Attachment 3 - SI001 - GENERAL NOTES -STRUCTURAL.pdf
PDF 434 KB Posted
- Attached to
- Y1MG--654-19-3-6360-0025, Construction, 654-19-914, Solar Panels New Parking Garage, (VA-19-00049803)
- Solicitation number
- 36C77621R0077
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C77621R0077 0001.docx | DOCX document | |
| Attachment 8 - Wage Determination SCA - WASHOE - 12-21-20.txt | TXT text file | |
| Attachment 9 - Wage Determination DBA - WASHOE - 2-12-21.txt | TXT text file | |
| Attachment 7 - EP401 ENLARGED ELECTRICAL PLANS.pdf | ||
| Attachment 6 - EP101 POWER _ SIGNAL PLANS - LEVEL 1.pdf | ||
| 36C77621R0077_1.docx | DOCX document | |
| Attachment 2 - Specs.zip | ZIP file | |
| Attachment 4 - Contractor Safety and Environmental Record Evaluation Form.docx | DOCX document | |
| Attachment 1 - SOW - Reno Solar Array DB.docx | DOCX document | |
| Attachment 5 - Release of Claims.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
DIVISION 01 - GENERAL REQUIREMENTS
1.1 ALL DESIGN SHALL BE IN ACCORDANCE WITH THE FOLLOWING:
A. 2015 INTERNATIONAL BUILDING CODE
1.2 SPECIAL INSPECTIONS
A. THE OWNER SHALL EMPLOY ONE OR MORE SPECIAL INSPECTORS WHO SHALL PROVIDE
INSPECTIONS AND MATERIALS TESTING DURING CONSTRUCTION. ALL SPECIAL INSPECTIONS
AND TESTING SHALL CONFORM TO THE REQUIREMENTS OF SPEC 014100, AND IBC 2015.
B. SPECIAL INSPECTIONS ARE IN ADDITION TO THE INSPECTIONS CONDUCTED BY THE LOCAL
BUILDING OFFICIAL. SPECIAL INSPECTIONS SHALL NOT RELIEVE THE OWNER AND CONTRACTOR
FROM REQUESTING THE BUILDING OFFICIAL'S INSPECTIONS REQUIRED BY IBC SECTION 110.
C. SPECIAL INSPECTORS SHALL BE GIVEN PROPER NOTICE AND ACCESS TO THE SITE TO
PERFORM TESTING AND INSPECTION AS NECESSARY.
D. REQUIRED CATEGORIES OF SPECIAL INSPECTIONS:
1. STEEL CONSTRUCTION (IBC SECTION 1705.2)
2. CONCRETE CONSTRUCTION (IBC SECTION 1705.3)
3. MASONRY CONSTRUCTION (IBC SECTION 1705.4)
4 SOILS (IBC SECTION 1705.6)
E. DUTIES AND RESPONSIBILITIES OF THE SPECIAL INSPECTOR:
1. THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED TO VERIFY THAT IT
CONFORMS TO THE CONTRACT DOCUMENTS.
2. THE SPECIAL INSPECTOR SHALL NOT AUTHORIZE OR APPROVE DEVIATIONS FROM THE
CONTRACT DOCUMENTS. ALL DEVIATIONS FROM THE CONTRACT DOCUMENTS MUST BE
INITIATED BY THE CONTRACTOR VIA A WRITTEN REQUEST FOR INFORMATION (RFI) AND
APPROVED BY THE ENGINEER OF RECORD PRIOR TO PROCEEDING WITH THE WORK.
3. THE SPECIAL INSPECTOR SHALL FURNISH WRITTEN INSPECTION REPORTS TO THE
ENGINEER OF RECORD. ALL DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE
ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF CORRECTIONS ARE NOT MADE,
THE BUILDING OFFICIAL AND ENGINEER AND/OR ARCHITECT SHALL BE NOTIFIED.
1.3 BUILDING CLASSIFICATION
A. REFER TO CODE ANALYSIS DRAWING GI101.
1.4 FIRE RESISTANCE
A. REFER TO CODE ANALYSIS DRAWING GI101.
1.5 SERVICE LOADING AND DESIGN PARAMETERS - ASCE7-10 OR AS SPECIFIED HEREIN
A. RISK CATEGORY II
B. LIVE LOADING:
1. SUPPORTED PARKING AND DRIVE AREAS:
i. UNIFORM LOAD 40 PSF
ii. CONCENTRATED LOAD ACTING ON 20 SQ. IN. AREA 3,000 LBS
2. SLAB ON GRADE:
i. UNIFORM LOAD 100 PSF
ii. CONCENTRATED LOAD ACTING ON 20 SQ. IN. AREA 3,000 LBS
3. STAIRS AND EXITS:
i. UNIFORM LOAD 100 PSF
ii. CONCENTRATED LOAD ACTING ON 4 SQ. IN. AREA 300 LBS
4. HANDRAILS AND GUARDS:
i. UNIFORM LOAD 50 PLF
ii. CONCENTRATED LOAD 200 LBS
5. INTERMEDIATE RAILS, BALUSTERS, AND PANEL FILLERS:
i. CONCENTRATED LOAD ACTING ON 1 SQ. FT. AREA 50 LBS
6. VEHICLE BARRIER SYSTEMS
i. CONCENTRATED LOAD ACTING ON 1 SQ. FT. AREA
AT 18 OR 27 INCHES ABOVE FINISHED FLOOR 6,000 LBS
7. LIVE LOAD REDUCTION:
i. MAXIMUM LOAD REDUCTION FOR MEMBERS
SUPPORTING TWO OR MORE LEVELS 20 %
C. SNOW LOADING:
1. GROUND SNOW LOAD (Pg) 20.0 PSF
2. FLAT ROOF SNOW LOAD (Pf) 16.8 PSF
3. EXPOSURE FACTOR (Ce) 1.0
4. THERMAL FACTOR (Ct) 1.2
5. IMPORTANCE FACTOR (Is) 1.0
D. WIND LOADING:
1. BASIC WIND SPEED (V) 130 MPH
2. EXPOSURE CATEGORY B
4. INTERNAL PRESSURE COEFFICIENT (GCpi) +/- 0.18
5. COMPONENTS AND CLADDING DESIGN PRESSURES
i. ROOF - ZONE 1 +13.3 -32.6 PSF
ii. ROOF - ZONE 2 +13.3 -54.8 PSF
iii. ROOF - ZONE 3 +13.3 -82.4 PSF
iv. WALL - ZONE 4 +29.9 -32.4 PSF
v. WALL - ZONE 5 +29.9 -39.8 PSF
E. SEISMIC LOADING:
1. IMPORTANCE FACTOR (Ie) 1.0
2. SPECTRAL RESPONSE ACCELERATIONS
i. SHORT PERIODS (SS) 1.832 %g
ii. 1 SEC PERIOD (S1) 0.618 %g
3. SITE CLASS C
4. DESIGN SPECTRAL RESPONSE ACCELERATIONS
i. SHORT PERIODS (SDS) 1.221 %g
ii. 1 SEC PERIOD (SD1) 0.536 %g
5. DESIGN CATEGORY D
6. SEISMIC BEHAVIOR:
i. NORTH/SOUTH DIRECTION:
ANALYSIS PROCEDURE:
EQUIVALENT LATERAL FORCE
SEISMIC FORCE RESISTING SYSTEM:
SPECIAL REINFORCED CONCRETE SHEAR WALLS
BASE SHEAR (V) 2177 KIPS
RESPONSE COEFFICIENT (Cs) 0.204
RESPONSE MODIFICATION FACTOR (R) 6
ii. EAST/WEST DIRECTION:
ANALYSIS PROCEDURE:
EQUIVALENT LATERAL FORCE
SEISMIC FORCE RESISTING SYSTEM:
SPECIAL REINFORCED CONCRETE SHEAR WALLS
BASE SHEAR (V) 2177 KIPS
RESPONSE COEFFICIENT (Cs) 0.204
RESPONSE MODIFICATION FACTOR (R) 6
F. VOLUMETRIC CHANGE LOADING - PCI MNL-120-10 (CHAPTER 4)
1. MAXIMUM SEASONAL CLIMATIC TEMPERATURE CHANGE 50 °F
2. ANNUAL AVERAGE AMBIENT RELATIVE HUMIDITY 50 %
1.6 FUTURE EXPANSION
A. THIS STRUCTURE IS DESIGNED FOR VERTICAL EXPANSION OF A STEEL FRAMED
PHOTOVOLTAIC ROOF STRUCTURE OF NOT MORE THAN 20 PSF TOTAL VERTICAL GRAVITY
LOAD.
