SubstitutionCAT 6.pdf
PDF 1 MB Posted
- Solicitation number
- 1240LU26Q0111
- Issued by
-
Department of Agriculture Forest Service
About this file
This document is a substitution request for a federal construction project (Lolo National Forest - Building 24 Basement Remodel) submitted after the bidding/negotiating phase, along with supporting technical specifications and product data sheets for communications cabling systems.
The substitution requests the replacement of a specified Category 6 twisted pair cable with a Panduit minicom cable with General Cable as the proposed substitute. The requestor indicates no performance differences between the proposed substitution and the specified product, cites that Panduit is not a product partner for the specified item as the reason for substitution, notes similar cost to the owner, and confirms no impact on other work or contract time. Supporting product data for the Panduit TX6 PLUS UTP jack modules and Mini-Com High Density Modular Patch Panels are included, demonstrating Category 6/Class E compliance with ANSI/TIA-568-C.2 standards and certified performance to 250 MHz. The specification section (27 1513) for Communications Copper Horizontal Cabling establishes requirements for Category 6 and Category 6A twisted pair cables, hardware, coaxial cable, and grounding provisions for the Missoula Montana Airport ATCT Modernization project. Acceptable manufacturers include CommScope, Leviton, and The Siemon Company. Installation must comply with TIA-568.1-E, NECA 1, and TIA-607-D standards, with cables rated CMR (non-plenum), 23 AWG solid copper conductors, and unshielded twisted pairs. The Division 27 contractor must be a manufacturer-certified contractor providing a minimum 25-year performance warranty on parts and labor, with personnel demonstrating minimum five years of cable installation experience and 40 hours of certified training.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
© Copyright 2013, CSI, 110 S. Union St., Suite 100, Alexandria, VA 22314
Page ___ of ___ Form Version: September 2013 CSI Form 13.1A
SUBSTITUTION
REQUEST
(After the Bidding/Negotiating Phase) Project:
To:
Re:
Substitution Request Number:
From:
Date:
A/E Project Number:
Contract For:
Specification Title:
Section: Page:
Description:
Article/Paragraph:
Proposed Substitution:
Manufacturer: Address: Phone:
Trade Name: Model No.:
Installer: Address: Phone:
History: ☐ New product ☐ 1-4 years old ☐ 5-10 years old ☐ More than 10 years old
Differences between proposed substitution and specified product:
☐ Point-by-point comparative data attached — REQUIRED BY A/E
Reason for not providing specified item:
Similar Installation:
Project: Architect:
Address: Owner:
Date Installed:
Proposed substitution affects other parts of Work: ☐ No ☐ Yes; explain
Savings to Owner for accepting substitution: ($ ).
Proposed substitution changes Contract Time: ☐ No ☐ Yes [Add] [Deduct] days.
Supporting Data Attached: ☐Drawings ☐Product Data ☐ Samples ☐ Tests ☐ Reports ☐
Cat 6 Cable and hardware
Panduit minicom with General Cable
Panduit
800-777-3300
Horizontal Cable
Communication Resources
5340 Mommont Rd. Missoula, MT 59808
406-203-1670
X
Similar Cost
JD
JD
18900 Panduit Dr, Tinley Park, IL
Austin Line
Austin Line
Austin Text Box Not a product partner for what is on spec
Gretchen Lolo National Forest - Building 24 Basement Remodel
Gretchen No performance differences.
Gretchen Category 6 twisted pair cable
Gretchen 27 1513
Gretchen T003
Gretchen Products A.2.
GenSPEED® Category 6 Cables Datacom
Separator
• Cross-web
Rip Cord
• Applied longitudinally under jacket
Jacket
| • | Non-Plenum: Flame-Retardant PVC |
| • | Plenum: Low-Smoke, Flame-Retardant |
PVC
Features and Benefits
■ Innovative cross-web design allowing for maximum pair separation, increasing key electrical performance parameters
| ■ | Performance guaranteed to 350 MHz |
| ■ | TRU-Mark® print legend contains |
footage markings from 1000' to 0'
■ Third-party verified for guaranteed performance
■ Made in U.S.A.
