The solicitation number is 36C25723B0045 and is titled "Z2DA--Renovate Basement Mechanical Room Bldg. 11 Project No: 671A4-22-106." It is an opportunity issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17. Responses are due by the date specified in the solicitation. The contract will be awarded to the responsible offeror whose offer conforming to the solicitation is most advantageous to the government, considering only price and past performance. The work required includes renovations and upgrades to the mechanical systems and structure in the basement of the specified building.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT TEAMPROJECT SUMMARY
PROJECT INFORMATION
THE MAIN HOSPITAL BUILDING 11 HAS EIGHT STORIES (BASEMENT TO 7TH FLOOR AND A MECHANICAL PENTHOUSE ON THE
ROOF LEVEL. THERE IS NO INTERSTITIAL SPACE ABOVE EACH FLOOR.
ASBESTOS SURVEYS SHALL IDENTIFY APPROXIMATE QUANTITIES OF ACM IN TYPE AND LOCATION FOR SELECT ABATEMENT. A PHASING PLAN IS PROVIDED TO MINIMIZE OUTAGES AND DISRUPTIONS WITH INFECTION CONTROL ACCESSMENT(ICRA) AND
ENVIRONMENTAL BARRIERS LOCATED TO CONTROL DUST AND DEBRIS.
RENOVATION OF THE BASEMENT MECHANICAL ROOM IN BUILDING 11.
1. REMOVAL OF EXISTING RAMP AT ENTRANCE WITH INSTALLATION OF A EQUIPMENT LIFT.
2. REMOVE EXIST I-BEAM AND SUPPORTS FOR OLD CHILLER NO LONGER IN USE.
3. REMOVE BACK ROOM EXTERIOR GRATE AND PROVIDE LEAK PROOF ENCLOSURE.
4. PROVIDE CABINETRY AND CABINET SINK STATION(S), UPGRADE EXHAUST, ELECTRICAL AND LIGHTING.
5. INSTALL WALL MOUNTED CIRCULATION FANS AT WORKSTATIONS.
6. REMOVE PIPING, FIRE ALARM CONDUIT AND PA SYSTEM NO LONGER IN SERVICE.
7. REPAIR EXISTING OR RESTORE CONCRETE FLOOR, DOORS AND SOUND PROOFING.
8. REPLACE EXTERIOR FAN WITH AN UP BLAST MOUNTED CONTROL T STAT.10.
9. ENCLOSE AREA AROUND MED-AIR/VAC AND INSTALL A MINI SPLIT.
10. REPLACE PNEUMATIC CONTROL FOR HEATING HOT WATER WITH DDC AND MAP BACK-UP TO FRONT OF COMPUTER.
11. INSTALL VDF'S AND CONTROL POINTS ON HOT WATER SYSTEM.
12. HOT WATER RECIRCULATION, REINSULATE ALL LINES, REPLACE ALL LINES AND VALVES. REPLACE 2 BOOSTER RECIRC
PUMPS, TIE INTO HEAT EXCHANGER SYSTEM.
13. POTABLE HOT WATER, REINSULATE AND REPLACE MAIN LIN EAND VALVES. REPLACE 2 HEAT EXCHANGER, VALVES, GAUGES AND MIXING VALUES. TIE SYSTEM INTO COLD POTABLE WATER LINE AND
INTO HOT WATER RECIRC LINE.
14. POTABLE COLD WATER SUPPLY, REINSULATE, REPLACE MAIN LINE AND VALVES. REPLACE 2 BOOSTER PUMPS AND
EXISTING PIPING AND SECONDARY POTABLE WATER TIE IN LINE.
15. GREYWATER/SEWAGE LINES, REPLACE MAIN LINE AND ALL TIE IN CONNECTIONS, PIPING.
16. REPLACE OLD SUMP PUMP, PIPING AND FLOAT SWITCH.
17. LABEL AND COLOR CODE ALL PIPING.
18. ADD TEMPORARY SHUT OFF KEY LOCATIONS TO ALLOW REDIRECT SERVICING TO LINES.
19. REPLACE EXISTING PVC PIPES WITH BLACK STEEL.
20. RELOCATE EXISTING PIPING WITH A MORE DIRECT ROUTE AS NEED.
GENERAL NOTES
PROJECT NAME: BUILDING 11 BASEMENT RENOVATION
PROJECT NUMBER: 671A4-22-106
PROJECT LOCATION: KERRVILLE VAMC - 3600 MEMORIAL BOULEVARD, KERRVILLE, TX 78028-3768
1. THESE DRAWINGS SHALL BE USED ONLY FOR THIS SPECIFIC PROJECT/SITE LOCATION. THESE DRAWINGS ARE A COMPOSITE SET OF CONTRACT DOCUMENTS AND SHALL NOT BE SEPARATED FOR DISTRIBUTION. THE GC SHALL REVIEW ALL DRAWINGS
AND PROVIDE/DISTRIBUTE THE ENTIRE SET TO EACH SUBCONTRACTOR.
2. THE GC SHALL VISIT THE SITE TO INSPECT EXISTING CONDITIONS AND VERIFY WORK BEING PERFORMED BEFORE
SUBMITTING COST QUOTATIONS FOR WORK.
3. NOTIFY THE ARCHITECT PROMPTLY OF ANY ERRORS, OMISSIONS, INCONSISTENCIES, DISCREPANCIES AND CONFLICTS WITHIN THE CONTRACT DOCUMENTS AND ITS ASSOCIATED FIELD/PROJECT CONDITIONS SO THAT A RESOLUTION CAN BE
PROVIDED PRIOR TO CONTINUING WITH WORK.
4. DO NOT SCALE THE DRAWINGS. REQUEST ANY MISSING DIMENSIONS FROM THE ARCHITECT
5. ALL WORK PERFORMED SHALL BE IN STRICT COMPLIANCE WITH GOVERNING FEDERAL, STATE AND LOCAL BUILDING CODE REQUIREMENTS, SHALL BE EXECUTED IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS, AND SHALL CONFORM TO SPECIFIC REGULATIONS AS MANDATED BY THE OWNER, THE ARCHITECT, AND THE AUTHORITIES HAVING JURISDICTION. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ANY FEES ASSOCIATED WITH PROCURING SUCH PERMITS AND CERTIFICATES
AND SHALL FURNISH COPIES OF PERMITS, INSPECTIONS, AND CERTIFICATES TO THE OWNER.
6. THE GENERAL CONTRACTOR SHALL COORDINATE ALL WORK TO MINIMIZE DISRUPTION OF ANY EXISTING TENANTS OR BUILDING OPERATIONS. THE GENERAL CONTRACTOR SHALL TAKE ADEQUATE PRECAUTIONS TO PROTECT BUILDING OCCUPANTS, MATERIALS, AND EXISTING CONSTRUCTION THROUGHOUT ALL PHASES OF CONSTRUCTION. DAMAGE TO EXISTING-TO-REMAIN CONSTRUCTION OR EQUIPMENT SHALL BE RESTORED TO ORIGINAL CONDITION AT THE CONTRACTOR'S
EXPENSE.
7. THE GENERAL CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE JOB SITE ON A DAILY BASIS.
8. ANY REQUESTS FOR SUBSTITUTIONS OF ANY SPECIFIED ITEM ARE TO BE SUBMITTED TO THE ARCHITECT IN WRITING AND WILL BE CONSIDERED ONLY IF THE ALTERNATE PROPOSED IS PROVEN TO BE ADVANTAGEOUS TO THE OWNER WITH
RESPECT TO DELIVERY DATE, QUALITY, OR COST.
9. THE MEANS AND METHODS OF CONSTRUCTION, AND TEMPORARY STRUCTURES AND FACILITIES, ARE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE ARCHITECT DOES NOT ASSUME ANY RESPONSIBILITY FOR THE CONTRACTOR'S MEANS
AND METHODS OR FOR TEMPORARY STRUCTURES.
10. DEMOLITION OF EXISTING STRUCTURES IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE CONTRACTOR SHALL
EMPLOY ENGINEERING EXPERTISE AS NEEDED TO ASSIST IN DEMOLITION.
11. JOB SITE SAFETY AND SECURITY ARE THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE GENERAL CONTRACTOR SHALL CONSULT WITH LOCAL FIRE AUTHORITIES TO ASCERTAIN REQUIREMENTS FOR FIRE SUPPRESSION AND SAFETY DURING CONSTRUCTION. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR MEETING OSHA REGULATIONS
DURING CONSTRUCTION.
12. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR STORAGE AND PROTECTION OF BUILDING MATERIALS, AND INSTALLED CONSTRUCTION, FROM INCLEMENT WEATHER, THEFT, AND OTHER HAZARDS. THE GC SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS FOR STORAGE OF MATERIALS. PARTIALLY COMPLETED WALLS SHALL BE COVERED TO PROTECT FROM WATER INTRUSION. DAMAGE, INCLUDING BUT NOT LIMITED TO MOLD, RESULTING FROM WATER INTRUSION DURING CONSTRUCTION SHALL BE REPAIRED AT THE GENERAL CONTRACTOR'S EXPENSE.
13. ANY WORK NOT SHOWN ON THE DRAWINGS, BUT CONSIDERED NECESSARY
FOR THE COMPLETION OF THE WORK IN A PROPER MANNER SHALL BE PROVIDED
BY THE GC WITHOUT ADDITIONAL CHARGE.
