170, 2021
LIFE SAFETY CODE NFPA 101, 2021
STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS NFPA 90A, 2021
NATIONAL FIRE ALARM AND SIGNALING CODE NFPA 72, 2019
NATIONAL ELECTRIC CODE NEC 70, 2020
STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS THEIR APPURTENANCES NFPA 24, 2019
STANDARD FOR INSTALLATION OF SPRINKLER SYSTEMS NFPA 13, 2019
FIRE CODE NFPA 1, 2021
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
INTERNATIONAL BUILDING CODE (IBC) 2021
ARCHITECTURAL BARRIERS ACT
VA A/E DESIGN SUBMISSION REQUIREMENTS FOR MINOR AND NRM CONSTRUCTION PROGRAM PG-18-15 VOLUME C, NOVEMBER 2008
PG-18-10, DESIGN MANUALS: FIRE PROTECTION EIGHTH EDITION, JUNE 2021
1.3 APPLICABLE FIRE PROTECTION AND LIFE SAFETY RELATED CODES AND STANDARDS
SEPARATE ALL OCCUPIED AREAS FROM DEMOLITION, RENOVATION, OR CONSTRUCTION ACTIVITIES BY TEMPORARY SMOKE-TIGHT CONSTRUCTION PARTITIONS OF GYPSUM BOARD OR OTHER APPROVED NON-COMBUSTIBLE OR LIMITED-COMBUSTIBLE MATERIAL.
PARTITIONS SHALL BE FULL HEIGHT, EXTENDING THROUGH SUSPENDED CEILINGS TO THE FLOOR SLAB OR ROOF DECK ABOVE AND SHALL BE ONE-HOUR FIRE RATED, UNLESS SPRINKLERS ARE INSTALLED AND ARE OPERATIONAL ON BOTH SIDES OF THE TEMPORARY PARTITION WHEREUPON THE PARTITION MAY BE PERMITTED TO TERMINATE AT THE CEILING IN ACCORDANCE WITH NFPA 241. WHERE THE CEILING ON ONE SIDE OF THE TEMPORARY CONSTRUCTION BARRIER HAS BEEN REMOVED, THE TEMPORARY PARTITION MUST
EXTEND TO THE DECK ABOVE.
PHASE CONSTRUCTION AS NECESSARY TO ENSURE THAT OBSTRUCTION OF EXITS IS MINIMIZED OR AVOIDED. IF EXITS ARE OBSTRUCTED DURING CONSTRUCTION, PROVIDE ALTERNATE EXIT ROUTES DURING EACH PHASE OF CONSTRUCTION AND IDENTIFY
THE ALTERNATE ROUTES ON THE CONSTRUCTION DRAWINGS.
MINIMIZE OR AVOID DISRUPTIONS TO FIRE ALARM AND SPRINKLER SYSTEMS. DELINEATE PHASING OF CONSTRUCTION TO ENSURE THAT INSTALLATIONS OF NEW SYSTEMS ARE EXPEDITED, AND WHERE POSSIBLE, MAINTAIN EXISTING SYSTEMS IN SERVICE UNTIL THE REPLACEMENT SYSTEM IS OPERATIONAL. IF FIRE PROTECTION SYSTEMS ARE TO BE DISRUPTED, ENSURE PROCEDURES ARE INCORPORATED TO MAINTAIN EQUIVALENT LEVELS OF FIRE PROTECTION AND PROVIDE FORMAL NOTIFICATION TO THE FACILITY WHILE SYSTEMS ARE DOWN. ALL PLANNED FIRE PROTECTION SYSTEM SHUTDOWNS OR OUTAGES ARE TO BE COORDINATED WITH THE VA COR
AT LEAST 3 BUSINESS DAYS IN ADVANCE.
1.4 FIRE PROTECTION DURING CONSTRUCTION
ANY BUILDING UNDERGOING RECONSTRUCTION SHALL COMPLY WITH THE REQUIREMENTS OF THE APPLICABLE EXISTING OCCUPANCY
CHAPTERS AND §43.6 OF THE LIFE SAFETY CODE [NFPA 101 §43.1.2.1].
A RECONSTRUCTION SHALL COMPLY WITH ALL OF THE FOLLOWING [NFPA 101 §43.6.1]:
•NFPA 101 §43.6 – RECONSTRUCTION
•NFPA 101 §43.5 – MODIFICATION, EXCEPT THAT ANY STAIRWAY REPLACING AN EXISTING STAIRWAY SHALL BE PERMITTED TO COMPLY
WITH NFPA 101 §7.2.2.2.1.1(3)
•NFPA 101 §43.4 – RENOVATIONS
THE MEANS OF EGRESS SHALL COMPLY WITH THE REQUIREMENTS APPLICABLE TO THE EXISTING OCCUPANCY CHAPTER, AS MODIFIED BY NFPA 101 §43.6.2 [NFPA 101 §43.6.2]. MEANS OF EGRESS IN REHABILITATION WOK AREAS SHALL BE PROVIDED WITH ILLUMINATION, EMERGENCY LIGHTING, AND MARKING OF MEANS OF EGRESS IN ACCORDANCE WITH THE REQUIREMENTS OF OTHER SECTIONS OF
NFPA 101 APPLICABLE TO NEW CONSTRUCTION FOR THE OCCUPANCY.
ANY BUILDING UNDERGOING ADDITION SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 101 §43.8 [NFPA 101 §43.1.2.3].
WHERE AN ADDITION IS MADE TO A BUILDING, BOTH OF THE FOLLOWING CRITERIA SHALL BE MET [NFPA 101 §43.8.1.1]:
1.THE ADDITION SHALL COMPLY WITH OTHER SECTIONS OF NFPA 101 APPLICABLE TO NEW CONSTRUCTION FOR THE OCCUPANCY 2.THE EXISTING PORTION OF THE BUILDING SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 101 TO EXISTING BUILDING FOR THE
OCCUPANCY.
