This document provides details for a federal solicitation related to construction services. Solicitation number 36C77622R0019 from the Department of Veterans Affairs Technology Acquisition Center Austin is seeking offers for the EHRM Training and Admin Space Support Construction DBB Support Construction project at the Minneapolis Veterans Affairs Medical Center. The solicitation involves design-bid-build support for construction of training and administrative spaces to support the medical center's electronic health record modernization efforts. Offerors should respond with pricing and plans to complete the construction project by the anticipated award date. Key agencies involved include the Department of Veterans Affairs Technology Acquisition Center and Minneapolis Veterans Affairs Medical Center.
View the file
Other files for this federal contract opportunity
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
XYZAABBCCDD
72"x36"
"ø
"ø
46"ø
46"ø
EXISTING AHU '70-HVP-7'
ATRIUM SMOKE CONTROL
ONLY
120"x36"
52"ø
84"x54"
22"x36" 22"x36" 22"x36"
CHWR
CHWS
CHWR
CHWS
2" MPC
6" 6" 5" 5"
CHWS
CHWR
CHWS
CHWR
MPS
6"
EXISTING EXHAUST PLENUM TO
REMAIN. PROTECT DURING
CONSTRUCTION.
EXISTING OUTSIDE AIR PLENUM TO
REMAIN. PROTECT DURING
CONSTRUCTION.
EXISTING EXHAUST PLENUM
TO REMAIN. PROTECT
DURING CONSTRUCTION.
M
M
1. REMOVE EXISTING AIR HANDLING UNIT 70-AHPW-46 AND ALL ASSOCIATED DUCTWORK, PIPING, VALVING, CONTROLS, HANGERS, SUPPORTS, INSULATION, BASES, ETC. SHOWN DASHED.
2. REMOVE EXISTING RETURN FAN RF-38 AND ALL ASSOCIATED DUCTWORK, INSULATION, CONTROLS, BASES, ETC. SHOWN
DASHED.
3. REMOVE EXISTING DUCTWORK, HANGERS, INSULATION, ETC. SHOWN DASHED TO ACCOMMODATE 70-AHP-46 REPLACEMENT
AND NEW DUCT LAYOUT.
4. EXISTING 60x36 RETURN GRILLE TO BE RELOCATED. GRILLE SHALL BE RETAINED AND STORED FOR REUSE. EXTEND DUCTWORK AS REQUIRED TO FACILITATE SCOPE OF WORK. REFER TO SHEET MH105 FOR NEW LOCATION.
5. REMOVE EXISTING DUCTWORK TO PLENUM OPENING INCLUDING MOTORIZED DAMPER AND ALL ASSOCIATED COMPONENTS.
6. REMOVE ALL CHILLED WATER PIPING (FIELD LABELED WW AND WWR), VALVING, HANGERS, INSULATION, ETC. SHOWN DASHED
BACK TO MAINS.
7. REMOVE ALL MEDIUM PRESSURE STEAM AND CONDENSATE PIPING, VALVING, STEAM TRAPS, CONDENSATE METERS
HANGERS, INSULATION, ETC. SHOWN DASHED BACK TO MAINS.
8. REMOVE EXISTING GRILLE AND DUCTWORK AS SHOWN. PATCH AND SEAL WALL TO MATCH EXISTING CONDITIONS.
X MECHANICAL DEMOLITION KEY NOTES
A. ALL ABANDONED OPENINGS TO BE CLOSED, REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS.
B. REMOVE ALL CLAMPS, HANGERS, SUPPORTS, ETC. ASSOCIATED WITH PIPING REMOVAL.
C. COORDINATE ALL MECHANICAL SERVICE OUTAGES WITH COR.
D. PIPING MAY BE SHOWN OFFSET FROM IT'S ACTUAL LOCATION FOR CLARITY. FIELD VERIFY EXACT LOCATIONS.
E. REMOVE ALL PIPING, VALVING, INSULATION, HANGERS, THERMOSTATS, REHEAT COILS, VAV BOXES, ETC. SHOWN DASHED.
GENERAL MECHANICAL DEMOLITION NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No.
BUILDING 70 KEYPLAN
VA CONTRACT NO.
AREA K
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ 70-129AREAG70-131AREAH
AREA L
AREA B
AREA F
AREA J AREA G
AREA H
AREA E
AREA D
AREA C
AREA AAREA M
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ70-129AREAG70-131AREAH
N
C U s e rs \i ly tl e
\D o c u m e n ts \6
M e c h a n ic a l_ ily tl e
E G
V K
N .r v t
/1
/2
:2
:5
P
M
09/07/2021
MECHANICAL - PENTHOUSE - DEMOLITION
PLAN
EHRM Training and Admin Space Support
Minneapolis VA Healthcare System
DG IL
618-701
1384-MHD105
ISSUE FOR BID
18-11636C26319D0022
N
1/8" = 1'-0"
MECHANICAL - PENTHOUSE - DEMOLITION PLAN
Revisions: Date:
65% DESIGN DEVELOPMENT SUBMITTAL 07/15/2021
95% CONSTRUCTION DOCUMENTS SUBMISSION 08/19/2021
ISSUE FOR BID 09/07/2021
CCDDEEFFGGHH
1. REMOVE EXISTING STEAM-TO-WATER HEAT EXCHANGER (70-C-005) AND ASSOCIATED STEAM, CONDENSATE, AND HOT WATER PIPING CONNECTIONS. EXISTING MOUNTING RACK TO REMAIN. EXISTING VALVES, STRAINERS, TRAPS, AND CONTROL VALVES
TO REAMIN AS IS. WHERE APPLICABLE, REWORK PIPING AS REQUIRED.
2. EXISTING AIR SEPARATOR TO REMAIN.
3. EXISTING EXPANSION TANK TO REMAIN.
X MECHANICAL DEMOLITION KEY NOTES
EXISTING
'70-P-23'
140 GPM
CW
MPC
2"
4" HWS
4" MPS
H W
S H
W R
4" 4"
1"
4" HWS
MPC
MPC
2"1"
EXISTING AHU EXISTING AHU
A. ALL ABANDONED OPENINGS TO BE CLOSED, REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS.
B. REMOVE ALL CLAMPS, HANGERS, SUPPORTS, ETC. ASSOCIATED WITH PIPING REMOVAL.
C. COORDINATE ALL MECHANICAL SERVICE OUTAGES WITH COR.
D. PIPING MAY BE SHOWN OFFSET FROM IT'S ACTUAL LOCATION FOR CLARITY. FIELD VERIFY EXACT LOCATIONS.
E. REMOVE ALL EXISTING PNEUMATIC TUBING INCLUDING CONDUITS AND WIRING SERVING EXISTING EQUIPMENT BEING
DEMOLISHED. CAP AND SEAL ALL PNEUMATIC TUBING.
GENERAL MECHANICAL DEMOLITION NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No.
BUILDING 70 KEYPLAN
VA CONTRACT NO.
AREA K
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ 70-129AREAG70-131AREAH
AREA L
AREA B
AREA F
AREA J AREA G
AREA H
AREA E
AREA D
AREA C
AREA AAREA M
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ70-129AREAG70-131AREAH
N
C U s e rs \i ly tl e
\D o c u m e n ts \6
M e c h a n ic a l_ ily tl e
E G
V K
N .r v t
/1
/2
:2
:0
P
M
09/07/2021
MECHANICAL - SECOND FLOOR
INTERSTITIAL DEMOLITION PLAN -
MECHANICAL ROOM 2J-132
EHRM Training and Admin Space Support
Minneapolis VA Healthcare System
DG IL
618-701
1384-MPD102-I
ISSUE FOR BID
18-11636C26319D0022
N
1/8" = 1'-0"
MECHANICAL - SECOND FLOOR INTERSTIAL PIPING PLAN - MECHANICAL ROOM 2J-132
Revisions: Date:
GENERAL MECHANICAL NOTES
A. CONTRACTOR SHALL REPAIR AND/OR REPLACE ALL INSULATION AT EXISTING SHEET METAL DUCTWORK WHICH BECOMES DAMAGED DURING CONSTRUCTION ACTIVITIES AND SHALL REPAIR OR REPLACE ANY INSULATION AT NEW AND OLD DUCT CONNECTIONS AND ANY MISSING OR DAMAGED INSULATION ON REUSED OR EXISTING DUCTWORK.
B. PROVIDE BALANCING DAMPER AT ALL SUPPLY DIFFUSERS, RETURN AND EXHAUST GRILLES, WHETHER OR NOT SHOWN
ON DRAWINGS.
C. COORDINATE CEILING MOUNTED GRILLES AND DIFFUSERS WITH SPRINKLER HEADS, LIGHTING FIXTURES AND ALL CEILING
MOUNTED DEVICES. REFER TO ARCHITECTURAL CEILING GRID DRAWINGS FOR LOCATIONS.
D. CEILING ACCESS SHALL BE PROVIDED FOR ALL HVAC EQUIPMENT AND COMPONENTS LOCATED ABOVE THE CEILING THAT
REQUIRE OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION.
E. ALL VAV TERMINAL UNITS SHALL BE TAGGED USING A PERMANENT MARKING SYSTEM SUCH AS STENCIL OR ENGRAVED RIGID BLACK PLASTIC NAMEPLATES WITH WHITE LETTERS NOT LESS THAN 3/16" INCH HIGH. THE LABELS SHALL BE PERMANENTLY AFFIXED TO THE UNITS AND SHALL BE VISIBLE FROM MULTI DIRECTIONS ON BOTH SIDES OF THE TERMINAL UNIT. PEEL AND STICK DEVICES SHALL NOT BE PERMITTED. VAV BOX TO BE LABELED PER THE DRAWINGS.
