Attachment 4 - Plans Drawings.pdf
PDF 10 MB Posted
- Attached to
- Pendleton Building Repairs Project A (Pendleton, OR) Federal contract opportunity
- Solicitation number
- 12905B25R0003
About this file
The provided document is a comprehensive set of architectural and engineering drawings for the USDA Agricultural Research Service's Pendleton Building Repairs Project A located in Adams, Oregon. The drawings cover multiple buildings (001, 002, 003, and 011) at the Columbia Plateau Conservation Research Center and detail extensive mechanical, electrical, plumbing, and architectural repairs and replacements.
The project includes base bid and alternate work scopes across different buildings, with key components including replacing boilers, laboratory faucets, vacuum breakers, air handling units, electrical panels, overhead doors, solar domestic water heater, rooftop units, exhaust fans, roofing, and fume hood systems. The alternates range from Alternate 01 (replacing laboratory equipment in Building 001) to Alternate 11 (replacing a fume hood in Building 011). The drawings provide detailed floor plans, roof plans, electrical layouts, mechanical systems, and technical specifications for each proposed modification, with an emphasis on modernizing aging infrastructure and meeting current code requirements.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SF30_12905B25R0003_0003.pdf | ||
| Attachment 9 Hazardous Building Materials Inspection Report.pdf | ||
| Questions and Answers_12905B25R0003.pdf | ||
| Attachment 8 Revised M-Sheet Drawings.pdf | ||
| SF30_12905B25R0003_0002.pdf | ||
| SF30_12905B25R0003_0001.pdf | ||
| Site Visit Sign-In Sheet.pdf | ||
| Attachment 1 SF1442 Provisions_Clauses.pdf | ||
| Attachment 2 Contract Line-Item Breakdown Form Excel .xlsx | XLSX spreadsheet | |
| Attachment 5 DOL WD OR20250089_02282025.pdf | ||
| Attachment 7 ARS-372 - CONTRACTOR REQUEST FOR PAYMENT TRANSMITTAL.pdf | ||
| Attachment 3 - Technical Specifications.pdf | ||
| Attachment 6 ARS-371 - CONSTRUCTION PROGRESS AND PAYMENT SCHEDULE.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET INDEX
SHEET NUMBER SHEET NAME
GENERAL
G-001 COVER SHEET
ARCHITECTURE
A-001 SYMBOLS & ABBREVIATIONS
A-101 FIRST FLOOR PLAN - BUILDING 001
A-102 FIRST FLOOR PLAN - BUILDING 002
A-103 FIRST FLOOR PLAN - BUILDING 003
A-104 FIRST FLOOR PLAN - BUILDING 011
A-110 ROOF PLAN - BUILDING 001
A-202 ELEVATIONS - BUILDING 002
A-203 ELEVATIONS - BUILDING 003
MECHANICAL
M-001 MECHANICAL LEGENDS, NOTES AND ABBREVIATIONS
M-002 MECHANICAL NOTES
MD-101 BUILDING 001 MECHANICAL FLOOR PLAN DEMOLITION
MD-102 BUILDING 001 MECHANICAL ROOF PLAN DEMOLITION
MD-103 BUILDING 003 MECHANICAL FLOOR PLAN DEMOLITION
MD-104 BUILDING 011 MECHANICAL FLOOR PLANS DEMOLITION
M-101 BUILDING 001 MECHANICAL FLOOR PLAN
M-102 BUILDING 001 MECHANICAL ROOF PLAN
M-103 BUILDING 003 MECHANICAL FLOOR PLANS
M-104 BUILDING 011 MECHANICAL FLOOR PLANS
M-401 MECHANICAL LARGE SCALE PLANS
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
M-602 MECHANICAL SCHEDULES
M-701 MECHANICAL CONTROL DIAGRAMS
PLUMBING
PD-101 BUILDING 001 PLUMBING FLOOR PLAN DEMOLITION
P-101 BUILDING 001 PLUMBING FLOOR PLAN
P-501 PLUMBING DETAILS & SCHEDULES
ELECTRICAL
E-001 ELECTRICAL SHEET INDEX, LEGENDS, NOTES, SYMBOLS, AND ABBREVIATIONS
E-101 ELECTRICAL SITE PLAN
E-102 BUILDING 001 - POWER PLAN
E-103 BUILDING 001 - ELECTRICAL ROOF PLAN
E-104 BUILDING 002 - POWER PLAN
E-105 BUILDING 003 - ELECTRICAL PLANS
E-106 BUILDING 011 - POWER PLANS
E-601 OVERALL ONE-LINE DIAGRAM - EXISTING
E-602 OVERALL ONE-LINE DIAGRAM - NEW
A-301 WALL SECTIONS AND DETAILS
E-701 ELECTRICAL PANEL SCHEDULES
E-702 ELECTRICAL PANEL SCHEDULES
PROJECT SUMMARY
THE USDA RESEARCH CENTER IN PENDLETON CONSISTS OF MULTIPLE BUILDINGS. PROJECT A MODIFIES COMPONENTS OF BUILDINGS 001, 003, AND 011 WHICH WERE CONSTRUCTED BETWEEN 1970 AND 1986.
THIS PROJECT WILL REPLACE AGING MECHANICAL AND ELECTRICAL EQUIPMENT AS WELL AS REPAIR
AND MODERNIZE SEVERAL ARCHITECTURAL ELEMENTS.
ABATEMENT OF HAZARDOUS MATERIALS IS INCLUDED IN THE PROJECT SCOPE, SEE SPECIFICATIONS
028200, 028300, AND 028400.
THE ITEMS TO BE INCLUDED IN THE BASE BID VS ALTERNATES ARE IDENTIFIED THROUGHOUT THE BID
DOCUMENTS AND LISTED HERE:
BASE BID:
REPLACE BOILERS IN BUILDING 001
ALTERNATE 01:
REPLACE LABORATORY FAUCETS AND VACUUM BREAKERS IN BUILDING 001
REPLACE VACUUM PUMP IN BUILDING 001
REPLACE AIR HANDLING UNITS IN BUILDING 003
REPLACE AGING ELECTRICAL PANELS AND PANELS AND ELECTRICAL WORK NOT DIRECTLY
ASSOCIATED WITH THE BASE BID OR ALTERNATES IDENTIFIED BELOW.
LIGHTING SCOPE IN BUILDING 003.
ALTERNATE 02:
REPLACE 5 (FIVE) OVERHEAD DOORS ON BUILDING 003.
ALTERNATE 03:
REPLACE THE SOLAR DOMESTIC WATER HEATER IN BUILDING 001.
ALTERNATE 04:
REPLACE 8 (EIGHT) OVERHEAD DOORS ON BUILDING 002.
ALTERNATE 05:
REPLACE PACKAGED ROOFTOP UNIT IN BUILDING 001.
ALTERNATE 06:
REPLACE GENERAL EXHAUST FANS IN BUILDING 001.
ALTERNATE 07:
REPAIR ROOFING ON BUILDING 001.
ALTERNATE 08:
INSTALL ELECTRICAL POWER AND CONTROLS TO THREE MOTORIZED GARAGE DOORS
LOCATED IN THE EXISTING GARAGE BAYS ADJACENT TO NEW SAMPLE CLEANING ROOM 101.
SEE ELECTRICAL DRAWINGS FOR A DETAILED DESCRIPTION OF WORK THAT IS INCLUDED IN
ALTERNATE 08.
ALTERNATE 09:
DEMOLISH EXISTING FUME HOOD FH-2, EXHAUST FAN EF-4, AND DUCT. INSTALL NEW FUME
HOOD FH-001-02, NEW EXHAUST FAN FX-001-02, DUCTWORK, CONTROLS, AND ELECTRICAL. SEE
MECHANICAL AND ELECTRICAL DRAWINGS FOR DETAILED WORK THAT IS INCLUDED IN
ALTERNATE 09.
ALTERNATE 10:
DEMOLISH EXISTING FUME HOOD FH-1, EXHAUST FAN EF-3, AND DUCT. INSTALL NEW FUME
HOOD FH-001-01, NEW EXHAUST FAN FX-001-01, DUCTWORK, CONTROLS, AND ELECTRICAL. SEE
MECHANICAL AND ELECTRICAL DRAWINGS FOR DETAILED WORK THAT IS INCLUDED IN
ALTERNATE 10.
ALTERNATE 11:
DEMOLISH EXISTING FUME HOOD, EXHAUST FAN, AND DUCT IN BUILDING 011. INSTALL NEW
FUME HOOD FH-011-01, NEW EXHAUST FAN FX-011-01, DUCTWORK, CONTROLS, AND
ELECTRICAL. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR DETAILED WORK THAT IS
INCLUDED IN ALTERNATE 11.
THE NEW EQUIPMENT WILL MEET ALL CURRENT APPLICABLE CODE AND USER REQUIREMENTS.
