Attachment 3_Drawings Supplemental Set.pdf

PDF 6 MB Posted

Attached to
LOLO NATIONAL FOREST - Building 24 Basement Remodel
Solicitation number
1240LU26Q0111
Issued by

About this file

These are architectural and engineering construction documents for a building remodel at 26 Fort Missoula Road, Missoula, Montana (Building 24, Basement). The project involves remodeling existing office space for updated office needs and is classified as a Type IIIB, non-sprinklered construction project under Group B (Business) occupancy per the 2021 International Building Code.

The project complies with Montana's adopted building codes including the 2021 IBC, IMC, IFGC, and IECC (Climate Zone 6), along with the 2020 NEC and 2012 IFC. The design encompasses a three-story building (one below grade) with a total actual floor area of 28,240 SF across basement and levels 1-2, which is below the allowable 66,500 SF for the occupancy classification. Key architectural specifications include egress requirements with maximum travel distances of 200 feet for Business occupancy and 75 feet for common path of egress travel, corridor fire resistance ratings of 1-hour for occupancy loads exceeding 30, and interior finish classifications ranging from Class A for exit stairways to Class C for rooms. The documents detail wall construction types (nonrated, 1-hour, and 2-hour fire-rated), flooring specifications (carpet tile, luxury vinyl tile), wall finishes (paint colors P1-P3, fiberglass reinforced panels), and baseboards. Plumbing demolition and installation plans show fixture removals, sanitary/storm drain connections, and coordination requirements. Construction documents reference special inspections for steel, concrete, masonry, wood, and seismic resistance per IBC Sections 1704-1705. The architectural team is Mosaic Architecture Planning Design, with mechanical/plumbing engineer Jason D. Beaudette (PE No. 11138). Documents are dated July 14, 2026 (100% Construction Documents phase).

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

DN

NONRATED WALL: WITH NO OPENING PROTECTION REQUIRED AT DOORS,

WINDOWS, DUCTS, PENETRATIONS, AND JOINTS UON. SEE WALL TYPES.

EXIT SIGN W/ INTEGRATED DIRECTIONAL ARROW WHERE OCCURS AT ALL

EXITS, EVERY 100' IN CORRIDORS, AND IN SPACES WHERE 2 MEANS OF

EGRESS ARE REQUIRED PER S §1006. SEE ELECTRICAL DRAWINGS. (W/

POCHE IN QUADRANT INDICATING "EXIT" TEXT SIDE OF SIGN.) SIGNS

SHOWN IN CORRIDORS ARE CEILING HUNG. SIGNS SHOWN ON WALL ARE

WALL HUNG.

1-HOUR FIRE WALL, FIRE BARRIER, FIRE PARTITION, OR SMOKE BARRIER

WALL: OR COMBINATION OF (WHERE OCCURS) CONFORMING TO THE MOST

STRINGENT REQUIREMENTS OF EACH. SEE CODE ANALYSIS PLANS FOR

SPECIFIC NAMES OF IBC WALL DESIGNATIONS. ALL WITH FIRE-RESISTIVE

OPENING PROTECTION AT DOORS, WINDOWS, DUCTS (WITH EXCEPTIONS),

PENETRATIONS, AND PROTECTION AT JOINTS. SEE WALL TYPES, DOOR AND

WINDOW SCHEDULES, MECHANICAL DRAWINGS, PENETRATION DETAILS, AND

JOINT DETAILS WHERE APPLICABLE.

2-HOUR FIRE WALL OR FIRE BARRIER: OR COMBINATION OF (WHERE

OCCURS) CONFORMING TO THE MOST STRINGENT REQUIREMENTS OF EACH.

SEE CODE ANALYSIS PLANS FOR SPECIFIC NAMES OF IBC WALL

DESIGNATIONS. ALL WITH FIRE-RESISTIVE OPENING PROTECTION AT

DOORS, WINDOWS, DUCTS (WITH EXCEPTIONS), PENETRATIONS, AND

PROTECTION AT JOINTS. SEE WALL TYPES, DOOR AND WINDOW

SCHEDULES, MECHANICAL DRAWINGS, PENETRATION DETAILS, AND JOINT

DETAILS WHERE APPLICABLE.

PORTABLE CLASS ABC FIRE EXTINGUISHER IN ADA-COMPLIANT SEMI-

RECESSED CABINET

FE

Wmin MINIMUM EGRESS WIDTH (INCHES) BASED ON ACCUMULATIVE NUMBER OF

OCCUPANTS SERVED AT INDICATED EGRESS COMPONENT, PER SECTION

1005.3: .3 INCHES/OCC FOR STAIRWAYS(NONSPRINKLERED BUILDINGS); .2

INCHES/OCC FOR OTHER EGRESS COMPONENTS (NONSPRINKLERED BLDGS).

MOER:2 MEANS OF EGRESS REQUIRED (QUANTITY). ONLY DESIGNATED WHERE

(2) MEANS OF EGRESS ARE REQUIRED, PER §1006.2.1.