14. GC IS RESPONSIBLE FOR ALL SAFETY CONDITIONS RELATING TO PROJECT CONSTRUCTION.
15. GC SHALL BE RESPONSIBLE FOR COORDINATING THE INSTALLATION OF NEW UTILITIES WITH EXISTING ADJACENT UTILITIES.
16. WHERE PRESENT WORK IS DAMAGED IN THE EXECUTION OF THE CONTRACT OR WHERE OPENINGS ARE LEFT DUE TO THE REMOVAL OF PIPES, EQUIPMENT OR APPARATUS, REPAIR OR CLOSE UP TO CORRESPONDING MATERIAL, FINISH OF THE ADJOING WORK. WHERE DAMAGE IS NOT REPAIRABLE, NEW ITEMS OR EQUIPMENT SHALL BE PROVIDED.
17. FLAMMABLE AND COMBUSTIBLE MATERIALS IF USED DURING CONSTRUCTION SHALL BE HANDLED AND STORED IN
ACCORDANCE WITH NFPA 30 (2020).
18. ANY DUCTWORK THAT PENETRATES A RATED ASSEMBLY SHALL BE PROTECT WITH AN APPROPRIATE DAMPER AND TIED TO
THE FIRE ALARM.
19. ALL PROJECT-RELATED REMOVAL/DEMOLITION ACTIVITIES (I.E. PIPE INSULATION, FLOORING, FINISHES) SHALL BE PERFORMED BY THE ABATEMENT CONTRACTOR INSIDE THE REGULATED ABATEMENT WORK AREAS, FOLLOWED BY A THOROUGH CLEANING OF ALL ACCESSIBLE SURFACES/CAVITIES. THE LOCATION OF SITE STORAGE OF ALL MATERIAL, EQUIPMENT AND DECONTAMINATION UNITS AND THE WASTE TRAILER/DUMPSTER SHALL BE COORDINATED WITH AND APPROVED BY THE COR. CONTRACTOR TO COMPLY WITH OSHA ASBESTOS GUIDELINES 1910.10001, REFER TO
SPECIFICATIONS.
20. CONTRACTOR TO COMPLY WITH OSHA 1926 GUIDELINES FOR LEAD PAINT TESTING AND ABATEMENT, REFER TO
SPECIFICATIONS.
SCOPE OF WORK SUMMARY:
VICINITY MAP
M
EM
O
RIAL BLVD (TX-27)
VETERANS H
W
Y (T X-5
1594 N
N
N
N
1311 N
N
N
NORTH
OWNER:
Department of Veterans Affairs - Network Contracting Office NCO17 2002 Scott Boulevard Temple, TX 76504
CONTRACTING OFFICER REPRESENTATIVE (COR):
Kerrville VA Medical Center 3600 Memorial Boulevard Kerrville, TX 78028-3768
Hector L. Corominas Hector.Corominas@va.gov
830-896-2020 x12788
PROJECT MANAGER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com
855.424.3838 x324
319.721.4986 cell
MECHANICAL ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com
855.424.3838 x324
319.721.4986 cell
PLUMBING ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com
855.424.3838 x324
319.721.4986 cell
ELECTRICAL ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Yumei Wang, PE, PMP, LEED AP yumei.wang@RomanykConsulting.com
855.424.3838 x311
402.321.3766 cell
STRUCTURAL ENGINEER:
IMEG CORP.
15 Sunnen Drive Suite 104 St. Louis, MO 63143
Katie M. Goldberg, SE, PE, LEED AP katie.m.goldberg@imegcorp.com
314.951.2538
319.573.1239 cell
PROJECT ARCHITECT:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Gary Friedman Gary.Friedman@RomanykConsulting.com
855.424.3838
720.989.8588 cell
ENVIRONMENTAL ENGINEER:
Argus Environmental Consultants, LLC 10004 Wurzbach #247 San Antonio, Texas 78230
Mark D. Freemyer, CIEC www.ArgusEnvironmental.com
210.493.2560
• 2018 NFPA 101 LIFE SAFETY CODE
• 2018 IBC INTERNATIONAL BUILDING CODE
• 2018 IEBC INTERNATIONAL EXISTING BUILDING CODE
• 2018 IFC INTERNATIONAL FIRE CODE
• 2018 IPC INTERNATIONAL PLUMBING CODE
• 2018 IECC INTERNATIONAL ENERGY CONSERVATION CODE
• 2018 IMC INTERNATIONAL MECHANICAL CODE
• 2018 IFGC INTERNATIONAL FUEL GAS CODE
• 2017 ABAAS VA BARRIER FREE DESIGN STANDARDS
• 2020 NFPA 70 NATIONAL ELECTRIC CODE
• 2020 NFPA 13 STANDARD FOR TTHE INSTALLATION OF SPRINKLER SYSTEMS.
APPLICABLE CODES
IBC OCCUPANCY GROUP I-2 (PRIMINARY HEALTH CARE) SECTION 308.3.
NFPA 101 OCCUPANCY GROUP HEALTH CARE OCCUPANCY SECTION 43.5.1.3 & CHAPTER 18
OCCUPANCY GROUP
NFPA 101 TYPE II (222) SECTION 18.1.6.1 & TABLE 18.1.6.1
IBC I-B TABLE 601
CONSTRUCTION CLASSIFICATION
2 HR. PRIMARY STRUCTURAL FRAME
2 HR. BEARING WALLS-EXTERIOR
2 HR. BEARING WALLS-INTERIOR
NONBEARING WALLS & PARTITIONS TABLE 602
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS PER IBC TABLE 601
INTERIOR FINISHES PER IBC TABLE 803.13
CLASS B INTERIOR EXIT STAIRWAYS & RAMPS
CLASS B CORRIDORS & ENCLOSURE FOR EXIT ACCESS STAIRWAYS & RAMPS
CLASS B ROOMS & ENCLOSED SPACES
0 HR . NONBEARING WALLS & PARTITION-INTERIOR 2 HR.
2 HR. FLOOR CONSTRUCTION & SECONDARY MEMBERS SECTION 202
1 HR. ROOF CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS SECTION 202
BUILDING IS PROTECTED THROUGHOUT BY AN AUTOMATIC SPRINKLER SYSTEM.
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
8910 7 6 5 4 3 2 1
U.S. Department of Veterans Affairs
Project Number
Building Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD
STAMP
CONSULTANT
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered Drawing Number
VA FORM 08 - 6231
Office of Construction and Facilities Management
B
IM
V
IS
N
K er rv ill e
R en vt . B as em en t M ec h
B ld g
/R en vt B as em en t M ec h
R m
B ld g
.r vt
/5
/2
7:
:0
A
M
PROJECT NUMBER - 671A4-22-106
VAMC KERRVILE, TX BUILDING 11 BASEMENT
RENOVATION
CONSTRUCTION DOCUMENTS
NOV. 22, 2022
PROJECT COVER SHEET
GF ACB
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
671A4-22-106VAMC KERRVILE, TX BUILDING 11
BASEMENT RENOVATION
NOV. 22, 2022
11-GI100VAMC KERRVILLE, TX
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com
Revisions: Date:
0 GRID / COLUMN LINE DESIGNATOR
EQUIPMENT NUMBER
WALL TYPE
WINDOW TYPE
ROOM NAME
ROOM NAME / NUMBER
REVISION TAG
NORTH ARROW WITH TRUE
NORTH INDICATION
ELEVATION NUMBER
SECTION
INTERIOR ELEVATION
ENLARGEMENT,
DETAIL
SPOT ELEVATION
Name Elevation
FLOOR LEVEL &
NAME
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
SHEET KEYNOTE
A101
SIM
EXTERIOR ELEVATION
A-101
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
ANNOTATION DRAWING
SYMBOLS
A101
A101
OR
PLAN NORTH
TRUE NORTH
NORTH
INDEX OF DRAWINGS
DISCIPLINE DESIGNATOR
(MAJOR):
G - GENERAL
A - ARCHITECTURE
P - PLUMBING
M - MECHANICAL
E - ELECTRICAL
SHEET TYPE
DESIGNATOR
SHEET NUMBER
WITHIN SERIES
11-AE101
DISCIPLINE DESIGNATOR
(MINOR)
BUILDING NUMBER
ICRA CONTAINMENT WALL-LITE BARRIER ICRA CONTAINMENT WALL-REAL WALL ICRA CONTAINMENT WALL-FIREBLOCK WALL321
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD
STAMP
CONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
E
D
C
B
A
F
Office of Construction and Facilities Management
B
IM
V
IS
N
K er rv ill e
R en vt . B as em en t M ec h
B ld g
/R en vt B as em en t M ec h
R m
B ld g
.r vt
/5
/2
7:
:0
A
M
SHEET INDEX, ABBREVIATIONS, AND SYMBOLS
AND ICRA
MR ACB
CONSTRUCTION DOCUMENTS 671A4-22-106VAMC KERRVILE, TX BUILDING 11
BASEMENT RENOVATION
VAMC KERRVILLE, TX
NOV. 22, 2022
11-GI101
FULLY
SPRINKLERED15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com
NTS NOT TO SCALE
NS... NATIONAL STANDARD...
NOM NOMINAL
NOA
A
NATIONAL OCEANIC &
ATMOSPHERIC...
NO NORMALLY OPEN
NIC NOT IN CONTRACT
NFPA NATIONAL FIRE...
NEM
A
NATIONAL ELECTRICAL
MANUFACTURERS...
NEC NATIONAL ELECTRICAL...
NC NORMALLY CLOSED
NA NOT APPLICABLE (ALSO...
MRI MAGNETIC RESONANCE...
MER MECHANICAL EQUIPMENT...