1.7 MINIMUM HEADROOM CLEARANCE
A. SIGNED CLEARANCE:
1. ALL LEVELS 8'-2"
1.8 DRAINAGE
A. PROVIDE AS INDICATED BY PLAN ELEVATIONS WITH 1 1/2% MINIMUM SLOPE ON
PARKING SURFACES WHERE ELEVATIONS NOT INDICATED
1.9 DATUM
A. ALL STRUCTURAL ELEVATIONS ARE REFERENCED FROM MEAN SEA LEVEL (MSL) UNLESS
NOTED OTHERWISE
1.10 CORROSION PROTECTION SYSTEM
A. CORROSION PROTECTION SYSTEM IS BASED ON CRITERIA PRESENTED IN ACI 362.1R "GUIDE
FOR THE DESIGN AND CONSTRUCTION OF DURABLE CONCRETE PARKING STRUCTURES" FOR
ZONE III EXPOSURE
1. POST-TENSIONED STRUCTURE WITH CONCRETE SEALER, CORROSION INHIBITOR,
EPOXY COATED REINFORCEMENT, LOW PERMEABILITY, AND SPECIAL COVER
REQUIREMENTS AS SPECIFIED HEREIN
2. CONCRETE ACCESSORIES TO BE HOT-DIP GALVANIZED AND/OR STAINLESS STEEL AS
SPECIFIED HEREIN
1.11 CONSTRUCTION NOTES
A. GENERAL
1. WHERE DIMENSIONS ARE INDICATED FOR EXISTING STRUCTURES, THEY ARE
APPROXIMATE AND FOR REFERENCE ONLY. CONTRACTOR SHALL VERIFY IN FIELD (VIF)
ALL DIMENSIONS AND ELEVATIONS PRIOR TO CONSTRUCTION. ANY VARIATIONS
BETWEEN EXISTING DIMENSIONS AND/OR ELEVATIONS ON DRAWINGS SHALL BE
REPORTED TO ENGINEER.
2. ALL OMISSIONS OR CONFLICTS AMONG VARIOUS ELEMENTS OF DRAWINGS AND/OR
SPECIFICATIONS SHALL BE REPORTED TO ENGINEER BEFORE PROCEEDING WITH ANY
WORK.
3. VERIFY AND COORDINATE LOCATION AND SIZE OF ALL OPENINGS AND SLEEVES
THROUGH FLOORS, WALLS, AND ROOFS WITH RESPECTIVE SUBCONTRACTOR
(MECHANICAL, ELECTRICAL, HVAC, ETC.) AND SUBMIT TO STRUCTURAL ENGINEER FOR
REVIEW AND APPROVAL PRIOR TO FABRICATION AND INSTALLATION.
4. VERIFY STRUCTURAL ELEVATIONS AND DIMENSIONS WITH RESPECTIVE OTHER TRADES
AND DRAWINGS.
5. VERIFY LOCATION OF SLAB DEPRESSIONS, FLOOR DRAINS, INSERTS, AND OTHER
RELATED ITEMS.
6. NO STRUCTURAL MEMBERS SHALL BE CUT OR PENETRATED FOR PIPES, DUCTS,
CONDUITS, ETC., UNLESS SPECIFICALLY DETAILED OR APPROVED IN WRITING BY
ENGINEER.
7. FIELD VERIFY THE LOCATIONS OF EXISTING STRUCTURES, UTILITIES, ETC., AND NOTIFY
ENGINEER OF INTERFERENCES NOT NOTED ON DRAWINGS.
8. FLOOR SLAB ELEVATIONS INDICATED ON DRAWINGS ARE ESTABLISHED TO PROVIDE
POSITIVE DRAINAGE AND PROVIDE REQUIRED HEADROOM CLEARANCE, REFER TO
SECTIONS 1.7 AND 1.8. NOTIFY ENGINEER OF GRADES INDICATED WHICH DO NOT ALLOW
FOR MINIMUM HEADROOM CLEARANCE.
DIVISION 02 - EXISTING CONDITIONS
DIVISION 03 - CONCRETE
3.1 ALL DESIGN AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE FOLLOWING:
A. ACI 318-14
B. ACI 362.1R-12
C. REFER TO SPECIFICATION SECTION 033000 FOR INFORMATION NOT LISTED HEREIN
3.2 CONCRETE
DESCRIPTION F'C (PSI)
MAXIMUM
CHLORIDE ION
MAX W/C
RATIO
AVERAGE
ENTRAINED AIR
FOOTINGS 4000 STD 0.30 0.50 N/A
WALLS 5500 CNA/SPA 0.15 0.40 6-1/2%
COLUMNS 5500 CNA/SPA 0.15 0.40 6-1/2%
BEAMS 5500 CNA/SPA 0.06 0.40 6-1/2%
SLABS & STAIRS 5500 CNA/SPA 0.06 0.40 6-1/2%
SLAB-ON-GRADE 4500 STD/SF 0.15 0.40 6-1/2%
ISLANDS & PADS 4000 STD/F 0.15 0.40 6-1/2%
ALL OTHERS 4000 STD 0.30 0.40 6-1/2%
NOTES:
(1) STD: DESIGNATES A CONCRETE MIX DESIGN IN ACCORDANCE WITH SPECIFICATION SECTION
033000 WHICH DOES NOT REQUIRE SILICA FUME, GGBS/FLY ASH, OR CALCIUM NITRITE
ADMIXTURE
(2) CNA: DESIGNATES A CONCRETE MIX DESIGN IN ACCORDANCE WITH SPECIFICATION SECTION
033000 WHICH CONTAINS 1 GAL/CY OF CALCIUM NITRITE CORROSION-INHIBITOR ADMIXTURE
(3) SPA: DESIGNATES A CONCRETE MIX DESIGN IN ACCORDANCE WITH SPECIFICATION SECTION
033000 WHICH CONTAINS 10% MINIMUM FLY ASH BY WEIGHT OF CEMENT.
(4) SF: DESIGNATES A CONCRETE MIX DESIGN IN ACCORDANCE WITH SPECIFICATION SECTION
033000 WHICH CONTAINS 4-1/2 LBS/CY OF STRUCTURAL MACRO FIBERS
(5) F: DESIGNATES A CONCRETE MIX DESIGN IN ACCORDANCE WITH SPECIFICATION SECTION
033000 WHICH CONTAINS 1-1/2 LBS/CY OF FIBRILLATED FIBER REINFORCEMENT OR 1 LBS/CY
MICROFILAMENT REINFORCEMENT
(6) ALL NORMALWEIGHT CONCRETE SHALL HAVE A DENSITY OF APPROXIMATELY 145 PCF UNLESS
NOTED OTHERWISE
(7) AVERAGE AIR-ENTRAINED VALUES ARE FOR IN-PLACE CONCRETE. TOLERANCE ON TOTAL AIR
CONTENT IS 1-1/2% PER ACI 318.