IU INCIDENTAL USE W/ REQUIRED SEPARATION PER TABLE 509.1. SHALL NOT

OCCUPY >10% OF FLOOR AREA OF STORY IN WHICH LOCATED, AND IS

CALCULATED AS PART OF OCCUPANCY IN WHICH IT IS LOCATED.

ACCESSORY OCCUPANCY AREA: W/ NO SEPARATION REQUIRED AND

CALCULATED AS PART OF MAIN OCCUPANCY IF TOTAL ACCESSORY

OCCUPANCIES WITHIN A STORY OCCUPY LESS THAN 10% OF AREA OF THAT

STORY, PER SECTION 508.2.3.

CODE PLAN LEGEND

OCCUPANCY GROUP B AREA

EXIT ACCESS TRAVEL DISTANCE (E.A.T.D.) - MAXIMUM 200' FOR 'B'

OCCUPANCY W/OUT SPRINKLER SYSTEM, PER TABLE 1017.2. MAXIMUM

DISTANCE FOR EACH STORY SHOWN.

COMMON PATH OF EGRESS TRAVEL (C.P.E.T.) - MAXIMUM 75' FOR 'B'

OCCUPANCY W/OUT SPRINKLER SYSTEM, OCC LOAD >30, PER TABLE 1006.2.1.

ROOM AREA

OCCUPANT

LOAD

MAX. FLOOR

AREA PER

OCCUPANT

FROM TABLE

1004.5

SF

ROOM NAME

OCCUPANT LOADS FOR FUNCTIONS DESIGNATED NET

FLOOR AREA IN TABLE 1004.5 ARE IDENTIFIED FOR

ACTUAL OCCUPIED AREAS.

OCCUPANT LOADS FOR FUNCTIONS DESIGNATED GROSS

FLOOR AREA ARE IDENTIFIED FOR ENTIRE AREA OF THE

FUNCTION W/ DEDUCTIONS ONLY FOR AREA OF

EXTERIOR WALLS, VENT SHAFTS AND INTERIOR COURTS.

AO

OCCUPANCY GROUP B WITH ACCESSORY SMALL ASSEMBLY SPACE WITH

OCCUPANT LOAD <50 OR AREA <750 SF, CLASSIFIED AS PART OF GROUP B

OCCUPANCY PER 303.1.2

REQUIRED EXIT AND EXIT EGRESS DIRECTION WITH ACCUMULATIVE

NUMBER OF OCCUPANTS SERVED. (DESIGNATED WHERE (2) MEANS OF

EGRESS ARE REQUIRED PER TABLE §1006.2.1)

THIS PROJECT SHALL COMPLY WITH THE LATEST EDITION OF CODES ADOPTED BY THE STATE

OF MONTANA:

2021 International Building Code (IBC) 2021 International Mechanical Code (IMC) 2021 International Fuel Gas Code (IFGC) 2021 Uniform Plumbing Code (IAMPO) 2020 National Electrical Code (NEC) 2012 International Fire Code (IFC) 2021 International Energy Conservation Code (IECC)

APPLICABLE BUILDING CODES

N

IECC COMPLIANCE FOR COMMERCIAL PROJECTS

CLIMATE ZONE: 6

INSULATION REQUIREMENTS - IECC 2021 TABLE C402.1.3/C402.4 AND MT AMENDMENTS

ROOFS R-30 CONTINUOUS ABOVE DECK, R-49 AT ATTICS

METAL FRAMED WALLS, ABOVE GRADE R-13 CAVITY + R-12.5 CONTINUOUS

WOOD FRAMED WALLS, ABOVE GRADE R-13 CAVITY + R-7.5 CONTINUOUS OR R-20 + R-3.8 CONTINUOUS

MASS WALLS, ABOVE GRADE: R-15.2 CONTINUOUS

BELOW GRADE WALLS: R-15 CONTINUOUS

FLOORS - JOIST/FRAMING: R-38 (R-38 FOR STEEL FLOOR JOISTS)

UN-HEATED SLAB: R-20 VERTICAL FOR 48" BELOW (FULL HEIGHT OF THICKENED SLAB EDGE)

HEATED SLAB: R-15 FOR 36" BELOW + R-5 FULL SLAB

OPAQUE SWINGING DOORS: U-0.37

SKYLIGHT U-FACTOR: 0.50, MAXIMUM

FIXED FENESTRATION U-FACTOR: 0.34, MAXIMUM

OPERABLE FENESTRATION U FACTOR 0.42 MAXIMUM

ENTRANCE DOOR: 0.63, MAXIMUM

SHGC 0.41 WITH ADJUSTMENT FOR PROJECTION FACTOR >.2

INSULATION TO BE PROVIDED - REQUIREMENTS IN OTHER AREAS OF DRAWINGS OR SPECIFICATIONS TAKE

PRECEDENCE OVER THE FOLLOWING REQUIREMENTS:

ROOFS R-30 BLOWN-IN ATTIC INSULATION

WOOD FRAMED WALLS: R-21 CAVITY + R3.8 CONTINUOUS

UNHEATED SLAB: R-10 VERTICAL FOR 24" BELOW (FULL HEIGHT OF THICKENED SLAB EDGE)

OPAQUE SWINGING DOORS: U-0.37

ROLL UP OR SLIDING DOORS R-4.75

FENESTRATION U-FACTOR (FIXED): 0.34 MAXIMUM

FENESTRATION U-FACTOR (OPERABLE): 0.42, MAXIMUM

ENTRANCE DOOR: 0.63, MAXIMUM

SHGC 0.40 WITH PROJECTION FACTOR <.2

OCCUPANCY GROUPS:

(CHAPTER 3)

• B - BUSINESS

• ACCESSORY OCCUPANCIES PER SEC. 508.2 WHERE OCCUR.

• INCIDENTAL USES PER TABLE 509 WHERE OCCUR.

NONSEPARATED OCCUPANCIES:

(SEC. 508.3.2)

CONSTRUCTION TYPE:

(TABLE 601)

TYPE IIIB, NON-SPRINKLERED

ALLOWABLE FLOOR AREA (At):

(TABLE 506.2)

B: 19,000 SF

ALLOWABLE FLOOR AREA:

SINGLE OCCUPANCY

MULTISTORY BLDG: (Aa)

(SEC. 506.2.1)

S-1:

ALLOWABLE NO. OF STORIES / HEIGHT:

(TABLE 504.4/504.3)

B: 3 STORIES / 55 FT

OCCUPANT LOAD BY FLOOR: AFFECTED AREA: 2 occu ACCESSORY AREA: 0 occu

SEE CODE ANALYSIS PLANS THIS SHEET.

SUMMARY CODE REVIEW

PROJECT DESCRIPTION: REMODEL EXSISTING OFFICE SPACE FOR UPDATED OFFICE NEEDS

ACTUAL NO. OF STORIES / HEIGHT: 3 STORY (1 BELOW GRADE) / 43 FT; OK

OCCUPANT LOADS FOR EGRESS DESIGN:

(SEC. 1004 + TABLE 1004.5)

ASSEMBLY - UNCONCENTRATED 15 NET

BUSINESS: 150 GROSS

STORAGE/MECHANICAL EQUIPMENT 300 GROSS

LOCKER ROOM 50 GROSS

SEE CODE ANALYSIS PLAN. OCCUPANT LOADS BASED ON MAX. FLOOR

AREA IN SQ FT PER OCCUPANT FROM TABLE 1004.5:

EGRESS WIDTH PER OCCUPANT SERVED:

(SEC. 1005.3)

STAIRWAYS:

OTHER EGRESS

COMPONENTS:

0.3 INCHES / OCCUPANT (NONSPRINKLERED)

0.2 INCHES / OCCUPANT (NONSPRINKLERED)

INTERIOR FINISH REQUIREMENTS:

(TABLE 803.13)

INTERIOR EXIT STAIRWAYS, EXIT RAMPS & EXIT PASSAGEWAYS: CLASS A.

CORRIDORS & ENCLOSURE FOR EXIT ACCESS STAIRWAYS & EXIT ACCESS RAMPS: CLASS B.

ROOMS AND ENCLOSED SPACES: CLASS C

THIS MIXED OCCUPANCY BUILDING INCORPORATES NONSEPARATED

OCCUPANCIES. NO OCCUPANCY SEPARATIONS ARE PROVIDED, AND

THE ALLOWABLE AREA AND HEIGHT OF THE BUILDING IS BASED ON

THE REQUIREMENTS OF THE MOST RESTRICTIVE OCCUPANCY.

Aa = [At + (NS x If)] x Sa Aa = 19,000 + [19,000 x .75] x 2 Aa = 66,500 SF

ACTUAL FLOOR AREA: BASEMENT: 14,240 SF (NEED NOT INCLUDE, SPRINKLED)

1-2 LEVELS: 28,240 SF

28,240 SF < 66,500 ALLOWABLE; OK

EXSTING:

44" AT STAIRWAYS (36" WHERE OCC LOAD < 50) [IBC §1011.2];

32" CLEAR AT DOORS [§1010.1.1],

44" AT CORRIDORS, AISLES & EXIT PASSAGEWAYS (36" for occupant load

<50) [§ 1020.2; 1018.3, 1018.5; 1024.2 RESPECTIVELY], PROVIDED.