www.coffman.com
221 N. Wall Street, Suite 500
Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/1
/2
:0
:0
P
M
04/19/2024
TAH
RKC
231290
G-001
COVER SHEET
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
USDA AGRICULTURAL RESEARCH SERVICE
PENDLETON BUILDING REPAIRS PROJECT A
COLUMBIA PLATEAU CONSERVATION
RESEARCH CENTER
OREGON STATE SITE MAP
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
UMATILLA COUNTY
COLUMBIA PLATEAU
CONSERVATION RESEARCH
CENTER
BUILDING 001
BUILDING 003 BUILDING 002 BUILDING 011
REV DATE DESCRIPTION
1 09/18/24 RE-ISSUE FOR BID
01 40
Peter.Lane Polygon
Peter.Lane Callout 9/20/24 USDA: Alternates 1-8 not in contract
DRAWING ABBREVIATIONS DRAWING REFERENCE
01 / A-210
DISCIPLINE:
G- GENERAL
LS LIFE SAFETY
C- CIVIL
A- ARCHITECTURAL
I- INTERIOR
S- STRUCTURAL
M- MECHANICAL
P- PLUMBING
E- ELECTRICAL
SERIES NUMBER
REFERENCE SYMBOLS
SHEET NUMBER WHERE
ELEVATION IS DRAWN
NUMBER OF PLAN,
DETAIL, ETC. ON
SHEET
SHEET NUMBER
WITHIN SERIES
AB ANCHOR BOLT
ABV ABOVE
AC ACOUSTICAL / AIR CONDITIONING
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADDL ADDITIONAL
ADJ ADJUSTABLE
ADJT ADJACENT
A/E ARCHITECT/ENGINEER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGG AGGREGATE
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZE
APPROX APPROXIMATE
ARCH ARCHITECT
AUX AUXILIARY
A/V AUDIO / VISUAL
AVG AVERAGE
B/ BOTTOM OF
B/B BACK TO BACK
B/F BOTTOM OF FOOTING
BD BOARD
BDRY BOUNDARY
BHMA BUILDER'S HARDWARE
MANUFACTURER'S ASSOCIATION
BLDG BUILDING
BLKG BLOCKING
BOS BOTTOM OF STEEL
BOT BOTTOM
BP BASE PLATE
BRG BEARING
BRK BRICK
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
BW BOTH WAYS
CAB CABINET
CB CATCH BASIN
CCTV CLOSED CIRCUIT TV
CD CONSTRUCTION DOCUMENTS
CDR CARD READER
CEM CEMENT
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED
/CONTRACTOR INSTALLED
CFMF COLD-FORMED METAL FRAMING
CG CORNER GUARD
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG HT CEILING HEIGHT
CLO CLOSET
CLR COLOR, CLEARANCE
CLRM CLASSROOM
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
COL COLUMN
COMB COMBINATION
COMM COMMUNICATION
CONC CONCRETE
CONF CONFERENCE
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
CORR CORRIDOR, CORRUGATED
CPT CARPET
CSWK CASEWORK
CT CERAMIC TILE
CTR CENTER
CU FT CUBIC FEET
D DEPTH
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL. DIAGRAM
DIM DIMENSION
DIR DIRECTION
DIST DISTANCE
DL DEAD LOAD
DN DOWN
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
DWG DRAWING
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION
AND FINISH SYSTEM
EB EXPANSION BOLT
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ELEC ELECTRIC
ELEV ELEVATOR
EMER EMERGENCY
EPS EXPANDED POLYSTYRENE BOARD
(INSULATION)
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXP EXPOSED
EXT EXTERIOR, EXTINGUISHER
F/ FACE OF
F/C FACE OF CONCRTETE
F/F FACE TO FACE, FLOOR TO FLOOR
F/M FACE OF MASONRY
F/S FACE OF STUDS
FA FIRE ALARM
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FF&E FIXTURE, FURNISHING & EQUIPMENT
FHC FIRE HOSE CABINET
FHR FIRE HOSE RACK
FIN FINISH
FLR FLOOR
FM FACTORY MUTUAL
FP FIRE PROOFING
FR FRAME
FTG FOOTING
FUR FURRING
FUT FUTURE
FVC FIRE VALVE CABINET
GA GAUGE
GAL GALLON
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GEN GENERAL, GENERATOR
GFCI GOVERNMENT FURNISHED
CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED
INSTALLED BY GOVERNMENT
GL GLASS
GR GRADE
GR BM GRADE BEAM
GRD GROUND
GUT GUTTER
GYP BD GYPSUM BOARD
H HIGH
HB HOSE BIBB
HC HANDICAPPED
HD HEAVY DUTY
HDR HEADER
HDW HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HIGH POINT
HT HEIGHT
HTR HEATER
HVAC HEATING, VENTILATING, & AIR
CONDITIONING
HWD HARDWOOD
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
ILO IN LIEU OF
IN INCH
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INV INVERT
J JOIST
JAN JANITOR
JB JUNCTION BOX
JT JOINT
KD KNOCK DOWN
KIP KILO-POUND
KIT KITCHEN
KO KNOCKOUT
KPL KICKPLATE
LAM LAMINATE
LAV LAVATORY
LBR LUMBER
LB POUND
LF LINEAR FEET (FOOT)
LH LEFT HAND
LIN LINEAR
LKR LOCKER
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATION
LP LOW POINT
LT LIGHT
LTWT LIGHT WEIGHT
LVR LOUVER
M METER
MAINT MAINTENANCE
MAS MASOMRY
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEMB MEMBRANE
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM, MINUTE
MISC MISCELLANEOUS
MM MILLIMETER
MO MASONRY OPENING
MOD MODULAR, MODIFY
MOV MOVABLE
MTD MOUNTED
MTL METAL
MULL MULLION
NA NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OFD OVERFLOW DRAIN
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OWSJ OPEN WEB STEEL JOIST
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
OZ OUNCE
PA PUBLIC ADDRESS
PAR PARAPET
PAT PATTERN
PB PULL BOX
PBD PARTICLEBOARD
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PH PHASE
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTER, PLASTIC
PLBG PLUMBING
PLG PILING
PLYWD PLYWOOD
PNL PANEL
PR PAIR
PRCST PRECAST
PRKG PARKING
PROP PROPERTY, PROPOSED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT, POINT, PRESSURE TREATED
PTN PARTITION
PWR POWER
QT QUARRY TILE
QTY QUANTITY
R RADIUS, RISER
RB RESILIENT BASE
RBM REINFORCED BRICK MASONRY
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RDG INS RIGID INSULATION, SOLID
REC RECESSED
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
REV REVISED, REVISION
RFG ROOFING
RH RIGHT HAND
RHR RIGHT HAND REVERSE
RL ROOF LEADER
RLG RAILING
RM ROOM
RND ROUND
RO ROUGH OPENING
RVL REVEAL
SAN SANITARY
SB SPLASH BLOCK
SCHED SCHEDULE
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SGL SINGLE
SH SHOWER
SHT SHEET
SHTHG SHEATHING
SHV SHELVING
SIM SIMILAR
SJ SCORED JOINT
SK SINK
SLV SLEEVE
SM SHEET METAL
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SST STAINLESS STEEL
ST STAIRS
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STR STRUCTURAL
SUB FL SUBFLOOR
SUPP SUPPLEMENTAL
SW SIDEWALK, SHORT WAY
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
T&B TOP & BOTTOM
T&G TONGUE & GROOVE
T/ TOP OF
T/BM TOP OF BEAM
T/C TOP OF CONCRETE, TOP OF CURB
T/COL TOP OF COLUMN
T/FTG TOP OF FOOTING
T/J TOP OF JOIST
T/S TOP OF STEEL
TB TEST BORING
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPORARY
TER TERRAZZO
THK THICK
TKBD TACKBOARD
TOPO TOPOGRAPHY
TV TELEVISION
TYP TYPICAL
UC UNDERCUT
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
UNF UNFINISHED
UNO UNLESS NOTED OTHERWISE
USGS UNITED STATES GEOLOGICAL
SURVEY
VAR VARIES
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VTR VENT THRU ROOF
VWC VINYL WALL COVERING
W WIDE, WIDTH
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WF WIDE FLANGE
WH WALL HYDRANT, WATER HEATER
WL WIND LOAD
WP WATERPROOFING, WORK POINT
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
YD YARD DRAIN
EXTERIOR ELEVATION
SECTION
INTERIOR ELEVATION
SHEET NUMBER WHERE
SECTION IS DRAWN
DRAWING SYMBOLS
SHEET NUMBER WHERE
ELEVATION IS DRAWN
ELEVATION NUMBER ON
SHEET
ELEVATION NUMBER ON
SHEET
SECTION NUMBER ON SHEET
SHEET NUMBER WHERE
DETAIL IS DRAWN
DETAIL NUMBER ON
SHEET
DETAIL
X
SPOT ELEVATION
FLOOR LEVEL & NAME
ROOM NAME / NUMBER
DOOR NUMBER
WINDOW TYPE
INTERIOR PARTITIONS
EQUIPMENT NUMBER
REVISION CLOUD
REVISION NUMBER
NORTH ARROW
DRAWING NOTENNN
NN COLUMN CENTERLINE
FACE OF BUILDINGNN
CEILING HEIGHT AFFX'-XX"
ROOM NAME
A3F
NAME
ELEVATION
DEMOLITION DRAWING NOTENNN
TOILET ACCESSORYTA-XX
N www.coffman.com
10 N Post Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/2
/2
:3
:2
P
M
04/05/2024
KING
LITMER
8050.03
A-001
SYMBOLS &
ABBREVIATIONS
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
REV DATE DESCRIPTION
02 40
BE9-2553
E1-1054
BE9-2553
E1-1054
BE9-2552
BE9-2553
BE9-2552
BE9-2553
B E9- 2553
E 1- 1 054
B E9- 2553
E 1- 1 054
B E9- 2552
B E9- 2553
B E9- 2552
B E9- 2553
B E9- 2553
E 1- 1 054
B E9- 2553
E 1- 1 054
B E9- 2552
B E9- 2553
B E9- 2552
B E9- 2553
105A105B106107108109110111112
113 114 115 116 117 118 119 120B
131 132 133
134 135
130 128
141142143
145 139
148 149
120A
A. ROOM NUMBERS ARE FOR CONSTRUCTION
PURPOSES ONLY.
B. ALL DIMENSIONS ARE FROM FACE TO FACE OF
FINISH CONSTRUCTION UNLESS INDICATED
OTHERWISE.
C. USE ONLY WRITTEN DIMENSIONS - DO NOT SCALE
DRAWINGS.
D. CONTRACTOR SHALL VERIFY ALL CONDITIONS AND
DIMENSIONS ON THE SITE PRIOR TO COMMENCING
WORK. ALL INQUIRIES AND DISCREPANCIES SHALL
BE DIRECTED TO THE GOVERNMENT.
E. ALL WORK SHOWN ON THESE DRAWINGS IS TO BE
BY THE CONTRACTOR UNLESS OTHERWISE
INDICATED.
F. ALL BLOCKING SHALL BE AS FOLLOWS: (1) BLOCKING
INCLUDES WOOD AND METAL REINFORCEMENT
INSTALLED DURING CONSTRUCTION TO SUPPORT
WALL HUNG ITEMS. PROVIDE BLOCKING FOR
MILLWORK, MARKERBOARDS, TACKBOARDS,
DISPLAY CASES, OR OTHER ITEMS. (2) BLOCKING
SHOWN OR DETAILED IN THESE DOCUMENTS IS TO
ILLUSTRATE CONCEPT AND IS NOT INTENDED TO
LIMIT THE CONTRACTOR'S REQUIREMENT TO
PROVIDE A COMPLETE AND SOUND INSTALLATION.
