Attachment 4 LCIC Lighting Drawings.pdf

PDF 10 MB Posted

Attached to
GAOA LCIC Lighting Upgrades Federal contract opportunity
Solicitation number
1240LU25R0026
Issued by
Department of Agriculture Forest Service

About this file

These documents are construction documents for the Lewis & Clark Interpretive Center located at 4201 Giant Springs Road in Great Falls, Montana. The architectural and electrical plans, prepared by Mosaic Architecture and Morrison-Maierle engineering, detail a multi-level facility with basement, first floor, and mezzanine levels. The electrical plans include comprehensive lighting design with multiple bid alternates focused on replacing and upgrading existing track lighting, theatrical dimming equipment, and fixtures throughout the building.

Key electrical design elements include LED track lighting with 0-10V dimming capabilities, occupancy sensors, photo sensors for daylight harvesting, and provisions for replacing existing lighting control systems. The design covers track lighting in exhibit areas, offices, conference rooms, and back-of-house spaces across different building levels. Bid alternates provide flexibility for the owner, including options to replace theatrical dimming equipment, upgrade stair tread lighting, retrofit existing fixtures, and implement new lighting control systems while maintaining existing A/V controls in the theater.

View the file

Other files for this federal contract opportunity

Other files attached to GAOA LCIC Lighting Upgrades, newest first.
File Type Posted
1240LU25R0026 LCIC Lighting Upgrade.pdf PDF
Attachment 2 Statement of Work.pdf PDF
Attachment 1 Schedule of Items.docx DOCX document
Attachment 3 LCIC Lighting Specifications.pdf PDF
Attacment 5 Wage Determination.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE:

SHEET:

428 N. Last Chance Gulch Helena, Montana 59601

406.449.2013 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

CITY STAMP

/2

9/

:4 3:

A

M

11.29.2021

A000

COVER

4201 GIANT SPRINGS RD, GREAT FALLS MT

59405

LEWIS & CLARK

INTERPRETIVE CENTER

C O

N S

T R

U C

T I O

N D

O C

U M

E N

T S

LEWIS & CLARK INTERPRETIVE CENTER

4201 GIANT SPRINGS RD

GREAT FALLS, MT MOSAIC ARCHITECTURE, P.C.

428 N. LAST CHANCE GULCH

HELENA, MT 59601

(406) 449-2013 CONTACT: MATT AUNE, AIA matta@mosaicarch.com

ARCHITECT:

MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:

THESE DRAWINGS WERE PREPARED BY MOSAIC ARCHITECTURE, P.C. FOR CONSTRUCTION OF THE PROJECT DESCRIBED HEREIN. AS SUCH, THE DOCUMENTS ARE THE PROPERTY OF MOSAIC ARCHITECTURE, P.C. & MAY NOT BE REPRODUCED, COPIED OR USED IN ANY WAY WITHOUT PRIOR APPROVAL FROM MOSAIC ARCHITECTURE, P.C.

SHEET INDEX

PROJECT DIRECTORY

VICINITY MAP

PROJECT SITE

CITY STAMPS

ARCHITECTURAL DRAWINGS

A000 COVER

A002 GENERAL INFORMATION & ASSEMBLY TYPES

A103 FLOOR PLAN

A104 BASEMENT FLOOR PLAN

A105 REFLECTED CEILING PLAN - LEVEL 1

A106 REFLECTED CEILING PLAN - BASEMENT

A108 Unnamed

A109 Unnamed

E101 ELECTRICAL SYMBOLS AND ABBREVIATIONS

E102 LIGHTING SCHEDULES AND DETAILS

E200 BASEMENT - LIGHTING PLAN

E201 LEVEL 1 - LIGHTING PLAN

E202 MEZZANINE - LIGHTING PLAN

ELECTRICAL DRAWINGS

E101 ELECTRICAL SYMBOLS AND ABBREVIATIONS

E102 LIGHTING SCHEDULES AND DETAILS

E200 BASEMENT - LIGHTING PLAN

E201 LEVEL 1 - LIGHTING PLAN

E202 MEZZANINE - LIGHTING PLAN

MORRISON-MAIERLE

1 ENGINEERING PL

HELENA, MT 59601

(406) 442-3050

CONTACT: GARTH STEVENS, gstevens@m-m.net

# DATE REVISION

RECOMMENDED:

LCIC DIRECTOR

APPROVED:

FOREST ENGINEER

FOREST SUPERVISOR

reidstovall Line reidstovall Line reidstovall Line

1. DIMENSIONS ARE TO FACE OF STUD, EXISTING WALL FINISH,

MASONRY, OR DOOR/WINDOW OPENINGS. DIMENSIONS OF EXISTING

CONSTRUCTION ARE NOT SHOWN ON DRAWINGS - VERIFY

DIMENSIONS OF ALL EXISTING CONSTRUCTION IN THE FIELD.

DIMENSIONS TO OPENINGS ARE NOMINAL. VERIFY ALL OPENINGS

WITH ROUGH OPENING REQUIREMENTS.

2. ALL DOOR OPENINGS PERPENDICULAR TO A WALL ARE 4" TO THE

WALL FRAMING UNO.

3. EXISTING CONSTRUCTION TO REMAIN SHOWN SHADED, NEW

CONSTRUCTION SHOWN SOLID.

4. SEE SHEET A-002 FOR WALL TYPES. IN AREAS WITH SUSPENDED

ACOUSTICAL TILE CEILINGS, GYPSUM WALL BOARD MAY BE

TERMINATED 6" ABOVE THE CEILING. IN AREAS WITH EXPOSED

STRUCTURE CONTINUE GYPSUM BOARD TO UNDERSIDE OF

STRUCTURE.

5. VERIFY EXISTING WALL CONSTRUCTION.

6. ALL EGRESS DOORS SHALL BE READILY OPERABLE FROM THE

EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE

OR EFFORT.

GENERAL FLOOR PLAN NOTES

NEW CONSTRUCTION

EXISTING ELEMENTS TO REMAIN

LINEWORK LEGEND

A A

B B

CC

DD

EE

FF

GG

HH

II

JJ

KK

LL

MM

NN

10' - 0" 23' - 0" 25' - 0" 10' - 0" 25' - 0" 28' - 0" 21' - 3" 14' - 9" 13' - 0" 26' - 0"

5'

0"

196' - 0"

8'

0"

9'

0"

0"

3'

1/

2" 6'

1/ 2"

6'

1/

2"

/2

5'

0"

9'

0" 4'

0"

DN

CLEAN-UP

STORAGE

KITCHEN

THEATER

STORAGE

STORAGE

STORAGE

LOBBY/GATHERING

LOBBY

101B

COAT ALCOVE

CONFERENCE LOBBY

MEN BATHROOM

118 WOMEN BATHROOM

CONFERENCE ROOM

INFORMATION

UP

DATE:

SHEET:

428 N. Last Chance Gulch Helena, Montana 59601

406.449.2013 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

CITY STAMP

/2

9/

:4 3:

A

M

11.29.2021

A103

FLOOR PLAN

4201 GIANT SPRINGS RD, GREAT FALLS MT

59405

LEWIS & CLARK

INTERPRETIVE CENTER

C O

N S

T R

U C

T I O

N D

O C

U M

E N

T S

1/8" = 1'-0"

LEVEL 1 FLOOR PLAN

# DATE REVISION

A A

B B

CC

DD

EE

FF

GG

HH

STORAGE

STORAGE

PERJECTOR ROOM

013 OPEN TO BELOW

DN

UP

DN

STORAGE

MEZZANINE

A A

B B

CC

DD

EE

FF

GG

HH

II

JJ

KK

LL

MM

NN

TOILET

008A

DRESSING ROOM

STORAGE

Room

TEMPORARY EXHIBIT AREA

011B AREA OF REF.

EXIBITS

EXHIBITS EXPANSION

011A

ELEV. MECH.

UP

STAGE

TOILET

008B

CORRIDOR

STORAGE

OPEN TO ABOVE

DISPLAY

UP

DATE:

SHEET:

428 N. Last Chance Gulch Helena, Montana 59601

406.449.2013 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

CITY STAMP

/2

9/

:4 3:

A

M

11.29.2021

A104

BASEMENT FLOOR PLAN

4201 GIANT SPRINGS RD, GREAT FALLS MT

59405

LEWIS & CLARK

INTERPRETIVE CENTER

C O

N S

T R

U C

T I O

N D

O C

U M

E N

T S

1/8" = 1'-0"

MEZZANINE

1/8" = 1'-0"

BASEMENT

A

B

CC

DD

EE

FF

GG

HH

II

JJ

KK

LL

MM

NN

CLEAN-UP

STORAGE

KITCHEN

THEATER

COAT ALCOVE

115 CONFERENCE LOBBY

LOBBY/GATHERING

LOBBY

101B

MEN BATHROOM

WOMEN BATHROOM

108' - 0"

110' - 2"

110' - 2"

108' - 0"

110' - 2"

108' - 0" 108' - 0"

108' - 0"

110' - 2"

110' - 2" 108' - 0"

110' - 2"

2'

0"

2' - 0"

2'

0"

2' - 0"

2'

0"

2'

6"

2' - 9"

110' - 0"

108' - 0"

110' - 2"

110' - 0"

108' - 0" 108' - 0" 108' - 0"

110' - 2"110' - 2"110' - 2"

NOT INCLUDED

104' - 2"

106' - 0"

107' - 10"

110' - 2"

CONFERENCE ROOM

T&G

6"X T&G CLEAR FIR BOARDS W/ 1/8" REVEALS,

STAINED, ON 5/8" TYPE X GWB ON LIGHT

GAUGE STEEL FRAMING

OPEN TO STRUCTURE

CEILING LAYOUT NOTES: LAY-IN CEILINGS ARE SHOWN CONCEPTUALLY.