EGRESS WIDTH MINIMUMS BY

COMPONENT (USE WHERE EXCEED

MINIMUMS BY OCCUPANT LOAD):

CORRIDOR FIRE RESISTANCE RATING:

(TABLE 1020.2)

B OCCUPANCY, OCC LOAD <30:

B OCCUPANCY, OCC LOAD >30:

NOT REQUIRED (NONSPRINKLERED)

1-HOUR (NONSPRINKLERED)

OPENING PROTECTIVES:

(TABLE 716.1(2))

20 MINUTE

D-20

DH-OH-20

45 MINUTE

OH-45 OR W-60

1-HR FIRE PARTITIONS (CORRIDOR WALLS):

FIRE DOOR RATING:

DOOR VISION PANEL GLAZING MARKING:

SIDELIGHT/TRANSOM ASSEMBLY MARKING:

FIRE WINDOW ASSEMBLY RATING:

WINDOW ASSEMBLY MARKING:

(TABLE 716.1(3))

FRONTAGE INCREASE (If):

(TABLE 506.3.3)

>30' OPEN SPACE FOR 100% OF BLDG PERIMETER:

If = .75

TOTAL FLOOR AREA: 95 occu

REQUIRED SPECIAL INSPECTIONS:

IN ADDITION TO REGULAR INSPECTIONS, THE FOLLOWING ITEMS WILL ALSO REQUIRE SPECIAL INSPECTIONS AND TESTING IN ACCORDANCE WITH SECTIONS 1704 AND 1705 OF THE 2018 INTERNATIONAL BUILDING CODE.

SEE STRUCTURAL FOR SPECIFIC REQUIREMENTS. COPIES OF 3RD PARTY REPORTS TO BE SENT TO

BUILDING DEPARTMENT & COPIES KEPT ON-SITE FOR INSPECTOR REVIEW.

a) SPECIAL INSPECTIONS:

- INSPECTION OF FABRICATORS (1704.2.5)

- STEEL CONSTRUCTION (1705.2)

- CONCRETE CONSTRUCTION (1705.3)

- MASONRY CONSTRUCTION (1705.4)

- WOOD CONSTRUCTION (1705.5)

- SOILS (1705.6)

- SPECIAL CASES (1705.1.1)

EPOXY SET ANCHORS

POWDER-ACTUATED FASTENERS

CONCRETE EXPANSION ANCHORS

b) SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE (1705.12):

- STRUCTURAL STEEL (1705.12.1)

- STRUCTURAL WOOD (1705.12.2)

- COLD-FORMED STEEL LIGHT-FRAME CONSTRUCTION (1705.12.3)

1/16" = 1'-0"

LEVEL 2 FLOOR PLAN AO - EXISTING

TannerGrimstad PolyLine

TannerGrimstad Callout

REQUIREMENTS FOR OFFICE 201 TO BE APPLIED TO ALL AREAS OUTLINED BELOW

TannerGrimstad Callout

CPT 1

TannerGrimstad Callout

EXISTING WINDOW SHADES TO BE REMOVED, TYP. 7 LOCATIONS

NOTE: SUPPLY NEW WINDOW SHADE - VERIFY SIZE IN FIELD

TannerGrimstad Callout

FLOORING IN OFFICE SPACE TO BE REMOVED, PREP FOR INSTALL OF NEW

TannerGrimstad Callout

FLOORING IN OFFICE SPACE TO BE REMOVED, PREP FOR INSTALL OF NEW

TannerGrimstad Callout

PROTECT EXISTING WALLBASE & PICTURE RAIL THROUGHOUT SPACE

TannerGrimstad Callout

ALL WALLS TO BE PAINTED P1

TannerGrimstad Text Box

SUPPLEMENTAL DRAWINGS PAGE 1 OF 4

A

A

WALLS TO ALIGN

PROTECT EXISTING

WALLBASE & PICTURE

RAIL THROUGHOUT SPACE

(N) WALLBASE TO

MATCH EXISTING

ALL WALLS TO BE PAINTED P1

NEW WALL PAINTED P1

2' - 0"

SUPPLY NEW WINDOW SHADE -

VERIFY SIZE IN FIELD

136 SF

OFFICE

(N) PICTURE RAIL TO

MATCH EXISTING

(N) WALLBASE TO

MATCH EXISTING

NEW WALL PAINTED P1

(N) PICTURE RAIL TO

MATCH EXISTING

2X4 FRAMED WALL WITH

GYP. BD BOTH SIDES

PROTECT ALL

EXISTING STORAGE

CPT 1

FLOORING IN OFFICE SPACE

TO BE REMOVED, PREP FOR

INSTALL OF NEW

EXISTING WINDOW SHADES

TO BE REMOVED

e2s

WALL TYPE

WALL HEIGHT

WALL STUD & FINISH HEIGHT

a GWB TO 6" ABOVE CEILING; FRAME OR BRACE TO STRUCTURE b TO STRUCTURE

WALL TYPE TAG

1. DIMENSIONS ARE TO FACE OF STUD, EXISTING WALL FINISH,

MASONRY, OR DOOR/WINDOW OPENINGS. DIMENSIONS OF EXISTING

CONSTRUCTION ARE NOT SHOWN ON DRAWINGS - VERIFY

DIMENSIONS OF ALL EXISTING CONSTRUCTION IN THE FIELD.