Applications
■ IEEE 802.3: 1000 BASE-T, 100 BASE-TX,
10 BASE-T, PoE, PoE+
| ■ | ANSI/TIA 854: 1000 BASE-TX |
| ■ | CDDI, Token Ring, ATM |
| ■ | Digital Video |
| ■ | Broadband and Baseband Analog Video |
Standard Compliances
| ■ | ANSI/TIA 568-C.2 |
| ■ | NEC/CEC Type CMR (UL 1666) |
for Non-Plenum
■ NEC/CEC Type CMP (NFPA 262) for Plenum
| ■ | UL 444 |
| ■ | RoHS Compliant Directive 2011/65/EU |
| ■ | ANSI/TIA 862 (Building Automation) |
| ■ | ICEA S-116-732 |
| ■ | ICEA S-102-700 |
| ■ | ISO/IEC 11801 Ed. 2.0 (Class E) |
PHYSICAL DATA
CMR (Non-Plenum) CMP (Plenum)
Nominal Cable Diameter (in) 0.235 0.215
Nominal Cable Weight (lbs/1000 ft) 28 28
Minimum Bend Radius (in) 1.0 1.0
Maximum Pulling Force (lbs) 32 32
Temperature Rating (˚C)
Installation: 0 to +60 0 to +60
Operation: -20 to +75 -20 to +75
Data subject to change without notice.
PART NUMBERS
Standard packaging: 1000' Pull-Pac® ll
Pull-Pac® Il Spool-Pac® Spool
Jacket Color
CMR
(Non-Plenum)
CMP
(Plenum)
CMR
(Non-Plenum)
CMP
(Plenum)
CMR
(Non-Plenum)
CMP
(Plenum)
Blue 7133900 7131900 7133940 7131940 7133960 7131960
White 7133901 7131901 7133941 7131941 7133961 7131961
Yellow 7133902 7131902 7133942 7131942 7133962 7131962
Gray 7133903 7131903 7133943 7131943 7133963 7131963
Red 7133904 7131904 7133944 7131944 7133964 7131964
Orange 7133905 7131905 7133945 7131945 7133965 7131965
Green 7133906 7131906 7133946 7131946 7133966 7131966
Black 7133907 7131907 7133947 7131947 7133967 7131967
Pink 7133908 7131908 7133948 7131948 7133968 7131968
Purple 7133909 7131909 7133959 7131959 7133969 7131969
| Note: | Bulk reels are available as a special request with a maximum allowable length of 3000 feet per reel. Minimum run and |
| lead time may apply. |
Non-stock items may be subject to minimum order quantities.
CONSTRUCTION
Conductors
• 23 AWG solid bare annealed copper
Insulation
| • | Non-Plenum: Polyolefin |
| • | Plenum: Fluoropolymer |
Color Code
| • | Pair 1: Blue-White/Blue |
| • | Pair 2: Orange-White/Orange |
| • | Pair 3: Green-White/Green |
| • | Pair 4: Brown-White/Brown |
TIA 568-C.2
GenSPEED ® 6000 Enhanced Category 6 Cable Optimally Balanced Enhanced Performance
Datacom GenSPEED® Category 6 Cables
ELECTRICAL PERFORMANCE
Frequency MHz PSACR* (min) ACR* (min) Insertion Loss (max) PSNEXT (min) NEXT (min)
Guaranteed Guaranteed TIA 568-C.2 Guaranteed TIA
568-C.2 Guaranteed TIA 568-C.2 Guaranteed
1 75.3 77.3 2.0 2.0 72.3 77.3 74.3 79.3 4 64.5 66.5 3.8 3.8 63.3 68.3 65.3 70.3 10 56.4 58.4 6.0 5.9 57.3 62.3 59.3 64.3 16 51.7 53.8 7.6 7.5 54.2 59.3 56.2 61.3 20 49.4 51.4 8.5 8.4 52.8 57.8 54.8 59.8
31.25 44.3 46.3 10.7 10.6 49.9 54.9 51.9 56.9
62.5 35.1 37.1 15.4 15.3 45.4 50.4 47.4 52.4 100 27.6 29.6 19.8 19.7 42.3 47.3 44.3 49.3 150 20.0 22.0 24.7 24.7 39.7 44.7 41.7 46.7 200 13.8 15.8 29.0 29.0 37.8 42.8 39.8 44.8 250 8.7 10.7 32.8 32.6 36.3 41.3 38.3 43.3 350 — 1.7 — 39.5 — 39.2 — 41.2 500 — — — 48.6 — 36.8 — 38.8
Note: Values are expressed in dB per 100 m (328 ft.) length @ 20˚C. Results beyond 350 MHz for reference only.