1. PROVIDE AIR FLOW MEASURING STATION IN VERTICAL.
2. INSTALL DUCTWORK AT ELEVATION SO AS NOT TO IMPEDE ON VAV BOX SERVICE CLEARANCE REQUIREMENTS.
X MECHANICAL KEY NOTES
XYZAABBCCDD
TRAINING 1
2P-146
WAITING /
CHECK-IN
2P-130
CORRIDOR
C2P-115
TRAINING 2
2P-145
TRAINING 3
2P-144
TRAINING 4
2P-143
ROOF ACCESS
2P-142 WOMEN'S TOILET
ROOM
2P-141
BREAK ROOM
2P-138
MEN'S TOILET
ROOM
2P-137
HAC
2P-136
CONFERENCE
ROOM
2P-135
TRAINING 8
2P-134
TRAINING 7
2P-133
TRAINING 6
2P-139
TRAINING 5
2P-140
TRAINING 13
2P-147
TRAINING 12
2P-148
TRAINING 11
2P-149
STORAGE
2P-147A
STORAGE
2P-149A
TRAINING 9
2P-132
TRAINING 10
2P-131
CORRIDOR
C2P-118
CORRIDOR
C2P-117
CORRIDOR
C2P-116
"x
"x
14"x12"
12"x12"
14"x12"
42"x20"
12"x12"
12"x12"
38"x20"
"x
18"x16"
"x
"x
"x
16"x16"
12"x12"
"x
24"x20"
12"x12" 12"x12"
14"x12"
"x
"x
38"x20"36"x20"
"x
"x
24"ø
"x
14"ø
14"ø
12"x12"
12"x12"
14"x12"
1000 CFM
70-VAV-46-130
825 CFM
70-VAV-46-143
650 CFM
70-VAV-46-144
825 CFM
70-VAV-46-145
650 CFM
70-VAV-46-146
650 CFM
70-VAV-46-147
650 CFM
70-VAV-46-148
650 CFM
70-VAV-46-149
650 CFM
70-VAV-46-140
650 CFM
70-VAV-46-139
825 CFM
70-VAV-46-133
650 CFM
70-VAV-46-134
650 CFM
70-VAV-46-132
825 CFM
70-VAV-46-131
325 CFM
70-VAV-46-138
400 CFM
70-VAV-46-135
2000 CFM
70-VAV-46-150-3
2400 CFM
70-VAV-46-150-1 1995 CFM
70-VAV-46-150-2
10"ø NK
SA
325 CFM
EB
280 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM
10"ø NK
SA
325 CFM8"ø NK
SA
350 CFM
8"ø NK
SA
350 CFM
10"ø NK
SA
325 CFM
8"ø NK
SA
325 CFM
8"ø NK
SA
200 CFM
8"ø NK
SA
200 CFM
RB
400 CFM
RB
650 CFM
RB
650 CFM
RB
650 CFM
RB
650 CFM
RB
650 CFM
RB
650 CFM
RB
650 CFM
RB
650 CFM
RB
650 CFM
RB
650 CFM
RB
650 CFM
RB
650 CFM
10"ø NK
SA
250 CFM
RB
290 CFM
10"ø NK
SA
175 CFM
RB
700 CFM
RB
350 CFM
SD
SD
SD
SD
SD
SD
14"⌀ NK
SURGICAL
WAITING ROOM
2P-150
CONSULTATION
ROOM
2P-150C
CONSULTATION
ROOM
2P-150B
EB
280 CFM
EB
280 CFM
18"x14" EA
UP
48"x36" RA UP46"x36" SA
UP
SD
30"x24"
10"ø NK
SA
175 CFM
8"ø NK
SA
175 CFM
6"ø NK
SA
120 CFM
6"ø NK
SA
120 CFM
120 CFM
70-VAV-46-150C
120 CFM
70-VAV-46-150B
10"x10"
500 CFM
14"⌀ NK
500 CFM
14"⌀ NK
1000 CFM
14"⌀ NK
665 CFM
14"⌀ NK
800 CFM
14"⌀ NK
800 CFM
14"⌀ NK
800 CFM
14"ø
18"x14" 6"ø
RB
500 CFM
10"ø NK
SA
250 CFM
12"ø
"x
24"x20"
SD SD
14"ø
10"ø NK
SA
350 CFM
14"ø 14"ø
1200 CFM
70-VAV-46-137
EB
280 CFM
12"ø
14"ø
12"ø
14"ø
14"ø
10"ø NK
SA
325 CFM
14"Ø
10"ø
RB
650 CFM
14"ø
14"ø
"x
24"x20"
14"⌀ NK
665 CFM
14"⌀ NK
665 CFM
10"ø
10"Ø 10"Ø
10"ø
"x
14"ø
12"ø
8"ø 6"ø
6"ø
RB
120 CFM
RB
120 CFM
12"ø
10"ø
14"Ø 14"ø
12"Ø
8"x6" NK
EC
100 CFM
8"ø NK
SA
175 CFM
12"x12"
12"x12"
18"x14"
70-EF-C2P-115
1565 CFM
18"x14"
EB
400 CFM
10"ø
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No.
BUILDING 70 KEYPLAN
VA CONTRACT NO.
AREA K
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ 70-129AREAG70-131AREAH
AREA L
AREA B
AREA F
AREA J AREA G
AREA H
AREA E
AREA D
AREA C
AREA AAREA M
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ70-129AREAG70-131AREAH
N
C U s e rs \i ly tl e
\D o c u m e n ts \6
M e c h a n ic a l_ ily tl e
E G
V K
N .r v t
/1
/2
:2
:4
P
M
09/07/2021
MECHANICAL - SECOND FLOOR PLAN EHRM Training and Admin Space Support
Minneapolis VA Healthcare System
DG IL
618-701
1384-MH102
ISSUE FOR BID
18-11636C26319D0022
N
1/8" = 1'-0"
MECHANICAL - SECOND FLOOR PLAN
Revisions: Date:
65% DESIGN DEVELOPMENT SUBMITTAL 07/15/2021
80"x36"
"x
(E )4
6" ø
48"ø
(E)84"x54"
(E)22"x36"(E)22"x36"
(E)120"x36"
30"x28"
30"x28"
SD
16"⌀
EXISTING AHU '70-HVP-7'
ATRIUM SMOKE CONTROL ONLY
(E)52"ø
2500 CFM
70-VAV-46-150-4
2500 CFM
70-VAV-46-150-5
2500 CFM
70-VAV-46-150-6
70-AHPW-46
46"ø
44"ø
46"ø
2500 CFM
46"ø
46x38 DN
SD
16"⌀
2500 CFM
"x
18x14 DN8 8 8 8
(E)22"x36"
30"ø
26"x14"
26"x14"
"x
26"x14"26"x14"
26"x14"
(E)30"ø
1. INSTALL NEW MOTORIZED DAMPER ON EXISTING 30"Ø RETURN DUCT PRIOR TO NEW CONNECTION TO NEW 46"Ø MAIN RETURN
DUCT.
2. 76x28x54 PLENUM BOX.
3. EXISTING RETURN 60x36 RETURN GRILLE TO BE RELOCATED TO THIS LOCATION.
4. CONNECT NEW 18x14 EXHAUST DUCT TO EXISTING LOUVER.
5. CONNECT 30"Ø TO EXISTING 30"Ø RETURN AIR DUCT UPSTREAM OF NEW MOTORIZED DAMPER PER KEY NOTE 1.
6. 48"Ø DOWN AND TRANSITION TO EXISTING 48x30 SUPPLY DUCT.
7. NEW AIR FLOW MEASURING STATION IN 44"Ø RELIEF AIR DUCT.
8. EXISTING 60x36 RETURN GRILLE (2800 CFM).
X MECHANICAL KEY NOTES
XYZAABBCCDD
SD
16"Ø
2500 CFM
"x
GENERAL MECHANICAL NOTES
A. CLEAN, SANITIZE AND SEAL ALL EXISTING DUCTWORK THAT WILL BE REUSED.
B. CONTRACTOR SHALL REPAIR AND/OR REPLACE ALL INSULATION AT EXISTING SHEET METAL DUCTWORK WHICH BECOMES DAMAGED DURING CONSTRUCTION ACTIVITIES AND SHALL REPAIR OR REPLACE ANY INSULATION AT NEW AND OLD DUCT CONNECTIONS AND ANY MISSING OR DAMAGED INSULATION ON REUSED OR EXISTING DUCTWORK.
C. PROVIDE BALANCING DAMPER AT ALL SUPPLY DIFFUSERS, RETURN AND EXHAUST GRILLES, WHETHER OR NOT SHOWN
ON DRAWINGS.
D. DURING CONSTRUCTION, PROVIDE TEMPORARY CLOSURES ON ALL SUPPLY AND RETURN AIR DUCT OPENINGS BY SEALING WITH A DISPOSABLE POLYETHYLENE SHEETING TO PREVENT CONSTRUCTION DUST FROM ENTERING
DUCTWORK SYSTEM OR AIR TERMINAL UNITS.
E. ALL VAV TERMINAL UNITS SHALL BE TAGGED USING A PERMANENT MARKING SYSTEM SUCH AS STENCIL OR ENGRAVED RIGID BLACK PLASTIC NAMEPLATES WITH WHITE LETTERS NOT LESS THAN 3/16" INCH HIGH. THE LABELS SHALL BE PERMANENTLY AFFIXED TO THE UNITS AND SHALL BE VISIBLE FROM MULTI DIRECTIONS ON BOTH SIDES OF THE
TERMINAL UNIT. PEEL AND STICK DEVICES SHALL NOT BE PERMITTED.
