Attachment 4 LCIC Lighting Drawings.pdf
PDF 10 MB Posted
- Attached to
- GAOA LCIC Lighting Upgrades Federal contract opportunity
- Solicitation number
- 1240LU25R0026
- Issued by
- Department of Agriculture Forest Service
About this file
These documents are construction documents for the Lewis & Clark Interpretive Center located at 4201 Giant Springs Road in Great Falls, Montana. The architectural and electrical plans, prepared by Mosaic Architecture and Morrison-Maierle engineering, detail a multi-level facility with basement, first floor, and mezzanine levels. The electrical plans include comprehensive lighting design with multiple bid alternates focused on replacing and upgrading existing track lighting, theatrical dimming equipment, and fixtures throughout the building.
Key electrical design elements include LED track lighting with 0-10V dimming capabilities, occupancy sensors, photo sensors for daylight harvesting, and provisions for replacing existing lighting control systems. The design covers track lighting in exhibit areas, offices, conference rooms, and back-of-house spaces across different building levels. Bid alternates provide flexibility for the owner, including options to replace theatrical dimming equipment, upgrade stair tread lighting, retrofit existing fixtures, and implement new lighting control systems while maintaining existing A/V controls in the theater.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 1240LU25R0026 LCIC Lighting Upgrade.pdf | ||
| Attachment 2 Statement of Work.pdf | ||
| Attachment 1 Schedule of Items.docx | DOCX document | |
| Attachment 3 LCIC Lighting Specifications.pdf | ||
| Attacment 5 Wage Determination.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE:
SHEET:
428 N. Last Chance Gulch Helena, Montana 59601
406.449.2013 www.mosaicarch.com
D A
TE
S
TA
M
P a r c h i t e c t u r e - p l a n n i n g - d e s i g n
CITY STAMP
/2
9/
:4 3:
A
M
11.29.2021
A000
COVER
4201 GIANT SPRINGS RD, GREAT FALLS MT
59405
LEWIS & CLARK
INTERPRETIVE CENTER
C O
N S
T R
U C
T I O
N D
O C
U M
E N
T S
LEWIS & CLARK INTERPRETIVE CENTER
4201 GIANT SPRINGS RD
GREAT FALLS, MT MOSAIC ARCHITECTURE, P.C.
428 N. LAST CHANCE GULCH
HELENA, MT 59601
(406) 449-2013 CONTACT: MATT AUNE, AIA matta@mosaicarch.com
ARCHITECT:
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
THESE DRAWINGS WERE PREPARED BY MOSAIC ARCHITECTURE, P.C. FOR CONSTRUCTION OF THE PROJECT DESCRIBED HEREIN. AS SUCH, THE DOCUMENTS ARE THE PROPERTY OF MOSAIC ARCHITECTURE, P.C. & MAY NOT BE REPRODUCED, COPIED OR USED IN ANY WAY WITHOUT PRIOR APPROVAL FROM MOSAIC ARCHITECTURE, P.C.
SHEET INDEX
PROJECT DIRECTORY
VICINITY MAP
PROJECT SITE
CITY STAMPS
ARCHITECTURAL DRAWINGS
A000 COVER
A002 GENERAL INFORMATION & ASSEMBLY TYPES
A103 FLOOR PLAN
A104 BASEMENT FLOOR PLAN
A105 REFLECTED CEILING PLAN - LEVEL 1
A106 REFLECTED CEILING PLAN - BASEMENT
A108 Unnamed
A109 Unnamed
E101 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E102 LIGHTING SCHEDULES AND DETAILS
E200 BASEMENT - LIGHTING PLAN
E201 LEVEL 1 - LIGHTING PLAN
E202 MEZZANINE - LIGHTING PLAN
ELECTRICAL DRAWINGS
E101 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E102 LIGHTING SCHEDULES AND DETAILS
E200 BASEMENT - LIGHTING PLAN
E201 LEVEL 1 - LIGHTING PLAN
E202 MEZZANINE - LIGHTING PLAN
MORRISON-MAIERLE
1 ENGINEERING PL
HELENA, MT 59601
(406) 442-3050
CONTACT: GARTH STEVENS, gstevens@m-m.net
# DATE REVISION
RECOMMENDED:
LCIC DIRECTOR
APPROVED:
FOREST ENGINEER
FOREST SUPERVISOR
reidstovall Line reidstovall Line reidstovall Line
1. DIMENSIONS ARE TO FACE OF STUD, EXISTING WALL FINISH,
MASONRY, OR DOOR/WINDOW OPENINGS. DIMENSIONS OF EXISTING
CONSTRUCTION ARE NOT SHOWN ON DRAWINGS - VERIFY
DIMENSIONS OF ALL EXISTING CONSTRUCTION IN THE FIELD.
DIMENSIONS TO OPENINGS ARE NOMINAL. VERIFY ALL OPENINGS
WITH ROUGH OPENING REQUIREMENTS.
2. ALL DOOR OPENINGS PERPENDICULAR TO A WALL ARE 4" TO THE
WALL FRAMING UNO.
3. EXISTING CONSTRUCTION TO REMAIN SHOWN SHADED, NEW
CONSTRUCTION SHOWN SOLID.
4. SEE SHEET A-002 FOR WALL TYPES. IN AREAS WITH SUSPENDED
ACOUSTICAL TILE CEILINGS, GYPSUM WALL BOARD MAY BE
TERMINATED 6" ABOVE THE CEILING. IN AREAS WITH EXPOSED
STRUCTURE CONTINUE GYPSUM BOARD TO UNDERSIDE OF
STRUCTURE.
5. VERIFY EXISTING WALL CONSTRUCTION.
6. ALL EGRESS DOORS SHALL BE READILY OPERABLE FROM THE
EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE
OR EFFORT.
GENERAL FLOOR PLAN NOTES
NEW CONSTRUCTION
EXISTING ELEMENTS TO REMAIN
LINEWORK LEGEND
A A
B B
CC
DD
EE
FF
GG
HH
II
JJ
KK
LL
MM
NN
10' - 0" 23' - 0" 25' - 0" 10' - 0" 25' - 0" 28' - 0" 21' - 3" 14' - 9" 13' - 0" 26' - 0"
5'
0"
196' - 0"
8'
0"
9'
0"
0"
3'
1/
2" 6'
1/ 2"
6'
1/
2"
/2
5'
0"
9'
0" 4'
0"
DN
CLEAN-UP
STORAGE
KITCHEN
THEATER
STORAGE
STORAGE
STORAGE
LOBBY/GATHERING
LOBBY
101B
COAT ALCOVE
CONFERENCE LOBBY
MEN BATHROOM
118 WOMEN BATHROOM
CONFERENCE ROOM
INFORMATION
UP
DATE:
SHEET:
428 N. Last Chance Gulch Helena, Montana 59601
406.449.2013 www.mosaicarch.com
D A
TE
S
TA
M
P a r c h i t e c t u r e - p l a n n i n g - d e s i g n
CITY STAMP
/2
9/
:4 3:
A
M
11.29.2021
A103
FLOOR PLAN
4201 GIANT SPRINGS RD, GREAT FALLS MT
59405
LEWIS & CLARK
INTERPRETIVE CENTER
C O
N S
T R
U C
T I O
N D
O C
U M
E N
T S
1/8" = 1'-0"
LEVEL 1 FLOOR PLAN
# DATE REVISION
A A
B B
CC
DD
EE
FF
GG
HH
STORAGE
STORAGE
PERJECTOR ROOM
013 OPEN TO BELOW
DN
UP
DN
STORAGE
MEZZANINE
A A
B B
CC
DD
EE
FF
GG
HH
II
JJ
KK
LL
MM
NN
TOILET
008A
DRESSING ROOM
STORAGE
Room
TEMPORARY EXHIBIT AREA
011B AREA OF REF.
EXIBITS
EXHIBITS EXPANSION
011A
ELEV. MECH.
UP
STAGE
TOILET
008B
CORRIDOR
STORAGE
OPEN TO ABOVE
DISPLAY
UP
DATE:
SHEET:
428 N. Last Chance Gulch Helena, Montana 59601
406.449.2013 www.mosaicarch.com
D A
TE
S
TA
M
P a r c h i t e c t u r e - p l a n n i n g - d e s i g n
CITY STAMP
/2
9/
:4 3:
A
M
11.29.2021
A104
BASEMENT FLOOR PLAN
4201 GIANT SPRINGS RD, GREAT FALLS MT
59405
LEWIS & CLARK
INTERPRETIVE CENTER
C O
N S
T R
U C
T I O
N D
O C
U M
E N
T S
1/8" = 1'-0"
MEZZANINE
1/8" = 1'-0"
BASEMENT
A
B
CC
DD
EE
FF
GG
HH
II
JJ
KK
LL
MM
NN
CLEAN-UP
STORAGE
KITCHEN
THEATER
COAT ALCOVE
115 CONFERENCE LOBBY
LOBBY/GATHERING
LOBBY
101B
MEN BATHROOM
WOMEN BATHROOM
108' - 0"
110' - 2"
110' - 2"
108' - 0"
110' - 2"
108' - 0" 108' - 0"
108' - 0"
110' - 2"
110' - 2" 108' - 0"
110' - 2"
2'
0"
2' - 0"
2'
0"
2' - 0"
2'
0"
2'
6"
2' - 9"
110' - 0"
108' - 0"
110' - 2"
110' - 0"
108' - 0" 108' - 0" 108' - 0"
110' - 2"110' - 2"110' - 2"
NOT INCLUDED
104' - 2"
106' - 0"
107' - 10"
110' - 2"
CONFERENCE ROOM
T&G
6"X T&G CLEAR FIR BOARDS W/ 1/8" REVEALS,
STAINED, ON 5/8" TYPE X GWB ON LIGHT
GAUGE STEEL FRAMING
OPEN TO STRUCTURE
CEILING LAYOUT NOTES: LAY-IN CEILINGS ARE SHOWN CONCEPTUALLY.
