Attachment 3 USFS Seeley Bunkhouse Drawing Set.pdf

PDF 37 MB Posted

Attached to
GAOA Seeley Lake Bunkhouse Remodel
Solicitation number
1240LU25R0030
Issued by

About this file

This file is a comprehensive architectural drawing set for the USFS Seeley Lake Bunkhouse Remodel project, located at 3583 HWY 83 N. Seeley Lake, Montana. The project involves a comprehensive renovation of an existing bunkhouse for Forest Service employees, with both base bid and eight optional bid items that can be selectively implemented. The remodel includes interior renovations on both the main and upper levels, such as bathroom and kitchen remodeling, bedroom construction, electrical and mechanical system updates, and limited exterior improvements.

Key renovation components include replacing electrical wiring and service, installing a new electric heating system, adding exterior envelope insulation, and replacing all interior plumbing. Optional items include wood floor refinishing, kitchen peninsula installation, casework and countertop additions, closet fit-outs, roof replacement, chimney exterior portion replacement, heat recovery ventilator installation, and window shade installation. The project is designed to restore the historic Seeley Bunkhouse to year-round serviceability for Forest Service employees, with a focus on maintaining the building's historical character while upgrading its functional systems. The architectural drawings were prepared by Mosaic Architecture, P.C. in Helena, Montana, with mechanical and electrical engineering by Morrison Maierle.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HW

Y 83

3 MILES TO SEELEY LAKE

24.4 M

ILES TO CONDON

VISITOR

CENTER

SEELEY BUNKHOUSE

NFOREST SERVICE CHECKLIST

RECOMMEDED BY:

Seeley Lake District Ranger Lolo National Forest

REVIEWED BY:

Forest Engineer Lolo National Forest

APPROVED BY:

Forest Supervisor Lolo National Forest

APPROVED BY:

Director of Engineering Northern Region

REVIEWED BY:

Regional Facilities Program Manager

DATE:

SHEET:

317 Cruse Ave. Suite 201 Helena, Montana 59601 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

3/ 4/

:0

0:

P M

3/01/2025

A000

COVER

SEELEY LAKE RANGER STATION

3583 HWY 83 N.

SEELEY LAKE, MT 59868

USFS SEELEY

BUNKHOUSE REMODEL

B

ID

S E

T

USFS SEELEY BUNKHOUSE REMODEL

SEELEY LAKE RANGER STATION

3583 HWY 83 N.

SEELEY LAKE, MT 59868

MOSAIC ARCHITECTURE, P.C.

317 N. CRUSE, STE 201

HELENA, MT 59601

CONTACT: GRETCHEN KRUMM, AIA

gretchen@mosaicarch.com

ARCHITECT:

MECHANICAL/PLUMBING ENGINEERING:

THESE DRAWINGS WERE PREPARED BY MOSAIC ARCHITECTURE, P.C. FOR CONSTRUCTION OF THE PROJECT DESCRIBED HEREIN. AS SUCH, THE DOCUMENTS ARE THE PROPERTY OF MOSAIC ARCHITECTURE, P.C. & MAY NOT BE REPRODUCED, COPIED OR USED IN ANY WAY WITHOUT PRIOR APPROVAL FROM MOSAIC ARCHITECTURE, P.C.

SHEET INDEX

PROJECT DIRECTORY

VICINITY MAP

ELECTRICAL ENGINEERING:

ARCHITECTURAL DRAWINGS

A000 COVER

A001 CODE INFORMATION

A002 GENERAL INFORMATION & ASSEMBLY TYPES

A101 SITE PLAN

A102 DEMOLITION PLANS

A103 FLOOR PLANS

A104 REFLECTED CEILING PLAN

A105 ROOF PLAN

A201 EXTERIOR ELEVATIONS

A301 BUILDING SECTIONS

A401 INTERIOR ELEVATIONS & ENLARGED PLANS

A501 DETAILS

A601 DOOR & WINDOW TYPES, DOOR SCHEDULE

A801 CASEWORK DETAILS

ELECTRICAL DRAWINGS

E001 ELECTRICAL SYMBOLS AND ABBREVIATIONS

E002 ELECTRICAL SPECIFICATIONS

E003 ELECTRICAL SPECIFICATIONS

E004 ELECTRICAL DETAILS

E005 ELECTRICAL SCHEDULES

E101 ELECTRICAL DEMO PLANS

E102 ELECTRICAL POWER AND SIGNAL PLANS

E103 ELECTRICAL LIGHTING PLANS

MECHANICAL DRAWINGS

M001 MECHANICAL LEGEND & NOTES

M002 MECHANICAL SPECIFICATIONS

M003 MECHANICAL SCHEDULES

M004 MECHANICAL DETAILS

M100 MECHANICAL DEMO PLANS

M101 MECHANICAL LEVEL 1 & 2 PLAN

M103 MECHANICAL ROOF PLAN

PLUMBING DRAWINGS

P001 PLUMBING LEGEND & NOTES

P002 PLUMBING SPECIFICATIONS

P003 PLUMBING SCHEDULES

P004 PLUMBING DETAILS

P100 PLUMBING DEMO PLANS

P101 PLUMBING LEVEL 1 & 2 PLAN

P102 PLUMBING ROOF PLAN

P103 PLUMBING ROOF PLAN

MORRISON MAIERLE

1 ENGINEERING PLACE

HELENA, MT 59602

CONTACT: LUKASH HOFF-PRUSS & JASON BEAUDETTE

lhoffpruss@m-m.net and jbeaudette@m-m.net

MORRISON MAIERLE

1 ENGINEERING PLACE

HELENA, MT 59602

CONTACT: TREVOR LARSON

tlarson@m-m.net

SUMMARY OF WORK:

SECOND LEVEL BEDROOM WINDOWS ARE TO BE REPLACED WITH CASEMENT WINDOWS THAT IMPROVE THE EMERGENCY EGRESS CLEARANCES AND REPLICATE THE LOOK OF THE HISTORIC DOUBLE-HUNG WINDOWS.

CODE REQUIREMENTS:

NO SPECIAL INSPECTIONS REQUIRED.

REQUIRED SPECIAL INSPECTIONS:

PROJECT MANAGER/PRIMARY CONTACT:

CATINA MCLEAN, US FOREST SERVICE,

CONTRACTING OFFICER REP. (C.O.R.)

24 FORT MISSOULA ROAD

MISSOULA, MT 59804

(406) 329-3861 catina.mclean@usda.gov

ALL COMMUNICATIONS TO BE DIRECTED TO

THE ABOVE C.O.R.

OPTION ITEM #1 REFINISH WOOD FLOORS

BASE BID:

• Existing wood floors in Room 102 Kitchen/Living and Room 103 Bunk Room remain as-is.

UNDER OPTION ITEM #1:

• Refinish existing wood floors on Level 1 in rooms with indicated floor finish of E-RF (Room 102 Kitchen/Living and Room 103

Bunk Room).

OPTION ITEM #2 KITCHEN PENINSULA

BASE BID:

• No peninsula provided or installed

UNDER OPTION ITEM #2:

• Provide casework and countertop as described and drawn in 3/A4001 and 21/A401.

OPTION ITEM #3 CASEWORK

BASE BID:

• No casework, countertop, S-1 sink, or mirror installed in Laundry Room 104.

• Install S-2 sink in Laundry Room 104.

• Install L-1 lavatory in Bathrooms 105 & 106.

• Shelving as indicated in Bathroom 204 not provided.

• Install L-1 lavatory in Circulation 201.

UNDER OPTION ITEM #3:

• Install casework shown in Laundry Room 104 including all cabinets, countertop, mirror, and install sink S-1 in lieu of S-2.

• Install vanities, solid countertops and L-2 undermount lavatories in lieu of L-1 lavatories in bathrooms 105 & 106 as shown.

• Install shelving in Bathroom 204 as shown.

• Install casework vanity and L-2 lavatory in lieu of L-1 in Circulation 201 as shown.

• Drawings show all option items

OPTION ITEM #4 CLOSET FIT-OUTS

BASE BID:

• No closet fit-out provided or installed.

UNDER OPTION ITEM #4:

• Provide and install bedroom closet fit-outs in Bedrooms 202 and 203 as detailed in 18/A401.

OPTION ITEM # 5 BUNKHOUSE ROOF

BASE BID: Existing roof remains in place as-is.

UNDER OPTION ITEM #5

• Demolish bunkhouse roof in entirety including underlayment and flashings

• Install ice and water shield material and underlayment

• Install roof eave, rake, ridge, sidewall and other detailed roof flashings and boots

• Install new metal roof complete as indicated in drawings

OPTION ITEM # 6 EXTERIOR PORTION OF CHIMNEY REPLACEMENT

BASE BID:

• Existing chimney remains in place as-is.

UNDER OPTION ITEM #6:

• Demolish exterior portion of brick chimney

• Rebuild exterior portion of brick chimney, and installation of chimney cap

OPTION ITEM # 7 HEAT RECOVERY VENTILATOR

BASE BID:

• Provide and install bath fans as shown on M101.

• Exhaust system includes Exhaust Fan equipment EF-1, EF-2, EF-3, exhaust air ductwork for each associated exhaust fan, and exhaust louver L-3

UNDER OPTION ITEM #7:

• Provide and install Heat Recovery Ventilator as shown on M101, in lieu of bath fans EF-1, EF-2, EF-3, including all associated ductwork up to and including exhaust louver L-3.

• HRV system includes Heat Recovery Ventilator equipment HRV-1, timeclock, outside air duct and louver L-1, relief air duct and louver L-2, supply air ductwork and three S-1 grilles, exhaust air ductwork and three E-1 grilles.

OPTION ITEM # 8 WINDOW SHADES

BASE BID:

• No window shades provided.

UNDER OPTION ITEM #8:

• Provide and install window shades as specified for every exterior window in rooms 102, 103, 202 & 203.

BID OPTION ITEMS SUMMARY:

THIS PROJECT WILL BRING THE HISTORIC SEELEY BUNKHOUSE BACK INTO SERVICEABILITY FOR YEAR-ROUND USE AS HOUSING FOR FOREST SERVICE EMPLOYEES. THE BULK OF THE WORK IS INTERIOR AND WILL INVOLVE REMODEL OF EXISTING MAIN LEVEL RESTROOMS AND KITCHEN AND THE CONSTRUCTION OF A NEW RESTROOM AND TWO BEDROOMS ON THE UPPER LEVEL. THE REMODEL ALSO INCLUDES THE ADDITION OF EXTERIOR ENVELOPE INSULATION, REPLACEMENT OF ALL ELECTRICAL WIRING AND SERVICE, A NEW ELECTRIC HEATING SYSTEM, AND ALL NEW INTERIOR

PLUMBING.