AN ADDITION SHALL NOT CREATE OR EXTEND ANY NON-CONFORMITY WITH REGARD TO FIRE SAFETY OR THE MEANS OF EGRESS IN THE
EXISTING BUILDING FOR WHICH THE ADDITION IS CONSTRUCTED [NFPA 101 §43.8.1.2].
ANY REPAIR, RENOVATION, ALTERATION, OR RECONSTRUCTION WORK WITHIN AN EXISTING BUILDING TO WHICH AN ADDITION IS BEING MADE SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 101 §43.3, 43.4, 43.5, 43.6 [NFPA 101 §43.8.1.3].
THE EXISTING OCCUPANCY CLASSIFICATION OF THE RADIATION THERAPY DEPARTMENT IS BUSINESS IN ACCORDANCE WITH NFPA 101.
THE NEW OCCUPANCY USE OF AREA OF REHABILITATION AND THE ADDITION WILL BE BUSINESS.
1.5 NFPA 101 BUILDING REHABILITATION
TOTAL BUILDING AREA [SF] 12,000 69,000
FLOOR AREA PER STORY WITH FRONTAGE INCREASE [SF] 12,000 69,000
FLOOR AREA PER STORY WITHOUT FRONTAGE INCREASE [SF] 12,000 69,000
B
OCCUPANCY CLASSIFICATION PROVIDED LIMIT
OCCUPANCY CLASSIFICATION FLOOR AREA PER STORY
W/O FRONTAGE [SF]
FLOOR AREA PER STORY WITH
FRONTAGE [SF]
MAXIMUM FLOOR AREA PER STORY PROVIDED [SF] TOTAL BUILDING FLOOR AREA
PROVIDED [SF]
FRONTAGE INCREASE 0
WIDTH OF PUBLIC WAY OR OPEN SPACE [FT] 0
TOTAL BUILDING PERIMETER [FT] 0
BUILDING PERIMETER THAT FRONTS PUBLIC WAY OR OPEN SPACING ≥ 20 FT. [FT] 0
SPRINKLER SYSTEM SM
CONSTRUCTION TYPE IIB
BUILDING WHERE SCOPE OF WORK AREA IS LOCATED AND VA BUILDINGS THAT ARE ADJACENT TO THE WORK AREA ARE FULLY SPRINKLER PROTECTED. NO
BUILDING SEPARATION REQUIREMENTS ARE REQUIRED.
THE REQUIREMENTS FOR FIRE RESISTANCE RATINGS OF EXTERIOR WALLS, MAXIMUM AREA FOR EXTERIOR WALL OPENINGS, AND OPENING PROTECTION SHALL
COMPLY WITH THE IBC EXCEPT AS FOLLOWS:
THERE ARE NO REQUIREMENTS FOR SEPARATION OR OPENINGS BETWEEN VA BUILDINGS WHEN BOTH (ALL) BUILDINGS ARE FULLY SPRINKLER PROTECTED.
THIS EXCEPTION DOES NOT APPLY TO VA BUILDINGS THAT ARE ADJACENT TO NON-VA PROPERTY LINES.
BUILDING SEPARATION REQUIREMENTS ARE IDENTIFIED IN IBC TABLE 705.5 AND OPENING REQUIREMENTS ARE IDENTIFIED IN IBC TABLE 705.8. THERE ARE NO REQUIREMENTS IN THE IBC WHERE GREATER THAN 60 FEET OF SEPARATION BETWEEN BUILDINGS OR GREATER THAN 30 FEET OF SEPARATION BETWEEN A
BUILDING AND A PROPERTY LINE OCCURS.
2.2 BUILDING SEPARATION
NO INTERSTITIAL SPACE IS BEING PROVIDED AS PART OF THIS PROJECT. THIS SECTION IS NOT APPLICABLE.
2.3 VA HOSPITAL BUILDING SYSTEM (INTERSTITIAL)
BUSINESS [NFPA 101 §38.3.3.2] CLASS C CLASS C CLASS C N/A
OCCUPANCY USE EXIT ENCLOSURE LOBBIES AND CORRIDORS OTHER SPACES FLOOR FINISH
INTERIOR FINISH RATINGS PROVIDED MEET OR EXCEED THE MOST RESTRICTIVE REQUIREMENTS FOR EACH OCCUPANCY IDENTIFIED BELOW. WHERE AN OCCUPANCY REQUIRES A MORE RESTRICTIVE FINISH RATING WITHIN THE EXIT ENCLOSURE, LOBBY, CORRIDOR, OR FLOOR FINISH COLUMN(S) THAN ANOTHER OCCUPANCY, THE MOST RESTRICTIVE FINISH RATING WITHIN THAT COLUMN SHALL APPLY TO ALL OCCUPANCIES.
WHERE AN APPROVED AUTOMATIC SPRINKLER SYSTEM IS INSTALLED FINISH RATINGS ARE PERMITTED TO BE REDUCED. FINISH RATINGS IDENTIFIED BELOW INCLUDE THE REDUCTION FOR AN AUTOMATIC SPRINKLER SYSTEM INSTALLED WITHIN THE BUILDING [NFPA 101 §10.2.8.1 & §10.2.8.2].
2.4 INTERIOR FINISH
SITE ACCESS IS NOT MODIFIED BY THIS PROJECT.
ACCESS FOR EMERGENCY VEHICLES SHALL BE IN ACCORDANCE WITH NFPA 1.
2.5 SITE CONSIDERATIONS
COMPLY WITH IBC.
2.6 INSULATION, INCLUDING FOAM PLASTIC
ROOF COVERINGS SHALL BE APPROVED OR LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY FOR COMPLIANCE WITH UL STANDARD 790 AND
SHALL BE CLASS B MINIMUM.
ROOF DECK ASSEMBLIES SHALL BE FM CLASS I APPROVED OR SHALL BE UL LISTED AS FIRE-CLASSIFIED.