IT IS THE INTENT THE CEILINGS AREA CENTERED WITHIN THE ROOM. IN
ODD SHAPED ROOMS, PRIMARY VISUAL AREA TO BE CENTERED. CEILNG
INSTALLER SHOULD CONSULT WITH THE ARCHITECT IN THE FIELD FOR
ANY AREAS IN WHICH THEY WOULD LIKE TO MODIFY THE LAYOUT FROM
THAT SHOWN ON THE PLAN. MODIFICATIONS MAY BE ALLOWED, AT THE
DISCRETION OF THE ARCHITECT, TO EASE INSTALLATION, SAVE CUTTING,
OR INCREASE VISUAL APPEAL.
CEILING LEGEND
ACT1
2'x2' ACT SYSTEM: ARMSTRONG 'OPTIMA'
TEGULAR W/ PRELUDE XL HEAVY DUTY 15/16"
GRID. SEE SEISMIC INSTALLATION REQ'TS &
DETAILS
GWB 5/8" TYPE "X" GYPSUM WALLBOARD ON
STL. FRAMING - SEE DETAILS. PAINT P1
UNO
NEW CONSTRUCTION
EXISTING ELEMENTS TO REMAIN
LINEWORK LEGEND
1. GENERALLY CENTER CEILING GRIDS IN EACH ROOM AS SHOWN
ON PLANS TO PROVIDE EQUALLY SIZED PANELS ON OPPOSITE
WALLS. IF PLANS INDICATE A GRID ALIGNING WITH A COLUMN,
WALL, SOFFIT, ETC., START GRID AT INDICATED SURFACE.
2. SEE FLOOR PLAN FOR WALL TYPES AND WALLS THAT EXTEND
FULL HEIGHT TO STRUCTURE.
3. SEE TYPICAL DETAILS THIS SHEET.
4. CEILING FIXTURES ARE SHOWN FOR REFERENCE ONLY FOR
COORDINATION WITH CEILING FINISH SYSTEM. SEE MECHANICAL,
ELECTRICAL AND SPRINKLER DRAWINGS FOR ALL CEILING
FIXTURES AND TYPES.
5. SPOT ELEVATIONS ARE FROM FINISH FLOOR TO SURFACE FINISH
OF CEILING AND ARE ROUNDED TO THE NEAREST INCH.
GENERAL CEILING NOTES
DATE:
SHEET:
428 N. Last Chance Gulch Helena, Montana 59601
406.449.2013 www.mosaicarch.com
D A
TE
S
TA
M
P a r c h i t e c t u r e - p l a n n i n g - d e s i g n
CITY STAMP
/2
9/
:4 3:
A
M
11.29.2021
A105
REFLECTED CEILING PLAN -
LEVEL 1
4201 GIANT SPRINGS RD, GREAT FALLS MT
59405
LEWIS & CLARK
INTERPRETIVE CENTER
C O
N S
T R
U C
T I O
N D
O C
U M
E N
T S
1/8" = 1'-0"
LEVEL 1 RCP
A A
B B
CC
DD
EE
FF
GG
HH
II
JJ
KK
LL
MM
NN
90' - 0"
90' - 0" 90' - 0"
89' - 4"
89' - 4"
89' - 4"
89' - 4"
DRESSING ROOM
CORRIDOR
STORAGE
TOILET
008A
TOILET
008B
STORAGE
TEMPORARY EXHIBIT AREA
011B
EXHIBITS EXPANSION
011A
STAGE
BASEMENT LOBBY
A A
B B
CC
DD
EE
FF
GG
STORAGE
STORAGE
PERJECTOR ROOM
STORAGE
MEZZANINE
DATE:
SHEET:
428 N. Last Chance Gulch Helena, Montana 59601
406.449.2013 www.mosaicarch.com
D A
TE
S
TA
M
P a r c h i t e c t u r e - p l a n n i n g - d e s i g n
CITY STAMP
/2
9/
:4 3:
A
M
11.29.2021
A106
REFLECTED CEILING PLAN -
BASEMENT
4201 GIANT SPRINGS RD, GREAT FALLS MT
59405
LEWIS & CLARK
INTERPRETIVE CENTER
C O
N S
T R
U C
T I O
N D
O C
U M
E N
T S
1/8" = 1'-0"
BASEMENT
1/8" = 1'-0"
MEZZANINE
X
LVD
LV
OS OS
P
M
M
M
SPD
L
PFC
X
VFD
G
CB
PNL A
208Y/120V
3ø, 4W
XX
X
J
T V
J
PS-X
X
D-1 X
AP
ELECTRICAL ABBREVIATIONS LEGEND
A, AMP AMPERES
AC ALTERNATING CURRENT
A/C AIR CONDITIONING
AF AMP FUSE
AFC AVAILABLE FAULT CURRENT
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AL ALUMINUM
AS AMP SWITCH
ATS AUTOMATIC TRANSFER SWITCH
BAS BUILDING AUTOMATION SYSTEM
BKR BREAKER
BOF BOTTOM OF FIXTURE
C RACEWAY/CONDUIT
CB CIRCUIT BREAKER
CCT COLOR RENDERING TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
C.O. RACEWAY/CONDUIT ONLY, WITH PULL STRING
COD CENTER OF DEVICE
CNTRL CONTROL
CU COPPER
(D) EXISTING TO BE DEMOLISHED
DISC DISCONNECT
DIST DISTRIBUTION
DPDT DOUBLE POLE DOUBLE THROW
DWG DRAWING
EA EACH
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
ELEC ELECTRIC
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EX, EXIST EXISTING
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
FACP FIRE ALARM CONTROL PANEL
FD FUSED DISCONNECT
FLR FLOOR
FO FIBER OPTIC
FSD FIRE SMOKE DAMPER RELAY, CONTROLLED BY
ASSOCIATED SMOKE DETECTOR AND CIRCUITED
BACK TO FACP
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
GEC GROUNDED ELECTRODE CONDUCTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
GRC GALVANIZED RIGID CONDUIT
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HTR HEATER
HVAC HEATING, VENTILATION & AIR CONDITIONING
HZ HERTZ
J-BOX JUNCTION BOX
KVA KILOVOLT-AMPERES
KW KILOWATTS
LCP LIGHTING CONTROL PANEL
LPW LUMENS PER WATT
LTG LIGHTING
LM LUMENS
LV LOW VOLTAGE
MAG MAGNETIC STARTER
MAN MANUAL
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, PLUMBING
MH METAL HALIDE
MIN MINIMUM
MSS MOTOR STARTER SWITCH WITH THERMAL OVERLOADS
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFD NON-FUSED DISCONNECT
NIC NOT IN CONTRACT
NO NORMALLY OPEN
# NUMBER
OAE OR APPROVED EQUAL
OC ON CENTER
OCPD OVERCURRENT PROTECTIVE DEVICE
OH OVERHEAD
P POLE
PB PUSHBUTTON
PC PLUMBING CONTRACTOR
PH PHASE
PNL PANEL
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
(R) EXISTING TO REMAIN
RCPT RECEPTACLE
RECEPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
RVNR REDUCED VOLTAGE NON-REVERSING
RVR REDUCED VOLTAGE REVERSING
SP SINGLE POLE TOGGLE SWITCH
SPD SURGE PROTECTIVE DEVICE (TVSS)
SPEC SPECIFICATION
SPST SINGLE POLE SINGLE THROW
SSPB START-STOP PUSHBUTTON
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TB TELEPHONE BOARD
TC TIME CLOCK
TD TIME DELAY
TEL TELEPHONE
TR TAMPER RESISTANT
TSP TWISTED SHIELDED PAIR
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
V VOLT
VA VOLT-AMPERES
VFD VARIABLE FREQUENCY DRIVE
W WATTS
WAO WORK AREA OUTLET
WP WEATHERPROOF
W/O WITHOUT
XFMR TRANSFORMER
Y WYE-CONNECTED
Δ DELTA-CONNECTED
ø PHASE
ELECTRICAL LIGHTING FIXTURE LEGEND
RECESSED LED FIXTURE - "a" & "b"
DESIGNATES SWITCH
EXIT SIGN - WALL MOUNT, CEILING MOUNT. ARROW
INDICATES DIRECTION OF TRAVEL, SHADING
INDICATES LIGHTED FACE.
RECESSED EMERGENCY LED FIXTURE - "a" & "b"
DESIGNATES SWITCH
SURFACE LED FIXTURE - "a" & "b" DESIGNATES
SWITCH
SURFACE EMERGENCY LED FIXTURE - "a" & "b"
DESIGNATES SWITCH
SURFACE WALL MOUNT LED FIXTURE
LED STRIP OR INDUSTRIAL, SURFACE OR CHAIN
HUNG
EMERGENCY LED STRIP OR INDUSTRIAL, SURFACE
OR CHAIN HUNG
POLE MOUNTED FIXTURE
LIGHTED BOLLARD
PENDANT FIXTURE; HIGH BAY, LOW BAY,
DECORATIVE
DUAL HEAD EMERGENCY EGRESS BATTERY PACK,
WALL MOUNT OR CEILING MOUNT
WALL MOUNTED SCONCE
SURFACE DOWNLIGHT
SURFACE EMERGENCY DOWNLIGHT
RECESSED CAN DOWNLIGHT
RECESSED CAN EMERGENCY DOWNLIGHT
RECESSED CAN WALL WASHER
TRACK LIGHTING. SEE FIXTURE SCHEDULE AND
LIGHTING PLANS.
COMBINATION EXIT SIGN/ EGRESS LIGHTING UNIT -
WALL MOUNT, CEILING MOUNT. ARROW INDICATES
DIRECTION OF TRAVEL, SHADING INDICATES LIGHTED
FACE.