EXTERIOR WORK IS LIMITED TO REPLACEMENT OF THE BACK SCREEN DOOR, UPPER LEVEL WINDOW REPLACEMENT FOR EGRESS, EXTERIOR LIGHTING REPLACEMENT, PERIMETER GRAVEL, AND BID OPTION ITEMS FOR ROOFING

REPLACEMENT AND REPLACEMENT OF THE EXTERIOR PORTION OF THE CHIMNEY.

# DATE REVISION

UP

SS

SS

SS

SS

SS

CO

T T

T

T

T

T

T

DN

SS

SS

SS

CO

R-3

WORK AREA = 296sf

WORK AREA IS 30% OF

FLOOR AREA

304 SF

KITCHEN/LIVING

304 SF

BUNK RM.

101 SF

ENTRY

73 SF

BATHROOM

78 SF

LAUNDRY

MAXIMUM 4 OCCUPANTS

OCCUPANCY GROUPS:

(CHAPTER 3)

• R-3 - CONGREGATE LIVING FACILITY - NONTRANSIENT WITH

16 OR FEWER OCCUPANTS (MAXIMUM 8 PROPOSED)

CONSTRUCTION TYPE:

(TABLE 601)

TYPE VB, NON-SPRINKLERED

EXISTING FLOOR AREA: LEVEL 1:

LEVEL 2:

994 SF

700 SF

SEE CODE ANALYSIS PLANS THIS SHEET.

SUMMARY CODE REVIEW

PROJECT DESCRIPTION: REMODEL OF MAIN LEVEL BATHROOMS, REPLACEMENT OF KITCHEN CABINETS

AND COUNTERS, CONSTRUCTION OF TWO SEPARATE BUNK ROOMS AND NEW

BATHROOM ON SECOND LEVEL

APPLICABLE CODE: IEBC: EXISTING BUILDING CODE, CHAPTER 8

EXISTING FLOOR AREA TO REMAIN UNCHANGED. NO ADDITIONS PROPOSED.

IEBC CHAPTER 8 - WORK AREA

COMPLIANCE METHOD - LEVEL 2:

PROJECT SCOPE FITS WITHIN THE DEFINITION OF LEVEL 2 ALTERATIONS AND

THE COMPLIANCE METHOD SELECTED IS THE WORK AREA METHOD.

ACCESSIBILITY GROUP R-3:

1108.6.3

FACILITY PROVIDES ONLY 3 SLEEPING UNITS WITHIN A CONGREGATE LIVING

FACILITY. NO ACCESSIBLE OR TYPE B UNITS REQUIRED.

IEBC CHAPTER 3 - GENERAL

PROVISIONS:

SECTION 306 ACCESSIBILITY

A FACILITY THAT IS ALTERED SHALL COMPLY WITH THE APPLICABLE

PROVISIONS OF CHAPTER 11 OF THE IBC.

IEBC CHAPTER 3 - GENERAL

PROVISIONS:

307.1 SMOKE ALARMS

WHERE AN ALTERATION IS MADE TO AN EXISTING BUILDING OF GROUP R, THE

EXISTING BUILDING SHALL BE PROVIDED WITH SMOKE ALARMS IN

ACCORDANCE WITH IFC OR R314.

IEBC CHAPTER 3 - GENERAL

PROVISIONS:

308.1 CARBON MONOXIDE DETECTION

WHERE AN ALTERATION IS MADE TO AN EXISTING BUILDING OF GROUP R, THE

EXISTING BUILDING SHALL BE PROVIDED WITH CARBON MONOXIDE DETECTION

IN ACCORDANCE WITH IFC OR R315.

EXCEPTION: INSTALLATION OF PLUMBING OR MECHANICAL SYSTEMS, OTHER

THAN FUEL-BURNING APPLIANCES. NO FUEL-BURNING APPLIANCES PROPOSED.

IEBC CHAPTER 8 - LEVEL 2:

801.2

LEVEL 2 COMPLIANCE: ALL WORK SHALL COMPLY WITH CHAPTER 7 REQUIREMENTS.

702.1: INTERIOR FINISHES MUST COMPLY WITH IBC CHAPTER 8

702.4: IN GROUP R-3 BUILDINGS, WINDOW OPENING CONTROL DEVICES OR FALL

PREVENTION DEVICES COMPLYING WITH ASTM F2090 SHALL BE INSTALLED WHERE AN

EXISTING WINDOW IS REPLACED.

* THIS APPLIES TO WINDOW REPLACEMENTS FOR EGRESS ON THE SECOND LEVEL.

702.5: REPLACEMENT WINDOW FOR EMERGENCY ESCAPE AND RESCUE OPENINGS.

WHERE WINDOWS ARE REQUIRED TO PROVIDE EMERGENCY ESCAPE AND RESCUE

OPENINGS IN GROUP R-3 OCCUPANCIES, REPLACEMENT WINDOWS SHALL BE EXEMPT

FROM THE REQUIREMENTS OF SECTION 1031.3 OF THE IBC PROVIDED THE WINDOW

MEETS THE FOLLOWING:

1. THE REPLACEMENT WINDOW IS THE MANUFACTURER'S LARGEST STANDARD

SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING ROUGH OPENING. THE

REPLACEMENT IS PERMITTED TO BE OF THE SAME OPERATING STYLE AS

THE EXISTING OR A STYLE THAT PROVIDES FOR AN EQUAL OR GREATER

WINDOW OPENING AREA THAN THE EXISTING.

703: ALTERATIONS SHALL BE DONE IN A MANNER THAT MAINTAINS THE LEVEL OF FIRE

PROTECTION PROVIDED:

* ALL NEW WORK MEETS OR EXCEEDS THE EXISTING LEVEL OF FIRE PROTECTION.

704: ALTERATIONS SHALL BE DONE IN A MANNER THAT MAINTAINS THE LEVEL OF

PROTECTION PROVIDED FOR THE MEANS OF EGRESS.

* ALL NEW WORK MEETS OR EXCEEDS THE EXISTING LEVEL OF PROTECTION

PROVIDED FOR THE MEANS OF EGRESS.

705: REROOFING

MATERIALS AND METHODS OF APPLICAITON USED FOR REPLACING AN EXISTING ROOF

COVERING SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 15 OF THE IBC.

* REROOFING ALTERNATIVE SHALL COMPLY.

706: STRUCTURAL

REPLACEMENT OF ROOFING:

ANY EXISTING GRAVITY LOAD-CARRYING STRUCTURAL ELEMENT FOR WHICH AN

ALTERATION CAUSES AN INCREASE IN DESIGN DEAD, LIVE OR SNOW LOAD, INCLUDING

SNOW DRIFT EFFECTS, OF MORE THAN 5% SHALL BE REPLACED OR ALTERED AS NEEDED

TO CARRY THE GRAVITY LOADS REQUIRED BY THE IBC.

1. EXCEPTION: BUILDINGS OF GROUP R OCCUPANCY WITH NOT MORE THAN 5

SLEEPING UNITS WHERE THE ALTERED BUILDING COMPLIES WITH THE

CONVENTIONAL LIGHT-FRAME CONSTRUCTION METHODS OF THE IBC OR IRC.

708: ENERGY CONSERVATION

LEVEL 1 ALTERATIONS DO NOT REQUIRE THE ENTIRE BUILDING TO COMPLY WITH THE

IECC.

IEBC CHAPTER 8 - WORK AREA

COMPLIANCE METHOD - LEVEL 2:

801.4 NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND SPACES

SHALL COMPLY WITH THE REQUIREMENTS OF THE IBC.

EXCEPTIONS THAT MAY APPLY TO THIS PROJECT:

1. LIGHT & VENTILATION REQUIREMENTS OF WINDOWS

2. ELECTRICAL EQUIP. SHALL COMPLY WITH 806.

3. MINIMUM CEILING HEIGHT OF NEWLY CREATED HABITABLE AND

OCCUPIABLE SPACES AND CORRIDORS SHALL BE 7'.

802.1 REQUIREMENTS OF THIS SECTION ARE LIMITED TO WORK AREAS IN

WHICH LEVEL 2 ALTERATIONS ARE BEING PERFORMED AND SHALL APPLY

BEYOND WHERE SPECIFIED.

APPLICABLE PROVISIONS OF 802.

1. INTERIOR FINISH AND TRIM OF WALLS AND CEILINGS IN EXITS AND

CORRIDORS IN ANY WORK AREA SHALL COMPLY WITH THE IBC.

803 FIRE PROTECTION: REQUIREMENTS OF THIS SECTION ARE LIMITED TO

WORK AREAS IN WHICH LEVEL 2 ALTERATIONS ARE BEING PERFORMED AND

WHERE SPECIFIED SHALL APPLY THROUGHT THE FLOOR ON WHICH THE WORK

AREA IS LOCATED.

803.2.2 AUTOMATIC SPRINKLER SYSTEMS NOT REQUIRED IN R-3 OCCUPANCY.

804 MEANS OF EGRESS

IBC 1006.3.4 SINGLE EXITS

GROUP R-3 OCCUPANCIES SHALL BE PERMITTED TO HAVE ONE EXIT OR

ACCESS TO A SINGLE EXIT.

806 ELECTRICAL

806.1 NEWLY INSTALLED ELECTRICAL EQUIP AND WIRING RELATING TO WORK IN

ANY WORK AREA SHALL COMPLY WITH NFPA 70 EXCEPT AS PROVIDED FOR IN

SECTION 806.4.

806.4 RESIDENTIAL OCCUPANCIES

IN GROUP R-3 AND BUILDINGS REGULATED BY THE IBC:

1. ENCLOSED AREAS, OTHER THAN CLOSETS, KITCHENS, BASEMENTS,

GARAGES, HALLWAYS, LAUNDRY AREAS, UTILITY AREAS AND

BATHROOMS SHALL HAVE NOT FEWER THAN TWO DUPLEX

RECEPTACLE OUTLETS OR ONE DUPLEX RECEPTACLE OUTLET AND

ONE CEILING OR WALL-TYPE LIGHTING OUTLET.

2. KITCHENS SHALL HAVE NOT FEWER THAN 2 DUPLEX RECEPTACLE

OUTLETS

3. LAUNDRY AREAS SHALL HAVE NOT FEWER THAN 1 DUPLEX

RECEPTACLE OUTLET

4. NEWLY INSTALLED RECEPTACLE OUTLETS SHALL BE PROVIDED WITH

GROUND FAULT CIRCUIT INTERRUPTION BY NFPA 70

5. NOT FEWER THAN 1 LIGHTING OUTLET SHALL BE PROVIDED IN EVERY

BATHROOM, HALLWAY, STAIRWAY WITH ELECTRIC POWER AND TO

ILLUMINATE OUTDOOR ENTRANCES AND EXITS.