2.7 ROOF COVERINGS AND ROOF DECK ASSEMBLIES
(a)SEE NFPA 5000 §7.3.2.1.
(b)SEE NFPA 5000 §7.3.
(c)SEE NPFA 220 §4.3.2.12, §4.4.2.3, AND §4.5.6.8.
EXTERIOR NONBEARING WALLS(c) 0(b)/0
INTERIOR NONBEARING WALLS 0/0
ROOF/CEILING ASSEMBLIES 0/0
FLOOR/CEILING ASSEMBLIES 0/0
SUPPORTING A ROOF ONLY 0/0
SUPPORTING ONE FLOOR ONLY 0(b)/0
SUPPORTING MORE THAN ONE FLOOR, COLUMNS, OR OTHER BEARING WALLS 0(b)/0
BEAMS, GIRDERS, TRUSSES, AND ARCHES
SUPPORTING A ROOF ONLY 0/0
SUPPORTING ONE FLOOR ONLY 0(b)/0
SUPPORTING MORE THAN ONE FLOOR, COLUMNS, OR OTHER BEARING WALLS 0(b)/0
COLUMNS
SUPPORTING A ROOF ONLY 0/0
SUPPORTING ONE FLOOR ONLY 0(b)/0
SUPPORTING MORE THAN ONE FLOOR, COLUMNS, OR OTHER BEARING WALLS 0(b)/0
INTERIOR BEARING WALLS
SUPPORTING A ROOF ONLY 0/2
SUPPORTING ONE FLOOR ONLY 0(b)/2
SUPPORTING MORE THAN ONE FLOOR, COLUMNS, OR OTHER BEARING WALLS 0(b)/2
EXTERIOR BEARING WALLS(a)
BUILDING ELEMENT REQUIRED / PROVIDED [HOUR]
FIRE-RESISTANCE RATING FOR BUILDING ELEMENTS: II [000] [NFPA 220 TABLE 4.1.1]
EXISTING BUILDING IS TYPE II (200) CONSTRUCTION.
FIRE RESISTANCE RATINGS OF STRUCTURAL MEMBERS SHALL BE IN ACCORDANCE WITH NFPA 220.
2.1.A TYPES OF CONSTRUCTION [NFPA 5000]
NFPA 101 DOES NOT PROVIDE CONSTRUCTION REQUIREMENTS FOR BUSINESS
OCCUPANCIES. THE CONSTRUCTION TYPE AS WELL AS HEIGHT AND AREA LIMITATIONS
FOR THE BUILDING SHALL COMPLY WITH THE REQUIREMENTS OF THE IBC.
THE BUILDING CONTAINS BUSINESS OCCUPANCIES.
FOR BUILDINGS WHERE NFPA 101 PROVIDES CONSTRUCTION REQUIREMENTS FOR ONE
OR MORE OF THE OCCUPANCIES WITHIN THE BUILDING, THE TYPE OF CONSTRUCTION
AS WELL AS THE HEIGHT FOR THE BUILDING SHALL COMPLY WITH THE MOST
RESTRICTIVE OCCUPANCY CONSTRUCTION REQUIREMENTS OF NFPA 101.
FOR BUILDINGS WHERE NFPA 101 DOES NOT PROVIDE CONSTRUCTION REQUIREMENTS
FOR ANY OF THE OCCUPANCIES WITHIN THE BUILDING, THE CONSTRUCTION TYPE AS
WELL AS HEIGHT AND AREA LIMITATIONS FOR THE BUILDING SHALL COMPLY WITH THE
REQUIREMENTS OF THE IBC.
2.1.B NFPA 101 CONSTRUCTION REQUIREMENTS
NUMBER OF STORIES 1 4
HEIGHT [FT] 20 75
B
OCCUPANCY CLASSIFICATION PROVIDED
LIMIT
SPRINKLER SYSTEM SM
IIB
CONSTRUCTION TYPE
IBC
2.1.B.1 IBC HEIGHT AND STORIES RESTRICTIONS [IBC TABLE 504.3 AND TABLE 504.4]
COMPLY WITH IBC.
2.8 ROOF ACCESS
THERE ARE NO SHELTERS, PAVILIONS, CONNECTING CORRIDORS, OR SIMILAR STRUCTURES LOCATED NEAR THE ADDITION. THIS SECTION IS NOT APPLICABLE.
2.9 SHELTERS, PAVILIONS, OR SIMILAR STRUCTURES LOCATED NEAR HEALTH CARE BUILDINGS
PROTECTION FROM ANY AREA HAVING A
DEGREE OF HAZARD GREATER THAN THAT
NORMAL TO THE GENERAL OCCUPANCY - ROOMS
FOR GENERAL STORAGE, BOILER OR FURNANCE
ROOMS, AND MAINTENANCE SHOPS THAT
INCLUDE WOODWORKING AND PAINTING AREAS
[NFPA 101 §8.7]
SMOKE PARTITION N/A N/A N/A N/A
SEPARATION FROM HAZARDS
COMPONENTS WALLS AND
PARTITIONS [HOUR]
FIRE DOOR
ASSEMBLIES [HOUR]
MINIMUM FIRE
PROTECTION
WINDOW RATING
[HOUR]
MINIMUM
FIRE-RESISTANCE
WINDOW RATING
[HOUR]
MEP &
COMMUNICATION
PENETRATIONS
[HOUR]
FIRE AND SMOKE BARRIERS SHALL BE PROVIDED AS REQUIRED BY NFPA 101
OPENINGS IN FIRE RATED BARRIERS SHALL BE PROTECTED ACCORDING TO NFPA 101, 80, AND 90A. DOORS IN SUCH OPENINGS SHALL BE NORMALLY CLOSED, UNLESS EQUIPPED WITH ELECTROMAGNETIC DOOR HOLD OPEN DEVICES ARRANGED TO CLOSE UPON ACTIVATION OF THE FIRE ALARM SYSTEM OR SMOKE DETECTOR INSTALLED PROXIMATE TO THE DOOR. FIRE SHUTTERS SHALL BE PROVIDED TO PROTECT OPENINGS IN FIRE RATED BARRIERS DESIGNED TO BE NORMALLY OPEN. SHUTTERS SHALL BE DESIGNED TO CLOSE UPON ACTIVATION OF A SMOKE DETECTOR PROXIMATE TO THE SHUTTER. SUCH DETECTORS SHALL CLOSE ALL SHUTTERS WITHIN A FIRE BARRIER SERVED. CLOSING SPEED SHALL BE IN ACCORDANCE WITH NFPA 80. FIRE DAMPERS SHALL BE INSTALLED IN FIRE RATED BARRIERS IN ACCORDANCE WITH NFPA 90A. FIRE RATED GLAZING, WHERE USED, SHALL MEET APPLICABLE SAFETY STANDARDS.