G. ALL NEW STANDARD DOORS IN STUD PARTITIONS TO
BE LOCATED 4" FROM FACE OF PERPENDICULAR
WALL ON THE HINGE SIDE UNLESS INDICATED
OTHERWISE.
H. REFER TO SHEET A-202 FOR HEAD AND JAMB
DETAILS AND HARDWARE SETS.
www.coffman.com
10 N Post Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/2
/2
:3
:2
P
M
04/05/2024
KING
LITMER
8050.03
A-101
FIRST FLOOR PLAN
- BUILDING 001
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
GENERAL NOTES
DRAWING NOTES
3/32" = 1'-0"A-101
01 BUILDING 001 FLOOR PLAN
N
ROOM SCHEDULE BLDG 001
NO. ROOM NAME
100 VESTIBULE
101 VESTIBULE
102 LOBBY
103 CORRIDOR
104 CORRIDOR
105A OFFICE
105B OFFICE
106 OFFICE
107 OFFICE
108 OFFICE
109 OFFICE
110 OFFICE
111 OFFICE
112 OFFICE
113 OFFICE
114 OFFICE
115 OFFICE
116 OFFICE
ROOM SCHEDULE BLDG 001
NO. ROOM NAME
135 STORAGE
136 LAB
137 WOMEN
138 MECHANICAL
139 DOCK
140 PREPARATION
141 TOILET
142 PLANT
143 SOIL
144 DRYING
145 STORAGE
146 BREAK
147 OFFICE
148 CORRIDOR
149 OPEN OFFICE
150 STORAGE
151 DRYING
ROOM SCHEDULE BLDG 001
NO. ROOM NAME
117 OFFICE
118 OFFICE
119 OFFICE
120A OFFICE
120B OFFICE
121 RECORDS
122 OFFICE
123 OFFICE
124 OFFICE
125 JANITOR
126 MEN
127 CONFERENCE
128 LAB
130 LAB
131 LAB
132 STORAGE
133 LAB
134 STORAGE
03 40
A -2
A07A07A01A01A02
A-301
A03A03A03
002-01002-05002-06002-12
002-02002-03002-04002-07002-08002-09002-10002-11
3'-5" TYP2'-2" TYP
A05A05 A05A05
A-301
W1 W1 W1W1
A-301 A03
A07
ALTERNATE 04ALTERNATE 04ALTERNATE 04ALTERNATE 04ALTERNATE 04ALTERNATE 04
A. ROOM NUMBERS ARE FOR CONSTRUCTION
PURPOSES ONLY.
B. ALL DIMENSIONS ARE FROM FACE TO FACE OF
FINISH CONSTRUCTION UNLESS INDICATED
OTHERWISE.
C. USE ONLY WRITTEN DIMENSIONS - DO NOT SCALE
DRAWINGS.
D. CONTRACTOR SHALL VERIFY ALL CONDITIONS AND
DIMENSIONS ON THE SITE PRIOR TO COMMENCING
WORK. ALL INQUIRIES AND DISCREPANCIES SHALL
BE DIRECTED TO THE GOVERNMENT.
E. ALL WORK SHOWN ON THESE DRAWINGS IS TO BE
BY THE CONTRACTOR UNLESS OTHERWISE
INDICATED.
F. ALL BLOCKING SHALL BE AS FOLLOWS: (1) BLOCKING
INCLUDES WOOD AND METAL REINFORCEMENT
INSTALLED DURING CONSTRUCTION TO SUPPORT
WALL HUNG ITEMS. PROVIDE BLOCKING FOR
MILLWORK, MARKERBOARDS, TACKBOARDS,
DISPLAY CASES, OR OTHER ITEMS. (2) BLOCKING
SHOWN OR DETAILED IN THESE DOCUMENTS IS TO
ILLUSTRATE CONCEPT AND IS NOT INTENDED TO
LIMIT THE CONTRACTOR'S REQUIREMENT TO
PROVIDE A COMPLETE AND SOUND INSTALLATION.
G. ALL NEW STANDARD DOORS IN STUD PARTITIONS TO
BE LOCATED 4" FROM FACE OF PERPENDICULAR
WALL ON THE HINGE SIDE UNLESS INDICATED
OTHERWISE.
H. REFER TO SHEET A-202 FOR HEAD AND JAMB
DETAILS AND HARDWARE SETS.
REMARKS
R1 INSULATED DOOR
R2 REPLACE DOOR OPENER
R3 VERIFY EXISTING OVERHEAD
DOOR OPENING DIMENSIONS
R4 OWNER PROVIDED LOCKSET
ABBREVIATIONS
AL ALUMINUM
HM HOLLOW METAL
PF PRE-FINISHED
PT PAINT
STL STEEL
GLASS TYPES
01 1/4" CLEAR FLOAT GLASS
02 1/4" CLEAR TEMPERED GLASS
03 1" CLEAR INSULATING GLASS
04 1" CLEAR TEMPERED INSULATING GLASS
HG
SCHED
SEE
5" 5"
2" 2"
D O
O R
S
IZ
E
S E
E S
C H
E D
U L E
SCHED
SEE
S E
E S
C H
E D
U L E
2" 2"
W1
3'-0"
DOOR TYPES FRAME TYPES WINDOW TYPES
OHA
S E
E S
C H
E D
U L E
SEE SCHEDULE
EQ 2'-0" EQ
04 04 www.coffman.com
10 N Post Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/2
/2
:3
:2
P
M
04/05/2024
KING
LITMER
8050.03
A-102
FIRST FLOOR PLAN
- BUILDING 002
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
GENERAL NOTES
DRAWING NOTES
1/8" = 1'-0"A-102
01 BUILDING 002 FLOOR PLAN
A01 REMOVE EXISTING MANUAL OVERHEAD
DOOR AND TRACK AND REPLACE WITH NEW
OVERHEAD DOOR, TRACK, AND OPERATOR
A02 REMOVE EXISTING OVERHEAD DOOR,
TRACK, AND OPERATOR AND REPLACE WITH
NEW OVERHEAD DOOR, TRACK, AND
OPERATOR
A03 NEW INSULATED HOLLOW METAL DOOR
A05 REMOVE EXISTING OVERHEAD DOOR AND
TRACK AND INFILL WITH NEW WALL
A07 REMOVE EXISTING MANUAL OVERHEAD
DOOR AND TRACK AND REPLACE WITH NEW
OVERHEAD DOOR AND TRACK
N
BUILDING 002 DOOR AND FRAME SCHEDULE
MARK
DOOR FRAME DETAILS
RATING HDW SET REMARKS MARK
# OF
LEAFS WIDTH HEIGHT THK TYPE MATL FINISH GLASS TYPE MATL FINISH HEAD JAMB
002-01 1 3' - 6" 7' - 0" 0' - 1 3/4" HG HM PT 04 01 HM PT H01 J01 -- H01 R1, R4 002-01
002-02 0 10' - 0" 12' - 0" 0' - 2" OHA STL PF 04 -- -- -- -- -- -- -- R1, R3 002-02
002-03 0 10' - 0" 12' - 0" 0' - 2" OHA STL PF 04 -- -- -- -- -- -- -- R1, R3 002-03
002-04 0 10' - 0" 12' - 0" 0' - 2" OHA STL PF 04 -- -- -- -- -- -- -- R1, R3 002-04
002-05 1 3' - 6" 7' - 0" 0' - 1 3/4" HG HM PT 04 01 HM PT H01 J01 -- H01 R1, R4 002-05
002-06 1 3' - 6" 7' - 0" 0' - 1 3/4" HG HM PT 04 01 HM PT H01 J01 -- H01 R1, R4 002-06
002-07 0 10' - 0" 12' - 0" 0' - 2" OHA STL PF 04 -- -- -- -- -- -- -- R3 002-07
002-08 0 10' - 0" 12' - 0" 0' - 2" OHA STL PF 04 -- -- -- -- -- -- -- R3 002-08
002-09 0 10' - 0" 12' - 0" 0' - 2" OHA STL PF 04 -- -- -- -- -- -- -- R3 002-09
002-10 0 10' - 0" 12' - 0" 0' - 2" OHA STL PF 04 -- -- -- -- -- -- -- R3 002-10
002-11 0 10' - 0" 12' - 0" 0' - 2" OHA STL PF 04 -- -- -- -- -- -- -- R3 002-11
002-12 1 3' - 6" 7' - 0" 0' - 1 3/4" HG HM PT 04 01 HM PT H01 J01 -- H01 R1, R4 002-12
04 40
A -2
A06 A06 A06 A02 A02
003-01003-02003-03003-04003-05
A04A04A04A04
ALTERNATE 02ALTERNATE 02ALTERNATE 02ALTERNATE 02ALTERNATE 02
A. ROOM NUMBERS ARE FOR CONSTRUCTION
PURPOSES ONLY.
B. ALL DIMENSIONS ARE FROM FACE TO FACE OF
FINISH CONSTRUCTION UNLESS INDICATED
OTHERWISE.
C. USE ONLY WRITTEN DIMENSIONS - DO NOT SCALE
DRAWINGS.
D. CONTRACTOR SHALL VERIFY ALL CONDITIONS AND
DIMENSIONS ON THE SITE PRIOR TO COMMENCING
WORK. ALL INQUIRIES AND DISCREPANCIES SHALL
BE DIRECTED TO THE GOVERNMENT.
E. ALL WORK SHOWN ON THESE DRAWINGS IS TO BE
BY THE CONTRACTOR UNLESS OTHERWISE
INDICATED.
F. ALL BLOCKING SHALL BE AS FOLLOWS: (1) BLOCKING
INCLUDES WOOD AND METAL REINFORCEMENT
INSTALLED DURING CONSTRUCTION TO SUPPORT
WALL HUNG ITEMS. PROVIDE BLOCKING FOR
MILLWORK, MARKERBOARDS, TACKBOARDS,
DISPLAY CASES, OR OTHER ITEMS. (2) BLOCKING
SHOWN OR DETAILED IN THESE DOCUMENTS IS TO
ILLUSTRATE CONCEPT AND IS NOT INTENDED TO
LIMIT THE CONTRACTOR'S REQUIREMENT TO
PROVIDE A COMPLETE AND SOUND INSTALLATION.