6. CLEARANCE FOR SERVICE EQUIPMENT SHALL BE PROVIDED IN

ACCORDANCE WITH NFPA 70.

* IT IS THE INTENT OF THIS PROJECT THAT ALL NEW ELECTRICAL EQUIPMENT

WILL MEET CURRENT IBC CODE REQUIREMENTS.

807 MECHANICAL

807.1 RECONFIGURED SPACES SHALL BE PROVIDED WITH NATURAL OR

MECHANICAL VENTILATION IN ACCORDANCE WITH IMC.

809 ENERGY CONSERVATION

LEVEL 2 ALTERATIONS TO EXISTING BUILDINGS ARE PERMITTED WITHOUT

REQUIRING THE ENTIRE BUILDING TO COMPLY WITH THE IECC. THE

ALTERATIONS SHALL CONFORM TO THE IECC AS THEY RELATE TO NEW

CONSTRUCTION ONLY.

* WHERE FEASIBLE, EXISTING WALL AND ROOF CAVITIES WILL BE INSULATED AS

A PART OF THIS PROJECT.

IEBC CHAPTER 8 - WORK AREA

COMPLIANCE METHOD - LEVEL 2

CONTINUED:

* SECOND LEVEL BEDROOM WINDOWS WILL BE REPLACED WITH CASEMENT

WINDOWS THAT IMPROVE THE EMERGENCY EGRESS CLEARANCES AND

REPLICATE THE LOOK OF THE HISTORIC DOUBLE-HUNGS.

THIS PROJECT SHALL COMPLY WITH THE LATEST EDITION OF PUBLISHED CODES ADOPTED BY

THE STATE OF MONTANA:

2021 International Existing Building Code (IEBC) 2021 International Building Code (IBC) 2021 International Mechanical Code (IMC) 2021 International Fuel Gas Code (IFGC) 2021 Uniform Plumbing Code (IAMPO) 2021 National Electrical Code (NEC) 2021 International Fire Code (IFC) 2021 International Energy Conservation Code (IECC)

APPLICABLE BUILDING CODES

201 SF

BEDROOM

222 SF

BEDROOM

76 SF

BATHROOM

WORK AREA = 253sf

WORK AREA IS 36% OF

FLOOR AREA

167 SF

CIRCULATION

REPLACMENT WINDOW REPLACMENT WINDOW

MAXIMUM 2 OCCUPANTS MAXIMUM 2 OCCUPANTS

DATE:

SHEET:

317 Cruse Ave. Suite 201 Helena, Montana 59601 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

3/ 4/

:0

0:

P M

3/01/2025

A001

CODE INFORMATION

SEELEY LAKE RANGER STATION

3583 HWY 83 N.

SEELEY LAKE, MT 59868

USFS SEELEY

BUNKHOUSE REMODEL

B

ID

S E

T

1/4" = 1'-0"

LEVEL 1 CODE PLAN

N

1/4" = 1'-0"

LEVEL 2 CODE PLAN

@ at A.B. anchor bolt A/C air conditioning ACC PNL access panel ACOUST acoustical ACT acoustical ceiling tile AD area drain ADJ adjacent AFF above finished floor AIB air infiltration barrier ALT alternate ALUM aluminum ANOD anodized APPROX approximate

ARCH CONTRACTING

OFFICER

AUTO automatic BBD bulletin board BD board BITUM bituminuous BL building line BLDG building BLK block BLKG blocking BM beam/bench mark BO by CONTRACTING

OFFICER

B.O. bottom of BOT bottom BRG bearing BSBD baseboard BTWN between B.O.W. bottom of wall BU built up CAB cabinet CAP capacity CB catch basin CL centerline C.C. center to center CDX exterior grade plywood CG corner guard CH channel CI cast iron/cubic inches CJ control joint CLG ceiling C.L.L. contract limit line CL center line

ABBREVIATIONS:

GA gauge GB grab bar GALV galvanized G.C. general contractor GEN general GFRG glass fiber reinforced gypsum GI galvanized iron GL glass GLU LAM or G.L.B. glue laminated beam GRD grade/grid GWB gypsum wall board GYP gypsum HB hose bib HC hollow core/handicapped HD BD Hard board HDR header HOR horizontal HR hour HT height HTG heating HVAC heating, ventilation, air conditioning HW hot water

PART.BD. particle board PART’N partition PC precast concrete PFM prefinished metal PL plate P.LAM plastic laminate PLWD plywood PNL panel PR pair PSL parallel strand lumber PT point PTD paper towel dispenser

T tread/thermostat TB towel bar TEL telephone TEMP temperature T&G tongue and groove THK thick THRU through TJI Truss Joist Incorporated

CLR clear CMU concrete masonry unit CO clean out COL column CONC concrete COND condition CONF conference CONN connection CONST construction CTRD centered CONT continuous CONTR contractor CORR corridor CPT carpet CT ceramic tile CUH cabinet unit heater CW curtain wall system CY cubic yard DBL double DEPT department DF drinking fountain DIA diameter DIAG diagonal DIM dimension DISP dispenser DN down DR door DWR drawer DS downspout DTL detail DWG drawing E east EA each EIFS exterior insulation finish system E.J. expansion joint EL/ELEV elevation - height/elevator ELEC electrical ENCL enclosure EO electrical outlet EP electrical panel EQ equal EQUIP equipment EWA/EW exterior wall assembly EWC electrical water cooler EWH electrical water heater (E)/EXIST existing EXH exhaust EXP expansion EXT exterior

IN inch INCL included INFO information INSUL insulation INT interior IWA/IW interior wall assembly

T.O. top of T.O.B. top of beam T.O.C. top of concrete T.O.P. top of plate T.O. FTG top of footing T.O.S. top of steel T.O.SL. top of slab T.O.W. top of wall TPD toilet paper dispenser TR tread TS tubular steel TV television TYP typical UG underground UNO unless noted otherwise UR urinal VAC vacuum outlet VAR varies VB vapor barrier VCT vinyl composition tile VERT vertical VEST vestibule VFY verify VT vinyl tile VWC vinyl wall covering W west/women/width W/ with W/O without WC water closet WD wood W/D washer/dryer WH water heater WNDW window WP waterproof WR water resistant WRB weather resistive barrier WT weight WWF welded wire fabric WWM welded wire mesh X by YD yard

REINF reinforcing REQD required RES resilient RM room RO rough opening RV roof vent R&S rod and shelf S south SACT suspended acoustical ceiling tile SC solid core SCD seat cover dispenser SCHED schedule SD soap dispenser SECT section SF square feet SGL single SHT sheet SHTG sheathing SHWR shower SIM. similar S.I.P. structural insulated panel SLNT sealant SOG slab on grade SPEC specifications S.S. stainless steel SS service sink SSM solid surface material STD standard STF storefront STL steel STOR storage STRUCT structural SUBFLR subfloor SUSP suspended SV sheet vinyl SY square yard

M men's MAT material MAX maximum MECH mechanical MDF medium density fiber board MEMB membrane MEZZ mezzanine MFR manufacturer MH manhole MIN minimum MIR mirror MISC miscellaneous MO masonry opening MTL metal MULL mullion N north NA not applicable NIC not in contract NO number NTS not to scale

OFCI CONTRACTING OFFICER

furnished/contractor installed OC on center OD outside diameter OH overhead/opposite hand OPNG opening OPP opposite

FLR/FL floor FLUOR fluorescent FND feminine napkin dispenser/disposal FOC face of concrete FOF face of finish FOS face of stud FOW face of wall FT foot or feet FTG footing

QTY quantity R/RAD radius R riser RA roof/ceiling assembly RB rubber base RD roof drain RE regarding REF reference/refrigerator

JAN janitor JST joist JT joint LAV lavatory LF lineal foot LTG lighting

FA fire alarm/floor-ceiling assembly FAH fire alarm horn FAS fire alarm station FD floor drain FDN/FND foundation FE fire extinguisher FEC fire extinguisher cabinet FF finished floor FFHB frost free hose bib FG finish grade FH fire hydrant FIN. FLR top of floor sheathing FIN finish FIXT fixture F.O. face of

PTD/R paper towel dispenser/receptacle PVMT pavement PVC polyvinylchloride

1. REFER TO SPECIFICATIONS FOR ADDITIONAL DESCRIPTIONS & REQUIREMENTS OF

CONSTRUCTION.

2. GENERAL CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES, PROVIDE ON-SITE

SUPERVISION & BE RESPONSIBLE FOR COMPLIANCE WITH ALL SAFETY PRECAUTIONS, CODES

AND REGULATIONS.

3. PROTECT EXISTING UTILITIES. SITE IMPROVEMENTS & PLANTING TO REMAIN U.N.O.

4. PATCH ANY SURFACES DAMAGED DURING CONSTRUCTION. SURFACES ARE TO BE PATCHED

FLUSH WITH EXISTING. MATCH EXISTING ADJACENT FINISH OR APPLY NEW FINISH AS

SCHEDULED.

5. PROVIDE SOLID BACKING FOR ALL WALL-MOUNTED ITEMS.

6. IN GENERAL, REPETITIVE DETAILS DRAWN ARE SHOWN IN FULL ONLY ONCE. REPETITIONS

MAY NOT BE COMPLETE IN EVERY DETAIL AS SHOWN IN THE ORIGINAL DETAIL.

7. DIMENSIONS ARE SHOWN ON THE DRAWINGS. DO NOT SCALE THE DRAWINGS.

8. ALL HEIGHTS ARE DIMENSIONED FROM THE TOP OF SUBFLOOR OR SLAB UNLESS NOTED

OTHERWISE.

9. WHERE COLUMNS & STUD WALLS ALIGN, GYPSUM BOARD TO BE CONTINUOUS OVER

COLUMNS OR BOXED AROUND COLUMN IF COLUMN PROJECTS BEYOND WALL.

10. BRING TO THE ATTENTION OF THE CONTRACTING OFFICER ANY CONDITION OR AREA OF

FINISH THAT IS IN QUESTION OR NOT NOTED.

11. SEAL ALL PENETRATIONS OF WALLS, FLOORS AND CEILINGS WITH A FIRE RATING EQUIVALENT

TO THE CONSTRUCTION PENETRATED AND PER DETAILS & SPECIFICATIONS.

12. DUST BARRIERS MUST BE INSTALLED WHEREVER NEW WORK IS ADJACENT TO OCCUPIED

AREAS. BARRIERS MUST BE SEALED TO INSURE NO DUST TRANSMISSION TO OCCUPIED

SPACES.