ELECTRICAL LIGHTING CONTROL LEGEND
TOGGLE SWITCH (MOUNT AT +48", UNO)
"X" INDICATES TYPE:
BLANK - SINGLE POLE
3 - INDICATES THREE-WAY
4 - INDICATES FOUR-WAY
D - INDICATES DIMMER SWITCH
PHILIPS SUNRISE - ON/OFF
K - INDICATES KEYED SWITCH
T - INDICATES TIMER
P - INDICATES PILOT LIGHT
OS - INDICATES WALL SWITCH OCC SENSOR
WATTSTOPPER DW100 (SINGLE OR DUAL
DW-200 SWITCH)
OSD - INDICATES WALL SWITCH OCC SENSOR
WITH 0-10V DIMMING - WATTSTOPPER PW-311
a - INDICATES SINGLE POLE LIGHTING SWITCH ZONE FOR ZONE a b - INDICATES SINGLE POLE LIGHTING SWITCH ZONE FOR ZONE b ab - INDICATES LIGHTING SWITCHES WITH
MULTIPLE ZONES
WIRELESS PHOTOCELL - BATERY POWERED,
CEILING MOUNT
STANDARD LIGHTING CONTROLS:
SWITCHES AND LINE VOLTAGE DIMMERS
DIGITAL LIGHTING CONTROLS WITH WIRELESS, (BATTERY
POWERED) LOW VOLTAGE DEVICES AND (LINE VOLTAGE)
RELAYS AS REQUIRED
LOW VOLTAGE DIMMING SWITCH
LOW VOLTAGE SWITCH, # INDICATES NUMBER OF
BUTTONS. NO "#" IS A 2 BUTTON SWITCH
WIRELESS OCCUPANCY SENSOR - BATTERY
POWERED, PIR TECHNOLOGY, CEILING MOUNT
(PENDANT HUNG IN BASEMENT AT HEIGHT TO MATCH
TRACK LIGHTS, AND WALL MOUNT (AT +96", UNO)
DIMMING RELAY/POWER PACKS ARE NOT SHOWN,
BUT SHALL BE PROVIDED AS REQUIRED.
RELAY/POWER PACKS SHALL COMMUNICATE
WIRELESSLY WITH SENSORS
ELECTRICAL ONE-LINE LEGEND
MOTOR
CT AND CUSTOMER POWER METER
UTILITY ELECTRIC METER AND BASE (BASE BY
CUSTOMER)
SURGE PROTECTION DEVICE
LIGHTNING ARRESTER, TYPE 1 SPD, MOUNTED ON
EXTERIOR OF MAIN SWITCHGEAR (SQUARE D NO.
SDSA3650, OAE)
STRESS RELIEF CONE
POWER FACTOR CORRECTION CAPACITOR
EQUIPMENT TOGGLE DISCONNECT SWITCH
"X" INDICATES TYPE:
F - FUSTAT
M - MOTOR STARTER SWITCH W/ THERMAL
OVERLOADS
CONTACTOR NORMALLY OPEN, NORMALLY CLOSED
TRANSFORMER, 3-PH, 3-WIRE DELTA CONNECTION
TRANSFORMER, 3-PH, 4-WIRE GROUNDED WYE
CONNECTION
AUTOMATIC TRANSFER SWITCH
VARIABLE FREQUENCY DRIVE
FIXED MOUNT LV BREAKER
FUSED SWITCH ("XXAS/XXAF" - SW AND FUSE AMP
RATING)
GENERATOR
WALL MOUNTED BREAKER
THERMAL OVERLOAD ELEMENT
DISCONNECT SWITCH ("XXAS" = SWITCH AMP RATING)
FUSED DISCONNECT SWITCH ("XXAS/XXAF" = SW AND
FUSE AMP RATING)
COMBINATION MOTOR STARTER (STR SIZE, TYP, AS,
AF, SEE MEP COORDINATION SCHEDULE)
SWITCHBOARD OR PANELBOARD; NAME, VOLTAGE,
PHASE, NUMBER OF WIRES WHEN INDICATED
ELECTRICAL POWER LEGEND
PANEL AND CIRCUIT DESIGNATION ARE SHOWN NEXT
TO EACH DEVICE (PANEL NAME - CIRCUIT NUMBER).
BRANCH CIRCUIT WIRE SIZE IS #12, UNO. A SINGLE
INSULATED GREEN GROUND CONDUCTOR SHALL BE
PROVIDED WITH EACH HOME RUN. PROVIDE A
SEPARATE NEUTRAL FOR EACH CIRCUIT. HOME RUNS
SHALL HAVE NO MORE THAN THREE CIRCUITS. LINE
VOLTAGE AND LOW VOLTAGE WIRING IS NOT SHOWN
ON PLANS. FOR EQUIPMENT CIRCUITING, SEE MEP
COORDINATION SCHEDULE.
"X" INDICATES TYPE:
GFI - GROUND FAULT INTERRUPTER
WP - WEATHERPROOF WHILE-IN-USE COVER
U - PROVIDE WITH (2) USB PORTS
TR - TAMPER RESISTANT
PANELBOARD OR LOAD CENTER
JUNCTION BOX
FLATSCREEN TV BOX: 3-GANG, FLUSH IN WALL, PASS
& SEYMOUR TV3WMTVSSW. DUPLEX RECEPTACLE &
2-SINGLE GANG DATA/ LOW VOLTAGE OPENINGS.
PROVIDE BLANK COVERS FOR LOW VOLTAGE
OPENINGS AND ROUTE AN 1-1 1/4" EMPTY C. TO
CENTER OPENING AND 1-1" EMPTY C. TO SIDE
OPENING. CONDUITS START AT THE TOP OF GANG
OPENING IN WALL AND ROUTE INTO ACCESSIBLE
CEILING SPACE. MOUNT BOX AT +72", UNO
SIMPLEX RECEPTACLE - CEILING MOUNT, WALL
MOUNT (+18", UNO)
DUPLEX RECEPTACLE - CEILING MOUNT, WALL
MOUNT (+18", UNO)
QUADRUPLEX RECEPTACLE - CEILING MOUNT, WALL
MOUNT (+18", UNO)
FLOOR BOX WITH QUADRUPLEX RECEPTACLE - WITH
(2) COMM PORTS, OR WITHOUT COMM AS SHOWN.
FURNISH (1) 2" DEDICATED CONDUIT FROM EACH
DATA COMPARTMENT AS WELL AS (1) 3/4" POWER
CONDUIT FROM BOX. ROUTE DATA CONDUITS,
COMPLETE WITH PULL STRINGS OVER TO AND UP
WALL INTO ACCESSIBLE CEILING SPACE, UNO.
INCLUDE ALL HARDWARE/ACCESSORIES AS
REQUIRED FOR COMPLETE INSTALLATION. PROVIDE
COVER (COORDINATE WITH ARCHITECT FOR
FLOORING TYPE AND FINISH).
SPECIAL PURPOSE RECEPTACLE (MOUNT AT
+18", UNO)
"X" INDICATES TYPE:
A - NEMA 5-20R, #12 CU; B - NEMA 5-30R, #10 CU;
C - NEMA 5-50R, #8 CU; D - NEMA 6-20R, #12 CU;
E - NEMA 6-30R, #10 CU; F - NEMA 6-50R, #8 CU;
G - NEMA 14-20R, #12 CU; H - NEMA 14-30R, #10 CU;
I - NEMA 14-50R, #8 CU*
* +4" AFF FOR RANGE
DROP-DOWN RECEPTACLE
SURFACE MOUNTED PLUGSTRIP
"X" INDICATES TYPE:
A - PLUGSTRIP, POWER ONLY, OUTLET EVERY 3' OC
B - WIREMOLD SERIES 4000 POWER AND DATA
C - WIREMOLD SERIES 5000 POWER AND DATA
SURFACE MOUNTED RACEWAY
RACEWAY CONCEALED IN WALL, FLOOR, OR CEILING
IN FINISHED SPACES, EXPOSED IN UNFINISHED
SPACES
RACEWAY BELOW FLOOR OR BELOW GRADE
RACEWAY STUB-OUT WITH CAPPED END
RACEWAY STUB-OUT WITH BRUSHED END
GROUNDING BUS
PUSHBUTTON (MOUNT AT +48", UNO)
"X" INDICATES TYPE:
EPO - EMERGENCY POWER OFF
ADA - HANDICAPPED ACCESSIBLE DOOR
(DEVICE BY OTHERS)
ODO - OVERHEAD DOOR OPERATOR
(DEVICE BY OTHERS)
"X" INDICATES TYPE:
A - 4-GANG FLOOR BOX, CORROSION RESISTANT
COATING FOR CONCRETE FLOORS (3" MIN. POUR
DEPTH), UP TO 2" CONDUIT FEED (HUBBELL NO.
CFB4G30CR, OAE)
B - 4-GANG FLOOR BOX FOR RAISED ACCESS FLOORS,
UP TO 2" CONDUIT FEED (HUBBELL NO. AFB4G50,
OAE)
C - FIRE RATED POKE-THROUGH FLOOR BOX FOR
ELEVATED CONCRETE* SLABS, 3" DIA. CORE
(HUBBELL NO. PT7FSD, OAE)
D - 8" DIA., FIRE RATED POKE-THROUGH FLOOR BOX
FOR ELEVATED CONCRETE* SLABS, UP TO 2"
CONDUIT FEED (HUBBELL NO. S1R8PTFIT3, OAE)
E - FLUSH, ROUND SINGLE SURFACE FLOOR BOX FOR
CONCRETE FLOORS, UP TO 1" CONDUIT FEED
(HUBBELL NO. B2506, OAE)
F - TOMBSTONE PEDESTAL FLOOR BOX, 1" CONDUIT
FEED (HUBBELL NO. 6301, OAE)
* NOTE THAT POKE-THROUGH FLOOR BOXES CAN
ALSO BE USED FOR TILE, CARPET, OR WOOD FLOORS.
ABOVE COUNTER RECEPTACLE - MOUNT AT
+4" ABOVE BACKSPLASH
ELECTRICAL LOW VOLTAGE LEGEND
TELEPHONE/DATA SYSTEM
TELEPHONE OUTLET (MOUNT AT +18", UNO).
SEE NOTE.
VOICE-DATA OUTLET (MOUNT AT +18", UNO).
SEE NOTE.
DATA OUTLET (MOUNT AT +18", UNO). SEE NOTE.
