Attachment 3 DWGS FINAL_Proj 463-21-101.pdf

PDF 8 MB Posted

Attached to
Repair Bld Moisture Barrier Proj 463-21-101
Solicitation number
36C26026R0061_RFP
Issued by

About this file

This is a set of architectural and mechanical design drawings for the "Repair Building 100 Envelope Moisture Barrier" project at the Alaska VA Healthcare System in Anchorage, Alaska (Project Number 463-21-101). The drawings provide detailed specifications for renovation work on the building's exterior envelope and related systems.

The scope of work includes removal and replacement of existing metal panels, corrugated metal siding, and associated framing throughout multiple wall sections and penthouse areas. Key work items include: replacing air handling room penthouses (Sheet A100), removing and replacing stair 4 panel assemblies (Sheet A110), repairing the atrium curtain wall and parapet (Sheet A120), replacing glazed curtain wall sections with new construction and punched windows (Sheet A130), and addressing seismic joint and stair HVAC details (Sheet A140). Specific demolition and reconstruction tasks involve removal of metal cladding panels, louvers, flashing, and related hardware, followed by installation of new mineral wool insulation, fiberglass girt clip systems, metal studs, gypsum board substrates, and new roofing membrane connections. The mechanical work includes installation of a new cooling-only two-pipe fan coil unit (ACU-16A) in Stair 03 with chilled water piping using 50% ethylene glycol, condensate drainage, and DDC controls integrated with the existing building automation system. All work must comply with 2020 National Electrical Code, 2018 International Mechanical Code, VA Facility Standards, and applicable federal and state codes.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1t

1i

Room Name

A101

SIM

A7.01 1

A7.024

ROOM TITLE TAGBUILDING SECTION

CALLOUT MARK

DETAIL CALLOUT

MARK

EXTERIOR ELEVATION

CALLOUT MARK

INTERIOR ELEVATION

CALLOUT MARK

DOOR TAG

WINDOW TAG

WALL TYPE TAG

REFERENCE NORTH

ARROW

A101

SIM

A

A

SIZE

MOD

ALL PENTHOUSE EXTERIOR WALLS:

1. REMOVE THE EXTERIOR CORRUGATED SIDING FROM THE PERIMETER OF THE PENTHOUSE.

2. PROVIDE 3” OF RIGID INSULATION WITH FIBERGLASS FURRING STRIPS.

3. PATCH AND REPAIR THE AIR BARRIER TO REMAIN IN PLACE.

4. REINSTALL THE EXTERIOR SIDING.

5. PROVIDE VERTICAL CORNER PIECES TO CLOSE THE CORNERS.

6. PROVIDE NEW METAL COPING OVER THE WIDER WALL.

7. REFERENCE DETAILS FOR THE LOUVER AND DOOR OPENINGS.

8. REPAIR THE INTERIOR SIDE OF EXTERIOR WALLS WHERE CUTS WERE MADE IN THE GYPSUM BOARD TO INVESTIGATE THE VAPOR RETARDER. PATCH THE VAPOR RETARDER TO SEAL IT TIGHT, THEN PATCH AND REPAIR THE GYPSUM BOARD, TAPE AND PAINT.

ALL STAIRS TO/FROM ROOF/PENTHOUSE:

1. REMOVE THE DOOR AND FRAME, THE TOP LANDING STEP, AND THE GYPSUM BOARD ON THE INTERIOR.

2. REPAIR OR REPLACE THE VAPOR RETARDER.

3. PROVIDE A PIECE OF ROOFING OVER THE TOP OF THE SILL AND SEAL IT TO THE EXISTING ROOFING MEMBRANE.

4. PROVIDE A SECTION OF DOOR FRAME AT THE SILL TO MATCH SIZE OF EXISTING DOOR FRAME.

5. MODIFY THE DOOR AND FRAME TO FIT AROUND THE NEW DOOR SILL AND REINSTALL.

6. REINSTALL THE TOP LANDING.

AT LOUVERS:

1. REMOVE AND STORE THE LOUVERS.

2. REMOVE THE INTERIOR WALL FINISH UP TO 8 ’ IN ALL DIRECTIONS AROUND THE DUCT,

3. REMOVE THE DUCT INSULATION FROM THE FACE ON THE INTERIOR WALL TO A MINIMUM OF 3 ’ DOWN THE DUCT.

4. INSPECT THE WALL CAVITY FOR SIGNS OF LEAKS AND WATER DAMAGE AND SEAL GAPS AND REPLACE MATERIALS AS NECESSARY.

5. REPLACE THE WALL AND DUCT INSULATION.

6. REPLACE THE VAPOR RETARDER AND SEAL TIGHT TO EXISTING VAPOR RETARDER.

7. REINSTALL OR REPLACE THE LOUVER. LOUVERS DAMAGED DURING REMOVAL SHALL BE REPLACED WITH NEW.

1. REMOVE THE METAL PANELS AND MOUNTING FRAME FROM THE

SOUTH FACE OF THIS PENTHOUSE.

2. REMOVE AND REPLACE THE AIR BARRIER.

3. ADD 3” OF RIGID INSULATION IN FIBERGLASS FURRING STRIPS.

4. REPLACE THE METAL MOUNTING FRAME AND THE METAL PANELS

5. PROVIDE NEW VERTICAL CORNER PIECES

6. PROVIDE NEW METAL COPING AT THE TOP OF THE WALL.

7. REMOVE AND REPLACE ALL SCUPPERS ON UPPER PENTHOUSE AND

ATRIUM ROOFS

1. REMOVE THE EXTERIOR METAL PANEL SIDING FROM THE PERIMETER OF

THE ATRIUM.

2. PROVIDE 3” OF RIGID INSULATION WITH FIBERGLASS FURRING STRIPS.

3. PATCH AND REPAIR THE AIR BARRIER TO REMAIN IN PLACE.

4. REINSTALL THE EXTERIOR SIDING.

5. PROVIDE VERTICAL CORNER PIECES TO CLOSE THE CORNERS.

6. PROVIDE NEW METAL COPING OVER THE WIDER WALL. .

7. CREATE A SILL DAM USING CLOSED CELL LOW EXPANSION SPRAY FOAM

AND BACKER ROD ON TOP OF THE ROOFING MEMBRANE AT THE INTERIOR

WALL TO APPROXIMATELY ¾” IN FROM THE FACE OF THE FRAME.

8. CLEAN INSIDE AND OUTSIDE OF ALUMINUM FRAMING AND GLASS PER

MANUF. RECOMMENDATION.

AT WINDOWS 'A', 'B' AND 'C':

1. REMOVE THE ENTIRE CURTAINWALL SECTION.

2. INFILL WITH TYPICAL EXTERIOR WALL TO MATCH THE “COMPOSITE METAL

PANEL” WALL TYPE.

3. PROVIDE 2 SINGLE FIXED WINDOWS UNITS, ONE AT EACH LEVEL, AT

FRAMES 'A' AND 'C'.

4. AT FRAME 'B', REINSTALL SALVAGED DOOR AND FRAME AT FIRST LEVEL

AND NEW FIXED WINDOW AT UPPER LEVEL.

5. REBUILD THE PARAPET AND REPLACE THE COPING.

ALONG GRID W 0.0:

1. REMOVE THE CEILING ALONG THE WALL.

2. FILL SPACE AROUND BEAM AND BOTTOM OF ROOF DECK WITH CLOSED

CELL SPRAY FOAM INSULATION FROM THE TOP OF THE WINDOW HEAD

FRAME. SEAL TIGHT AT BOTTOM, TOP, AND ALL PENETRATIONS.

3. REPLACE THE CEILING WITH MATERIAL TO MATCH EXISTING (GWB OR

ACT).

4. REPLACE ALL MULLION AND FRAMING PIECES THAT ARE DEFORMED.

APPROXIMATELY 2-4 PIECES, FIELD VERIFY.

5. CLEAN OXIDATION FROM ALL INTERIOR FRAMING AND GLASS AS

RECOMMENDED BY THE MANUFACTURER.

6. REMOVE ALL EXTERIOR GLAZING FROM ENTIRE WALL AND REPLACE WITH

NEW.

AT DOOR FROM FACILITIES OFFICE TO LINK ROOF:

1. REBUILD AND REPLACE THE SEISMIC JOINT.

AT STAIR 03:

1. DISCONNECT WATER LINES TO EXISTING AHU UNIT ABOVE CEILING.

2. ABANDON UNIT IN PLACE.

3. CONNECT PLUMBING LINES TO NEW HVAC UNIT MOUNTED ABOVE DOOR

ALCOVE.

4. ADD NEW ACCESS DOOR TO CEILING IN ALCOVE.

5. PATCH HOLE IN CEILING WHERE EXISTING HVAC UNIT IS ABANDONED.

1. COORDINATE WITH ALL PLANS AND DETAILS FOR CLARIFICATIONS OF DEMOLITION

SCOPE PRIOR TO PROCEEDING.

2. GC TO COMPLY WITH BLDG. CONSTRUCTION CODES AND REGULATIONS.

3. THESE DRAWINGS ARE SUPPLIED TO THE CONTRACTOR AND OTHERS FOR THEIR

USE FOR THIS SPECIFIC PROJECT.

4. THE ORGANIZATION OF DOCUMENTS ARE NOT INTENDED TO CONTROL THE

DIVISION OF WORK. DIVISION OF WORK SHALL BE THE SOLE RESPONSIBILITY OF THE

CONTRACTOR.

5. DIMENSIONS ARE TO FACE OF FINISH AT EXISTING REMAINING WALLS, FACE OF

STUD AT NEW WALLS, OR CENTERLINE OF COLUMNS, UNLESS OTHERWISE NOTED.

6. CONTRACTOR SHALL VERIFY DIMENSIONS, REQUIRED CLEARANCES, AND POWER

AND HVAC REQUIREMENTS FOR ALL ITEMS. NOTIFY OWNERS REPRESENTATIVE OF

ANY DISCREPANCIES PRIOR TO COMMENCEMENT OF WORK.

7. DO NOT SCALE DRAWINGS; VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION.

8. FIELD VERIFY AREA OF WORK. NOTIFY ARCHITECT IMMEDIATELY OF ANY

DISCREPANCIES BETWEEN DEMOLITION SCOPE AND FIELD CONDITIONS. ALL

ELEMENTS NOT SHOWN TO BE DEMOLISHED REQUIRE ARCHITECTS REVIEW AND

APPROVAL.