G. ALL NEW STANDARD DOORS IN STUD PARTITIONS TO
BE LOCATED 4" FROM FACE OF PERPENDICULAR
WALL ON THE HINGE SIDE UNLESS INDICATED
OTHERWISE.
H. REFER TO SHEET A-202 FOR HEAD AND JAMB
DETAILS AND HARDWARE SETS.
REMARKS
R1 INSULATED DOOR
R2 REPLACE DOOR OPENER
R3 VERIFY EXISTING OVERHEAD
DOOR OPENING DIMENSIONS
R4 OWNER PROVIDED LOCKSET
ABBREVIATIONS
AL ALUMINUM
HM HOLLOW METAL
PF PRE-FINISHED
PT PAINT
STL STEEL
GLASS TYPES
01 1/4" CLEAR FLOAT GLASS
02 1/4" CLEAR TEMPERED GLASS
03 1" CLEAR INSULATING GLASS
04 1" CLEAR TEMPERED INSULATING GLASS
DOOR TYPES
OHA
S E
E S
C H
E D
U L E
SEE SCHEDULE
EQ 2'-0" EQ
OHB
S E
E S
C H
E D
U L E
SEE SCHEDULE
EQ 2'-0" 1'-9" 2'-0" 1'-9" 2'-0" EQ
www.coffman.com
10 N Post Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/2
/2
:3
:2
P
M
04/05/2024
KING
LITMER
8050.03
A-103
FIRST FLOOR PLAN
- BUILDING 003
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
GENERAL NOTES
DRAWING NOTES
N
1/8" = 1'-0"A-103
01 BUILDING 003 FLOOR PLAN
A02 REMOVE EXISTING OVERHEAD DOOR,
TRACK, AND OPERATOR AND REPLACE WITH
NEW OVERHEAD DOOR, TRACK, AND
OPERATOR
A04 EXISTING DOOR TO REMAIN
A06 REMOVE EXISTING MANUAL OVERHEAD
DOOR AND TRACK AND REPLACE WITH NEW
OVERHEAD DOOR AND TRACK
BUILDING 003 DOOR AND FRAME SCHEDULE
MARK
DOOR FRAME DETAILS
RATING HDW SET REMARKS MARK
# OF
LEAFS WIDTH HEIGHT THK TYPE MATL FINISH GLASS TYPE MATL FINISH HEAD JAMB
003-01 0 18' - 10" 13' - 2" 0' - 2" OHB STL PF 04 -- -- -- -- -- -- -- R1, R2, R3 003-01
003-02 0 10' - 0" 12' - 0" 0' - 2" OHA STL PF 04 -- -- -- -- -- -- -- R1, R2, R3 003-02
003-03 0 12' - 0" 12' - 0" 0' - 2" OHA STL PF 04 -- -- -- -- -- -- -- R1, R3 003-03
003-04 0 10' - 0" 12' - 0" 0' - 2" OHA STL PF 04 -- -- -- -- -- -- -- R1, R3 003-04
003-05 0 10' - 0" 12' - 0" 0' - 2" OHA STL PF 04 -- -- -- -- -- -- -- R1, R3 003-05
05 40
A. ROOM NUMBERS ARE FOR CONSTRUCTION
PURPOSES ONLY.
B. ALL DIMENSIONS ARE FROM FACE TO FACE OF
FINISH CONSTRUCTION UNLESS INDICATED
OTHERWISE.
C. USE ONLY WRITTEN DIMENSIONS - DO NOT SCALE
DRAWINGS.
D. CONTRACTOR SHALL VERIFY ALL CONDITIONS AND
DIMENSIONS ON THE SITE PRIOR TO COMMENCING
WORK. ALL INQUIRIES AND DISCREPANCIES SHALL
BE DIRECTED TO THE GOVERNMENT.
E. ALL WORK SHOWN ON THESE DRAWINGS IS TO BE
BY THE CONTRACTOR UNLESS OTHERWISE
INDICATED.
F. ALL BLOCKING SHALL BE AS FOLLOWS: (1) BLOCKING
INCLUDES WOOD AND METAL REINFORCEMENT
INSTALLED DURING CONSTRUCTION TO SUPPORT
WALL HUNG ITEMS. PROVIDE BLOCKING FOR
MILLWORK, MARKERBOARDS, TACKBOARDS,
DISPLAY CASES, OR OTHER ITEMS. (2) BLOCKING
SHOWN OR DETAILED IN THESE DOCUMENTS IS TO
ILLUSTRATE CONCEPT AND IS NOT INTENDED TO
LIMIT THE CONTRACTOR'S REQUIREMENT TO
PROVIDE A COMPLETE AND SOUND INSTALLATION.
G. ALL NEW STANDARD DOORS IN STUD PARTITIONS TO
BE LOCATED 4" FROM FACE OF PERPENDICULAR
WALL ON THE HINGE SIDE UNLESS INDICATED
OTHERWISE.
H. REFER TO SHEET A-202 FOR HEAD AND JAMB
DETAILS AND HARDWARE SETS.
www.coffman.com
10 N Post Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/2
/2
:3
:2
P
M
04/05/2024
KING
LITMER
8050.03
A-104
FIRST FLOOR PLAN
- BUILDING 011
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
GENERAL NOTES
DRAWING NOTES
N
1/8" = 1'-0"A-104
01 BUILDING 011 FLOOR PLAN
ROOM SCHEDULE BLDG 011
NO. ROOM NAME
152 LAB
153 LAB
154 SOIL
155 STORAGE
156 MICROSCOPE
157 LAB
158 GROWTH CHAMBER
159 MECHANICAL
06 40
R01R02
R03
R03
R03
R03
R03
R03
R03
R03
R03
R03
R03
R03
R03 R03
R03
R03
R03
R03
R03
R03
R03
R03
STAINLESS STEEL
FASTENERS WITH GASKETED
WASHERS AT 18" O.C. MAX
WITH BUTYL SEALANT
NEW COPPER
COPING TO MATCH
EXISTING
EXISTING WOOD
BLOCKING
EXISTING
COPPER BATTEN
ROOFING
EXISTING ROOF
MEMBRANE
STAINLESS STEEL
FASTENERS WITH
GASKETED WASHERS AT
18" O.C. MAX WITH
BUTYL SEALANT
A. SEAL ALL SEAMS IN EXISTING COPPER COPING WITH
BUTYL SEALANT.
B. ALL WORK ON THIS SHEET IS TO BE INCLUDED IN
ALTERNATE 07.
3/32" = 1'-0"A-110
01 BUILDING 001 ROOF PLAN
www.coffman.com
10 N Post Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/2
/2
:3
:2
P
M
04/05/2024
KING
LITMER
8050.03
A-110
ROOF PLAN -
BUILDING 001
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
R01 REPLACE MISSING COPING WITH NEW
COPPER COPING TO MATCH EXISTING.
REFER TO DETAIL 02/A-110
R02 REMOVE DAMAGED COPING AND REPLACE
WITH NEW COPPER COPING TO MATCH
EXISTING. TOTAL AMOUNT TO REPLACE IS
APPROXIMATELY 30'
R03 ATTACH BOTH SIDES OF EXISTING COPING
WITH NEW STAINLESS STEEL FASTENERS
WITH GASKETED WASHERS AT 18" O.C. MAX
WITH BUTYL SEALANT
DRAWING NOTES
1" = 1'-0"A-110
02 ROOF DETAIL
N
GENERAL NOTES
07 40
E05E05E01 E02E02E01E03E02
A-301
W1W1W1W1
A04E04E04
5'-0"
A-301
E05
12" WIDE, 24 GAUGE
SMOOTH METAL
PANELS
METAL TRIM TO MATCH
PANELS
METAL DRIP FLASHING
CONT. SEALANT -
BOTH SIDES
THERMALLY BROKEN
HOLLOW METAL FRAME
5/8" GYPSUM
BD
WEATHER BARRIER
1/2" PLYWOOD
SHEATHING
JAMB J01 HEAD H01
12" WIDE, 24 GAUGE
SMOOTH METAL
PANELS
METAL TRIM TO MATCH
PANELS
CONT. SEALANT -
BOTH SIDES
THERMALLY BROKEN
HOLLOW METAL FRAME
5/8" GYPSUM
BD
WEATHER BARRIER
1/2" PLYWOOD
SHEATHING
STANDARD JAMB
ANCHOR -
SECURE TO STUD
7 3/4"
7 3/4"
Set H01 – Entry Function Qty Item Manufacturer BOD Model # / Series Finish 3 Hinges Ives 5BB1HW-NRP 26D 1 Entrance Function Cylindrical Lockset Best Access 9K37AB15DS3 626 1 Closer (parallel arm) LCN 4021-MC-H 689 1 Kickplate Ives 8400 (8”x2” LDW) 626 1 Set Seals National Guard Products 5020 Charcoal 1 Auto Door Bottom National Guard Products 320S Mill
HARDWARE SCHEDULE
www.coffman.com
10 N Post Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/8
/2
:3
:2
P M
04/05/2024
KING
LITMER
8050.03
A-202
ELEVATIONS -
BUILDING 002
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
GENERAL NOTES
DRAWING NOTES
1/8" = 1'-0"A-202
01 BUILDING 002 WEST ELEVATION
E01 REMOVE EXISTING MANUAL OVERHEAD
DOOR AND TRACK AND REPLACE WITH NEW
OVERHEAD DOOR, TRACK, AND OPERATOR
E02 NEW INFILL WALL WITH SMOOTH 24 GAUGE
HORIZONTAL METAL PANEL SIDING
E03 REMOVE EXISTING OVERHEAD DOOR,
TRACK, AND OPERATOR AND REPLACE WITH
NEW OVERHEAD DOOR, TRACK, AND
OPERATOR
E04 NEW PRE-FINISHED METAL AWNING
E05 REMOVE EXISTING MANUAL OVERHEAD
DOOR AND TRACK AND REPLACE WITH NEW
OVERHEAD DOOR AND TRACK
08 40
E05E05E05E03E03 www.coffman.com
10 N Post Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/2
/2
:3
:2
P
M
04/05/2024
KING
LITMER
8050.03
A-203
ELEVATIONS -
BUILDING 003
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
GENERAL NOTES
DRAWING NOTES
E03 REMOVE EXISTING OVERHEAD DOOR,
TRACK, AND OPERATOR AND REPLACE WITH
NEW OVERHEAD DOOR, TRACK, AND
OPERATOR
E05 REMOVE EXISTING MANUAL OVERHEAD
DOOR AND TRACK AND REPLACE WITH NEW
OVERHEAD DOOR AND TRACK
1/8" = 1'-0"A-203
01 BUILDING 003 EAST ELEVATION
09 40
12" WIDE, 24 GAUGE
SMOOTH METAL
PANELS
2x6 WOOD STUDS
AT 16" O.C.