2.10 & 2.11 RATED ASSEMBLY AND OPENING PROTECTION REQUIREMENTS
SUITES ARE NOT PROVIDED AS PART OF THIS PROJECT.
2.12 SUITES
TWO EXIT SIGNS ARE NOT REQUIRED TO BE VISIBLE IN AN EXIT ACCESS CORRIDOR.
EXIT SIGNS WITH TRITIUM ARE NOT PERMITTED.
2.13 EXIT SIGNS
B. ACCESS CONTROLLED WHERE PERMITTED BY THE OCCUPANCY CHAPTER
A. DELAYED EGRESS WHERE PERMITTED BY THE OCCUPANCY CHAPTER
DOORS ARE PERMITTED TO BE LOCKED IN THE DIRECTION OF EGRESS TRAVEL UNDER CONDITIONS AS IDENTIFIED IN NFPA 101 AS FOLLOWS:
2.14 DOOR LOCKING REQUIREMENTS
STORAGE ROOMS SHALL BE CONSIDERED HAZARDOUS AREAS AND SHALL COMPLY WITH APPROPRIATE OCCUPANCY CHAPTER REQUIREMENTS OF NFPA 101.
STORAGE
3 SPECIAL PROTECTION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
523-417
BLDG 1, D-WING
JAMAICA PLAIN, MA
RADIATION THERAPY EXPANSION
VAMC
C U s e rs \L th o m a s .S
T A
N T
O N
\D o c u m e n ts
\4
S E
S V
A J
P R
A D
IA
T
IO
N
T H
E R
A P
Y
F
IR
E R lt h o m a s N
Q U
.r v t
/1
/2
:5
:2
A
M
LS002
LIFE SAFETY BUILDING CODES
ANALYSIS
09/17/21 D.
FUECKER
D. LITTLE
TOTAL 170
SOUTH
DIRECT TO
EXTERIOR
EXTERIOR 0 36 0 170 170
EXIT TYPE DISCHARGE STAIR WIDTH
[INCHES]
DOOR WIDTH
[INCHES]
STAIR CAPACITY DOOR CAPACITY LIMITING
CAPACITY
RADIATION THERAPY EXITS
EXISTING BUSINESS [NFPA 101 §39.2.5] 100 50 300
NEW BUSINESS [NFPA 101 §38.2.5] 100 50 300
OCCUPANCY MAXIMUM COMMON PATH
OF TRAVEL [FT]
MAXIMUM DEAD-END
CORRIDOR [FT]
MAXIMUM TRAVEL
DISTANCE [FT]
MEANS OF EGRESS SHALL BE ARRANGED TO MEET THE REQUIREMENTS OF THE LIFE SAFETY CODE. REFER TO TABLE PROVIDED FOR MAXIMUM COMMON PATH OF TRAVEL, DEAD-END CORRIDOR, AND TRAVEL DISTANCE ALLOWED. REFER TO LIFE SAFETY FLOOR PLANS FOR
MAXIMUM COMMON PATH OF TRAVEL, DEAD-END CORRIDOR, AND TRAVEL DISTANCE PROVIDED.
MEANS OF EGRESS FOR THE RECONSTRUCTION AREA SHALL COMPLY WITH THE REQUIREMENTS APPLICABLE TO THE EXISTING OCCUPANCY CHAPTER. MEANS OF EGRESS FOR THE ADDITION SHALL COMPLY WITH REQUIREMENTS APPLICABLE TO THE NEW
CONSTRUCTION FOR THE OCCUPANCY.
ARRANGEMENT OF MEANS OF EGRESS
THE RADIATION THERAPY DEPARTMENT CONTAINS BUSINESS OCCUPANCY.
OCCUPANCY CLASSIFICATIONS ARE DEFINED IN NFPA 101.