WIRELESS ACCESS POINT
CABLE TRAY OR BASKET TRAY - LENGTH AND HEIGHT
PER PLAN
NOTE: PROVIDE ROUGH-IN ONLY. 4-SQUARE BOX WITH MUD
RING & 1" C. STUBBED UP TO ACCESSIBLE CEILING SPACE.
ELECTRICAL PROJECT GENERAL NOTES
A. PRIOR TO BID CONTRACTOR SHALL VISIT THE SITE. NOT ALL WORK REQUIRED TO COMPLETE THE PROJECT IS SHOWN ON THE DRAWINGS.
THE CONTRACTOR SHALL BECOME THOROUGHLY FAMILIAR WITH ALL THE WORK REQUIRED TO COMPLETE THE PROJECT IN ADDITION TO
THE LOCAL CONDITIONS AND INCLUDE SAID WORK IN THE BID.
B. GENERAL WORK PRACTICES FOR ELECTRICAL CONSTRUCTION SHALL BE IN ACCORDANCE WITH NECA 1, "STANDARD PRACTICES FOR GOOD WORKMANSHIP IN ELECTRICAL CONTRACTING." THIS PUBLICATION IS AVAILABLE FROM NECA BY TELEPHONE AT 301-657-3110 OR ON-LINE AT
WWW.NECANET.ORG.
C. IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE WITH MECHANICAL FOR PLENUM SPACES AND PROVIDE PLENUM RATED CABLES WHERE REQUIRED FOR LIGHTING CONTROL, DATA, FIRE ALARM AND ALL OTHER L.V. SYSTEMS NOT INSTALLED IN CONDUIT. VERIFY CONDUIT
REQUIREMENTS ON DRAWINGS AND SPECIFICATIONS.
D. FIRE-RESISTANCE: PROVIDE A MINIMUM HORIZONTAL DISTANCE OF 24" BETWEEN OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE- RESISTANCE RATED WALLS. WHERE THIS IS NOT POSSIBLE INSTALL UL LISTED PUTTY PADS ON ALL OUTLET BOXES NOT MEETING THE 24" SEPARATION. PROVIDE A UL LISTED THROUGH -PENETRATION FIRESTOP FOR PENETRATIONS OF FIRE-RESISTANCE RATED ASSEMBLIES.
E. CONDUCTORS ARE SIZED PER THE 75 DEGREE C RATING COLUMN OF NEC TABLE 310.16. IF THE TERMINAL USED FOR A TERMINATION OF A PARTICULAR CONDUCTOR IS NOT MARKED, OR THE TERMINAL IS MARKED FOR 60 DEGREE C CONDUCTORS, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO EITHER ADJUST THE AMPACITY OF THE CONDUCTOR TO MATCH THE 60 DEGREE COLUMN OF TABLE 310.16, OR
REPLACE THE TERMINAL WITH ONE RATED FOR AT LEAST 75 DEGREES C.
F. BASED ON ACTUAL HOMERUN LENGTHS REQUIRED IN THE FIELD, THE CONTRACTOR SHALL CALCULATE AND INCREASE THE WIRE SIZES AS REQUIRED TO LIMIT BRANCH CIRCUIT VOLTAGE DROP TO 3%. FOR 20A BRANCH CIRCUITS THE MINIMUM CONDUCTOR SIZES SHALL BE AS FOLLOWS: #10 AWG CU FOR RUNS BETWEEN 100 AND 200 LINEAR FEET, #8 AWG CU FOR RUNS BETWEEN 200 AND 325 LINEAR FEET, AND AS CALCULATED BY THE CONTRACTOR FOR CIRCUITS EXTENDING BEYOND 325 LINEAR FEET. IN ALL CASES WHERE WIRE SIZES INCREASE, THE
CONTRACTOR SHALL PROVIDE LARGER CONDUITS AS REQUIRED.
G. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH 120V BRANCH CIRCUIT.
ABBREVIATIONS AND SYMBOLS GENERAL NOTES
A. THE ABBREVIATIONS ON THIS SHEET COMPRISE A STANDARD LIST; NOT ALL ABBREVIATIONS APPEAR ON THIS PROJECT.
B. THE SYMBOLS ON THIS SHEET COMPRISE A STANDARD LIST; NOT ALL SYMBOLS APPEAR ON THIS PROJECT.
C. ALL MOUNTING HEIGHTS ARE TO CENTER OF DEVICE ABOVE FINISHED FLOOR, UNLESS NOTED OTHERWISE. ELECTRICAL CONTRACTOR
SHALL COORDINATE WITH OTHER CONTRACTORS, MAKING ADJUSTMENTS AS REQUIRED TO AVOID INTERFERENCE WITH EQUIPMENT SUCH AS BASEBOARD FIN-TUBE, CABINET UNIT HEATERS, ETC. ARCHITECT/ENGINEER SHALL BE NOTIFIED OF ALL SUCH HEIGHT ADJUSTMENTS.
MOUNTING HEIGHTS INDICATED ON ARCHITECTURAL WALL ELEVATIONS OR AS NOTED SPECIFICALLY ON THE DRAWINGS OR IN THE
SPECIFICATIONS SHALL TAKE PRECEDENCE OVER MOUNTING HEIGHTS LISTED.
ELECTRICAL PROJECT DEMO NOTES
A. DURING DEMOLITION, THE CONTRACTOR SHALL NOTE ALL EXISTING RACEWAY (BOTH SURFACE AND CONCEALED) TO THE EXTENT
POSSIBLE. THESE RACEWAYS SHALL BE REUSED TO THE GREATEST EXTENT POSSIBLE TO INSURE A CLEAN FINISHED PRODUCT. WHERE PRACTICAL, AND ALLOWED PER CODE, FISHING THROUGH WALLS WITH MC CABLE IS PREFERRED TO SURFACE-MOUNTED CONDUIT.
B. CONTRACTOR SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OF LAMPS AND BALLASTS OFF-SITE. IT IS ASSUMED THAT THE BALLASTS DO NOT CONTAIN PCBs. THE CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY IF IT IS SUSPECTED THAT BALLASTS CONTAIN PCBs.
C. ALL POWER INTERRUPTIONS SHALL BE COORDINATED WITH OWNER. ANY DISRUPTION OF WORKERS IN THE SPACE SHALL BE KEPT TO A MINIMUM AND BE COORDINATED WITH THE OWNER PRIOR TO WORK COMMENCING IN THAT SPACE.
D. CONTRACTOR SHALL EXTEND UNSWITCHED HOT LEG FROM EXISTING EMERGENCY FIXTURE LOCATION TO NEW EMERGENCY FIXTURES, AS NEEDED. SEE DEMO PLANS FOR AN APPROXIMATION OF EXISTING EMERGENCY FIXTURE LOCATIONS. FIELD VERIFY EXACT LOCATION PRIOR
TO BID.
E. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY EXISTING CONDUIT OR FEEDER CIRCUITS THAT ARE INTENDED TO REMAIN THAT ARE SAW-CUT, OR OTHERWISE DAMAGED, AS PART OF THE DEMOLITION PROCESS. PROVISION FOR THIS WORK SHALL INCLUDE, BUT NOT BE LIMITED TO: ALL NECESSARY CONDUIT AND CONDUCTORS, MOUNTING ACCESSORIES AND LABOR, TO RESTORE THE
SYSTEM TO ITS INTENDED FUNCTION.
F. ELECTRICAL DRAWINGS SHOWING EXISTING BUILDING CONDITIONS, SUCH AS DEMOLITION DRAWINGS, EXISTING PANEL SCHEDULES, ETC ARE BASED ON RECORD DRAWINGS AND SITE VISITS. IF ACTUAL EXISTING CONDITIONS DIFFER FROM THOSE SHOWN ON DRAWINGS, PLEASE
NOTIFY ENGINEER.
DATE:
SHEET:
428 N. Last Chance Gulch Helena, Montana 59601
406.449.2013 www.mosaicarch.com
D A
TE
S
TA
M
P a r c h i t e c t u r e - p l a n n i n g - d e s i g n
CITY STAMP
-D ec -2
9:
:2
29 November 2021
E101
ELECTRICAL SYMBOLS AND
ABBREVIATIONS
4201 Giant Springs Road Great Falls, MT 59405
Lewis and Clark Interpretive Center
Lighting Upgrade
C o n s t r u c t io n D o c u m e n t s
# DATE REVISION
I S S
E F
O R
P
LAN
O EN
G
IN
E E R
ON
T
M
AN
A
LICENSE
D
GARTH L.
STEVENS
No. 11492 PE
DATE:
SHEET:
428 N. Last Chance Gulch Helena, Montana 59601
406.449.2013 www.mosaicarch.com
D A
TE
S
TA
M
P a r c h i t e c t u r e - p l a n n i n g - d e s i g n
CITY STAMP
-D ec -2
9:
:2
29 November 2021
E102
LIGHTING SCHEDULES AND
DETAILS
4201 Giant Springs Road Great Falls, MT 59405
Lewis and Clark Interpretive Center
Lighting Upgrade
C o n s t r u c t io n D o c u m e n t s
NOTES:
1. IN ADDITION TO OCCUPANCY SENSORS, LIGHTING LEVELS FOR THESE TRACKS ARE CONTROLLED BY PHOTO SENSORS FOR DAYLIGHT HAVESTING.