(8) ALL AIR-ENTRAINED CONCRETE SHALL INCLUDE 564 LBS/CY MINIMUM OF CEMENT. THE
WEIGHT OF SILICA FUME, GGBS, AND FLY ASH MAY BE INCLUDED WITH THE WEIGHT OF
CEMENT.
3.3 CEMENT
A. ASTM C 150 TYPE I OR III
3.4 AGGREGATES
A. ASTM C 33
3.5 MILD REINFORCEMENT
A. MILD REINFORCEMENT, ASTM A 615 GRADE 60
B. MILD REINFORCEMENT (LOW ALLOY WELDABLE), ASTM A 706 GRADE 60
C. MECHANICAL TENSION AND COMPRESSION SPLICES AS INDICATED ON DRAWINGS
D. MECHANICAL TERMINATION SIZES AS INDICATED ON DRAWINGS
E. EPOXY COATING FOR PLAIN AND DEFORMED MILD REINFORCEMENT, ASTM A 775
F. WELDED PLAIN WIRE FABRIC SHEETS, ASTM A 185 GRADE 65
G. EPOXY COATING FOR PLAIN WELDED WIRE FABRIC, ASTM A 884
H. EPOXY COATING FOR DOWEL BARS SHALL BE THE SAME AS SPECIFIED FOR REINFORCEMENT
TO BE SPLICED
I. WELDING FOR REINFORCING STEEL, AWS D1.4
J. CONCRETE PROTECTION SHALL BE PER ACI 362.1R, EXCEPT AS NOTED ON DRAWINGS AND
SPECIFIED HEREIN. SPECIFIC DRAWINGS AND DETAILS MAY OR MAY NOT INDICATE EPOXY
COATING OR UNCOATED REINFORCING. IN AREAS OF DISPUTE, THIS SCHEDULE SHALL
GOVERN IN ALL CASES.
DESCRIPTION COVER PROTECTION
FOOTINGS 3" A615 - UNCOATED
WALLS IN CONTACT WITH EARTH 2" A615 - UNCOATED
WALLS NOT IN CONTACT WITH EARTH 1-1/2" A615 - UNCOATED
SHEAR WALLS 2" A706 - UNCOATED
COLUMNS MAIN REINFORCING 2-1/2" A706 - UNCOATED
COLUMN TIES 2" A706 - EPOXY COATED
BEAM TOP REINFORCING 3" A706 - EPOXY COATED
BEAM BOTTOM REINFORCING 2" A706 - UNCOATED
BEAM STIRRUPS AT TOP 2-1/2" A706 - EPOXY COATED
BEAM STIRRUPS AT SIDE AND BOTTOM 1-1/2" A706 - EPOXY COATED
SLAB TOP REINFORCING 2" A615 - EPOXY COATED
SLAB BOTTOM REINFORCING 1" A615 - EPOXY COATED
STAIR TOP REINFORCING 2" A615 - UNCOATED
STAIR BOTTOM REINFORCING 1" A615 - UNCOATED
SLAB-ON GRADE REINFORCING 2" FROM TOP A615 - UNCOATED
ISLANDS, HK PADS, CURBS, MISC. 1-1/2" A615 - EPOXY COATED
BACK-UP BARS, SUPPORT BARS, ETC. N/A A615 - EPOXY COATED
3.6 POST-INSTALLED MILD REINFORCEMENT
A. POST-INSTALLED REINFORCING BAR CONNECTIONS SHALL BE DESIGNED PER THE ACI 318
BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE. POST-INSTALLED
REINFORCING BAR CONNECTIONS SHALL CONSIST OF THE FOLLOWING ADHESIVE SYSTEMS AS
PROVIDED BY HILTI, INC. (OR APPROVED EQUAL) CONTACT HILTI AT (800) 879-8000 FOR
PRODUCT RELATED QUESTIONS.
B. POST-INSTALLED REINFORCING BAR CONNECTIONS IN CONCRETE
1. EPOXY SYSTEMS WITH SAFESET TECHNOLOGY:
i. HILTI HIT-RE 500 V3 SAFESET SYSTEM WITH HILTI HOLLOW DRILL BIT (TE-CD OR
TE-YD), AND HILTI VC 20/40 VACUUM (VC 20-U OR VC 40-U) WITH POST-INSTALLED
STEEL REINFORCING BARS INSTALLED PER ICC ESR-3814
ii. HILTI HIT-HY 200 SAFESET SYSTEM WITH HILTI HOLLOW DRILL BIT (TE-CD OR
TE-YD), AND HILTI VC 20/40 VACUUM (VC 20-U OR VC 40-U) WITH POST-INSTALLED
STEEL REINFORCING BARS INSTALLED PER ICC ESR-3817
C. THE DESIGN OF STRAIGHT POST-INSTALLED REINFORCING BARS SHALL BE PERFORMED PER
THE DEVELOPMENT AND SPLICE LENGTH REQUIREMENTS OF THE ACI 318 BUILDING CODE
REQUIREMENTS FOR STRUCTURAL CONCRETE. THE POST-INSTALLED REINFORCING BAR
SYSTEM IS AN ALTERNATIVE TO CAST-IN-PLACE REINFORCING BARS GOVERENED BY ACI 318
AND IBC CHAPTER 19.
D. THE EPOXY SYSTEM SHALL BE TESTED IN ACCORDANCE WITH THE ICC-ES ACCEPTANCE
CRITERIA FOR POST-INSTALLED EPOXY ANCHORS IN CONCRETE ELEMENTS (AC308), TABLE 3.8.
TECHNICAL DATA SHALL BE PUBLISHED IN AN ICC-ES EVALUATION SERVICE REPORT SHOWING
COMPLIANCE WITH IBC.
1. ICC-ES ESR-3814 FOR HILTI HIT-RE 500 V3 EPOXY ANCHORS AND POST-INSTALLED
REINFORCING BAR CONNECTIONS IN CRACKED AND UNCRACKED CONCRETE.
2. ICC-ES ESR-3187 FOR HILTI HIT-HY 200 EPOXY ANCHORS AND POST-INSTALLED
REINFORCING BAR CONNECTIONS IN CRACKED AND UNCRACKED CONCRETE.