IT IS THE INTENT THE CEILINGS AREA CENTERED WITHIN THE ROOM. IN

ODD SHAPED ROOMS, PRIMARY VISUAL AREA TO BE CENTERED. CEILNG

INSTALLER SHOULD CONSULT WITH THE ARCHITECT IN THE FIELD FOR

ANY AREAS IN WHICH THEY WOULD LIKE TO MODIFY THE LAYOUT FROM

THAT SHOWN ON THE PLAN. MODIFICATIONS MAY BE ALLOWED, AT THE

DISCRETION OF THE ARCHITECT, TO EASE INSTALLATION, SAVE CUTTING,

OR INCREASE VISUAL APPEAL.

CEILING LEGEND

ACT1

2'x2' ACT SYSTEM: ARMSTRONG 'OPTIMA'

TEGULAR W/ PRELUDE XL HEAVY DUTY 15/16"

GRID. SEE SEISMIC INSTALLATION REQ'TS &

DETAILS

GWB 5/8" TYPE "X" GYPSUM WALLBOARD ON

STL. FRAMING - SEE DETAILS. PAINT P1

UNO

NEW CONSTRUCTION

EXISTING ELEMENTS TO REMAIN

LINEWORK LEGEND

1. GENERALLY CENTER CEILING GRIDS IN EACH ROOM AS SHOWN

ON PLANS TO PROVIDE EQUALLY SIZED PANELS ON OPPOSITE

WALLS. IF PLANS INDICATE A GRID ALIGNING WITH A COLUMN,

WALL, SOFFIT, ETC., START GRID AT INDICATED SURFACE.

2. SEE FLOOR PLAN FOR WALL TYPES AND WALLS THAT EXTEND

FULL HEIGHT TO STRUCTURE.

3. SEE TYPICAL DETAILS THIS SHEET.

4. CEILING FIXTURES ARE SHOWN FOR REFERENCE ONLY FOR

COORDINATION WITH CEILING FINISH SYSTEM. SEE MECHANICAL,

ELECTRICAL AND SPRINKLER DRAWINGS FOR ALL CEILING

FIXTURES AND TYPES.

5. SPOT ELEVATIONS ARE FROM FINISH FLOOR TO SURFACE FINISH

OF CEILING AND ARE ROUNDED TO THE NEAREST INCH.

GENERAL CEILING NOTES

DATE:

SHEET:

428 N. Last Chance Gulch Helena, Montana 59601

406.449.2013 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

CITY STAMP

/2

9/

:4 3:

A

M

11.29.2021

A105

REFLECTED CEILING PLAN -

LEVEL 1

4201 GIANT SPRINGS RD, GREAT FALLS MT

59405

LEWIS & CLARK

INTERPRETIVE CENTER

C O

N S

T R

U C

T I O

N D

O C

U M

E N

T S

1/8" = 1'-0"

LEVEL 1 RCP

A A

B B

CC

DD

EE

FF

GG

HH

II

JJ

KK

LL

MM

NN

90' - 0"

90' - 0" 90' - 0"

89' - 4"

89' - 4"

89' - 4"

89' - 4"

DRESSING ROOM

CORRIDOR

STORAGE

TOILET

008A

TOILET

008B

STORAGE

TEMPORARY EXHIBIT AREA

011B

EXHIBITS EXPANSION

011A

STAGE

BASEMENT LOBBY

A A

B B

CC

DD

EE

FF

GG

STORAGE

STORAGE

PERJECTOR ROOM

STORAGE

MEZZANINE

DATE:

SHEET:

428 N. Last Chance Gulch Helena, Montana 59601

406.449.2013 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

CITY STAMP

/2

9/

:4 3:

A

M

11.29.2021

A106

REFLECTED CEILING PLAN -

BASEMENT

4201 GIANT SPRINGS RD, GREAT FALLS MT

59405

LEWIS & CLARK

INTERPRETIVE CENTER

C O

N S

T R

U C

T I O

N D

O C

U M

E N

T S

1/8" = 1'-0"

BASEMENT

1/8" = 1'-0"

MEZZANINE

X

LVD

LV

OS OS

P

M

M

M

SPD

L

PFC

X

VFD

G

CB

PNL A

208Y/120V

3ø, 4W

XX

X

J

T V

J

PS-X

X

D-1 X

AP

ELECTRICAL ABBREVIATIONS LEGEND

A, AMP AMPERES

AC ALTERNATING CURRENT

A/C AIR CONDITIONING

AF AMP FUSE

AFC AVAILABLE FAULT CURRENT

AFCI ARC FAULT CIRCUIT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AL ALUMINUM

AS AMP SWITCH

ATS AUTOMATIC TRANSFER SWITCH

BAS BUILDING AUTOMATION SYSTEM

BKR BREAKER

BOF BOTTOM OF FIXTURE

C RACEWAY/CONDUIT

CB CIRCUIT BREAKER

CCT COLOR RENDERING TEMPERATURE

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

C.O. RACEWAY/CONDUIT ONLY, WITH PULL STRING

COD CENTER OF DEVICE

CNTRL CONTROL

CU COPPER

(D) EXISTING TO BE DEMOLISHED

DISC DISCONNECT

DIST DISTRIBUTION

DPDT DOUBLE POLE DOUBLE THROW

DWG DRAWING

EA EACH

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

ELEC ELECTRIC

EMT ELECTRICAL METALLIC TUBING

EQUIP EQUIPMENT

EX, EXIST EXISTING

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR

FACP FIRE ALARM CONTROL PANEL

FD FUSED DISCONNECT

FLR FLOOR

FO FIBER OPTIC

FSD FIRE SMOKE DAMPER RELAY, CONTROLLED BY

ASSOCIATED SMOKE DETECTOR AND CIRCUITED

BACK TO FACP

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

GEC GROUNDED ELECTRODE CONDUCTOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFI GROUND FAULT INTERRUPTER

GFP GROUND FAULT PROTECTION

GND GROUND

GRC GALVANIZED RIGID CONDUIT

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HTR HEATER

HVAC HEATING, VENTILATION & AIR CONDITIONING

HZ HERTZ

J-BOX JUNCTION BOX

KVA KILOVOLT-AMPERES

KW KILOWATTS

LCP LIGHTING CONTROL PANEL

LPW LUMENS PER WATT

LTG LIGHTING

LM LUMENS

LV LOW VOLTAGE

MAG MAGNETIC STARTER

MAN MANUAL

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPACITY

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MEP MECHANICAL, ELECTRICAL, PLUMBING

MH METAL HALIDE

MIN MINIMUM

MSS MOTOR STARTER SWITCH WITH THERMAL OVERLOADS

N NEUTRAL

NC NORMALLY CLOSED

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NFD NON-FUSED DISCONNECT

NIC NOT IN CONTRACT

NO NORMALLY OPEN

# NUMBER

OAE OR APPROVED EQUAL

OC ON CENTER

OCPD OVERCURRENT PROTECTIVE DEVICE

OH OVERHEAD

P POLE

PB PUSHBUTTON

PC PLUMBING CONTRACTOR

PH PHASE

PNL PANEL

PVC POLYVINYL CHLORIDE CONDUIT

PWR POWER

(R) EXISTING TO REMAIN

RCPT RECEPTACLE

RECEPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RM ROOM

RVNR REDUCED VOLTAGE NON-REVERSING

RVR REDUCED VOLTAGE REVERSING

SP SINGLE POLE TOGGLE SWITCH

SPD SURGE PROTECTIVE DEVICE (TVSS)

SPEC SPECIFICATION

SPST SINGLE POLE SINGLE THROW

SSPB START-STOP PUSHBUTTON

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TB TELEPHONE BOARD

TC TIME CLOCK

TD TIME DELAY

TEL TELEPHONE

TR TAMPER RESISTANT

TSP TWISTED SHIELDED PAIR

TTB TELEPHONE TERMINAL BOARD

TYP TYPICAL

UG UNDERGROUND

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

V VOLT

VA VOLT-AMPERES

VFD VARIABLE FREQUENCY DRIVE

W WATTS

WAO WORK AREA OUTLET

WP WEATHERPROOF

W/O WITHOUT

XFMR TRANSFORMER

Y WYE-CONNECTED

Δ DELTA-CONNECTED

ø PHASE

ELECTRICAL LIGHTING FIXTURE LEGEND

RECESSED LED FIXTURE - "a" & "b"

DESIGNATES SWITCH

EXIT SIGN - WALL MOUNT, CEILING MOUNT. ARROW

INDICATES DIRECTION OF TRAVEL, SHADING

INDICATES LIGHTED FACE.

RECESSED EMERGENCY LED FIXTURE - "a" & "b"

DESIGNATES SWITCH

SURFACE LED FIXTURE - "a" & "b" DESIGNATES

SWITCH

SURFACE EMERGENCY LED FIXTURE - "a" & "b"

DESIGNATES SWITCH

SURFACE WALL MOUNT LED FIXTURE

LED STRIP OR INDUSTRIAL, SURFACE OR CHAIN

HUNG

EMERGENCY LED STRIP OR INDUSTRIAL, SURFACE

OR CHAIN HUNG

POLE MOUNTED FIXTURE

LIGHTED BOLLARD

PENDANT FIXTURE; HIGH BAY, LOW BAY,

DECORATIVE

DUAL HEAD EMERGENCY EGRESS BATTERY PACK,

WALL MOUNT OR CEILING MOUNT

WALL MOUNTED SCONCE

SURFACE DOWNLIGHT

SURFACE EMERGENCY DOWNLIGHT

RECESSED CAN DOWNLIGHT

RECESSED CAN EMERGENCY DOWNLIGHT

RECESSED CAN WALL WASHER

TRACK LIGHTING. SEE FIXTURE SCHEDULE AND

LIGHTING PLANS.

COMBINATION EXIT SIGN/ EGRESS LIGHTING UNIT -

WALL MOUNT, CEILING MOUNT. ARROW INDICATES

DIRECTION OF TRAVEL, SHADING INDICATES LIGHTED

FACE.