*PSACR & ACR not specified in ANSI/TIA 568-C.2
Frequency MHz PSACRF (min) ACRF (min) Return Loss (min) TCL (min) ELTCTL (min)
TIA
568-C.2 Guaranteed TIA
568-C.2 Guaranteed TIA 568-C.2 Guaranteed TIA
568-C.2 Guaranteed TIA 568-C.2 Guaranteed
1 64.8 69.8 67.8 72.8 20.0 20.0 40.0 40.0 35.0 35.0 4 52.8 57.7 55.7 60.7 23.0 23.6 40.0 40.0 23.0 23.0 10 44.8 49.8 47.8 52.8 25.0 26.0 40.0 40.0 15.0 15.0 16 40.7 45.7 43.7 48.7 25.0 26.0 38.0 38.0 10.9 10.9 20 38.8 43.7 41.7 46.7 25.0 26.0 37.0 37.0 9.0 9.0
31.25 34.9 39.9 37.9 42.9 23.6 25.0 35.1 35.1 — 5.1
62.5 28.9 33.8 31.8 36.8 21.5 23.5 32.0 32.0 — 5.0 100 24.8 29.8 27.8 32.8 20.1 22.5 30.0 30.0 — 5.0 150 21.3 26.3 24.3 29.3 18.9 21.6 28.2 28.2 — 5.0 200 18.8 23.8 21.8 26.8 18.0 21.0 27.0 27.0 — 5.0 250 16.8 21.8 19.8 24.8 17.3 20.5 26.0 26.0 — 5.0 350 — 18.9 — 21.9 — 19.8 — — — — 500 — 15.8 — 18.8 — 19.0 — — — —
Note: Values are expressed in dB per 100 m (328 ft.) length @ 20˚C. Results beyond 350 MHz for reference only.
GenSPEED® 6000 ENHANCED CATEGORY 6
CROSS-SECTION
CROSS-WEB
INSULATION
RIP CORD
OUTER
JACKET
23 AWG
CONDUCTOR
ELECTRICAL CHARACTERISTICS
Max. Nom.
DC Resistance Ohms/100 m (328 ft) @ 20˚C
9.38 7.20
DC Resistance Unbalance Individual Pair %
4.00 < 1
Delay Skew ns/100 m
CMP: 30
CMR: 40
Nom. Velocity of Propagation % Speed of Light
CMP: 70
CMR: 68
Characteristic Impedance Frequency (f): 1-500 MHz
Ohms 100 ± 15
100% performance tested Confidence that each jack module will deliver the critical electrical performance requirements
Utilizes enhanced Optimizes performance by eliminating conductor untwist and reduces Giga-TX ™ Technology installation time and expense
Improved termination cap Conductor retention slots simplify jack module termination
Modular UTP jack modules snap in and out of all Mini-Com® Faceplates, Modular Patch Panels and Surface Mount Boxes for easy moves, adds, and changes
True strain relief Controls cable bend radius for long term installed performance
Individually serialized Marked with quality control number for future traceability
RJ45 interface Industry standard interface provides a quick and easy plug and play connection to RJ45 patch cords; backwards compatible
Identification Can be clearly identified with optional labels and icons for port identification
Keyed version available Color-specific keys with positive and negative keying features mechanically and visually distinguish connections to prevent unintentional mating with unlike keyed or non-keyed modular plugs, offering network design flexibility, versatility, accommodating discrete networks for enhanced security
Termination tools (optional) EGJT termination tool ensures conductors are fully terminated by utilizing a smooth forward motion without impact on critical internal components for maximum reliability; TGJT termination tool ideal for high volume installations
Block out device (optional) Provides a simple and secure method to control access to data ports while not in use
Shuttered version (optional) Integrated shuttered door keeps out dust and debris of unmated RJ45 jack modules www.panduit .com
Category 6/Class E Exceeds channel requirements of ANSI/TIA-568-C.2 Category 6 and channel and ISO 11801 Class E standards at swept frequencies 1 to 250 MHz component performance:
Exceeds component requirements of ANSI/TIA-568-C.2 Category 6 and ISO 11801 Class E standards at swept frequencies 1 to 250 MHz
FCC and ANSI Meets all applicable ANSI/TIA-968-A requirements; contacts plated with compliance: 50 microinches of gold for superior performance
IEC compliance: Meets IEC 60603-7
RoHS compliance: Compliant
PoE compliance: Meets requirements of IEEE 802.3af and IEEE 802.3at for PoE applications
UL rated: UL 1863 approved
Conductor termination Wire cap compatible with 22 – 26 AWG solid or stranded cable with conductor range: insulation diameters of 0.060 in. max. and overall cable O.D. 0.200 in. to 0.330 in.
k e y f e a t u r e s a n d b e n e f i t s a p p l i c a t i o n s t e c h n i c a l i n f o r m a t i o n s p e c i f i c a t i o n s Category 6/Class E, 8-position, UTP jack module shall terminate 4-pair, 22 – 26 AWG, 100 ohm unshielded twisted pair cable and shall not require use of a punchdown tool. UTP jack modules shall use a forward motion termination method to optimize performance by maintaining cable pair geometry while eliminating conductor untwist.
The termination cap shall be color-coded white to designate Category 6 performance and shall include a universal label coded for T568A and T568B wiring schemes.
Mini-Com® TX6™ PLUS UTP Jack Modules are a component of the TX6™ PLUS UTP Copper Cabling System. This end-to-end system is interoperable and backwards compatible, providing design flexibility to protect network investments well into the future. With certified performance to the ANSI/TIA-568-C.2 Category 6 and ISO 11801 Class E standards, this system is ideal for today's high performance workstation applications. With certified performance to the ANSI/TIA-568-C.2 Category 6 and ISO 11801 Class E Edition 2.1 standards, these systems will support the following applications:
• Ethernet 10BASE-T, 100BASE-T (Fast Ethernet), 1000BASE-T (Gigabit Ethernet)
• 155 Mb/s ATM, 622 Mb/s ATM, 1.2 Gb/s ATM
• Token Ring 4/16
• Digital video and broadband/baseband analog video
• Voice over Internet Protocol (VoIP)
Mini-Com ® TX6 ™ PLUS UTP Jack Modules
Jack module: CJ688TGIW* Shuttered jack module: CJD688TGIW* Keyed jack module: CJK688TG**
TX6000 ™ UTP Copper Cable
Plenum: PUP6004*** Riser: PUR6004***
LSZH: PUL6004***
CM: PUC6004***
TX6 ™ PLUS UTP Patch Cords
CM (foot lengths): UTPSP^Y CM (meter lengths): UTPSP^^MY LSZH (meter lengths): UTPSPL^^MY
Mini-Com ® Angled Modular Patch Panels
24-port, 1 RU: CPPLA24WBLY 48-port, 2 RU: CPPLA48WBLY
Mini-Com ® Flat Modular Patch Panels 24-port, 1 RU: CPPL24WBLY 48-port, 2 RU: CPPL48WBLY For additional modular patch panels and punchdown patch panels, visit www.panduit.com
Tools and Accessories Jack module termination tool: EGJT or TGJT Wire snipping tool: CWST Wire stripping tool: CJAST Clear dust cap: MDC-C Block out device: PSL-DCJB-^^^ Phone icons: CIPIW-C+ Data icons: CIDIW-C+
*To designate color other than IW (Off White), replace IW suffix with EI (Electric Ivory), IG (International Gray), AW (Arctic White), BL (Black), BU (Blue), RD (Red), YL (Yellow), GR (Green), OR (Orange), or VL (Violet).