5/8" GYPSUM
BOARD
R-19 BATT
INSULATION
EXISTING OPENING
FRAME TO REMAIN
1/2" PLYWOOD
SHEATHING
NEW PRE-FINISHED
METAL AWNING
A-301
4'-0" ±
PROVIDE BLOCKING
FOR AWNING
ATTACHMENT
LIGHT FIXTURE -
REFER TO ELECTRICAL
EXSTING METAL
BUILDING FRAMING
METAL DRIP
FLASHING
12" WIDE, 24 GAUGE
SMOOTH METAL
PANELS
METAL TRIM TO MATCH
PANELS
WEATHER BARRIER
1/2" PLYWOOD
SHEATHING
5/8" GYPSUM BD
R-19 BATT
INSULATION
3/4"
/4
12" WIDE, 24 GAUGE
SMOOTH METAL
PANELS
METAL TRIM TO MATCH
PANELS
CONT. SEALANT
WEATHER BARRIER
1/2" PLYWOOD
SHEATHING
5/8" GYPSUM BD
R-19 BATT
INSULATION
EXSTING METAL
BUILDING FRAMING
12" WIDE, 24 GAUGE
SMOOTH METAL PANELS
WEATHER BARRIER
1/2" PLYWOOD SHEATHING
5/8" GYPSUM BD
R-19 BATT
INSULATION
METAL FLASHING TO
MATCH PANELS
SAW CUT EXISTING
CONCRETE AND TURN
FLASHING DOWN INTO
SEALANT
RUBBER BASE
PRESERVATIVE
TREATED SILL
PLATE
1/2" EXPANSION
BOLTS AT 48" O.C.
A-301
12" WIDE, 24 GAUGE
SMOOTH METAL
PANELS
2x6 WOOD STUDS
AT 16" O.C.
5/8" GYPSUM
BOARD
R-19 BATT
INSULATION
EXISTING OPENING
FRAME TO REMAIN
1/2" PLYWOOD
SHEATHING
ALUMINUM WINDOW
WITH 1" INSULATING
GLASS
A-301
A-301
12" WIDE, 24 GAUGE
SMOOTH METAL PANELS
WEATHER BARRIER
1/2" PLYWOOD SHEATHING
5/8" GYPSUM BD
R-19 BATT
INSULATION
METAL DRIP FLASHING
METAL TRIM TO MATCH
PANELS
SEALANT AND
BACKER ROD BOTH
SIDES
ALUMINUM WINDOW
WITH 1" INSULATING
GLASS
12" WIDE, 24 GAUGE
SMOOTH METAL PANELS
WEATHER BARRIER
1/2" PLYWOOD
SHEATHING
METAL SILL FLASHING
METAL TRIM TO MATCH
PANELS
SEALANT AND
BACKER ROD BOTH
SIDES
ALUMINUM WINDOW
WITH 1" INSULATING
GLASS
5/8" GYPSUM BD
R-19 BATT
INSULATION
www.coffman.com
10 N Post Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/2
/2
:3
:2
P
M
04/05/2024
KING
LITMER
8050.03
A-301
WALL SECTIONS
AND DETAILS
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
3/4" = 1'-0"A-301
01 WALL SECTION
3" = 1'-0"A-301
06 PLAN DETAIL
3" = 1'-0"A-301
05 SECTION DETAIL
3" = 1'-0"A-301
07 SECTION DETAIL
3/4" = 1'-0"A-301
02 WALL SECTION
3" = 1'-0"A-301
03 WINDOW HEAD
3" = 1'-0"A-301
04 WINDOW SILL
10 40
M
GENERAL ABBREVIATIONS
ø ROUND or DIAMETER
AAV AUTOMATIC AIR VENT
ABV ABOVE
AD ACCESS DOOR
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
AL ACOUSTIC LINED
AP ACCESS PANEL
APD AIR PRESSURE DROP
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AWT AVERAGE WATER TEMPERATURE
BB BASEBOARD
BBD BACKDRAFT DAMPER
BFF BELOW FINISH FLOOR
BHP BRAKE HORSEPOWER
BG BELOW GROUND/GRADE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
C CENTIGRADE
CC COOLING COIL
CD CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
CG CEILING GRILLE
CI CAST IRON
CLG CEILING
CO CLEANOUT
CMU CONCRETE MASONRY UNIT
CM CONDENSATE METER
CONC CONCRETE
CONN CONNECT or CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION
(D) DEMOLISH
DB DECIBEL or DRY BULB
DDC DIRECT DIGITAL CONTROL
DIA DIAMETER
DIM DIMENSION
DN DOWN
DOAS DEDICATED OUTDOOR AIR SYSTEM
DPR DAMPER
DPS DIFFERENTIAL PRESSURE SWITCH
DWG DRAWING
(E) EXISTING
EA EACH
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
ELEC ELECTRIC or ELECTRICAL
ELEV ELEVATION
EMCS ENERGY MANAGEMENT CONTROL
SYSTEM
ERV ENERGY RECOVERY VENTILATOR
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXST EXISTING
F FAHRENHEIT
FCO FLOOR CLEANOUT
FCU FAN COIL UNIT
FD FLOOR DRAIN
FD FIRE DAMPER
FFD FUNNEL FLOOR DRAIN
FF FINAL FILTER
FLR FLOOR
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOOR SINK
FSD COMBINATION FIRE/SMOKE DAMPER
FT FOOT/FEET
FTR FINNED TUBE RADIATION
FV FACE VELOCITY
GA GAGE or GAUGE
GAL GALLON
GALV GALVANIZED
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GRD GRILLE, REGISTER, OR DIFFUSER
H HEIGHT
HB HOSE BIBB
HD HEAD
HP HORSEPOWER
HRV HEAT RECOVERY VENTILATOR
HTG HEATING
HVAC HEATING, VENTILATION AND
AIR CONDITIONING
HWG HIGH WALL GRILLE
HWR HIGH WALL REGISTER
HZ HERTZ
ID INSIDE DIAMETER
IE INVERT ELEVATION
IN INCH or INCHES
INSUL INSULATION
INV INVERT
KH KICKSPACE HEATER
KW KILOWATT
KWH KILOWATT HOUR
L LENGTH
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LF LINEAR FOOT/FEET
LVG LEAVING
LWG LOW WALL GRILLE
LWR LOW WALL REGISTER
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MAV MANUAL AIR VENT
MBH 1000 BRITISH THERMAL UNITS
PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MCC MOTOR CONTROL CENTER
MFR MANUFACTURER
MOP MAXIMUM OVERCURRENT
PROTECTION
MUA MAKEUP AIR UNIT
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTG MOUNTING
(N) NEW
(NL) NEW LOCATION
N/A NOT APPLICABLE
N/C NORMALLY CLOSED
N/O NORMALLY OPEN
NC NOISE CRITERIA
N.I.C. NOT IN CONTRACT
NPT NATIONAL PIPE THREAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
O/C ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
PVC PRESSURE CONTROL VALVE
PD PRESSURE DROP
PH PHASE
PLCS PLACES
POC POINT OF CONNECTION
POUA POINT OF USE ALARM
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH (GAGE)
(REL) RELOCATE/RELOACTED
RA RETURN AIR
RAG RETURN AIR GRILLE
REQD REQUIRED
R.O. ROUGH OPENING
RPBP REDUCED PRESSURE BACKFLOW
PREVENTER
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SD SMOKE DETECTOR
SF SUPPLY FAN
SHT SHEET
SIM SIMILAR
SL SOUNDLINING
SP STATIC PRESSURE
SQ SQUARE
SQ FT SQUARE FOOT/FEET
SS STAINLESS STEEL
STD STANDARD
TAB TESTING, ADJUSTING & BALANCING
THK THICK
TP TRAP PRIMER or TEST PLUG
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
TU TERMINAL UNIT
UBC UNIFORM BUILDING CODE
UFC UNIFORM FIRE CODE
UMC UNIFORM MECHANICAL CODE
UPC UNIFORM PLUMBING CODE
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
VA VALVE
VAC VACUUM
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
VTR VENT THRU ROOF
W WIDE
W/ WITH
W/O WITHOUT
WB WET BULB
WC WATER COLUMN
WCO WALL CLEANOUT
WG WATER GAGE
WGE WASTE GAS EVACUATION
WH WALL HYDRANT
WPD WATER PRESSURE DROP
WT WEIGHT
GENERAL LEGEND
THERMOSTAT. ADJACENT NUMBER
INDICATES TERMINAL UNIT CONTROLLED
HUMIDISTAT
SENSOR
CO2 SENSORCO2
T
H
S
PLUMBING FIXTURE TAG, SEE PLUMBING SCHEDULES
NOTES:
XX-X
SPECIFIC TO LOCATION(S) INDICATED.
A. NOTE APPLIES TO ENTIRE SHEET.
EXISTING
NEW
(E)
(N)
EXISTING (THIN)
NEW (MEDIUM)
POINT OF CONNECTION (POC)
EXISTING TO BE DEMOLISHED
MECHANICAL EQUIPMENT, SEE MECHANICAL SCHEDULES.XX-X
x
SD DUCT SMOKE DETECTOR
SP DUCT STATIC PRESSURE
LINETYPES:
B
A
A
B
DETAIL SYMBOL:
A = IDENTIFYING NUMBER
B = SHEET WHERE DETAIL IS SHOWN
SECTION SYMBOL:
A = IDENTIFYING NUMBER
B = SHEET WHERE DETAIL IS SHOWN
NEW LOCATION(NL)
RELOCATED(REL)
HVAC DUCTWORK LEGEND
DUCTWORK
24x12 S/A
RECTANGULAR DUCT
SIZE (INCHES) FIRST
DIMENSION IS SIDE OF
DUCT SHOWN
DUCT SIZES SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS OF DUCT. DUCT SIZE
SHOWN DOES NOT INCLUDE INSULATION OR LINING UNLESS NOTED OTHERWISE. SEE
BELOW FOR DUCT SIZE TAG LEGEND.