ELECTRICAL LIGHTING CONTROL LEGEND

TOGGLE SWITCH (MOUNT AT +48", UNO)

"X" INDICATES TYPE:

BLANK - SINGLE POLE

3 - INDICATES THREE-WAY

4 - INDICATES FOUR-WAY

D - INDICATES DIMMER SWITCH

PHILIPS SUNRISE - ON/OFF

K - INDICATES KEYED SWITCH

T - INDICATES TIMER

P - INDICATES PILOT LIGHT

OS - INDICATES WALL SWITCH OCC SENSOR

WATTSTOPPER DW100 (SINGLE OR DUAL

DW-200 SWITCH)

OSD - INDICATES WALL SWITCH OCC SENSOR

WITH 0-10V DIMMING - WATTSTOPPER PW-311

a - INDICATES SINGLE POLE LIGHTING SWITCH ZONE FOR ZONE a b - INDICATES SINGLE POLE LIGHTING SWITCH ZONE FOR ZONE b ab - INDICATES LIGHTING SWITCHES WITH

MULTIPLE ZONES

WIRELESS PHOTOCELL - BATERY POWERED,

CEILING MOUNT

STANDARD LIGHTING CONTROLS:

SWITCHES AND LINE VOLTAGE DIMMERS

DIGITAL LIGHTING CONTROLS WITH WIRELESS, (BATTERY

POWERED) LOW VOLTAGE DEVICES AND (LINE VOLTAGE)

RELAYS AS REQUIRED

LOW VOLTAGE DIMMING SWITCH

LOW VOLTAGE SWITCH, # INDICATES NUMBER OF

BUTTONS. NO "#" IS A 2 BUTTON SWITCH

WIRELESS OCCUPANCY SENSOR - BATTERY

POWERED, PIR TECHNOLOGY, CEILING MOUNT

(PENDANT HUNG IN BASEMENT AT HEIGHT TO MATCH

TRACK LIGHTS, AND WALL MOUNT (AT +96", UNO)

DIMMING RELAY/POWER PACKS ARE NOT SHOWN,

BUT SHALL BE PROVIDED AS REQUIRED.

RELAY/POWER PACKS SHALL COMMUNICATE

WIRELESSLY WITH SENSORS

ELECTRICAL ONE-LINE LEGEND

MOTOR

CT AND CUSTOMER POWER METER

UTILITY ELECTRIC METER AND BASE (BASE BY

CUSTOMER)

SURGE PROTECTION DEVICE

LIGHTNING ARRESTER, TYPE 1 SPD, MOUNTED ON

EXTERIOR OF MAIN SWITCHGEAR (SQUARE D NO.

SDSA3650, OAE)

STRESS RELIEF CONE

POWER FACTOR CORRECTION CAPACITOR

EQUIPMENT TOGGLE DISCONNECT SWITCH

"X" INDICATES TYPE:

F - FUSTAT

M - MOTOR STARTER SWITCH W/ THERMAL

OVERLOADS

CONTACTOR NORMALLY OPEN, NORMALLY CLOSED

TRANSFORMER, 3-PH, 3-WIRE DELTA CONNECTION

TRANSFORMER, 3-PH, 4-WIRE GROUNDED WYE

CONNECTION

AUTOMATIC TRANSFER SWITCH

VARIABLE FREQUENCY DRIVE

FIXED MOUNT LV BREAKER

FUSED SWITCH ("XXAS/XXAF" - SW AND FUSE AMP

RATING)

GENERATOR

WALL MOUNTED BREAKER

THERMAL OVERLOAD ELEMENT

DISCONNECT SWITCH ("XXAS" = SWITCH AMP RATING)

FUSED DISCONNECT SWITCH ("XXAS/XXAF" = SW AND

FUSE AMP RATING)

COMBINATION MOTOR STARTER (STR SIZE, TYP, AS,

AF, SEE MEP COORDINATION SCHEDULE)

SWITCHBOARD OR PANELBOARD; NAME, VOLTAGE,

PHASE, NUMBER OF WIRES WHEN INDICATED

ELECTRICAL POWER LEGEND

PANEL AND CIRCUIT DESIGNATION ARE SHOWN NEXT

TO EACH DEVICE (PANEL NAME - CIRCUIT NUMBER).

BRANCH CIRCUIT WIRE SIZE IS #12, UNO. A SINGLE

INSULATED GREEN GROUND CONDUCTOR SHALL BE

PROVIDED WITH EACH HOME RUN. PROVIDE A

SEPARATE NEUTRAL FOR EACH CIRCUIT. HOME RUNS

SHALL HAVE NO MORE THAN THREE CIRCUITS. LINE

VOLTAGE AND LOW VOLTAGE WIRING IS NOT SHOWN

ON PLANS. FOR EQUIPMENT CIRCUITING, SEE MEP

COORDINATION SCHEDULE.

"X" INDICATES TYPE:

GFI - GROUND FAULT INTERRUPTER

WP - WEATHERPROOF WHILE-IN-USE COVER

U - PROVIDE WITH (2) USB PORTS

TR - TAMPER RESISTANT

PANELBOARD OR LOAD CENTER

JUNCTION BOX

FLATSCREEN TV BOX: 3-GANG, FLUSH IN WALL, PASS

& SEYMOUR TV3WMTVSSW. DUPLEX RECEPTACLE &

2-SINGLE GANG DATA/ LOW VOLTAGE OPENINGS.

PROVIDE BLANK COVERS FOR LOW VOLTAGE

OPENINGS AND ROUTE AN 1-1 1/4" EMPTY C. TO

CENTER OPENING AND 1-1" EMPTY C. TO SIDE

OPENING. CONDUITS START AT THE TOP OF GANG

OPENING IN WALL AND ROUTE INTO ACCESSIBLE

CEILING SPACE. MOUNT BOX AT +72", UNO

SIMPLEX RECEPTACLE - CEILING MOUNT, WALL

MOUNT (+18", UNO)

DUPLEX RECEPTACLE - CEILING MOUNT, WALL

MOUNT (+18", UNO)

QUADRUPLEX RECEPTACLE - CEILING MOUNT, WALL

MOUNT (+18", UNO)

FLOOR BOX WITH QUADRUPLEX RECEPTACLE - WITH

(2) COMM PORTS, OR WITHOUT COMM AS SHOWN.

FURNISH (1) 2" DEDICATED CONDUIT FROM EACH

DATA COMPARTMENT AS WELL AS (1) 3/4" POWER

CONDUIT FROM BOX. ROUTE DATA CONDUITS,

COMPLETE WITH PULL STRINGS OVER TO AND UP

WALL INTO ACCESSIBLE CEILING SPACE, UNO.

INCLUDE ALL HARDWARE/ACCESSORIES AS

REQUIRED FOR COMPLETE INSTALLATION. PROVIDE

COVER (COORDINATE WITH ARCHITECT FOR

FLOORING TYPE AND FINISH).

SPECIAL PURPOSE RECEPTACLE (MOUNT AT

+18", UNO)

"X" INDICATES TYPE:

A - NEMA 5-20R, #12 CU; B - NEMA 5-30R, #10 CU;

C - NEMA 5-50R, #8 CU; D - NEMA 6-20R, #12 CU;

E - NEMA 6-30R, #10 CU; F - NEMA 6-50R, #8 CU;

G - NEMA 14-20R, #12 CU; H - NEMA 14-30R, #10 CU;

I - NEMA 14-50R, #8 CU*

* +4" AFF FOR RANGE

DROP-DOWN RECEPTACLE

SURFACE MOUNTED PLUGSTRIP

"X" INDICATES TYPE:

A - PLUGSTRIP, POWER ONLY, OUTLET EVERY 3' OC

B - WIREMOLD SERIES 4000 POWER AND DATA

C - WIREMOLD SERIES 5000 POWER AND DATA

SURFACE MOUNTED RACEWAY

RACEWAY CONCEALED IN WALL, FLOOR, OR CEILING

IN FINISHED SPACES, EXPOSED IN UNFINISHED

SPACES

RACEWAY BELOW FLOOR OR BELOW GRADE

RACEWAY STUB-OUT WITH CAPPED END

RACEWAY STUB-OUT WITH BRUSHED END

GROUNDING BUS

PUSHBUTTON (MOUNT AT +48", UNO)

"X" INDICATES TYPE:

EPO - EMERGENCY POWER OFF

ADA - HANDICAPPED ACCESSIBLE DOOR

(DEVICE BY OTHERS)

ODO - OVERHEAD DOOR OPERATOR

(DEVICE BY OTHERS)

"X" INDICATES TYPE:

A - 4-GANG FLOOR BOX, CORROSION RESISTANT

COATING FOR CONCRETE FLOORS (3" MIN. POUR

DEPTH), UP TO 2" CONDUIT FEED (HUBBELL NO.

CFB4G30CR, OAE)

B - 4-GANG FLOOR BOX FOR RAISED ACCESS FLOORS,

UP TO 2" CONDUIT FEED (HUBBELL NO. AFB4G50,

OAE)

C - FIRE RATED POKE-THROUGH FLOOR BOX FOR

ELEVATED CONCRETE* SLABS, 3" DIA. CORE

(HUBBELL NO. PT7FSD, OAE)

D - 8" DIA., FIRE RATED POKE-THROUGH FLOOR BOX

FOR ELEVATED CONCRETE* SLABS, UP TO 2"

CONDUIT FEED (HUBBELL NO. S1R8PTFIT3, OAE)

E - FLUSH, ROUND SINGLE SURFACE FLOOR BOX FOR

CONCRETE FLOORS, UP TO 1" CONDUIT FEED

(HUBBELL NO. B2506, OAE)

F - TOMBSTONE PEDESTAL FLOOR BOX, 1" CONDUIT

FEED (HUBBELL NO. 6301, OAE)

* NOTE THAT POKE-THROUGH FLOOR BOXES CAN

ALSO BE USED FOR TILE, CARPET, OR WOOD FLOORS.

ABOVE COUNTER RECEPTACLE - MOUNT AT

+4" ABOVE BACKSPLASH

ELECTRICAL LOW VOLTAGE LEGEND

TELEPHONE/DATA SYSTEM

TELEPHONE OUTLET (MOUNT AT +18", UNO).

SEE NOTE.

VOICE-DATA OUTLET (MOUNT AT +18", UNO).

SEE NOTE.