**To designate color, add suffix BL (Black), BU (Blue), RD (Red), YL (Yellow), GR (Green), or OR (Orange).
Each color representing a different keyed configuration.
***To designate color, add suffix BU (Blue) or WH (White). For additional cable colors, contact customer service.
^For lengths 1 to 20 feet (one foot increments) and 25, 30, 35, 40 feet, change the length designation in the part number to the desired length. For standard cable colors other than Off White, add suffix BL (Black), BU (Blue), RD (Red), YL (Yellow), GR (Green), OR (Orange), or VL (Violet). For example, the part number for a blue 15-foot patch cord is UTPSP15BUY.
^^For lengths 1 to 10 meters (one meter increments) and 2.5, 15, 20, 25, 30, 35, 40 meters, change the length designation in the part number to the desired length. For standard cable colors other than Off White, add suffix BL (Black), BU (Blue), RD (Red), YL (Yellow), GR (Green), OR (Orange), or VL (Violet).
For example, the part number for a blue 15-meter patch cord is UTPSP15MBUY.
^^^To designate color other than Red, add suffix Black (BL), Blue (BU), Yellow (YL), Green (GR), Orange (OR), Off White (IW) or International Gray (IG) at the end of the part number. 10/package.
+To designate color other than IW (Off White), replace IW with EI (Electric Ivory), IG (International Gray), BL (Black), BU (Blue), RD (Red), YL (Yellow), GR (Green), OR (Orange), or VL (Violet) in the part number. 100/package.
Contact customer service for bulk packaged and/ or keyed jack modules and patch cords.
TX6 ™ PLUS UTP Copper Cabling Systems
Mini-Com ® TX6 ™ PLUS UTP Jack Modules
SPECIFICATION SHEET
T e s t R e s u l t s
IEC 512-9b
Normal Force Mechanical Test Test Method Measurement Typical Test Results
Vibration
Shock
IEC 512-6d
IEC 512-6c
Load (grams) Circuit Resistance (mOhms)
Contact Disturbance (microseconds)
<40
Durability IEC 512-9a Circuit Resistance (mOhms) <40
Mating/Un-Mating IEC 512-13b Mating Force (N)
Un-mating Force (N)
<20
Termination Cycles IEC 352 Number of Cycles >20
<20
>100
<5
Temperature Life Environmental Test Test Method Measurement Typical Test Results
Humidity
Thermal Shock
IEC 512-11c
IEC 512-11d
Circuit Resistance (mOhms)
Circuit Resistance (mOhms)
Circuit Resistance (mOhms)
<40
<40
<40
Climatic Sequence IEC 512-11a Circuit Resistance (mOhms) <40
Flowing Mixed Gas Corrosion IEC 512-11g Circuit Resistance (mOhms) <40
Low Level Circuit Resistance Electrical Test Test Method Measurement Typical Test Results
Dielectric Withstand Voltage
Insulation Resistance
IEC 512-2a IEC 512-4a
IEC 512-3a
Resistance (mOhms) 1000 V, 1 minute
Resistance (MOhms)
Passed <20
>500
Mini-Com ® TX6 ™ PLUS UTP Jack Modules
.62 (15.87)
.71 (18.06)
1.50 (38.15)
Dimensions are in inches (Dimensions in parenthesis are metric)
©2011 Panduit Corp.
ALL RIGHTS RESERVED.
WW-COSP48
5/2011
WORLDWIDE SUBSIDIARIES AND SALES OFFICES
For a copy of Panduit product warranties, log on to www.panduit.com/warranty
PANDUIT CANADA
Markham, Ontario cs-cdn@panduit.com Phone: 800.777.3300
PANDUIT EUROPE LTD.