9. DRAWINGS IN THIS SET USE BACKGROUND IMAGES FROM THE ORIGINAL DESIGN

DOCUMENTS FOR CLARITY OF CONTEXT OF WORK. THESE ARE FOR INFORMATION

ONLY. WORK UNDER THIS CONTRACT IS ANNOTATED WITH DIFFERENT FONT.

CONTACT ARCHITECT IF ANY DISCREPANCY IS DISCOVERED FROM INSTALLED

CONDITIONS..

10. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR DEMOLITION WORK,

INCLUDING BUT NOT LIMITED TO ALL BUILDING SERVICES, UTILITIES, DATA, TELECOM,

SECURITY, FIRE/LIFE SAFETY, AND HVAC SERVING THE BUILDING SHALL REMAIN

OPERATIONAL AND UNAFFECTED BY THE DEMOLITION. ANY DISRUPTIONS IN

SERVICES SHALL BE SCHEDULED WITH THE BUILDING MANAGEMENT OFFICE.

11. PROTECT ALL EXISTING CONSTRUCTION TO REMAIN.

12. CONTRACTOR SHALL PATCH AND REPAIR ALL DAMAGE DUE TO DEMOLITION

AND/OR NEW WORK. THIS INCLUDES WALL SUBSTRATES AND FINISHES, CEILING

MATERIALS AND FINISHES, AND FLOOR SUBSTRATES AND FINISHES. PREPARE

SURFACES TO RECEIVE NEW FINISHES IN ACCORDANCE WITH MANUFACTURE'S

RECOMMENDATIONS. WHERE NOT INDICATED OTHERWISE, REPAIR SHALL MATCH

ADJACENT SUBSTRATE, MATERIALS, TEXTURE, PATTERN, COLOR, AND FINISH. WHERE

PATCHED AREA FINISHES DO NOT MATCH EXACTLY, THE ENTIRE AREA SHALL BE

REPAIRED / REPLACED / REFINISHED TO PROVIDE A UNIFORM FINISH. ALL DAMAGE

CAUSED BY THE CONTRACTOR, WHETHER RELATED TO DEMOLITION OR NEW

CONSTRUCTION, SHALL BE REPAIRED AT THE CONTRACTOR'S EXPENSE TO MATCH

EXISTING ADJACENT FINISH CONDITION. THIS INCLUDES AREAS OF THE BUILDING

RELATED TO THE PROJECT BUT NOT DIRECTLY IN THE SCOPE OF WORK, SUCH AS LAY-

DOWN AREAS, STORAGE AREAS, AND AREAS WHERE MOVEMENT OF EQUIPMENT AND

MATERIALS TAKES PLACE.

13. EXISTING REMAINING INTERIOR WALLS AFFECTED BY THE AREA OF WORK WILL BE

FLOATED TO SMOOTH SUBSTRATE, SIMILAR TO NEW CONSTRUCTION, AND PAINTED

FLOOR TO CEILING/CORNER TO CORNER. PREPARE FOR INSTALLATION OF NEW

FINISHES PER MANUFACTURES RECOMMENDATIONS.

14. SEE MEP CONSULTANT'S SPECIFICATIONS FOR SCOPE OF DEMOLITION OF

MECHANICAL, ELECTRICAL & PLUMBING WORK.

15. FIRE PROTECTION SYSTEM MUST REMAIN FULLY OPERATIONAL DURING

CONSTRUCTION.

16. A RATED CONSTRUCTION BARRIER MUST BE PROVIDED UNLESS THE AUTHORITY

HAVING JURISDICTION (VISN SAFETY ENGINEER) CONCURS THAT THE CONSTRUCTION

WORK IS NO MORE HAZARDOUS THAN NORMAL OPERATIONS. EXISTING WALLS

CREDITED AS PART OF A RATED CONSTRUCTION BARRIER MUST BE CONFIRMED TO

EXTEND TO THE DECK ABOVE WITH ALL PENETRATIONS FIRESTOPPED. IF WALL

UPGRADES ARE REQUIRED TO ESTABLISH THE RATED CONSTRUCTION BARRIER,

IDENTIFY THIS WORK ON THIS DRAWING. WORK AREAS THAT EXPOSE BUILDING

INSULATION WITHIN THE RATED CONSTRUCTION BARRIERS MUST BE NEGATIVELY

PRESSURIZED ADJACENT TO NON-CONSTRUCTION AREAS. PROVIDE EXHAUST AIR /

NEGATIVE AIR MACHINES AS REQUIRED TO MAINTAIN PRESSURIZATION. USE OF

EXISTING HVAC SYSTEMS ALLOWED ONLY UNDER 100% EXHAUST CONDITIONS (I.E. NO

RECIRCULAITON OF SPACE EXHAUST TO THE REST OF THE FACILTY) AND WITH

PERMISSION OF THE COR. PROVIDE VISIBLE PRESSURE MONITOR PER

SPECIFICATIONS TO VERIFY PRESSURIZATION IS BEING MAINTANED.

17. REFER TO VA GUIDLINES FOR ICRA REQUIREMENTS. ICRA BARRIER

REQUIREMENTS ARE DETERMINED BY THE MEDICAL CENTER ’S INFECTION CONTROL

PROCESS. A RATED BARRIER IS REQUIRED IF THE SPRINKLERS IN THE CONSTRUCTION

AREAS REMAIN IN SERVICE, BUT CEILING REMOVAL WOULD RENDER THEM

INEFFECTIVE SUCH THAT TEMPORARY UPRIGHT SPRINKLERS WOULD HAVE TO BE

INSTALLED IF CEILING REMOVAL LASTS MORE THAN A SHIFT.

18. HAZARDOUS MATERIALS ARE NOT EXPECTED TO BE ENCOUNTERED. HOWEVER, IT

IS POSSIBLE FOR MOLD TO BE FOUND INSIDE WALLS THAT HAVE REMAINED WET. THE

PRESENCE OF MOLD IN THIS LOCATION MAY OR MAY NOT POSE HEALTH RISKS . IF

MOLD IS ENCOUNTERED DURING THE DEMOLITION PROCESS, GC SHALL CONTACT THE

VA IMMEDIATELY. THE VA WILL CONTACT AN INDUSTRIAL HYGENIST TO ASSESS THE

EXTENT OF THE PROBLEM AND RECOMMEND TREATMENT.

PREPARATION REQUIREMENTS:

CONTRACTOR SHALL SUBMIT A WORK SCHEDULE INDICATING PROPOSED SEQUENCE OF

OPERATIONS FOR SELECTIVE DEMOLITION AND CONSTRUCTION WORK TO DESIGN TEAM

AND VA FOR REVIEW. INCLUDE COORDINATION FOR SHUT OFF, CAPPING AND/OR

CONTINUATION OF UTILITY SERVICES AS REQUIRED, TOGETHER WITH DETAILS FOR

DUST AND NOISE CONTROL. PROVIDE DETAILED SEQUENCE OF DEMOLITION AND

REMOVAL WORK TO ENSURE UNINTERRUPTED PROGRESS OF OWNER'S ONSITE

OPERATIONS AND BUILDING OPERATIONS.

CONTRACTOR IS SOLELY RESPONSIBLE FOR SHORING, BRACING, OR SUPPORT TO

PREVENT MOVEMENT, SETTLEMENT OR COLLAPSE OF STRUCTURES TO BE DEMOLISHED

AND ADJACENT FACILITIES TO REMAIN. WORK SHALL BE DONE UNDER THE

SUPERVISION OF A LICENSED STRUCTURAL ENGINEER PROVIDED BY THE CONTRACTOR

AT THE PROJECT SITE. CONTRACTOR SHALL CEASE OPERATIONS AT HIS/HER

DISCRETION AND NOTIFY OWNER AND BUILDING MANAGEMENT IMMEDIATELY IF SAFETY

OF STRUCTURE APPEARS TO BE ENDANGERED. CONTRACTOR SHALL TAKE ALL

NECESSARY PRECAUTIONS AS DIRECTED BY THE CONTRACTOR'S LICENSED

STRUCTURAL ENGINEER TO SAFELY SUPPORT THE STRUCTURE UNTIL A

DETERMINATION IS MADE FOR CONTINUING THE WORK AS DIRECTED BY THE

CONTRACTOR'S LICENSED STRUCTURAL ENGINEER. CONTRACTOR IS SOLELY

RESPONSIBLE FOR DEMOLITION MEANS AND METHODS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 -

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

Blue Trident, LLC 7829 NE Esperione LN Bainbridge Island, WA 98110 Mobile: (206)972-0645 Lauri Strauss, AIA LEED AP BD&C (907) 317-5040

SPRINKLERED

C :\U se rs

\la ur i\O ne

D riv e\ d2

L- Pr oj ec ts \2

7-

1_

An ch or ag e re pa ir bl dg e nv lp \0

4- D

ES

IG

N \R

EV

IT

\2

7-

1_ re pa ir bl dg

R

EB

ID

.rv t

2/ 7/

0:

:4

AM

G1.00

COVER AND GENERAL

INFORMATION SHEET

REPAIR BUILDING 100 MOISTURE

BARRIER

ANCHORAGE, ALASKA

463-21-101

FEBRUARY 14, 2024 lms LMS

IFC

ABBREVIATIONS DRAWING SYMBOLS

A

ACT ACOUSTICAL CEILING TILE

ADJ ADJACENT

AFF ABOVE FINISH FLOOR

ALT ALTERNATE

ALUM ALUMINUM

ANOD ANNODIZED

APPROX APPROXIMATE

B

BD BOARD

BLDG BUILDING

BLKG BLOCKING

BOD BOTTOM OF DECK

BOT BOTTOM

C

CAB CABINET(S)

CJ CONROL JOINT

CL CENTER LINE

CLG CEILING

CLO CLOSET

CLR CLEAR

COL COLUMN

CONC CONCRETE

CORR CORRIDOR

CPT CARPET

CT CERAMIC TILE

D

D DEEP/DEPTH

DBL DOUBLE

DEG DEGREE

DEMO DEMOLITION

DF DRINKING FOUNTAIN

DIAM DIAMETER

DIFF DIFFERENCE

DIM DIMENSION

DISP DISPENSER / DISPOSAL

DN DOWN

DWG DRAWING(S)