DIMENSIONS TO OPENINGS ARE NOMINAL. VERIFY ALL OPENINGS

WITH ROUGH OPENING REQUIREMENTS.

2. ALL DOOR OPENINGS PERPENDICULAR TO A WALL ARE 4" TO THE

WALL FRAMING UNO.

3. EXISTING CONSTRUCTION TO REMAIN SHOWN SHADED, NEW

CONSTRUCTION SHOWN SOLID.

4. SEE SHEET A-002 FOR WALL TYPES. IN AREAS WITH SUSPENDED

ACOUSTICAL TILE CEILINGS, GYPSUM WALL BOARD MAY BE

TERMINATED 6" ABOVE THE CEILING.

5. VERIFY EXISTING WALL CONSTRUCTION.

GENERAL FLOOR PLAN NOTES

NEW CONSTRUCTION

EXISTING ELEMENTS TO REMAIN

LINEWORK LEGEND

NEW WALL TO ALIGN WITH EXISTING WALL

WALL NOT TO INTERFERE WITH OPENING OF CASEWORK

PROTECT ALL BUILT IN

CASEWORK DURING

CONSTRUCTION- PAINT WALLS

AROUND CASEWORK.

WALLBASE TO BE PROTECTED

PICTURE RAIL TO BE

DUPLICATED

N

WALLBASE TO BE DUPLICATED

@ NEW WALL - VERIFY

DIMENSIONS IN FIELD

PORTION OF CEILING GRID TO BE

DEMOLISHED/ALTERED FOR NEW

WALL CONSTRUCTION

SUSPENDED CEILING

ACOUSTIC INSULATION

WHERE OCCURS - SEE WALL

TYPE

PROVIDE SEALANT @ BASE OF

ALL WALLS W/ ACOUSTIC

INSUL.

WALL TYPE PER PLANS

2" X 2" X 1/8" ANGLE BRACING

(SHOWN) OR 3 1/2" 25 GA MTL STUD

BRACING TO STRUCTURE @ MAX

8'-0" OC, ALTERNATING SIDES.

STRUCTURE

45° MAX

6"

ATTACH TO STRUCTURE W/

3/8"Ø EXPANSION ANCHORS

@ CONCRETE OR 3/8"Ø X 3"

LAG BOLTS @ WOOD

2 NO. 12 SCREWS

NEW PARTITION WALL BRACING

ROOM FINISH LEGEND

CPT1: CARPET TILE - INTERFACE, STYLE 'STEP IT UP', COLOR - ALBA

CPT2: CARPET TILE - INTERFACE, STYLE 'STEP IT UP', COLOR - ASH

LVT1: LUXURY VINYL TILE - INTERFACE, 22 MIL, STYLE: 'RIDGE', COLOR: AGATE

(E): EXISTING FINISH - NO WORK

FLOOR FINISHES

FLOOR AND BASE FINISH NOTES:

1. SEE SPECIFICATIONS FOR FINISH MANUFACTURER.

2. ALL FLOORING TO BE INSTALLED ON MANUFACTURERED APPROVED SUB FLOOR.

3. INSTALL FACTORY-PROVIDED TRANSITION STRIP OR AS DETAILED AT ALL FLOORING CHANGES.

4. CHANGE FLOORING WHERE INDICATED ON PLANS, CHANGE FLOOR CENTERED UNDER DOOR AT

ROOM TO ROOM CHANGES, U.N.O

5. AT CASEWORK, CONTINUE BASE AROUND ENDPANELS AND TOE-KICKS, U.N.O.

PAINT NOTE: MANUF. SHOWN ARE BASIS OF DESIGN ONLY. SUBSTITUTIONS ALLOWED WITH APPROVAL; SEE SPEC SECTION ON SUBSTITUTIONS. VERIFY FINAL PAINT COLORS AND LOCATIONS W/ CO PRIOR TO

INSTALLATION.

FRP1: FIBERGLASS REINFORCED PANEL- MANF: MARLITE COLOR: BISCUIT

FRP2: INDURO FRP - MANF: MARLITE - COLOR : FASHION GREY

P1: PAINT - COLOR: WHITE - MAIN WALLS

P2: PAINT - COLOR: BEIGE ACCENT/TRIM COLOR

P3: PAINT - COLOR:

WOOD FRAMES

P2: PAINT - BEIGE/ACCENT

WALL FINISHES

RB1: 6" RUBBER BASE - JOHNSONITE MILLWORK COLLECTION 'MANDALAY' - COLOR: BY CO

WB: MATCH EXISTING - 6" BASE TRIM WITH QUARTER ROUND- PAINT TO MATCH EXISTING

BASE FINISHES

CPT1

PL1: PLASTIC LAMINATE 1 - WILSONART PREMIUM LAMINATE - COLOR: HARVEST MAPLE

PL2: PLASTIC LAMINATE 2 - WILSONART PREMIUM LAMINATE - COLOR: CANYON ZEPHYR

SS1: SOLID SURFACE COUNTERTOP - CORIAN - COLOR: PEPPERED TERRAZZO

COUNTERTOP AND CASEWORK FINISHES NOTES:

1. SEE SPECIFICATION FOR MANUFACTURER.

2. PLASTIC LAMINATE COUNTERTOPS TO HAVE LAMINATE EDGES, U.N.O. NOTED IN DETAILS.

3. PROVIDE FINISHED END PANELS WHERE EXPOSED TO VIEW, PROVIDE SCRIBE STRIP AT ALL WALL ABUTMENTS.

4. WHERE NOTED ON ELEVATIONS, PROVIDE 4" BACKSPLASH W/ SQUARE EDGES, MATCH ADJ. COUNTERTOP

MATERIAL.

5. FOR BIDDING PURPOSES ASSUME EACH DRAWER AND/OR DOOR HAS A PULL, EVEN IF NOT SHOWN IN

ELEVATIONS

COUNTERTOPS, CASEWORK SURFACES, TRIM

WALL FINISHES NOTES:

1. SEE INTERIOR ELEVATIONS AND/OR DETAILS FOR INTERIOR WINDOWS, SPECIAL WALL

FINISHES, TRIM, ETC.

2. FINISH SCHEDULE APPLIES TO GENERAL AREA: THERE MAYBE SPECIFIC FINISH

REQUIREMENTS SHOWN ON DETAILS, DRAWINGS OR SPECIFICATIONS.

3. SEE SPECIFICATIONS FOR LEVEL(S) OF FINISH AT GWB SURFACES.

4. ALL WALLS/CEILINGS P1 UNLESS OTHERWISE NOTED ON PLANS &/OR ELEVATIONS.

LVT1

CEILING FINISHES

(E)CPT2

SEE RCP

D A

T E

S T

A M

P

/2

/2

:5 :1

P

M

1/4" = 1'-0"

AO- OFFICE FLOOR & FINISH PLAN

1/4" = 1'-0"

LEVEL 2 FLOOR PLAN AO - DEMOLITION

NTS

NEW WALL LOCATION

1" = 40'-0"

LOCATION FOR AREA OF WORK - LEVEL 2

1/4" = 1'-0"

WALL BASE DETAIL

1/4" = 1'-0"

2ND FLOOR RCP AO - DEMOLITION

TannerGrimstad PolyLine

TannerGrimstad Line

TannerGrimstad Line

TannerGrimstad Line

TannerGrimstad Line

TannerGrimstad Line

TannerGrimstad Line

TannerGrimstad Line

TannerGrimstad Line

TannerGrimstad Line

TannerGrimstad Line

TannerGrimstad Line

TannerGrimstad

SUPPLEMENTAL DRAWINGS PAGE 2 OF 4

2 2

KG

JIH

OFFICE

HERITAGE

STORAGE

IT

TRAINING

OFFICE

OFFICE

(E)AC-1 34

D ECBA

KITCHEN

16(D) S

(D) S

PLUMBING DEMO NOTES

A. LOCATIONS AND DIMENSIONS OF EXISTING FACILITIES IDENTIFIED ON THIS

DRAWING ARE APPROXIMATE AND REPRESENT THE BEST AVAILABLE

INFORMATION BASED ON A COMBINATION OF FIELD INVESTIGATIONS AND

VARIOUS DESIGN AND RECORD DRAWINGS AVAILABLE AT THE TIME OF

DESIGN. FIELD VERIFY LOCATIONS AND DIMENSIONS PRIOR TO ORDERING

EQUIPMENT AND DURING PERFORMANCE OF THE WORK. PROVIDE

DEMOLITION WORK, NECESSARY FITTINGS, TRANSITIONS, AND OTHER

COMPONENTS AS REQUIRED FOR A COMPLETE AND FUNCTIONAL

INSTALLATION OF NEW SYSTEMS AT NO ADDITIONAL COST TO THE OWNER.

B. EXISTING PLUMBING EQUIPMENT, FIXTURES, AND PIPING SHOWN AS DARK

AND DASHED SHALL BE DEMOLISHED. EXISTING PLUMBING EQUIPMENT,

FIXTURES, AND PIPING SHOWN LIGHT SHALL REMAIN UNCHANGED.

C. THE PLUMBING CONTRACTOR SHALL COORDINATE SALVAGE OF REMOVED

EQUIPMENT IN GOOD CONDITION WITH THE OWNER. THE PLUMBING

CONTRACTOR SHALL DISPOSE OF UNWANTED EQUIPMENT.

D. COORDINATE WITH GENERAL CONTRACTOR TO PATCH AND REPAIR ROOF

AND WALL ASSEMBLIES ASSOCIATED WITH PLUMBING DEMOLITION.

E. CONCRETE SLAB CUTTING REGIONS SHOWN ON DRAWINGS ARE

APPROXIMATE AND MUST BE FIELD COORDINATED PRIOR TO THE CUTTING

OF THE SLAB.