MIN MINIMUM
MAX MAXIMUM
XFER TRANSFER
LPG LIQUID PROPANE GAS
VHA VETERANS HEALTH...
IPC INTERNATIONAL PLUMBIN...
ID INSIDE DIAMETER UTIL UTILITY
ICU INTENSIVE CARE UNIT UPC UNIVERSAL PLUMBING...
I/O INPUT/OUTPUT UL UNDERWRITER'S...
HAC HOUSEKEEPING AIDE’S... TE... TEMPERATURE
TYP TYPICAL
EX EXISTING (OR EXIST)
EL ELEVATION SPEC SPECIFICATION
ES... EASEMENT SM... SHEET METAL AND AIR...
ETO ETHYLENE OXIDE SI INTERNATIONAL SYSTEM...
EA EXHAUST AIR SHT SHEET
SEN SENSIBLE HEAT
DWG DRAWING SCI SPINAL CODE INJURY
SA SUPPLY AIR
CO2 CARBON DIOXIDE RM ROOM
CENT CENTRIFUGAL RO REVERSE OSMOSIS
RDS ROOM DATA SHEETS
BMT BONE MARROW... RE... REQUIRED
BLDG BUILDING RA RETURN AIR
R/E RETURN OR EXHAUST
ASPE AMERICAN SOCIETY OF...
AS... AMERICAN SOCIETY OF... PSS PRIMARY SECONDARY...
ASH
RAE
AMERICAN SOCIETY OF
HEATING REFRIGERATION... PGW
PROPYLENE
GLYCOL-WATER SOLUTION
ARI AIR CONDITIONING AND...
AMB AMBIENT OR OPERATING ROOM
AFG ABOVE FINISHED GRADE OD OUTSIDE DIAMETER
AFF ABOVE FINISHED FLOOR OC ON CENTER
A/E ARCHITECTS AND... OA OUTSIDE AIR
GENERAL ABBREVIATIONS
NUMBER SHEET TITLE
GENERAL
11-GI100 PROJECT COVER SHEET
11-GI101 SHEET INDEX, ABBREVIATIONS, AND SYMBOLS AND ICRA
11-GI102 SITE PLAN
ARCHITECTURAL
11-AD100 ENLARGED BASEMENT FLOOR PLANS - DEMOLITION
11-AE100 ENLARGED BASEMENT FLOOR PLANS
11-AE500 DETAILS AND SCHEDULES
11-AE501 DETAILS AND SCHEDULES
STRUCTURAL
11-S001 GENERAL NOTES
11-S100 BASEMENT RENO DEMOLISH AND NEW PLANS
SPRINKLER
11-F-100 FIRE PROTECTION SYMBOLS, NOTES, AND ABBREVIATIONS
11-FD100 ENLARGED BASEMENT FLOOR PLAN - SPRINKLER DEMOLITION
11-FP100 ENLARGED BASEMENT FLOOR PLAN - SPRINKLER
PLUMBING
11-P-100 PLUMBING SYMBOLS, NOTES, AND ABBREVIATIONS
11-P-101 PLUMBING SCHEDULES AND DETAILS
11-PD100 ENLARGED BASEMENT FLOOR PLAN - PLUMBING DEMOLITION
11-PD101 ENLARGED BASEMENT FLOOR PLAN - SANITARY DEMOLITION
11-PP100 ENLARGED BASEMENT FLOOR PLAN - PLUMBING
11-PP101 ENLARGED BASEMENT FLOOR PLAN - SANITARY
MECHANICAL
11-M-100 MECHANICAL SYMBOLS, NOTES, AND ABBREVIATIONS
11-M-101 MECHANICAL SCHEDULES AND DETAILS
11-M-102 MECHANICAL CONTROLS
11-MD100 ENLARGED BASEMENT FLOOR PLAN - MECHANICAL EQUIPMENT
DEMOLITION
11-MD101 ENLARGED BASEMENT FLOOR PLAN - HYDRONIC PIPING
DEMOLITION
11-MP100 ENLARGED BASEMENT FLOOR PLAN - MECHANICAL EQUIPMENT
11-MP101 ENLARGED BASEMENT FLOOR PLAN - HYDRONIC PIPING
ELECTRICAL
11-E-001 ELECTRICAL SYMBOLS, NOTES, AND ABBREVIATIONS
11-ED100 ENLARGED BASEMENT FLOOR PLAN - ELECTRICAL DEMOLITION
11-EL100 ENLARGED BASEMENT LIGHTING FLOOR PLAN - ELECTRICAL
11-EP100 ENLARGED BASEMENT POWER FLOOR PLAN - ELECTRICAL
Grand total: 29
MESQUITE
M E S Q U I T E
S U M A C
E L M
E L M
H U
IS
A C H E
BLUEBONNET
LIV
E
OA
K
R E D
O A K
M A P L E
A G A R
IT
A
RE
D
OA
K
B L U E B O N N E T
CY
PR
ES
S
C Y P R E S S
MO
UN
TA
IN
LA
UR
EL
PR
IC
KL
Y
PE
AR
Y U C C A
W A L N U T
PECAN
PECAN
V E
T E
R A
N S
H
IG
H W
A Y
GENERAL NOTES
SITE LEGEND
SERVICE
PIT
ENGINEERING IDF
010D
CRAWL
SPACE
STORAGE
001A
STORAGE
001A
VENDING /
BREAK ROOM
RECREATION
THERAPIST
024C
MUSEUM
028A
DNSERVICE
PIT
ENGINEERING IDF
010D
CRAWL
SPACE
STORAGE
001A
STORAGE
001A
VENDING /
BREAK ROOM
RECREATION
THERAPIST
024C
MUSEUM
028A
LIFE SAFETY PHASING
KEYNOTES
19 8644 98A98B
ANNEX
(OPTIONAL)
IF PRIMARY
IS FULL
1. FIRE SAFETY DURING CONSTRUCTION SHALL COMPLY
WITH THE APPLICABLE REQUIREMENTS OF THE CODE.
2. CONSTRUCTION MATERIALS, FENCES AND EQUIPMENT
SHALL NOT BE PLACED OR STORED TO OBSTRUCT ACCESS
TO FIRE HYDRANTS, STANDPIPES, CATCH BASINS OR
MANHOLES AND NORMAL PEDESTRIAN AND CAR ROUTES.
BUILDING NOT IN SCOPE
EXCAVATION AREA
INFILL AREA
EXISTING SANITARY
EXISTING ABANDONED SANITARY
GENERAL CONTRACTOR
EGRESS PATH.
IRCA BARRIER
1. CONTRACTOR EMPLOYEES/COSNTRUCTION CREW TO
ENTER GATE LOCATED OFF IF 534 VETERAN HWY. SITE
ACCESS FOR CONTRACTOR, MATERIAL DELIVERIES AND
CHECKPOINT.
2. DESIGNATED PARKING FOR CONTRACTOR
3. MATERIAL DELIVERY AND CONTRACTOR STAGING AREA
4. CONTRACTOR ACCESS TO BUILDING
5. CONTRACTOR AND EQUIPMENT ENTRANCE.
6. CLOSED AND SEALED EXISTING DOOR MAY BE USED AS AN
ICRA BARRIER.
DOWN TO
BASEMENT
LEVEL.
DOWN TO
BASEMENT
LEVEL.
DOWN FROM
LEVEL 1.
DOWN FROM
LEVEL 1.
MECH ROOM
MECH ROOM
LIFE SAFETY PHASING NARRATIVE
PHASE 1 (LIFE SAFETY, STAGING AND ABATEMENT)
a. CONTRACTOR STAGING AREA AND FACILITY USE.
b. SAFEGUARDS DURING CONSTRUCTION.
c. ICRA BARRIERS, ETC.
d. PROTECT OR REMOVE EXISTING EQUIPMENT (I.E.
WASH), UTILITIES AND SLAB TO REMAIN.
e. ASBESTOS ABATEMENT IN MECHANICAL ROOM BASED
ON TEST REPORT. (I.E. INSULATION).
f. PROVIDE EGRESS LIGHTING AS NECESSARY IN THE
AREA
g. EXAM CONNECTIVITY OF ALL EXISTING ELECTRICAL
EQUIPMENT WHICH ARE UNUSED AND PREPARE FOR
REMOVAL.
h. PROTECT AND ALL EXISTING FIRE ALARM DEVICES, PROVIDE TEMPORARY FIRE ALARM DEVICES PER
CONSTRUCTION REQUIREMENTS.
i. COORDINATE POWER DOWN TIME DURATION AND
DATES WITH COR.
j. VA MAINTENANCE WILL NEED ACCESS TO THE MECH.
ROOM AT ALL TIMES TO ADDRESS ISSUES AS
NEEDED.
PHASE 2 (DEMOLITION, PREPARATION FOR NEW
WORKSCOPE)
a. TRENCH CONCRETE FLOOR FOR NEW UTILITIES AND
EQUIPMENT LIFT.
b. INSTALL UNDER SLAB UTILITIES (I.E. EQUIPMENT LIFT
DRAIN AND ELECTIRCAL).
c. REMOVE EXISTING UNUSED EQUIPMENT, CONDUIT, PIPING, FIRE ALARM, PA SYSTEM, ETC. NO LONGER IN
USE BACK TO ITS SOURCE. PROVIDE FIRE RATED UL
PENETRATION ASSEMBLIES FOR ANY WALL AND SLAB
EXISTING ROUTES THAT REMAIN.
d. REMOVE I BEAM AND SUPPORTS THAT ARE FOR THE
OLD CHILLER AND NO LONGER IN USE. PATCH AND
REPAIR CONCRETE SLAB ABOVE.
e. REMOVE EXISTING RAMP AND TRENCH DRAIN GRATE
REQUIRED FOR NEW WORK SCOPE. PREPARE
LANDING FOR NEW CONSTRUCTION WORK SCOPE.
f. REMOVE BASEMENT CORRIDOR DOUBLE DOORS AND
FRAME AND CUT NEW CMU OPENING, LINTEL AS
REQUIRED, PREPARE OPENING FOR NEW DOORS,
HARDWARE AND FRAME
g. REMOVE OLD SUMP PUMP AND REPLACE FLOAT
SWITCH.