E

EA EACH

ELEC ELECTRIC

EQ EQUAL

EQUIP EQUIPMENT

EXG EXISTING

EXP JT EXPANSION JOINT

EXT EXTERIOR

F

FACP FIRE ALARM CONTRL PANEL

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISH FLOOR

FIN FINISH

FLR FLOOR

FOC FACE OF CABINET

FOF FACE OF FINISH

GENERAL

G1.00 COVER AND GENERAL INFORMATION SHEET

G1.01 KEY PLANS

G1.02 KEY ELEVATIONS

ARCHITECTURE

A100 AIR HANDLING ROOM PENTHOUSES

A110 STAIR 04 PANEL REPLACEMENT

A120 ATRIUM CURTAIN WALL AND PARAPET

A130 GLAZED CURTAIN WALL

A140 SEISMIC JOINT AND STAIR HVAC DETAILS

MECHANICAL

ME001 MECH & ELEC.LEGEND, SCHED, CONTROLS

ME101 MECH & ELEC FLOOR PLANS AND DETAILS

REPAIR BUILDING 100 ENVELOPE MOISTURE BARRIER

Alaska VA Healthcare System

PROJECT NUMBER

463-21-101

PROJECT TEAM

PRIME CONTRACT HOLDER

BLUE TRIDENT, LLC

7829 NE ESPERIONE LN

BAINBRIDGE ISLAND, WA 98110

p.206-972-0645 data=E9Ks2YPXY8MG2G7HCjSLP8Hkr3%2B9IL86%2BsG7ny%2F76fo%3D&reserved=0" P.O.C. Emmanuel (Manny) Bautista, PE, F.SAME

MECHANICAL ENGINEER

NOTKIN a P2S COMPANY

920 FIFTH AVE, STE 2300

SEATTLE, WA 98104

p. 206-448-1911

TEST, ADJUST AND BALANCE

W.A.BOTTING CONSULTING, LLC

Woodinville, WA p.425-408-1200

P.O.C. WADE A BOTTING

BUIILDING ENVELOPE SPECIALIST

WETHERHOLT and ASSOC, INC 2639 Parkmont Lane SW, Suite A Olympia, WA 98502 p.360-786-1660

COST ESTIMATE

OCMI, ESTIMATING

1455 NW Leary Way Sst 400 Seattle, WA 98107 p.206-395-9738

DRAWING INDEXSCOPE OF WORK - REFERENCE DRAWINGS FOR EXTENT AT EACH AREA

SHEET A100 - AIR HANDLING ROOM PENTHOUSES

SHEET A110 - ROOF ACCESS STAIR PENTHOUSE SHEET A120 - ATRIUM WALLS

SHEET A130 - GLAZED CURTAIN WALLS

GENERAL NOTES

GOOGLE EARTH IMAGE OF EXISTING FACILITY

FOS FACE OF STUD

FOW FACE OF WALL

G

GA GAUGE

GALV GALVANIZED

GB GRAB BAR

GEN GENERAL

GLU-LAM GLUE LAM BEAM

GWB GYPSUM WALL BOARD

GYP GYPSUM

H

HDWR HARDWARE

HM HOLLOW METAL

HORIZ HORIZONTAL

HT HIGH/HEIGHT

HVAC HEATING VENTILATION AIR

CONDITIONING

I

IBC INTERNATIONAL BUILDING

CODE

ID INTERIOR DESIGN

INFO INFORMATION

INSUL INSULATION

INT INTERIOR

J

JAN JANITOR

JT JOINT

K

KIT KITCHEN

L

LAM LAMINATED

LAV LAVATORY

LF LINEAR FEEET

M

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MFG MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MR MOISTURE RESISTANT

MS METAL STUD

MTD MOUNTED

MTL METAL

N

NA NOT APPLICABLE

NAP NAPKIN

NIC NOT IN CONTRACT

NOM NOMINAL

NTS NOT TO SCALE

O

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OPNG OPENING

OPP OPPOSITE

ORIG ORIGINAL

P

PLAM PLASTIC LAMINATE

PLWD PLYWOOD

PREFAB PRE FABRICATED

PREFIN PRE FINISHED

PT PAINT

PTD PAPER TOWEL DISPENSER

PTN PARTITION

Q

QT QUARRY TILE

R

RAD RADIUS

RB RUBBER

REF REFERENCE

REINF REINFORCING

REQD REQUIRED

RESIL RESILIENT

S

SAN SANITARY

SCHED SCHEDULE

SF SQUARE FOOT

SHT SHEET

SHWR SHOWER

SIM SIMILAR

SOG SLAB ON GRADE

SS STAINLESS STEEL

STD STANDARD

STL STEEL

STO STORAGE

T

TEMP TEMPORARY

THK THICK

THRU THROUGH

TLT TOILET

TO TOP OF

TPD TOILET PAPER DISPENSER

TPTN TOILET PARTITION

TYP TYPICAL

U

UC UNDER COUNTER / UNDER

CABINET

UNFIN UNFINISHED

UNO UNLESS NOTED OTHERWISE

V

VAR VARIES

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

W

W WIDE/WIDTH

W/ WITH

W/I WITHIN

W/O WITHOUT

WC WATER CLOSET

WWF WELDED WIRE FABRIC

Revisions: Date:

SHEET A140 - SEISMIC JOINT & STAIR HVAC DETAILS

B-02/13/07

B-02/13/07 B-02/13/07

B-02/13/07

B-02/13/07

LOBBY

LOBBY

FP-02/13/07 FP-02/13/07

FP-02/13/07

FP-02/13/07

FP-02/13/07

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

LFP- 02/13/07

B-02/13/07

B-02/13/07 B-02/13/07

B-02/13/07

B-02/13/07

N 261'1

N 281'1

N 301'1

N 321'1

N 341'1

N 361'1

N 381'1

N 401'1

N 421'1

N 441'1

N 461'1

N 481'1

N 501'1

N 521'1

N 541'1

N 557'0

N 562'11

NE

8'8

NE

0'

E 9'4

E 0'8

NW 0'

NW 17

'5

NW

'5

NW

'5

NW

'8

NW

'7

NW 71

'8

FP-02/13/07

D DD D

D DD D

D DD D

DD DD

BIOMED

120/89

SEC

-/64

BIOMED

120/89

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

N 261'1

N 281'1

N 301'1

N 321'1

N 341'1

N 361'1

N 381'1

N 401'1

N 421'1

N 441'1

N 461'1

N 481'1

N 501'1

N 521'1

N 541'1

N 557'0

N 562'11

NE

8'8

NE

0'

E 9'4

E 0'8

NW 0'

NW 17

'5

NW

'5

NW

'5

NW

'8

NW

'7

NW 71

'8

LFP-02/13/07

B-02/13/07

B-02/13/07 B-02/13/07

B-02/13/07

B-02/13/07

3A102

3A100

3B100

3C101

3D101

3A101

3C100

3D100

2A4

2A5 2A3 2A1

2B1

2D1

2D2

2D4

2D3

2D5

2D6

2C2

2C1

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

ELEC.

3ER3

ELEC.

3ER1

ELEC.

3ER2

STAIR

MECH.

SHAFT

MECH.

SHAFT MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

FEC

FEB

FEBFEB

FEB

FEB

FEB

FEB

FEB

FEB

FEB

FEB

FEB

FEB

FA

CE

O F

SH

AF

T

SHAFT BELOW

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

LFP-02/13/07

B-02/13/07

B-02/13/07 B-02/13/07

B-02/13/07

B-02/13/07

3A102

3A100

3B100

3C101

3D101

3A101

3C100

3D100

2A4

2A5 2A3 2A1

2B1

2D1

2D2

2D4

2D3

2D5

2D6

2C2

2C1

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

ELEC.

3ER3

ELEC.

3ER1

ELEC.

3ER2

STAIR

MECH.

SHAFT

MECH.

SHAFT MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

AS201

20 20

LOWER

ROOF

UPPER

ROOF

UPPER

ROOF

LOWER

ROOF

LOWER

ROOF

UPPER

ROOF

LOWER

ROOF

LOWER

ROOF

UPPER

ROOF

LOWER

ROOF

UPPER

ROOF

UPPER

ROOF

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

LFP-02/13/07

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

A130 C1

A140 C3

A120 B8

A100 C6

A110 B9

REMOVE ONE PIECE OF COPING THAT IS

NOTICABLY WIDER THAN THE ADJACENT PIECES

(APPROX. LOCATION SHOWN). REPLACE WITH

CORRECTLY SIZED COPING PIECE TO MATCH

EXISTING. SPLICE, OVERLAP AND SET IN

SEALANT SIMILAR TO DETAIL F4/A110.

REMOVE AND

REPLACE SCUPPERS

ON ALL PENTHOUSES

REMOVE AND

REPLACE SCUPPERS

ON ALL PENTHOUSES

REMOVE AND

REPLACE SCUPPERS

ON ALL PENTHOUSES

REMOVE AND REPLACE

SCUPPERS ON ATRIUM

HIGH ROOF

A110 F1

TYP.

A110 F1

TYP.