E. POST-INSTALLED REINFORCING BAR INSTALLATION SHALL BE PERFORMED BY PERSONNEL
TRAINED TO INSTALL THE SYSTEM PER THE MANUFACTURER'S PRINTED INSTALLATION
INSTRUCTIONS (MPII), AS INCLUDED IN THE ANCHOR PACKAGING. THE CONTRACTOR SHALL
ARRANGE FOR A MANUFACTURER'S REPRESENTATIVE TO PROVIDE ONSITE INSTALLATION
TRAINING FOR POST-INSTALLED REINFORCING BARS. THE STRUCTURAL ENGINEER OF
RECORD MUST RECEIVE DOCUMENTED CONFIRMATION PRIOR TO THE COMMENCEMENT OF
INSTALLING THE BARS THAT ALL OF THE CONTRACTOR'S PERSONNEL WHO WILL INSTALL
POST-INSTALLED REINFORCING BARS HAVE BEEN TRAINED TO INSTALL THE SYSTEM PER THE
MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS (MPII).
F. THE POSITION OF EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE SHALL BE
LOCATED PRIOR TO POST-INSTALLING BARS. EXISTING BARS SHALL BE LOCATED USING HILTI
FERROSCAN, GPR, X-RAY, CHIPPING, OR OTHER MEANS.
3.7 POST-TENSIONING TENDONS
A. ENCAPSULATED 7-WIRE LOW-RELAXATION TYPE (LRS) STRAND, 270 KSI. ASTM A 416 AND
SUPPLEMENT.
1. TENSIONING SEQUENCE:
i. SLAB TEMPERATURE TENDONS (PARALLEL TO BEAMS)
ii. SLAB UNIFORM TENDONS (PERPENDICULAR TO BEAMS)
iii. SLAB ADDITIONAL TENDONS (PERPENDICULAR TO BEAMS)
iv. BEAM TENDONS
iv. GIRDER TENDONS
3.8 CONCRETE ACCESSORIES
A. MISCELLANEOUS STEEL SHAPES, PLATES, AND BARS, ASTM A 36, HOT-DIP GALVANIZED AFTER ASSEMBLY. STAINLESS STEEL ASTM A 666 OR ASTM A 276, TYPE 304L AS NOTED ON DRAWINGS.
B. ANCHOR BOLTS, ASTM F 1554 GRADE 36, HOT-DIP GALVANIZED.
C. HEADED STUD ANCHORS, ASTM A 108, TO BE IN ACCORDANCE WITH AWS D1.1-TYPE B, SIZES AS
INDICATED ON DRAWINGS.
D. POST-INSTALLED ANCHORS:
1. EXCEPT WHERE INDICATED ON THE DRAWINGS, POST-INSTALLED ANCHORS SHALL
CONSIST OF THE FOLLOWING ANCHOR TYPES AS PROVIDED BY HILTI, INC. (OR APPROVED
EQUAL) CONTACT HILTI AT (800) 879-8000 FOR PRODUCT RELATED QUESTIONS.
2. ANCHORAGE TO CONCRETE:
i. ADHESIVE ANCHORS FOR CRACKED AND UNCRACKED CONCRETE USE:
a. HILTI HIT-HY 200 SAFESET SYSTEM WITH HILTI HIT-Z ROD PER ICC ESR-3187
b. HILTI HIT-HY 200 SAFESET SYSTEM WITH HILTI HOLLOW DRILL BIT (TE-CD OR
TE-YD) AND VC 20/40 VACUUM (VC 20-U OR VC 40-U) SYSTEM WITH HAS-E
THREADED ROD PER ICC ESR-3187
c. HILTI HIT-RE 500 V3 SAFESET SYSTEM WITH HILTI HOLLOW DRILL BIT (TE-CD
OR TE-YD) AND VC 20/40 VACUUM (VC 20-U OR VC 40-U) SYSTEM WITH HAS-E
THREADED ROD PER ICC ESR-3184
d. HILTI HIT-RE 500 V3 SAFESET SYSTEM WITH HILTI ROUGHENING TOOL (TE-YRT)
WITH HAS-E THREADED ROD PER ICC ESR-3184 FOR DIAMOND CORED HOLES
ii. MEDIUM DUTY MECHANICAL ANCHORS FOR CRACKED AND UNCRACKED
CONCRETE USE:
a. HILTI KWIK HUS EZ AND KWIK HUS EZ-I SCREW ANCHORS PER ICC ESR-3027
b. HILTI KWIK BOLT-TZ EXPANSION ANCHORS PER ICC ESR-1917
c. HILTI KWIK BOLT 3 EXPANSION ANCHORS (UNCRACKED CONCRETE ONLY)
PER ICC ESR-2302
iii. HEAVY DUTY MECHANICAL ANCHORS FOR CRACKED AND UNCRACKED CONCRETE
USE:
a. HILTI HDA UNDERCUT ANCHORS PER ICC ESR-1546
b. HILTI HSL-3 EXPANSION ANCHORS PER ICC ESR-1545
3. REBAR DOWELING INTO CONCRETE:
i. REFER TO SECTION 3.6 POST-INSTALLED MILD REINFORCEMENT
4. ANCHORAGE TO SOLID GROUTED MASONRY:
i. ADHESIVE ANCHORS USE:
a. HILTI HIT-HY 70 MASONRY ADHESIVE ANCHORING SYSTEM PER ICC ESR-2682
b. HILTI HIT-HY 200 SAFESET SYSTEM WITH HILTI HIT-Z ROD PER ICC ESR-3963
c. HILTI HIT-HY 200 SAFESET SYSTEM WITH HILTI HOLLOW DRILL BIT (TE-CD OR
TE-YD) AND VC 20/40 VACUUM (VC 20-U OR VC 40-U) SYSTEM WITH HAS-E
THREADED ROD PER ICC ESR-3963
d. STEEL ANCHOR ELEMENT SHALL BE HILTI HAS-E CONTINUOUSLY THREADED
ROD OR CONTINUOUSLY DEFORMED STEEL REBAR
ii. MECHANICAL ANCHORS USE:
a. HILTI KWIK BOLT 3 EXPANSION ANCHORS PER ICC ESR-1385
b. HILTI KWIK BOLT-TZ EXPANSION ANCHORS PER ICC ESR-3785
5. ANCHORAGE TO HOLLOW/MULTI-WYTHE MASONRY:
i. ADHESIVE ANCHORS USE:
a. HILTI HIT-HY 70 MASONRY ADHESIVE ANCHORING SYSTEM PER ICC ESR-3342
b. STEEL ANCHOR ELEMENT SHALL BE HILTI HAS-E CONTINUOUSLY THREADED
ROD OR CONTINUOUSLY DEFORMED STEEL REBAR
c. THE APPROPRIATE SIZE SCREEN TUBE SHALL BE USED PER ADHESIVE
MAUNFACTURER'S RECOMMENDATION
6. ANCHOR CAPACITY USED IN DESIGN SHALL BE BASED ON THE TECHNICAL DATA
PUBLISHED BY HILTI OR SUCH OTHER METHOD AS APPROVED BY THE STRUCTURAL
ENGINEER OF RECORD. SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS MUST
BE APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD PRIOR TO USE.