PHASE 3 (STUB IN NEW UTILITIES)
a. ROUGH-IN NEW ELECTRICAL AND PLUMBING.
b. REMOVE OLD SUMP PUMP AND REPLACE FLOAT
SWITCH.
c. REPLACE EXTERIOR FAN WITH AN UP BLAST
MOUNTED TO EXTERIOR WITH CONTROL T-STAT.
PHASE 4 (LIFE SAFETY)
a. REPLACE ALL FIRE SPRINKLER HEADS IN ALL
ROOMS AND INSTALL NEW WALL MOUNTED
FIRE SPRINKLER HEADS. LAYOUT THE NEW
PIPE AND THEN CONNECT. SEPARATE
SYSTEM FROM REST OF BUILDING FOR NEW
PIPE CONNECTIONS AND COMPLETE TASK,
CONFIRM DOWNTIME WITH COR.
b. CONNECT NEW TAMPER AND FLOW SWITCHES
TO EXISTING FIRE ALARM SYSTEM
PHASE 5 (HOT WATER RECIRCULATION)
a. HOT WATER RECIRCULATION: REMOVE ALL
REMAINING NON-ASBESTOS INSULATION, LAYOUT
ALL NEW LINES NEXT TO EXISTING TO BE
REPLACED. PROVIDE CONNECTION SCHEDULE FOR
LINES AND VALVES AND REPLACEMENT OF 2
BOOSTER/ RECIRC PUMPS, TIE INTO HEAT
EXCHANGER SYSTEM. AND INSULATE, LABEL ALL
LINES.
b. POTABLE COLD-WATER SUPPLY: REMOVE ALL
INSULATION, REPLACE MAIN LINE AND VALVES,
REPLACE ALL BRANCH OFF LINES AND VALVES.
REMOVE 2 BOOSTER PUMPS AND EXISTING PIPING,
REMOVE SECONDARY POTABLE WATER TIE IN
LINE. MAKE TIE-IN TO HOT WATER LINE INSULATE
ALL PIPES.
c. REPLACE PNEUMATIC CONTROL FOR HEATING HOT
WATER W/ DDC. MAP BACK-UP TO FRONT END OF
COMPUTER.
d. INSTALL VDF’S AND CONTROL POINTS ON HOT
WATER SYSTEM.
e. CONNECT POWER TO NEW PUMPS
PHASE 6 (POTABLE HOT-WATER)
a. POTABLE HOT-WATER SUPPLY: REMOVE ALL
REMAINING NON-ASBESTOS INSULATION, LAYOUT
ALL NEW LINES NEXT TO EXISTING TO BE
REPLACED. PROVIDE CONNECTION SCHEDULE FOR
ALL BRANCH OFFLINE AND VALVES.
b. REMOVE AND REPLACE TWO (2) HEAT EXCHANGER
AND ALL VALVES, GAUGES AND MIXING VALVES.
c. TIE SYSTEM INTO COLD POTABLE WATER LINE. TIE
INTO HOT WATER RECIRC LINE, INSULATE ALL
PIPES.
PHASE 7 (GREYWATER/SEWAGE LINES)
a. GREYWATER/ SEWAGE LINES: REMOVE AND
REPLACE MAIN LINE AND ALL TIE IN CONNECTIONS
AND PIPING. HOT WELL TANK.
b. GREYWATER/ SEWAGE LINES: REMOVE AND
REPLACE MAIN LINE AND ALL TIE IN CONNECTIONS
AND PIPING. HOT WELL TANK.
c. LABELING: LABEL ALL PIPING OR COLOR CODE FOR
EASY RECOGNITION OF LINES.
d. ADD TEMPORARY SHUT OFF KEY LOCATIONS TO
ALLOW REDIRECT FOR SERVICING TO LINES.
e. REMOVE ALL NON-ASBESTOS COVERINGS ON
PIPING, INSPECT PIPES AND REPLACES AS NEEDED.
PHASE 8 (STEAM PIPING)
a. RELOCATE EXISTING PIPING WITH A MORE
STREAMLINE DIRECT ROUTE AS NEEDED. INSPECT
AND
b. REPLACE STEAM PIPES AS NEEDED.
c. REPLACE ALL PVC PIPES WITH BLACK STEEL.
d. INSPECT AND REPLACE ALL STEM VALVES AS
NEEDED.
PHASE 9 (LIGHTING AND POWER)
a. INSTALL NEW LED LIGHTS THROUGHOUT THE
THREE (3) ROOMS WITH BALANCED DISTRIBUTION
OF LITE AREAS.
b. INSTALL NEW POWER AND DATA OUTLETS IN
EXISTING WALLS.
PHASE 10 (REPAIR AND PATCH)
a. POUR NEW TRENCH SLAB, SLAB UNDER RAMP, NEW
LANDING, PROTECT DURING CONSTRUCTION.
b. REPAIR AND PATCH AND OR RESTORE EXISTING
CRACKED AND DETERIORATING SLAB.
c. REPLACE TRENCH GRATE WITH DIAMOND SURFACE
SOLID GRATE, PROTECT DURING CONSTRUCTION.
d. INSTALL NEW DOUBLE DOORS AND FRAME.
e. REPAIR OR REPLACE EXISTING CORK SOUND
BOARD CEILING.
f. INSTALL NEW SINK, ELECTORAL OUTLETS.
PHASE 11 (INSTALLATION OF EQUIPMENT)
a. REMOVE EXTERIOR GRATE LOCATED OVER A
BACK ROOM ONCE THE FANS ARE OPERATION.
REPLACE WITH A SECURE AND WATERPROOF
CONCRETE AND BOLLARDS. PROVIDE CANOPY
BREAK METAL CLOSURE AND DUCT SLEEVES.
b. INSTALL NEW INDUSTRIAL DOUBLE SINK.
c. REINSTALL EXISTING EYE WASH STATIONS.
d. INSTALL WALL MOUNTED CIRCULATING FANS AT
WORKSTATIONS.
e. INSTALL EQUIPMENT LIFT.
f. ENCLOSE AREA AROUND THE MED AIR / VAC
AND INSTALL A MINI SPLIT TO RELOCATE AIR
TEMP EQUIPMENT.
PHASE 12 (FURNISHINGS)
a. BRING IN NEW INDUSTRIAL CASEWORK
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD
STAMP
CONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
E
D
C
B
A
F
Office of Construction and Facilities Management
B
IM
V
IS
N
K er rv ill e
R en vt . B as em en t M ec h
B ld g
/R en vt B as em en t M ec h
R m
B ld g
.r vt
/5
/2
7:
:1
A
M
SITE PLAN
MR ACB
CONSTRUCTION DOCUMENTS 671A4-22-106VAMC KERRVILE, TX BUILDING 11
BASEMENT RENOVATION
VAMC KERRVILLE, TX
NOV. 22, 2022
11-GI102
FULLY
SPRINKLERED15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com
1" = 100'-0"
SITE PLAN
Approx. Total BSF= 417,457
121 FUEL FARM --
120 MAIN SIGN --
119 COMMAND CENTER 6,250
117 SHUTTLE WAITING AREA 900
115 GROUNDS SHOP 12,000
114 ENGINEERING STORAGE 11,500
99 EMERGENCY GENERATORS --
98B LOGISTICS STORAGE 12,000
98A EMS/LAUNDRY STORAGE 4,405
97 CHILLER PLANT 1,200
96 NURSING HOME CARE UNIT 63,726
94 HELIPORT WIND SOCK --
93 HELIPAD --
92 HELIPORT CONTROL BUILDING 120
91 COOLING TOWERS --
90 GENERATOR/REAR ELECTRICAL VAULT 1,997
88 TWO CAR GARAGE 409
87 TWO CAR GARAGE 409
86 BOILER PLANT STORAGE 800
85 TWO CAR GARAGE 200
84 WATER TREATMENT PLANT 150
83 STEEL WATER TANK --
62 TRANSFORMER VAULT 100
51 QUARTERS (CONDEMNED) 3,700
50 QUARTERS (CONDEMNED) 3,200
49 QUARTERS (CONDEMNED) 3,200
48 POLICE TRAINING 3,200
47 EMS/LAUNDRY STORAGE 4,800
46 TRANSPORTATION/PLUMBING 18,000
44/119 LAUNDRY MAINT SHOP 900
41 VACANT 200
40 SAFETY OFFICE 200
38 CONCRETE WATER TOWER --
32 TWO CAR GARAGE 409
29 ENGINEERING 9,329
22 PAINT SHOP 1,560
21 DIRECTOR'S GARAGE 490
20 DIRECTOR'S QUARTERS 2,684
19 BOILER PLANT 5,593
18 LAUNDRY 17,516
11 MAIN HOSPITAL 209,808
2 RECORDS 5,654
1 EDUCATION/AUDITORIUM 10,848
NO. NAME APPROX. BSF
SITE BLDG LEGEND
1/16" = 1'-0"
LEVEL 01 FLOOR PLAN- STAGING PLAN
1/16" = 1'-0"
BASEMENT FLOOR PLAN - STAGING PLAN
SERVICE
PIT
CRAWL
SPACE
MAIN ELEVATOR
LOBBY
ELECT.