4 OCCUPANCY CLASSIFICATION
ASSEMBLY - LESS CONCENTRATED USE, WITHOUT FIXED SEATING NON-CONCENTRATED 15
STORAGE - IN OTHER THAN STORAGE AND MERCANTILE OCCUPANCIES STORAGE 500
GENERAL AND HIGH HAZARD INDUSTRIAL GEN. & HIGH HAZ. 100
BUSINESS BUSINESS 150
NFPA 101 OCCUPANCY USE ABBREVIATION OCCUPANT LOAD FACTOR
5.0 OCCUPANCY LOAD ABBREVIATION LEGEND
RT-038 OFFICE BUSINESS 81 150 GROSS BUSINESS
RT-039 MED CLOSET STORAGE 14 500 GROSS BUSINESS
RT-020A HOLDING BUSINESS 86 150 GROSS BUSINESS
RT-012 H.C. TOILET BUSINESS 45 150 GROSS BUSINESS
RT-000A CLOSET STORAGE 4 500 GROSS BUSINESS
RT-010 GOWNED WAITING NON-CONCENTRATED 84 15 5 BUSINESS
RT-001B CLOSET STORAGE 18 500 GROSS BUSINESS
RT-003 STAFF TOILET BUSINESS 42 150 GROSS BUSINESS
RT-008 PHYSICS LAB / SOILED UTILITY STORAGE 54 500 GROSS BUSINESS
RT-006 ELEC STORAGE 84 500 GROSS BUSINESS
RT-005 JAN STORAGE 8 500 GROSS BUSINESS
RT-009 WHEELCHAIR STORAGE STORAGE 102 500 GROSS BUSINESS
RT-007 EXAM BUSINESS 136 150 GROSS BUSINESS
RT-002 OFFICE/SWING BUSINESS 244 150 GROSS BUSINESS
RT-001A RECEPTION BUSINESS 157 150 GROSS BUSINESS
RT-001 WAITING NON-CONCENTRATED 495 15 33 BUSINESS
RT-018 TREATMENT BUSINESS 557 150 GROSS BUSINESS
RT-027 DOSIMETRY BUSINESS 168 150 GROSS BUSINESS
RT-025 CONTROL ROOM BUSINESS 95 150 GROSS BUSINESS
RT-029 OFFICE BUSINESS 75 150 GROSS BUSINESS
RT-028 OFFICE BUSINESS 76 150 GROSS BUSINESS
RT-030 OFFICE BUSINESS 151 150 GROSS BUSINESS
RT-024 OFFICE BUSINESS 91 150 GROSS BUSINESS
RT-023 CLEAN UTILITY STORAGE 86 500 GROSS BUSINESS
RT-017 NURSE BUSINESS 42 150 GROSS BUSINESS
RT-022 OFFICE BUSINESS 73 150 GROSS BUSINESS
RT-026 LIN ACC TREATMENT BUSINESS 586 150 GROSS BUSINESS
RT-032 DOSIMETRIST BUSINESS 77 150 GROSS BUSINESS
RT-031 OFFICE BUSINESS 153 150 GROSS BUSINESS
RT-033 PHYSICIST BUSINESS 79 150 GROSS BUSINESS
RT-021 OFFICE BUSINESS 100 150 GROSS BUSINESS
RT-020 CONTROL ROOM BUSINESS 87 150 GROSS BUSINESS
RT-004 TELE/DATA STORAGE 81 500 GROSS BUSINESS
RT-017A NURSE BUSINESS 80 150 GROSS BUSINESS
RT-037 ELEC STORAGE 22 500 GROSS BUSINESS
RT-035 CLOSET STORAGE 15 500 GROSS BUSINESS
RT-034 CLOSET STORAGE 24 500 GROSS BUSINESS
STORAGE STORAGE 51 500 GROSS BUSINESS
RT-019 H.C. TOILET BUSINESS 49 150 GROSS BUSINESS
RT-016 INTERVIEW/VITALS BUSINESS 62 150 GROSS BUSINESS
RT-014 EXAM BUSINESS 94 150 GROSS BUSINESS
RT-013 EXAM BUSINESS 96 150 GROSS BUSINESS
RT-011 CHANGING BUSINESS 47 150 GROSS BUSINESS
ROOM NUMBER ROOM NAME NFPA 101 USE AREA [SF]
OCCUPANT
LOAD
FACTOR
CALCULATED
OCCUPANT LOAD
NFPA
CLASSIFICATION
OCCUPANCY USE SUMMARY
NON-CONCENTRATED 579 15 38
STORAGE 563 500 2
BUSINESS 8,010 150 54
TOTAL 9,152 94
OCCUPANCY USE AREA [SF]
OCCUPANT
LOAD FACTOR
OCCUPANT LOAD
OCCUPANT LOAD SUMMARY
OCCUPANT LOAD 94
TOTAL EXIT CAPACITY 210
NUMBER OF HORIZONTAL EXITS / CAPACITY 0 / 0
NUMBER OF EXTERIOR EXITS / CAPACITY 1 / 210
NUMBER OF INTERIOR EXITS / CAPACITY 0 / 0
NUMBER OF EXITS REQUIRED / PROVIDED 2 / 3
MINIMUM CORRIDOR WIDTH - REQUIRED / PROVIDED [IN] 36 / 72
MINIMUM DOOR WIDTH - REQUIRED / PROVIDED [IN] 32 / 36
MINIMUM STAIR WIDTH - REQUIRED / PROVIDED [IN] N/A
NEW OR EXISTING FLOOR ADDITION COMPLY WITH NEW, MODIFICATION COMPLY
WITH EXISTING
RESTRICTIVE OCCUPANCY TYPE BUSINESS (NFPA 101 38.2.2 FOR NEW AND 39.2.2 FOR
EXISTING)
FLOOR BASEMENT FLOOR
RADIATION THERAPY EXPANSION MEANS OF EGRESS ANALYSIS
2FB
F
B F
B F
B F
B F
B F
B F
B
DN
B B
F
B CA D EA1 D1
5.1
WAITING
RT-001
CLOSET
OFFICE
OFFICE
RT-006
STORAGE
RAD THERAPY
CALIBRATION
LAB
RT-004
WOMEN'S
TOILET
RT-003AOFFICE/SWING
RT-002
EXAM
RT-007
GOWNED
WAITING
RT-010
H.C. TOILET
RT-012
EXAM
RT-013
EXAM
RT-014
NURSE
RT-016
STAFF TOILET
RT-019
STORAGE
RT-020
OFFICE
RT-021
LIN. ACC.