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No.
BUILDING 70 KEYPLAN
VA CONTRACT NO.
AREA K
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ 70-129AREAG70-131AREAH
AREA L
AREA B
AREA F
AREA J AREA G
AREA H
AREA E
AREA D
AREA C
AREA AAREA M
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ70-129AREAG70-131AREAH
N
C U s e rs \i ly tl e
\D o c u m e n ts \6
M e c h a n ic a l_ ily tl e
E G
V K
N .r v t
/1
/2
:2
:4
P
M
09/07/2021
MECHANICAL - PENTHOUSE FLOOR PLAN EHRM Training and Admin Space Support
Minneapolis VA Healthcare System
DG IL
618-701
1384-MH105
ISSUE FOR BID
18-11636C26319D0022
N
1/8" = 1'-0"
MECHANICAL - PENTHOUSE FLOOR PLAN
Revisions: Date:
65% DESIGN DEVELOPMENT SUBMITTAL 07/15/2021
TRAINING 1
2P-146
WAITING /
CHECK-IN
2P-130
CORRIDOR
C2P-115
TRAINING 2
2P-145
TRAINING 3
2P-144
TRAINING 4
2P-143
ROOF ACCESS
2P-142
WOMEN'S TOILET
ROOM
2P-141
BREAK ROOM
2P-138
MEN'S TOILET
ROOM
2P-137
HAC
2P-136
CONFERENCE
ROOM
2P-135
TRAINING 8
2P-134
TRAINING 7
2P-133
TRAINING 6
2P-139
TRAINING 5
2P-140
TRAINING 13
2P-147
TRAINING 12
2P-148
TRAINING 11
2P-149
STORAGE
2P-147A
STORAGE
2P-149A
TRAINING 9
2P-132
TRAINING 10
2P-131
CORRIDOR
C2P-118
CORRIDOR
C2P-117
CORRIDOR
C2P-116
SURGICAL
WAITING ROOM
2P-150
T
T
T
T
T
T T
T
T
T
T
T
70-VAV-46-130
1.3 GPM
70-VAV-46-143
1.2 GPM
70-VAV-46-144
1.1 GPM
70-VAV-46-145
1.2 GPM
70-VAV-46-146
1.1 GPM
70-VAV-46-147
1.1 GPM
70-VAV-46-148
1.1 GPM
70-VAV-46-149
1.1 GPM
70-VAV-46-140
1.1 GPM
70-VAV-46-139
1.1 GPM
70-VAV-46-133
1.2 GPM
70-VAV-46-134
1.1 GPM
70-VAV-46-132
1.1 GPM
70-VAV-46-131
1.2 GPM
70-VAV-46-138
0.7 GPM
70-VAV-46-135
0.8 GPM
70-VAV-46-150-3
3.1 GPM70-VAV-46-150-1
3.1 GPM
70-VAV-46-150-2
3.1 GPM
T
T
SURGICAL
WAITING ROOM
2P-150
CONSULTATION
ROOM
2P-150C
CONSULTATION
ROOM
2P-150B
T T T
70-VAV-46-150C
0.5 GPM
70-VAV-46-150B
0.5 GPM
70-VAV-46-137
1.3 GPM
TT
T T
T
HWR
HWS
H W
R H W
S
HWR
HWS
2"
HWR
HWS
3/4" 3/4"
H W
S H
W R
H W
S H
W R
HWS
HWR
T
2"
2"
2" 2"
2"
2"
2" 2"
2"
1 1/4"
1 1/4"
1 1/4" 1 1/4"
HWR
HWS
1" 1" 3/4"
3/4"
H W
R H
W S
1 1/4" 1 1/4"
3/4" 3/4"
HWS
HWR
1" 1"
H W
S H
W R
70-VAV-46-150-1 70-VAV-46-150-2 70-VAV-46-150-3
70-VAV-46-140
2.0 GPM
11.4 GPM
29.1 GPM
19.8 GPM
3"
3"
1. INSTALL PIPING AT ELEVATION SO AS NOT TO IMPEDE ON VAV BOX SERVICE CLEARANCE REQUIREMENTS.
2. BALANCE CIRCUIT SETTER TO FLOW RATE INDICATED.
3. 2" HOT WATER SUPPLY AND RETURN PIPING UP TO PENTHOUSE. REFER TO SHEET 1384-MP105 FOR CONTINUATION.
4. REFER TO SHEET 1384-MP102-I FOR CONTINUATION.
X MECHANICAL KEY NOTES
GENERAL MECHANICAL NOTES
A. ALL CONNECTIONS BETWEEN DISSIMILAR METALS SHALL BE MADE WITH DIELECTRIC UNIONS OR COUPLINGS.
B. FIRESTOP ALL PIPE PENETRATIONS OF FIRE RATED WALLS. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS.
C. ROUTE HYDRONIC PIPING AS HIGH AS POSSIBLE ABOVE DUCTWORK.
D. CEILING ACCESS SHALL BE PROVIDED SUCH THAT EQUIPMENT SHALL BE READILY SERVICEABLE, FOR ALL HVAC EQUIPMENT AND COMPONENTS LOCATED ABOVE THE CEILING THAT REQUIRE OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION. SUCH EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, VAV BOXES, AIR VALVES, CONTROL VALVES, STRAINERS, BALANCING DAMPERS, ETC.
E. ALL BRANCH PIPING CONNECTING TO VAV BOXES SHALL BE 3/4" UNLESS NOTED OTHERWISE.
F. ALL STRAINERS SHALL BE PROVIDED WITH HOSE-BIB CONNECTIONS.
G. MANUAL AIR VENTS ARE NOT ACCEPTABLE. ALL AIR VENTS SHALL BE AUTOMATIC.
H. ALL VAV TERMINAL UNITS SHALL BE TAGGED USING A PERMANENT MARKING SYSTEM SUCH AS STENCIL OR ENGRAVED RIGID BLACK PLASTIC NAMEPLATES WITH WHITE LETTERS NOT LESS THAN 3/16 " INCH HIGH. THE LABELS SHALL BE PERMANENTLY AFFIXED TO THE UNITS AND SHALL BE VISIBLE FROM MULTI DIRECTIONS ON BOTH SIDES OF THE
TERMINAL UNIT. PEEL AND STICK DEVICES SHALL NOT BE PERMITTED.
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No.
BUILDING 70 KEYPLAN
VA CONTRACT NO.
AREA K
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ 70-129AREAG70-131AREAH
AREA L
AREA B
AREA F
AREA J AREA G
AREA H
AREA E
AREA D
AREA C
AREA AAREA M
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ70-129AREAG70-131AREAH
N
C U s e rs \i ly tl e
\D o c u m e n ts \6
M e c h a n ic a l_ ily tl e
E G
V K
N .r v t
/1
/2
:2
:5
P
M
09/07/2021
MECHANICAL - SECOND FLOOR PIPING PLAN EHRM Training and Admin Space Support
Minneapolis VA Healthcare System
DG IL
618-701
1384-MP102
ISSUE FOR BID
18-11636C26319D0022
N
1/8" = 1'-0"
MECHANICAL - SECOND FLOOR PIPING PLAN
CCDDEEFFGGHH
HWR
HWS
H W
R H
W S
3" 3"
FFGG
2"
4" 4"
1"
2" 1"
4"
4"
3"
3"
MPC
H W
S
H W
R
MPC
MPC
C W
HWS
HWR
4" HWS
MPS
4"
4" HWS
EXISTING
'70-P-23'
140 GPM
70-C-005
70-P-23A
190 GPM
STANDBY
48.9 GPM
141.1 GPM
H W
R H
W
S EXISTING AHUEXISTING AHU
3" 3"
REFER TO ENLARGED
PLAN ON THIS SHEET
FOR DETAILED WORK IN
THIS AREA
1. BALANCE CIRCUIT SETTER TO FLOW RATE INDICATED.
2. REFER TO SHEET 1384-MP102 FOR CONTINUATION.
3. EXISTING HWS/R TO EXISTING VAV BOX REHEAT COILS.
4. EXISTING AIR SEPARATOR TO REMAIN.
5. EXISTING EXPANSION TANK TO REMAIN.
6. PROVIDE ISOLATION VALVES AND PIPING AS REQUIRED FOR MANUAL CHANGEOVER.
7. CONTRACTOR TO REPLACE EXISTING HEAT EXCHANGER AS SHOWN ON SCHEDULE. EXISTING VALVES, STRAINERS, TRAPS, AND CONTROLS TO REMAIN AS IS. WHERE APPLICABLE, REWORK PIPING AS REQUIRED.
X MECHANICAL KEY NOTES
GENERAL MECHANICAL NOTES
A. ALL CONNECTIONS BETWEEN DISSIMILAR METALS SHALL BE MADE WITH DIELECTRIC UNIONS OR COUPLINGS.
B. FIRESTOP ALL PIPE PENETRATIONS OF FIRE RATED WALLS. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS.
C. ROUTE HYDRONIC PIPING AS HIGH AS POSSIBLE ABOVE DUCTWORK.
D. ALL STRAINERS SHALL BE PROVIDED WITH HOSE-BIB CONNECTIONS.
E. MANUAL AIR VENTS ARE NOT ACCEPTABLE. ALL AIR VENTS SHALL BE AUTOMATIC.
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No.
BUILDING 70 KEYPLAN
VA CONTRACT NO.