46 h 1 TLC-17 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
45 h 1 TLC-17 BLACK
(2) 96 +
(2) 24
LSI (2) TRK-SC-021-120-B 2.5 TCL-2.5-B 120 1 1 '+' FITTING 1 SUSPENDED 144 T1 8
44 h 1 TLC-17 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
43 g 1 TLC-15 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
42 g 1 TLC-15 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
41 g 1 TLC-15 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
40 f 1 TLC-13 BLACK 24 LSI TRK-SC-021-120-B 0.5 TCL-0.5-B 120 1 1 1 SUSPENDED 144 T1 1
39 f 1 TLC-13 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 90-DEG 1 SUSPENDED 144 T1 6
38 f 1 TLC-13 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
37 f 1 TLC-13 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
36 e 1 TLC-11 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
35 e 1 TLC-11 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
34 e 1 TLC-11 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 168 T1 2
33 e 1 TLC-11 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
32 e 1 TLC-11 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 1 SURF. & SUSP. 120 T1 6
31 d 1 TLC-9 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE WALL T1 4 1
30 d 1 TLC-9 BLACK (2) 144 LSI (2) TRK-SC-121-120-B 2.5 TCL-2.5-B 120 1 1 STRAIGHT 1 SURFACE WALL T1 9 1
29 d 1 TLC-9 BLACK 48 LSI TRK-SC-042-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2 1
28 d 1 TLC-9 BLACK 48 LSI TRK-SC-042-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2 1
27 d 1 TLC-9 BLACK 48 LSI TRK-SC-042-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2 1
26 d 1 TLC-9 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE SOFFIT T1 4 1
25 d 1 TLC-9 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SURFACE SOFFIT T1 2 1
24 c 1 TLC-7 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
23 c 1 TLC-7 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
22 c 1 TLC-7 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
21 c 1 TLC-7 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
20 c 1 TLC-7 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
19 c 1 TLC-7 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
18 c 1 TLC-5 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6
17 c 1 TLC-5 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
16 c 1 TLC-5 BLACK 24 LSI TRK-SC-021-120-B 0.5 TCL-0.5-B 120 1 1 1 SUSPENDED 144 T1 1
15 c 1 TLC-5 BLACK 24 LSI TRK-SC-021-120-B 0.5 TCL-0.5-B 120 1 1 1 SUSPENDED 144 T1 1
14 c 1 TLC-5 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
13 c 1 TLC-5 BLACK 24 LSI TRK-SC-021-120-B 0.5 TCL-0.5-B 120 1 1 1 SUSPENDED 144 T1 1
12 c 1 TLC-5 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
11 b 1 TLC-3 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
10 b 1 TLC-3 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
09 b 1 TLC-3 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
08 b 1 TLC-3 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE CEILING T1 4
07 b 1 TLC-3 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE CEILING T1 4
06 b 1 TLC-3 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
05 b 1 TLC-3 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
04 a 1 TLC-1 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
03 a 1 TLC-1 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
02 a 1 TLC-1 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
01 a 1 TLC-1 BLACK 24 LSI TRK-SC-021-120-B 0.5 TCL-0.5-B 120 1 1 1 SUSPENDED 144 T1 1
QTY DESIG
LIMIT
(A)
PART NO. VOLTS
PWR
FEED
CNTL
FEED
CONNECTORS
END
CAP
LTR QTY
TRACK
ID
ZONE
CIRCUIT
COLOR
LENG
(IN)
MFGR PART NO.
POWER HARDWARE
MOUNTING
HEIGHT
(IN AFF)
HEADS
NOTES
TRACK SCHEDULE
91 v 1 TLC-16 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE CEILING T1 4
90 v 1 TLC-16 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE CEILING T1 4
89 u 1 TLC-14 WHITE 96 LSI TRK-SC-081-120-W 1.5 TCL-1.5-W 120 1 1 1 SURFACE CEILING T1 4
88 t 1 TLC-12 WHITE 96 LSI TRK-SC-081-120-W 1.5 TCL-1.5-W 120 1 1 1 SURFACE CEILING T1 4
87 u 1 TLC-14 WHITE 96 LSI TRK-SC-081-120-W 1.5 TCL-1.5-W 120 1 1 1 SURFACE CEILING T1 4
86 t 1 TLC-12 WHITE 96 LSI TRK-SC-081-120-W 1.5 TCL-1.5-W 120 1 1 1 SURFACE CEILING T1 4
85 u 1 TLC-14 WHITE 96 LSI TRK-SC-081-120-W 1.5 TCL-1.5-W 120 1 1 1 SURFACE CEILING T1 4
84 t 1 TLC-12 WHITE 96 LSI TRK-SC-081-120-W 1.5 TCL-1.5-W 120 1 1 1 SURFACE CEILING T1 4
83 s 1 TLC-10 WHITE (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-W 120 1 1 STRAIGHT 1 SURFACE CEILING T1 6
82 s 1 TLC-10 WHITE (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-W 120 1 1 STRAIGHT 1 SURFACE CEILING T1 6
81 r 1 TLC-8 WHITE (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-W 120 1 1 STRAIGHT 1 SURFACE CEILING T1 6
80 r 1 TLC-8 WHITE (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-W 120 1 1 STRAIGHT 1 SURFACE CEILING T1 6
79 q 1 TLC-6 WHITE 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE CEILING T1 4
78 p 1 TLC-4 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SURFACE SOFFIT T1 2 1
77 p 1 TLC-4 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SURFACE SOFFIT T1 2 1
76 p 1 TLC-4 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE SOFFIT T1 4 1
75 p 1 TLC-4 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE SOFFIT T1 4 1
74 p 1 TLC-4 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SURFACE SOFFIT T1 2 1
73 o 1 TLC-2 WHITE 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SURFACE WALL T1 2
72 o 1 TLC-2 WHITE 144 LSI TRK-SC-121-120-B 2.0 TCL-2-B 120 1 1 1 SURFACE WALL T1 5
71 o 1 TLC-2 WHITE 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE WALL T1 4
70 a 1 TLC-1 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
69 a 1 TLC-1 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
68 n 1 TLC-29 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
67 n 1 TLC-29 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
66 n 1 TLC-29 BLACK 144 LSI TRK-SC-121-120-B 2.0 TCL-2-B 120 1 1 1 SUSPENDED 144 T1 5
65 n 1 TLC-29 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
64 n 1 TLC-29 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6
63 n 1 TLC-29 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
62 m 1 TLC-27 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6
61 m 1 TLC-27 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6
60 m 1 TLC-27 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
59 l 1 TLC-25 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
58 l 1 TLC-25 BLACK 96 + 48 LSI
TRK-SC-081-120-B
TRK-SC-041-120-B
2.0 TCL-2-B 120 1 1 90-DEG 1 SUSPENDED 144 T1 5
57 l 1 TLC-25 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
56 k 1 TLC-23 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
55 k 1 TLC-23 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
54 k 1 TLC-23 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6
53 k 1 TLC-23 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
52 j 1 TLC-21 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6
51 j 1 TLC-21 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 ANGLE ADJUST 1 SUSPENDED 144 T1 6
50 i 1 TLC-19 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2
49 i 1 TLC-19 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6
48 h 1 TLC-17 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
47 h 1 TLC-17 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4
QTY DESIG
LIMIT
(A)
PART NO. VOLTS
PWR
FEED
CNTL
FEED
CONNECTORS
END
CAP
LTR QTY
TRACK
ID
ZONE
CIRCUIT
COLOR
LENG
(IN)
MFGR PART NO.
POWER HARDWARE
MOIUNTING
HEIGHT
(IN AFF)
HEADS
NOTES
TRACK SCHEDULE (CONTINUED)
Notes:
Total Est. Demand: 53 A
Total Conn.: 42 A
Total Est. Demand: 19050 VA
Total Conn. Load: 15240 VA
Lighting 15240 VA 125.00% 19050 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 39 A 46 A 44 A
Total Load: 4680 VA 5400 VA 5160 VA
41 SPARE -- 20 A 1 0 0 42
39 SPARE -- 20 A 1 0 0 40
37 SPARE -- 20 A 1 0 0
3 200 A -- SPARE
35 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 36
33 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 34
31 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 32
29 TRACK LIGHTS 63, 64, 65, 66, 67, 68 Lighting 20 A 1 1020 0 1 20 A -- SPARE 30
27 TRACK LIGHTS 60, 61, 62 Lighting 20 A 1 660 0 1 20 A -- SPARE 28
25 TRACK LIGHTS 57, 58, 59 Lighting 20 A 1 600 0 1 20 A -- SPARE 26
23 TRACK LIGHTS 53, 54, 55, 56 Lighting 20 A 1 780 0 1 20 A -- SPARE 24
21 TRACK LIGHTS 51, 52 Lighting 20 A 1 480 0 1 20 A -- SPARE 22
19 TRACK LIGHTS 49, 50 Lighting 20 A 1 360 0 1 20 A -- SPARE 20
17 TRACK LIGHTS 44, 45, 46, 47, 48 Lighting 20 A 1 960 0 1 20 A -- SPARE 18
15 TRACK LIGHTS 41, 42,43 Lighting 20 A 1 540 360 1 20 A Lighting TRACK LIGHTS 90, 91 16
13 TRACK LIGHTS 37, 38, 39, 40 Lighting 20 A 1 540 540 1 20 A Lighting TRACK LIGHTS 85, 87, 89 14
11 TRACK LIGHTS 32, 33, 34, 35, 36 Lighting 20 A 1 840 540 1 20 A Lighting TRACK LIGHTS 84, 86, 88 12
9 TRACK LIGHTS 25, 26, 27, 28, 29, 30, 31 Lighting 20 A 1 1140 480 1 20 A Lighting TRACK LIGHTS 82, 83 10
7 TRACK LIGHTS 19, 20, 21,22, 23, 24 Lighting 20 A 1 840 480 1 20 A Lighting TRACK LIGHTS 80, 81 8
5 TRACK LIGHTS 12, 13, 14, 15, 16, 17, 18 Lighting 20 A 1 840 180 1 20 A Lighting TRACK LIGHTS 79 6
3 TRACK LIGHTS 05, 06, 07, 08, 09, 10, 11 Lighting 20 A 1 1020 720 1 20 A Lighting TRACK LIGHTS 74, 75, 76, 77, 78 4
1 TRACK LIGHTS 01, 02, 03, 04, 69, 70 Lighting 20 A 1 780 540 1 20 A Lighting TRACK LIGHTS 71, 72, 73 2
CKT Circuit Description Load
Classification Trip Poles A B C Poles Trip Load
Classification Circuit Description CKT
Notes:
Enclosure: Type 1
Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: Phases: 3 Mains Type: MCB
Location: STORAGE 014 Volts: 120/208 Wye A.I.C. Rating: 22,000
Branch Panel: TLC
LIGHTING CONTROL NOTES:
EXHIBIT AREA TRACK LIGHTING:
A. AFTER THE TRACK IS INSTALLED AND ENERGIZED, ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OWNER TO DETERMINE HOW MANY HEADS ARE
REQUIRED ON EACH TRACK AND HOW THEY NEED TO BE AIMED.