A110 F1

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 -

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

Blue Trident, LLC 7829 NE Esperione LN Bainbridge Island, WA 98110 Mobile: (206)972-0645 Lauri Strauss, AIA LEED AP BD&C (907) 317-5040

SPRINKLERED

C :\U se rs

\la ur i\O ne

D riv e\ d2

L- Pr oj ec ts \2

7-

1_

An ch or ag e re pa ir bl dg e nv lp \0

4- D

ES

IG

N \R

EV

IT

\2

7-

1_ re pa ir bl dg

R

EB

ID

.rv t

2/ 7/

0:

:1

AM

G1.01

KEY PLANS REPAIR BUILDING 100 MOISTURE

BARRIER

ANCHORAGE, ALASKA

463-21-101

FEBRUARY 14, 2024 Checker Author

IFC

1" = 50'-0"F7 OVERALL FLOOR PLAN - LEVEL 1

1" = 50'-0"D7 OVERALL LEVEL 2 FLOOR PLAN

1" = 50'-0"F1 OVERALL LEVEL 3 LOWER ROOF PLAN

1" = 50'-0"D1 OVERALL LEVEL 4 UPPER ROOF PLAN

E 340'0

E 310'0

E 280'0

E 250'0

E 220'0

E 190'0

E 160'0

E 130'0

E 100'0

E 70'0

E 40'0

E 10'0

E 0'0

S 30'0

S 0'0

N 258'0

N 228'0

N 198'0

N 168'0

N 138'0

N 108'0

N 78'0

N 48'0

N 18'0

N 9'0

N 0'0

S 300'0

S 270'0

S 240'0

S 210'0

S 180'0

S 150'0

S 120'0

S 90'0

S 60'0

S 30'0

S 0'0

S 300'0

S 270'0

S 240'0

S 150'0

S 120'0

S 90'0

S 60'0

S 30'0

N 258'0

N 228'0

N 198'0

N 168'0

N 138'0

N 108'0

N 78'0

N 48'0

S 210'0

S 180'0

E 340'0

E 310'0

E 280'0

E 250'0

E 220'0

E 190'0

E 160'0

E 130'0

W 99'0

W 69'0

W 39'0

W 9'0

W 0'0

E 100'0

N 258'0

N 228'0

N 18'0

N 9'0

N 0'0

S 0'0

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

30'0 S

0'0 S

258'0 N

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

300'0 S

270'0 S

240'0 S

210'0 S

180'0 S

150'0 S

120'0 S

90'0 S

60'0 S

30'0 S

0'0 S

300'0 S

270'0 S

240'0 S

150'0 S

120'0 S

90'0 S

60'0 S

30'0 S

0'0 S

258'0 N

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

210'0 S

180'0 S

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

99'0 W

69'0 W

39'0 W

9'0 W

0'0 W

100'0 E

258'0 N

228'0 N

0'-0"

FIRST FLOOR LEVEL

+14'-6"

SECOND FLOOR LEVEL

+31'-8"

TOP OF PARAPET

0'-0"

FIRST FLOOR LEVEL

+14'-6"

CLINIC SECOND FLOOR LEVEL

+44'-0"

TOP OF

PENTHOUSE

TOP OF ROOF

+42'-10"

0'-0"

+14'-6"

SECOND

FLOOR LEVEL

FIRST

FLOOR LEVEL

TOP OF ROOF

+42'-10"

0'-0"

FIRST FLOOR LEVEL

+14'-6"

SECOND FLOOR LEVEL

+31'-8"

TOP OF PARAPET

TOP OF ROOF

+42'-10"

+31'-8"

TOP OF

PARAPET

+31'-8"

TOP OF

PARAPET

+44'-0"

TOP OF

PENTHOUSE

+44'-0"

TOP OF

PENTHOUSE

+44'-0"

TOP OF

PENTHOUSE

0'-0"

FIRST FLOOR LEVEL

+14'-6"

CLINIC SECOND FLOOR LEVEL

+44'-0"

TOP OF

PENTHOUSE

TOP OF ROOF

+42'-10"

+31'-8"

TOP OF

PARAPET

NORTH ELEVATION - KEY

EAST ELEVATION - KEY

SOUTH ELEVATION - KEY

WEST ELEVATION - KEY

PER DETAILS B4 AND D4/A100, REMOVE EXISTING

METAL PANELS (MP), RELATED FRAMING, AND

LOUVERS ENTIRE LENGTH OF WALL

PER DETAILS B4 AND D4/A100, REMOVE EXISTING

METAL PANELS (MP), RELATED FRAMING, AND

LOUVERS ENTIRE LENGTH OF WALL

PER DETAILS B4 AND D4/A100, REMOVE EXISTING

METAL PANELS (MP), RELATED FRAMING, AND

LOUVERS ENTIRE LENGTH OF WALL

PER DETAILS B4 AND D4/A100, REMOVE EXISTING

METAL PANELS (MP), RELATED FRAMING, AND

LOUVERS ENTIRE LENGTH OF WALL

PER DETAILS B4 AND D4/A100, REMOVE EXISTING

METAL PANELS (MP), RELATED FRAMING, AND

LOUVERS ENTIRE LENGTH OF WALL

PER DETAILS B4 AND D4/A100, REMOVE EXISTING

METAL PANELS (MP), RELATED FRAMING, AND

LOUVERS ENTIRE LENGTH OF WALL

PER DETAILS B4 AND D4/A100, REMOVE EXISTING

METAL PANELS (MP), RELATED FRAMING, AND

LOUVERS ENTIRE LENGTH OF WALL

PER DETAILS B4 AND D4/A100, REMOVE EXISTING

METAL PANELS (MP), RELATED FRAMING, AND

LOUVERS ENTIRE LENGTH OF WALL

REMOVE EXISTING METAL PANELS

(MP) AND RELATED FRAMING ENTIRE

LENGTH OF WALL - REF B9/A110

REMOVE EXISTING METAL PANELS

(MP) AND RELATED FRAMING ENTIRE

LENGTH OF WALL - REF B9/A110

BA130

E1

AA130

E1 REMOVE EXISTING CURTAIN WALL FULL WALL

HEIGHT AND REPLACE WITH WALL

CONSTRUCTION AND PUNCHED WINDOWS

REMOVE EXISTING CURTAIN WALL FULL WALL

HEIGHT AND REPLACE WITH WALL

CONSTRUCTION AND PUNCHED WINDOWS

INSTALL CLOSED CELL SPRAY FOAM

INSULATION AT BOTTOM OF STEEL STRUCTURE

1ST AND 2ND FLOORS FROM ATRIUM TO POINT

WHERE NEW ADDITION CONNECTS REF B9/A130

NEW AHU-16 UNIT

A140 F1

REMOVE EXISTING METAL PANELS (MP) AND

RELATED FRAMING ENTIRE LENGTH OF

ATRIUM WALL REF B8/A120

REMOVE EXISTING METAL PANELS (MP)

ABOVE ATRIUM AND RELATED FRAMING

ENTIRE LENGTH OF WALL REF B8/A120

CA130

E1 REMOVE EXISTING CURTAIN WALL FULL WALL

HEIGHT AND REPLACE WITH WALL

CONSTRUCTION AND PUNCHED WINDOWS

DIAGONAL HATCHING

INDICATES APPROXIMATE AREA

OF FUTURE BUILDING ADDITION

SHADING INDICATES RECESSED BLDG

FACE UNDER CANOPY

PER DETAILS B4 AND D4/A100, REMOVE EXISTING

METAL PANELS (MP), RELATED FRAMING, AND

LOUVERS ENTIRE LENGTH OF WALL

REMOVE AND REPLACE SCUPPERS

ON ALL PENTHOUSES PER F1 / A110

REMOVE AND REPLACE SCUPPERS

ON ALL PENTHOUSES PER F1 / A110

REMOVE AND REPLACE SCUPPERS

ON ALL PENTHOUSES PER F1 / A110

REMOVE AND REPLACE SCUPPERS

ON ALL PENTHOUSES AND ATRIUM

HIGH ROOF PER F1 / A110

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 -

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

Blue Trident, LLC 7829 NE Esperione LN Bainbridge Island, WA 98110 Mobile: (206)972-0645 Lauri Strauss, AIA LEED AP BD&C (907) 317-5040

SPRINKLERED

C :\U se rs

\la ur i\O ne

D riv e\ d2

L- Pr oj ec ts \2

7-

1_

An ch or ag e re pa ir bl dg e nv lp \0

4- D

ES

IG

N \R

EV

IT

\2

7-

1_ re pa ir bl dg

R

EB

ID

.rv t

2/ 7/

0:

:1

AM

G1.02

KEY ELEVATIONS REPAIR BUILDING 100 MOISTURE

BARRIER

ANCHORAGE, ALASKA

463-21-101

FEBRUARY 14, 2024 Checker Author

IFC

1" = 20'-0"F1 KEY ELEVATIONS

B-02/13/07

B-02/13/07

3A102

3A100

3B100

3C101

3D101

3A101

3C100

3D100

2A4

2A5 2A3 2A1

2B1

2D1

2D2

2D4

2D3

2D5

2D6

2C2

2C1

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

ELEC.

3ER3

ELEC.

3ER1

ELEC.

3ER2

STAIR

MECH.

SHAFT

MECH.

SHAFT MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

FEC

FEB

FEBFEB

FEB

FEB

FEB

FEB

FEB

FEB

FEB

FEB

FEB

FEB

FA

CE

O F

SH

AF

T

SHAFT BELOW

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

LFP-02/13/07

GRID

VA

RI

ES

2' 6"

1'-4"

VA

RI

ES

8"

7" M A X

TY

P.

7" M A X

TY

P.

11" MIN. TYP.

FORMED METAL PLANK

GRATING STAIR TREADS

STEEL STRINGER

SINGLE PLY WALKWAY

SINGLE PLY ROOFING MEMBRANE

RECOVERY BOARD

RIGID INSULATION

GLASS MAT GYPSUM SUBSTRATE

VAPOR RETARDER

METAL DECKING

6" METAL STUDS WITH BATT

INSULATION

GLASS MAT GYPSUM SUBSTRATE

6"

1/ 2"

6" M

IN

TY

P.

REPLACE DOOR THRESHOLD

REPLACE DOOR

THRESHOLD

REPLACE DOOR THRESHOLD

REPLACE DOOR

THRESHOLD

REMOVE AND

REINSTALL LOUVER

REMOVE AND

REINSTALL LOUVER

REPLACE DOOR THRESHOLD

REPLACE DOOR

THRESHOLD

REMOVE AND

REINSTALL LOUVER

REMOVE AND REINSTALL

LOUVER

REPLACE DOOR THRESHOLD

REMOVE AND REINSTALL

LOUVER

REMOVE AND REINSTALL

LOUVER

NEW METAL COPING TO MATCH

EXISTING COPING

SLOPED 2" THICK TYPE IX EPS

RIGID INSULATION AT TOP OF WALL

ADHERED TO ROOFING MEMBRANE

3" RIGID MINERAL WOOL INSULATION

FIBERGLASS GIRT CLIP SYSTEM

FASTENED TO METAL WALL STUDS

AT 24" O.C. VERT MAX

EXISTING CORRUGATED METAL SIDING

MOUNTED TO FIBERGLASS CLIPS -

CONCEALED MOUNTING - REINSTALL

UNDAMAGED PIECES - REPLACE

DAMAGED PIECES WITH NEW

EXISTING AIR BARRIER TO REMAIN -

FIELD VERIFY INTEGRITY I.E. NO

TEARS, GAPS, HOLES, AND REPLACE

ALL DAMAGED PORTIONS AS REQ'D

CAREFULLY REMOVE

EXISTING CORRUGATED

METAL SIDING W/

CONCEALED MOUNTING

AND - SALVAGE FOR

REINSTALLATION

CAREFULLY REMOVE

EXISTING METAL COPING

TO ENSURE NO DAMAGE

TO MEMBRANES

CONT. ROOFING MEMBRANE

WRAPPED OVER TOP OF WALL

EXISTING CONSTRUCTION TO

REMAIN SHOWN IN HALFTONE2'

- 0

REMOVE TOP STEP/LANDING AS REQUIRED

TO ACCESS WALL BELOW DOOR - SALVAGE

FOR REINSTALLATION

18GA BENT METAL COPING - MOUNT ON CLEAT AT

EXTERIOR AND SCREW TO METAL STUD WALL ON

INTERIOR - PROVIDE NON-SLIP COATING ACROSS

TOP - SLOPE FRONT EDGE TO EXTERIOR

TPO ROOFING MEMBRANE LAPPED OVER TOP

OF WALL AND DOWN EACH SIDE MIN. 6" - SET

IN FULL BED OF ADHESIVE/ SEALANT AS

RECOMMENDED BY ROOFING MANUF.