DUCT SIZE
DUCT SYSTEM ABBREVIATION
(NOT ALWAYS BE SHOWN)
INSULATED DUCT
SOUND LINED DUCT
24x12ø
FLAT OVAL DUCT
SIZE (INCHES) FIRST
DIMENSION IS SIDE OF
DUCT SHOWN
24ø ROUND DUCT
18ø24x12
CHANGE IN DUCT SIZE
AND/OR SHAPE
SUPPLY AIR (SA)
OUTSIDE AIR (OSA)
RECTANGULAR DUCT
TURNED UP/SECTION
ROUND/FLAT OVAL DUCT
TURNED UP/SECTION
RECTANGULAR DUCT
TURNED DOWN/AWAY
ROUND/FLAT OVAL DUCT
TURNED DOWN/AWAY
RETURN AIR (RA)
RECTANGULAR DUCT
TURNED UP/SECTION
ROUND/FLAT OVAL DUCT
TURNED UP/SECTION
RECTANGULAR DUCT
TURNED DOWN/AWAY
ROUND/FLAT OVAL DUCT
TURNED DOWN/AWAY
EXHAUST AIR (EA)
RECTANGULAR DUCT
TURNED UP/SECTION
ROUND/FLAT OVAL DUCT
TURNED UP/SECTION
RECTANGULAR DUCT
TURNED DOWN/AWAY
ROUND/FLAT OVAL DUCT
TURNED DOWN/AWAY
DAMPERS
VOLUME/BALANCING
DAMPER
FIRE DAMPER (FD)
SMOKE DAMPER (SD)
FIRE/SMOKE DAMPER
(FSD)
BACKDRAFT DAMPER
MOTORIZED DAMPER
DUCT SYSTEM ABBREVIATIONS
M
SUPPLY AIRSA
OUTSIDE AIROSA
COMBUSTION AIRCA
RETURN AIRRA
TRANSFER AIRTA
EXHAUST AIREA
FLEXIBLE DUCT
DUCT SYMBOLS
DUCT END CAP
DUCT ACCESS DOOR
AD
SUPPLY AIR (SA)
TERMINAL
RETURN AIR (RA) OR
TRANSFER AIR (TA) TERMINAL
AIR TERMINAL
IDENTIFICATION
EXHAUST AIR (EA) TERMINAL
GRILLE, REGISTER, OR OPEN
DUCT
X
CFM
AIRFLOW DIRECTION
SOUND ATTENUATOR
PLUMBING LEGEND
COLD WATER (CW) W
SANITARY WASTE
ABOVE GRADE (W)
HOT WATER (HW)
HOT WATER
CIRCULATING (HWC)
GLYCOL HEATING
SUPPLY
GLYCOL HEATING
RETURN
HWS
HWR
INDUSTRIAL COLD
WATER (ICW)
ICW
IHW
INDUSTRIAL HOT
WATER (IHW)
SOFT COLD WATER
(SCW)
SCW
COLD WATER
FLUSHING SYSTEM
(FCW)
FCW
TEMPERED WATER
(TW)
TW
NON-POTABLE
WATER (NPW)
NPW
IRRIGATION
WATER (IW)
IW
DEIONIZED WATER
(DI)
DI
DISTILLED WATER
(DW)
DW
BGW
SANITARY WASTE
BELOW GRADE
(BGW)
PW
PUMPED WASTE
(PW)
OW OILY WASTE (OW)
V VENT - SANITARY (V)
AW ACID WASTE (AW)
AV ACID VENT (AV)
RV RELIEF VENT (RV)
RAIN LEADER (RD)RD
OVERFLOW RAIN
LEADER (ORD)
ORD
STORM DRAIN (SD)SD
TRAP PRIMER (TP)TP
FUEL OILFO
PROPANE GAS
(PG)
PG
PLUMBING SYMBOLS & FIXTURE TAGS
2" FD-1
4" FCO
4" RD-1
4" COG
4" ORD-1
WC-1
DRAIN SIZE (SEE PLANS)
DRAIN TYPE (SEE SCHEDULE)
CLEANOUT SIZE (SEE PLANS)
CLEANOUT TYPE (SEE SCHEDULE)
DRAIN SIZE (SEE PLANS)
DRAIN TYPE (SEE SCHEDULE)
FIXTURE TYPE (SEE SCHEDULE)L-1
(SEE PLANS FOR
FIXTURE SYMBOL)
4" WCO
CONDENSATE
DRAIN (D)
D
VACUUM (VAC)VAC
COMPRESSED AIR
(CA)
CA
2" FS-1
PLUMBING/PIPING SYMBOLS LEGEND
VALVE
GATE VALVE
BALL VALVE
GLOBE VALVE
PLUG VALVE
BUTTERFLY VALVE
SPECIALTY VALVE
OS & Y VALVE
STOP COCK
PRESSURE REDUCING
VALVE
PRESSURE REGULATING
VALVE
CHECK VALVE
SPRING CHECK VALVE
STRAINER
STRAINER W/
BLOWDOWN
BACKFLOW PREVENTER
BALANCING VALVE
AUTOMATIC BALANCING
VALVE
A
RELIEF VALVE
FUEL ANTI-SIPHON
VALVE
F
FUSIBLE OIL SAFETY
VALVE
MOTORIZED VALVE
NEEDLE VALVE
M M
SOLENOID VALVE
S S
AUTOMATIC CONTROL
VALVE
FLOW SWITCH
PRESSURE SWITCH
FS
PS
PIPE ELBOW DOWN
(OR AWAY)
PIPE ELBOW UP
(OR TOWARDS)
PIPE TEE DOWN
(OR AWAY)
PIPE TEE UP
(OR AWAY)
FLOW DIRECTION
PIPE SLOPE
& DIRECTION
REDUCER, CONCENTRIC
REDUCER, ECCENTRIC
UNION
FLANGES
BLIND FLANGE
END CAP
PT PLUG (TEST PORT)
FLEX CONNECTOR/
COUPLING
EXPANSION JOINT
EXPANSION GUIDE
PIPE ANCHOR
HOSE QUICK
DISCONNECT
HOSE THREAD DRAIN
BALL VALVE
HOSE BIBB
WALL HYDRANT
HOSE THREAD DRAIN
VALVE
FIRE DEPARTMENT
CONNECTION
WATER HAMMER
ARRESTOR
THERMOWELL
THERMOMETER
DIAL THERMOMETER
T
PRESSURE GAUGE
W/ COCK
P
PRESSURE GAUGE
W/ COCK & SIPHON
P
AIR VENT
A - AUTOMATIC
C - COIN
M - MANUAL
H - HIGH VOLUME
A
BASKET STRAINER
AIR FILTER W/
COALESCER & DRAIN
AIR FILTER W/
COALESCER, DRAIN,
REGULATOR & GAUGE
PUMP (SYMBOLIC -
ARROW INDICATES
FLOW DIRECTION)
WATER METERM
WATER HAMMER
ARRESTOR (PLAN)
V#
S=2%
ADJ ADJUSTABLE
AFMS AIR FLOW MEASURING STATION
AI ANALOG INPUT
ALM ALARM
AO ANALOG OUTPUT
AVG AVERAGE/AVERAGING
B BOILER
BAS BUILDING AUTOMATION SYSTEM
CAV CONSTANT AIR VOLUME
CC COOLING COIL
CH CHILLER
CS CURRENT SWITCH
CT CURRENT TRANSDUCER/
COOLING TOWER
DDC DIRECT DIGITAL CONTROL
DI DIGITAL INPUT
DEM DIGITAL ENERGY MONITOR
DMPR DAMPER
DO DIGITAL OUTPUT
DPT DIFFERENTIAL PRESSURE TRANSDUCER
DPS DIFFERENTIAL PRESSURE SWITCH
DX DIRECT EXPANSION
EA EXHAUST AIR
EF EXHAUST FAN
EH ELECTRIC HEATER
ES END SWITCH
F FAN
HPS HIGH PRESSURE SWITCH
HX HEAT EXCHANGER
LPS LOW PRESSURE SWITCH
LTD LOW TEMPERATURE DETECTOR
M MOTORIZED ACTUATOR
NO NORMALLY OPEN
NC NORMALLY CLOSED
OA OUTSIDE AIR
OCC OCCUPANCY
P PRESSURE/PUMP
RA RETURN AIR
RE RELAY
RF RETURN FAN
RFP REMOTE FIELD PANEL
RH RELATIVE HUMIDITY
SA SUPPLY AIR
SC STEAM COIL
SD SMOKE DETECTOR
T TEMPERATURE
TEC TERMINAL EQUIPMENT CONTROLLER
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VLV VALVE
XFMR TRANSFORMER
CONTROLS ABBREVIATIONS AND LEGEND
P
S
R
M
OR
PNEUMATIC ACTUATOR
AIR FLOW MEASURING
STATION
CURRENT SENSOR
DAMPER - BACKDRAFT
DAMPER - OPPOSED
DAMPER - PARALLEL
DDC CONTROL POINT
MOTOR ACTUATOR
ELECTRICAL FEEDERS
END SWITCH
HUMIDIFIER
INLET VANES
MOTOR
MANUAL MOTOR STARTER
COMBINATION MOTOR
STARTER
PILOT TUBE
SWITCH - SENSOR
SENSOR
SENSOR WITH SUN SHIELD
SOLENOID
STRAP-ON SENSOR
RELAY
RIGID SENSOR
VALVE 2-WAY
VALVE 3-WAY
(COMMON IS SOLID)
WELL SENSOR
WHIP SENSOR
VORTEX FLOW SENSOR
0'
/3 2" www.coffman.com
221 N. Wall Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/1
/2
:5
:4
P
M
04/19/2024
TAH
RKC
231290
M-001
MECHANICAL
LEGENDS, NOTES
AND
ABBREVIATIONS
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
REV DATE DESCRIPTION
4-3-24
11 40
DESIGN CONDITIONS
LOCATION PENDLETON, OR
CLIMATE ZONE 5B (UMATILLA COUNTY)
OUTDOORS
COOLING 97.1°F DB / 64.7°F WB
HEATING -2.0°F DB
INDOOR
COOLING 72°F
HEATING 70°F
VENTILATION PER ASHRAE 62.1-2019
ELEVATION 1486 FT ABOVE SEA LEVEL
GENERAL NOTES
1. CONTRACTOR SHALL SECURE, MAINTAIN, AND PAY FOR ALL REQUIRED PERMITS, LICENSES, AND INSPECTIONS FOR DURATION OF WORK UNLESS
DIRECTED OTHERWISE.