AREA K
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ 70-129AREAG70-131AREAH
AREA L
AREA B
AREA F
AREA J AREA G
AREA H
AREA E
AREA D
AREA C
AREA AAREA M
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ70-129AREAG70-131AREAH
N
C U s e rs \i ly tl e
\D o c u m e n ts \6
M e c h a n ic a l_ ily tl e
E G
V K
N .r v t
/1
/2
:2
:5
P
M
09/07/2021
MECHANICAL - SECOND FLOOR PIPING PLAN
- MECH ROOM 2J-132
EHRM Training and Admin Space Support
Minneapolis VA Healthcare System
DG IL
618-701
1384-MP102-I
ISSUE FOR BID
18-11636C26319D0022
N
1/8" = 1'-0"
MECHANICAL - SECOND FLOOR INTERSTIAL PIPING PLAN - MECHANICAL ROOM 2J-132
N
1/4" = 1'-0"
MECHANICAL - SECOND FLOOR - ENLARGED PLAN - MECHANICAL ROOM 2J-132
1" 1"
70-VAV-46-150-5
6.6 GPM
70-VAV-46-150-6
6.6 GPM
70-VAV-46-150-4
6.6 GPM
COOLING COIL
HUMIDIFIER
FACE AND
BYPASS
STEAM COIL
4" CHWS
4" CHWR
3"
1 1/4"
(E) 2" MPC
(E) CHWR
(E) CHWS
(E) 6"
(E) 6"
(E) CHWS
(E) CHWR
(E) 5"
(E) 5" M
PS
3"
(E) 6"
70-AHPW-46
EXISTING AHU '70-HVP-7'
ATRIUM SMOKE CONTROL ONLY
(E) MPS
1" 1"
1" 1"
HWS
HWR
2" 2"
HWR
HWS
1. CONNECT NEW 1-1/2" MEDIUM PRESSURE STEAM CONDENSATE PIPING TO EXISTING 2" MEDIUM PRESSURE STEAM
CONDENSATE PIPING.
2. CONNECT NEW 1" MEDIUM PRESSURE STEAM CONDENSATE PIPING TO EXISTING 2" MEDIUM PRESSURE STEAM CONDENSATE
PIPING.
3. 1-1/2" COOLING COIL CONDENSATE PIPING DOWN TO OPEN SITE DRAIN. COORDINATE WITH PLUMBING DRAWINGS FOR EXACT
LOCATION.
4. 2" HOT WATER SUPPLY AND RETURN PIPING DOWN TO 2ND FLOOR.
5. INSTALL PIPING AT ELEVATION SO AS NOT TO IMPEDE ON VAV BOX SERVICE CLEARANCE REQUIREMENTS.
X MECHANICAL KEY NOTES
GENERAL MECHANICAL NOTES
A. ALL CONNECTIONS BETWEEN DISSIMILAR METALS SHALL BE MADE WITH DIELECTRIC UNIONS OR COUPLINGS.
B. FIRESTOP ALL PIPE PENETRATIONS OF FIRE RATED WALLS. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS.
C. ROUTE HYDRONIC PIPING AS HIGH AS POSSIBLE ABOVE DUCTWORK.
D. ALL BRANCH PIPING CONNECTING TO VAV BOXES SHALL BE 3/4" UNLESS NOTED OTHERWISE.
E. ALL STRAINERS SHALL BE PROVIDED WITH HOSE-BIB CONNECTIONS.
F. MANUAL AIR VENTS ARE NOT ACCEPTABLE. ALL AIR VENTS SHALL BE AUTOMATIC.
G. ALL VAV TERMINAL UNITS SHALL BE TAGGED USING A PERMANENT MARKING SYSTEM SUCH AS STENCIL OR ENGRAVED RIGID BLACK PLASTIC NAMEPLATES WITH WHITE LETTERS NOT LESS THAN 3/16" INCH HIGH. THE LABELS SHALL BE PERMANENTLY AFFIXED TO THE UNITS AND SHALL BE VISIBLE FROM MULTI DIRECTIONS ON BOTH SIDES OF THE
TERMINAL UNIT. PEEL AND STICK DEVICES SHALL NOT BE PERMITTED.
H. ALL TWO-WAY CONTROL VALVES FOR CHILLED WATER COOLING COILS SHALL BE AN ENERGY METERING PRESSURE INDEPENDENT CONTROL VALVE SIMILAR TO BELIMO ENERGY VALVE SERIES 'EV' (OR VA APPROVED EQUAL). VALVE SHALL
BE BACNET COMPATIBLE WITH ALL NECESSARAY POINTS CONNECTED TO THE BAS.
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No.
BUILDING 70 KEYPLAN
VA CONTRACT NO.
AREA K
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ 70-129AREAG70-131AREAH
AREA L
AREA B
AREA F
AREA J AREA G
AREA H
AREA E
AREA D
AREA C
AREA AAREA M
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ70-129AREAG70-131AREAH
N
C U s e rs \i ly tl e
\D o c u m e n ts \6
M e c h a n ic a l_ ily tl e
E G
V K
N .r v t
/1
/2
:2
:5
P
M
09/07/2021
MECHANICAL - PENTHOUSE PIPING PLAN EHRM Training and Admin Space Support
Minneapolis VA Healthcare System
DG IL
618-701
1384-MP105
ISSUE FOR BID
18-11636C26319D0022
N
1/8" = 1'-0"
MECHANICAL - PENTHOUSE FLOOR PIPING PLAN
30°
30°
15°
15°
M A
X
M A
X
15°
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
M
AX.
M A
X
E Q
U
IP
M E
N T
AIR FLOW AIR FLOW
TYPICAL DUCTWORK
TRANSITION
PLAN OR SIDE VIEW
TYPICAL DUCTWORK
TRANSITION WITH
EQUIPMENT MOUNTED IN
DUCT
PLAN OR SIDE VIEW
M
AX.
M A
X
W
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR FLOW
AIR FLOW
PROVIDE VOLUME
DAMPER AT EACH
BRANCH DUCT
1/4W OR 4" MIN.
BRANCH DUCT
VD
W2
W1
NOTE:
1.
2.
3.
4.
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE REGARDLESS OF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2" MAXIMUM SPACE BETWEEN VANES AND A 3/4" TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" VANES SHALL BE DOUBLE VANE TYPE.
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION
SHALL BE SIMILAR FOR MULTI-BLADE DAMPERS & ROUND
DAMPERS.
INSULATION SEE
SPECIFICATION
DAMPER BLADE
1/8" CLEARANCE
ALL AROUND
OUTSIDE END
BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION
STAND-OFF
1/2" ROUND ROD PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
DAMPER
BLADE
2/3W
W W
1/2W
1/3W
1/6W
R RVANE
VANE
NOTE:
1.
2.
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS
ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE
CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
R SHALL
EQUAL OR
BE
GREATER
THAN W.
R SHALL
EQUAL OR
BE
GREATER
THAN 1/3W.
W
R
1/3W
R SHALL
EQUAL OR
BE
GREATER
THAN 1/6W.
STANDARD RADIUS OR LONG
RADIUS
ELBOW
SHORT RADIUS ELBOW WITH ONE VANE SHORT RADIUS ELBOW WITH TWO VANES
W
DESIGNER'S NOTES:
1. THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR UP UP TO 25% OF
THE MAIN DUCT CFM. THE BRANCH DUCT TAKE-OFF MAY BE USED FOR
UP TO 15% OF THE MAIN DUCT CFM ANYTIME AND UP TO 40% WHEN THE
MAIN DUCT VELOCITY IS 1000 FPM [5.1 M/S] OR LESS. THE AIR SPLIT DUCT
TAKE-OFF SHALL BE USED IN ALL OTHER CASES AND MAY BE USED AT
ANYTIME.
2. SHOW ALL VOLUME DAMPERS ON FLOOR PLANS.
AIR SPLIT DUCT TAKE-OFF PLAN VIEW BRANCH DUCT TAKE-OFF PLAN VIEW
AIR FLOW
AIR FLOW
A
IR
F
LO
W
SUPPLY
REGISTER OR
BRANCH
DUCT
TURNING VANES
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN FOR
SPLIT DIMENSION
PROVIDE
VOLUME
DAMPER
PROVIDE VOLUME DAMPER1/4 W OR 4" MIN.
AIR FLOW
MAIN SUPPLY DUCT
A
IR
F
LO
W
NOTE:
FLEXIBLE CONNECTION TO ISOLATE ALL DUCTS FROM ALL FANS AND FAN
ENCLOSURES TO PREVENT FANS AND FAN ENCLOSURES TO PREVENT
TRANSMISSION OF VIBRATION TO DUCTWORK AND STRUCTURE.
SP OF FAN
UP TO 2"
2 1/8" TO 4"
DUCT LINING
ANGLES, ALL SIDES MITRED,
WELDED CORNERS
SLACK
MIN. "L"MIN. SLACK
2" 1 1/4"
6" 4"
CONTINUOUS BAR-SAME
SIZE AS ANGLE x 1/4", BOLTED TO ANGLE
"L"
12"
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT (TYP.)
SHEET METAL SADDLE
BRANCH ROUND DUCT.
SEE FLOOR PLAN FOR SIZE.
CONICAL OUTLET
SUPPLY OR RETURN DUCT MAIN
SUPPORT
SADDLE FROM
STRUCTURE
5'-0" MAX.
VOLUME DAMPER W/
LOCKING QUAD
FLEXIBLE DUCT SIZE SAME AS
DIFFUSER
(ONLY WHERE CONCEALED ABOVE
ACCESSIBLE CEILINGS)
ROUND HARD DUCT ELBOW
6" MIN.