London, UK cs-emea@panduit.com Phone: 44.20.8601.7200
PANDUIT JAPAN
Tokyo, Japan cs-japan@panduit.com Phone: 81.3.6863.6000
PANDUIT SINGAPORE PTE. LTD.
Republic of Singapore cs-ap@panduit.com Phone: 65.6305.7575
PANDUIT AUSTRALIA PTY. LTD.
Victoria, Australia cs-aus@panduit.com Phone: 61.3.9794.9020
PANDUIT LATIN AMERICA
Guadalajara, Mexico cs-la@panduit.com Phone: 52.33.3777.6000
Contact Customer Service by email: cs@panduit.com or by phone: 800-777-3300 and reference COSP48
Visit us at www.panduit.com For more information
Jack Module Shuttered Jack Module
PANDUIT P/N WEIGHT
.62 LB/10 PCS
(286.1 g/10 PCS)
CBX2**-AY
NOTES:
1. SEE CURRENT CATALOG FOR ADDITIONAL
PART NUMBER SUFFIXES TO INDICATE
COLOR AND OR PACKAGE QUANTITY.
2. SEE CATALOG FOR A COMPLETE LIST
OF PARTS APPLICABLE FOR USE WITH
THIS PART.
3. DIMENSIONS IN [] ARE IN METRIC.
4. ALSO INCLUDED WITH BOX:
1- BOX BASE
1- BOX COVER
1- PLT1.5I-C PAN-TY
2- MOUNTING SCREW
1- STRIP OF 3.00" X .75" FOAM
TAPE FOR MOUNTING
1- ID LABEL KIT
5. BREAKOUTS DESIGNED TO ACCEPT
LD3/LDP3 OR LD5/LDP5 RACEWAY.
6. BASE MATERIAL THICKNESS= .090[2.29].
3.65
92.7
1.95
49.5
1.06
27.0
2.36
60.0
MOUNTING HOLES
FOR #6 PAN HEAD
SCREW (2 PLACES)
PAN-TY LOOP FOR
CABLE HOLD-DOWN BREAKOUT AREA
(3 PLACES)
THIS COPY IS PROVIDED ON A RESTRICTED BASIS AND IS NOT TO BE USED IN ANY WAY DETRIMENTAL TO THE INTERESTS OF PANDUIT CORP.
A
B
A
B
2 1
M02479EN/00
M02479EN_DC120/00B
D D
A /1
NO WARRANTY, EXPRESSED OR IMPLIED, IS MADE BY PANDUIT WITH RESPECT
TO ADHESIVE BOND PERFORMANCE. AMONG OTHER THINGS, THE CONDITIONS
UNDER WHICH THESE MOUNTS MAY BE APPLIED AND/OR THE SURFACE TO WHICH
THEY MAY BE APPLIED ARE BEYOND PANDUIT'S CONTROL.
PART NUMBER
CBX2**-AY
TITLE
MINI-COM 2 POSITION SURFACE MOUNT BOX
CUSTOMER DRAWING
ITEM REVISION NAME
DATASET FILE NAME
MATERIAL:
UNLESS OTHERWISE SPECIFIED,
DIMENSIONAL TOLERANCES ARE: IN [mm]
.X .1 [2.54] .XXX .005 [.127]
.XX .01 [.25] ANGLES 5
DRAWING NUMBER:
THIRD ANGLE
PROJECTION 02479-120
DRAWN BY DATE CHK SCALE SIZE
JSP 1-26-07 MJD NONE SHT 1 OF 1 A
1 3/11/14 JSP REFR MMR A. REVISED DRAWING TITLE BLOCK. 02479-120
R 1-26-07 JSP MJD MJD RELEASED TO PRODUCTION 02479-120
REV DATE BY CHK APR DESCRIPTION ECN
www.panduit.com s p e c i f i c a t i o n s High density modular patch panels shall consist of a metal panel with molded front or rear snap-in faceplates. Patch panels shall accept all Mini-Com® Modules for UTP, STP, A/V or select fiber and shall mount to standard 19" racks. Patch Panels shall be available in 32-port (1 RU), 48-port (1 RU) and 72-port (2 RU). Select styles shall be available in white. Flush mount panels shall be easy to identify with pre-numbered ports. Angled patch panels shall be designed at an optimum angle to help route the cable.