B. AFTER TRACK HEADS ARE INSTALLED AND AIMED, ELECTRICAL CONTRACTOR SHALL WORK WITH OWNER TO SET THE APPROPRIATE ILLUMINATION LEVEL
FOR THE EXHIBIT(S) LIT BY EACH TRACK.
C. THIS LEVEL THEN BECOMES THE TRIM SETTING FOR THAT TRACK.
D. WHEN MOTION IS SENSED IN A ZONE, THE LIGHTS ASSOCIATED WITH THAT ZONE WILL GO TO THAT TRIM LEVEL AND STAY AT THAT LEVEL UNTIL NO
OCCUPANCY IS SENSED FOR 20 MINUTES AT WHICH TIME THE LIGHTING LEVEL WILL DROP TO 30% OF THE TRIM SETTING.
E. IN THE DAYLIGHT HARVEST AREA, THE SENSORS SHALL BE SET TO MAINTAIN 30 FOOT-CANDLES AT THE FLOOR LEVEL AND WILL DIM THE TRACK LIGHTING
WHENEVER NATURAL LIGHT ILLUMINATES THE AREA BRIGHTER THAN THAT LEVEL.
• WHEN NO OCCUPANCY IS SENSED FOR 20 MINUTES, THE LIGHTING LEVEL WILL DROP TO 10 FOOT-CANDLES AT THE FLOOR LEVEL.
• WHEN OCCUPANCY IS AGAIN SENSED, THE LIGHTING LEVEL WILL RETURN TO 30 FOOT-CANDLES AT THE FLOOR LEVEL.
# DATE REVISION
I S S
E F
O R
P
LAN
O EN
G
IN
E E R
ON
T
M
AN
A
LICENSE
D
GARTH L.
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
1 2 3 4 5 6 7
A
B
C
D
E
F
G
H
I
J
K
L
M
N
59 57
F3F3
F3
F1E
F1
F1
F1
D1E
D1 D1
D1
D1
D1
D1
D1 D1
D1
D1
D1
D1
D1
D1
D1
D1E
D1E
D1E
D1E
D1E
D1E
C1 C1C1
C1
F1
D1E
D1
D1
D1E
D1E
D1
D1
D1E
D1
3' - 10" 3' - 10"4 4
ELEVATOR
ELEVATOR
F1
F2 F1
F1
F1 a a b b a a a aa a a a a a a a b b b b b b b c c c c c c c c c c c c c c c c d d d d d d d d d e e e e e e e f f f f f f g g g g g g h h h h h h h i i i j j j j j k k k k k k k l l l l m m m m n n n n n n n n a l a
DASHED LINE DENOTES
DAYLIGHT HARVEST AREA
TYP
TYP
5 5
BASEMENT
LOBBY
Redundant
Room
EXIBITS
5690 SF
EXHIBITS
EXPANSION
011A
720 SF
TEMPORARY
EXHIBIT
AREA
011B
543 SF
F6
F6
GENERAL ELECTRICAL NOTES
A. IT IS ABSOLUTELY NECESSARY FOR ELECTRICAL CONTRACTOR TO VERIFY
THAT THERE ARE NO CONFLICTS IN LOCATION OF DUCTS, CONDUITS,
DIFFUSERS, BOXES, AND OTHER ITEMS THROUGHOUT THIS PROJECT
BEFORE FINAL PLACEMENT OF MATERIALS.
B. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS,
WALLS AND CEILINGS TO PERFORM THE REQUIRED WORK DEPICTED IN
THESE DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR ALL
PATCHING OF HOLES TO THE SATISFACTION OF THE ARCHITECT/ENGINEER.
C. DURING DEMOLITION, THE CONTRACTOR SHALL NOTE ALL EXISTING
RACEWAY (BOTH SURFACE AND CONCEALED) TO THE EXTENT POSSIBLE.
THESE RACEWAYS SHALL BE REUSED TO THE GREATEST EXTENT POSSIBLE
TO INSURE A CLEAN FINISHED PRODUCT. WHERE PRACTICAL, AND
ALLOWED PER CODE, FISHING THROUGH WALLS WITH MC CABLE IS
PREFERRED TO SURFACE-MOUNTED CONDUIT.
D. CONTRACTOR SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OF
LAMPS AND BALLASTS OFF-SITE. IT IS ASSUMED THAT THE BALLASTS DO
NOT CONTAIN PCBS. THE CONTRACTOR SHALL NOTIFY THE OWNER
IMMEDIATELY IF IT IS SUSPECTED THAT BALLASTS CONTAIN PCBS.
E. ALL POWER INTERRUPTIONS SHALL BE COORDINATED WITH OWNER. ANY
DISRUPTION OF WORKERS IN THE SPACE SHALL BE KEPT TO A MINIMUM
AND BE COORDINATED WITH THE OWNER PRIOR TO WORK COMMENCING IN
THAT SPACE.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY
EXISTING CONDUIT OR FEEDER CIRCUITS THAT ARE INTENDED TO REMAIN
THAT ARE SAW-CUT, OR OTHERWISE DAMAGED, AS PART OF THE
DEMOLITION PROCESS. PROVISION FOR THIS WORK SHALL INCLUDE, BUT
NOT BE LIMITED TO: ALL NECESSARY CONDUIT AND CONDUCTORS,
MOUNTING ACCESSORIES AND LABOR, TO RESTORE THE SYSTEM TO ITS
INTENDED FUNCTION.
G. ELECTRICAL DRAWINGS SHOWING EXISTING BUILDING CONDITIONS, SUCH
AS DEMOLITION DRAWINGS, EXISTING PANEL SCHEDULES, ETC ARE BASED
ON RECORD DRAWINGS AND SITE VISITS. IF ACTUAL EXISTING CONDITIONS
DIFFER FROM THOSE SHOWN ON DRAWINGS, PLEASE NOTIFY ENGINEER.
H. LOW VOLTAGE CABLES (LIGHTING CONTROLS) ABOVE ACCESSIBLE
CEILINGS, AND WHERE EXPOSED IN OPEN CEILING AREAS SHALL BE
SUPPORTED USING J-HOOKS AT INTERVALS NOT TO EXCEED 48" OC, UNO.
LOW VOLTAGE CABLES SHALL BE BLACK AND J-HOOKS SHALL BE PAINTED
BLACK WHERE INSTALLED IN OPEN CEILING AREAS.
I. UNLESS NOTED OTHERWISE, NEW LIGHT FIXTURES SHALL REPLACE OLD
FIXTURES IN THE SAME LOCATION AND WITH THE SAME CIRCUIT AND
CONTROLS.
J. NEW TRACK SHALL REPLACE EXISTING TRACK IN THE SAME LOCATIONS,
USING EXISTING ALL-THREAD RODS AND FLEX CONNECTIONS WHEREVER
POSSIBLE.
K. OCCUPANCY SENSORS AND ASSOCIATED POWER PACKS/RELAYS SHALL BE
WIRED. THESE WILL COMMUNICATE WIRELESSLY WITH THE RECEIVER ON
EACH TRACK.
L. OCCUPANCY SENSORS SHOWN ON PLANS DO NOT INDICATE EXACT
LOCATIONS. SENSORS SHALL BE INSTALLED IN LOCATIONS TO BEST COVER
THE AREA AND AVOID CONFLICTS WITH OBSTRUCTIONS, AIR VENTS, ETC. IN
ACCORDANCE WITH MANUFACTURER’S GUIDELINES.
M. WHEN MULTIPLE OCCUPANCY SENSORS ARE LOCATED IN A SINGLE SPACE,
CONNECT DEVICES TOGETHER SUCH THAT THE ACTIVATION OF ANY ONE
SENSOR TURNS ON OR KEEPS ON ALL LIGHTS IN THAT AREA.
N. OCCUPANCY SENSORS INSTALLED IN REST ROOM AREAS SHALL BE SET
FOR A 30-MINUTE TIME OUT DELAY. OCCUPANCY SENSORS INSTALLED IN
THE DISPLAY AREAS SHALL BE SET FOR A 20-DELAY. OCCUPANCY SENSORS
INSTALLED IN OFFICES, CONFERENCE ROOMS, CORRIDORS AND COMMON
AREAS SHALL BE SET FOR A 15-MINUTE DELAY.
O. SUBSCRIPT AT EACH LIGHT FIXTURE INDICATES THE RELAY GROUP OR
ZONE IN THE LOCAL CONTROL PACK WITH WHICH THE FIXTURE IS
ASSOCIATED. THE MATCHING SUBSCRIPT AT EACH OCCUPANCY SENSOR
INDICATES THE SENSORS THAT CONTROL THOSE FIXTURES. WHERE NO
SUBSCRIPTS ARE INCLUDED, THE FIXTURES ARE ALL CONTROLLED
TOGETHER IN THAT AREA.
P. LIGHTING CONTROL METHODS VARY IN DIFFERENT SPACES THROUGHOUT
THE PROJECT. SEE PLAN VIEWS AND DETAILS FOR FURTHER
CLARIFICATION. DATE:
SHEET:
428 N. Last Chance Gulch Helena, Montana 59601
406.449.2013 www.mosaicarch.com
D A
TE
S
TA
M
P a r c h i t e c t u r e - p l a n n i n g - d e s i g n
CITY STAMP
-D ec -2
9:
:2
29 November 2021
E200
BASEMENT - LIGHTING PLAN
4201 Giant Springs Road Great Falls, MT 59405
Lewis and Clark Interpretive Center
Lighting Upgrade
C o n s t r u c t io n D o c u m e n t s
1/8" = 1'-0"1
BASEMENT - LIGHTING PLAN
KEY NOTES:#
BID ALTERNATE 1:
1. REPLACE EXISTING TRACK LIGHTING. SEE SHEET E102 FOR CIRCUITING.
2. PROVIDE NEW 16' TRACK AND MOUNT AT 144" AFF WITH ALL-THREAD ROD.
PAINT ROD AND FLEX POWER FEED BLACK. CIRCUIT AS SHOWN.