2" THICK TYPE IX EPS RIGID INSULATION

FULL WIIDTH OF DOOR OPENING

4" 1/2

4"

2 3/4"

REMOVE EXISTING SADDLE

THRESHOLD - SAWCUT APPROX. 2"

OFF TOP OF THRESHOLD WALL AND

REMOVE METAL TOP TRACK - LEAVE

EXG ROOFING MEMBRANE FLASHING

TO THE EXTENT POSSIBLE

FIELD VERIFY INSULATION CONDITION - REMOVE

AND REPLACE WET OR SAGGING INSULATION -

PROVIDE NEW METAL TOP TRACK - PATCH AND

REPAIR OR REPLACE DAMAGED GYP.

SHEATHING AND GYP. BD AS REQUIRED

BOTT. OF EXG DOOR JAMBS - SLIDE

NEW METAL COPING UNDER JAMBS

AND FIT TIGHT TO SIDE WALLS

PLAN VIEW AT NEW THRESHOLD COPING

8" FIELD VERIFY AT LARGER DOORS

3' - 0"

FABRICATE COPING IN 2 SECTIONS - INSTALL SHORT

PIECE FIRST - SLIDING IT UNDER THE EXISTING

JAMB ON THE HINGE SIDE - INSTALL LONG PIECE

SLIDING IT UNDER THE LATCH SIDE JAMB - SET END

IN TWO BEADS OF SEALANT AND OVERLAP 4" MIN.

SLOPE

HINGE

SIDE OF

DOOR

PROVIDE NEW DOOR BOTTOM

SWEEP W/ DRIP AND NEW WEATHER

STRIPPING AT HEAD AND JAMBS

2 3 /4"

3" RIGID MINERAL WOOL INSULATION

FIBERGLASS GIRT CLIP SYSTEM

FASTENED TO METAL WALL STUDS

AT 24" O.C. VERT MAX

EXISTING CORRUGATED METAL

SIDING MOUNTED TO

FIBERGLASS CLIPS -

CONCEALED MOUNTING -

REINSTALL UNDAMAGED

PIECES - REPLACE DAMAGED

PIECES WITH NEW

EXISTING AIR BARRIER TO REMAIN -

FIELD VERIFY INTEGRITY I.E. NO

TEARS, GAPS, HOLES, AND REPLACE

ALL DAMAGED PORTIONS AS REQ'D

PROVIDE NEW 6" HIGH

METAL FLASHING ALONG

BOTTOM OF WALL - SEAL

TO EXISTING AIR BARRIER

WITH SELF ADHERING

FLASHING TAPE

CAREFULLY REMOVE

EXISTING CORRUGATED

METAL SIDING W/

CONCEALED MOUNTING

AND - SALVAGE FOR

REINSTALLATION

EXISTING CONSTRUCTION TO

REMAIN SHOWN IN HALFTONE

PROVIDE A BEAD OF SPRAY FOAM

ALONG THE BOTTOM EDGE OF THE

DRYWALL WHERE IT MEETS THE

TOP OF THE CONCRETE CURB.

TRIM LOOSE PORTIONS OF

VAPOR RETARDER AT THE TOP

OF THE CONCRETE CURB

3" MINERAL WOOL

RIGID INSULATION

CONT. FLASHING TAPE - 8" WIDE

MINIMUM - LAP OVER FLASHING LEG

BREAK METAL FLASHING TO

MATCH SIDING PANELS -

FASTEN TO EXG STUD

FRAMING - SLOPE TO DRAIN

EXG HM DOOR AND

FRAME TO REMAIN

BACKER ROD AND

SEALANT, TYP

EXISTING CONSTRUCTION TO

REMAIN SHOWN HALFTONE

3" MINERAL WOOL

RIGID INSULATION

CONT. BREAK METAL

FLASHING TO MATCH SIDING

PANELS - FASTEN TO

FIBERGLASS CLIPS AND

THRU TO METAL STUDS

EXG HM DOOR AND

FRAME TO REMAIN

REPLACE

BACKER

ROD AND

SEALANT,

TYP

EXISTING CONSTRUCTION TO

REMAIN SHOWN HALFTONE

EXISTING LOUVER TO BE

REMOVED AND

REINSTALLED AS REQUIRED

TO ADDRESS WATER

DAMAGED INTERIOR WALLS

EXG WALL AND

HEADER TO REMAIN

3" MINERAL WOOL

RIGID INSULATION

CONT. FLASHING TAPE -

LAP OVER FLASHING LEG

BREAK METAL FLASHING TO

MATCH SIDING PANELS -

FASTEN TO EXG STUD

FRAMING - SLOPE TO DRAIN

REPLACE BACKER ROD

AND SEALANT, TYP

EXISTING CONSTRUCTION TO

REMAIN SHOWN HALFTONE

EXISTING CORRUGATED METAL

SIDING MOUNTED TO

FIBERGLASS CLIPS - CONCEALED

MOUNTING - REINSTALL

UNDAMAGED PIECES - REPLACE

DAMAGED PIECES WITH NEW

FIBERGLASS GIRT CLIP

SYSTEM FASTENED TO

METAL WALL STUDS AT

24" O.C. VERT MAX

8"

BUTYL FLASHING TAPE - WRAP

UP WALL AND AROUND

HEADER - TURN UP TO FORM

END DAMS AT THE SILL-TO-

JAMB TRANSITION, AND AT THE

ENDS OF THE HEAD FLASHING

HEAD CONDITION

SHOWN - JAMB

CONDITION IS SIMILAR

REPLACE WATER

DAMAGED GYP.BD

PROFILE OF FLASHING

AT JAMBS

EXISTING LOUVER TO BE

REMOVED AND REINSTALLED AS

REQUIRED TO ADDRESS WATER

DAMAGED INTERIOR WALLS

EXG WALL AND SILL

CONSTRUCTION TO REMAIN

3" MINERAL WOOL RIGID INSULATION

CONT. FLASHING TAPE -

LAP OVER FLASHING LEG

BREAK METAL FLASHING TO

MATCH SIDING PANELS -

FASTEN TO EXG STUD

FRAMING - SLOPE TO DRAIN

REPLACE BACKER ROD

AND SEALANT, TYP

EXISTING CONSTRUCTION TO

REMAIN SHOWN HALFTONE

EXISTING CORRUGATED METAL SIDING

MOUNTED TO FIBERGLASS CLIPS -

CONCEALED MOUNTING - REINSTALL

UNDAMAGED PIECES - REPLACE

DAMAGED PIECES WITH NEW

FIBERGLASS GIRT CLIP

SYSTEM FASTENED TO

METAL WALL STUDS AT 24"

O.C. VERT MAX

BUTYL FLASHING TAPE - WRAP UP

WALL AND OVER TOP OF WALL -

TURN UP TO FORM END DAMS AT THE

SILL-TO-JAMB TRANSITION, AND AT

THE ENDS OF THE HEAD FLASHING

CREATE SILL DAM BY TURNING UP

END OF METAL FLASHING AT INT.

FACE OF STUD

8"

REPLACE WATER DAMAGED GYP.BD

3" RIGID MINERAL WOOL INSULATION

FIBERGLASS GIRT CLIP SYSTEM

FASTENED TO METAL WALL STUDS

NEW BENT METAL WALL PANEL CORNER

CLADDING - PROVIDE AT ALL CORNERS

FULL HEIGHT OF WALL

EXISTING AIR BARRIER TO

REMAIN - FIELD VERIFY

INTEGRITY I.E. NO TEARS, GAPS,

HOLES, AND REPLACE ALL

DAMAGED PORTIONS AS REQ'D

AND SEALL ALL GAPS TIGHT

CAREFULLY REMOVE

EXISTING METAL WALL

PANEL CLADDING AND

HANGING RAILS - SALVAGE

FOR REINSTALLATION -

PROVIDE NEW PANELS

WHERE DAMAGE OCCURS

EXISTING CONSTRUCTION TO

REMAIN SHOWN IN HALFTONE

A110 F4

SIM AT

PARAPET 8"

8"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 -

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

Blue Trident, LLC 7829 NE Esperione LN Bainbridge Island, WA 98110 Mobile: (206)972-0645 Lauri Strauss, AIA LEED AP BD&C (907) 317-5040

SPRINKLERED

C :\U se rs

\la ur i\O ne

D riv e\ d2

L- Pr oj ec ts \2

7-

1_

An ch or ag e re pa ir bl dg e nv lp \0

4- D

ES

IG

N \R

EV

IT

\2

7-

1_ re pa ir bl dg

R

EB

ID

.rv t

2/ 7/

0:

:1

AM

A100

AIR HANDLING ROOM

PENTHOUSES

REPAIR BUILDING 100 MOISTURE

BARRIER

ANCHORAGE, ALASKA

463-21-101

FEBRUARY 14, 2024 BC LMS

IFC

PER DETAILS B4 AND D4, REMOVE

EXISTING METAL PANELS (MP) AND

RELATED FRAMING ENTIRE

LENGTH OF WALL

LEGEND

1" = 40'-0"C6 AIR HANDLING ROOM PENTHOUSES

1 1/2" = 1'-0"B4 CORRUGATED METAL PARAPET

1 1/2" = 1'-0"F7

DOOR THRESHOLD REPLACEMENT

PENTHOUSES

1 1/2" = 1'-0"D4 CORRUGATED METAL BOTTOM OF WALL

3" = 1'-0"B3 EXT DOOR HEAD CORRUGATED PANEL

3" = 1'-0"C3 EXT DOOR JAMB CORRUGATED PANEL

6" = 1'-0"C1 LOUVER HEAD/JAMB SECTION

6" = 1'-0"E1 LOUVER SILL SECTION

3" = 1'-0"E4 OUTSIDE CORNER PENTHOUSE

B-02/13/07

B-02/13/07

3A102

3A100

3B100

3C101

3D101

3A101

3C100

3D100

2A4

2A5 2A3 2A1

2B1

2D1

2D2

2D4

2D3

2D5

2D6

2C2

2C1

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

ELEC.