CEILING
SPACER (NOTE: SPACER SHALL ALSO BE
UTILIZED FOR TRANSITION WHERE DIFFUSER
NECK AND BRANCH DUCT SIZE DIFFER.)
SUPPLY DIFFUSER OR RETURN REGISTER
(SEE SCHEDULE FOR TYPE)
5'-0" MAX.
SPIN-IN COLLAR
WITH DAMPER
PROVIDE REMOTE CABLE CONTROL IN
INACCESSIBLE CEILINGS AT LOCATIONS
WHERE ARCHITECTURAL DRAWINGS DO
NOT INDICATE A CEILING ACCESS PANEL
FLEXIBLE DUCTWORK
(ONLY WHERE
CONCEALED ABOVE
CEILINGS)
PROVIDE CEILING ACCESS PANEL IN
INACCESSIBLE CEILINGS
REGISTER NECK SIZED
PLENUM WITH 1/2" THICK
ACOUSTICAL LINING.
RETURN
DUCT MAIN
BRANCH ROUND
DUCT. SEE FLOOR
PLAN FOR SIZE.
SUSPENDED ACOUSTICAL
TILE CEILING
RETURN/EXHAUST REGISTER
(SEE SCHEDULE FOR TYPE)
OPPOSED BLADE VOLUME DAMPER
OPERABLE THRU REGISTER FACE
WHERE MANUAL DAMPER NOT
SHOWN ON FLOOR PLANS.
SHEET METAL SADDLE
SUPPORT
SADDLE FROM
STRUCTURE1"
8"1"
DRAW THRU
BLOW THRU
2" [50mm]
PLUS X
1" [25mm]
MINIMUM
X
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT LEAST THE
SAME SIZE AS THE NIPPLE ON THE DRAIN
PAN PIPING SHALL BE RIGID COPPER
TYPE L OR TYPE M UNLESS NOTE BELOW
IS MET
PITCH DOWN TOWARD DRAIN
CLEAN OUT
FLOOR SINK
DRAIN PAN
NOTE:
1. DIELECTRIC FITTING TO BE USED WHEN TWO
DISSIMILAR METALS ARE TO BE CONNECTED.
[2 5m m
DIELECTRIC
FITTING
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No. VA CONTRACT NO.
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ 70-129AREAG70-131AREAH AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ70-129AREAG70-131AREAH
C U s e rs \i ly tl e
\D o c u m e n ts \6
M e c h a n ic a l_ ily tl e
E G
V K
N .r v t
/1
/2
:2
:3
P
M
09/07/2021
MECHANICAL DETAILS EHRM Training and Admin Space Support
Minneapolis VA Healthcare System
DG IL
618-701
1384-M501
ISSUE FOR BID
18-11636C26319D0022
NOT TO
SCALE
DETAIL - DUCTWORK TRANSITIONS (WITH DUCT MOUNTED
EQUIPMENT)
NOT TO
SCALE
DETAIL - EXHAUST OR RETURN BRANCH DUCTWORK
NOT TO
SCALE
DETAIL - DUCTWORK SQUARE VANE ELBOWS
NOT TO
SCALE
DETAIL - VOLUME DAMPER
NOT TO
SCALE
DETAIL - DUCTWORK RADIUS ELBOWS
NOT TO
SCALE
DETAIL - DUCTWORK - TAKEOFF
NOT TO
SCALE
DETAIL - FLEXIBLE CONNECTION
NOT TO
SCALE
DETAIL - DIFFUSER INSTALLATION
NOT TO
SCALE
DETAIL - RETURN/EXHAUST REGISTER INSTALLATION
NOT TO
SCALE
DETAIL - AIR HANDLING UNIT DRAIN TRAP
Revisions: Date:
35% SCHEMATIC DESIGN SUBMITTAL 06/10/2021
65% DESIGN DEVELOPMENT SUBMITTAL 07/15/2021
ANCHOR BOLTS
N=NUMBER
S=SIZE
DRILL = S+1/16"
PIPE ANCHOR SCHEDULE
D P C N S
4" 5_ " 3_
" 4" 3_
BOLT PATTERN
3" 1_ " 1_
" 4" 5_
21_
2"
11_
3_
3_
3_
3_
3_
1_
4"
4"
4"
5_
5_
1_
D=PIPE O.D.
INSULATE AS INDICATED FOR ALL
CHILLED WATER. INSULATE PIPE
ONLY FOR STEAM & CONDENSATE
D+3 3/4"
D+1 1/2"
5/16"
NOTE:
WHERE USED FOR COPPER TUBE OR PIPE,
BRAZE TO FABRICATED STEEL ANCHOR
P
D
STL PIPE OR
COPPER TUBE
NOTE
C
D+2 1/2"
D+4 3/4"
D+[25]
MM
13 13
191916
10 10
10 10
10 6
[8]
D+1"
DRILL = S+[2]
D+[38]
D+[95]
D+[64]
D+[121]
IN MMIN MMIN MMIN MMIN
STEEL EXPANSION SHIELD FOR EXISTING
CONSTRUCTION AND INSERTS FOR NEW
CONSTRICTION THIS TYPE SHALL BE USED ONLY
IN SLABS OR BEAMS OF 4" [100mm] MIN DEPTH
3/8" [10mm] MIN DIA EXPANSION
BOLTS FOR EXISTING
CONSTRUCTION AND INSERTS
FOR NEW CONSTRUCTION
CONCRETE
FLOOR SLAB
CLIP
ANGLE
NUTS &
WASHERS
3/8" [10mm] MIN DIA
HANGER RODS
FOR PIPES UNDER 2" [50mm] IN SIZE USE 1 1/2"x1 1/2"x1/4" [40x40x6.4mm] ANGLE. ALL PIPES 2" [50mm] & LARGER USE 3"x3"x1/4" [75x75x6.4mm] ANGLE
TURNBUCKLE
3/8" [10mm] MIN DIA
HANGER RODS
3/8" [10mm] MIN DIA
INSERTS NEW
CONSTRUCTION ONLY.
5 FT
THRU [20]
6 8 10
[32][25] [40]
[65]
[50]
[75]
-1312 14 -16 -
[125][100]
[150]
[250]
[200]
[300]
[400]
[350]
[450]
[600]
[500]
20 241814 16128 1064 532 2 1/21 1/21 1 1/4
[9100] [9600][8500][7600] [8200][7000][5800] [6700][5200][4100] [4900][3700][3000] [3400][2700][2100]
--- --[4900] -[4100][3700] [4000] -[3000][2400][1800][1500]
THRU 3/4
[2100] [2100]
[2100]
[2700]
[2400]
SIDE VIEW TRAPEZE HANGER FOR UP TO 1000
LB. [453KG] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
[mm]
FT.
[mm]
FT.
[mm]
[2 5m m
1" M
AX
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" [200mm] MIN.)
BAND
1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE
1/2" [15mm] DIA.
HANGER RODS WITH
36" [900mm] MAX.
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF MIN.
DENSITY) UNDER INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
NOTES:
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
2500 [1133]
1320 [598]
420 [190]ONE 1 [25] x 18 GA STRAP36 [900]
TWO 1/2 [13] RODS
TWO 3/8 [10]. RODS
ONE 1 [25] x 16 GA STRAP
84 [2100]
60 [1500]
50 [1250] 700 [317]
ONE 1 [25] x 22 GA STRAP
QUANTITY/SIZEMAX. DUCT ∅
26 [650]
HANGER STRAPS OR RODS
MAX. LOAD
LBS. [kg]
260 [119]
MAX.
144 [3600]
IN. [mm]
SPACING
IN. [mm] IN. [mm]
144 [3600]
144 [3600]
144 [3600]
144 [3600]
NOTE:
TABULATED DATA FROM SMAC NA ALLOWS FOR DUCT
REINFORCING AND INSULATION, BUT NO EXTERNAL
LOAD.
BAND
OVER 50"
[1250mm]
HANGER RODS
BAND OF SAME SIZE AS
HANGER STRAP
LOAD RATED
FASTENERS
50" [1250mm]
& UNDER
HANGER RODS
ROD
SUPPORT NUT
AND WASHER
IRON ANGLE
NOTES:
OVER 4 FEET NOT TO
EXCEED 10 FEET
OVER 10 FEET
1. DUCT SHALL BE SUSPENDED WITH GALVANIZED BAND IRON
STRAPS SECURELY FASTENED TO THE BOTTOM AND SIDE OF
THE DUCT. STRAPS SHALL BE SIZED IN ACCORDANCE WITH
SMACNA TABLE 4-1 OR ACCORDING TO LOCAL CODES,
WHICHEVER IS MORE STRINGENT.
2. DUCTS WIDER THAN 60 INCHES SHALL BE SUPPORTED BY
TRAPEZE ANGLES IN ACCORDANCE WITH SMACNA TABLE 4-1.
ROD
CHAMFER/CUT
CORNERS AT 45
DEGREES (TYP)
NOTES:
CROSS SECTIONAL
AREA
MAX HANGER
SPACING
1. DUCT SHALL BE SUSPENDED WITH GALVANIZED BAND IRON
STRAPS SECURELY FASTENED TO THE BOTTOM AND SIDE OF
THE DUCT. STRAPS SHALL BE SIZED IN ACCORDANCE WITH
SMACNA TABLE 4-1 OR ACCORDING TO LOCAL CODES,
WHICHEVER IS MORE STRINGENT.
2. DUCTS WIDER THAN 60 INCHES SHALL BE SUPPORTED BY
TRAPEZE ANGLES IN ACCORDANCE WITH SMACNA TABLE 4-1.
CONCRETE
SLABCONCRETE
INSERTS
(TYP.)