13. HEATING, PLUMBING AND ELECTRICAL PLANS WHERE SHOWN DIAGRAMMATICALLY ARE

INTENDED TO INDICATE CAPACITY, SIZE, LOCATION & GENERAL ARRANGEMENTS. ALL

NECESSARY FEATURES OF RELATED CONSTRUCTION WILL BE REQUIRED AS IF SHOWN IN

DETAIL.

14. WHERE MECHANICAL & ELECTRICAL EQUIPMENT LOCATIONS CONFLICT, ELECTRICAL LIGHT

FIXTURE LOCATIONS SHALL TAKE PRECEDENCE.

15. PROVIDE ALL NEW MATERIALS (U.N.O.) AND QUALIFIED CRAFT PERSONS TO COMPLETE THE

WORK.

16. CONSTRUCTION DOCUMENTS SHOW THE DESIGN INTENT OF THE PROJECT AND MAY NOT

SHOW MINOR DETAILS OF PROPOSED INSTALLATIONS. THE INCLUSION OF THESE MINOR

DETAILS IS IMPLIED TO PROVIDE A COMPLETE PROJECT AND ARE TO BE INCLUDED AS A PART

OF A BID.

17. IN THE CASE OF CONTRADICTIONS BETWEEN DRAWINGS OR BETWEEN DRAWINGS &

SPECIFICATIONS, ASSUME THE MORE COSTLY APPROACH FOR BIDDING PURPOSES. BRING

ALL CONTRADICTIONS TO THE ATTENTION OF THE CONTRACTING OFFICER.

18. CONTRACTOR SHALL PROMPTLY REMOVE ALL WASTE MATERIALS AND LEAVE PREMISES AND

SITE CLEAN.

19. THE CONTRACTOR SHALL PROVIDE ALL CEILING AND/OR WALL ACCESS PANELS/DOORS AS

REQUIRED BY THE AIR CONDITIONING, PLUMBING & ELECTRICAL SYSTEMS, PROVIDE

APPROVED ASSEMBLIES W/ SELF-CLOSING DEVICES IN RATED CONSTRUCTION. (PAINT TO

MATCH ADJACENT WALL COLOR)

20. ELECTRICAL OUTLETS AND LIGHTING ARE ONLY SHOWN ON ARCHITECTURAL "A" SHEETS

WHERE PLACEMENT OF SUCH IS CRITICAL TO PARTICULAR AESTHSTICS. SEE ELECTRICAL

DRAWINGS FOR ALL ELECTRICAL AND DATA FEATURES.

DRAWING SET NOTE: THESE DRAWINGS ARE TO BE UTILIZED AS A COMPLETE SET FOR BIDDING & CONSTRUCTION. INDIVIDUAL SECTIONS OF DRAWINGS SHOULD NOT BE SEPARATED FROM THE ENTIRE

SET. IMPORTANT NOTES FOR ONE AREA OF WORK MAY BE INCLUDED IN OTHER AREAS IN THE

DRAWINGS. ALL CONTRACTORS & SUPPLIERS MUST REVIEW ENTIRE DRAWING SET & SPECIFICATIONS.

GENERAL NOTES:

GENERAL WALL NOTES

1. WALL TYPE CONSTRUCTION IS CONTINUOUS FROM SLAB OR FLOOR TO ROOF OR CEILING

FRAMING ABOVE UNLESS INDICATED OTHERWISE.

2. IF A WALL TYPE IS NOT INDICATED, PROVIDE WALL TYPE OF MOST SIMILAR CONDITION -

VERIFY WITH CONTRACTING OFFICER.

3. IN CASES OF CONFLICT BETWEEN SECTIONS AND WALL TYPES, CLARIFY WITH CONTRACTING

OFFICER PRIOR TO BIDDING WHEN TIME ALLOWS, OTHERWISE ASSUME THE MOST

EXPENSIVE CONDITION FOR BIDDING PURPOSES.

4. STRUCTURAL NOTES, SPECIFICATIONS, STUD GAUGE NOTATIONS ETC. TAKE PRECEDENCE

OVER ARCHITECTURAL WALL TYPES.

5. TYPE "X" GYPSUM WALL BOARD SPECIFIED THROUGHOUT. PROVIDE WATER-RESISTANT

TYPE "X" GYPSUM BOARD ON ENTIRE WALL WHERE PLUMBING FIXTURES OCCUR. PROVIDE

TILE BACKER BOARD TYPE "X" ON ALL WALLS WITH TILE.

6. PROVIDE BACKER ROD & CAULKING JOINT AT ABUTMENT OF ALL DISSIMILAR MATERIALS.

7. PROVIDE STEEL "J" EDGE METAL AND 1/4" CAULK JOINT AT PERIMETER OF ALL GYPSUM

BOARD WALLS WHERE ABUTTING DIFFERENT MATERIALS.

8. PROVIDE CORNER BEADS AT ALL EXTERNAL GYPSUM BOARD CORNERS.

SCALE

BUILDING SECTIONS

WALL SECTIONS

EXTERIOR ELEVATION

DETAIL CALLOUT

INTERIOR ELEVATION

DOOR NUMBER

WINDOW TYPE

ROOM NAME, NUMBER, AND

AREA

GRID LINES:

LETTERS LEFT TO RIGHT

NUMBERS TOP TO BOTTOM

WALL TYPE

ELEVATION TAG, FLOOR = 100' - 0"

REFERENCE SYMBOLS:

DRAWING TITLE

STOREFRONT/CURTAINWALL

CALLOUT

TEXT INDICATES STOREFRONT

SYSTEM:

iSF = INTERIOR STOREFRONT

SF = EXTERIOR STOREFRONT

CW = CURTAINWALL

FIRE EXTINGUISHER, SEE CODE

PLANS

SHEET

NUMBER

DRAWING

NUMBER

SHEET

NUMBER

DRAWING

NUMBER

SHEET NUMBER

DRAWING

NUMBER

SHEET NUMBER

DRAWING

NUMBER

SHEET NUMBER

DRAWING NUMBER

FE

WITH CABINET

WALL-HUNG, NO

CABINET

ROOF TYPE

-SEE ELEVATIONS FOR HEIGHTS

"SIM" INDICATES SIMILAR

CONDITION; SEE NOTES

FLOOR TYPE

A7-14

A3-8

A5-2

VIEW NAME

1/8" = 1'-0"

A

Room name

A

101A

A1-1

A1-1

FA1

Name

Elevation

RA1

SIM

cw1 i1

EXISTING WD FINISH

TO REMAIN

EXISTING STUDS OF UNKNOWN

DEPTH, ASSUME 2X6 FOR

BIDDING

NEW 5/8" GYPSUM

BOARD TYPE X

NEW ACOUSTICAL

BATT INSULATION TO

FILL VOIDS

i1

5/8" GYPSUM BOARD

TYPE X

2X6 WD STUDS @

16" OC

5/8" GYPSUM BOARD

TYPE X

NOTE: SEE ELEVATIONS AND FINISH SCHEDULES FOR

WALL FINISHES, TYPICAL ALL WALL TYPES

5 1/2" ACOUSTICAL

BATT INSULATION

5/8" GYPSUM

BOARD TYPE X

2X4 WD STUDS

@ 16" O.C.

INTERIOR WALL TYPES

INTERIOR PARTITION

i3

INTERIOR PARTITION

i6

INTERIOR FURRED PARTITION

EXISTING PARTITION WITH NEW

FINISH ON ONE SIDE

NON-RATED SOUND WALL

NON-RATED

5/8" GYPSUM

BOARD TYPE X

2X4 WD STUDS @

16" O.C.

5/8" GYPSUM

BOARD TYPE X

i4

5/8" GYPSUM

BOARD TYPE X

2X6 WD STUDS

@ 16" OC

5/8" GYPSUM

BOARD TYPE X

INTERIOR PARTITION

i5

INTERIOR PARTITION

NON-RATED NON-RATED

KITCHEN/

BUNKROOM

SIDE

BATHROOM

SIDE

SEE INT. ELEVATIONS FOR

LOCATIONS OF WAINSCOT

NEW 5/8" GYPSUM

BOARD TYPE X

NEW ACOUSTICAL

BATT INSULATION TO

FILL VOIDS

i2

INTERIOR PARTITION

NON-RATED SOUND WALL

SEE INT. ELEVATIONS FOR

LOCATIONS OF WAINSCOT

2X4 WD STUDS @

16" O.C.

5/8" GYPSUM

BOARD TYPE X

SEE INT. ELEVATIONS FOR

LOCATIONS OF WAINSCOT

5/8" GYPSUM

BOARD TYPE X

2X6 WD STUDS

@ 16" O.C.

i7

INTERIOR FURRED PARTITION

NON-RATED

e1

NOTE: SEE STRUCTURAL FOR ADDITIONAL

INFORMATION FOR ALL WALL TYPESEXTERIOR WALL TYPES

EXTERIOR WALL - NON RATED

INTERIOR EXTERIOR

EXISTING LOG CABIN SIDING

EXISTING 2X4 WOOD STUDS

EXISTING 1"X8" SHIPLAP (DIAGONAL)

EXISTING VERTICAL WOOD

PANELING

EXISTING TAR PAPER

NEW BLOWN-IN CELLULOSE IN EVERY

ACCESSIBLE STRUCTURAL BAY

(APPROX. R-12)

ROOF/CEILING ASSEMBLIES

EXISTING 2X6 RAFTERS @

16" O.C.

EXISTING 2X COLLAR TIES

NEW 5/8" GWB CEILING - PAINT

NEW CLOSED-CELL SPRAY

FOAM IN ALL RAFTER BAYS

EXISTING 1X8 SHIPLAP

NEW UNDERLAYMENT OR ICE &

WATER SHIELD (SEE ROOF PLAN)

NEW METAL ROOFING, SEE SPECS

ROOFING REPLACEMENT ON THIS PROJECT IS A BID OPTION. INCLUDES

THE UNDERLAYMENT & METAL ROOFING PORTIONS OF THIS ASSEMBLY

ONLY. SPRAY FOAM AND GWB CEILINGS SHALL BE INCLUDED IN THE BASE

BID.

ROOF/CEILING ASSEMBLY

RA1

FLOOR/CEILING ASSEMBLIES

EXISTING 2X8 FLOOR JOISTS

AT 16" O.C.

NEW 5/8" TYPE 'X' GWB - PAINT

FLOOR/CEILING ASSEMBLY

FC1

EXISTING 8" SHIPLAP

EXISTING 1X4 WOOD FLOORING

LEVEL 2 FLOOR ASSEMBLY

NEW LVT FLOORING

[EXIST] RIM BOARD

2" (2) LAYERS ALUMINUM FACED BOARD INSULATION

ADHERE WITH CONSTRUCTION ADHESIVE @ RIM BOARD

REMOVAL OF 12"- 18" CRAWL SPACE DIRT BY

VACCUM TRUCK - NOT TO EXCEED T.O. FTG.