CONTRACTOR SHALL PROVIDE CALCULATIONS DEMONSTRATING THAT THE
SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERFORMANCE VALUES OF THE
SPECIFIED PRODUCT. SUBSTITUTIONS WILL BE EVALUATED BY THEIR HAVING AN ICC
ESR SHOWING COMPLIANCE WITH THE RELEVANT BUILDING CODE FOR SEISMIC USES,
LOAD RESISTANCE, INSTALLATION CATEGORY, AND AVAILABILITY OF COMPREHENSIVE
INSTALLATION INSTRUCTIONS. ADHESIVE ANCHOR EVALUATION WILL ALSO CONSIDER
CREEP, IN-SERVICE TEMPERATURE, AND INSTALLATION TEMPERATURE.
7. INSTALL ANCHORS PER THE MANUFACTURER INSTRUCTIONS, AS INCLUDED IN THE
ANCHOR PACKAGING.
8. OVERHEAD ADHESIVE ANCHORS MUST BE INSTALLED USING THE HILTI PROFI SYSTEM.
9. THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER'S REPRESENTATIVE TO
PROVIDE ONSITE INSTALLATION TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS
SPECIFIED. THE STRUCTURAL ENGINEER OF RECORD MUST RECEIVE DOCUMENTED
CONFIRMATION THAT ALL OF THE CONTRACTOR'S PERSONNEL WHO INSTALL ANCHORS
ARE TRAINED PRIOR TO THE COMMENCEMENT OF INSTALLING ANCHORS.
10. ANCHOR CAPACITY IS DEPENDANT UPON SPACING BETWEEN ADJACENT ANCHORS AND
PROXIMITY OF ANCHORS TO EDGE OF CONCRETE. INSTALL ANCHORS IN ACCORDANCE
WITH SPACING AND EDGE CLEARANCES INDICATED ON THE DRAWINGS.
11. EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY CONFLICT WITH THE
SPECIFIC ANCHOR LOCATIONS. UNLESS NOTED ON THE DRAWINGS THAT THE BARS CAN
BE CUT, THE CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL DRAWINGS AND
SHALL UNDERTAKE TO LOCATE THE POSITION OF THE REINFORCING BARS AT THE
LOCATIONS OF THE CONCRETE ANCHORS, BY HILTI FERROSCAN, GPR, X-RAY, CHIPPING,
OR OTHER MEANS.
E. ASPHALTIC JOINT FILLER (BOND BREAKER) SHALL BE 1/2" THICK OR AS NOTED ON DRAWINGS.
F. COMPRESSIBLE JOINT FILLER SHALL BE 1" THICK OR AS NOTED ON DRAWINGS.
G. EARTH DAMS 1/8" CONTINUOUS PREMOLDED MEMBRANES.
H. SLIDE BEARING SYSTEMS SHALL BE AS INDICATED ON DRAWINGS.
3.9 GROUT
A. PREMIXED, PACKAGED, NON-SHRINK, CHLORIDE-FREE, NON-STAINING, F'C = 6000 PSI MINIMUM, ASTM C 1107.
3.10 GENERAL CAST-IN-PLACE CONCRETE
A. REINFORCEMENT
1. PROVIDE EXTRA REINFORCING AROUND ALL OPENINGS, TWO #5 BARS ON ALL FOUR
SIDES OF EACH OPENING. EXTEND TWO FEET BEYOND CORNERS OF OPENING.
2. PROVIDE STANDARD 90 DEGREE BAR HOOKS UNLESS NOTED OTHERWISE ON DRAWINGS.
3. MINIMUM LENGTH OF LAP SPLICES SHALL BE BASED ON ACI 318 CLASS B OR A MINIMUM
OF 36 BAR DIAMETERS FOR UNCOATED BARS AND 54 BAR DIAMETERS FOR COATED
BARS UNLESS NOTED OTHERWISE ON DRAWINGS.
4. APPROVED REBAR COUPLERS MAY BE USED AT CONTRACTOR'S OPTION TO AID
PLACEMENT OF DOWELS THROUGH FORMS.
5. REINFORCING STEEL SHALL NOT BE BENT OR STRAIGHTENED UNLESS APPROVED BY
ENGINEER OR AS INDICATED ON DRAWINGS.
6. FIELD CUTTING OF REINFORCEMENT IS PROHIBITED UNLESS APPROVED BY ENGINEER.
7. WELDING OF REINFORCEMENT IS PROHIBITED UNLESS SPECIFICALLY CALLED FOR ON
DRAWINGS OR APPROVED BY ENGINEER. DO NOT WELD EPOXY COATED REINFORCEMENT.
B. ACCESSORIES
1. ALL WELD ASSEMBLIES SHALL USE E70XX LOW HYDROGEN ELECTRODES. MINIMUM
WELD SIZE IS 1/4 INCH. STAINLESS STEEL ELECTRODES SHALL BE TYPE 308L OR 347.
2. FOR FIELD WELDING GALVANIZED CONNECTION HARDWARE, REMOVE SLAG, WIRE
BRUSH, AND APPLY THREE COATS OF Z.R.C. COLD GALVANIZING.
3. INSTALL INSERTS AND ANCHORS IN CONCRETE FOR SUSPENDING MECHANICAL AND
ARCHITECTURAL ITEMS WHERE FEASIBLE. IF ADDITIONAL FASTENERS ARE NEEDED IN
CONVENTIONALLY REINFORCED CONCRETE, USE DRILLED-IN TYPE ANCHORS LOCATED
TO AVOID CONFLICT WITH REINFORCEMENT. DO NOT USE DRILLED-IN ANCHORS OR
POWER DRIVEN FASTENERS IN POST-TENSIONED CONCRETE UNLESS APPROVED BY
ENGINEER.
4. NO ALUMINUM CONDUIT OR PRODUCTS CONTAINING ALUMINUM OR ANY OTHER
MATERIAL INJURIOUS TO THE CONCRETE SHALL BE EMBEDDED IN CONCRETE.
C. JOINTS
1. PROVIDE A 3/4 INCH CHAMFER ON EXPOSED CORNERS OF CONCRETE UNLESS
OTHERWISE INDICATED ON DRAWINGS. TOP EDGES OF WALLS MAY BE TOOLED.
2. TOOL SLAB JOINTS AT THE TIME OF FINISHING. SAW CUTTING IS NOT ALLOWED UNLESS
SPECIFICALLY CALLED FOR ON DRAWINGS OR APPROVED BY ENGINEER.
3. CAST WALLS WITH CONSTRUCTION AND CONTROL JOINTS AT 20 FEET ON CENTER
MAXIMUM UNLESS NOTED ON DRAWINGS.
4. CAST SLAB ON GRADE WITH CONSTRUCTION AND CONTROL JOINTS IN STRIPS 20 FEET
BY 100 FEET MAXIMUM UNLESS NOTED OTHERWISE ON DRAWINGS.
5. CONSTRUCTION JOINTS FOR SUPPORTED SLABS SHALL BE AS NOTED ON DRAWINGS OR
AS APPROVED BY THE ENGINEER.
6. PROVIDE WATERSTOPS IN CONSTRUCTION JOINTS IN CAST-IN-PLACE CONCRETE
ELEMENTS THAT HAVE ONE SIDE EXPOSED TO THE WEATHER OR SOIL AND OTHE OTHER
SIDE ADJACENT TO ENCLOSED SPACE. REFER TO DRAWINGS FOR OTHER
WATERPROOFING AND DAMPPROOFING DETAILS.