Mini-Com® High Density Modular Patch Panels S P E C I F I C A T I O N S H E E T a p p l i c a t i o n s Mini-Com® High Density Patch Panels are ideal for multi-media applications. Flat and angled designs are available in various port densities to fit most needs. Flush mount style includes pre-numbered ports or area for adhesive labeling, select faceplate style panels with label pockets include pre-numbered labels and covers. Angled patch panels are available for applications in which rack space is limited. The design allows cable to flow to each side of the rack, minimizing the need for horizontal cable managers and increasing the density of the rack space. High density patch panels can mount on a standard 19" rack or a 23" rack when using the extender brackets PEB1 or PEB2.
t e c h n i c a l i n f o r m a t i o n Mounting options: Mounts to standard 19" rack
Material: Stamping is CRS and faceplate is ABS
Packaging: Packaged with appropriate pre-installed snap in faceplates and a set of mounting screws (#12-24) k e y f e a t u r e s a n d b e n e f i t s Modular Panels with front snap-in faceplates will accept any
Mini-Com® Modules and panels with rear snap-in faceplates will accept all UTP, STP, A/V and most fiber modules
Angled design Minimizes the need for horizontal cable managers enabling patch cords to be routed directly into vertical cable managers which leads to increase closet density
Port and panel identification Pre-numbered ports and labeling capabilities on select panels
Optional strain relief bars To help support and manage cables
Optional filler panels Flat and angled design fill unused rack openings to provide a clean and consistent look when used with any version of Panduit patch panels
Optional extender bracket Allows 19" patch panels to be mounted on a 23" rack
High density More modules per rack space
Color options Select styles available in white, standard color is black
Mini-Com® High Density Flat Style, Flush Mount Black 48-port, 1 RU: CPP48HDWBLY* 48-port, 1 RU (extended area for labeling): CPP48HDEWBL 48-port, 1 RU (vertical
| numbering): | CPP48HDVNSWBL* |
| 72-port, 2 RU: | CPP72FMWBLY |
White 48-port, 1 RU: CPP48HDWWH* Mini-Com® High Density Angled Style, Flush Mount Black 48-port, 1 RU: CPPA48HDWBLY* 48-port, 1 RU (extended area for labeling): CPPA48HDEWBL 48-port, 1 RU (vertical
| numbering): | CPPA48HDVNSWBL* |
| 72-port, 2 RU: | CPPA72FMWBLY |
White 48-port, 1 RU: CPPA48HDWWH* Mini-Com® High Density Patch Panels Faceplate Style 32-port, 1 RU, flat: CPP32WBLY 72-port, 2 RU, flat: CPPL72WBLY 72-port, 2 RU, angled: CPPLA72WBLY Patch Panel Accessories
Black Transitional cover: CPATCBL Angled filler panel, 1 RU: CPAF1BL
Angled filler panel, 2 RU: CPAF2BL
Flat filler panel, 1 RU: DPFP1
Flat filler panel, 2 RU: DPFP2
White Transitional cover: CPATCWH Angled filler panel, 1 RU: CPAF1WH