2" ALUMINUM FACED BOARD INSULATION; ADHERE TO

FOUNDATION WALL W/ CONSTRUCTION ADHESIVE, TAPE &

SEAL JOINTS

MIN. 6 MIL REINFORCED VAPOR BARRIER,

TAPE SEAL TO FOUNDATION WALL

[EXIST] FOUNDATION WALL

[EXISTING] WALL

FOAM SEALANT TO SEAL GAPS & CRACKS

[EXISTING] FOOTING

e2

EXTERIOR, FOUNDATION WALL

- NON RATED

INTERIOR EXTERIOR

[EXIST] SIDING

OILED OAKUM #50 SUPER GOLDEN @ GAPS & PEST ACCESS POINTS

16" O.C.

NEW LVT FLOORING

[NEW] PLYWOOD SUBFLOOR. DEPTH TO

MATCH EXISTING (3/4" DEPTH PRESUMED

FOR BIDDING PURPOSES - FIELD VERIFY)

[EXIST] FLOOR JOISTS @ 16" O.C.

FL1

SUB-FLOOR ASSEMBLY NEW PLYWOOD UNDERLAYMENT TO BRING LVT

FLOORING FLUSH WITH EXISTING WOOD

FLOORING (1/2" DEPTH PRESUMED FOR BIDDING

PURPOSES - FIELD VERIFY)

LEVEL 1 FLOOR SYSTEM WHERE SUBFLOOR IS INDICATED TO BE

REMOVED AND REPLACED

DATE:

SHEET:

317 Cruse Ave. Suite 201 Helena, Montana 59601 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

3/ 5/

1:

:1

A

M

3/01/2025

A002

GENERAL INFORMATION &

ASSEMBLY TYPES

SEELEY LAKE RANGER STATION

3583 HWY 83 N.

SEELEY LAKE, MT 59868

USFS SEELEY

BUNKHOUSE REMODEL

B I D

S E

T

1. DETERMINE LOCATION OF ALL UNDERGROUND UTILITIES PRIOR TO

DEMO, EXCAVATION OR PLANTING. MAINTAIN 10' MIN DISTANCE FROM

ALL TREES TO UTILITY LINES.

2. PROTECT ALL EXISTING ITEMS/SURFACES TO REMAIN. EXISTING

ELEMENTS DAMAGED DURING CONSTRUCTION TO BE REPAIRED OR

REPLACED BY CONTRACTOR AS DIRECTED BY THE CONTRACTING

OFFICER AT NO COST TO CONTRACTING OFFICER.

3. PROTECT EXISTING TREES WITH TEMPORARY CONSTRUCTION FENCE

LOCATED 3 FEET OUTSIDE DRIP LINE, PROTECT OVERHANGING LIMBS

FROM DAMAGE AS REQUIRED.

GENERAL SITE PLAN NOTES

NEW CONSTRUCTION

EXISTING ELEMENTS TO REMAIN

LINEWORK LEGEND

A

B

2' GRAVEL PERIMETER

AROUND FOUNDATION

EXISTING STRUCTURE

UTILITY POLE

OPTION ITEM;

STANDING SEAM METAL ROOF

OVERHEAD LINE

A101

FOREST SERVICE ROAD 598

FOREST SERVICE ROAD 598-E

40' - 0"

40' - 0"

C O

N S

TR

U

C

TI

O N

L

IM

IT

L

IN

E

C O

N S

TR

U

C

TI

O N

L

IM

IT

L

IN

E

CONSTRUCTION LIMIT LINE

3" LAYER OF STONE MULCH

WEED BARRIER FABRIC

8" STAPLES TO ANCHOR WEED BARRIER TRIANGLAR SPACING

36" O.C. & 12" O.C. LINEAR SPACING AT JOINTS.

CORTEN EDGING, INSTALL

ACCORDING TO MFGR.S SPECS.

2 FOOT GRAVEL STRIP

DATE:

SHEET:

317 Cruse Ave. Suite 201 Helena, Montana 59601 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

3/ 4/

:0

0:

P M

3/01/2025

A101

SITE PLAN

SEELEY LAKE RANGER STATION

3583 HWY 83 N.

SEELEY LAKE, MT 59868

USFS SEELEY

BUNKHOUSE REMODEL

B

ID

S E

T

1/16" = 1'-0"

SITE PLAN

N

1 1/2" = 1'-0"

MOW STRIP

DN

A

B

8 8 8

4 10

14 14

15 15 15 15

DEMOLITION KEYNOTES

NOTE: SEE MECH/ELEC/STRUCT AND CIVIL DRAWINGS FOR ADDITIONAL DEMOLITION

INFORMATION.

REMOVE EXISTING INTERIOR WALL COMPLETELY, INCLUDING BRACING ABOVE CEILING

WHERE OCCURS. REPAIR ALL ADJACENT SURFACES TO RECEIVE NEW FINISHES.

REMOVE WINDOW & PREPARE ROUGH OPENING FOR INSTALLATION OF NEW WINDOW.

MUST DISPOSE OF PROPERLY, (SEE HAZARDOUS TESTING RESULTS AND ABATEMENT

SCOPE.)

REMOVE FIBERBOARD CEILING THROUGHOUT THIS ROOM. REMOVE ALL ASSOCIATED

LIGHT FIXTURES, SMOKE DETECTORS, DIFFUSERS AND RETURN GRILLES. MUST

DISPOSE OF PROPERLY, (SEE HAZARDOUS TESTING AND ABATEMENT SCOPE.)

REMOVE ALL WALL FINISHES THIS SIDE OF WALL, EXPOSING THE EXISTING FRAMING.

REMOVE EXISTING FLOORING AND SUBFLOORING IN HATCHED AREA TO PREPARE FOR

INSTALLATION OF PLUMBING, INSULATION AND VAPOR BARRIER IN CRAWLSPACE. SAME

AREA TO HAVE REPLACEMENT SUBFLOOR INSTALLED IN ACCORDANCE WITH ASSEMBLY

FL-1.

REMOVE ALL EXISTING CASEWORK, COUNTERTOPS & APPLIANCES IN KITCHEN.

REMOVE EXISTING TOILET PARTITION AND RELATED COMPONENTS.

REMOVE EXISTING PLUMBING FIXTURE & RELATED COMPONENTS.

REMOVE EXISTING HVAC EQUIPMENT & RELATED COMPONENTS.

REMOVE TRANSFER GRILLE FROM WALL, CLEAN, INFILL OPENING WITH FRAMING AND

PAINTED DRYWALL AND REINSTALL GRILLE IN FRONT OF INFILL

REMOVE DOOR HINGES AND CLASPS AND PERMANENTLY ATTACH DOOR TO PONY WALL

REMOVE SCREEN DOOR AND PREP OPENING FOR REPLACEMENT

REMOVE AND DISCARD SECOND FLOOR STAIR HATCH DOOR

REMOVE CROWN TRIM & WALL BASE FROM EXTERIOR WALLS FOR INSULATING AND

RETAIN FOR REINSTALLATION

REMOVE TRIM FROM AROUND WINDOWS AND RETAIN FOR REINSTALLATION

REMOVE ALL EXISTING PLUMBING PIPING IN CRAWLSPACE - SEE PLUMBING DRAWINGS

REMOVE EXISTING WIRING, DEVICES, AND ELEC. FIXTURES - SEE ELECTRICAL

DRAWINGS

1. VERIFY ALL CONDITIONS AND COORDINATE WITH ALL DISCIPLINES OF

CONTRACT. UNDOCUMENTED FIELD CHANGES MAY HAVE OCCURRED AND ARE

TO BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER WHEN

DISCOVERED.

2. SEE MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR DEMOLITION

WORK OF THOSE TRADES.

3. CONTRACTOR SHALL MAINTAIN A TEMPORARY WEATHER TIGHT ENCLOSURE

AS ITEMS ARE BEING REMOVED.

4. COORDINATE ALL MECHANICAL, ELECTRICAL, FIRE SYSTEMS,

COMMUNICATIONS AND UTILITY SHUT-DOWNS WITH CONTRACTING OFFICER

PRIOR TO REMOVING AND OR RELOCATING.

5. DEMOLITION IS NOT NECESSARILY LIMITED TO WHAT IS SHOWN ON

DRAWINGS. THE INTENT IS TO INDICATE THE GENERAL SCOPE OF

DEMOLITION REQUIRED TO COMPLETE THE WORK IN ACCORDANCE WITH THE

CONTRACT DRAWINGS.

6. THESE DRAWINGS INDICATE STRUCTURAL AND NON-STRUCTURAL

DEMOLITION THAT IS TO OCCUR TO MAKE WAY FOR NEW CONSTRUCTION.

ADDITIONAL STRUCTURAL DEMOLITION WORK, CONSTRUCTION OR SHORING

REQUIRING COORDINATION WITH NEW STRUCTURAL IS INDICATED ON THE

STRUCTURAL DRAWINGS.

7. SEE HAZARDOUS MATERIALS ABATEMENT DRAWINGS FOR ADDITIONAL

INFORMATION AND COORDINATION.

8. ALL EXTERIOR WALLS ARE TO RECEIVE INJECTION FOAM INSULATION. IN

ORDER TO ACCOMPLISH THIS, IT IS INTENDED THAT ALL OF THE CROWN

MOLDING TRIM AND WINDOW APRONS WILL BE REMOVED FROM EXTERIOR

WALLS AND AS-REQUIRED, HOLES DRILLED BEHIND THESE AREAS TO

PROVIDE ACCESS TO EACH STUD BAY FOR INSULATING. IF CROWN MOLDINGS

AND WINDOW APRONS CAN BE REUSED, THEY ARE TO BE REINSTALLED

AFTER INSULATION INSTALLATION. IF THEY ARE DAMAGED DURING

REMOVAL, THEY ARE TO BE REPLACED WITH SAME SPECIES, MATCHING

STAIN AND CLEAR FINISH. IF BLOCKING IS DISCOVERED IN EXTERIOR WALLS,

BASE TRIMS MAY ALSO HAVE TO BE REMOVED FOR STUD BAY ACCESS.

GENERAL DEMOLITION NOTES

DEMOLISHED ELEMENTS

EXISTING ELEMENTS TO REMAIN

LINEWORK LEGEND

INDICATES AREA OF SUBFLOOR REMOVAL

AND REPLACEMENT

A

B

11 11 11

22 3

15 15 14 15 15

A

B

ROOF REPLACEMENT BID OPTION ITEM- SCOPE OF WORK:

• REMOVE EXISTING EXPOSED FASTENER METAL ROOFING

• REMOVE EXISTING UNDERLAYMENT

• REMOVE EXISTING EDGE FLASHINGS

• PREPARE EXISTING PLANKS FOR INSTALLATION OF NEW ROOFING

EXTERIOR PORTION OF THE CHIMNEY REPLACEMENT BID OPTION ITEM- SCOPE OF WORK

• REMOVE EXTERIOR PORTION OF BRICK MASONRY CHIMNEY. WEATHER PROTECT

OPENING DURING WALL WORK.