CLOSET
SERVICE
ELEVATOR
LOBBY
MUSEUM
028A
IDF
ELECT.
CLOSET
UP
SERVICE
PIT
CRAWL
SPACE
MAIN ELEVATOR
LOBBY
ELECT.
CLOSET
SERVICE
ELEVATOR
LOBBY
MUSEUM
028A
IDF
ELECT.
CLOSET
2 22 2 2 2
2 22 2 2 2 2 2 2 2 2
2 22 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
2 22 2
2 2 22 2 2 2 2 2 2
2 22
2 22 2 2 2 2 2 2
1 11 1 1 1 1 1 1
1 11 1 1 1 1
SB SBSB SB SB SB
IB
IB
IB
IB
IB
KEYNOTES GENERAL NOTES:PLAN LEGENDLEGEND
RAMP
UP
RAMP
UP
EXISTING
8" CHR UP
EXISTING
8" CHS UP
1689 SF
MECH ROOM
099F
70 SF
STAIR-1
S-001
6' - 0"
8"
4' - 0"
1. REFER TO ENLARGED FLOOR PLANS, ELEVATIONS AND
DETAILS ON OTHER DRAWING SHEETS FOR ADDITIONAL
DETAILS OF NEW WORK.
2. REFER TO SHEET SERIES FP, P, M, E, T AND V FOR
ADDITIONAL DETAIL OF DEMOLITION AND NEW WORK
RELATED TO THOSE DISCIPLINES.
3. REMOVE I-BEAM AND SUPPORTS THAT FOR THE OLD CHILLER
AND IS NO LONGER IN USE. GC TO RETAIN DELEGATED
DESIGN STRUCTURAL ENGINEER TO REVIEW CONSTRUCTION
OF SUPPORTS ATTACHED TO CONCRETE FLOOR SLAB PRIOR
TO WORK SCOPE PROCEEDING TO DETERMINE SLAB REPAIR.
4. ALL COMPONENTS INDICATED TO BE REMOVED AND
SALVAGED SHALL BE LABELED AND RETURNED TO THE
OWNER. COORDINATE WITH COR FOR LOCATIONS.
5. ALL COMPONENTS INDICATED ONLY TO BE REMOVED SHALL
BE DISPOSED OFF-SITE DAILY
6. EXISTING AREAS TO REMAIN UNDISTURBED. PATCH AND
REPAIR ANY DAMAGE CAUSED BY DEMOLITION. PROTECT
THESE AREAS FROM THE SPREAD OF DIRT AND DEBRIS
ASSOCIATED WITH ANY DEMOLITION AND/OR
IMPROVEMENTS ASSOCIATED WITH WORK REQUIRED
OUTSIDE OF THE PROJECT AREA.
7. PROVIDE UL FIRE RATED ASSEMBLY FOR ALL NEW WALL AND
SLAB PENETRATIONS DUE TO NEW CONSTRUCTION,
PROVIDE LABELS.
8. ADVISE THE ARCHITECT OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH DEMOLITION WORK SCOPE.
9. THE GENERAL CONTRACTOR (GC) SHALL BE RESPONSIBLE
FOR TAKING ADEQUATE PRECAUTIONS TO PROTECT
BUILDING OCCUPANTS, MATERIALS, AND EXISTING FINISHES
THROUGHOUT ALL PHASES OF CONSTRUCTION. ANY
DAMAGE TO THE EXISTING COMPONENTS, WHICH HAVE NOT
BEEN IDENTIFIED FOR REMOVAL/DEMOLITION, SHALL BE
RESTORED TO THE ORIGINAL CONDITION AT THE GC'S
EXPENSE
10. GC IS RESPONSIBLE FOR KEEPING A CLEAN AND SAFE
ENVIRONMENT THROUGHOUT CONSTRUCTION
11. GENERAL CONTRACTOR (GC) SHALL COMPLY WITH VA'S
ICRA REQUIREMENTS. COORDINATE WITH VA PRIOR TO
COMMENCING ANY DEMOLITION ACTIVITIES.
12. ALL CABLING, PA SYSTEM, CONDUIT, PIPING, ETC. SHALL BE
REMOVED BACK TO POINT OF ORIGIN (WHICH MAY REQUIRE
WORK OUTSIDE THIS FOOTPRINT).REF, TO MEP&FP
DEMOLITION DRAWINGS.
13. AFTER DEMO, GENERAL CONTRACTOR WILL FIELD VERIFY
MEASUREMENTS AND CONDITIONS PRIOR TO BEGINNING
NEW CONSTRUCTION.
14. GENERAL CONTRACTOR (GC) SHALL PROVIDE DETAILED
DEMO PLAN WHICH CLEARLY SHOWS HOW ACCESS
TO/FROM OCCUPIED AREAS IS MAINTAINED.
15. WORK SHALL BE NIGHTS/WEEKENDS AND COORDINATED
WITH THE COR 2 WEEKS AHEAD OF TIME.
NO SCOPE OF WORK ASSOCIATED WITH
THIS OCCUPIED AREA
SCOPE OF WORK AREA AS DESIGNATED/NOTED
WITH BLACK BORDER
EXISTING WALL SHALL REMAIN
EXISTING DOOR, FRAME AND HARDWARE
SHALL REMAIN
EXISTING WALL AND ASSOCIATED COMPONENTS
SHALL BE REMOVED - REFER TO DEMOLITION
KEYNOTES FOR ADDITIONAL DETAILS AT SPECIFIC
CONDITIONS.
EXISTING DOOR, FRAME, HARDWARE AND
ASSOCIATED COMPONENTS SHALL BE REMOVED
-REFER TO DEMOLITION KEYNOTES FOR
ADDITIONAL DETAILS AT SPECIFIC CONDITIONS
BASEMENT
LEVEL
FB1 = FIRE BARRIER 1HR
FB2 = FIRE BARRIER 2HR
SB1 = SMOKE BARRIER- 1 HOUR
CONTRACTOR ACCESS
UTILITY LOCATION IN CORRIDOR
SMOKE COMPARTMENTS
ICREA BARRIER
REFERENCE WALL TYPES SHEET FOR
CONSTRUCTION TYPE
AREA WITHIN SCOPE OF WORK
AREA NOT IN CONTRACT
NON-RATED INTERIOR PARTITION WALL
NON-RATED INTERIOR PARTITION WALL (WITH
INSULATION)
EXISTING WALL TO REMAIN
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD
STAMP
CONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
E
D
C
B
A
F
Office of Construction and Facilities Management
B
IM
V
IS
N
K er rv ill e
R en vt . B as em en t M ec h
B ld g
/R en vt B as em en t M ec h
R m
B ld g
.r vt
/5
/2
7:
:0
A
M
ENLARGED BASEMENT FLOOR PLANS -
DEMOLITION
MR ACB
CONSTRUCTION DOCUMENTS 671A4-22-106VAMC KERRVILE, TX BUILDING 11
BASEMENT RENOVATION
VAMC KERRVILLE, TX
NOV. 22, 2022
11-AD100
FULLY
SPRINKLERED
1/4" = 1'-0"
ENLARGED BASEMENT FLOOR PLAN - DEMOLITION
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com
NO. DESCRIPTION
1 MECHAICAL EQUIPMENT; SHOWN FOR REFERENCE.
3 REMOVE EXISTING CABINETRY. REMOVE EXISTING FLAMABLE CABINET FOR
REUSE.
4 COORDINATE EXISTING TRENCH DRAIN WITH LOCATION OF NEW EQUIPEMNT LIFT
AND REVISED LANDING.
5 EXISTING DOUBLE DOORS TO BE REPLACED, REUSE EXISTING HARDWARE.
7 DEMOLISH EXISTING LANDING, REMOVE RAMP AND PREPARE SURFACE FOR NEW
LANDING ONTO LIFT.
9 REMOVE EXISTING WALL HUNG PORCELAIN LAVATORY.
10 EXISTING EYEWASH TO REMAIN, PROTECT OR REMOVE TEMPORARILY DURING
RENOVATION.
11 PROTECT EXISTING DRAIN DURING CONSTRUCTION.
12 EXISTING AREAS TO REMAIN UNDISTURBED. PATCH AND REPAIR ANY DAMAGE
CAUSED BY DEMOLITION AND/OR CONSTRUCTION. CONTRACTOR TO PROTECT
THESE AREAS FROM THE SPREAD OF DIRT AND DEBRIS ASSOCIATED WITH ANY
DEMOLITION AND/OR IMPROVMENTS ASSOCIATED WITH WORK REQUIRED OUTSIDE
THE PROJECT AREA.
13 CUT OUT EXISTING SLAB AND PREPARE FOR NEW EQUIPMENT LIFT.
14 STUB IN DRAIN PIPING FOR NEW EQUIPMENT LIFT DRAIN. TRENCH CONCRETE SLAB
AS REQUIRED.
15 NEW EYEWASH/SHOWER STATION AND PIPING.
16 STUB IN NEW PLUMBING PIPING FOR NEW SINKS, TRENCH CONCRETE SLAB AS
REQUIRED.
17 PROTECT EXISTING EQUIPMENT.
18 REMOVE ALL OLD UNUSED PIPING, CONDUIT, ALARM, ECT. REFER TO MEP&FP
DRAWINGS.