3ER3

ELEC.

3ER1

ELEC.

3ER2

STAIR

MECH.

SHAFT

MECH.

SHAFT MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

AS201

20 20

LOWER

ROOF

UPPER

ROOF

UPPER

ROOF

LOWER

ROOF

LOWER

ROOF

UPPER

ROOF

LOWER

ROOF

LOWER

ROOF

UPPER

ROOF

LOWER

ROOF

UPPER

ROOF

UPPER

ROOF

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

LFP-02/13/07

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

6" 6"

M

IN

TY

P.

6"

MI

N.

T

YP

1/ 2"

258'0 N

276'2 N

2C167

1C192

PROGRAM

SUPPORT

GENERATOR

ROOM

C O

LU

M N

LI

N E

18'-2"

FACE OF

STUD

SUSPENDED

GYP. BD. CLG.

CEILING

LINE

1'-4" ℄ GRID

TO F.O.S.

GRID

3' 2"

VA

RI

ES

1'-4"

GRID

1'-4"

REMOVE EXG METAL PANELS

E9

A110

A110 F7

A110 F7

A110 F1

REMOVE AND REPLACE

SCUPPER

NEW CONT. CLOSURE PIECE

MOUNTED ON FIBERGLASS GIRTS

3" RIGID MINERAL WOOL INSULATION

FIBERGLASS GIRT CLIP SYSTEM

FASTENED TO METAL WALL STUDS

EXISTING METAL WALL PANEL

CLADDING - REINSTALL

UNDAMAGED PIECES - REPLACE

DAMAGED PIECES WITH NEW

EXISTING AIR BARRIER TO REMAIN -

FIELD VERIFY INTEGRITY I.E. NO TEARS,

GAPS, HOLES, AND REPLACE ALL

DAMAGED PORTIONS AS REQ'D

CAREFULLY REMOVE

EXISTING METAL

WALL PANEL

CLADDING AND

HANGING RAILS -

SALVAGE FOR

REINSTALLATION TAPE BOTT. OF AIR BARRIER TO TOP OF

ROOF MEMBRANE BEHIND NEW INSULATION

TO PROVIDE CONT MEMBRANE

EXISTING CONSTRUCTION TO

REMAIN SHOWN IN HALFTONE

3" RIGID MINERAL WOOL INSULATION

FIBERGLASS GIRT CLIP SYSTEM

FASTENED TO METAL WALL STUDS

NEW METAL WALL PANEL CORNER

CLADDING - PROVIDE AT BOTH CORNERS

FULL HEIGHT OF WALL

EXISTING AIR BARRIER TO

REMAIN - FIELD VERIFY

INTEGRITY I.E. NO TEARS, GAPS,

HOLES, AND REPLACE ALL

DAMAGED PORTIONS AS REQ'D

CAREFULLY REMOVE

EXISTING METAL

WALL PANEL

CLADDING AND

HANGING RAILS -

SALVAGE FOR

REINSTALLATION

EXISTING CONSTRUCTION TO

REMAIN SHOWN IN HALFTONE

A110 F4

AT PARAPET

3" RIGID MINERAL WOOL INSULATION

FIBERGLASS GIRT CLIP SYSTEM

FASTENED TO METAL WALL STUDS

EXISTING CLADDING HANGING RAILS

MOUNTED TO FIBERGLASS CLIPS

EXISTING METAL WALL

PANEL CLADDING -

REINSTALL

UNDAMAGED PIECES -

REPLACE DAMAGED

PIECES WITH NEW

EXISTING AIR BARRIER TO REMAIN -

FIELD VERIFY INTEGRITY I.E. NO

TEARS, GAPS, HOLES, AND REPLACE

ALL DAMAGED PORTIONS AS REQ'D

CAREFULLY REMOVE

EXISTING METAL

WALL PANEL

CLADDING AND

HANGING RAILS -

SALVAGE FOR

REINSTALLATION

EXISTING CONSTRUCTION TO

REMAIN SHOWN IN HALFTONE

REMOVE EXISTING AND

PROVIDE NEW SEALANT ALL

AROUND DOOR FRAME

EXG DOOR AND FRAME TO REMAIN

EXISTING FLASHING TO REMAIN

1/2" GAP TO REMAIN

8" WIDE MIN. BUTYL FLASHING

TAPE, WRAP OVER FLASHING

LEG AND TO AIR BARRIER

3" RIGID MINERAL WOOL INSULATION

FIBERGLASS GIRT CLIP SYSTEM

FASTENED TO METAL WALL STUDS

NEW JAMB CLOSURE

FRAME PIECE BY PANEL

MANUF. MOUNTED TO

FIBERGLASS CLIPS

EXISTING METAL WALL

PANEL CLADDING -

REINSTALL UNDAMAGED

PIECES - REPLACE DAMAGED

PIECES WITH NEW

EXISTING AIR BARRIER TO REMAIN -

FIELD VERIFY INTEGRITY I.E. NO

TEARS, GAPS, HOLES, AND REPLACE

ALL DAMAGED PORTIONS AS REQ'D

CAREFULLY REMOVE

EXISTING METAL

WALL PANEL

CLADDING AND

HANGING RAILS -

SALVAGE FOR

REINSTALLATION

EXISTING CONSTRUCTION TO

REMAIN SHOWN IN HALFTONE

EXG DOOR AND FRAME TO REMAIN

CONT. BENT METAL END CLOSURE

FASTEN BEHIND CLADDING

FRAMES TO FIBERGLASS CLIPS

REMOVE EXISTING AND PROVIDE NEW

SEALANT ALL AROUND DOOR FRAME

LAP FLASHING PIECES 6"

MINIMUM. PROVIDE 2

CONTINUOUS BEADS OF

BUTYL SEALANT

TYP. ALL FLASHING

CONDITIONS WHERE

FLASHING PIECES MUST

OVERLAP TO CREATE

CONTINUOUS INSTALLATION

PROVIDE CONCEALED

SPLICE PLATES W/ BUTYL

SEALANT AT COPING JOINTS

PER MANUFACTURERS

RECOMMENDATIONS

MITER JOINT WHERE

DIFFERING WALL THICKNESS

MEET AT A CORNER -

(PENTHOUSE WALL

THICKNESSES ARE THE SAME)

AT CONTRACTORS

OPTION, PROVIDE A

PREFABRICATED CORNER

PIECE TO FIT DIFFERENT

WALL THICKNESS -

OVERLAP 6" MIN PAST

INSIDE CORNER

PORTION OF WALL

TO BE REMOVED

AND REPLACED15

6"

A110 E7

A110 B7

FI

EL

D

VE

RI

FY

2'

- 8 1/ 2"

5"

NEW METAL COPING TO MATCH

EXISTING COPING

SLOPED 2" THICK TYPE IX EPS RIGID

INSULATION AT TOP OF WALL - ADHERED

TO ROOFING MEMBRANE

3" RIGID MINERAL WOOL INSULATION

FIBERGLASS GIRT CLIP SYSTEM

FASTENED TO METAL WALL STUDS

EXISTING CLADDING HANGING RAILS

MOUNTED TO FIBERGLASS CLIPS

EXISTING METAL WALL PANEL

CLADDING - REINSTALL

UNDAMAGED PIECES - REPLACE

DAMAGED PIECES WITH NEW

EXISTING AIR BARRIER TO REMAIN -

FIELD VERIFY INTEGRITY I.E. NO

TEARS, GAPS, HOLES, AND REPLACE

ALL DAMAGED PORTIONS AS REQ'D

CAREFULLY REMOVE

EXISTING METAL

WALL PANEL

CLADDING AND

HANGING RAILS -

SALVAGE FOR

REINSTALLATION

CAREFULLY REMOVE

EXISTING METAL COPING

TO ENSURE NO DAMAGE

TO MEMBRANES

CONT. ROOFING MEMBRANE

WRAPPED OVER TOP OF WALL

EXISTING CONSTRUCTION TO

REMAIN SHOWN IN HALFTONE

1/2

1' - 4"

4"

4"

4" 1 1/2"

PROVIDE 1/2" RIGID INSULATION

OVER TOP OF WALL AND EXTEND

MIN 4" PAST WALL STUDS

18 GA. TYPE 304 STAINLESS STEEL

SCUPPER - WELDED ONE PEICE

CONSTRUCTION. FIELD VERIFY WIDTH

AND HEIGHT OF EACH EXG SCUPPER

TO ENSURE TIGHT FIT - FASTEN TO EXG

CONSTRUCTION W/ STAINLESS STEEL

SCREWS

REMOVE TOP LAYER OF ROOFING

AND CORNER PATCHES. REMOVE

EXG METAL SCUPPER.

SAWCUT AND REMOVE TOP STUD TRACK

FOR WIDTH OF SCUPPER OPENING. FILL

GAP WITH SPRAY FOAM INSULATION TO

NEAREST CROSS BRACE BELOW.