DATA OUTLET (MOUNT AT +18", UNO). SEE NOTE.

WIRELESS ACCESS POINT

CABLE TRAY OR BASKET TRAY - LENGTH AND HEIGHT

PER PLAN

NOTE: PROVIDE ROUGH-IN ONLY. 4-SQUARE BOX WITH MUD

RING & 1" C. STUBBED UP TO ACCESSIBLE CEILING SPACE.

ELECTRICAL PROJECT GENERAL NOTES

A. PRIOR TO BID CONTRACTOR SHALL VISIT THE SITE. NOT ALL WORK REQUIRED TO COMPLETE THE PROJECT IS SHOWN ON THE DRAWINGS.

THE CONTRACTOR SHALL BECOME THOROUGHLY FAMILIAR WITH ALL THE WORK REQUIRED TO COMPLETE THE PROJECT IN ADDITION TO

THE LOCAL CONDITIONS AND INCLUDE SAID WORK IN THE BID.

B. GENERAL WORK PRACTICES FOR ELECTRICAL CONSTRUCTION SHALL BE IN ACCORDANCE WITH NECA 1, "STANDARD PRACTICES FOR GOOD WORKMANSHIP IN ELECTRICAL CONTRACTING." THIS PUBLICATION IS AVAILABLE FROM NECA BY TELEPHONE AT 301-657-3110 OR ON-LINE AT

WWW.NECANET.ORG.

C. IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE WITH MECHANICAL FOR PLENUM SPACES AND PROVIDE PLENUM RATED CABLES WHERE REQUIRED FOR LIGHTING CONTROL, DATA, FIRE ALARM AND ALL OTHER L.V. SYSTEMS NOT INSTALLED IN CONDUIT. VERIFY CONDUIT

REQUIREMENTS ON DRAWINGS AND SPECIFICATIONS.

D. FIRE-RESISTANCE: PROVIDE A MINIMUM HORIZONTAL DISTANCE OF 24" BETWEEN OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE- RESISTANCE RATED WALLS. WHERE THIS IS NOT POSSIBLE INSTALL UL LISTED PUTTY PADS ON ALL OUTLET BOXES NOT MEETING THE 24" SEPARATION. PROVIDE A UL LISTED THROUGH -PENETRATION FIRESTOP FOR PENETRATIONS OF FIRE-RESISTANCE RATED ASSEMBLIES.

E. CONDUCTORS ARE SIZED PER THE 75 DEGREE C RATING COLUMN OF NEC TABLE 310.16. IF THE TERMINAL USED FOR A TERMINATION OF A PARTICULAR CONDUCTOR IS NOT MARKED, OR THE TERMINAL IS MARKED FOR 60 DEGREE C CONDUCTORS, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO EITHER ADJUST THE AMPACITY OF THE CONDUCTOR TO MATCH THE 60 DEGREE COLUMN OF TABLE 310.16, OR

REPLACE THE TERMINAL WITH ONE RATED FOR AT LEAST 75 DEGREES C.

F. BASED ON ACTUAL HOMERUN LENGTHS REQUIRED IN THE FIELD, THE CONTRACTOR SHALL CALCULATE AND INCREASE THE WIRE SIZES AS REQUIRED TO LIMIT BRANCH CIRCUIT VOLTAGE DROP TO 3%. FOR 20A BRANCH CIRCUITS THE MINIMUM CONDUCTOR SIZES SHALL BE AS FOLLOWS: #10 AWG CU FOR RUNS BETWEEN 100 AND 200 LINEAR FEET, #8 AWG CU FOR RUNS BETWEEN 200 AND 325 LINEAR FEET, AND AS CALCULATED BY THE CONTRACTOR FOR CIRCUITS EXTENDING BEYOND 325 LINEAR FEET. IN ALL CASES WHERE WIRE SIZES INCREASE, THE

CONTRACTOR SHALL PROVIDE LARGER CONDUITS AS REQUIRED.

G. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH 120V BRANCH CIRCUIT.

ABBREVIATIONS AND SYMBOLS GENERAL NOTES

A. THE ABBREVIATIONS ON THIS SHEET COMPRISE A STANDARD LIST; NOT ALL ABBREVIATIONS APPEAR ON THIS PROJECT.

B. THE SYMBOLS ON THIS SHEET COMPRISE A STANDARD LIST; NOT ALL SYMBOLS APPEAR ON THIS PROJECT.

C. ALL MOUNTING HEIGHTS ARE TO CENTER OF DEVICE ABOVE FINISHED FLOOR, UNLESS NOTED OTHERWISE. ELECTRICAL CONTRACTOR

SHALL COORDINATE WITH OTHER CONTRACTORS, MAKING ADJUSTMENTS AS REQUIRED TO AVOID INTERFERENCE WITH EQUIPMENT SUCH AS BASEBOARD FIN-TUBE, CABINET UNIT HEATERS, ETC. ARCHITECT/ENGINEER SHALL BE NOTIFIED OF ALL SUCH HEIGHT ADJUSTMENTS.

MOUNTING HEIGHTS INDICATED ON ARCHITECTURAL WALL ELEVATIONS OR AS NOTED SPECIFICALLY ON THE DRAWINGS OR IN THE

SPECIFICATIONS SHALL TAKE PRECEDENCE OVER MOUNTING HEIGHTS LISTED.

ELECTRICAL PROJECT DEMO NOTES

A. DURING DEMOLITION, THE CONTRACTOR SHALL NOTE ALL EXISTING RACEWAY (BOTH SURFACE AND CONCEALED) TO THE EXTENT

POSSIBLE. THESE RACEWAYS SHALL BE REUSED TO THE GREATEST EXTENT POSSIBLE TO INSURE A CLEAN FINISHED PRODUCT. WHERE PRACTICAL, AND ALLOWED PER CODE, FISHING THROUGH WALLS WITH MC CABLE IS PREFERRED TO SURFACE-MOUNTED CONDUIT.

B. CONTRACTOR SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OF LAMPS AND BALLASTS OFF-SITE. IT IS ASSUMED THAT THE BALLASTS DO NOT CONTAIN PCBs. THE CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY IF IT IS SUSPECTED THAT BALLASTS CONTAIN PCBs.

C. ALL POWER INTERRUPTIONS SHALL BE COORDINATED WITH OWNER. ANY DISRUPTION OF WORKERS IN THE SPACE SHALL BE KEPT TO A MINIMUM AND BE COORDINATED WITH THE OWNER PRIOR TO WORK COMMENCING IN THAT SPACE.

D. CONTRACTOR SHALL EXTEND UNSWITCHED HOT LEG FROM EXISTING EMERGENCY FIXTURE LOCATION TO NEW EMERGENCY FIXTURES, AS NEEDED. SEE DEMO PLANS FOR AN APPROXIMATION OF EXISTING EMERGENCY FIXTURE LOCATIONS. FIELD VERIFY EXACT LOCATION PRIOR

TO BID.

E. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY EXISTING CONDUIT OR FEEDER CIRCUITS THAT ARE INTENDED TO REMAIN THAT ARE SAW-CUT, OR OTHERWISE DAMAGED, AS PART OF THE DEMOLITION PROCESS. PROVISION FOR THIS WORK SHALL INCLUDE, BUT NOT BE LIMITED TO: ALL NECESSARY CONDUIT AND CONDUCTORS, MOUNTING ACCESSORIES AND LABOR, TO RESTORE THE

SYSTEM TO ITS INTENDED FUNCTION.

F. ELECTRICAL DRAWINGS SHOWING EXISTING BUILDING CONDITIONS, SUCH AS DEMOLITION DRAWINGS, EXISTING PANEL SCHEDULES, ETC ARE BASED ON RECORD DRAWINGS AND SITE VISITS. IF ACTUAL EXISTING CONDITIONS DIFFER FROM THOSE SHOWN ON DRAWINGS, PLEASE

NOTIFY ENGINEER.

DATE:

SHEET:

428 N. Last Chance Gulch Helena, Montana 59601

406.449.2013 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

CITY STAMP

-D ec -2

9:

:2

29 November 2021

E101

ELECTRICAL SYMBOLS AND

ABBREVIATIONS

4201 Giant Springs Road Great Falls, MT 59405

Lewis and Clark Interpretive Center

Lighting Upgrade

C o n s t r u c t io n D o c u m e n t s

# DATE REVISION

I S S

E F

O R

P

LAN

O EN

G

IN

E E R

ON

T

M

AN

A

LICENSE

D

GARTH L.

STEVENS

No. 11492 PE

DATE:

SHEET:

428 N. Last Chance Gulch Helena, Montana 59601

406.449.2013 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

CITY STAMP

-D ec -2

9:

:2

29 November 2021

E102

LIGHTING SCHEDULES AND

DETAILS

4201 Giant Springs Road Great Falls, MT 59405

Lewis and Clark Interpretive Center

Lighting Upgrade

C o n s t r u c t io n D o c u m e n t s

NOTES:

1. IN ADDITION TO OCCUPANCY SENSORS, LIGHTING LEVELS FOR THESE TRACKS ARE CONTROLLED BY PHOTO SENSORS FOR DAYLIGHT HAVESTING.