19 REPAIR DETERIORATING CONCRETE SLAB.
20 PROVIDE ICRA BARRIER OR SEAL EXISITNG DOUBLE DOORS TO SERVE AS ICRA
BARRIER.
21 ELEVATOR USED FOR CONTRACTOR ACCESS AND MATERIAL DELIVERY,
COORDINATE SCHEDULE AND TIME WITH COR.
23 TRENCH EXISTING CONCRETE SLAB FOR NEW EQUPMENT LIFT DRAIN AND
PROVIDE A VAPOR BARRER UNTER CONCRETE TRENCH AND EQUIPMENT
LIFT PIT.
25 PROTECT EXISTING SPRINKLER HEADS AND LIGHTING.
26 REMOVE EXISTING LEVEL 01 CHASE ACCESS PANEL AND ASPHALT AREA, PREPARE
FOR NIEW CIP CONC. CHASE COVER AND DUCT FLASHING.
27 PROTECT FLOORINGS, WALLS AND PEDESTRIAN ACCESS
28 REMOVE CORK SOUND PROOFING AND PREPARE UNDERSIDE OF SLAB SURFACE
FOR SPRAY APPLIED ACOUSTIC INSULATION.BASIS OF DESIGN PRODUCT
SONASPRAY FC (INTERNATIONAL CELLULOSE CORPORATION) UL RATED, 1" THICK
(NRC .85) ARTIC WHITE.
29 REMOVE CORK SOUND PROOFING AND PREPARE UNDERSIDE OF SLAB SURFACE
FOR INSULATION
NTS
KEYPLAN
CRAWL
SPACE
MUSEUM
028A
UP
CRAWL
SPACE
MUSEUM
028A
2 22 2 2 2
2 22 2 2 2 2 2 2 2 2
2 22 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
2 22 2
2 2 22 2 2 2 2 2 2
2 22
2 22 2 2 2 2 2 2
1 11 1 1 1 1 1 1
1 11 1 1 1 1
SB SBSB SB SB SB
KEYNOTES
FLOOR PLAN NOTESPLAN LEGEND LEGEND
219 SF
STORAGE
B061
1468 SF
MECH ROOM
099G
EQUIPMENT
LIFT
RAMP
UP
1689 SF
MECH ROOM
099F
NON-ACCESSIBLE NON-ACCESSIBLE
22 2
11-AE100
11-AE500
Sim
11-AE500
11-AE500
EXTENDED
LANDING
4' - 11"
CABINET 3
SHELVES
60X24X66
CABINET 3
SHELVES
80 60X24X84
CABINET 2 SHELF,
7 DRAWERS
36X24X78
CABINET 2 SHELF,
7 DRAWERS
36X24X78
11-AE500 4
11-AE500
/8
/8
7' - 3 3/8"
8"
8"
11-AE500
6' - 0"
1. GC SHALL VERIFY DIMENSIONS OF OWNER FURNISHED
EQUIPMENT AND COORDINATE INSTALLATION WITH ALL
TRADES WHERE REQUIRED.
2. THE CONTRACTOR SHALL PREVENT UNAUTHORIZED
PERSONNEL FROM ACCESS TO CONSTRUCTION AREAS AND
THE AREA SHALL BE SECURED FROM UNAUTHORIZED ENTRY
DURING OFF HOURS.
3. PROVIDE UL FIRE RATED ASSEMBLY FOR ALL AXISTING WALL
AND SLAB PENETRATIONS WHERRE EXISTING DUCTS, PIPES,
ECT. HAVE BEEN REMOVED. FER. WALL TYPES SHEET FOR
CONSTRUCTION TYPE.
4. PATCH FLOOR AND WALLS AS REQUIRED WHERE EXISTING
CONSTRUCTION IS REMOVED TO MATCH EXISTING ADJACENT
SURFACES.
5. CONTRACTOR TO COORDINATE WITH COR FOR QUESTIONS
AND/OR CONCERNS REGARDING SITE ACCESS (WORKERS
AND MATERIALS), INFECTION CONTROL, MATERIAL DISPOSAL,
AND HOURS OF OPERATION.
11-AE500
ACCESS UNDERNEATH STRUCTURE
1' - 9"4' - 0"4' - 0"1' - 9"
NO SCOPE OF WORK ASSOCIATED WITH
THIS OCCUPIED AREA
SCOPE OF WORK AREA AS DESIGNATED/NOTED
WITH BLACK BORDER
EXISTING WALL SHALL REMAIN
EXISTING DOOR, FRAME AND HARDWARE
SHALL REMAIN
EXISTING WALL AND ASSOCIATED COMPONENTS
SHALL BE REMOVED - REFER TO DEMOLITION
KEYNOTES FOR ADDITIONAL DETAILS AT SPECIFIC
CONDITIONS.
EXISTING DOOR, FRAME, HARDWARE AND
ASSOCIATED COMPONENTS SHALL BE REMOVED
-REFER TO DEMOLITION KEYNOTES FOR
ADDITIONAL DETAILS AT SPECIFIC CONDITIONS
BASEMENT
LEVEL
FB1 = FIRE BARRIER 1HR
FB2 = FIRE BARRIER 2HR
SB1 = SMOKE BARRIER- 1 HOUR
CONTRACTOR ACCESS
UTILITY LOCATION IN CORRIDOR
SMOKE COMPARTMENTS
ICREA BARRIER
REFERENCE WALL TYPES SHEET FOR
CONSTRUCTION TYPE
AREA WITHIN SCOPE OF WORK
AREA NOT IN CONTRACT
NON-RATED INTERIOR PARTITION WALL
NON-RATED INTERIOR PARTITION WALL (WITH
INSULATION)
EXISTING WALL TO REMAIN
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD
STAMP
CONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
E
D
C
B
A
F
Office of Construction and Facilities Management
B
IM
V
IS
N
K er rv ill e
R en vt . B as em en t M ec h
B ld g
/R en vt B as em en t M ec h
R m
B ld g
.r vt
/5
/2
7:
:0
A
M
ENLARGED BASEMENT FLOOR PLANS
MR ACB
CONSTRUCTION DOCUMENTS 671A4-22-106VAMC KERRVILE, TX BUILDING 11
BASEMENT RENOVATION
VAMC KERRVILLE, TX
NOV. 22, 2022
11-AE100
FULLY
SPRINKLERED
1/4" = 1'-0"
ENLARGED BASEMENT FLOOR PLAN
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com
NO. DESCRIPTION
1 MECHANICAL AND ELECTRICAL EQUIPMENT FOR REFERENCE ONLY.
2 NEW INDUSTRIAL PREMANUFACTURED CABINETS. CABINTES BASIS OF DESIGN
DURHAM MANUFACTURING.
(1) CABINET 14 GAUGE, 3 SHELVES 60X24X84) SSC-602484-BDLP-35-95)
(1) CABINET 12 GAUGE, 3 SHELVES 60X24X66) (HDC246066-3595)
(2) CABINET 12 GUAGE, 2 SHELF, 7 DRAWERS 36X24X78 (HDCD243678-7805)
4 PROTECT RENOVATED CONCRETE FLOOR AND DRAINS.
5 REPLACE EXISTING HM DOOR AND REUSE HARDWARE, SEE DOOR SCHEDULE.
6 NEW INDUSTRIAL DOUBLE BOWL SERVICE SINK, BASIS OF DESIGN PRODUCT ELKAY
MODEL NO. RNSF82482LR2 (89 1/4X29 3/4X12 3/4 DOUBLE FLOOR COMPARTMENT
SINK WITH DRAINBOARD.
7 EXISTING EYEWASH TO REMAIN, PROTECT OR REMOVE TEMPORARILY DURING
RENOVATION.
8 EXISTING AREAS TO REMAIN UNDISTURBED. PATCH AND REPAIR ANY DAMAGE
CAUSED BY DEMOLITION AND/OR CONSTRUCTION. CONTRACTOR TO PROTECT
THESE AREAS FROM THE SPREAD OF DIRT AND DEBRIS ASSOCIATED WITH ANY
DEMOLITION AND/OR IMPROVMENTS ASSOCIATED WITH WORK REQUIRED OUTSIDE
THE PROJECT AREA.
10 NEW EQUIPMENT LIFT (DRAIN TO CONCRETE PIT). PROVIDE UNDER SLAB
WATERPROOFING IN PIT.
12 NEW CONCRETE EXTERIOR SLAB CHASE COVER. CANOPY ABOVE OPENING FOR
DUCTS, WATERPROOF OPENING WITH BREAKMETAL FLASHING AND DUCT
SLEEVES, WEATHERPROOFING.
13 EXISTING DUCTS TO REMAIN. PROTECT DURING CONSTRUCTION.
14 NEW OVERHEAD LIGHTING, REF. ELECTRICAL DRAWINGS.
15 NEW WALL MOUNTED SPRINKLER HEADS AND CEILING SPRINKLERS, REF. TO FIRE
PROTECTION DRAWINGS.
16 METAL FLASHING, WATERPROOF OPENING WITH BREAK METAL FLASHING, DUCT
SLEEVES AND WEATHERPROOFING TO BE INSTALLED AROUND EXISTING DUCTS.
17 PROVIDE AND REPAIR FLASHING ENCLOSURE AND PIPE SLEVES AT METAL CANOPY
ABOVE.
18 PROVIDE ICRA BARRIER OR SEAL EXISITNG DOUBLE DOORS TO SERVE AS ICRA
BARRIER.