F. PROTECT EXISTING BUILDING ELEMENTS DURING DEMOLITION WORK.

COORDINATE WITH OTHER TRADES TO ENSURE NO EXISTING

EQUIPMENT/PIPING TO REMAIN IS DAMAGED DURING THE DEMOLITION

WORK.

KEY NOTES:#

1. COMPLETELY DEMOLISH THE EXISTING SINK, INCLUDING ALL TRIM TO THE

WALL. FURNISH AND INSTALL A PERMANENT CAP ON DCW, DHW, AND SAN.

2. COMPLETELY DEMOLISH THE EXISTING SINK, INCLUDING ALL TRIM TO THE

WALL INCLUDING ANGLE VALVES. PREPARE THE EXISTING DCW, DHW, AND

SAN ROUGH-IN SERVICES FOR NEW CONNECTION.

3. EXISTING 4" PVC RADON PIPE RISES FROM BELOW THE BASEMENT FLOOR

SLAB-ON-GRADE, AND TERMINATES THROUGH THE WALL AT

APPROXIMATELY 4'-6" AFF. NO WORK.

4. EXISTING AC-1 PUMPED CONDENSATE LINE TO REMAIN, NO WORK.

EXISTING 3/8" POLY LINE IS ROUTED ABOVE THE LAY-IN CEILING.

5. EXISTING WALL CLEAN OUT TO REMAIN. SEE CONSTRUCTION DRAWINGS

FOR NEW WORK.

6. PLUMBING CONTRACTOR SHALL COORDINATE WITH THE SITE CIVIL

CONTRACTOR TO RESTORE EXTERIOR SANITARY SEWER SERVICE TO THE

EXTERIOR SEWER MANHOLE. NO WORK IS ANTICIPATED FROM THE

FIXTURE UP TO AND INCLUDING TO THE BUILDING FOUNDATION WALL.

DATE:

SHEET:

317 N. Cruse Ave. STE. 201

Helena, Montana

59601

406.449.2013 www.mosaicarch.com

D A

T E

S T

A M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

/1

/2

:2 :2

A

M

07.14.2026

P101

PLUMBING DEMO PLAN -

BASEMENT

26 FORT MISSOULA RD, MISSOULA, MT

BUILDING 24

BASEMENT

REMODEL

C O

N S

T R

U C

T I O

N D

O C

U M

E N

T S

N.T.S.2

PLUMBING DEMO PLAN EAST

N.T.S.1

PLUMBING DEMO PLAN WEST

N

KEY PLAN

I S S

E F

O R

P

LAN

O EN

G

IN

E E R

ON

T

M

AN

A

LICENSE

D

JASON D.

BEAUDETTE

No. 11138 PE

# DATE REVISION

TannerGrimstad PolyLine

TannerGrimstad PolyLine

TannerGrimstad Text Box

CONTRACTOR RESPONSIBILITY AS FOLLOWS:

1. VERIFY EXISTING PLUMBING LINE SIZE, LENGTH, AND ATTACHMENT LOCATION TO SITE MANHOLE. ALL INFORMATION IS TO BE INCLUDED IN BID.

2. UNCLOG OR REPLACE EXISTING PLUMBING LINE AS REQUIRED TO ENSURE ADEQUATE PERFORMANCE OF SINK IN BREAK ROOM.

3. ALL SITE WORK TRENCHNING/EXCAVATION TO BE COMPLETED BY THE CONTRACTOR AND INCLUDED IN THEIR BID.

4. ALL EXTERIOR PENETRATION, PIPE SEALING, AND ATTACHMENTS REQUIREMENTS TO BE COMPLETED BY THE CONTRACTOR AND INCLUDED IN THEIR BID.

TannerGrimstad Dimension

VERIFY

TannerGrimstad

SUPPLEMENTAL DRAWINGS PAGE 3 OF 4

2 2

KG

JIH

(E)AC-1 34

D ECBA

KITCHEN

S-1

A. PROVIDE ACCESS DOORS TO ALLOW SERVICE AND INSPECTION OF

EQUIPMENT, VALVES, AND OTHER DEVICES INSTALLED IN INACCESSIBLE

LOCATIONS. COORDINATE SUCH INSTALLATIONS WITH THE ARCHITECT AND

ENGINEER.

B. PROVIDE TRAP SEALS AND TRAP PRIMERS FOR FLOOR DRAINS, FLOOR

SINKS, AND OTHER FLOOR RECEPTORS.

C. INSTALL ACCESSIBLE PLUMBING FIXTURES IN COMPLIANCE WITH ADA

REQUIREMENTS. INSULATE EXPOSED PIPING BELOW ADA ACCESSIBLE

FIXTURES.

D. INSTALL FLOOR DRAIN STRAINERS AND CLEANOUT COVERS FLUSH AND

LEVEL WITH FINISHED FLOOR.