46 h 1 TLC-17 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

45 h 1 TLC-17 BLACK

(2) 96 +

(2) 24

LSI (2) TRK-SC-021-120-B 2.5 TCL-2.5-B 120 1 1 '+' FITTING 1 SUSPENDED 144 T1 8

44 h 1 TLC-17 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

43 g 1 TLC-15 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

42 g 1 TLC-15 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

41 g 1 TLC-15 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

40 f 1 TLC-13 BLACK 24 LSI TRK-SC-021-120-B 0.5 TCL-0.5-B 120 1 1 1 SUSPENDED 144 T1 1

39 f 1 TLC-13 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 90-DEG 1 SUSPENDED 144 T1 6

38 f 1 TLC-13 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

37 f 1 TLC-13 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

36 e 1 TLC-11 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

35 e 1 TLC-11 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

34 e 1 TLC-11 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 168 T1 2

33 e 1 TLC-11 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

32 e 1 TLC-11 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 1 SURF. & SUSP. 120 T1 6

31 d 1 TLC-9 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE WALL T1 4 1

30 d 1 TLC-9 BLACK (2) 144 LSI (2) TRK-SC-121-120-B 2.5 TCL-2.5-B 120 1 1 STRAIGHT 1 SURFACE WALL T1 9 1

29 d 1 TLC-9 BLACK 48 LSI TRK-SC-042-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2 1

28 d 1 TLC-9 BLACK 48 LSI TRK-SC-042-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2 1

27 d 1 TLC-9 BLACK 48 LSI TRK-SC-042-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2 1

26 d 1 TLC-9 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE SOFFIT T1 4 1

25 d 1 TLC-9 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SURFACE SOFFIT T1 2 1

24 c 1 TLC-7 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

23 c 1 TLC-7 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

22 c 1 TLC-7 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

21 c 1 TLC-7 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

20 c 1 TLC-7 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

19 c 1 TLC-7 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

18 c 1 TLC-5 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6

17 c 1 TLC-5 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

16 c 1 TLC-5 BLACK 24 LSI TRK-SC-021-120-B 0.5 TCL-0.5-B 120 1 1 1 SUSPENDED 144 T1 1

15 c 1 TLC-5 BLACK 24 LSI TRK-SC-021-120-B 0.5 TCL-0.5-B 120 1 1 1 SUSPENDED 144 T1 1

14 c 1 TLC-5 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

13 c 1 TLC-5 BLACK 24 LSI TRK-SC-021-120-B 0.5 TCL-0.5-B 120 1 1 1 SUSPENDED 144 T1 1

12 c 1 TLC-5 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

11 b 1 TLC-3 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

10 b 1 TLC-3 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

09 b 1 TLC-3 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

08 b 1 TLC-3 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE CEILING T1 4

07 b 1 TLC-3 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE CEILING T1 4

06 b 1 TLC-3 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

05 b 1 TLC-3 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

04 a 1 TLC-1 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

03 a 1 TLC-1 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

02 a 1 TLC-1 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

01 a 1 TLC-1 BLACK 24 LSI TRK-SC-021-120-B 0.5 TCL-0.5-B 120 1 1 1 SUSPENDED 144 T1 1

QTY DESIG

LIMIT

(A)

PART NO. VOLTS

PWR

FEED

CNTL

FEED

CONNECTORS

END

CAP

LTR QTY

TRACK

ID

ZONE

CIRCUIT

COLOR

LENG

(IN)

MFGR PART NO.

POWER HARDWARE

MOUNTING

HEIGHT

(IN AFF)

HEADS

NOTES

TRACK SCHEDULE

91 v 1 TLC-16 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE CEILING T1 4

90 v 1 TLC-16 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE CEILING T1 4

89 u 1 TLC-14 WHITE 96 LSI TRK-SC-081-120-W 1.5 TCL-1.5-W 120 1 1 1 SURFACE CEILING T1 4

88 t 1 TLC-12 WHITE 96 LSI TRK-SC-081-120-W 1.5 TCL-1.5-W 120 1 1 1 SURFACE CEILING T1 4

87 u 1 TLC-14 WHITE 96 LSI TRK-SC-081-120-W 1.5 TCL-1.5-W 120 1 1 1 SURFACE CEILING T1 4

86 t 1 TLC-12 WHITE 96 LSI TRK-SC-081-120-W 1.5 TCL-1.5-W 120 1 1 1 SURFACE CEILING T1 4

85 u 1 TLC-14 WHITE 96 LSI TRK-SC-081-120-W 1.5 TCL-1.5-W 120 1 1 1 SURFACE CEILING T1 4

84 t 1 TLC-12 WHITE 96 LSI TRK-SC-081-120-W 1.5 TCL-1.5-W 120 1 1 1 SURFACE CEILING T1 4

83 s 1 TLC-10 WHITE (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-W 120 1 1 STRAIGHT 1 SURFACE CEILING T1 6

82 s 1 TLC-10 WHITE (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-W 120 1 1 STRAIGHT 1 SURFACE CEILING T1 6

81 r 1 TLC-8 WHITE (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-W 120 1 1 STRAIGHT 1 SURFACE CEILING T1 6

80 r 1 TLC-8 WHITE (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-W 120 1 1 STRAIGHT 1 SURFACE CEILING T1 6

79 q 1 TLC-6 WHITE 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE CEILING T1 4

78 p 1 TLC-4 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SURFACE SOFFIT T1 2 1

77 p 1 TLC-4 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SURFACE SOFFIT T1 2 1

76 p 1 TLC-4 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE SOFFIT T1 4 1

75 p 1 TLC-4 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE SOFFIT T1 4 1

74 p 1 TLC-4 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SURFACE SOFFIT T1 2 1

73 o 1 TLC-2 WHITE 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SURFACE WALL T1 2

72 o 1 TLC-2 WHITE 144 LSI TRK-SC-121-120-B 2.0 TCL-2-B 120 1 1 1 SURFACE WALL T1 5

71 o 1 TLC-2 WHITE 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SURFACE WALL T1 4

70 a 1 TLC-1 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

69 a 1 TLC-1 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

68 n 1 TLC-29 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

67 n 1 TLC-29 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

66 n 1 TLC-29 BLACK 144 LSI TRK-SC-121-120-B 2.0 TCL-2-B 120 1 1 1 SUSPENDED 144 T1 5

65 n 1 TLC-29 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

64 n 1 TLC-29 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6

63 n 1 TLC-29 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

62 m 1 TLC-27 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6

61 m 1 TLC-27 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6

60 m 1 TLC-27 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

59 l 1 TLC-25 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

58 l 1 TLC-25 BLACK 96 + 48 LSI

TRK-SC-081-120-B

TRK-SC-041-120-B

2.0 TCL-2-B 120 1 1 90-DEG 1 SUSPENDED 144 T1 5

57 l 1 TLC-25 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

56 k 1 TLC-23 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

55 k 1 TLC-23 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

54 k 1 TLC-23 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6

53 k 1 TLC-23 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

52 j 1 TLC-21 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6

51 j 1 TLC-21 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 ANGLE ADJUST 1 SUSPENDED 144 T1 6

50 i 1 TLC-19 BLACK 48 LSI TRK-SC-041-120-B 1.0 TCL-1-B 120 1 1 1 SUSPENDED 144 T1 2

49 i 1 TLC-19 BLACK (2) 96 LSI (2) TRK-SC-081-120-B 2.0 TCL-2-B 120 1 1 STRAIGHT 1 SUSPENDED 144 T1 6

48 h 1 TLC-17 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

47 h 1 TLC-17 BLACK 96 LSI TRK-SC-081-120-B 1.5 TCL-1.5-B 120 1 1 1 SUSPENDED 144 T1 4

QTY DESIG

LIMIT

(A)

PART NO. VOLTS

PWR

FEED

CNTL

FEED

CONNECTORS

END

CAP

LTR QTY

TRACK

ID

ZONE

CIRCUIT

COLOR

LENG

(IN)

MFGR PART NO.

POWER HARDWARE

MOIUNTING

HEIGHT

(IN AFF)

HEADS

NOTES

TRACK SCHEDULE (CONTINUED)

Notes:

Total Est. Demand: 53 A

Total Conn.: 42 A

Total Est. Demand: 19050 VA

Total Conn. Load: 15240 VA

Lighting 15240 VA 125.00% 19050 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 39 A 46 A 44 A

Total Load: 4680 VA 5400 VA 5160 VA

41 SPARE -- 20 A 1 0 0 42

39 SPARE -- 20 A 1 0 0 40

37 SPARE -- 20 A 1 0 0

3 200 A -- SPARE

35 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 36

33 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 34

31 SPARE -- 20 A 1 0 0 1 20 A -- SPARE 32

29 TRACK LIGHTS 63, 64, 65, 66, 67, 68 Lighting 20 A 1 1020 0 1 20 A -- SPARE 30

27 TRACK LIGHTS 60, 61, 62 Lighting 20 A 1 660 0 1 20 A -- SPARE 28

25 TRACK LIGHTS 57, 58, 59 Lighting 20 A 1 600 0 1 20 A -- SPARE 26

23 TRACK LIGHTS 53, 54, 55, 56 Lighting 20 A 1 780 0 1 20 A -- SPARE 24

21 TRACK LIGHTS 51, 52 Lighting 20 A 1 480 0 1 20 A -- SPARE 22

19 TRACK LIGHTS 49, 50 Lighting 20 A 1 360 0 1 20 A -- SPARE 20

17 TRACK LIGHTS 44, 45, 46, 47, 48 Lighting 20 A 1 960 0 1 20 A -- SPARE 18

15 TRACK LIGHTS 41, 42,43 Lighting 20 A 1 540 360 1 20 A Lighting TRACK LIGHTS 90, 91 16

13 TRACK LIGHTS 37, 38, 39, 40 Lighting 20 A 1 540 540 1 20 A Lighting TRACK LIGHTS 85, 87, 89 14

11 TRACK LIGHTS 32, 33, 34, 35, 36 Lighting 20 A 1 840 540 1 20 A Lighting TRACK LIGHTS 84, 86, 88 12

9 TRACK LIGHTS 25, 26, 27, 28, 29, 30, 31 Lighting 20 A 1 1140 480 1 20 A Lighting TRACK LIGHTS 82, 83 10

7 TRACK LIGHTS 19, 20, 21,22, 23, 24 Lighting 20 A 1 840 480 1 20 A Lighting TRACK LIGHTS 80, 81 8

5 TRACK LIGHTS 12, 13, 14, 15, 16, 17, 18 Lighting 20 A 1 840 180 1 20 A Lighting TRACK LIGHTS 79 6

3 TRACK LIGHTS 05, 06, 07, 08, 09, 10, 11 Lighting 20 A 1 1020 720 1 20 A Lighting TRACK LIGHTS 74, 75, 76, 77, 78 4

1 TRACK LIGHTS 01, 02, 03, 04, 69, 70 Lighting 20 A 1 780 540 1 20 A Lighting TRACK LIGHTS 71, 72, 73 2

CKT Circuit Description Load

Classification Trip Poles A B C Poles Trip Load

Classification Circuit Description CKT

Notes:

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 400 A

Supply From: Phases: 3 Mains Type: MCB

Location: STORAGE 014 Volts: 120/208 Wye A.I.C. Rating: 22,000

Branch Panel: TLC

LIGHTING CONTROL NOTES:

EXHIBIT AREA TRACK LIGHTING:

A. AFTER THE TRACK IS INSTALLED AND ENERGIZED, ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OWNER TO DETERMINE HOW MANY HEADS ARE

REQUIRED ON EACH TRACK AND HOW THEY NEED TO BE AIMED.