TREATMENT
RT-026
OFFICE
RT-023
OFFICE
RT-030
CLOSET
OFFICE
RT-031
PHYSICIST
RT-033
DOSIMETRY
RT-034
MECH
B10-A
ELEC
RT-037
Room
Room
Room
Room
Room
CYBERKNIFE
TREATMENT
RT-018
JAN
RT-005
CHANGING
RT-011
DOSIMETRIST
RT-032
CONTROL
ROOM
COURTYARD
CONTROL
ROOM
RECEPTION
HOLDING BAY
EQUIPMENT
ROOM
ENTRANCE
MAZE
ALCOVE
ALCOVE
ALCOVE
- 1
DE-1A
CP-1A
C P
-1 B
TP-1A
CP-1C
TP-1B
TP-1C
LEGEND
WORK AREA DURING PHASE
NOT IN WORK AREA
EXIT DISCHARGE PATH, FOR REFERENCE ONLY
B CA D EA1 D1
5.1
TEMP OFFICE
DE-1A
CP-1A
C P
-1 B
DE-1B
CP-1C
TP-1A
TP-1B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
523-417
BLDG 1, D-WING
JAMAICA PLAIN, MA
RADIATION THERAPY EXPANSION
VAMC
C U s e rs \L th o m a s .S
T A
N T
O N
\D o c u m e n ts
\4
S E
S V
A J
P R
A D
IA
T
IO
N
T H
E R
A P
Y
F
IR
E R lt h o m a s N
Q U
.r v t
/1
/2
:5
:1
A
M
LS101
LIFE SAFETY FLOOR PLAN -
EXISTING
09/17/21 D.
FUECKER
D. LITTLE
3/32" = 1'-0"F1
LIFE SAFETY FLOOR PLAN - EXISTING
0 4'-0" 8'-0" 16'-0"
1 EXISTING EXIT DISCHARGE INTO COURTYARD TO BE MAINTAINED
DURING DEMOLITION AND CONSTRUCTION.
2 MAINTAIN CLEAR WIDTH OF 44 INCHES.
3 PROTECTION OF PEDESTRIANS SHALL BE IN ACCORDANCE WITH IBC
SECTION 3306 DURING CONSTRUCTION AND DEMOLITION ACTIVITIES.
WALKWAY SHALL NOT BE LESS THAN 4 FEET IN WIDTH.
4 STAIRS TO BE PROVIDED FOR EXIT DISCHARGE PRIOR TO
DEMOLITION OF EXISTING EGRESS RAMP.
5 CONTINUATION OF EXIT DISCHARGE TO PUBLIC WAY.
6 EXISTING EGRESS RAMP TO BE DEMOLISHED AT START OF PHASE 1.
7 TEMPORARY EXIT DOOR AND STAIR TO BE COMPLETED PRIOR TO
START OF PHASE 1 AND TO BE REMOVED PRIOR TO START OF PHASE
2.
KEYED NOTES
3/32" = 1'-0"F5
LIFE SAFETY FLOOR PLAN - PHASE 1
0 4'-0" 8'-0" 16'-0"
GENERAL NOTES
A. SEPARATE ALL OCCUPIED AREAS FROM DEMOLITION, RENOVATION, OR
CONSTRUCTION ACTIVITIES BY TEMPORARY SMOKE-TIGHT
CONSTRUCTION PARTITIONS OF GYPSUM BOARD OR OTHER APPROVED
NON-COMBUSTIBLE OR LIMITED-COMBUSTIBLE MATERIAL. PARTITIONS
SHALL BE FULL HEIGHT, EXTENDING THROUGH SUSPENDED CEILINGS
TO THE FLOOR SLAB OR ROOF DECK ABOVE AND SHALL BE ONE-HOUR
FIRE RATED, UNLESS SPRINKLERS ARE INSTALLED AND ARE
OPERATIONAL ON BOTH SIDES OF THE TEMPORARY PARTITION
WHEREUPON THE PARTITION MAY BE PERMITTED TO TERMINATE AT
THE CEILING IN ACCORDANCE WITH NFPA 241. WHERE THE CEILING ON
ONE SIDE OF THE TEMPORARY CONSTRUCTION BARRIER HAS BEEN
REMOVED, THE TEMPORARY PARTITION MUST EXTEND TO THE DECK
ABOVE.
B. PROVIDE TEMPORARY EXIT SIGNAGE AND WARNING SIGNS TO NOTIFY
OCCUPANTS OF TEMPORARY EGRESS ROUTES. CONTRACTOR TO
COORDINATE WITH THE MEDICAL CENTER SAFETY COMMITTEE TO
DETERMINE ILSMS IN ACCORDANCE WITH MEDICAL CENTER POLICY.
PHASE 1 TRAVEL PATHS
TYPE NAME DISTANCE [FT-IN]
COMMON PATH OF TRAVEL CP-1A 56' - 1"
COMMON PATH OF TRAVEL CP-1B 42' - 6"
COMMON PATH OF TRAVEL CP-1C 131' - 11"
DEAD END PATH DE-1A 37' - 5"
DEAD END PATH DE-1B 46' - 2"
TOTAL TRAVEL PATH TP-1A 261' - 5"
TOTAL TRAVEL PATH TP-1B 139' - 5"
EXISTING TRAVEL PATHS
TYPE NAME DISTANCE [FT-IN]
COMMON PATH OF TRAVEL CP-1A 56' - 2"
COMMON PATH OF TRAVEL CP-1B 42' - 6"
COMMON PATH OF TRAVEL CP-1C 90' - 8"
DEAD END PATH DE-1A 37' - 5"
TOTAL TRAVEL PATH TP-1A 126' - 10"
TOTAL TRAVEL PATH TP-1B 229' - 7"
TOTAL TRAVEL PATH TP-1C 142' - 1"
DN
B B
F
DN
B
B F
DN
B B
F
B CA D EA1 D1
5.1
TEMP
OFFICE
TEMP
OFFICE
TEMP
OFFICE
(FROM
PHASE 1)
DE-1A
CP-1A
C P
-1 B
DE-1B
TP-1A
CP-1C
TP-1B
TP-1C
CP-1D
TP-1D
B CA D EA1 D1
5.1
TEMP PATIENT
HOLDING
TEMP
OFFICE
TEMP
OFFICE
TEMP
OFFICE
(FROM
PHASE 1)
DE-1A
C P
-1 B
CP-1A
TP-1A
CP-1C
TP-1B
CP-1D
TP-1C
TP-1D
B CA D EA1 D1
5.1
TEMP
OFFICE
(MOVED
FROM
PHASE 1)
TEMP PATIENT
HOLDING
NEW
DOSYMETRY
TEMP
OFFICE
(MOVED
FROM
PHASE 2)
DE-1A
CP-1B
TP-1B
CP-1A
TP-1A
DE-1B
TP-1C
CP-1C
TP-1D
LEGEND
WORK AREA DURING PHASE
NOT IN WORK AREA
EXIT DISCHARGE PATH, FOR REFERENCE ONLY
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
523-417
BLDG 1, D-WING
JAMAICA PLAIN, MA
RADIATION THERAPY EXPANSION
VAMC
C U s e rs \L th o m a s .S
T A
N T
O N
\D o c u m e n ts
\4
S E
S V
A J
P R
A D
IA
T
IO
N
T H
E R
A P
Y
F
IR
E R lt h o m a s N
Q U
.r v t
/1
/2
:5
:3
A
M
LS102
LIFE SAFETY FLOOR PLAN -
PHASING
09/17/21 D.