" M
AX
SELF TAPPING
SCREWS (TYP)
DUCT HANGING
STRAP
2" MIN
ROD
LOCKING NUT
AND WASHER
INSULATION
DUCT
NOTES:
UP TO 4 FEET 8 FEET
6 FEET
4 FEET
DUCT
1. DUCT SHALL BE SUSPENDED WITH GALVANIZED BAND IRON
STRAPS SECURELY FASTENED TO THE BOTTOM AND SIDE OF
THE DUCT. STRAPS SHALL BE SIZED IN ACCORDANCE WITH
SMACNA TABLE 4-1 OR ACCORDING TO LOCAL CODES,
WHICHEVER IS MORE STRINGENT.
2. DUCTS WIDER THAN 60 INCHES SHALL BE SUPPORTED BY
TRAPEZE ANGLES IN ACCORDANCE WITH SMACNA TABLE 4-1.
PACK VOID BETWEEN PIPE OR
INSULATION AND WALL WITH FIBERGLASS
BATT, THEN SEAL WITH A SILICONE
COMPOUND OR OTHER APPROVED
SEALANTS. IF WALL IS FIRE RATED,
FILL VOID BETWEEN PIPE OR
INSULATION AND WALL WITH FIRE
BARRIER CAULK.
CONTINUOUS
SEALANT AROUND
OPENING BOTH SIDE
OF WALL.
PIPE INSULATION.
SEE DRAWINGS FOR PIPE
SIZE AND MATERIAL.
NOTES:
1. I.D. OF WALL OPENING TO BE A MIN. OF 1/2" LARGER THAN O.D. OF PIPE OR
INSULATION PASSING THROUGH WALL.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THEIR WALL
OPENINGS WITH OTHER TRADES AND/OR CONTRACTORS.
3. PIPE PENETRATIONS OF SMOKE OR FIRE WALLS SHALL BE IN COMPLIANCE WITH
NFPA-90A.
PROVIDE A MINIMUM OF 1/2"
CLEARANCE BETWEEN WALL
AND PIPE OR INSULATION.
FACE OF WALL.
SHEET METAL DUCT
FILL VOID WITH FIRE
BARRIER CAULK
GYPSUM BOARD/METAL STUD WALL
22 GA. GALVANIZED SHEET
METAL CAP
22 GA. GALVANIZED METAL SLEEVE
POURED CONCRETE OR CONCRETE
BLOCK
WALL
FILL VOID WITH FIRE
BARRIER CAULK
GROUT
1/8" NPT SAFETY DRAIN
CONNECTION PIPED TO DRAIN.
BRASS BODY WATER MAIN VENT
VALVE WITH 3/4" NPT CONNECTION.
SHUT-OFF VALVE
MAIN VENTS CONNECTED
AT VERTICAL HIGH POINTS
TO DRAIN
3/4" CONNECTION LINE
SUPPLY
HEADER
SUPPLY
HEADER
HWS
HWR
VAV BOX W/ FACTORY
ACOUSTICAL/THERMAL LINING
3/4" DRAIN VALVE WITH HOSE THREAD
OUTLET
TWO WAY MODULATING
CONTROL VALVE
CEILING BY PRIME
CONTRACTOR
SUPPLY DIFFUSER
1" EXTERNALLY INSULATED
MEDIUM PRESS. SUPPLY
DUCTWORK MAIN
RIGID DUCT CONNECTION TO BOX INLET.
MIN 1.5 TIMES BOX INLET DIAMETER BUT NOT
LESS THAN 12"
SPIRAL RIGID ROUND
DUCTWORK (WHERE SHOWN
ON FLOOR PLANS)
SAME SIZE AS BOX INLET
DIA. SEE VAV BOX
SCHEDULE
CONICAL "SPIN-IN" FITTING
BALL VALVE AT TAKE-OFF FROM MAIN
WHERE SHOWN ON PLANS
INTEGRAL HOT WATER
REHEAT COIL (WHERE
SHOWN ON FLOOR PLANS)
LOW PRESS. RECTANGULAR SUPPLY AIR DUCT WITH
1-1/2" THICK FLEXIBLE FIBERGLASS WITH VAPOR
BARRIER JACKET DOWNSTREAM FROM DISCHARGE
OF ALL VAV BOXES
SPIN-IN COLLAR
WITH DAMPER
MANUAL AIR
VENT(TYP.)
CIRCUIT
BALANCING VALVE
UNION
REDUCER/INCREASER (TYP.)
VAV BOX
CONTROLLER
MAX. 3FT. OF 1" THICK FACTORY INSULATED
MED. PRESS. FLEXIBLE DUCTWORK W/ VAPOR
BARRIER JACKET
NOTE:
VAV BOXES SHALL BE LOCATED NO HIGHER
THAN 12" ABOVE CEILING.
CHWR
CHWS
PITCH COIL
DRAIN PAN
UNION
FLEX. CONN.
AIR FLOW
FLOW CONTROL BALANCE VALVE
THERMOMETER (TYP.) BALL VALVE (TYP.)
NOTES:
1. ALL VALVES 2" AND SMALLER TO BE BALL VALVES, 2 1/2" AND LARGER TO BE BUTTERFLY VALVES.
2. INSTALL PIPE UNIONS ON 2" AND SMALLER PIPE, FLANGED PIPE 2 1/2" AND LARGER.
3. ALL COILS TO BE FACTORY TAPPED FOR MANUAL AIR VENT AT HIGH POINT AND DRAIN AT LOW POINT OF COIL.
4. ALL COILS TO BE PIPED FOR COUNTER FLOW OF AIR AND WATER.
5. PIPING TO COIL SHALL BE ARRANGED SO AS NOT TO BLOCK OFF ANY ACCESS REQUIREMENTS OR SERVICE
AREAS OF AIR HANDLING UNIT.
6. SEE FLOOR PLANS FOR PIPE SIZES.
7. PROVIDE FLEXIBLE PIPING CONNECTIONS AS SHOWN WHERE AIR HANDLING UNIT IS NOT INTERNALLY
ISOLATED OR WHERE SPECIFICALLY CALLED FOR ON DRAWINGS.
8. PIPING CONTRACTOR SHALL FURNISH/INSTALL TEMPERATURE WELLS AS SHOWN FOR FUTURE USE EVEN IF
SENSORS ARE NOT PROVIDED UNDER THIS PROJECT.
2-WAY VALVE BY T.C. CONTR.,
INSTALLED BY PIPING CONTR.
TEMPERATURE WELL BY PIPING
CONTR., SENSOR BY T.C.
CONTRACTOR (TYP.)
INCREASER OR
DECREASER AS
REQUIRED (TYP.)
PRESSURE/TEMPERATURE PLUG
WITH CAP FOR MANUAL
READINGS (TYP.)
1/2" COIL DRAIN VALVE W/ HOSE
THREAD OUTLET (TYP.)
DRAIN LINE TRAP. SEE
DETAIL ELSEWHERE.
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No. VA CONTRACT NO.
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ 70-129AREAG70-131AREAH AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ70-129AREAG70-131AREAH
C U s e rs \i ly tl e
\D o c u m e n ts \6
M e c h a n ic a l_ ily tl e
E G
V K
N .r v t
/1
/2
:2
:3
P
M
09/07/2021
MECHANICAL DETAILS EHRM Training and Admin Space Support
Minneapolis VA Healthcare System
DG IL
618-701
1384-M502
ISSUE FOR BID
18-11636C26319D0022
NOT TO
SCALE
SMALL PIPE ANCHOR DETAIL
NOT TO
SCALE
SECURING HANGER RODS IN CONCRETE DETAIL
NOT TO
SCALE
PIPE HANGER DETAIL
NOT TO
SCALE
ROUND DUCT HANGER DETAIL
NOT TO
SCALE
RECTANGULAR DUCT INSTALLATION DETAIL
NOT TO
SCALE
PIPE PENETRATION OF INTERIOR WALL DETAIL
NOT TO
SCALE
DUCT SLEEVE THRU INTERIOR WALL DETAIL
NOT TO
SCALE
MAIN AIR VENT DETAIL
NOT TO
SCALE
VAV BOX PIPING DETAIL
NOT TO
SCALE
CHILLED WATER COIL 2-WAY VALVE PIPING
Revisions: Date:
35% SCHEMATIC DESIGN SUBMITTAL 06/10/2021
65% DESIGN DEVELOPMENT SUBMITTAL 07/15/2021
2 86T TE FC W EG
2 86T TE FC W EG
2 86T TE FC W EG
2 86T TE FC W EG
2 86T TE FC W EG
2 86T TE FC W EG
2 86T TE FC W EG
2 86T TE FC W EG
12"
MEDIUM
RISE IN STEAM MAIN
CHECK VALVE
F & T TRAP
PROVIDE TEST PLUG AND
STEAM TRAP
TEMPERATURE MONITOR.
STRAINER
UNION
GATE VALVE
DIRT LEG (2" MIN. DIA.)
RETURN MAIN
OR HIGH
PRESSURE
STEAM MAIN
INSULATE ALL STEAM
TRAPS AND PROVIDE
MONITOR.
AHU
HEIGHT
AHU WIDTH
12" OR
20" STAND
AHU FLOOR
DRAIN TO
NEARBY
FLOOR DRAIN
MANUAL SHUT-OFF
VALVE (TYP.)
STEAM MAIN
STRAINER
CONTROL VALVE
SEPARATOR
F&T TRAP
(TYPICAL). INSULATE ALL
STEAM TRAPS AND
PROVIDE MONITOR.
LOW PRESSURE CONDENSATE
RETURN MAIN.