19 NEW EYEWASH/SHOWER STATION AND PIPING.
20 COORDINATE NEW LANDING RAILS WITH EQUIPMENT LIFT.
21 NEW EQUIPMENT LIFT, BASIS OF DESIGN ADVANCED LIFT (RECESSED SISSORS
EQUIPMENT LIFT T2-50608 SERIES, CUSTOM SIE 4X6).
22 REPLACE EXISTING GRATE TRENCH WITH SOLID DIAMOND TEXTURE TRENCH
COVER.
23 UNDERSIDE OF STRUCTURE SPRAY APPLIED ACOUSTIC INSULATION. BASIS OF
DESIGN PRODUCT SONASPRAY FC (INTERNATIONAL CELLULOSE CORPORATION)
UL RATED, 1" THICK (NRC 0.85) ARTIC WHITE.
1/4" = 1'-0"
CHASE COVER LEVEL 01
NTS
KEYPLAN
6'
BRIDGE
WIDTH
8' PLA TFORM LENGTH
6'
PLA TFORM
WID TH
5 1/ 4"
8 1/4"
BRIDGE RECESS 8'-6 1 /2" PI T LENGTH
6'-2"
PIT
WIDTH
8 1/ 4"
2'-8"
5'-6" RA ISED HEI GHT
8 1/4"
PIT D EPTH
4'-10"
TRAVEL
3'-6"
GUARDRAIL
A
A
HOSE RECESS
STRUCTURE
NEW CIP CONCRETE PIT, REFER
TO STRUCTURAL.
REMOVABLE STEEL
GUARDRAILS WITH
SAFETY CHAIN PER
ANSI MH 29.1
BLACK AND YELLOW
SAFETY STRIPING
(4) SIDES
REMOVABLE
SAFETY
MAINTENANCE BAR
RAWL-STUD WEDGE
ANCHORS,WEJ-IT
STUDS, OR EQUIVALENT
INSTALLER TO USE CONTINUOUS
SHIMS AND GROUT AS REQUIRED
TO BRING PLATFORM FLUSH
WITH FLOOR.
LIFT BASE IS
PRE-DRILLED FOR
LAGGING LIFT TO PIT
FLOOR (4) PLACES.
(2) RAMS WITH
CHROME
PLATED RODS
8" BEVEL
TOE
GUARDS
PER ANSI MH
29.1 (4) SIDES
4" HIGH KICKPLATE
MIDRAIL
BRIDGE LIFTING CHAIN
3" CONDUIT FOR
HYDRAULIC CONNECTING
HOSE
0.5" CONDUIT (IF LIMIT
SWTICH OR ELECTRIC
TOE GUARD IS USED)
OR 1" CONDUIT (IF
QUICK DISCONNECT IS
USED)
CURB ANGLES, BY OTHERS
(TYP. 3" X 3" X .25")
BRIDGE LIFTING CHAIN
12" LONG X
72" WIDE
HINGED
STEEL BRIDGE
USE 32" LONG 2X4 LUMBER
TO FORM HOSE RECESS
PIT DRAIN
SAFETY CHAIN
SAFETY CHAIN
SAFETY TREAD SURFACE
HYDRAULIC
CONNECTING
HOSE
GUARDRAIL
LEVEL 01
0' - 0"
VIF. Block out
11-AE500
EXISTING BLDG.
MASONRY WALL
CONT. EXPANSION
JOINT WITH ELASTIC
FILLER
CIP CONC-SLAB, REFER
TO STRUCTURAL
DRAWINGS
SEALANT & BACKER ROD
EXISTING CONCRETE
CHASE FOUNDATION
WALL.
EXISTING ASPHALT ROAD
CONCRETE BLOCKOUT
FOR DUCT(S),
WATERPROOF
ENCLOSURE, FLASHING
AND PIPE SLEEVES.
EXISTING CHASE
CONC. FOUNDATION
WALL BEYOND
SLOPE TO DRAIN
/1
EXTERIOR
4% SLOPE,
4" FRONT
WATERSTOP
STRUCTURAL DOWELS
WALL FLASHING
VIF.
6' - 7 3/4"
COORDINATE WITH
STRUCTURE, DOWELS
DIMENSIONS ETC.
NEW DIAMOND STEEL PLATE
TRENCH COVER. REMOVE
EXISTING GRATE, SEE
DIMENSIONED PLAN FOR
EXTENT OF WORK.
EXISTING
CONCRETE
SLAB
EXISTING CIP
CONCRETE TRENCH
1' - 4 3/4" V.I.F.
SHIM AND GROUT AS
REQUIRED TO SUIT
SLOPE OF STRUTURE.
6" DIA. STL BOLLARD
EXISTING ASPHALT
ROAD
6'-0"
'-2
6MIL VAPOR
BARRIER
DOWEL BARS REFER
TO STRUCTURAL
DRAWINGS.
NEW CIP
CONCRETE SLAB
ON GRADE
EXISTING SLAB
ON GRADE
1 1/4" DIA. VERTICAL PIPE
SUPPORTS SPACED EQUALLY,
MAX. 4'-0" SPACING
EXTERNAL ALUMINUM MAGNESIUM
CONNECTIONS
1-1/4" DIA. STL. PIPE RAIL
PAINTED.
SECURELY BOLT VERTICAL RAIL SUPPORTS
TO FLOOR AND COVER WITH DECORATIVE
ESCUTCHEON
EXISTING CONCRETE
SLAB LANDING
REMOVABLE PIPE RAIL SLEEVE
1-1/2" ALUMINUM STANDARD RAILING
FLANGE.
NEW DIAMOND STEEL PLATE
TRENCH COVER. REMOVE
EXISTING GRATE, SEE
DIMENSIONED PLAN FOR
EXTENT OF WORK.
EXISTING
CONCRETE
SLAB
EXISTING CIP
CONCRETE TRENCH
8" V.I.F.
NOTE:
REFER TO STRUCTURAL DRAWINGS.
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD
STAMP
CONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
E
D
C
B
A
F
Office of Construction and Facilities Management
B
IM
V
IS
N
K er rv ill e
R en vt . B as em en t M ec h
B ld g
/R en vt B as em en t M ec h
R m
B ld g
.r vt
/5
/2
7:
:0
A
M
DETAILS AND SCHEDULES
MR ACB
CONSTRUCTION DOCUMENTS 671A4-22-106VAMC KERRVILE, TX BUILDING 11
BASEMENT RENOVATION
VAMC KERRVILLE, TX
NOV. 22, 2022
11-AE500
FULLY
SPRINKLERED15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com
3/4" = 1'-0"
ROOF CHASE SECTION
3/4" = 1'-0"
TRENCH COVER PLATE DETAIL
3/4" = 1'-0"
BOLLARD DETAIL
3/4" = 1'-0"
EQUIPMENT LIFT DETAIL
3/4" = 1'-0"
TRENCH FILL DETAIL
1 1/2" = 1'-0"
GUARDRAIL DETAIL.
3/4" = 1'-0"
PLUMBING TRENCH COVER PLATE DETAIL
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD
STAMP
CONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
E
D
C
B
A
F
Office of Construction and Facilities Management
B
IM
V
IS
N
K er rv ill e
R en vt . B as em en t M ec h
B ld g
/R en vt B as em en t M ec h
R m
B ld g
.r vt
/5
/2
7:
:0
A
M
DETAILS AND SCHEDULES
MR ACB
CONSTRUCTION DOCUMENTS 671A4-22-106VAMC KERRVILE, TX BUILDING 11
BASEMENT RENOVATION
VAMC KERRVILLE, TX
NOV. 22, 2022
11-AE501
FULLY
SPRINKLERED15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com
A-501 - DOOR SCHEDULE
LOCATION DOOR SLAB FRAME DETAILS
HARDWARE
ACCESS
CONTROL NOTES / REMARKS
DOOR
NUMBER
SIZE
TYPE RATING MATL. FINISH MATL. TYPE HEAD JAMB SILLWIDTH HEIGHT THK
LEVEL 0B
129 6' - 0" 7' - 0" 1 3/4" A 20 MIN. HM PTD REUSE EXISTING HARDWARE AND HM JAMB TO REMAIN.
STRUCTURAL ABBREVIATION KEY
ABBR: DESCRIPTION: ABBR: DESCRIPTION:
KSF
KSI
L
LBS
LL
LLH
LLV
LONG.
LSH
LSV
LT WT
MAX
MECH
MANUF
MIN
NIC
NTS
OC
OH
OPNG
OSB
PCF
P.H.
PJP
PL
PLF
PSF
PSI
PT
R
REINF
REQD
RTU
SC
SCHED
SFRS
SIM
SL
S.M.S.
SP
SPECS
SQ
STIFF
STL
SYM
T&B T.O.
TC
TEMP
tf
THK
TRANS
TYP
UON
VERT
VIF
W/
WP
WT
WWR
(E) A.B.
ARCH
B.O.
bf
BF
BM
B.N.
BOTT
BTWN
CFSF
CGS
CJP
CLR
CL
CMU
COL
CONC
CONN
CONST
CONT
COORD
DIA
DL
DET
DWG
DWL
EA
EF
EFF
EL
ELEC
EMBED
E.N.
EOD
EOS
EQ
EQUIP
ETC
EW
EXP
EXT
f 'c
FDN
F.N.