D. GENERAL
1. THE USE OF CHLORIDES SUCH AS DEICING SALTS ARE PROHIBITED FOR USE OF MELTING
ICE PRIOR TO PLACEMENT OF CONCRETE.
DIVISION 04 - MASONRY
4.1 ALL DESIGN AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE FOLLOWING:
A. ACI 530-13
B. ACI 530.1-13
C. REFER TO SPECIFICATION SECTION 042000 FOR INFORMATION NOT LISTED HEREIN
4.2 CONCRETE UNIT MASONRY
A. HOLLOW AND SOLID LOAD-BEARING UNITS ASTM C 90, GRADE N, TYPE I.
B. NET AREA COMPRESSIVE STRENGTH OF CONCRETE MASONRY UNITS 2800 PSI.
C. NET AREA COMPRESSIVE STRENGTH OF MASONRY F'M = 2000 PSI.
D. REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATING REQUIREMENTS.
4.3 MORTAR
A. MORTAR, ASTM C 270, TYPE S, MINIMUM COMPRESSIVE STRENGTH 1800 PSI.
4.4 GROUT
A. GROUT, ASTM C 476, F'C = 2000 PSI.
4.5 REINFORCING STEEL
A. REFER TO SPECIFICATION SECTION 041500 FOR REINFORCING STEEL
4.6 MASONRY ACCESSORIES
A. JOINT REINFORCEMENT, ASTM A 82 9-GAGE GALVANIZED LADDER TYPE AT 16 INCHES O.C.
B. ANCHORS AND TIES:
1. SLOTS, 20 GAGE GALVANIZED
2. ANCHORS, 3/16 INCH DIAMETER WIRE TIE WITH 12 GAGE DOVETAIL
C. CONTROL JOINTS SOLID RUBBER OR PVC STRIPS
D. BOND BREAKER 15 LB ROOFING FELT.
E. MEMBRANE FLASHING 20 MIL PVC.
4.7 GENERAL - MASONRY
A. MASONRY CONTROL JOINTS SHALL BE SPACED AS FOLLOWS OR AS INDICATED ON DRAWINGS:
1. MAXIMUM OF 4 FEET FROM CORNERS
2. MAXIMUM OF 24 FEET O.C.
3. AT ALL CHANGES IN WALL HEIGHT OR THICKNESS
4. AT ABUTMENT OF WALLS TO COLUMNS
5. ALIGN JOINTS IN MASONRY W/ JOINTS IN SUPPORTING CONCRETE WALL WHERE
APPLICABLE
B. BOND BEAMS SHALL BE FILLED WITH GROUT AND REINFORCED WITH A MINIMUM OF TWO #4
CONTINUOUS OR AS INDICATED ON DRAWINGS. WHERE BOND BEAMS INTERSECT AT CORNERS
AT DIFFERENT ELEVATIONS, RUN EACH BOND BEAM AROUND CORNER FOR TWO BLOCK
LENGTHS MINIMUM BEFORE TERMINATING.
C. LINTELS SHALL HAVE A MINIMUM BEARING OF 6 INCHES.
D. MAINTAIN A 1 INCH GAP BETWEEN THE TOP OF ALL NON-BEARING INTERIOR MASONRY WALLS
AND THE UNDERSIDE OF STRUCTURE ABOVE.
DIVISION 05 - METALS
5.1 ALL DESIGN AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE FOLLOWING:
A. AISC 360-10
B. AISC 341-10
C. REFER TO SPECIFICATION SECTION 051200 FOR INFORMATION NOT LISTED HEREIN
5.2 W-SHAPES, ASTM A 992, GRADE 50
5.3 CHANNELS ANGLES, M-SHAPES, S-SHAPES, ASTM A 36
5.4 PLATES AND BARS, ASTM A 36
5.5 CORROSION-RESISTING STRUCTURAL STEEL, ASTM A 588, GRADE 50
5.6 COLD-FORMED STEEL TUBING, ASTM A 500, GRADE B OR C
5.7 CORROSION-RESISTING COLD-FORMED STEEL TUBING, ASTM A 847
5.8 STEEL PIPE, ASTM A 53, TYPE E OR S, GRADE B STANDARD WEIGHT.
5.9 ALL WELDING SHALL BE MADE WITH E70XX LOW HYDROGEN ELECTRODES AND SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN WELDING SOCIETY SPECIFICATIONS. ALL WELDS SHALL BE
PERFORMED BY AN AWS CERTIFIED WELDER.
5.10 BOLTED CONNECTIONS SHALL BE MADE USING ASTM A 325-N 3/4 INCH DIAMETER HIGH STRENGTH
BOLTS, NUTS, AND WASHERS BEARING TYPE CONNECTION WITH THREADS INCLUDED IN SHEAR
PLANE, OR ASTM A 325-SC FOR SLIP CRITICAL CONNECTIONS OR AS INDICATED OTHERWISE ON
DRAWINGS.
5.11 ANCHOR BOLTS, ASTM F 1554 GRADE 36
A. NUTS, ASTM A 563 HEAVY HEX CARBON STEEL
B. PLATE WASHERS, ASTM A 36
C. WASHERS, ASTM F 436
D. FINISH, HOT-DIP ZINC COATING, ASTM A 153 CLASS C
5.12 CONNECTIONS NOT DETAILED ON DRAWINGS SHALL BE DESIGNED BY FABRICATOR IN ACCORDANCE
WITH AISC SPECIFICATIONS
5.13 USE STANDARD AISC DOUBLE ANGLE CONNECTIONS WHERE POSSIBLE. SHOP CONNECTIONS NOT SPECIFICALLY DETAILED ON DRAWINGS SHALL BE BOLTED OR WELDED. FIELD CONNECTIONS SHALL
BE BOLTED UNLESS SPECIFICALLY DETAILED OTHERWISE.
5.14 WHEN NO REACTIONS ARE INDICATED, DESIGN CONNECTIONS TO SUPPORT A REACTION VALUE EQUAL TO ONE HALF THE AISC TABULATED ALLOWABLE UNIFORM LOAD VALUE (6 KIPS MINIMUM)
5.15 NO SPLICES IN COLUMNS WILL BE PERMITTED UNLESS SPECIFICALLY NOTED ON DRAWINGS
DIVISION 05A - MISCELLANEOUS METALS
5A.1 ALL DESIGN AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE FOLLOWING:
A. AISC 360-10
B. AISC 341-10
C. REFER TO SPECIFICATION SECTION 055700 FOR INFORMATION NOT LISTED HEREIN
5A.2 W-SHAPES, ASTM A 992, GRADE 50
5A.3 CHANNELS ANGLES, M-SHAPES, S-SHAPES, ASTM A 36
5A.4 PLATES AND BARS, ASTM A 36
5A.5 STAINLESS STEEL SHEET STRIP, PLATE, AND FLAT BARS, ASTM A 666, TYPE 304
5A.6 STAINLESS STEEL BARS AND SHAPES, ASTM A 276, TYPE 304
5A.7 STEEL PIPE, ASTM A 53, TYPE E OR S, GRADE B STANDARD WEIGHT.