3. REPLACE EXISTING FIXTURES ABOVE DISPLAYS WITH NEW LED FIXTURES.
COORDINATE WORK WITH OWNER TO ENSURE THAT FRAGILE DISPLAYS ARE
REMOVED PRIOR TO THE WORK IN ORDER TO AVOID DAMAGE TO THE
DISPLAY.
BID ALTERNATE 2:
4. PROVIDE DIMMABLE LED TAPE LIGHTING TO FIT IN EXISTING 1/4" NOMINAL
SLOT IN BULLNOSE HARDWARE OF EACH STAIR TREAD. REUSE EXISTING
CIRCUITING THAT IS ACCESSED VIA FLUSH MOUNTED J-BOXES IN WALL.
BID ALTERNATE 3:
5. REPLACE/RETROFIT EXISTING FIXTURES.
6. REPLACE PENDANT LUMINAIRES THAT SUPLIMENT THE TRACK LIGHTING FOR
CLEANING AND MAINTENANCE AS WELL AS SERVING AS EMERGENCY
EGRESS LIGHTING.
7. PROVIDE NEW PENDANT LIGHT AND MOUNT UP NEAR CEILING (MATCHING
HEIGHT OF OTHER PENDANT LIGHTS). PAINT FLEX POWER FEED BLACK.
CIRCUIT TO LOCAL CIRCUIT THAT FEEDS OTHER PENDANT FIXTURES IN THE
AREA.
1. LIGHTING IN THIS PORTION OF THE BUILDING IS OUTSIDE THE SCOPE OF
THIS PROJECT.
BID ALTERNATE NOTES:
BID ALTERNATE 1:
A. REPLACE EXISTING THEATRICAL DIMMING EQUIPMENT THAT CONTROLS
POWER TO TRACK LIGHTING THROUGHOUT THE EXHIBIT AREAS IN
BASEMENT, MEZZANINE AND LEVEL 1.
B. REPLACE TRACK LIGHTING IN BASEMENT, MEZZANINE AND LEVEL 1 WITH
NEW TRACK LIGHTING THAT INCLUDES PROVISION FOR 0-10V CONTROL OF
THE TRACK HEADS.
C. PROVIDE OCCUPANCY SENSORS AND RELAY POWER PACKS TO ALLOW FOR
CONTROL OF TRACK LIGHTING BASED ON OCCUPANCY.
D. COORDINATE INSTALLATION, AIMING AND DIMMER SETTINGS FOR TRACK
HEADS ON ALL NEW TRACK.
E. MAINTAIN EXISTING CONTROL 4, A/V CONTROLS IN THE THEATER.
BID ALTERNATE 2:
A. REPLACE THE EXISTING STAIR TREAD LIGHTING IN THE THEATER WITH NEW
LED TAPE LIGHTING AND ENSURE THAT IT FUNCTIONS IN THE SAME MANNER
AS THE EXISTING STAIR TREAD LIGHTING.
BID ALTERNATE 3:
A. REPLACE/RETROFIT LIGHTING IN EXISITNG OFFICES, CONFERENCE ROOMS
AND BACK OF HOUSE AREAS WITH LED FIXTURES. THIS INCLUDES THE HIGH-
BAY LIGHT FIXTURES IN THE BASEMENT EXHIBIT AREA THAT SUPLIMENT THE
TRACK LIGHTING IN THAT AREA.
B. PROVIDE OCCUPANCY SENSOR CONTROLS OF REPLACED/RETROFIT
LUMINAIRES IN EXISITNG OFFICES, CONFERENCE ROOMS AND BACK OF
HOUSE AREASAS SHOWN ON PLANS.
# DATE REVISION
I S S
E F
O R
P
LAN
O EN
G
IN
E E R
ON
T
M
AN
A
LICENSE
D
GARTH L.
L V
O S
OS
LVDLVD
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
P
P
1 2 3 4 5 6 7
8 9 10 11
A
B
C
D
E
F
G
H
I
J
K
L
M
N
B2E
B2 B2 B2 B2
B2EB2B2
B2 B2 B2B2B2
F4
F4
F3
F3
B4 B4 B4 B4E
B4
F3 F3 F3
B1
B1E
B1
B1E B1
B1B1
B1E B1
B1
C3 C3
C3C3
C4 C4
C4
C4
C4
C4
B4
B4E
B4B4 B4 B4 B4E B3 B3
B3
B3
B3
B3
B3B3
B3
B3
C1
F6 F6
F6F6
C1
B4
F5
F5
C2
C3C3 C3 90 91
B1E
B1
B1
B1B1
B1
84 85
B1 B1
7 7
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
C2
ELEVATOR
ELEVATOR
p p p p p q r r ut s s ut ut vv
DASHED LINE DENOTES
DAYLIGHT HARVEST AREA
6 6
6 6 6
3 3
TYP ALL TRACK
GENERAL ELECTRICAL NOTES
A. IT IS ABSOLUTELY NECESSARY FOR ELECTRICAL CONTRACTOR TO VERIFY
THAT THERE ARE NO CONFLICTS IN LOCATION OF DUCTS, CONDUITS,
DIFFUSERS, BOXES, AND OTHER ITEMS THROUGHOUT THIS PROJECT
BEFORE FINAL PLACEMENT OF MATERIALS.
B. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS,
WALLS AND CEILINGS TO PERFORM THE REQUIRED WORK DEPICTED IN
THESE DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR ALL
PATCHING OF HOLES TO THE SATISFACTION OF THE ARCHITECT/ENGINEER.
C. DURING DEMOLITION, THE CONTRACTOR SHALL NOTE ALL EXISTING
RACEWAY (BOTH SURFACE AND CONCEALED) TO THE EXTENT POSSIBLE.
THESE RACEWAYS SHALL BE REUSED TO THE GREATEST EXTENT POSSIBLE
TO INSURE A CLEAN FINISHED PRODUCT. WHERE PRACTICAL, AND
ALLOWED PER CODE, FISHING THROUGH WALLS WITH MC CABLE IS
PREFERRED TO SURFACE-MOUNTED CONDUIT.
D. CONTRACTOR SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OF
LAMPS AND BALLASTS OFF-SITE. IT IS ASSUMED THAT THE BALLASTS DO
NOT CONTAIN PCBS. THE CONTRACTOR SHALL NOTIFY THE OWNER
IMMEDIATELY IF IT IS SUSPECTED THAT BALLASTS CONTAIN PCBS.
E. ALL POWER INTERRUPTIONS SHALL BE COORDINATED WITH OWNER. ANY
DISRUPTION OF WORKERS IN THE SPACE SHALL BE KEPT TO A MINIMUM
AND BE COORDINATED WITH THE OWNER PRIOR TO WORK COMMENCING IN
THAT SPACE.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY
EXISTING CONDUIT OR FEEDER CIRCUITS THAT ARE INTENDED TO REMAIN
THAT ARE SAW-CUT, OR OTHERWISE DAMAGED, AS PART OF THE
DEMOLITION PROCESS. PROVISION FOR THIS WORK SHALL INCLUDE, BUT
NOT BE LIMITED TO: ALL NECESSARY CONDUIT AND CONDUCTORS,
MOUNTING ACCESSORIES AND LABOR, TO RESTORE THE SYSTEM TO ITS
INTENDED FUNCTION.
G. ELECTRICAL DRAWINGS SHOWING EXISTING BUILDING CONDITIONS, SUCH
AS DEMOLITION DRAWINGS, EXISTING PANEL SCHEDULES, ETC ARE BASED
ON RECORD DRAWINGS AND SITE VISITS. IF ACTUAL EXISTING CONDITIONS
DIFFER FROM THOSE SHOWN ON DRAWINGS, PLEASE NOTIFY ENGINEER.
H. LOW VOLTAGE CABLES (LIGHTING CONTROLS) ABOVE ACCESSIBLE
CEILINGS, AND WHERE EXPOSED IN OPEN CEILING AREAS SHALL BE
SUPPORTED USING J-HOOKS AT INTERVALS NOT TO EXCEED 48" OC, UNO.
LOW VOLTAGE CABLES SHALL BE BLACK AND J-HOOKS SHALL BE PAINTED
BLACK WHERE INSTALLED IN OPEN CEILING AREAS.
I. UNLESS NOTED OTHERWISE, NEW LIGHT FIXTURES SHALL REPLACE OLD
FIXTURES IN THE SAME LOCATION AND WITH THE SAME CIRCUIT AND
CONTROLS.
J. NEW TRACK SHALL REPLACE EXISTING TRACK IN THE SAME LOCATIONS,
USING EXISTING ALL-THREAD RODS AND FLEX CONNECTIONS WHEREVER
POSSIBLE.
K. OCCUPANCY SENSORS AND ASSOCIATED POWER PACKS/RELAYS SHALL BE
WIRED. THESE WILL COMMUNICATE WIRELESSLY WITH THE RECEIVER ON
EACH TRACK.
L. OCCUPANCY SENSORS SHOWN ON PLANS DO NOT INDICATE EXACT
LOCATIONS. SENSORS SHALL BE INSTALLED IN LOCATIONS TO BEST COVER
THE AREA AND AVOID CONFLICTS WITH OBSTRUCTIONS, AIR VENTS, ETC. IN
ACCORDANCE WITH MANUFACTURER’S GUIDELINES.
M. WHEN MULTIPLE OCCUPANCY SENSORS ARE LOCATED IN A SINGLE SPACE,
CONNECT DEVICES TOGETHER SUCH THAT THE ACTIVATION OF ANY ONE
SENSOR TURNS ON OR KEEPS ON ALL LIGHTS IN THAT AREA.