6" MIN.
UNION
SEE DETAIL
ELSEWHERE
CONDENSATE
TEMPERATURE SWITCH
4" THICK CONCRETE BASE
SUCTION
SUCTION DIFFUSER
BLOW DOWN PIPE AND
ADJUSTABLE PIPE
SUPPORT FOOT
BUTTERFLY VALVE
HYDRONIC INDICATOR
W/TRUMPET VALVES
EXTEND CONCRETE BASE MINIMUM
OF 4" ALL SIDES OF PUMP
BASE MOUNTED PUMP
TRIPLE DUTY VALVE
FLEXIBLE CONNECTION
PIPE INCREASER
1/4" COPPER TUBES
TEMPERATURE SENSOR
PIPING CONTRACTOR SHALL
FURNISH AND INSTALL ALL
DISCHARGE
MOUNT PIPE HANGER
AT EACH PIPE DROP
TO AVOID STRAIN
ON PUMP (TYPICAL)
WATER FLOW SWITCH
FLEXIBLE CONNECTIONFILL PUMP BASE WITH
NON-SHRINK GROUT
GATE VALVE WITH
THREADED HOSE CONN.
PIPE WELLS REQUIRED BY
T.C. CONTRACTOR
NOTE:
PIPING CONTRACTOR SHALL FURNISH/INSTALL WELL FOR TEMPERATURE SENSOR AND TAP FOR
FLOW SWITCH REGARDLESS IF DDC CONTROLS ARE ON PROJECT. IF DDC CONTROLS ARE NOT
ON PROJECT, PIPING CONTRACTOR SHALL PROVIDE THERMOMETER IN DISCHARGE WELL.
STEAM MAIN DRIP
TRAP. INSULATE ALL
STEAM TRAPS AND
PROVIDE MONITOR. T
STEAM
MAIN
STRAINER
1/4" PETCOCK CRACKED
OPEN FOR CONTINUOUS
AIR VENTING
3/4" SPRING LOADED VACUUM
BREAKER VENTED TO
ATMOSPHERE RECOMMENDED
ON BOTH THE SUPPLY AND
THE CONDENSATE LINES.
VIFB
COIL
AIR
FLOW
12" MINIMUM
8"
FLEXIBLE CONNECTOR INSTALLED
PARALLEL TO COIL HEADER AND AS
CLOSE AS POSSIBLE TO COIL
CONDENSATE CONNECTION.
12" MIN.
STRAINER
T
F & T TRAP
PROVIDE TEST PLUG AND
STEAM TRAP
TEMPERATURE MONITOR.
CHECK
VALVE
RETURN MAIN
ON/OFF CONTROL
VALVE
VFD
MMP
UV
VFD
MMP
VFD
MMP UV
VFD
MMP
SA
OA
EA
IA
IA
ELEVATION VIEW
PLAN VIEW
SUPPLY FAN AND
DISCHARGE
PLENUM SECTION
UV LIGHTS
STEAM
HUMIDIFIER
AIR BLENDER
FACE AND
BYPASS STEAM
PREHEAT COIL
OUTSIDE AIR
SECTION
RELIEF AIR
SECTION
RETURN FAN
SECTION
RETURN FAN
(TYP. OF 4)
CHILLED WATER
COOLING COIL
SUPPLY FAN
(TYP. OF 4)
GALVANIZED
STEEL OUTER
WALL
304 STEEL INNER
WALL
12" BASE RAIL 1-1/4" INSULATED
COPPER DRAIN LINE
TO FLOOR DRAIN
PENTHOUSE
FLOOR
PRE-FILTER AND
FILTER
FLEXIBLE CONNECTION (TYP.)
MIN.
2.5 DIA
MIN.
2.5 DIA
DUCT TRANSITION IF REQUIRED
VIBRATION ISOLATORS (TYP.)SUPPORT FAN FROM STRUCTURE WITH
THREADED
STEEL RODS (TYP.)
MOTORBELT GAURD
AIR FLOW
FULL SIZE OF FAN CONNECTION (TYP.)
AIR FLOW
MOUNTING BRACKET
NOTE:
1. ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 12" MINIMUM HIGH DRIP LEG FROM BOTTOM OF
STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 6" SCALE POCKET BELOW TRAP INLET.
TO RETURN MAIN
PIPE SIZE SHALL BE SAME SIZE AS TRAP
FLOAT AND THERMOSTATIC TRAP.
SEE PLANS, AND SCHEDULES
DIELECTRIC FITTING WHERE
RETURN IS COPPER PIPE
SCHEDULE 80
STEEL PIPE
BYPASS-INSTALL IN HORIZONTAL PLANE LEVEL WITH
TRAP OR IN VERTICAL PLANE & BELOW TRAP PROVIDE
BYPASS PIPING FOR ALL TRAPS 1" AND LARGER.
DRIP LEG OR EQUIPMENT CONNECTION. MAKE
THE SAME SIZE AS THE SUPPLY MAIN OR
EQUIPMENT CONNECTION. SEE NOTE 1
SCHEDULE 80 STEEL PIPE
SEE DRAWINGS FOR PIPE SIZES
1" GATE VALVE
FLOW
" M
IN
6" M
IN
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No. VA CONTRACT NO.
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ 70-129AREAG70-131AREAH AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ70-129AREAG70-131AREAH
C U s e rs \i ly tl e
\D o c u m e n ts \6
M e c h a n ic a l_ ily tl e
E G
V K
N .r v t
/1
/2
:2
:3
P
M
09/07/2021
MECHANICAL DETAILS EHRM Training and Admin Space Support
Minneapolis VA Healthcare System
DG IL
618-701
1384-M503
ISSUE FOR BID
18-11636C26319D0022
NOT TO
SCALE
MEDIUM-HIGH PRESSURE STEAM DRIP
NOT TO
SCALE
STEAM HUMIDIFIER PIPING CONNECTIONS DEATIL
NOT TO
SCALE
BASE MOUNTED PUMP
NOT TO
SCALE
STEAM FACE AND BYPASS COIL PIPING DETAIL
NOT TO
SCALE
AIR HANDLING UNIT (70-AHPW-46) ARRANGEMENT DETAIL
Revisions: Date:
ISSUE FOR BID 09/07/2021
NOT TO
SCALE
IN-LINE EXHAUST FAN
NOT TO
SCALE
FLOAT AND THERMOSTATIC STEAM TRAP ASSEMBLY
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No. VA CONTRACT NO.
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ 70-129AREAG70-131AREAH AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ70-129AREAG70-131AREAH
C U s e rs \i ly tl e
\D o c u m e n ts \6
M e c h a n ic a l_ ily tl e
E G
V K
N .r v t
/1
/2
:2
:3
P
M
09/07/2021
MECHANICAL SCHEDULES EHRM Training and Admin Space Support
Minneapolis VA Healthcare System
DG IL
618-701
1384-M601
ISSUE FOR BID
18-11636C26319D0022
FOR QUANTITY AND LOCATION.
9. PROVIDE NECESSARY 120V / 24V POWER SUPPLY FOR CONTROLLER POWER. COORDINATE WITH ELECTRICAL DRAWINGS
PRESSURE SHALL NOT BE LESS THAN 0.25" AT AIR FLOW RATE SCHEDULED. 8. COORDINATE LEFT HANDED/RIGHT HANDED COIL CONNECTIONS WITH DESIGN DRAWINGS AND EXISTING FIELD CONDITIONS
4. REGARDLESS OF HOT WATER COIL AIR PRESSURE DROP, AVAILABLE DISCHARGE STATIC 7. PROVIDE WITH ACCESS DOORS FOR REHEAT COIL AND FACTORY MOUNTED DISCONNECT.
DISCHARGE PRESSURE. NOISE CRITERIA (NC) SOUND INFORMATION IS BASED ON ARI-880-98. MANUFACTURER HAS COORDINATED WITH T.C. CONTRACTOR.
3. SOUND LEVELS (NC) AST FULL AIR FLOW WITH 0.75" INLET STATIC PRESSURE AND 0.5" FURNISHED BY THE T.C. CONTRACTOR. BOXES SHALL NOT BE RELEASED FOR PRODUCTION UNTIL BOX
2. BOX SHALL BE LINED WITH 1" FIBER-FREE INSULATION. 6. VAV MANUFACTURER TO MOUNT IN FACTORY THE DDC CARD/CONTROLLER AND DAMPER ACTUATOR
1. OTHER ACCEPTABLE MANUFACTURERS: VA APPROVED EQUAL 5. HOT WATER COIL WATER PRESSURE DROP SHALL NOT EXCEED 5' AND AIR PRESSURE DROP SHALL NOT EXCEED 0.3" WG.
