Attachment 3 Quality specifications.docx

DOCX document 31 KB Posted

Attached to
RFQ: Multiple Award IDIQ for Liquefied Natural Gas (LNG) to Naval Station Guantanamo Bay (NSGB)
Solicitation number
N6945026QPW13
Issued by

About this file

This is a Quality Specifications attachment for Liquefied Natural Gas (LNG) supplies to be delivered under contract to Naval Station Guantanamo Bay in support of a natural gas-powered combined cycle power plant. The specification establishes composition requirements, contaminant standards, and documentation requirements for LNG deliveries.

LNG product must conform to federal, state, and local environmental requirements applicable at the delivery location, including compliance with Title V Clean Air Act Permits, with the contractor required to meet the more stringent requirement if conflicts exist. The specification defines three composition profiles (Rich, Lean, and Average) with component limits including methane (minimum 92.000 mol%), ethane (maximum 8.000 mol%), propane (maximum 2.500 mol%), and other trace components. Product must meet minimum heating value requirements of 1,000 Btu/scf (Higher Heating Value) and 900 Btu/scf (Lower Heating Value), maintain a minimum Wobbe Index of 1,350 Btu/scf, and contain hydrogen sulfide not exceeding 0.25 grains per 100 scf and total sulfur not exceeding 1.35 grains per 100 scf. Delivered LNG must be free of contaminants, water, and solid matter affecting product quality. Contractors must provide comprehensive manifests and discharge reports documenting supplier information, delivery location, quantity (in cubic meters and metric tons), time logs from arrival through vessel departure, custody transfer measurements including gas meter readings and LNG temperatures, complete composition analysis by component, and physical properties including density and heating values at specified conditions.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 3 Quality Specifications Liquefied Natural Gas

Supplies delivered under this contract shall conform to all Federal, State, and local environmental requirements applicable to the geographic location of the receiving activity on the date of delivery. This includes delivery of fuel and documentation in a manner consistent with existing or future Title V (Clean Air Act) Permits. In the event that a Federal, State, or local environmental requirement is more stringent than a similar requirement in the specification contained in this contract, the Contractor shall deliver product that complies with the more stringent requirement. Product that fails to meet the more stringent environmental requirement will be considered to be a nonconforming supply. All supplies furnished under this contract shall fully meet the requirements of the applicable specification(s) as cited below. In the event that compliance with the more stringent requirement causes the contractor to incur additional costs, the contractor may request an equitable adjustment.

NATIONAL STOCK NUMBER
PRODUCT NOMENCLATURE
ENERGY PRODUCT CODE
6830-01-672-6379
Liquefied Natural Gas
LNG

a) LIQUEFIED NATURAL GAS

(1) Composition of product shall conform to the table listed below:

Component
Units
Rich

Composition Lean Composition Average Composition Suggested Limits for LNG when converted into gaseous state

Nitrogen
mol%
0.486
0.713
0.495
1,500 maximum
Methane
mol%
89.299
97.682
96.605
92.000 minimum
Ethane
mol%
7.601
1.342
2.476
8.000 maximum
n-Propane
mol%
1.832
0.171
0.270
2.500 maximum

Maximum butane and heavier (C4+)

2.000 maximum

i-Butane
mol%
0.359
0.035
0.059
See C4+
n-Butane
mol%
0.280
0.027
0.050
See C4+
i-Pentane
mol%
0.073
0.015
0.016
See C4+
n-Pentane
mol%
0.035
0.008
0.012
See C4+
Hexane
mol%
0.031
0.001
0.011
See C4+
Carbon Dioxide
mol%
0.0005
0.005
0.005
0.010 maximum
Hydrogen
mol%
-
-
-
Trace
Oxygen
mol%
-
-
-
Trace
Molecular Weight
lb/lb mol
18.03
16.40
16.59
-
Higher Heating Value
Btu/scf
1,109
1.017
1,031
1,000 minimum
Lower heating Value
Btu/scf
1,002
917
930
900 minimum
Wobbe Index (59 deg. F, 14.696 psia)
Btu/scf (HHV)
1,406
1.351
1,362
1,350 minimum
Methane Number (AVL calculation)
_
73

75 minimum

Hydrogen Sulfide
Grains per 100 scf
-
-
-
0.25 maximum
Sulfur
Grains per 100 scf
-
-
-
1.35 maximum

(2) Delivered LNG shall contain no contaminants, water or solid matter that may affect product quality.

Manifest and/or LNG Discharge Report

At a minimum, the manifest/discharge report provided to the Government afetr the delivery shall contain the following.

General Information

· Supplier’s Name

· Supplier’s Vessel

· Location of Delivery

· Receiver

· Receiver Vessel

· Cargo Reference Number

Quantity Delivered

· Volume in cubic meters

· Mass in metric tons

· Gross Energy in MM BTU

· Vapor Displaced in MM BTU

· Net Energy in MM BTU

· Net Energy in MWh

Time Log (Date and time)

· Arrival at Pilot Station

· Arrival at STS Location

· Notice of Readiness Tendered

· Vessel All Fast

· Cargo Arm/Hoss Connected

· Commenced Transfer

· Completed Transfer

· Cargo Arm/Hose Disconnected

· Vessel Sailed.

Custody Transfer Measurements

· Gas Meter Reading at OCT in kg

· Gas Meter Reading at CCT in kg

· LNG temperature before Transfer in degrees C

· LNG Volume OCT in cubic meters

· LNG Volume CCT in cubic meters

· Vapor temperature in degrees C

· Vapor Pressure CCT in MPa

LNG Composition

· Methane in mol%

· Ethane in mol%

· Propane in mol%

· iso-Butane in mol%

· n-Butane in mol%

· Iso-Pentane in mol%

· n-Pentane in mol%

· n-Hexane in mol%

· Nitrogen in mol%

· Oxygen in mol%

· Carbon Dioxide in mol%

· Sulpher in mol%

Physical Properties

· LNG Density at –157.2 C in kg per cubic meter

· Gross Heating Value (mass) at 60 deg. F in btu per kg

· Gross Heating Value (volume) at 60 deg. F in BTU per scf

· Wobbe Index at 60 deg. F. in BTU per scf.

End of Attachment 3.