PIMC operates four Galaxy/Hollister Whitney traction elevators (4,000-pound capacity, 350 feet per minute speed) across two shafts in a five-story hospital tower built in 1970. Two elevators serve staff only (requiring PIV access cards) and two serve patients. The contract awardee shall provide certified or licensed elevator mechanics to perform monthly preventative maintenance per ASME A17.1/CSA B44 (2010) standards, including examination, lubrication, adjustment, repair, and replacement of all elevator system components such as machines, drives, motors, governors, sheaves, counterweights, safety mechanisms, hoist ropes, relays, controllers, limit switches, door operators, and associated electrical and lighting systems. The contractor must conduct six-month periodic inspections and annual testing per Appendix N of the ASME code, performed by a QEI-1 certified inspector, with written documentation of all findings and corrective actions. Monthly written records of firefighter emergency operations tests per NFPA 101 (2012) are required. Service support includes up to 25 hours annually for non-emergency calls during regular business hours (defined as at least one working elevator), up to 15 emergency hours with mandatory two-hour response time (zero working elevators), and up to 10 after-hours response hours. The contractor shall provide parts up to $25,000 per option year to correct deficiencies discovered during maintenance and service visits. The contract performance period consists of a base year and four one-year renewal options, with Douglas Barber (602-263-1539, douglas.barber@ihs.gov) designated as the Contracting Officer's Representative.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INDIAN HEALTH SERVICE
PHOENIX INDIAN MEDICAL CENTER
Statement of Work
Background The Phoenix Indian Medical Center (PIMC) is a 1.2M SF campus comprised of a hospital tower and numerous outpatient care and support buildings. The campus is located at 4212 North 16th Street, Phoenix, Arizona 85016. The PIMC hospital tower (Building 233) is a five-story, Joint Commission (TJC) accredited, 127-bed hospital employing 1,200 staff that primarily serves a patient population of 140,000 Native Americans in the Phoenix metropolitan area. The hospital tower was built in 1970 and is approximately 163,000 SF.
This is a federal facility on federal property and the authority having jurisdiction (AHJ) is not the City of Phoenix. The AHJ is the Phoenix Area Indian Health Service Director of the Office of Environmental Health and Engineering. There are four (4) total elevator cars operating in two (2) elevator shafts in the main tower of the hospital. The elevator shaft on the west side houses two (2) cars that serve staff only (PIV access card required to operate – Cars #1 and #2) and the elevator shaft on the and east side houses two (2) elevator cars that serve patients (Car #3 and #4). The elevator mechanical room is accessed on the tower roof in the penthouse above the 5th floor of the hospital tower.
Each car is manufactured by Galaxy/Hollister Whitney, is geared, and is rated at 4,000 pounds with a speed of 350. The controller is a Galaxy IV Traction elevator controller. Each car is operated by a 50 HP Nidec Elevator System Type E motor running on 3-phase power.
Objective The objective of this contract is to provide PIMC with services to ensure the hospital’s elevators are maintained and reliable by providing the following services:
1) To perform Preventative Maintenance (PMs) for elevators per ASME A17.1/CSA B44, Safety Code for Elevators and Escalators (2010).
2) To performing PM tests and inspections at frequencies specified in Appendix N ASME A17.1/CSA B44, Safety Code for Elevators and Escalators (2010)
3) To perform service calls for elevator repair at regular hour rates
4) To perform service calls for elevator repair at emergency rates
5) To perform service calls for elevator repair after hour rates
6) To coordinate with fire alarm contractors for access to elevator shafts
7) To perform monthly test of firefighter’s emergency operations and written record of findings per
NFPA 101 (2012) 9.4.3 and 9.4.6
8) To provide parts necessary up to $25,000 per option year to correct deficiencies found during PM and service visits.
All technicians performing elevator maintenance or repairs shall be licensed or certified elevator mechanics. All required inspections, such as the 6 month ASME A17.1 Appendix N inspection, shall be be performed by an inspector certified by an organization accredited by ASME in accordance with the requirements of ASME QEI-1.