5A.8 COLD-FORMED STEEL TUBING, ASTM A 500, GRADE B OR C
5A.9 ALL WELDING SHALL BE MADE WITH E70XX LOW HYDROGEN ELECTRODES AND SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN WELDING SOCIETY SPECIFICATIONS. ALL WELDS SHALL BE
PERFORMED BY AN AWS CERTIFIED WELDER.
5A.10 BOLTED CONNECTIONS SHALL BE MADE USING ASTM A 325 HIGH STRENGTH BOLTS OR ASTM A 307, GRADE A, CARBON STEEL BOLTS
5A.11 ANCHOR BOLTS, ASTM F 1554 GRADE 36
A. NUTS, ASTM A 563 HEAVY HEX CARBON STEEL
B. PLATE WASHERS, ASTM A 36
C. WASHERS, ASTM F 436
5A.12 BARRIER STRAND, 1/2 INCH DIAMETER SEVEN-WIRE LOW-RELAXATION TYPE GALVANIZED BARRIER
STRAND, 270 KSI
5A.13 SURFACE FINISH FOR STEEL MISCELLANEOUS METAL WORK SHALL BE:
DESCRIPTION SURFACE FINISH
SHELF ANGLES AND EMBEDS HOT-DIP GALVANIZED
LINTELS HOT-DIP GALVANIZED
PIPE BOLLARDS HOT-DIP GALVANIZED
MASONRY WALL SUPPORTS AND EMBEDS HOT-DIP GALVANIZED
BARRIER STRAND HARDWARE AND EMBEDS HOT-DIP GALVANIZED
MISC FRAMING EXPOSED TO WEATHER HOT-DIP GALVANIZED
MISC FRAMING NOT EXPOSED TO WEATHER HOT-DIP GALVANIZED
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
7.1 CONCRETE SEALER
A. CONCRETE SEALER SHALL BE APPLIED TO ALL SLAB ON GRADE AND SUPPORTED SLAB
SURFACES AND EXTENDED UP VERTICAL SURFACES 24 INCHES.
7.2 TRAFFIC-BEARING MEMBRANE (DECK COATING)
A. TRAFFIC-BEARING MEMBRANE SHALL BE HEAVY DUTY AND APPLIED TO SUPPORTED SLAB
SURFACES AND EXTENDED UP VERTICAL SURFACES 4 INCHES, INCLUDING WALLS, PANELS,
COLUMNS, CURBS, PIPES, ETC., AS INDICATED ON DRAWINGS.
7.3 JOINT SEALANTS
A. ALL JOINTS BETWEEN STRUCTURAL (AND ARCHITECTURAL) MEMBERS SHALL BE PROPERLY
PREPARED AND FILLED WITH JOINT SEALANT UNLESS NOTED OTHERWISE. ALL JOINT EDGES,
INCLUDING TOP AND BOTTOM SURFACES AND VERTICAL AND HORIZONTAL SURFACES, SHALL
BE FORMED OR TOOLED AS REQUIRED. JOINT SEALANT SHALL BE APPLIED ONLY TO TOP,
VERTICAL, AND HORIZONTAL SURFACES UNLESS NOTED OTHERWISE ON DRAWINGS.
B. JOINTS TO BE PREPARED AND FILLED WITH JOINT SEALANT SHALL INCLUDE BUT ARE NOT
LIMITED TO, CONSTRUCTION JOINTS, CONTROL JOINTS, ISOLATION JOINTS, AND ALL
INTERFACE JOINTS BETWEEN SIMILAR AND DISSIMILAR MEMBERS. SPECIFIC LOCATIONS MAY
BE INDICATED ON DRAWINGS OR MAY BE REQUIRED BY SHOP DRAWINGS OR MAY OCCUR DUE
TO CONSTRUCTION SEQUENCE SELECTED BY CONTRACTOR.
DIVISION 31 - EARTHWORK
31.1 FOUNDATION DESIGN CAPACITIES
DESCRIPTION CAPACITY
A. SPREAD FOOTINGS 5000 PSF (NET)
31.2 SOIL LATERAL LOADS
A. ACTIVE PRESSURE 50 PSF/FT
B. AT-REST PRESSURE 70 PSF/FT
C. PASSIVE PRESSURE 325 PSF/FT
31.3 GENERAL - SITE WORK
A. FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE RECOMMENDATIONS OF
GEOTECHNICAL INVESTIGATION PROPOSED VA HOSPITAL PARKING GARAGE EAST OF 975 KIRMAN
AVENUE RENO, NEVADA, DATED MAY 23, 2017, PREPARED BY PEZONELLA ASSOCIATES, INC.
B. ALL FOUNDATION BEARING TO BE ON UNDISTURBED NATURAL SOIL CONSISTING OF
NON-EXPANSIVE GRANULAR NATIVE MATERIAL. WHERE UNSUITABLE MATERIAL IS
ENCOUNTERED AT PROPOSED FOUNDATION BEARING, THE UNSUITABLE MATERIAL SHALL BE
REMOVED AND REPLACED WITH FLOWABLE FILL WITH A MIN COMPRESSIVE STRENGTH OF 100
PSI. ON SITE GEOTECHNICAL ENGINEER SHALL REVIEW ALL FOUNDATION BEARING
CONDITIONS PRIOR TO CASTING FOUNDATION CONCRETE.
C. PROOF ROLL AND PLACE ENGINEERED FILL IN ACCORDANCE WITH SOILS INVESTIGATION
REPORT. SLAB ON GRADE TO BE ON 24 INCHES MINIMUM OF COMPACTED GRANULAR SUBBASE.
D. ALL MATERIALS TO BE COMPACTED MODIFIED PROCTOR ASTM D 1557. TESTING LABORATORY TO VERIFY ADEQUACY OF SUBGRADE PREPARATION, FILL MATERIAL AND COMPACTION AS FOLLOWS:
1. BUILDING SLABS SUPPORTED ON GRADE: 95%
2. PAVING AND WALKS: 95%
3. AREAS OF GENERAL GRADING AND EXTERIOR MECHANICAL AND ELECTRICAL
BACKFILLING: 95%
E. SUBGRADE IF FROZEN SHALL BE REMOVED AND REPLACED.
F. ALL FOUNDATIONS, EARTHWORK, EXCAVATION, BACKFILL, AND SUBGRADE DRAINAGE SHALL
BE SUBJECT TO OBSERVATION BY GEOTECHNICAL ENGINEER, WHOSE APPROVAL IS REQUIRED
PRIOR TO PLACEMENT OF CONCRETE. COORDINATE SCHEDULE TO FACILITATE OBSERVATION.
G. DETERMINE IN FIELD HORIZONTAL AND VERTICAL LOCATION OF ANY EXISTING UTILITY LINES
AND/OR APPURTENANCES AND ADVISE ENGINEER OF ANY CONFLICTS WITH NEW STRUCTURE
PRIOR TO CONSTRUCTION. DO NOT DESTROY ANY EXISTING UNDERGROUND STRUCTURES
UNLESS AUTHORIZATION IS OBTAINED PRIOR TO CONSTRUCTION.