SET PIECE OF ICE AND WATER SHIELD

IN FULL BED OF ADHESIVE OVER TOP

OF INSULATION AND DOWN FACE OF

EXTERIOR WALL MATERIAL

3"

TPO MEMBRANE SHEET SET IN

FULL BED OF ADHESIVE PER

MANUF. RECOMM. - OVERLAP

SCUPPER LEGS MIN 4" ALL

DIRECTIONS - RUN INTO

SCUPPER AND SEAL TO METAL

TOP, BOTT AND SIDES

LOOSEN COPING TO ALLOW

INSTALLATION OF TPO MEMBRANE

FLASHING OVER SCUPPER LEG - SET

IN FULL BED OF ADHESIVE SEALANT

FILL GAP BETWEEN FLUTES IN

METAL SOLID WITH LOW

EXPANSION FOAM FLUSH WITH TOP

OF FLASHING - SEAL TOP WITH

COMPATIBLE WATER TIGHT SEALER

STAINLESS STEEL SUPPORT

ANGLE BELOW SCUPPER FULL

WIDTH - FASTEN TO FACE OF

METAL PANELS OVER ICE AND

WATER SHIELD

ADHESIVE SEALANT

BED FULL WIDTH

TPO MEMBRANE

FLASHING SHEET OVER

MEMBRANE SHEET

EXG CONSTRUCTION TO

REMAIN SHOWN HALFTONE

TYP SCUPPER AT AIR

HANDLING PENTHOUSE TO BE

REPLACED - REUSE OR

REPLACE FLASHING PIECES

TYP SCUPPER AT ATRIUM TO

BE REPLACED

TYP SCUPPER - VIEW

FROM ROOF SIDE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 -

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

Blue Trident, LLC 7829 NE Esperione LN Bainbridge Island, WA 98110 Mobile: (206)972-0645 Lauri Strauss, AIA LEED AP BD&C (907) 317-5040

SPRINKLERED

C :\U se rs

\la ur i\O ne

D riv e\ d2

L- Pr oj ec ts \2

7-

1_

An ch or ag e re pa ir bl dg e nv lp \0

4- D

ES

IG

N \R

EV

IT

\2

7-

1_ re pa ir bl dg

R

EB

ID

.rv t

2/ 7/

0:

:1

AM

A110

STAIR 04 PANEL REPLACEMENT REPAIR BUILDING 100 MOISTURE

BARRIER

ANCHORAGE, ALASKA

463-21-101

FEBRUARY 14, 2024 lms LMS

IFC

REMOVE EXISTING METAL PANELS

(MP) AND RELATED FRAMING

ENTIRE LENGTH OF WALL

LEGEND

1" = 40'-0"B9 STAIR 4 PENTHOUSE

1 1/2" = 1'-0"E7 STAIR WALL TO ROOF DETAIL

3" = 1'-0"F7 OUTSIDE CORNER

6" = 1'-0"C4 EXT DOOR HEAD

6" = 1'-0"E4 EXT DOOR JAMB

1 1/2" = 1'-0"F4 TYP FLASHING at CORNER

1/4" = 1'-0"E9 STAIR 4 SECTION

1 1/2" = 1'-0"B7 STAIR PARAPET DETAIL

3" = 1'-0"F1 TYP. SCUPPER REPLACEMENT DETAIL

B-02/13/07

B-02/13/07

3A102

3A100

3B100

3C101

3D101

3A101

3C100

3D100

2A4

2A5 2A3 2A1

2B1

2D1

2D2

2D4

2D3

2D5

2D6

2C2

2C1

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

AIR HANDLING

ROOM

ELEC.

3ER3

ELEC.

3ER1

ELEC.

3ER2

STAIR

MECH.

SHAFT

MECH.

SHAFT MECH.

SHAFT MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

MECH.

SHAFT

FEC

FEB

FEBFEB

FEB

FEB

FEB

FEB

FEB

FEB

FEB

FEB

FEB

FEB

FA

CE

O F

SH

AF

T

SHAFT BELOW

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

LFP-02/13/07

GRID

VA

RI

ES

4' 2"

1'-3 3/8" 4"

VARIES

BOTTOM

OF SOFFIT

TOP OF

PARAPET

SINGLE PLY ROOFING MEMBRANE

RECOVERY BOARD

RIGID INSULATION

VAPOR RETARDER

GLASS MAT GYPSUM SUBSTRATE

PAINTED ACOUSTIC METAL DECKING

ROOF MEMEBRANE FLASHING

CONT. OVER PARAPET

1/4" 12"

SLOPE TO

DRAIN

GLASS CURTAIN WALL

COMPOSITE METAL PANEL

4" METAL STUDS WITH BATT INSULATION

CONT. BENT METAL PLATE

GLASS MAT GYPSUM SUBSTRATE

GLASS MAT GYPSUM SUBSTRATE

PERSERVATIVE TREATED

WOOD 3x NAILER

METAL PLATE, REF STRUCT.

6" METAL STUDS WITH BATT INSULATION

6"x 15"x 4" BENT PLATE AT 48" O.C.

VAPOR RETARDER

ALUMINUM FLASHING

CONT. STEEL CHANNEL

CONT. PARAPET CAP FINISHED TO

MATCH COMPOSITE METAL PANEL, TYP.

(NO VERTICAL REVEALS)

METAL TRACK BEYOND

GLASS MAT GYPSUM SUBSTRATE

BACKER ROD & SEALANT

1/4"

SINGLE PLY ROOFING MEMBRANE

RECOVERY BOARD

RIGID INSULATION

VAPOR RETARDER

GLASS-MAT GYPSUM SUBSTRATE

METAL DECKING

12"

DOWNSPOUT

RECOVERY BOARD

N 18'0

EDGE OF SILL

COLUMN, REF.

STRUCTURAL

ALUMINUM CORNER

TRIM BY CURTAIN

MFR. FINISH TO

MATCH CURTAIN WALL

7 1/2"

1/ 2"

7 1/2"

7 1/2"

REPLACE GLASS PANEL

WITH ACCESS DOOR

REMOVE EXISTING METAL

PANELS (MP) AND RELATED

FRAMING ENTIRE LENGTH

OF WALL

INSTALL BACKER ROD AND CLOSED

CELL SPRAY FOAM INSULATION AT

BOTTOM OF SILL/TOP OF WALL

JOINT TO CREATE A SILL DAM

C5

A120

C5

A120

E5

A120

E5

A120

E5

A120

E5

A120

F7

A110

F7

A110

F4

A110

F4

A110

F7

A110

F7

A110

F4

A110 F4

A110

REMOVE ONE GLASS PANEL AND

REPLACE WITH ACCESS DOOR

NEW METAL COPING TO MATCH

EXISTING COPING

SLOPED 2" THICK TYPE IX EPS

RIGID INSULATION AT TOP OF

WALL - ADHERED TO ROOFING

MEMBRANE

3" RIGID MINERAL WOOL INSULATION

FIBERGLASS GIRT CLIP SYSTEM

FASTENED TO METAL WALL STUDS

AT 24" O.C. VERT MAX

EXISTING METAL SIDING PANELS -

MOUNT CONCELAED FRAMING TRACKS

TO FIBERGLASS CLIPS - CONCEALED

MOUNTING - REINSTALL UNDAMAGED

PIECES - REPLACE DAMAGED PIECES

WITH NEW

SALVAGE EXG BOTTOM END FRAMING

TRACK FOR REINSTALLATION - SCREW

TO WOOD NAILER - PROVIDE NEW

PIECES WHERE TRACK IS DAMAGED

DURING DECONSTRUCTION

CAREFULLY REMOVE

EXISTING METAL PANELS

W/ CONCEALED

MOUNTING TRACK AND -

SALVAGE FOR

REINSTALLATION

CAREFULLY REMOVE EXISTING

METAL COPING TO ENSURE NO

DAMAGE TO MEMBRANES

CONT. ROOFING MEMBRANE

WRAPPED OVER TOP OF WALLEXISTING

CONSTRUCTION TO

REMAIN SHOWN IN

HALFTONE 1'

- 8 /16

2"

BUTYL FLASHING TAPETO WRAP

BOTTOM OF EXISTING CONSTRUCTION

CONT. BENT METAL FLASHING TO MATCH

METAL PANELS - FASTEN TO STRUCTURE

WITH SELF-TAPPING SCREWS AT 16" O.C.

BENT METAL FLASHING CLOSURE

PIECE - SNAP INTO BOTTOM END

FRAMING TRACK - TUCK UNDER

INSULATION

FRICTION FIT RIGID INSULATION

BEHIND METAL PANEL AND

FRAMING TRACK

5 3 /4"

8"

WOOD NAILER SCREWED TO BOTTOM

OF AND BETWEEN GIRTS

REMOVE EXG. ALUMINUM

FLASHING PIECE

COVERING TOP OF FRAME

SMALL FONT TEXT DESCRIBES ASSUMED EXG CONSTRUCTION

LIFT FLAP OF EXG ROOFING MEMBRANE AND

PLACE BACKERROD UNDER EDGE (APPROX.

3/4" DEEP) TO HOLD MEMBRANE UP - FILL GAP

WITH CLOSED CELL SPRAY FOAM INSULATION -

ALLOW NO MORE THAN 1/2" TO PROTRUDE

FROM FACE OF FRAME - CLEAN ALL EXCESS

FROM FACE OF FRAME AND WALL

SMALL FONT TEXT DESCRIBES

ASSUMED EXG CONSTRUCTION

DRILL HOLES 3/4" DIAM. IN CORNER

MULLION AND FILL CAVITY SOLID WITH

LOW EXPANSION CLOSED CELL SPRAY

FOAM INSULATION - SUPPORT

MULLION TO PREVENT DEFORMATION

DURING FOAM EXPANSION

PATCH HOLES IN FRAME WITH FULL

HT VERTICAL COVER PLATE -

TOGGLE BOLT USING DRILLED

HOLES WITH ALUMINUM BOLTS

AND SET IN BEAD OF SEALANT

1 1/2"

4"

1/2

PREFAB. ALUM. DOOR

AND FRAME - FILL

WITH FOAM INSUL. -

FIELD VERIFY WIDTH

AND FAB DOOR TO FIT

IN CURTAIN FRAME

1" THICK INSULATED

HOLLOW ALUMINUM

DOOR - 2'-0" WIDE X

3'-0" HIGH

WEATHER STRIPPING

ALL AROUND

CAREFULLY REMOVE SNAP

ON STOP AND SALVAGE

FOR REINSTALLATION -

PROVIDE NEW PIECE IF

DAMAGE OCCURS DURING

REMOVAL

1" THICK INSULATED

HOLLOW ALUMINUM

DOOR - 2'-0" WIDE X

3'-0" HIGH

WEATHER STRIPPING

ALL AROUND

PREFAB. ALUM. DOOR

AND FRAME - FILL

WITH FOAM INSUL. -

FIELD VERIFY WIDTH

AND FAB DOOR TO FIT

IN CURTAIN FRAME

CAREFULLY REMOVE

STRUCTURAL GLAZING

AND REPLACE WITH NEW

BACKER ROD AND GLAZING

WITH DOOR INSTALLATION

HEAD

JAMB

SILL

PREFAB. ALUM. DOOR

AND FRAME - FILL

WITH FOAM INSUL. -

FIELD VERIFY WIDTH

AND FAB DOOR TO FIT

IN CURTAIN FRAME -

PROVIDE NEW

NEOPRENE SEAT

1" THICK INSULATED

HOLLOW ALUMINUM

DOOR - 2'-0" WIDE X

3'-0" HIGH

WEATHER STRIPPING

ALL AROUND

CAREFULLY REMOVE SNAP

ON STOP AND SALVAGE

FOR REINSTALLATION -

PROVIDE NEW PIECE IF

DAMAGE OCCURS DURING

REMOVAL - PROVIDE NEW

BACKER ROD AND

SEALANT OVER TOP OF

FLASHING

4"