B. AFTER TRACK HEADS ARE INSTALLED AND AIMED, ELECTRICAL CONTRACTOR SHALL WORK WITH OWNER TO SET THE APPROPRIATE ILLUMINATION LEVEL

FOR THE EXHIBIT(S) LIT BY EACH TRACK.

C. THIS LEVEL THEN BECOMES THE TRIM SETTING FOR THAT TRACK.

D. WHEN MOTION IS SENSED IN A ZONE, THE LIGHTS ASSOCIATED WITH THAT ZONE WILL GO TO THAT TRIM LEVEL AND STAY AT THAT LEVEL UNTIL NO

OCCUPANCY IS SENSED FOR 20 MINUTES AT WHICH TIME THE LIGHTING LEVEL WILL DROP TO 30% OF THE TRIM SETTING.

E. IN THE DAYLIGHT HARVEST AREA, THE SENSORS SHALL BE SET TO MAINTAIN 30 FOOT-CANDLES AT THE FLOOR LEVEL AND WILL DIM THE TRACK LIGHTING

WHENEVER NATURAL LIGHT ILLUMINATES THE AREA BRIGHTER THAN THAT LEVEL.

• WHEN NO OCCUPANCY IS SENSED FOR 20 MINUTES, THE LIGHTING LEVEL WILL DROP TO 10 FOOT-CANDLES AT THE FLOOR LEVEL.

• WHEN OCCUPANCY IS AGAIN SENSED, THE LIGHTING LEVEL WILL RETURN TO 30 FOOT-CANDLES AT THE FLOOR LEVEL.

# DATE REVISION

I S S

E F

O R

P

LAN

O EN

G

IN

E E R

ON

T

M

AN

A

LICENSE

D

GARTH L.

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

1 2 3 4 5 6 7

A

B

C

D

E

F

G

H

I

J

K

L

M

N

59 57

F3F3

F3

F1E

F1

F1

F1

D1E

D1 D1

D1

D1

D1

D1

D1 D1

D1

D1

D1

D1

D1

D1

D1

D1E

D1E

D1E

D1E

D1E

D1E

C1 C1C1

C1

F1

D1E

D1

D1

D1E

D1E

D1

D1

D1E

D1

3' - 10" 3' - 10"4 4

ELEVATOR

ELEVATOR

F1

F2 F1

F1

F1 a a b b a a a aa a a a a a a a b b b b b b b c c c c c c c c c c c c c c c c d d d d d d d d d e e e e e e e f f f f f f g g g g g g h h h h h h h i i i j j j j j k k k k k k k l l l l m m m m n n n n n n n n a l a

DASHED LINE DENOTES

DAYLIGHT HARVEST AREA

TYP

TYP

5 5

BASEMENT

LOBBY

Redundant

Room

EXIBITS

5690 SF

EXHIBITS

EXPANSION

011A

720 SF

TEMPORARY

EXHIBIT

AREA

011B

543 SF

F6

F6

GENERAL ELECTRICAL NOTES

A. IT IS ABSOLUTELY NECESSARY FOR ELECTRICAL CONTRACTOR TO VERIFY

THAT THERE ARE NO CONFLICTS IN LOCATION OF DUCTS, CONDUITS,

DIFFUSERS, BOXES, AND OTHER ITEMS THROUGHOUT THIS PROJECT

BEFORE FINAL PLACEMENT OF MATERIALS.

B. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS,

WALLS AND CEILINGS TO PERFORM THE REQUIRED WORK DEPICTED IN

THESE DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR ALL

PATCHING OF HOLES TO THE SATISFACTION OF THE ARCHITECT/ENGINEER.

C. DURING DEMOLITION, THE CONTRACTOR SHALL NOTE ALL EXISTING

RACEWAY (BOTH SURFACE AND CONCEALED) TO THE EXTENT POSSIBLE.

THESE RACEWAYS SHALL BE REUSED TO THE GREATEST EXTENT POSSIBLE

TO INSURE A CLEAN FINISHED PRODUCT. WHERE PRACTICAL, AND

ALLOWED PER CODE, FISHING THROUGH WALLS WITH MC CABLE IS

PREFERRED TO SURFACE-MOUNTED CONDUIT.

D. CONTRACTOR SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OF

LAMPS AND BALLASTS OFF-SITE. IT IS ASSUMED THAT THE BALLASTS DO

NOT CONTAIN PCBS. THE CONTRACTOR SHALL NOTIFY THE OWNER

IMMEDIATELY IF IT IS SUSPECTED THAT BALLASTS CONTAIN PCBS.

E. ALL POWER INTERRUPTIONS SHALL BE COORDINATED WITH OWNER. ANY

DISRUPTION OF WORKERS IN THE SPACE SHALL BE KEPT TO A MINIMUM

AND BE COORDINATED WITH THE OWNER PRIOR TO WORK COMMENCING IN

THAT SPACE.

F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY

EXISTING CONDUIT OR FEEDER CIRCUITS THAT ARE INTENDED TO REMAIN

THAT ARE SAW-CUT, OR OTHERWISE DAMAGED, AS PART OF THE

DEMOLITION PROCESS. PROVISION FOR THIS WORK SHALL INCLUDE, BUT

NOT BE LIMITED TO: ALL NECESSARY CONDUIT AND CONDUCTORS,

MOUNTING ACCESSORIES AND LABOR, TO RESTORE THE SYSTEM TO ITS

INTENDED FUNCTION.

G. ELECTRICAL DRAWINGS SHOWING EXISTING BUILDING CONDITIONS, SUCH

AS DEMOLITION DRAWINGS, EXISTING PANEL SCHEDULES, ETC ARE BASED

ON RECORD DRAWINGS AND SITE VISITS. IF ACTUAL EXISTING CONDITIONS

DIFFER FROM THOSE SHOWN ON DRAWINGS, PLEASE NOTIFY ENGINEER.

H. LOW VOLTAGE CABLES (LIGHTING CONTROLS) ABOVE ACCESSIBLE

CEILINGS, AND WHERE EXPOSED IN OPEN CEILING AREAS SHALL BE

SUPPORTED USING J-HOOKS AT INTERVALS NOT TO EXCEED 48" OC, UNO.

LOW VOLTAGE CABLES SHALL BE BLACK AND J-HOOKS SHALL BE PAINTED

BLACK WHERE INSTALLED IN OPEN CEILING AREAS.

I. UNLESS NOTED OTHERWISE, NEW LIGHT FIXTURES SHALL REPLACE OLD

FIXTURES IN THE SAME LOCATION AND WITH THE SAME CIRCUIT AND

CONTROLS.

J. NEW TRACK SHALL REPLACE EXISTING TRACK IN THE SAME LOCATIONS,

USING EXISTING ALL-THREAD RODS AND FLEX CONNECTIONS WHEREVER

POSSIBLE.

K. OCCUPANCY SENSORS AND ASSOCIATED POWER PACKS/RELAYS SHALL BE

WIRED. THESE WILL COMMUNICATE WIRELESSLY WITH THE RECEIVER ON

EACH TRACK.

L. OCCUPANCY SENSORS SHOWN ON PLANS DO NOT INDICATE EXACT

LOCATIONS. SENSORS SHALL BE INSTALLED IN LOCATIONS TO BEST COVER

THE AREA AND AVOID CONFLICTS WITH OBSTRUCTIONS, AIR VENTS, ETC. IN

ACCORDANCE WITH MANUFACTURER’S GUIDELINES.

M. WHEN MULTIPLE OCCUPANCY SENSORS ARE LOCATED IN A SINGLE SPACE,

CONNECT DEVICES TOGETHER SUCH THAT THE ACTIVATION OF ANY ONE

SENSOR TURNS ON OR KEEPS ON ALL LIGHTS IN THAT AREA.

N. OCCUPANCY SENSORS INSTALLED IN REST ROOM AREAS SHALL BE SET

FOR A 30-MINUTE TIME OUT DELAY. OCCUPANCY SENSORS INSTALLED IN

THE DISPLAY AREAS SHALL BE SET FOR A 20-DELAY. OCCUPANCY SENSORS

INSTALLED IN OFFICES, CONFERENCE ROOMS, CORRIDORS AND COMMON

AREAS SHALL BE SET FOR A 15-MINUTE DELAY.

O. SUBSCRIPT AT EACH LIGHT FIXTURE INDICATES THE RELAY GROUP OR

ZONE IN THE LOCAL CONTROL PACK WITH WHICH THE FIXTURE IS

ASSOCIATED. THE MATCHING SUBSCRIPT AT EACH OCCUPANCY SENSOR

INDICATES THE SENSORS THAT CONTROL THOSE FIXTURES. WHERE NO

SUBSCRIPTS ARE INCLUDED, THE FIXTURES ARE ALL CONTROLLED

TOGETHER IN THAT AREA.

P. LIGHTING CONTROL METHODS VARY IN DIFFERENT SPACES THROUGHOUT

THE PROJECT. SEE PLAN VIEWS AND DETAILS FOR FURTHER

CLARIFICATION. DATE:

SHEET:

428 N. Last Chance Gulch Helena, Montana 59601

406.449.2013 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

CITY STAMP

-D ec -2

9:

:2

29 November 2021

E200

BASEMENT - LIGHTING PLAN

4201 Giant Springs Road Great Falls, MT 59405

Lewis and Clark Interpretive Center

Lighting Upgrade

C o n s t r u c t io n D o c u m e n t s

1/8" = 1'-0"1

BASEMENT - LIGHTING PLAN

KEY NOTES:#

BID ALTERNATE 1:

1. REPLACE EXISTING TRACK LIGHTING. SEE SHEET E102 FOR CIRCUITING.

2. PROVIDE NEW 16' TRACK AND MOUNT AT 144" AFF WITH ALL-THREAD ROD.

PAINT ROD AND FLEX POWER FEED BLACK. CIRCUIT AS SHOWN.