NOTES:
70-VAV-146-150-6 PENTHOUSE ATRIUM 2P TITUS DESV 2,500 2,500 16 18x24 18.0 15.5 24 2500 99.4 55 91.7 180 150 6.6 2 18 17 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-146-150-5 PENTHOUSE ATRIUM 2P TITUS DESV 2,500 2,500 16 18x24 18.0 15.5 24 2500 99.4 55 91.7 180 150 6.6 2 18 17 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-150- 4 PENTHOUSE ATRIUM 2P TITUS DESV 2,500 2,500 16 18x24 18.0 15.5 24 2500 99.4 55 91.7 180 150 6.6 2 18 17 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-150-3 CSP-116 2P-150 TITUS DESV 1,000 2,000 16 18x24 18.0 15.5 24 2000 47.6 55 77 180 150 3.2 2 17 16 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-150-2 C2P-117 2P-150 TITUS DESV 1,000 1,995 16 18x24 18.0 15.5 24 2000 47.6 55 77 180 150 3.2 2 17 16 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-150-1 2P-143 2P-150 TITUS DESV 1,000 2,400 16 18x24 18.0 15.5 24 2400 51.6 55 80.6 180 150 3.4 1 20 17 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-150C CONSULTATION 2P-150C 2P-150C TITUS DESV 60 120 6 8x14 8.0 15.5 10.0 120 4.7 55 90.9 180 150 0.5 1 17 19 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-150B CONSULTATION 2P-150B 2P-150B TITUS DESV 60 120 6 8x14 8.0 15.5 14.0 120 4.7 55 90.9 180 150 0.5 1 17 19 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-149 TRAINING 11 2P-149 TITUS DESV 325 650 10 14x12.5 12.5 15.5 14.0 650 16.4 55 78.2 180 150 1.1 1 18 18 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46 -48 TRAINING 12 2P-148 TITUS DESV 325 650 10 14x12.5 12.5 15.5 14.0 650 16.4 55 78.2 180 150 1.1 1 18 18 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-147 TRAINING 13 2P-147 TITUS DESV 325 650 10 14x12.5 12.5 15.5 14.0 650 16.4 55 78.2 180 150 1.1 1 18 18 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-146 TRAINING 1 2P-146 TITUS DESV 325 650 10 14x12.5 12.5 15.5 14.0 650 16.4 55 78.2 180 150 1.1 1 18 18 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-145 TRAINING 2 2P-145 TITUS DESV 400 825 10 14x12.5 12.5 15.5 14.0 825 18.2 55 75.3 180 150 1.2 1 19 19 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-144 TRAINING 3 2P-144 TITUS DESV 325 650 10 14x12.5 12.5 15.5 14.0 650 16.4 55 78.2 180 150 1.1 1 18 18 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-143 TRAINING 4 2P-143 & C2P-118 TITUS DESV 400 825 10 14x12.5 12.5 15.5 14.0 825 18.2 55 75.3 180 150 1.2 1 19 19 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-140
TRAINING 5
2P-140 2P-140 TITUS DESV 325 650 10 14x12.5 12.5 15.5 14.0 650 16.4 55 78.2 180 150 1.1 1 18 18 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-137 CORRIIDOR C2P-117 C2P-117,2P-137 &2P-141 TITUS DESV 400 900 10 14x12.5 12.5 15.5 14.0 900 19.1 55 74 180 150 1.3 1 20 19 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-139
TRAINING 6
2P-139 2P-139 TITUS DESV 325 650 10 14x12.5 12.5 15.5 14.0 650 16.4 55 84.2 180 150 0.7 1 18 18 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-138
BREAK ROOM
2P-138 2P-138 TITUS DESV 160 325 8 12x10 10.0 15.5 12.0 325 19.1 55 78.2. 180 150 0.7 1 15 15 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-135
CONFERENCE ROOM
2P-135 2P-135 TITUS DESV 200 400 8 12x10 10.0 15.5 12.0 400 11.4 55 81.2 180 150 0.8 1 18 16 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-134
TRAINING 8
2P-134 2P-134 TITUS DESV 325 650 10 14x12.5 12.5 15.5 14.0 650 16.4 55 78.2 180 150 1.1 1 18 18 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-133
TRAINING 7
2P-133 2P-133 & C2P-116 TITUS DESV 400 825 10 14x12.5 12.5 15.5 14.0 825 18.2 55 75.3 180 150 1.2 1 19 19 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-132
TRAINING 9
2P-132 2P-132 TITUS DESV 325 650 10 14x12.5 12.5 15.5 14.0 650 16.4 55 78.2 180 150 1.1 1 18 18 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-131
TRAINING 10
2P-131 2P-131 & C2P-116 TITUS DESV 400 825 10 14x12.5 12.5 15.5 14.0 825 18.2 55 75.3 180 150 1.2 1 19 19 YES 1,2,3,4,5,6,7,8 & 9
70-VAV-46-130 WAITING/CHECK & CORRIDOR 2P-130 2P-130 & C2P-115 TITUS DESV 500 1,000 10 14x12.5 12.5 15.5 14.0 1000 19.7 55 73.2 180 150 1.3 1 22 20 YES 1,2,3,4,5,6,7,8 & 9
MIN. MAX.
INLET
SIZE
OUTLET
SIZE
H L W HEATING CFM
CAPACITY
(MBH)
EAT (°F) LAT (°F) EWT (°F) LWT(°F) GPM ROWS RADIATED DISCHARGE
EQUIPMENT
TAG
LOCATION SERVES ROOM (S)#
BASIS OF DESIGN
MANUFACTURER
MODEL
AIRFLOW (CFM) APPROX. DIMENSIONS (IN.) HOT WATER COIL NOISE LEVEL(NC)
INTEGRAL
SOUND
ATTENUATOR
NOTES
VAV BOX WITH HOT WATER REHEAT SCHEDULE
Revisions: Date:
65% DESIGN DEVELOPMENT SUBMITTAL 07/15/2021
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
FULLY SPRINKLERED
Bancroft Project No. VA CONTRACT NO.
AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ 70-129AREAG70-131AREAH AREAM70-139AREAA70-11770-121AREACAREAL70-13770-119AREAB70-123AREAD70-135AREAK70-127AREAF70-125AREAE70-133AREAJ70-129AREAG70-131AREAH
C U s e rs \i ly tl e
\D o c u m e n ts \6
M e c h a n ic a l_ ily tl e
E G
V K
N .r v t
/1
/2
:2
:3
P
M
09/07/2021
MECHANICAL SCHEDULES EHRM Training and Admin Space Support
Minneapolis VA Healthcare System
DG IL
618-701
1384-M602
ISSUE FOR BID
18-11636C26319D0022
8. FACTORY SUPPLIED VFD WITH DISCONNECT. (1 FOR FOR EACH FAN.)
IN ALL SECTIONS REQUIRED MAINTENANCE.
7. PROVIDE DOUBLE WALL CONSTRUCTION WITH INNER WALL TO BE STAINLESS STEEL WITH ALUMINUM DIAMOND PLATE 15. PROVIDE A SINGLE POINT POWER CONNECTION FOR THE SUPPLY FAN AND ONE SINGLE POINT POWER CONNECTION FOR THE RETURN FAN.
6. PRE-INSULATED STAINLESS STEEL DRAIN PAN. 14. PROVIDE UV LIGHTS DOWNSTREAM OF COOLING WITH SEPARATE WITH SEPARATE SWITCH MOUNTED ON EXTERIOR OF CABINET FACTORY MOUNTED.
5. HINGED ACCESS DOORS AND MARINE LIGHTS AT EACH SECTION. 13. PROVIDE WITH AIR BLENDER SECTION ON DISCHARGE SIDE OF MIXING BOX.
4. PROVIDE NON-POWERED, GFI CONVENIENCE OUTLET. 12. PROVIDE WITH FACTORY SUPPLIED AND MOUNTED STEAM DISRIBUTOR AND HUMIDIFIER SECTION.
3. SAME END CHILLED WATER AND STEAM COIL CONNECTIONS. 11. PROVIDE MAGNAHELIC MAGNEHELIC GAGES ACROSS EACH FILTER.
2. INTERNAL VIBRATION ISOLATION FOR EACH FAN. 10. UNIT TO BE SHIPPED IN SECTIONS FOR ASSEMBLY IN FIELD.
1. OTHER ACCEPTABLE MANUFACTURER'S: VA APPROVED EQUALS 9. COORDINATE LEFT HANDED/RIGHT HANDED COIL CONNECTIONS WITH DESIGN DRAWINGS AND EXISTING FIELD CONDITIONS.
NOTES:
70-AHPW-46 YORK XTI-102x102 PENTHOUSE L1 VAV 102 102 487 24,000 4,950 24,000 4.8 2.5 SWSI 1,800 7.3 10 3 460 85/69 55/54 44 56 0.50 426 1,153 6/10 WATER 6.1 190.0
MANUFACTURER MODEL H W L BHP HP PH VOLT
SUPPLY
CFM
TSP
(IN. WG)
ESP
(IN. WG)
TYPE FAN RPM
EACH MOTOR (TYP. 4)
EAT DB/WB
(°F)
LAT
DB/WB (°F)
EWT
(°F)
LWT
(°F)
AIR
P.D.
(IN)
AIR VELOCITY
(FPM)
TOTAL
MBH
ROWS/
FPI
FLUID
TYPE
WATER
PRESSURE
DROP
(FEET)
FLOW
(GPM)
EQUIPMENT TAG
BASIS OF DESIGN
LOCATION TYPE OF SYSTEM
APPROX. OVERALL
DIMENSIONS (IN.)
WEIGHT
(LBS)
MIN.
O.A.
SUPPLY FANS - FAN WALL (4 FANS TOTAL) CHW COOLING COIL
AIR HANDLING UNIT SCHEDULE
-20 55 30 2,860 2,727 0.08 30.0 2/10 24,000 1.7 1.5 SWSI 1,286 2.60 3.0 3 460 MERV 8 MERV 11 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 , 11, 12, 13, 14, AND 15
BHP HP PH VOLT
EAT
DB
(°F)
LAT
DB
(°F)
STEAM
PRESSURE
(PSI)
STEAM FLOW
(LBS/HR)
TOTAL
MBH
AIR
P.D.
(IN)
STEAM
PRESSURE
(PSI)
ROWS/
FPI
RETURN
CFM
TSP
(IN. WG)
ESP
(IN.)
TYPE FAN RPM
EACH MOTOR (TYP.-4)
STEAM…