E. PIPING SHALL BE IDENTIFIED WITH PIPE LABELS MARKED AT A MAXIMUM OF

EVERY 25 FT. VALVES SHALL BE IDENTIFIED WITH BRASS OR ALUMINUM

VALVE TAGS.

F. PROVIDE AND INSTALL PIPE GUIDES, EXPANSION JOINTS, AND HANGERS PER

MANUFACTURER'S RECOMMENDATIONS.

G. PIPING WALL PENETRATIONS SHALL BE FINISHED WITH A CHROME

ESCUTCHEON PLATE.

H. MAINTAIN THE INTEGRITY OF DRAFTSTOPPING WHERE PIPES PENETRATE

DRAFTSTOPPING MATERIALS.

I. NO FITTINGS OR PIPING CONNECTIONS SHALL BE INSTALLED UNDERSLAB.

J. REFER TO THE PLUMBING FIXTURE SCHEDULE FOR PIPE SIZES TO

INDIVIDUAL FIXTURES.

K. COORDINATE CONCRETE PENETRATIONS WITH STRUCTURAL DRAWINGS TO

VERIFY HOW AND WHERE CONCRETE CAN BE CUT.

L. EXPOSED PIPING SHALL BE PAINTED PER ARCHITECTURAL OR PROVIDED

WITH A PVC COATED JACKET IN THE COLOR OF THE ARCHITECT'S

CHOOSING. CONTRACTOR TO CLEAN AND DRY PIPING PRIOR TO PAINTING.

M. SANITARY SEWER, RAINWATER, AND OTHER DRAIN PIPING SHALL BE

INSTALLED AT A MINIMUM 1/4" PER FOOT (2%) SLOPE IN DIRECTION OF FLOW.

UNLESS OTHERWISE INDICATED ON THE DRAWINGS.

N. COORDINATE UNDERGROUND FIRE RISER STUB UP LOCATION WITH FIRE

SUPPRESSION SHOP DRAWINGS.

PLUMBING PLAN NOTES

DATE:

SHEET:

317 N. Cruse Ave. STE. 201

Helena, Montana

59601

406.449.2013 www.mosaicarch.com

D A

T E

S T

A M

P a r c h i t e c t u r e - p l a n n i n g - d e s i g n

/1

/2

:2 :2

A

M

07.14.2026

P201

PLUMBING FLOOR PLAN -

BASEMENT

26 FORT MISSOULA RD, MISSOULA, MT

BUILDING 24

BASEMENT

REMODEL

C O

N S

T R

U C

T I O

N D

O C

U M

E N

T S

KEY NOTES:#

1. EXISTING WALL CLEAN OUT TO REMAIN. EXTEND EXISTING CLEAN OUT

THROUGH NEW CABINET BACK WALL. FURNISH AND INSTALL STAINLESS

STEEL COVER AND SCREW. COORDINATE WITH GENERAL CONTRACTOR TO

MAINTAIN ACCESS.

2. CONNECT (N) SINK TO EXISTING DCW, DHW, AND SAN SERVICES.

3. EXISTING 4" PVC RADON PIPE RISES FROM BELOW THE BASEMENT FLOOR

SLAB-ON-GRADE, AND TERMINATES THROUGH THE WALL AT

APPROXIMATELY 4'-6" AFF. NO WORK.

4. EXISTING AC-1 PUMPED CONDENSATE LINE TO REMAIN, NO WORK.

EXISTING 3/8" POLY LINE IS ROUTED ABOVE THE LAY-IN CEILING.

N 1/8" = 1'-0"2

PLUMBING BASEMENT PLAN EAST

1/8" = 1'-0"1

PLUMBING BASEMENT PLAN WEST KEY PLAN

I S S

E F

O R

P

LAN

O EN

G

IN

E E R

ON

T

M

AN

A

LICENSE

D

JASON D.

BEAUDETTE

No. 11138 PE

# DATE REVISION

TannerGrimstad PolyLine

TannerGrimstad PolyLine

TannerGrimstad Text Box

CONTRACTOR RESPONSIBILITY AS FOLLOWS:

1. VERIFY EXISTING PLUMBING LINE SIZE, LENGTH, AND ATTACHMENT LOCATION TO SITE MANHOLE. ALL INFORMATION IS TO BE INCLUDED IN BID.

2. UNCLOG OR REPLACE EXISTING PLUMBING LINE AS REQUIRED TO ENSURE ADEQUATE PERFORMANCE OF SINK IN BREAK ROOM.

3. ALL SITE WORK TRENCHNING/EXCAVATION TO BE COMPLETED BY THE CONTRACTOR AND INCLUDED IN THEIR BID.

4. ALL EXTERIOR PENETRATION, PIPE SEALING, AND ATTACHMENTS REQUIREMENTS TO BE COMPLETED BY THE CONTRACTOR AND INCLUDED IN THEIR BID.

TannerGrimstad Dimension

VERIFY

TannerGrimstad

SUPPLEMENTAL DRAWINGS PAGE 4 OF 4