2. ALL WORK SHALL COMPLY WITH THE OWNER'S REQUIREMENTS, AND WITH ALL APPLICABLE STATE AND LOCAL CODES, OR AUTHORITY HAVING
JURISDICTION.
3. SUBSTITUTIONS OF EQUIPMENT OTHER THAN AS SPECIFIED SHALL BE THE COMPLETE RESPONSIBILITY OF THE CONTRACTOR, ANY ADDITIONAL ELECTRICAL, STRUCTURAL, MECHANICAL, OR ARCHITECTURAL REQUIREMENTS SHALL BE PROVIDED AT NO ADDITIONAL EXPENSE TO THE OWNER.
4. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT ATTEMPT TO SHOW ALL REQUIRED OFFSETS. COORDINATE WITH OTHER TRADES AND PROVIDE ALL NECESSARY OFFSETS. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR CONSTRUCTION DETAILS.
5. REFER TO PROJECT MANUAL (SPECIFICATIONS) FOR ADDITIONAL REQUIREMENTS. PLANS AND SPECIFICATIONS SHALL BE TAKEN TOGETHER.
PROVIDE ALL WORK CALLED FOR IN EITHER. IN CASE OF CONFLICT BETWEEN SPECIFICATIONS AND PLANS THE MORE STRINGENT SHALL APPLY.
6. ALL EQUIPMENT AND MATERIAL ON THE JOB SITE PRIOR TO INSTALLATION SHALL BE COVERED AND PROTECTED FROM RAIN, DIRT, DUST, AND
DAMAGE.
7. VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT ACCESS CLEARANCES CAN BE MET. COORDINATE FINAL EQUIPMENT LOCATIONS W/ GENERAL CONTRACTOR AND OTHER TRADES TO ALLOW FOR REQUIRED MECHANICAL EQUIPMENT CLEARANCES.
8. PROVIDE AN UNOBSTRUCTED PASSAGEWAY MEASURING NO LESS THAN 36" WIDE BY 80" HIGH FROM DOOR INTO THE SPACE TO SERVICEABLE MECHANICAL EQUIPMENT. A LEVEL WORKING SPACE MEASURING NO LESS THAN 30" WIDE BY 36" DEEP MUST BE PROVIDED IN FRONT OF CONTROL
SIDE OF EQUIPMENT FOR SERVICING.
9. PROVIDE NEC CODE MINIMUM HORIZONTAL AND VERTICAL WORKING CLEARANCES FOR ALL ELECTRICAL PANELS AND EQUIPMENT. OFFSET
MECHANICAL WORK AS REQUIRED.
10. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF INSTALLATION STANDARDS AND CONSTRUCTION CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO SHOP FABRICATION AND/OR FIELD INSTALLATION. DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE CONSTRUCTION DRAWINGS SHALL BE CALLED TO THE ATTENTION OF THE ENGINEER.
11. ALL MECHANICAL EQUIPMENT, MATERIALS, AND INSTALLATION SHALL BE PROVIDED BY THE CONTRACTOR. ALL EQUIPMENT SHALL BE COMPLETE, INSTALLED, AND FULLY FUNCTIONAL PRIOR TO FINAL ACCEPTANCE OF THE WORK.
12. INSTALL ALL EQUIPMENT PER MANUFACTURERS RECOMMENDATIONS AND REQUIREMENTS. ANY CONFLICTS BETWEEN THE MANUFACTURERS DOCUMENTATION AND THE CONTRACT DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER.
13. DO NOT ALLOW ANY WORK TO BE COVERED UP OR ENCLOSED UNTIL INSPECTED, TESTED AND APPROVED BY OWNER'S REPRESENTATIVE OR
AUTHORITY HAVING JURISDICTION.
14. MECHANICAL EQUIPMENT SHALL NOT BE USED FOR TEMPORARY HEATING OR COOLING DURING CONSTRUCTION.
15. PIPES AND WIRING IN PLENUM SHALL BE RATED FOR PLENUM USE. PVC, ABS, AND PLASTIC PIPING IS NOT ACCEPTABLE IN PLENUM APPLICATIONS.
16. ALL DETAILS ARE TYPICAL UNLESS NOTED OTHERWISE.
GENERAL HVAC NOTES
1. SHEET METAL DUCTWORK AND COMPONENTS INCLUDING HANGING, SEALING, PLENUMS, & ACCESSORIES SHALL BE CONSTRUCTED IN STRICT ACCORDANCE WITH THE LATEST EDITION OF SMACNA STANDARDS FOR HVAC DUCT CONSTRUCTION, NFPA 90A, & 90B STANDARDS.
2. ALL DUCTWORK OPENINGS SHALL BE COVERED DURING CONSTRUCTION.
3. ALL DAMPERS SHALL BE SET FULLY OPEN PRIOR TO BALANCING.
4. CONTRACTOR TO PROVIDE TRANSITION TO CONNECT TO ALL MECHANICAL EQUIPMENT. PROVIDE FLEXIBLE CONNECTION ON INTAKE AND DISCHARGE
OF ALL MECHANICAL EQUIPMENT.
5. DUCT DIMENSIONS SHOWN ARE INSIDE SHEET METAL DIMENSIONS OR CLEAR OPENING INSIDE LINED DUCT.
6. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT ATTEMPT TO SHOW ALL REQUIRED OFFSETS. COORDINATE WITH OTHER TRADES AND
PROVIDE ALL NECESSARY OFFSETS.
7. ALL ELBOWS SHALL BE LONG RADIUS ELBOWS WHEREVER POSSIBLE, OR SHALL HAVE TURNING VANES WHERE INDICATED ON PLANS. NO SQUARE
THROAT OR ZERO RADIUS ELBOWS ALLOWED.
8. ALL DUCT BRANCH CONNECTIONS TO DIFFUSER OR GRILLES, TO OR FROM MAIN DUCTS, SHALL INCLUDE MANUAL VOLUME DAMPERS. ALL SPIN-IN FITTINGS SHALL BE CONICAL, RECTANGULAR BRANCH DUCT TAKEOFFS SHALL HAVE 45° TAKEOFFS.
9. PROVIDE CONCEALED DAMPER REGULATORS OR ACCESS DOORS FOR ALL MANUAL VOLUME DAMPERS LOCATED THAT ARE INACCESSIBLE. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES. ALL FINAL ACCESS DOOR LOCATIONS SHALL BE APPROVED BY ARCHITECT PRIOR TO
INSTALLATION.
10. 24"x24" ACCESS DOORS SHALL BE PROVIDED FOR ALL MECHANICAL EQUIPMENT LOCATED ABOVE GYPSUM BOARD CEILINGS. ALL FINAL ACCESS
DOOR LOCATIONS SHALL BE APPROVED BY ARCHITECT PRIOR TO INSTALLATION.
11. PROVIDE DIFFUSER AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES AND COORDINATE LOCATIONS WITH THE
ARCHITECTURAL REFLECTED CEILING PLAN AND ELECTRICAL LIGHTING LAYOUT.
12. ALL DUCTWORK VISIBLE THROUGH RETURN OR SUPPLY GRILLES TO BE PAINTED FLAT BLACK.
13. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTS SHALL HAVE THE TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS
SEALED AIRTIGHT WITH DUCT SEALANT (SMACNA SEAL CLASS "A").
14. COORDINATE EXACT LOCATIONS OF ALL ROOM THERMOSTATS AND/OR ROOM TEMPERATURE SENSORS WITH ARCHITECT/OWNER PRIOR TO
INSTALLATION.
15. BALANCE AIR SYSTEM TO QUANTITIES SHOWN, AND SUBMIT A COPY OF THE BALANCE REPORT TO THE ENGINEER FOR REVIEW.
GENERAL PLUMBING NOTES
1. PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY TO CONSTRUCT A COMPLETE, OPERATIONAL PLUMBING SYSTEM FOR THE ENTIRE
PROJECT AS SHOWN ON THESE DRAWINGS, INCLUDING ALL NECESSARY FEES AND PERMITS.
2. THE ENTIRE INSTALLATION SHALL CONFORM TO THE MOST RECENTLY ADOPTED REQUIREMENTS OF THE PLUMBING CODE, AND ALL OTHER APPLICABLE CITY, COUNTY, STATE, AND FEDERAL CODES AND REGULATIONS IN EFFECT AT THE DATE OF THE BID. CONFORM TO ANY CODES, RULES, REGULATIONS AND REQUIREMENTS THAT THE PROJECT OWNER HAS.
3. PRIOR TO FABRICATION AND INSTALLATION, THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL PLUMBING WORK WITH ALL OTHER TRADES INCLUDING THE MECHANICAL CONTRACTOR, FIRE PROTECTION CONTRACTOR, ELECTRICAL CONTRACTOR, GENERAL CONTRACTOR, AND ANY CONTRACTOR HIRED DIRECTLY BY THE OWNER. WHERE CONFLICTS MAY OCCUR, THEY SHALL BE RESOLVED PRIOR TO INSTALLATION.
4. THE WORKING DRAWINGS ARE DIAGRAMMATIC. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, THEY DO NOT SHOW EVERY OFFSET, BEND OR ELBOW NECESSARY FOR THE COMPLETE INSTALLATION IN THE SPACE PROVIDED. ALL LOCATIONS FOR PLUMBING EQUIPMENT AND PIPING SHALL BE CHECKED AND COORDINATED WITH THE ARCHITECTURAL, MECHANICAL, STRUCTURAL AND ELECTRICAL DRAWINGS.
5. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL FITTINGS, TRANSITIONS, VALVES, WORKING CLEARANCES, AND OTHER DEVICES AND ACCESSORIES REQUIRED FOR A COMPLETE, WORKABLE
INSTALLATION.
6. PROVIDE PROPER PROVISIONS FOR EXPANSION OR MOVEMENT OF ALL PIPING.
7. PROVIDE WATER HAMMER ARRESTORS (SHOCK ABSORBERS) AT ALL PIPE LOCATIONS WHERE VALVE CLOSURES MAY CAUSE WATER HAMMER OR RESULT IN EXCESSIVE PIPE VIBRATION OR MOVEMENT. (EXAMPLES INCLUDE FLUSH VALVES, SENSOR FAUCETS, AND WASHING MACHINES).