DOOR HARDWARE:

(1) ALUM. PIANO HINGE

(1) ALUM LEVER HANDLE W/ LATCH

(1) DEADBOLT - THUMB TURN ON

INTERIOR, KEYED LOCK ON EXTERIOR

(1) 48"x48" WALK PAD ON ROOF

OUTSIDE DOOR

PROVIDE RUBBER MAT 60"

WIDE BY WALL WIDTH AT

TOP OF WALL INSIDE DOOR

EXISTING CURTAIN WALL

MULLION TO REMAIN

EXISTING GLASS ADJACENT

GLASS PANEL TO REMAIN

EXISTING CURTAIN WALL

SILL TO REMAIN

EXISTING CURTAIN WALL

MULLION TO REMAIN

EXISTING GLASS ADJACENT

GLASS PANEL TO REMAIN

REMOVE EXG GLASS PANEL

REMOVE EXG GLASS PANEL

REMOVE EXG GLASS PANEL

EXISTING WALL

CONSTRUCTION TO REMAIN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 -

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

Blue Trident, LLC 7829 NE Esperione LN Bainbridge Island, WA 98110 Mobile: (206)972-0645 Lauri Strauss, AIA LEED AP BD&C (907) 317-5040

SPRINKLERED

C :\U se rs

\la ur i\O ne

D riv e\ d2

L- Pr oj ec ts \2

7-

1_

An ch or ag e re pa ir bl dg e nv lp \0

4- D

ES

IG

N \R

EV

IT

\2

7-

1_ re pa ir bl dg

R

EB

ID

.rv t

2/ 7/

0:

:1

AM

A120

ATRIUM CURTAIN WALL AND

PARAPET

REPAIR BUILDING 100 MOISTURE

BARRIER

ANCHORAGE, ALASKA

463-21-101

FEBRUARY 14, 2024 ls LMS

IFC

REMOVE EXISTING METAL PANELS

(MP) AND RELATED FRAMING

ENTIRE LENGTH OF WALL

LEGEND

INSTALL BACKER ROD AND

CLOSED CELL SPRAY FOAM

INSULATION AT BOTTOM OF

SILL/TOP OF WALL JOINT TO

CREATE A SILL DAM

REPLACE GLASS PANEL WITH

ACCESS DOOR - SEE ELEVATIONS

3/8" = 1'-0"D8 ATRIUM ELEVATIONS

1" = 30'-0"B8 ATRIUM CURTAIN WALL AND PARAPET

1 1/2" = 1'-0"C5 ATRIUM CURTAIN WALL PARAPET

1 1/2" = 1'-0"E5 ATRIUM CURTAIN WALL SILL

1 1/2" = 1'-0"F5 ATRIUM CORNER - TYPICAL (4) CORNERS

3" = 1'-0"E2 ATRIUM ACCESS DOOR

B-02/13/07

B-02/13/07

LOBBY

LOBBY

FP-02/13/07 FP-02/13/07

FP-02/13/07

FP-02/13/07

FP-02/13/07

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

LFP- 02/13/07

B-02/13/07

B-02/13/07 B-02/13/07

B-02/13/07

B-02/13/07

N 261'1

N 281'1

N 301'1

N 321'1

N 341'1

N 361'1

N 381'1

N 401'1

N 421'1

N 441'1

N 461'1

N 481'1

N 501'1

N 521'1

N 541'1

N 557'0

N 562'11

NE

8'8

NE

0'

E 9'4

E 0'8

NW 0'

NW 17

'5

NW

'5

NW

'5

NW

'8

NW

'7

NW 71

'8

GRID

VA

RI

ES

3' 2"

1/ 2"

GRID

7 1/2"

TYP

9 3/8"

TYP

LEVEL 2

14'-6"

TOP OF

PARAPET

31'-8"

TOP OF

PARAPET

31'-8"

LEVEL 2

14'-6"

G-03 G-03G-03

G-03

G-07

G-09

G-06

G-01

G-09

G-09

G-06

G-07

G-09

G-06

G-01

G-09

G-09

G-06

G-03

G-01

G-03

G-07

G-09

G-06

G-01

G-09

G-09

G-06

LVL 1 CLG

9'-0"

LVL 1 CLG

9'-0"

LVL 2 CLGLVL 2 CLG

7'-11 1/2" 4'-0"

AT S300'0

7' 1/ 4"

4'-0"

3/ 4"

3/ 4"

1' 2"

7' 3"

2' 5"

2' 5"

2' 3/ 4"

1' 1/ 2"

1' 2"

7' 3"

2' 5"

2' 5"

2' 3/ 4"

6' 1/ 4"

2' 1/ 2"

EQ. EQ.

2' 2"

2' 2"

7' 0"

NORTH ELEVATION

LCGRID

ANCHOR

CONCEALING SLEEVE

WITH ESCUTCHEON

PIPE MATERIAL

TRANSITION

4 1/2"

W18x35

GRID

1'-4"

5"

3' 2"

SECURITY CAMERA

WHERE OCCURS

CONDUIT

METAL COPING

WITH HEMMED DRIPS

ROOF MEMBRANE FLASHING

CONT. OVER PARAPET

METAL STUDS WITH BATT INSULATION

COMPOSITE METAL PANEL

SLOPE TO

DRAIN

2" 'Z' CHANNELS

GLASS MAT GYPSUM SUBSTRATE

SINGLE PLY ROOFING MEMBRANE

RECOVERY BOARD

RIGID INSULATION

VAPOR RETARDER

GLASS MAT GYPSUM SUBSTRATE

METAL DECKING

PERSERVATIVE TREATED

WOOD 2X NAILER

CURTAIN WALL

METAL BACKING PLATE

METAL TRACK BEYOND

BACKER ROD & SEALANT

W18x35

C2-2

C1-1

W

0'0 TOP OF

PARAPET

31'-8"

TOP OF BEAM

LEVEL 1

0'-0"

TOP OF BEAM

LEVEL 2

14'-6"

GLAZED ALUMINUM

CURTAIN WALL

CONCRETE SLAB & REINFORCEMENT

UNDERSLAB VAPOR RETARDER

CAST IN PLACE CONC.

METAL DECKING

SUSPENDED CEILING SYSTEM

SUSPENDED CEILING SYSTEM

COMPOSITE METAL

PANEL

COMPOSITE METAL PANEL

FINNED TUBE

FINNED TUBE

W12x19

W18x35

W10x12

W18x35

W12x16

FP-02/13/07

D D

D D

D D

D D

D D

D D

DD

DD

BIOMED

120/89

SEC

-/64

BIOMED

120/89

0'0 N

9'0 N

18'0 N

48'0 N

78'0 N

108'0 N

340'0 E

310'0 E

280'0 E

250'0 E

220'0 E

190'0 E

160'0 E

130'0 E

100'0 E

70'0 E

40'0 E

10'0 E

0'0 E

258'0 N

30'0 S

99'0 W

60'0 S90'0

S120'0 S150'0

S180'0 S210'0

S

240'0 S270'0

S300'0 S

228'0 N

198'0 N

168'0 N

138'0 N

108'0 N

78'0 N

48'0 N

18'0 N

9'0 N

0'0 N

69'0 W

39'0 W

9'0 W

0'0 W

0'0 S

136' 11 N

276'2 N

N 261'1

N 281'1

N 301'1

N 321'1

N 341'1

N 361'1

N 381'1

N 401'1

N 421'1

N 441'1

N 461'1

N 481'1

N 501'1

N 521'1

N 541'1

N 557'0

N 562'11

NE

8'8

NE

0'

E 9'4

E 0'8

NW 0'

NW 17

'5

NW

'5

NW

'5

NW

'8

NW

'7

NW 71

'8

LFP-02/13/07

A

B

BA,C F4

A130 F4

A130 SIM

C6

A130

A6

A130

C6

A130

A6

A130

A6

A130

SIM

SALVAGE STOREFRONT DOOR/ SIDELIGHT/

AND TRANSOM FRAME FOR REINSTALLATION

C

SIM

2 PC STAINLESS STEEL FLASHING -

LOWER PC SAME WIDTH AS WALL,

MOUNT TO HEADER - UPPER PIECE

TO SNAP INTO LOWER PIECE,

MOUNT ON FACE OF AVM, COVER

IN 8" WIDE BUTYL FLASHING TAPE

6" METAL STUDS T

16" O.C. - BUILT-UP

HEADER AT

WINDOW HEAD

6 MIL POLY. VAPOR

RETARDER

BACKER ROD AND SEALANT GAP

5/8

WRAP CUT END OF INSULATION WITH

FLASHING TAPE

5/8" GYPSUM

BOARD - TAPE

AND FEATHER TO

EXG WALL - PAINT

R-21 BATT

INSULATION

NEW ALUM.

STOREFRONT FIXED

WINDOWS W/

DOUBLE PANE,

INSULATED GLASS W/

LOW E COATING -

MATCH EXISTING

STOREFRONT FINISH

AND FRAME SIZE

1 PC CONT. STAINLESS STEEL

FLASHING SILL DAM - SET ON AVM -

SLOPE OVER INSULATION THICKNES

AND PROVIDE HEMMED DRIP EDGE

CUT INSULATION AND TILE SHORT OF TOP

OF SILL - WRAP EDGE IN FLASHING TAPE

PORCELAIN TILE TO MATCH EXG

3" CEMENT BOARD FACED RIGID

INSULATION FASTEN PER MANUF.

RECOMMENDATIONS - THINSET MORTAR

BED PER MANUF. RECOMMENDATIONS

LIQUID APPLIED AIR VAPOR MEMBRANE

DRAINAGE LAYER

2 PC STAINLESS STEEL FLASHING -

LOWER PIECE SAME WIDTH AS

WALL, MOUNT TO HEADER - UPPER

PIECE TO SNAP INTO LOWER PIECE,

MOUNT ON FACE…

This is the start of the file's text. The full file is on GovTribe.