FUECKER
D. LITTLE
3/32" = 1'-0"F1
LIFE SAFETY FLOOR PLAN - PHASE 2
0 4'-0" 8'-0" 16'-0" 3/32" = 1'-0"F3
LIFE SAFETY FLOOR PLAN - PHASE 3
0 4'-0" 8'-0" 16'-0" 3/32" = 1'-0"F6
LIFE SAFETY FLOOR PLAN - PHASE 4
0 4'-0" 8'-0" 16'-0"
1 EXISTING EXIT DISCHARGE INTO COURTYARD TO BE
MAINTAINED DURING DEMOLITION AND CONSTRUCTION.
2 MAINTAIN CLEAR WIDTH OF 44 INCHES.
3 PROTECTION OF PEDESTRIANS SHALL BE IN ACCORDANCE
WITH IBC SECTION 3306 DURING CONSTRUCTION AND
DEMOLITION ACTIVITIES. WALKWAY SHALL NOT BE LESS THAN
4 FEET IN WIDTH.
4 STAIRS TO BE PROVIDED FOR EXIT DISCHARGE PRIOR TO
DEMOLITION OF EXISTING EGRESS RAMP.
5 CONTINUATION OF EXIT DISCHARGE TO PUBLIC WAY.
KEYED NOTES
GENERAL NOTES
A. SEPARATE ALL OCCUPIED AREAS FROM DEMOLITION,
RENOVATION, OR CONSTRUCTION ACTIVITIES BY TEMPORARY
SMOKE-TIGHT CONSTRUCTION PARTITIONS OF GYPSUM BOARD OR
OTHER APPROVED NON-COMBUSTIBLE OR LIMITED-COMBUSTIBLE
MATERIAL. PARTITIONS SHALL BE FULL HEIGHT, EXTENDING
THROUGH SUSPENDED CEILINGS TO THE FLOOR SLAB OR ROOF
DECK ABOVE AND SHALL BE ONE-HOUR FIRE RATED, UNLESS
SPRINKLERS ARE INSTALLED AND ARE OPERATIONAL ON BOTH
SIDES OF THE TEMPORARY PARTITION WHEREUPON THE
PARTITION MAY BE PERMITTED TO TERMINATE AT THE CEILING IN
ACCORDANCE WITH NFPA 241. WHERE THE CEILING ON ONE SIDE
OF THE TEMPORARY CONSTRUCTION BARRIER HAS BEEN
REMOVED, THE TEMPORARY PARTITION MUST EXTEND TO THE
DECK ABOVE.
B. PROVIDE TEMPORARY EXIT SIGNAGE AND WARNING SIGNS TO
NOTIFY OCCUPANTS OF TEMPORARY EGRESS ROUTES.
CONTRACTOR TO COORDINATE WITH THE MEDICAL CENTER
SAFETY COMMITTEE TO DETERMINE ILSMS IN ACCORDANCE WITH
MEDICAL CENTER POLICY.
PHASE 2 TRAVEL PATHS
TYPE NAME DISTANCE [FT-IN]
COMMON PATH OF TRAVEL CP-1A 56' - 3"
COMMON PATH OF TRAVEL CP-1B 42' - 6"
COMMON PATH OF TRAVEL CP-1C 85' - 11"
COMMON PATH OF TRAVEL CP-1D 28' - 2"
DEAD END PATH DE-1A 37' - 5"
DEAD END PATH DE-1B 16' - 8"
TOTAL TRAVEL PATH TP-1A 151' - 0"
TOTAL TRAVEL PATH TP-1B 227' - 0"
TOTAL TRAVEL PATH TP-1C 42' - 11"
TOTAL TRAVEL PATH TP-1D 141' - 0"
PHASE 3 TRAVEL PATHS
TYPE NAME DISTANCE [FT-IN]
COMMON PATH OF TRAVEL CP-1A 56' - 1"
COMMON PATH OF TRAVEL CP-1B 42' - 6"
COMMON PATH OF TRAVEL CP-1C 87' - 0"
COMMON PATH OF TRAVEL CP-1D 26' - 11"
DEAD END PATH DE-1A 37' - 5"
TOTAL TRAVEL PATH TP-1A 152' - 2"
TOTAL TRAVEL PATH TP-1B 225' - 10"
TOTAL TRAVEL PATH TP-1C 42' - 0"
TOTAL TRAVEL PATH TP-1D 141' - 0"
PHASE 4 TRAVEL PATHS
TYPE NAME DISTANCE [FT-IN]
COMMON PATH OF TRAVEL CP-1A 55' - 4"
COMMON PATH OF TRAVEL CP-1B 42' - 6"
COMMON PATH OF TRAVEL CP-1C 27' - 4"
DEAD END PATH DE-1A 37' - 4"
DEAD END PATH DE-1B 16' - 8"
TOTAL TRAVEL PATH TP-1A 148' - 8"
TOTAL TRAVEL PATH TP-1B 152' - 11"
TOTAL TRAVEL PATH TP-1C 40' - 8"
TOTAL TRAVEL PATH TP-1D 141' - 3"
B
F
DN
B
B F
DN
B B
F
B CA D EA1 D1
5.1
NEW
DOSYMETRY
PHASE 5A PHASE 5B
TEMP
OFFICE
(MOVED
FROM
PHASE 2)
TEMP
OFFICE
(MOVED
FROM
PHASE 1)
DE-1A