ENERGY CODE NOTES (2018 IECC)
1. DOCUMENTATION REQUIREMENTS DESCRIBED IN SECTION C103.6 SHALL BE PROVIDED TO THE OWNER WITHIN 90 DAYS OF THE DATE OF RECEIPT
OF THE CERTIFICATION OF OCCUPANCY.
2. HVAC EQUIPMENT SHALL HAVE MINIMUM PERFORMANCE AT SPECIFIED RATING CONDITIONS NOT LESS THAN THE VALUES INDICATED IN TABLES C403.3.2.
3. PROVIDE DEADBAND BETWEEN HEATING/COOLING SPACE SENSOR SETPOINTS OF 5 DEGREES AS REQUIRED BY SECTION C403.4.1.2.
4. HVAC SYSTEMS SHALL BE EQUIPPED WITH AUTOMATIC CONTROLS CAPABLE OF ACCOMPLISHING SETBACK OR SHUTDOWN DURING UNOCCUPIED
PERIOD AS REQUIRED BY SECTION C403.4.2.
5. SUPPLY AIR SHALL BE AUTOMATICALLY RESET AS REQUIRED IN SECTION C403.6.5.
6. ALL DUCTWORK SHALL BE INSULATED AS REQUIRED BY SECTION C403.11.1 AND AS DESCRIBED IN THE PROJECT SPECIFICATIONS.
7. ALL DUCTWORK SHALL COMPLY WITH SMACNA STANDARDS FOR CONSTRUCTION OF GALVANIZED DUCTWORK. ALL DUCTWORK SHALL BE SEALED
AS REQUIRED BY SECTION C403.11.2.
8. ALL PIPING SHALL BE INSULATED AS REQUIRED BY SECTION C403.11.3 AND AS DESCRIBED IN THE PROJECT SPECIFICATIONS.
9. SERVICE HEATING WATER EQUIPMENT SHALL HAVE MINIMUM PERFORMANCE AT SPECIFIED RATING CONDITIONS NOT LESS THAN THE VALUES
INDICATED IN TABLE C404.2.
10. DOMESTIC HOT WATER CIRCULATION PUMPS SHALL BE SHUT DOWN DURING UNOCCUPIED PERIODS AND WHEN THERE IS NO DEMAND FOR HOT
WATER AS REQUIRED BY SECTION C404.6.1.
11. HVAC SYSTEMS SHALL BE BALANCED AS REQUIRED BY SECTION C408.2.2. PROVIDE A WRITTEN REPORT PER SECTION C408.2.5.1.
12. PROVIDE BALANCING DEVICES IN ALL BRANCH DUCTS AS REQUIRED BY SECTION C408.2.2.1.
13. PROVIDE FUNCTIONAL TESTING OF HVAC EQUIPMENT PER SECTION C408.2.3. SUBMIT REPORT PER SECTION C408.3.2.3.
14. HVAC CONTROL SYSTEMS SHALL BE TESTED PER SECTION C408.2.3.2
15. COMMISSIONING SHALL BE PROVIDED AND A REPORT SHALL BE SUBMITTED TO THE OWNER AS REQUIRED BY SECTION C408. PROVIDE A CX PLAN
PER C408.2.1. PROVIDE WRITTEN REPORT PER C408.2.5.2.
16. OPERATION AND MAINTENANCE MANUALS SHALL BE PROVIDED TO THE OWNER AS REQUIRED BY SECTION C408.3.2.2. AT THE MINIMUM MANUALS
SHALL INCLUDE:
A. NAME AND ADDRESS OF AT LEAST ONE SERVICE AGENCY.
B. NARRATIVE OF HOW SYSTEM IS INTENDED TO OPERATE.
C. SUBMITTAL DATA.
D. OPERATION AND MAINTENANCE DATA FOR EQUIPMENT.
E. HVAC AND SERVICE HOT WATER CONTROLS SYSTEM MAINTENANCE AND CALIBRATION INFORMATION, INCLUDING WIRING DIAGRAMS.
www.coffman.com
221 N. Wall Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/1
/2
:5
:4
P
M
04/19/2024
TAH
RKC
231290
M-002
MECHANICAL
NOTES
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
REV DATE DESCRIPTION
12 40
BE9-2553
E1-1054 BE9-2552
BE9-2553
BE9-2552
BE9-2553
B E9 - 25 53
E 1- 10 54
B E9 - 25 53
E 1- 10 54
B E9 - 25 52
B E9 - 25 53
B E9 - 25 52
B E9 - 25 53
B E9 - 25 53
E 1- 10 54
B E9 - 25 53
E 1- 10 54
B E9 - 25 52
B E9 - 25 53
B E9 - 25 52
B E9 - 25 53
(E) B-1
DEMO FH-1 AND
12" EXHAUST
DUCT TO EF-3
DEMO FH-2 AND
12" EXHAUST DUCT
TO EF-4
(E) B-2
DEMO (E) BOILER
FLUE
(E) 4000 GALLON
ABOVE GROUND FUEL
OIL TANK TO REMAIN
(E) SUMP TO REMAIN
(E) HOT WATER PUMPS
TO REMAIN
(E) BRICK CHIMNEY
TO REMAIN
(E) BOILER TO
BE REMOVED
(E) FUEL OIL TANK
TO REMAIN
(E) BOILER TO
BE REMOVED
(E) FLOOR SINK
(E) FLOOR SINK
(E) EXPANSION TANK
(E) VACUUM PUMP
SEE PLUMBING
(ALTERNATE 01)
(E) VACUUM PUMP
RECEIVER TANK
(E) COMPRESSOR
(E) CHILLED WATER
TO REMAIN
(E) CHILLED WATER
PUMPS TO REMAIN
(E) FLOOR DRAIN
(E) AHU-1
TO REMAIN
VARIOUS (E) CONTROL
PLANES, (E) ELECTRICAL
PANELS ALONG WALL
DEMO (E) WATER HEATER
AS PART OF ALTERNATE 03
(E) HEAT EXCHANGER
TO REMAIN
(E) FUEL OIL PUMP
TO REMAIN
(E) FUEL OIL SUPPLY AND
RETURN PIPES TO BOILERS
EXHAUST UP
TO (E) EF
DEMO (E) BOILER
FLUE
(E) FUEL OIL SUPPLY
AND RETURN PIPES
TO ABOVE GROUND
TANK
(E) AHU-1INTAKE LOUVER
12x12 EXHAUST UP
TO (E) EF-1
(E) GLYCOL FEEDER
TO REMAIN
(E) HEV-2
(E) HEV-1
GENERAL NOTES
A. THESE DRAWINGS HAVE BEEN PREPARED USING OWNER
PROVIDED RECORD DRAWINGS AND THROUGH FIELD
OBSERVATIONS. VERIFY EXISTING CONDITIONS AS THEY
APPLY TO THIS PROJECT AND INCLUDE IN BID A SUFFICIENT
ALLOWANCE TO COVER ANY DISCREPANCY BETWEEN THE
DRAWINGS AND THE ACTUAL CONDITIONS AS THEY
CURRENTLY EXIST.
B. EXISTING WORK IS SHOWN WITH LIGHT LINES AND DEMO
WORK IS SHOWN WITH BOLD BROKEN LINES, TYP.
C. CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OF
ALL EQUIPMENT THE OWNER DOES NOT WISH TO RETAIN
FOR FUTURE USE. DO NOT ABANDON ANY ITEMS IN PLACE.
D. CONTRACTOR SHALL COORDINATE ANY SHUT DOWN OF
SYSTEMS WITH OWNER.
E. WORK SHOWN ON PLANS IS BASE BID UNLESS IDENTIFIED
OTHERWISE. SEE SHEET G-001 FOR ALTERNATE SCOPE
BREAKDOWN.
F. CONTRACTOR SHALL PERFORM PRE-CONSTRUCTION
AIRFLOW MEASUREMENTS OF EXISTING GENERAL EXHAUST
FANS TO DETERMINE POST-CONSTRUCTION SETPOINTS.
G. CONTRACTOR SHALL PERFORM PRE-CONSTRUCTION
AIRFLOW MEASUREMENTS (SUPPLY AND EXHAUST) FOR
LABORATORY ROOMS WITH FUME HOOD SCOPE.
www.coffman.com
221 N. Wall Street, Suite 500 Spokane, WA 99201 ph 509.328.2994
SHEET OF
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERSC
A
B
C
D
54321
D
C
B
A
1 2 3 4 5
SHEET NO:
SHEET TITLE:
/1
/2
:5
:4
P
M
04/19/2024
TAH
RKC
231290
MD-101
BUILDING 001
MECHANICAL
FLOOR PLAN
DEMOLITION
PENDLETON
BUILDING
REPAIRS
PROJECT A
48037 TUBBS RANCH ROAD
ADAMS, OR 97810
FINAL
TURNOVER
1/8" = 1'-0"MD-101
1 BUILDING 001 MECHANICAL FLOOR PLAN DEMOLITION
KEY NOTES
1 (E) FH-1 IS A PERCHLORIC ACID HOOD WITH STAINLESS STEEL
DUCTWORK AND A WASHDOWN SYSTEM. CONTRACTOR SHALL
TAKE APPROPRIATE MEASURES DURING DEMOLITION TO
PROTECT PROPERTY AND PERSONNEL.
2 DISCONNECT EXISTING AIR, VACUUM, WASTE, AND VENT LINES
FROM THE EXISTING HOOD. TEMPORARILY CAP FOR FUTURE
CONNECTION TO NEW HOOD.
3 FUME EXHAUST SYSTEM INCLUDES PHOENIX ELECTRONIC
EXHAUST VALVE. VALVES SHALL BE SAVED FOR
REINSTALLATION IN NEW HOOD DUCTWORK.
4 VENTURI VALVE CONTROL PANEL LOCATED ABOVE CEILING.
5 BELOW-ROOF DUCTWORK TO REMAIN, IT WILL CONNECT TO NEW
EXHAUST FAN (ALTERNATE 06).
6 CONTRACTOR SHALL PROTECT EXISTING FLOOR…