N. OCCUPANCY SENSORS INSTALLED IN REST ROOM AREAS SHALL BE SET
FOR A 30-MINUTE TIME OUT DELAY. OCCUPANCY SENSORS INSTALLED IN
THE DISPLAY AREAS SHALL BE SET FOR A 20-DELAY. OCCUPANCY SENSORS
INSTALLED IN OFFICES, CONFERENCE ROOMS, CORRIDORS AND COMMON
AREAS SHALL BE SET FOR A 15-MINUTE DELAY.
O. SUBSCRIPT AT EACH LIGHT FIXTURE INDICATES THE RELAY GROUP OR
ZONE IN THE LOCAL CONTROL PACK WITH WHICH THE FIXTURE IS
ASSOCIATED. THE MATCHING SUBSCRIPT AT EACH OCCUPANCY SENSOR
INDICATES THE SENSORS THAT CONTROL THOSE FIXTURES. WHERE NO
SUBSCRIPTS ARE INCLUDED, THE FIXTURES ARE ALL CONTROLLED
TOGETHER IN THAT AREA.
P. LIGHTING CONTROL METHODS VARY IN DIFFERENT SPACES THROUGHOUT
THE PROJECT. SEE PLAN VIEWS AND DETAILS FOR FURTHER
CLARIFICATION.
DATE:
SHEET:
428 N. Last Chance Gulch Helena, Montana 59601
406.449.2013 www.mosaicarch.com
D A
TE
S
TA
M
P a r c h i t e c t u r e - p l a n n i n g - d e s i g n
CITY STAMP
-D ec -2
9:
:2
29 November 2021
E201
LEVEL 1 - LIGHTING PLAN
4201 Giant Springs Road Great Falls, MT 59405
Lewis and Clark Interpretive Center
Lighting Upgrade
C o n s t r u c t io n D o c u m e n t s
1/8" = 1'-0"1
LEVEL 1 - LIGHTING PLAN
KEY NOTES:#
1. LIGHTING IN THIS PORTION OF THE BUILDING IS OUTSIDE THE SCOPE OF THIS
PROJECT.
2. LIGHT FIXTURES IN CEILING OF THEATER WERE RECENTLY UPGRADED AND
WILL REMAIN AS THEY ARE. EXISTING CONTROL 4 PANEL WILL CONTINUE TO
CONTROL THESE FIXTURES.
BID ALTERNATE 1:
3. REPLACE EXISTING TRACK LIGHTING. SEE SHEET E102 FOR CIRCUITING.
4. PROVIDE PHOTO SENSORS AND MOUNT ON CEILING WHERE THEY CAN BE
ACCESSED FROM A LADDER ON LEVEL 1. SENSORS WILL CONTROL ZONES 'd' AND 'p' TRACK LIGHTS.
5. REPLACE EXISTING LIGHTING CONTROL TOUCHSCREEN WITH NEW ONE
INTEGRATED INTO NEW LIGHTING CONTROL SYSTEM.
BID ALTERNATE 3:
6. REPLACE/RETROFIT EXISTING FIXTURES. RE-USE EXISTING CIRCUITS AND
INSTALL OCCUPANCY SENSOR CONTROLS AS SHOWN.
7. PROVIDE (2) RECESSED LIGHT FIXTURES OVER THE STAIRS. TIE INTO
CIRCUITTHAT FEEDS THE FIXTURES IN THE OPEN AREA.
BID ALTERNATE NOTES:
BID ALTERNATE 1:
A. REPLACE EXISTING THEATRICAL DIMMING EQUIPMENT THAT CONTROLS
POWER TO TRACK LIGHTING THROUGHOUT THE EXHIBIT AREAS IN
BASEMENT, MEZZANINE AND LEVEL 1.
B. REPLACE TRACK LIGHTING IN BASEMENT, MEZZANINE AND LEVEL 1 WITH
NEW TRACK LIGHTING THAT INCLUDES PROVISION FOR 0-10V CONTROL OF
THE TRACK HEADS.
C. PROVIDE OCCUPANCY SENSORS AND RELAY POWER PACKS TO ALLOW FOR
CONTROL OF TRACK LIGHTING BASED ON OCCUPANCY.
D. COORDINATE INSTALLATION, AIMING AND DIMMER SETTINGS FOR TRACK
HEADS ON ALL NEW TRACK.
E. MAINTAIN EXISTING CONTROL 4, A/V CONTROLS IN THE THEATER.
BID ALTERNATE 2:
A. REPLACE THE EXISTING STAIR TREAD LIGHTING IN THE THEATER WITH NEW
LED TAPE LIGHTING AND ENSURE THAT IT FUNCTIONS IN THE SAME MANNER
AS THE EXISTING STAIR TREAD LIGHTING.
BID ALTERNATE 3:
A. REPLACE/RETROFIT LIGHTING IN EXISITNG OFFICES, CONFERENCE ROOMS
AND BACK OF HOUSE AREAS WITH LED FIXTURES. THIS INCLUDES THE HIGH-
BAY LIGHT FIXTURES IN THE BASEMENT EXHIBIT AREA THAT SUPLIMENT THE
TRACK LIGHTING IN THAT AREA.
B. PROVIDE OCCUPANCY SENSOR CONTROLS OF REPLACED/RETROFIT
LUMINAIRES IN EXISITNG OFFICES, CONFERENCE ROOMS AND BACK OF
HOUSE AREASAS SHOWN ON PLANS.
# DATE REVISION
I S S
E F
O R
P
LAN
O EN
G
IN
E E R
ON
T
M
AN
A
LICENSE
D
GARTH L.
2 3 4
B
C
D
E
F
G
H
F1
C1C1C1
C1B1 B1E
F1 F1E
F1
F1
F1E F1
F1
74 6
ELEVATOR
D12 o o o
C1
C1
TYP
o
NEW TLC PANEL
GENERAL ELECTRICAL NOTES
A. IT IS ABSOLUTELY NECESSARY FOR ELECTRICAL CONTRACTOR TO VERIFY
THAT THERE ARE NO CONFLICTS IN LOCATION OF DUCTS, CONDUITS,
DIFFUSERS, BOXES, AND OTHER ITEMS THROUGHOUT THIS PROJECT
BEFORE FINAL PLACEMENT OF MATERIALS.
B. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS,
WALLS AND CEILINGS TO PERFORM THE REQUIRED WORK DEPICTED IN
THESE DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR ALL
PATCHING OF HOLES TO THE SATISFACTION OF THE ARCHITECT/ENGINEER.
C. DURING DEMOLITION, THE CONTRACTOR SHALL NOTE ALL EXISTING
RACEWAY (BOTH SURFACE AND CONCEALED) TO THE EXTENT POSSIBLE.
THESE RACEWAYS SHALL BE REUSED TO THE GREATEST EXTENT POSSIBLE
TO INSURE A CLEAN FINISHED PRODUCT. WHERE PRACTICAL, AND
ALLOWED PER CODE, FISHING THROUGH WALLS WITH MC CABLE IS
PREFERRED TO SURFACE-MOUNTED CONDUIT.
D. CONTRACTOR SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OF
LAMPS AND BALLASTS OFF-SITE. IT IS ASSUMED THAT THE BALLASTS DO
NOT CONTAIN PCBS. THE CONTRACTOR SHALL NOTIFY THE OWNER
IMMEDIATELY IF IT IS SUSPECTED THAT BALLASTS CONTAIN PCBS.
E. ALL POWER INTERRUPTIONS SHALL BE COORDINATED WITH OWNER. ANY
DISRUPTION OF WORKERS IN THE SPACE SHALL BE KEPT TO A MINIMUM
AND BE COORDINATED WITH THE OWNER PRIOR TO WORK COMMENCING IN
THAT SPACE.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY
EXISTING CONDUIT OR FEEDER CIRCUITS THAT ARE INTENDED TO REMAIN
THAT ARE SAW-CUT, OR OTHERWISE DAMAGED, AS PART OF THE
DEMOLITION PROCESS. PROVISION FOR THIS WORK SHALL INCLUDE, BUT
NOT BE LIMITED TO: ALL NECESSARY CONDUIT AND CONDUCTORS,
MOUNTING ACCESSORIES AND LABOR, TO RESTORE THE SYSTEM TO ITS
INTENDED FUNCTION.
G. ELECTRICAL DRAWINGS SHOWING EXISTING BUILDING CONDITIONS, SUCH
AS DEMOLITION DRAWINGS, EXISTING PANEL SCHEDULES, ETC ARE BASED
ON RECORD DRAWINGS AND SITE VISITS. IF ACTUAL EXISTING CONDITIONS
DIFFER FROM THOSE SHOWN ON DRAWINGS, PLEASE NOTIFY ENGINEER.
H. LOW VOLTAGE CABLES (LIGHTING CONTROLS) ABOVE ACCESSIBLE
CEILINGS, AND WHERE EXPOSED IN OPEN CEILING AREAS SHALL BE
SUPPORTED USING J-HOOKS AT INTERVALS NOT TO EXCEED 48" OC, UNO.
LOW VOLTAGE CABLES SHALL BE BLACK AND J-HOOKS SHALL BE PAINTED
BLACK WHERE INSTALLED IN OPEN CEILING AREAS.
I. UNLESS NOTED OTHERWISE, NEW LIGHT FIXTURES SHALL REPLACE OLD
FIXTURES IN THE SAME LOCATION AND WITH THE SAME CIRCUIT AND
CONTROLS.
J. NEW TRACK SHALL REPLACE EXISTING TRACK IN THE SAME LOCATIONS,
USING EXISTING ALL-THREAD RODS AND FLEX CONNECTIONS WHEREVER
POSSIBLE.
K. OCCUPANCY SENSORS AND ASSOCIATED POWER PACKS/RELAYS SHALL BE
WIRED. THESE WILL COMMUNICATE WIRELESSLY WITH THE RECEIVER ON
EACH TRACK.
L. OCCUPANCY SENSORS SHOWN ON PLANS DO NOT INDICATE EXACT
LOCATIONS. SENSORS SHALL BE INSTALLED IN LOCATIONS…
This is the start of the file's text. The full file is on GovTribe.