CP-1A
C P
-1 B
DE-1B
CP-1C
TP-1A
TP-1B
CP-1D
TP-1C
TP-1D
B CA D EA1 D1
5.1
NEW
DOSYMETRY
TEMP WAITING
AND
REGISTRATION
TEMP
WAITING
TEMP
OFFICE
(MOVED
FROM
PHASE 2)
TEMP
OFFICE
(MOVED
FROM
PHASE 1)
DE-1A
DE-1B
CP-1A
C P
-1 B
TP-1B
CP-1C
TP-1A
CP-1D
TP-1C
B CA D EA1 D1
5.1
TEMP
OFFICE
(MOVED
FROM
PHASE 2)
TEMP
OFFICE
(MOVED
FROM
PHASE 1)
NEW
DOSYMETRY
TP-1A
DE-1B
D E
-1 C
TP-1B
CP-1C
TP-1C
CP-1D
TP-1D
LEGEND
WORK AREA DURING PHASE
NOT IN WORK AREA
EXIT DISCHARGE PATH, FOR REFERENCE ONLY
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
523-417
BLDG 1, D-WING
JAMAICA PLAIN, MA
RADIATION THERAPY EXPANSION
VAMC
C U s e rs \L th o m a s .S
T A
N T
O N
\D o c u m e n ts
\4
S E
S V
A J
P R
A D
IA
T
IO
N
T H
E R
A P
Y
F
IR
E R lt h o m a s N
Q U
.r v t
/1
/2
:5
:0
A
M
LS103
LIFE SAFETY FLOOR PLAN -
PHASING
09/17/21 D.
FUECKER
D. LITTLE
3/32" = 1'-0"F1
LIFE SAFETY FLOOR PLAN - PHASE 5
3/32" = 1'-0"F3
LIFE SAFETY FLOOR PLAN - PHASE 6
3/32" = 1'-0"F6
LIFE SAFETY FLOOR PLAN - PHASE 7
0 4'-0" 8'-0" 16'-0" 0 4'-0" 8'-0" 16'-0" 0 4'-0" 8'-0" 16'-0"
1 EXISTING EXIT DISCHARGE INTO COURTYARD TO BE MAINTAINED
DURING DEMOLITION AND CONSTRUCTION.
2 MAINTAIN CLEAR WIDTH OF 44 INCHES.
3 STAIRS TO BE PROVIDED FOR EXIT DISCHARGE PRIOR TO
DEMOLITION OF EXISTING EGRESS RAMP.
4 CONTINUATION OF EXIT DISCHARGE TO PUBLIC WAY.
5 CONSTRUCTION TO OCCUR DURING OFF-HOURS WHEN AREA IS
NOT OCCUPIED.
6 DOORS TO BE KEPT OPEN DURING CONSTRUCTION.
KEYED NOTES
GENERAL NOTES
A. SEPARATE ALL OCCUPIED AREAS FROM DEMOLITION,
RENOVATION, OR CONSTRUCTION ACTIVITIES BY TEMPORARY
SMOKE-TIGHT CONSTRUCTION PARTITIONS OF GYPSUM BOARD
OR OTHER APPROVED NON-COMBUSTIBLE OR LIMITED-
COMBUSTIBLE MATERIAL. PARTITIONS SHALL BE FULL HEIGHT,
EXTENDING THROUGH SUSPENDED CEILINGS TO THE FLOOR SLAB
OR ROOF DECK ABOVE AND SHALL BE ONE-HOUR FIRE RATED,
UNLESS SPRINKLERS ARE INSTALLED AND ARE OPERATIONAL ON
BOTH SIDES OF THE TEMPORARY PARTITION WHEREUPON THE
PARTITION MAY BE PERMITTED TO TERMINATE AT THE CEILING IN
ACCORDANCE WITH NFPA 241. WHERE THE CEILING ON ONE SIDE
OF THE TEMPORARY CONSTRUCTION BARRIER HAS BEEN
REMOVED, THE TEMPORARY PARTITION MUST EXTEND TO THE
DECK ABOVE.
B. PROVIDE TEMPORARY EXIT SIGNAGE AND WARNING SIGNS TO
NOTIFY OCCUPANTS OF TEMPORARY EGRESS ROUTES.
CONTRACTOR TO COORDINATE WITH THE MEDICAL CENTER
SAFETY COMMITTEE TO DETERMINE ILSMS IN ACCORDANCE WITH
MEDICAL CENTER POLICY.
PHASE 5 TRAVEL PATHS
TYPE NAME DISTANCE [FT-IN]
COMMON PATH OF TRAVEL CP-1A 57' - 0"
COMMON PATH OF TRAVEL CP-1B 40' - 11"
COMMON PATH OF TRAVEL CP-1C 84' - 11"
COMMON PATH OF TRAVEL CP-1D 27' - 1"
DEAD END PATH DE-1A 38' - 2"
DEAD END PATH DE-1B 16' - 8"
TOTAL TRAVEL PATH TP-1A 148' - 11"
TOTAL TRAVEL PATH TP-1B 225' - 5"
TOTAL TRAVEL PATH TP-1C 42' - 6"
TOTAL TRAVEL PATH TP-1D 140' - 11"
PHASE 6 TRAVEL PATHS
TYPE NAME DISTANCE [FT-IN]
COMMON PATH OF TRAVEL CP-1A 56'…