Period of Performance Contract performance shall be for a base year and four (4) one (1) year option for renewal. If the Government exercises its option pursuant to FAR 52.217-9, “Option to extend the term of the contract”, the performance period will be extended in accordance with the following schedule:
Contract Awardee Responsibilities & Tasks
1) Utilize a certified or licensed elevator mechanic to provide a monthly PM service to examine, lubricate, adjust, and when conditions warrant, to repair or replace the components of the traction elevator system listed below.
a. Machines, Drives, Motors, Governors, Sheaves, Counterweights, Safety Mechanisms, Hoist Ropes, Relays, Motor Starters, Fuses, Transformers, Contacts, Circuit Boards, Limit Switches, Door Operators and Belts, Gibs, Door Closers and Door Protective Devices, Emergency Lighting, Car and Hall Position Indicators, Lobby Control Panels, fireman's service key switches. Re-lamping of signal fixtures is included during preventive maintenance visits
2) Provide a monthly written record of monthly firefighters’ emergency operation test.
3) QEI-1 certified inspector to perform all required periodic inspections as outlined in Appendix N of ASME A17.1/CSA B44, Safety Code for Elevators and Escalators (2010), and provide written records of inspection. Written records submitted shall include date of inspections, components or systems that have not been inspected, and code deficiencies noted during the inspection along with a statement of corrective action taken if any.
Per Appendix N, every six months the following are to be inspected:
4) Utilize a licensed or certified elevator mechanic to perform all required periodic tests as outlined in Appendix N of ASME A17.1/CSA B44, Safety Code for Elevators and Escalators (2010), and provide written records of tests performed. Written records submitted shall include date of test, type of test(s) performed, detailed results of the test(s) including but not limited to, speed, governor trip speed, safety slide distance, relief valve setting, escalator/moving walk brake torque setting, etc. Code deficiencies found during the test are to be noted in the report along with any corrective action taken.
Per Appendix N the following are to be tested annually:
• Oil Buffers
• Safeties
• Governors
• Slack-Rope Devices on Winding Drum Machines
• Normal and Final Terminal Stopping
• Standby or emergency power operation
• Power operation of door system
• Broken Rope/Tape/Chain Switch
• E/E/PES electrical protective devices
• Ascending Car Overspeed Protection and Unintended Car Movement
• Traction loss detection means
• Broken-Suspension Member and residual-strength detection means
5) Contractor shall provide up to 25 of non-emergency service visit hours per year during regular business hours. Non-Emergency calls are defined as calls where there is at least 1 of the 4 elevators at the hospital working.
6) Contractor shall provide up to 15 emergency service hours defined as having no working elevators at the hospital. Contractor is required to respond within 2 hours of an emergency call.
7) Contractor shall provide up to 10 hours of after hours response.
8) Contractor to provide parts necessary to correct deficiencies found during service visits.
Contracting Officer’s Representative (COR) The person identified below is hereby designated as the Contracting Officer's Representative (COR) for this contract.
Contacts: Douglas Barber 602-263-1539 douglas.barber@ihs.gov mailto:douglas.barber@ihs.gov
| Statement of Work |
| Background |
| The Phoenix Indian Medical Center (PIMC) is a 1.2M SF campus comprised of a hospital tower and numerous outpatient care and support buildings. The campus is located at 4212 North 16th Street, Phoenix, Arizona 85016. The PIMC hospital tower (Building 2... |
| This is a federal facility on federal property and the authority having jurisdiction (AHJ) is not the City of Phoenix. The AHJ is the Phoenix Area Indian Health Service Director of the Office of Environmental Health and Engineering. There are four (4)... |
| Each car is manufactured by Galaxy/Hollister Whitney, is geared, and is rated at 4,000 pounds with a speed of 350. The controller is a Galaxy IV Traction elevator controller. Each car is operated by a 50 HP Nidec Elevator System Type E motor running o... |
| Objective |
| Period of Performance |
| Contract Awardee Responsibilities & Tasks |
| Contracting Officer’s Representative (COR) |