• PREPARE BRICK COURSINGS BELOW FOR EXTERIOR PORTION OF CHIMNEY

REPLACEMENT.

• REGROUT AND REPOINT

SEE FULL HAZARDOUS MATERIALS TESTING REPORT INCLUDED IN THE SPECIFICATIONS BOOK.

THE FOLLOWING SCOPES OF WORK ARE TO BE INCLUDED IN THE CONTRACT BID.

1. PERFORM THE SET UP & REMOVAL OF ALL LEAD PAINTED CEILING TILE. INCLUDE ALL LABOR, MOBILIZATION, REMOVAL AND DISPOSAL. THIS INCLUDES ALL CEILING PANELS INDICATED FOR

DEMOLITION, WHICH INCLUDES ALL CEILING PANELS IN THE BUILDING.

a. MOBILIZATION AND DEMOBILIZATION OF EQUIPMENT

b. ESTABLISH NEGATIVE PRESSURE WORK AREA

c. CRITICAL BARRIERS

d. REMOVAL OF LEAD PAINTED CEILING TILE

e. T-CLIP OF COMPONENTS

f. CLEANUP AND DISPOSAL OF LBP WASTE AT AN EPA ACCREDITED LICENSED

LANDFILL

g. BLOOD SAMPLES FOR WORKER EVALUATION

2. PERFORM THE SET UP & REMOVAL PCB BALLASTS AND MERCURY CONTAINING LIGHT

BULBS. INCLUDE ALL LABOR, MOBILIZATION, REMOVAL & DISPOSAL. INCLUDES (8) 4'

FLUORESCENT LIGHT BULBS AND 4 EA. PCB BALLASTS.

a. REMOVE BALLASTS AND MERCURY CONTAINING LIGHT BULBS IN CONJUNCTION

WITH LEAD PAINTED CEILING TILE.

b. CLEANUP AND DISPOSAL OF WASTE AT AN EPA ACCREDITED LICENSED LANDFILL

3. PERFORM SET UP & REMOVAL AND DISINFECTING OF PACK RAT DROPPINGS, URINE, AND

NESTS. INCLUDE ALL LABOR, MOBILIZATION, REMOVAL & DISPOSAL. EVIDENCE OF RATS IS IN THE

CRAWLSPACE.

a. REMOVAL OF ALL LISTED ITEMS

b. CLEANING/DISINFECTING AREA AS NEEDED

c. CLEANUP AND DISPOSAL OF WASTE AT AN EPA ACCREDITED LICENSE LANDFILL

4. PERFORM CRAWLSPACE MOLD REMEDIATION. INCLUDE LABOR, MOBILIZATION, REMOVAL &

DISPOSAL.

a. MOBILIZATION OF EQUIPMENT (AFTER CRAWLSPACE SOIL HAS BEEN REMOVED BY

OTHERS)

b. LABOR AND MATERIALS TO COMPLETE REMEDIATION

c. ESTABLISH CONTAINMENT WITH NEGATIVE AIR PRESSURE AS NEEDED

d. CRITICAL BARRIERS

e. HEPA VACUUM AND CLEANING AS NEEDED.

f. REMOVAL USING CHEMICAL, SANDING METHODS FOR MICROBIAL GROWTH AND

COMPLETE BIO-WASH IN EACH SPACE.

g. CLEANUP AND DISPOSAL OF WASTE AT AN EPA APPROVED LANDFILL.

5. REMOVE AND PROPERLY DISPOSE OF ONLY TWO LEVEL 2 EXISTING WINDOWS SLATED FOR

REPLACEMENT THAT HAVE ASBESTOS-CONTAINING WINDOW GLAZING (LESS THAN 1%

ASBESTOS). INCLUDE LABOR, MOBILIZATION, REMOVAL & DISPOSAL. OTHER EXISTING WINDOWS

WITH ASBESTOS-CONTAINING WINDOW GLAZING ARE TO REMAIN IN PLACE WITHOUT

ABATEMENT.

a. MOBILIZATION OF EQUIPMENT

b. ALL LABOR AND MATERIALS TO COMPLETE REMOVAL

c. REMOVAL OF WINDOW FRAME AND SASHES.

d. BOARDING OFF WINDOW OPENINGS FOR PROTECTION UNTIL NEW WINDOWS ARE

INSTALLED

e. CLEANUP AND DISPOSAL OF WASTE AT AN EPA APPROVED LANDFILL

ABATEMENT & REMEDIATION SCOPE

DATE:

SHEET:

317 Cruse Ave. Suite 201 Helena, Montana 59601 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

3/ 4/

:0

0:

P M

3/01/2025

A102

DEMOLITION PLANS

SEELEY LAKE RANGER STATION

3583 HWY 83 N.

SEELEY LAKE, MT 59868

USFS SEELEY

BUNKHOUSE REMODEL

B

ID

S E

T

3/16" = 1'-0"

LEVEL 1 DEMOLITION PLAN

N

3/16" = 1'-0"

LEVEL 2 DEMOLITION PLAN

3/16" = 1'-0"

ROOF DEMOLITION PLAN

* SEE NOTES BELOW & DETAILS ON A601 REGARDING

RECOMMENDED METHODS FOR INSULATING EXTERIOR WALLS

INVOLVING REMOVAL OF TRIMS.

CRAWL SPACE, VACCUM REMOVAL

OF 12"- 18" DIRT, - NOT TO EXCEED

T.O.FTG. - ADD VAPOR BARRIER

-BID OPTION ITEM -

REPLACE DECAYED AND

DAMAGED PORTION OF THE

CHIMNEY W/ BRICKS IN KIND.

-BID OPTION ITEM -

REPLACE EXISTING FLASHING

AND WEATHERPROOFING

SURROUND

REMOVE ALL EXISTING CASEWORK

AND APPLIANCES

REMOVE SINK AND CABINET,

DEMO CEILING PANELS,

(SEE HAZMAT)

DEMO CASEWORK, AND SHELVING

REMOVE LIGHTING FIXTURE,

(SEE HAZMAT)

DEMO FIXTURES

REMOVE AND FILL HEAT TRANSFER

GRILLES & OPENINGS

DEMOLISH PARTION

STRIP WALL MATERIAL TO THE WOOD

STUDS

DEMO SHOWER & SURROUND

DEMOLISH WALL PARTION

DEMOLISH CEILING PANELS

REMOVE TRIM

DEMO ANY FLOORING,

INCLUDING SUBFLOOR

DEMO PARTITIONS

DEMO PLUMBING FIXTURES

DEMO WALL MATERIAL TO THE STUD

REMOVE EXISTING OIL FURNACE

DEMO CEILING PANELS [THROUGHOUT,]

(SEE HAZMAT)

PREP FLOOR FOR NEW LAMINATE

GROUT AND REPOINT CHIMENY AS NEEDED

REMOVE CEILING FIXTURE

REMOVE TRANSITION AND

PREP FOR NEW.

SAND FLOOR, PREP FOR REFINISHING

DEMO CRAWL SPACE VENTS.

• FILL CAVITY W/ RIGID INSULATION

SEE - DETAIL 4 - A501

• [EXIST] SCREEN TO REMAIN

PREP GROUND AT FOUNDATION FOR

2' PERIMETER OF GRAVEL.

DEMO ANY FLOORING,

INCLUDING SUBFLOOR

SAND AND PREP

FLOORS FOR REFINISH

SAND AND PREP

FLOOR FOR REFINISH

DEMO CEILING PANELS,

(SEE HAZMAT)

PREP WOOD FLOOR FOR NEW FLOORING

DEMO BEAM WRAPS,

(SEE HAZMAT)

REMOVE FINISHES DOWN TO

EXISTING FRAMING

REMOVE FINISHES DOWN TO

EXISTING FRAMING

HAZMAT NOTE:

SEE HAZARDOUS MATERIAL REPORT FOR TESTING

DETAILS OF ALL MATERIALS. SEE ABATEMENT AND

REMEDIATION SCOPE DESCRIPTIONS ON THIS

SHEET FOR SCOPES OF WORK.

LEAVE THE STAIR TREAD AND RISERS,

NO WORK.

DN

1. DIMENSIONS ARE TO FACE OF STUD, EXISTING REMAINING WALL FINISH, MASONRY, OR DOOR/WINDOW OPENINGS. DIMENSIONS OF EXISTING CONSTRUCTION ARE NOT SHOWN ON DRAWINGS - VERIFY DIMENSIONS OF ALL EXISTING CONSTRUCTION IN THE FIELD. DIMENSIONS TO OPENINGS ARE NOMINAL. VERIFY ALL OPENINGS WITH ROUGH OPENING REQUIREMENTS.

2. ALL DOOR OPENINGS PERPENDICULAR TO A WALL ARE 4" TO THE WALL FRAMING UNO.

3. EXISTING CONSTRUCTION TO REMAIN SHOWN SHADED, NEW CONSTRUCTION SHOWN BLACK.

4. SEE SHEET A002 FOR WALL TYPES.

5. VERIFY EXISTING WALL CONSTRUCTION.

6. ALL EXTERIOR WALLS ARE TO RECEIVE INJECTION FOAM INSULATION. IN ORDER TO ACCOMPLISH THIS, IT IS INTENDED THAT ALL OF THE CROWN MOLDING TRIM AND WINDOW APRONS WILL BE REMOVED FROM

EXTERIOR WALLS AND AS-REQUIRED, HOLES DRILLED BEHIND THESE AREAS TO PROVIDE ACCESS TO EACH STUD BAY FOR INSULATING. IF CROWN MOLDINGS AND WINDOW APRONS CAN BE REUSED, THEY ARE TO BE REINSTALLED AFTER INSULATION INSTALLATION. IF THEY ARE DAMAGED DURING REMOVAL, THEY ARE TO BE REPLACED WITH SAME SPECIES, MATCHING STAIN AND CLEAR FINISH. IF BLOCKING IS DISCOVERED IN EXTERIOR WALLS, BASE TRIMS MAY ALSO HAVE TO BE REMOVED FOR STUD BAY ACCESS.

GENERAL FLOOR PLAN NOTES

NEW CONSTRUCTION

EXISTING ELEMENTS TO REMAIN

LINEWORK LEGEND

A2011

A201

A201

A201

A

B

A301

A301

304 SF

BUNK RM.