H. MAINTAIN SAFETY IN CONNECTION WITH EARTH SLOPES CAUSED BY TRENCHING, EXCAVATION, AND/OR FILL DURING CONSTRUCTION. WHERE HEIGHT OF SUCH SLOPES WILL EXCEED 8 FEET, SUBMIT FOR RECORD A DETAILED PLAN INDICATING DESIGN OF SOIL RETENTION SYSTEM
WHICH WILL BE IMPLEMENTED (SUCH AS SHEETING AND SHORING OR OTHER METHODS),
PREPARED, SIGNED, AND SEALED BY A GEOTECHNICAL AND/OR STRUCTURAL ENGINEER
REGISTERED IN STATE WHICH PROJECT IS LOCATED.
I. ANY UNUSUAL SOIL CONDITIONS (WATER, SOFT LAYERS, ODORS, ETC.) ENCOUNTERED DURING
EXCAVATION FOR FOUNDATIONS SHOULD BE IMMEDIATELY BROUGHT TO ATTENTION OF
GEOTECHNICAL ENGINEER.
ABBREVIATIONS
ADDL = ADDITIONAL
ALT = ALTERNATE
ARCH = ARCHITECTURAL
BO ___ = BOTTOM OF ___
BOT = BOTTOM
BRG = BEARING
CIP = CAST-IN-PLACE CONCRETE
CJ = CONSTRUCTION JOINT
CLR = CLEAR
CMU = CONCRETE MASONRY UNIT
COL = COLUMN
CONC = CONCRETE
CONN = CONNECTION
CONT = CONTINUOUS
DBA = DEFORMED BAR ANCHOR
DET = DETAIL
DIA = DIAMETER
DIAPH = DIAPHRAGM
DWL = DOWEL
EA = EACH
EC = EPOXY COATED
EE = EACH END
EF = EACH FACE
EL = ELEVATION
ELEC = ELECTRICAL
ELEV = ELEVATOR
EQ = EQUAL
EW = EACH WAY
EXIST = EXISTING
EXP = EXPANSION
FD = FLOOR DRAIN
FDN = FOUNDATION
FT = FOOT
FTG = FOOTING
GA = GAUGE
GALV = GALVANIZED
GC = GENERAL CONTRACTOR
GGBS = GROUND GRANULATED BLAST-FURNACE SLAG
HK = HOOK
HORIZ = HORIZONTAL
HSA = HEADED STUD ANCHOR
IP = INFLECTION POINT
JT = JOINT
LT WALL = LIGHT WALL
MECH = MECHANICAL
MFR = MANUFACTURER
MIN = MINIMUM
NOM = NOMINAL
NSNS = NON-SHRINK, NON-STAIN
NTS = NOT TO SCALE
OC = ON CENTER
OH = OPPOSITE HAND
PCC = PRECAST CONCRETE
PT = POST-TENSIONED
REINF = REINFORCING
REQD = REQUIRED
SECT = SECTION
SIM = SIMILAR
SOG = SLAB ON GRADE
SPEC = SPECIFICATION
SS = STAINLESS STEEL
STD = STANDARD
STL = STEEL
TO ___ = TOP OF ___
TOB = TOP OF BEAM
TOC = TOP OF CONCRETE
TOF = TOP OF FOUNDATION
TOS = TOP OF SLAB
TOW = TOP OF WALL
TEMP = TEMPERATURE
TYP = TYPICAL
UNO = UNLESS NOTED OTHERWISE
VERT = VERTICAL
VIF = VERIFY IN FIELD
W/ = WITH
WWF = WELDED WIRE FABRIC
ZRC = ZINC RICH COATING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Architect / Civil Engineer:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Structural Engineers: E/T Engineers:
CARL WALKER INC.
8910 Purdue Rd.
Suite 400 Indianapolis, IN 46268
Tele: 317.735.3349 POC: Doug Gannon
P.K. ELECTRICAL INC.
681 Sierra Rose Drive Suite B Reno, NV 89511
Tele: 775.826.9010 POC: Jason Aviles
M/P Engineers:
AINSWORTH ASSOCIATES
1420 Holcomb Avenue Suite 201 Reno, NV 89502
Tele: 775.329.9100 POC: Roger Gravelle
GUIDON DESIGN INC.
905 North Capitol Avenue Suite 100 Indianapolis, IN 46204
Tele: 317.800.6388 POC: Stacey Paul
NOT SPRINKLERED
D R e v it U s e r
F ile s \N
-2
-2
-C
W I-
V e r1 d a n .b ro w n L D
P W
Z .r v t
/5
/2
:0 :1
P
M
RENO, NV
SI001
GENERAL NOTES -STRUCTURAL PARKING GARAGE DESIGN 654-250
2018/03/05 DPG DEB
BID DOCUMENTS
C. Patrick Cassady, CORRevisions: Date:
VHARENCASSAC
Oval
| Sheets |
| AP101 - LEVEL 1 PLAN - ARCHITECTURAL PARKING |
| AP102 - LEVEL 2 PLAN - ARCHITECTURAL PARKING |
| AP103 - LEVEL 3 PLAN - ARCHITECTURAL PARKING |
| AP104 - LEVEL 4 PLAN - ARCHITECTURAL PARKING |
| AP501 - STRIPING AND PAINTED GRAPHICS - ARCHITECTURAL PARKING |
| AP511 - SIGN MOUNTING & SIGN DETAILS - ARCHITECTURAL PARKING |
| SB100 - FOUNDATION PLAN - STRUCTURAL |
| SB501 - SLAB ON GRADE & FOUNDATION DETAILS - STRUCTURAL |
| SB502 - FOUNDATION DETAILS - STRUCTURAL |
| SB503 - FOUNDATION DETAILS - STRUCTURAL |
| SB601 - FOUNDATION SCHEDULE AND TYPICAL DETAILS - STRUCTURAL |
| SF101 - LEVEL 1 PLAN - STRUCTURAL |
| SF102 - LEVEL 2 PLAN - STRUCTURAL |
| SF103 - LEVEL 3 PLAN - STRUCTURAL |
| SF104 - LEVEL 4 PLAN - STRUCTURAL |
| SF301 - BUILDING SECTIONS - STRUCTURAL |
| SF401 - EAST STAIR ENLARGED PLANS - STRUCTURAL |
| SF402 - WEST STAIR-ELEVATOR ENLARGED PLANS - STRUCTURAL |
| SF511 - CIP COLUMN DETAILS - STRUCTURAL |
| SF521 - POST-TENSIONED FRAMING DETAILS - STRUCTURAL |
| SF522 - POST-TENSIONED FRAMING DETAILS - STRUCTURAL |
| SF531 - PT SLAB DETAILS - STRUCTURAL |
| SF541 - WATERPROOFING DETAILS - STRUCTURAL |
| SF551 - STANDARD & MISCELLANEOUS DETAILS - STRUCTURAL |
| SF561 - ENLARGED PLAN DETAILS - STRUCTURAL |
| SF562 - ENLARGED PLAN DETAILS - STRUCTURAL |
| SF611 - CIP COLUMN SCHEDULE - STRUCTURAL |
| SF622 - PT BEAM & GIRDER DETAILS - STRUCTURAL |
| SF631 - RC BEAM SCHEDULES & DETAILS - STRUCTURAL |
| SI001 - GENERAL NOTES -STRUCTURAL |
| SI002 - GENERAL NOTES -STRUCTURAL |
File details come from the government source that posted it. Updated .