FT
FTG
Fy
GA
GALV
GLB
GT
HORIZ
HSA
HSB
JT
K, KIP
NUMBER OR POUNDS
AT
DEGREE
DIAMETER
EXISTING
ANCHOR BOLT
ARCHITECT, -URE, -URAL
BOTTOM OF
BEAM FLANGE WIDTH
BRACE FRAME
BEAM
BOUNDARY NAILING
BOTTOM
BETWEEN
COLD FORM STEEL FRAMING
CENTER OF GRAVITY OF THE TENDON
COMPLETE JOINT PENETRATION WELD
CLEAR
CENTERLINE
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
COORDINATION
DIAMETER
DEAD LOAD
DETAIL
DRAWING
DOWEL
EACH
EACH FACE
EFFECTIVE
ELEVATION
ELECTRICAL
EMBEDMENT
EDGE NAILING
EDGE OF DECK
EDGE OF SLAB
EQUAL
EQUIPMENT
ETCETERA
EACH WAY
EXPANSION
EXTERIOR
CONCRETE COMPRESSIVE STRENGTH
FOUNDATION
FIELD NAILING
FOOT
FOOTING
YIELD STRESS
GAGE OR GAUGE
GALVANIZED
GLULAM BEAM
GIRDER TRUSS
HORIZONTAL
HEADED STUD ANCHOR
HIGH STRENGTH BOLT
JOINT
KILOPOUND (1,000 POUNDS)
KIPS PER SQUARE FOOT
KIPS PER SQUARE INCH
LENGTH
POUNDS
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL
LONG SIDE HORIZONTAL
LONG SIDE VERTICAL
LIGHTWEIGHT
MAXIMUM
MECHANICAL
MANUFACTURER
MINIMUM
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
OPPOSITE HAND
OPENING
ORIENTED STRAND BOARD
POUNDS PER CUBIC FOOT
PENTHOUSE
PARTIAL JOINT PENETRATION WELD
PLATE
POUNDS PER LINEAR FOOT
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POST-TENSION, -ED, -ING
RADIUS
REINFORCING, -MENT, -ED
REQUIRED
ROOF TOP UNIT
SLIP CRITICAL
SCHEDULE
SEISMIC FORCE-RESISTING SYSTEM
SIMILAR
SNOW LOAD
SHEET METAL SCREW
SPACE(S)
SPECIFICATION(S)
SQUARE
STIFFENER
STEEL
SYMMETRICAL
TOP AND BOTTOM
TOP OF
PRE-TENSIONED BOLT
TEMPERATURE
BEAM FLANGE THICKNESS
THICK
TRANSVERSE
TYPICAL
UNLESS OTHERWISE NOTED
VERTICAL
VERIFY IN FIELD
WITH
WORK POINT
WEIGHT
WELDED WIRE REINFORCING
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
S300
SIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE KEY:
NEW WORK
(DARK SOLID LINE/LINE WEIGHT WILL VARY)
NEW WORK BELOW OR BEYOND VIEW
(DARK DASH LINE)
EXISTING TO BE REMOVED
(DARK DASH LINE)
EXISTING WORK TO REMAIN
(HALFTONED SOLID LINE/LINE WEIGHT WILL VARY)
NON STRUCTURAL
(HALFTONED LIGHT SOLID LINE)
GRID OR CENTERLINE
MATERIAL LEGEND:
CONCRETE - CAST-IN-PLACE
CONCRETE - EXISTING
EARTH
GRAVEL OR GRANULAR FILL
GROUT OR DRYPACK OR SAND
MASONRY
METAL / COLD-FORM STUD
PRECAST CONCRETE
STEEL
COLUMN DESIGNATION
BASE PLATE MARK
SF#(+X'-X")
P# (+X'-X")
FOOTING MARK (TOP ELEVATION)
PIER MARK (TOP ELEVATION)
N O R
HT
W XxX
BPX
STRUCTURAL SYMBOL LIST
GENERAL SYMBOLS:
SYMBOL DESCRIPTION DETAIL REFERENCE
TOP OF STRUCTURAL FRAMING ABOVE
ELEVATION (+0'-0")
(+16'-3")
TOP OF STRUCTURAL FOUNDATION
BELOW ELEVATION (+0'-0")
(-2'-0")
STEEL SYMBOLS:
SYMBOL DESCRIPTION DETAIL REFERENCE
N/A
N/A
N/ASTEEL DECK (DIRECTION)
RAMP DOWN
RAMP UP
CONCRETE SYMBOLS:
DESCRIPTION DETAIL REFERENCESYMBOL
N/ARAMP (DIRECTION)RAMP UP
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/1 6"
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/3 2"
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
G ra p h ic S ca le
/2
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD
STAMP
CONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
E
D
C
B
A
F
Office of Construction and Facilities Management
B
IM
V
IS
N
K er rv ill e
R en vt . B as em en t M ec h
B ld g
/S
_1
3.
_B ld g
B as em en t R en o_ C
.r vt
/1
8/
:2 6:
P
M
GENERAL NOTES
DKS JMB
CONSTRUCTION DOCUMENTS 671A4-22-106BUILDING 11 BASEMENT
RENOVATION
VAMC KERRVILLE, TX
11/22/2022
11-S001
FULLY
SPRINKLERED15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com
DESIGN CRITERIA
1. STRUCTURE HAS BEEN DESIGNED TO COMPLY WITH:
IBC 2018
ASCE 7-16
ACI 318-14
AISC 360-16
2. RISK CATEGORY II
3. LIVE LOADS:
TYPICAL FLOOR 40 PSF (REDUCIBLE)
CORRIDORS, STAIRS & PUBLIC AREAS 100 PSF (UNREDUCIBLE)
4. SEISMIC AND WIND LATERAL SYSTEMS ARE NOT AFFECTED BY THIS PROJECT.
GENERAL
1. DURING THE CONSTRUCTION PERIOD, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
THE SAFETY OF PERSONNEL AND PROPERTY ON AND AROUND THE JOBSITE. THE
CONTRACTOR SHALL PROVIDE ADEQUATE SHORING, BRACING, GUYS, ETC. IN
ACCORDANCE WITH ALL NATIONAL, STATE, AND LOCAL SAFETY ORDINANCES.
2. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION
OF ALL DRAWINGS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO THE START OF
CONSTRUCTION SO A CLARIFICATION CAN BE ISSUED. ANY WORK PERFORMED IN
CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE
CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE AND AT NO EXPENSE TO THE
OWNER OR ARCHITECT.
3. ALL DIMENSIONS AND SITE CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AT THE
JOBSITE PRIOR TO CONSTRUCTION, START OF SHOP DRAWINGS, START OF
CONSTRUCTION, AND/OR FABRICATION OF MATERIALS. IF DISCREPANCIES ARE
ENCOUNTERED, OR CONDITIONS DEVELOP THAT ARE NOT COVERED BY THE CONTRACT
DOCUMENTS, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION.
4. CONTRACTOR SHALL PROVIDE AND BE RESPONSIBLE FOR THE PROTECTION AND REPAIR
OF ADJACENT EXISTING SURFACES AND AREAS WHICH MAY BE DAMAGED AS A RESULT OF
NEW WORK.
5. STRUCTURAL DRAWINGS INCLUDE DESIGN REQUIREMENTS AND DIMENSIONS FOR
STRUCTURAL INTEGRITY BUT DO NOT SHOW ALL DETAIL DIMENSIONS TO FIT INTRICATE
ARCHITECTURAL AND MECHANICAL DETAILS. CONTRACTOR SHALL SO CONSTRUCT THE
WORK SO IT WILL CONFORM TO THE CLEARANCES REQUIRED BY ARCHITECTURAL,
MECHANICAL AND ELECTRICAL DESIGN.
6. ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE
CONSTRUCTION STANDARDS. IF CLARIFICATION IS REQUIRED, THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
7. DO NOT SCALE DRAWINGS. PRINTED DIMENSIONS HAVE PRECEDENCE OVER SCALED
DRAWINGS AND LARGE-SCALE OVER SMALL-SCALE DRAWINGS. CONTRACTOR TO
DETERMINE FINAL DIMENSION WITH ARCHITECT.
8. TYPICAL DETAILS SHALL APPLY TO SITUATIONS OCCURRING ON THE PROJECT THAT ARE
THE SAME OR SIMILAR TO THOSE SPECIFICALLY REFERENCED. WHERE NO DETAILS ARE
GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
9. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT
INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL
MEASURES NECESSARY TO PROTECT THE STRUCTURE AND SAFETY OF WORKMEN
DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO,
BRACING AND SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC.
OBSERVATION VISITS TO THE SITE BY THE ARCHITECT OR STRUCTURAL ENGINEER SHALL
NOT INCLUDE INSPECTION OR APPROVAL OF THE ABOVE ITEMS AND DO NOT IN ANY WAY
RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES FOR THE ABOVE.
10. SEE ARCHITECTURAL, ELECTRICAL AND MECHANICAL DRAWINGS FOR DETAILS,
CONDITIONS, PITS, TRENCHES, PADS, DEPRESSIONS, ROOF/FLOOR OPENINGS, SLEEVES,
ITEMS TO BE EMBEDDED OR ATTACHED TO STRUCTURAL ELEMENTS, ETC., NOT SHOWN
ON THE STRUCTURAL DRAWINGS.
11. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR MECHANICAL, ELECTRICAL AND
PLUMBING WITH APPROPRIATE TRADE CONTRACTORS. OPENING SIZES AND LOCATIONS
SHOWN FOR DUCTS, PIPE, INSERTS AND OTHER PENETRATIONS WHEN SHOWN ARE FOR
GENERAL INFORMATION ONLY AND SHALL BE VERIFIED PRIOR TO FORMING.
SUBMITTALS
1. SUBMITTALS ARE:
a. CONCRETE MIX DESIGNS
b. MATERIAL PRODUCT DATA…