101 SF

ENTRY

304 SF

KITCHEN/LIVING

12' - 8 1/2" 14' - 6 1/4" 12' - 0 3/4"

/2

40' - 1 1/2"

A301

A301

73 SF

BATHROOM

78 SF

LAUNDRY

i1 i1 i2 i1 i3 i4 i4 i5 e1 e1 e1 e1

58 SF

BATHROOM

E-RF

LVT1

LVT1 LVT1

E-RF E-RF

[UNDERSTAIRS]

A401

NOTE:

1. ANY EXISTING TRANSFER GRILLES & DUCTS ARE TO BE FILLED AND APPROPRIATELY FINISHED W/

CONGRUENT MATERIALS.

2. WOOD FLOOR REFINISH WORK DOES NOT INCLUDE THE STAIRS. NO NEW FLOORING WORK TO BE

INCLUDED ON THE STAIR.

A401

LVT1

E-RF

E-RF

NEW SCREEN DOOR

CLEAN AND REPOINT

CHIMNEY ALL SIDES

6A

[EXIST] CRAWL SPACE ACCESS.

[NEW] HINGED FLOOR ACCESS

HATCH W/ HOLD OPEN HOOK &

LATCH

103A

103B

FL1

3. BID OPTION ITEM: PROVIDE AND INSTALL WINDOW BLINDS ON ALL WINDOWS IN KITCHEN/LIVING 102 AND BUNK RM. 103.

FLOORING TRANSITION

/9 A501

FLOORING TRANSITION

/9 A501

FLOORING TRANSITION

/9 A501

A2011

A201

A201

A201

A

B

A301

A301

A301

A301

201 SF

BEDROOM

4'

1/

2" 6'

5/ 8"

2'

5/

8" 3'

/2

"222 SF

BEDROOM

76 SF

BATHROOM

i2 i2i2 i2 i2 i6i6 i4i7 i6 i2 i2

167 SF

CIRCULATION

201 203

AA

LVT1

(E)(E)

(E) (E)

3 1/8" 2' - 6 3/8" 3' - 11"

9'

/8

LVT 1 LVT 1

LVT1

A401

NOTE:

1. ANY EXISTING TRANSFER GRILLES & DUCTS ARE TO BE FILLED AND APPROPRIATELY FINISHED W/

CONGRUENT MATERIALS.

2. WOOD FLOOR REFINISH WORK DOES NOT INCLUDE THE STAIRS. NO NEW FLOORING WORK TO BE

INCLUDED ON THE STAIR.

A6013

A501

NEW EGRESS WINDOW

REPLACEMENT

NEW EGRESS WINDOW

REPLACEMENT

2' - 6" 10' - 8"

A

CLEAN & REPOINT

CHIMNEY ALL SIDES

i6 i6

ALIGN FINISH FACE OF EXISTING

WALL TO FINISH FACE OF GYPSUM.

A

M

IR

R O

R E

D

(E)

(E) (E) (E)

3. BID OPTION ITEM: PROVIDE AND INSTALL WINDOW BLINDS ON ALL WINDOWS IN BEDROOM 202 AND BEDROOM 203.

1' - 6"

LVT 1

FLOORING TRANSITION

FLOORING TRANSITION

/8 A501

/8 A501

FLOORING TRANSITION

FLOORING TRANSITION

/8 A501

/8 A501

ROOM FINISH LEGEND

LVT 1: VINYL TILE, COLOR SEE SPECS

E-RF: EXISTING WOOD FLOORING - REFINISHED

(E): EXISTING TO REMAIN AS-IS

FLOOR FINISHES

FLOOR AND BASE FINISH NOTES:

1. IF FINISHES ARE NOT CLEARLY INDICATED FOR AN AREA, CLARIFY INTENT WITH CONTRACTING

OFFICER.

2. TEST ALL SUBSTRATES TO VERIFY COMPLIANCE WITH MANUFACTURER'S SPECIFICATIONS

PRIOR TO FLOORING INSTALLATION.

3. PATCH, REPAIR, AND/OR GRIND ALL SUBSTRATES TO ACCEPTABLE LEVEL OF

SMOOTHNESS/LEVELNESS PRIOR TO FLOORING INSTALLATION.

4. INSTALL FACTORY-PROVIDED TRANSITION STRIP OR AS DETAILED AT ALL FLOORING CHANGES.

5. CHANGE FLOORING WHERE INDICATED ON PLANS, CHANGE FLOOR CENTERED UNDER DOOR AT

ROOM TO ROOM CHANGES, U.N.O

6. AT CASEWORK, CONTINUE BASE AROUND ENDPANELS AND TOE-KICKS, U.N.O.

7. SAMPLES FOR ALL FINISHES MUST BE SUBMITTED TO AND APPROVED BY CONTRACTING

OFFICER PRIOR TO ORDERING.

PAINT NOTE: MANUF. SHOWN ARE BASIS OF DESIGN ONLY. SUBSTITUTIONS ALLOWED WITH APPROVAL.

PAINTED GWB: PAINT COLOR OVER GYPSUM BOARD - TYP. U.N.O., COLOR AS INDICATED.

(E): EXISTING WOOD PANELING TO REMAIN

P1: PAINT - COLOR: SW 7002 - DOWNY

P2: PAINT - COLOR: SW 7757 - HIGH REFLECTIVE WHITE

WD: VERTICAL WOOD PANELING TO MATCH EXISTING

WNS: PAINTED P2 BEADBOARD WAINSCOT TO 48" - PAINTED P1 GWB ABOVE

WALL FINISHES

1X4 WD-P: 1X4, PAINTED SEMI-GLOSS

1X4 WD: 1X4, STAINED, CLEAR FINISH TO MATCH EXISTING

QRTR: QUARTER ROUND WOOD, STAINED, CLEAR FINISH

(E): EXISTING TO REMAIN

BASE FINISHES

SS1: SOLID SURFACE COUNTERTOP - CORIAN - COLOR: SANDSTONE

WD1: WOOD BUTCHER BLOCK, COMMERCIAL MAPLE, EDGE GRAIN VARNIQUE SEMI - GLOSS FINISH

COUNTERTOP AND CASEWORK FINISHES NOTES:

1. SEE SPECIFICATION FOR MANUFACTURER.

2. PROVIDE FINISHED END PANELS WHERE EXPOSED TO VIEW, PROVIDE SCRIBE STRIP AT ALL WALL

ABUTMENTS.

3. WHERE NOTED ON ELEVATIONS, PROVIDE 4" BACKSPLASH W/ SQUARE EDGES, MATCH ADJ.

COUNTERTOP MATERIAL.

4. FOR BIDDING PURPOSES ASSUME EACH DRAWER AND/OR DOOR HAS A PULL, EVEN IF NOT SHOWN

IN ELEVATIONS

COUNTERTOPS, CASEWORK SURFACES, TRIM

WALL FINISHES NOTES:

1. SEE INTERIOR ELEVATIONS AND/OR DETAILS FOR INTERIOR WINDOWS, SPECIAL WALL FINISHES, TRIM, ETC.

2. FINISH SCHEDULE APPLIES TO GENERAL AREA: THERE MAYBE SPECIFIC FINISH REQUIREMENTS

SHOWN ON DETAILS, DRAWINGS OR SPECIFICATIONS.

3. SEE SPECIFICATIONS FOR LEVEL(S) OF FINISH AT GWB SURFACES.

4. ALL WALLS/CEILINGS P1 UNLESS OTHERWISE NOTED ON PLANS &/OR ELEVATIONS.

LVT1

CEILING FINISHES

(E)

SEE RCP

GYP CEILING: KNOCKDOWN FINISH, PAINT

E-RF

WINDOW COVERINGS

1. PROVIDE WINDOW COVERINGS FOR WINDOWS THROUGHOUT. (SEE-SPECS)

WALL A

WALL B

WALL C

WALL D

DATE:

SHEET:

317 Cruse Ave. Suite 201 Helena, Montana 59601 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

4/ 2/

0:

:3

A

M

3/01/2025

A103

FLOOR PLANS

SEELEY LAKE RANGER STATION

3583 HWY 83 N.

SEELEY LAKE, MT 59868

USFS SEELEY

BUNKHOUSE REMODEL

B

ID

S E

T

1/4" = 1'-0"

LEVEL 1 FLOOR PLAN

11/4" = 1'-0"

LEVEL 2 FLOOR PLAN

ROOM FINISH SCHEDULE

NO. ROOM NAME AREA PERIMETER FLOOR FINISH BASE FINISH WALL (A) WALL (B) WALL (C) WALL (D) COMMENTS

101 ENTRY 101 SF 62'-8" LVT1 (E) (E) (E) (E) (E)

102 KITCHEN/LIVING 304 SF 74'-7" E-RF (E) (E) (E) (E) (E)

103 BUNK RM. 304 SF 74'-7" E-RF (E) (E) (E) (E) (E)

104 LAUNDRY 78 SF 44'-2" LVT1 1X4 WD-P P1 (E) P1 P1

105 BATHROOM 73 SF 44'-8" LVT1 1X4 WD-P WNS WNS WNS H

106 BATHROOM 58 SF 34'-2" LVT1 1X4 WD-P WNS WNS WNS WNS

201 CIRCULATION 167 SF 58'-4" LVT1 QRTR P1 (E) P1 P1 (E) (E)

202 BEDROOM 222 SF 63'-1" LVT1 QRTR (E) (E) P1 (E) (E)

203 BEDROOM 201 SF 59'-6" LVT1 QRTR P1 (E) (E) (E) P1 (E)

204 BATHROOM 76 SF 47'-5" LVT1 1X4 WD-P WNS WNS WNS WNS

NN

* SEE NOTES BELOW REGARDING RECOMMENDED METHODS FOR INSULATING EXTERIOR WALLS.

3" = 1'-0"

ROOM FINISH SCHEDULE WALL LABELING DIAGRAM

A2011

A201

A201

A

B

A301

A301

A301

A301

GWB

8' - 2 3/8"

GWB

8' - 2 3/8"

GWB

8' - 2 3/8"

GWB

8' - 2 3/8"

GWB

8' - 2 3/8"

GWB

8' - 2 3/8"

GWB

8' - 2 3/8"

A6013

GWB

7' - 4"

A

NEW BEAM WRAPS

NEW BEAM WRAPS

GYPSUM WALL BOARD

UNDERSIDE OF STAIRS

1'

8"

CEILING LEGEND

GWB 5/8" TYPE "X" GYPSUM WALLBOARD ON

EXISTING FRAMING. PAINT P1 UNO

NEW CONSTRUCTION

EXISTING ELEMENTS TO REMAIN

LINEWORK LEGEND

1. CEILING FIXTURES ARE SHOWN FOR REFERENCE ONLY FOR

COORDINATION WITH CEILING FINISH SYSTEM. SEE MECHANICAL,

ELECTRICAL AND SPRINKLER DRAWINGS FOR ALL CEILING

FIXTURES AND TYPES.