3. REPLACE EXISTING FIXTURES ABOVE DISPLAYS WITH NEW LED FIXTURES.

COORDINATE WORK WITH OWNER TO ENSURE THAT FRAGILE DISPLAYS ARE

REMOVED PRIOR TO THE WORK IN ORDER TO AVOID DAMAGE TO THE

DISPLAY.

BID ALTERNATE 2:

4. PROVIDE DIMMABLE LED TAPE LIGHTING TO FIT IN EXISTING 1/4" NOMINAL

SLOT IN BULLNOSE HARDWARE OF EACH STAIR TREAD. REUSE EXISTING

CIRCUITING THAT IS ACCESSED VIA FLUSH MOUNTED J-BOXES IN WALL.

BID ALTERNATE 3:

5. REPLACE/RETROFIT EXISTING FIXTURES.

6. REPLACE PENDANT LUMINAIRES THAT SUPLIMENT THE TRACK LIGHTING FOR

CLEANING AND MAINTENANCE AS WELL AS SERVING AS EMERGENCY

EGRESS LIGHTING.

7. PROVIDE NEW PENDANT LIGHT AND MOUNT UP NEAR CEILING (MATCHING

HEIGHT OF OTHER PENDANT LIGHTS). PAINT FLEX POWER FEED BLACK.

CIRCUIT TO LOCAL CIRCUIT THAT FEEDS OTHER PENDANT FIXTURES IN THE

AREA.

1. LIGHTING IN THIS PORTION OF THE BUILDING IS OUTSIDE THE SCOPE OF

THIS PROJECT.

BID ALTERNATE NOTES:

BID ALTERNATE 1:

A. REPLACE EXISTING THEATRICAL DIMMING EQUIPMENT THAT CONTROLS

POWER TO TRACK LIGHTING THROUGHOUT THE EXHIBIT AREAS IN

BASEMENT, MEZZANINE AND LEVEL 1.

B. REPLACE TRACK LIGHTING IN BASEMENT, MEZZANINE AND LEVEL 1 WITH

NEW TRACK LIGHTING THAT INCLUDES PROVISION FOR 0-10V CONTROL OF

THE TRACK HEADS.

C. PROVIDE OCCUPANCY SENSORS AND RELAY POWER PACKS TO ALLOW FOR

CONTROL OF TRACK LIGHTING BASED ON OCCUPANCY.

D. COORDINATE INSTALLATION, AIMING AND DIMMER SETTINGS FOR TRACK

HEADS ON ALL NEW TRACK.

E. MAINTAIN EXISTING CONTROL 4, A/V CONTROLS IN THE THEATER.

BID ALTERNATE 2:

A. REPLACE THE EXISTING STAIR TREAD LIGHTING IN THE THEATER WITH NEW

LED TAPE LIGHTING AND ENSURE THAT IT FUNCTIONS IN THE SAME MANNER

AS THE EXISTING STAIR TREAD LIGHTING.

BID ALTERNATE 3:

A. REPLACE/RETROFIT LIGHTING IN EXISITNG OFFICES, CONFERENCE ROOMS

AND BACK OF HOUSE AREAS WITH LED FIXTURES. THIS INCLUDES THE HIGH-

BAY LIGHT FIXTURES IN THE BASEMENT EXHIBIT AREA THAT SUPLIMENT THE

TRACK LIGHTING IN THAT AREA.

B. PROVIDE OCCUPANCY SENSOR CONTROLS OF REPLACED/RETROFIT

LUMINAIRES IN EXISITNG OFFICES, CONFERENCE ROOMS AND BACK OF

HOUSE AREASAS SHOWN ON PLANS.

# DATE REVISION

I S S

E F

O R

P

LAN

O EN

G

IN

E E R

ON

T

M

AN

A

LICENSE

D

GARTH L.

L V

O S

OS

LVDLVD

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

P

P

1 2 3 4 5 6 7

8 9 10 11

A

B

C

D

E

F

G

H

I

J

K

L

M

N

B2E

B2 B2 B2 B2

B2EB2B2

B2 B2 B2B2B2

F4

F4

F3

F3

B4 B4 B4 B4E

B4

F3 F3 F3

B1

B1E

B1

B1E B1

B1B1

B1E B1

B1

C3 C3

C3C3

C4 C4

C4

C4

C4

C4

B4

B4E

B4B4 B4 B4 B4E B3 B3

B3

B3

B3

B3

B3B3

B3

B3

C1

F6 F6

F6F6

C1

B4

F5

F5

C2

C3C3 C3 90 91

B1E

B1

B1

B1B1

B1

84 85

B1 B1

7 7

C2

C2

C2

C2

C2

C2

C2

C2

C2

C2

C2

C2

ELEVATOR

ELEVATOR

p p p p p q r r ut s s ut ut vv

DASHED LINE DENOTES

DAYLIGHT HARVEST AREA

6 6

6 6 6

3 3

TYP ALL TRACK

GENERAL ELECTRICAL NOTES

A. IT IS ABSOLUTELY NECESSARY FOR ELECTRICAL CONTRACTOR TO VERIFY

THAT THERE ARE NO CONFLICTS IN LOCATION OF DUCTS, CONDUITS,

DIFFUSERS, BOXES, AND OTHER ITEMS THROUGHOUT THIS PROJECT

BEFORE FINAL PLACEMENT OF MATERIALS.

B. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS,

WALLS AND CEILINGS TO PERFORM THE REQUIRED WORK DEPICTED IN

THESE DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR ALL

PATCHING OF HOLES TO THE SATISFACTION OF THE ARCHITECT/ENGINEER.

C. DURING DEMOLITION, THE CONTRACTOR SHALL NOTE ALL EXISTING

RACEWAY (BOTH SURFACE AND CONCEALED) TO THE EXTENT POSSIBLE.

THESE RACEWAYS SHALL BE REUSED TO THE GREATEST EXTENT POSSIBLE

TO INSURE A CLEAN FINISHED PRODUCT. WHERE PRACTICAL, AND

ALLOWED PER CODE, FISHING THROUGH WALLS WITH MC CABLE IS

PREFERRED TO SURFACE-MOUNTED CONDUIT.

D. CONTRACTOR SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OF

LAMPS AND BALLASTS OFF-SITE. IT IS ASSUMED THAT THE BALLASTS DO

NOT CONTAIN PCBS. THE CONTRACTOR SHALL NOTIFY THE OWNER

IMMEDIATELY IF IT IS SUSPECTED THAT BALLASTS CONTAIN PCBS.

E. ALL POWER INTERRUPTIONS SHALL BE COORDINATED WITH OWNER. ANY

DISRUPTION OF WORKERS IN THE SPACE SHALL BE KEPT TO A MINIMUM

AND BE COORDINATED WITH THE OWNER PRIOR TO WORK COMMENCING IN

THAT SPACE.

F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY

EXISTING CONDUIT OR FEEDER CIRCUITS THAT ARE INTENDED TO REMAIN

THAT ARE SAW-CUT, OR OTHERWISE DAMAGED, AS PART OF THE

DEMOLITION PROCESS. PROVISION FOR THIS WORK SHALL INCLUDE, BUT

NOT BE LIMITED TO: ALL NECESSARY CONDUIT AND CONDUCTORS,

MOUNTING ACCESSORIES AND LABOR, TO RESTORE THE SYSTEM TO ITS

INTENDED FUNCTION.

G. ELECTRICAL DRAWINGS SHOWING EXISTING BUILDING CONDITIONS, SUCH

AS DEMOLITION DRAWINGS, EXISTING PANEL SCHEDULES, ETC ARE BASED

ON RECORD DRAWINGS AND SITE VISITS. IF ACTUAL EXISTING CONDITIONS

DIFFER FROM THOSE SHOWN ON DRAWINGS, PLEASE NOTIFY ENGINEER.

H. LOW VOLTAGE CABLES (LIGHTING CONTROLS) ABOVE ACCESSIBLE

CEILINGS, AND WHERE EXPOSED IN OPEN CEILING AREAS SHALL BE

SUPPORTED USING J-HOOKS AT INTERVALS NOT TO EXCEED 48" OC, UNO.

LOW VOLTAGE CABLES SHALL BE BLACK AND J-HOOKS SHALL BE PAINTED

BLACK WHERE INSTALLED IN OPEN CEILING AREAS.

I. UNLESS NOTED OTHERWISE, NEW LIGHT FIXTURES SHALL REPLACE OLD

FIXTURES IN THE SAME LOCATION AND WITH THE SAME CIRCUIT AND

CONTROLS.

J. NEW TRACK SHALL REPLACE EXISTING TRACK IN THE SAME LOCATIONS,

USING EXISTING ALL-THREAD RODS AND FLEX CONNECTIONS WHEREVER

POSSIBLE.

K. OCCUPANCY SENSORS AND ASSOCIATED POWER PACKS/RELAYS SHALL BE

WIRED. THESE WILL COMMUNICATE WIRELESSLY WITH THE RECEIVER ON

EACH TRACK.

L. OCCUPANCY SENSORS SHOWN ON PLANS DO NOT INDICATE EXACT

LOCATIONS. SENSORS SHALL BE INSTALLED IN LOCATIONS TO BEST COVER

THE AREA AND AVOID CONFLICTS WITH OBSTRUCTIONS, AIR VENTS, ETC. IN

ACCORDANCE WITH MANUFACTURER’S GUIDELINES.

M. WHEN MULTIPLE OCCUPANCY SENSORS ARE LOCATED IN A SINGLE SPACE,

CONNECT DEVICES TOGETHER SUCH THAT THE ACTIVATION OF ANY ONE

SENSOR TURNS ON OR KEEPS ON ALL LIGHTS IN THAT AREA.

N. OCCUPANCY SENSORS INSTALLED IN REST ROOM AREAS SHALL BE SET

FOR A 30-MINUTE TIME OUT DELAY. OCCUPANCY SENSORS INSTALLED IN

THE DISPLAY AREAS SHALL BE SET FOR A 20-DELAY. OCCUPANCY SENSORS

INSTALLED IN OFFICES, CONFERENCE ROOMS, CORRIDORS AND COMMON

AREAS SHALL BE SET FOR A 15-MINUTE DELAY.

O. SUBSCRIPT AT EACH LIGHT FIXTURE INDICATES THE RELAY GROUP OR

ZONE IN THE LOCAL CONTROL PACK WITH WHICH THE FIXTURE IS

ASSOCIATED. THE MATCHING SUBSCRIPT AT EACH OCCUPANCY SENSOR

INDICATES THE SENSORS THAT CONTROL THOSE FIXTURES. WHERE NO

SUBSCRIPTS ARE INCLUDED, THE FIXTURES ARE ALL CONTROLLED

TOGETHER IN THAT AREA.

P. LIGHTING CONTROL METHODS VARY IN DIFFERENT SPACES THROUGHOUT

THE PROJECT. SEE PLAN VIEWS AND DETAILS FOR FURTHER

CLARIFICATION.

DATE:

SHEET:

428 N. Last Chance Gulch Helena, Montana 59601

406.449.2013 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

CITY STAMP

-D ec -2

9:

:2

29 November 2021

E201

LEVEL 1 - LIGHTING PLAN

4201 Giant Springs Road Great Falls, MT 59405

Lewis and Clark Interpretive Center

Lighting Upgrade

C o n s t r u c t io n D o c u m e n t s

1/8" = 1'-0"1

LEVEL 1 - LIGHTING PLAN

KEY NOTES:#

1. LIGHTING IN THIS PORTION OF THE BUILDING IS OUTSIDE THE SCOPE OF THIS

PROJECT.

2. LIGHT FIXTURES IN CEILING OF THEATER WERE RECENTLY UPGRADED AND

WILL REMAIN AS THEY ARE. EXISTING CONTROL 4 PANEL WILL CONTINUE TO

CONTROL THESE FIXTURES.

BID ALTERNATE 1:

3. REPLACE EXISTING TRACK LIGHTING. SEE SHEET E102 FOR CIRCUITING.

4. PROVIDE PHOTO SENSORS AND MOUNT ON CEILING WHERE THEY CAN BE

ACCESSED FROM A LADDER ON LEVEL 1. SENSORS WILL CONTROL ZONES 'd' AND 'p' TRACK LIGHTS.

5. REPLACE EXISTING LIGHTING CONTROL TOUCHSCREEN WITH NEW ONE

INTEGRATED INTO NEW LIGHTING CONTROL SYSTEM.

BID ALTERNATE 3:

6. REPLACE/RETROFIT EXISTING FIXTURES. RE-USE EXISTING CIRCUITS AND

INSTALL OCCUPANCY SENSOR CONTROLS AS SHOWN.

7. PROVIDE (2) RECESSED LIGHT FIXTURES OVER THE STAIRS. TIE INTO

CIRCUITTHAT FEEDS THE FIXTURES IN THE OPEN AREA.

BID ALTERNATE NOTES:

BID ALTERNATE 1:

A. REPLACE EXISTING THEATRICAL DIMMING EQUIPMENT THAT CONTROLS

POWER TO TRACK LIGHTING THROUGHOUT THE EXHIBIT AREAS IN

BASEMENT, MEZZANINE AND LEVEL 1.

B. REPLACE TRACK LIGHTING IN BASEMENT, MEZZANINE AND LEVEL 1 WITH

NEW TRACK LIGHTING THAT INCLUDES PROVISION FOR 0-10V CONTROL OF

THE TRACK HEADS.

C. PROVIDE OCCUPANCY SENSORS AND RELAY POWER PACKS TO ALLOW FOR

CONTROL OF TRACK LIGHTING BASED ON OCCUPANCY.

D. COORDINATE INSTALLATION, AIMING AND DIMMER SETTINGS FOR TRACK

HEADS ON ALL NEW TRACK.

E. MAINTAIN EXISTING CONTROL 4, A/V CONTROLS IN THE THEATER.

BID ALTERNATE 2:

A. REPLACE THE EXISTING STAIR TREAD LIGHTING IN THE THEATER WITH NEW

LED TAPE LIGHTING AND ENSURE THAT IT FUNCTIONS IN THE SAME MANNER

AS THE EXISTING STAIR TREAD LIGHTING.

BID ALTERNATE 3:

A. REPLACE/RETROFIT LIGHTING IN EXISITNG OFFICES, CONFERENCE ROOMS

AND BACK OF HOUSE AREAS WITH LED FIXTURES. THIS INCLUDES THE HIGH-

BAY LIGHT FIXTURES IN THE BASEMENT EXHIBIT AREA THAT SUPLIMENT THE

TRACK LIGHTING IN THAT AREA.

B. PROVIDE OCCUPANCY SENSOR CONTROLS OF REPLACED/RETROFIT

LUMINAIRES IN EXISITNG OFFICES, CONFERENCE ROOMS AND BACK OF

HOUSE AREASAS SHOWN ON PLANS.

# DATE REVISION

I S S

E F

O R

P

LAN

O EN

G

IN

E E R

ON

T

M

AN

A

LICENSE

D

GARTH L.

2 3 4

B

C

D

E

F

G

H

F1

C1C1C1

C1B1 B1E

F1 F1E

F1

F1

F1E F1

F1

74 6

ELEVATOR

D12 o o o

C1

C1

TYP

o

NEW TLC PANEL

GENERAL ELECTRICAL NOTES

A. IT IS ABSOLUTELY NECESSARY FOR ELECTRICAL CONTRACTOR TO VERIFY

THAT THERE ARE NO CONFLICTS IN LOCATION OF DUCTS, CONDUITS,

DIFFUSERS, BOXES, AND OTHER ITEMS THROUGHOUT THIS PROJECT

BEFORE FINAL PLACEMENT OF MATERIALS.

B. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS,

WALLS AND CEILINGS TO PERFORM THE REQUIRED WORK DEPICTED IN

THESE DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR ALL

PATCHING OF HOLES TO THE SATISFACTION OF THE ARCHITECT/ENGINEER.

C. DURING DEMOLITION, THE CONTRACTOR SHALL NOTE ALL EXISTING

RACEWAY (BOTH SURFACE AND CONCEALED) TO THE EXTENT POSSIBLE.

THESE RACEWAYS SHALL BE REUSED TO THE GREATEST EXTENT POSSIBLE

TO INSURE A CLEAN FINISHED PRODUCT. WHERE PRACTICAL, AND

ALLOWED PER CODE, FISHING THROUGH WALLS WITH MC CABLE IS

PREFERRED TO SURFACE-MOUNTED CONDUIT.

D. CONTRACTOR SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OF

LAMPS AND BALLASTS OFF-SITE. IT IS ASSUMED THAT THE BALLASTS DO

NOT CONTAIN PCBS. THE CONTRACTOR SHALL NOTIFY THE OWNER

IMMEDIATELY IF IT IS SUSPECTED THAT BALLASTS CONTAIN PCBS.

E. ALL POWER INTERRUPTIONS SHALL BE COORDINATED WITH OWNER. ANY

DISRUPTION OF WORKERS IN THE SPACE SHALL BE KEPT TO A MINIMUM

AND BE COORDINATED WITH THE OWNER PRIOR TO WORK COMMENCING IN

THAT SPACE.

F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY

EXISTING CONDUIT OR FEEDER CIRCUITS THAT ARE INTENDED TO REMAIN

THAT ARE SAW-CUT, OR OTHERWISE DAMAGED, AS PART OF THE

DEMOLITION PROCESS. PROVISION FOR THIS WORK SHALL INCLUDE, BUT

NOT BE LIMITED TO: ALL NECESSARY CONDUIT AND CONDUCTORS,

MOUNTING ACCESSORIES AND LABOR, TO RESTORE THE SYSTEM TO ITS

INTENDED FUNCTION.

G. ELECTRICAL DRAWINGS SHOWING EXISTING BUILDING CONDITIONS, SUCH

AS DEMOLITION DRAWINGS, EXISTING PANEL SCHEDULES, ETC ARE BASED

ON RECORD DRAWINGS AND SITE VISITS. IF ACTUAL EXISTING CONDITIONS

DIFFER FROM THOSE SHOWN ON DRAWINGS, PLEASE NOTIFY ENGINEER.

H. LOW VOLTAGE CABLES (LIGHTING CONTROLS) ABOVE ACCESSIBLE

CEILINGS, AND WHERE EXPOSED IN OPEN CEILING AREAS SHALL BE

SUPPORTED USING J-HOOKS AT INTERVALS NOT TO EXCEED 48" OC, UNO.

LOW VOLTAGE CABLES SHALL BE BLACK AND J-HOOKS SHALL BE PAINTED

BLACK WHERE INSTALLED IN OPEN CEILING AREAS.

I. UNLESS NOTED OTHERWISE, NEW LIGHT FIXTURES SHALL REPLACE OLD

FIXTURES IN THE SAME LOCATION AND WITH THE SAME CIRCUIT AND

CONTROLS.

J. NEW TRACK SHALL REPLACE EXISTING TRACK IN THE SAME LOCATIONS,

USING EXISTING ALL-THREAD RODS AND FLEX CONNECTIONS WHEREVER

POSSIBLE.

K. OCCUPANCY SENSORS AND ASSOCIATED POWER PACKS/RELAYS SHALL BE

WIRED. THESE WILL COMMUNICATE WIRELESSLY WITH THE RECEIVER ON

EACH TRACK.

L. OCCUPANCY SENSORS SHOWN ON PLANS DO NOT INDICATE EXACT

LOCATIONS. SENSORS SHALL BE INSTALLED IN LOCATIONS…