GENERAL CEILING NOTES

A2011

A201

A201

A201

A

B

A301

A301

A301

A301

GWB

7' - 5 7/8"

GWB

7' - 5 7/8"

VARIES

GWB

GWB

6' - 1 7/8"

VARIES

GWB

VARIES

GWB

VARIES

GWB

VARIES

GWB

GWB

7' - 5 7/8"

8"

1' -0

8"

1' -0

8"

1' -0

8"

1' -0

[No Slope] GWB 7' - 5 7/8"

[No Slope]

8"

1' -0

8"

1' -0

[No Slope]

8"

1' -0

8"

1' -0

8"

1' -0

8"

1' -0

8"

1' -0

[No Slope]

[No Slope]

[No Slope]

ATTIC ACCESS HATCH

(18"x 18"OPENING)

A6013

A

A501

DATE:

SHEET:

317 Cruse Ave. Suite 201 Helena, Montana 59601 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

3/ 4/

:0

0:

P M

3/01/2025

A104

REFLECTED CEILING PLAN

SEELEY LAKE RANGER STATION

3583 HWY 83 N.

SEELEY LAKE, MT 59868

USFS SEELEY

BUNKHOUSE REMODEL

B

ID

S E

T

1/4" = 1'-0"

LEVEL 1 RCP

11/4" = 1'-0"

LEVEL 2 RCP

A

B

A301

A301

A301

A301

8"

1' -0

3"

1' -0

8"

1' -0

REPLACE DAMAGED AND DECAYED

BRICKS WITH KIND. REGROUT &

REPOINT DAMAGED PORTION OF THE

CHIMNEY.

A105

A105

A105

A105

A105

A105

A105

A105

A105

A105

A105

ICE & WATER SHIELD

MIN

3' - 0"

M

IN

3'

0"

MIN

3' - 0"

M

IN

3'

0"

ICE & WATER SHIELD

ICE & WATER SHIELD

ICE & WATER SHIELD

TY

P

3'

0"

1. INSTALL SELF-ADHERING ICE BARRIER MATERIAL ON ALL EAVES AND

OVERHANGS FROM THE LOWEST EDGE OF ALL ROOF SURFACES TO A

POINT AT LEAST 24" INSIDE THE EXTERIOR WALL LINE OF THE

BUILDING.

2. INSTALL SELF-ADHERING ICE BARRIER MATERIAL AT ALL VALLEYS,

CRICKETS & CHANGES IN ROOF SLOPE, 24" MIN. EACH SIDE OF

TRANSITION.

3. GANG PLUMBING VENTS ABOVE CEILING TO MINIMIZE ROOF

PENETRATIONS. VERIFY PENETRATIONS IN FIELD. LOCATE

PENETRATIONS TO NOT BE VISIBLE FROM APPROACH TO FRONT ENTRY

WHERE FEASIBLE.

4. SEE MECHANICAL AND PLUMBING DRAWINGS FOR PIPING AND

EQUIPMENT PENETRATIONS. ALL PVC PIPE PENETRATIONS TO BE

PAINTED.

5. NEW UNDERLAYMENT TO BE INSTALLED (SEE SPECS).

6. NEW METAL DRIP EDGE FLASHING TO BE INSTALLED (SEE SPECS).

7. NEW METAL ROOFING TO BE INSTALLED (SEE SPECS).

GENERAL ROOFING NOTES

ALL REROOFING WORK IS AN ADDITIVE

ALTERNATE BID ITEM

NEW CONSTRUCTION

EXISTING ELEMENTS TO REMAIN

LINEWORK LEGEND

[NEW] CLASSIC RIB METAL ROOF

[NEW] METAL DRIP EDGE

[NEW] ROOF UNDERLAYMENT

• ICE & WATER SHIELD

• ROOFING UNDERLAYMENT

[EXIST] ROOF PLANKING

[EXIST] WOOD FACIA

[EXIST] ROOF PURLIN

CLASSIC RIB METAL ROOF

METAL RETAINING CLIP

BUTYL TAPE @ ROOF PANEL

ROOFING UNDERLAYMENT

• ICE & WATER SHEILD

• UNDERLAYMENT

METAL DRIP EDGE

[EXIST] OUTLOOKER

[NEW] BLOWN-IN CELULLOSE INSULATION

[EXIST] LOG-LAP SIDING

[EXIST] TARPAPER MEMBRANE

METAL RIDGE CAP

BOX END OF PANEL

CAULK SEAMS VERTICALLY

W/ APPROVED SEALANT

S.S. POP RIVET @ 18" O.C.

PERFORATED Z-BAR

BUTYL TAPE SEALANT

APPROVED ROOF UNDERLAYMENT

[EXIST] ROOF PLANKS

ROOF PURLINS

RIDGE BEAM

LEAVE RIDGE UNOBSTRUCTED & OPEN

6" M

AX.

6" M

AX.

FASTENERS @ 12" O.C.

FASTENERS @ 24" O.C.

BUTYL TAPE SEALANT

ICE & WATER SHEILD , UNDERLAYMENT

24" WIDE VALLEY FLASHING, HEM EDGES

[EXIST] ROOF PLANKS

ROOF JOIST

[EXISTING] SIDING

SEALANT

FASTENER @ 12" O.C.

BITMOUS TAPE

Z- CLOSURE, SET IN CONT. BUTYL

TAPE SEALANT, FASTEN 12" O.C.

FASTENER @ 12" O.C.

ICE & WATER UNDERLAYMENT- PRY AND

TUCK, AS FAR AS POSSIBLE UNDER LAST

COARSE OF SIDING. RESET

EXISTING PLANKS

CAP FLASHING

NOTE: MIN. LAP ON ALL FLASHING IS 4". APPROVED

SEALANT IN LAPS OF ALL FLASHING. TURN

APPROVED UNDERLAYMENT 3" VERTICALLY MIN.

3"

NOTE: MINIMUM LAP ON ALL FLASHING IS 4". APPROVED

SEALANT IN LAPS OF ALL FLASHING. TURN APPROVED

UNDERLAYMENT 3" VERTICALLY MINIMUM.

SEALANT

FASTENER

BYTUL SEALANT TAPE

RAKE FLASHING

[EXIST] SIDING

Z-CLOSURE, SET IN CONT. BUTYL

TAPE SEALANT, FASTEN 12" O.C.

FASTENER, 12" O.C.

ICE & WATER SHEILD UNDERLAYMENT

PRY SHINGLES, RUN ICE DAM

UNDER SIDING, RESET

BLOCKING

CLASSIC RIB METAL PANEL

EXISTING PLANKING

FASTENER

BACKER ROD W/ SEALANT

GROUT- JOINT FLASHING TERMINATION

ICE & WATER FLASHING

FASTENER @ 12" O.C.

CLASSIC RIB METAL PANEL

WOOD STUD CLEAT

[NEW PORTION] CHIMNEY,

[EXIST] SHEATHING

[EXIST] UN-DAMAGED BRICK

NOTE: MINIMUM LAP ON ALL FLASHING IS 4". APPROVED

SEALANT IN LAPS OF ALL FLASHING. TURN APPROVED

UNDERLAYMENT 3" VERTICALLY MINIMUM.

FIRE RESISTANT FOAM SEALANT

PFM FLASHING

FASTENER @ 12' O.C.

GROUT - JOINT TERMINATION

ICE & WATER SHEILD

BLOCKING

FIRE RESISTANT FOAM SEALANT

[NEW] PORTION OF CHIMNEY

NOTE: MINIMUM LAP ON ALL FLASHING IS 4". APPROVED

SEALANT IN LAPS OF ALL FLASHING. TURN APPROVED

UNDERLAYMENT 3" VERTICALLY MINIMUM.

PFM FLASHING

PFM CHIMNEY CAP

3/4" SHEATHING

BUTYL BASED,

WEATHERPROOF STRIP

WEATHERSTRIPING

FASTENER

CONSTRUCTION ADHESIVE

RIGID FOAM INSULATION

NEW BRICK

ICE & WATER SHIELD

2" PVC PLUMBING VENT

PLUMBING VENT BOOT CLOSURE

STEEL BAND

METAL ROOF

BOOT FLANGE

SELF SEALING FASTENER

BITUMINOUS SEALER;

COVER SURROUND

SEALANT

EXISTING ROOF PURLIN

DATE:

SHEET:

317 Cruse Ave. Suite 201 Helena, Montana 59601 www.mosaicarch.com

D A

TE

S

TA

M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

3/ 4/

:0

0:

P M

3/01/2025

A105

ROOF PLAN

SEELEY LAKE RANGER STATION

3583 HWY 83 N.

SEELEY LAKE, MT 59868

USFS SEELEY

BUNKHOUSE REMODEL

B

ID

S E

T

1/4" = 1'-0"

ROOF PLAN

1 N

* NOTE:

ALL ROOFING WORK IS A BID OPTION ITEM.

CHIMNEY REPLACEMENT IS A BID OPTION ITEM.

3" = 1'-0"

ROOF DETAIL - EAVE

2 3" = 1'-0"

ROOF DETAIL - RAKE

3 3" = 1'-0"

ROOF DETAIL - RIDGE

4 3" = 1'-0"

VALLEY DETAIL

3" = 1'-0"

SIDEWALL FLASHING TYP.

6 3" = 1'-0"

SIDEWALL FLASHING DETAIL 2 TYP.

3" = 1'-0"

CHIMNEY FLASHING

8 3" = 1'-0"

CHIMNEY FLASHING - RAKE

3" = 1'-0"

CHIMNEY CAP

10 1 1/2" = 1'-0"

PLUMBING VENT @ ROOF

NEW CONSTRUCTION

EXISTING ELEMENTS TO REMAIN

LINEWORK LEGEND

Level 1

100' - 0"

Level 2

109' - 0 3/4"

AB

A301

T.O. FOOTING

96' - 8 3/4"

A301

A

WINDOW REPLACEMENT WITH

CASEMENT STYLE

OPTION ITEM # 2

REPLACE DAMAGED PORTION OF

EXTERIOR BRICK, GROUT AND REPOINT

CHIMNEY CAP

Level 1

100' - 0"

Level 2

109' - 0 3/4"

2 11

A301

T.O. FOOTING

96' - 8 3/4"

A301

NEW SCREEN DOOR

OPTION ITEM # 2

REPLACE DAMAGED PORTION OF

EXTERIOR BRICK, GROUT AND REPOINT

CHIMNEY CAP

Level 1

100' - 0"

Level 2

109' - 0 3/4"

21 1

A301

T.O. FOOTING

96'…

This is the start of the file's text. The full file is on GovTribe.