Angled filler panel, 2 RU: CPAF2WH
Flat filler panel, 1 RU: DPFP1WH
Flat filler panel, 2 RU: DPFP2WH
Extender Brackets
| 1 RU: | PEB1 |
| 2 RU: | PEB2 |
* = Space not available for labeling
Mini-Com® High Density Modular Patch Panels
CPP48HDVNSWBL
1.25 [31.8]
0.62 [15.9]
1.08 [27.4]
19.00 [482.6]
1.72 [43.7]
18.20 [462.3]
CPPL72WBLY
1.25 [31.8]
0.62 [15.9]
1.75 [44.4]
19.00 [482.6]
3.47 [88.1]
3.92 [99.5]
2.38 [60.3]
3.00 [76.2]
18.20 [462.3]
CPP48HDEWBL
1.25 [31.8]
1.25 [31.8]
1.08 [27.4]
19.00 [462.6]
1.72 [43.7]
18.20 [462.3]
CPP72FMWBLY
2.38 [60.3]
3.00 [76.2]
3.47 [88.1]
19.00 [482.6]
0.67 [19.2]
1.75 [44.4]
1.25 [31.8]
0.62 [15.9]
18.20 [462.3]
CPP48HDWBLY
CPP48HDWWH
1.25 [31.8]
0.62 [15.9]
1.08 [27.4]
19.00 [482.6]
1.72 [43.7]
18.20 [462.3]
Mini-Com® High Density Modular Patch Panels Label Chart
Part Number Label Type Replacement for
Label Pocket Laser/Ink LS8 Thermal
CPP32WBLY
Adhesive — — T024X000VPC-BK T024X000FJT
CPP48HDEWBL
CPP48HDWWH
CPPA48HDEWBL
CPPA48HDWWH
CPP72FMWBLY
CPPA72FMWBLY
CPPL72WBLY
Pocket C72PPLK C282X030Y1J C282X030Y1C —
CPPLA72WBLY
CPP32WBLY
0.62 [15.9]
0.58 [14.8]
19.00 [482.6]
1.73 [44.0]
18.20 [462.3]
1.25 [31.8]
©2019 Panduit Corp.
ALL RIGHTS RESERVED.
OTSP49--WW-ENG
1/2019
Dimensions are in inches (Dimensions in parentheses are metric)
Mini-Com® High Density Modular Patch Panels
WORLDWIDE SUBSIDIARIES AND SALES OFFICES
For a copy of Panduit product warranties, log on to www.panduit.com/warranty
PANDUIT US/CANADA
Phone: 800.777.3300
PANDUIT EUROPE LTD.
London, UK cs-emea@panduit.com Phone: 44.20.8601.7200
PANDUIT JAPAN
Tokyo, Japan cs-japan@panduit.com Phone: 81.3.6863.6000
PANDUIT SINGAPORE PTE. LTD.
Republic of Singapore cs-ap@panduit.com Phone: 65.6305.7575
PANDUIT AUSTRALIA PTY. LTD.
Victoria, Australia cs-aus@panduit.com Phone: 61.3.9794.9020
PANDUIT LATIN AMERICA
Guadalajara, Mexico cs-la@panduit.com Phone: 52.33.3777.6000
Contact Customer Service by email: cs@panduit.com or by phone: 800.777.3300
Visit us at www.panduit.com For more information
Dimensions are in inches [Dimensions in brackets are metric]
CPPA48HDWBLY
CPPA48HDWWH
3.86 [98.0]
1.25 [31.8]
0.62 [15.9]
4.67 [118.7]
19.00 [482.6]
1.72 [43.7]
18.20 [462.3]
CPPA48HDEWBL
3.86 [98.0]
1.25 [31.8]
4.67 [118.7]
19.00 [482.6]
1.72 [43.7]
18.20 [462.3]
0.62 [15.9]
CPPA48HDVNSWBL
3.86 [98.0]
1.25 [31.8]
4.67 [118.7]
19.00 [482.6]
1.72 [43.7]
18.20 [462.3]
0.62 [15.9]
CPPA72FMWBLY
4.36 [110.7]
2.38 [60.3]
3.47 [88.1]
19.00 [482.6]
0.50 [12.7]
18.20 [462.3]
1.75 [44.4]
3.00 [76.2]
1.25 [31.8]
0.62 [15.9]
CPPLA72WBLY
1.25 [31.8]
0.62 [15.9]
1.75 [44.4]
19.00 [482.6]
3.47 [88.1]
4.26 [108.1]
3.92 [99.5]
2.38 [60.3]
3.00 [76.2]
18.20 [462.3]
MISSOULA MONTANA AIRPORT
ATCT MODERNIZATION
Section 27 1513 Communications Copper Horizontal Cabling 1 of 6
SECTION 27 1513
COMMUNICATIONS COPPER HORIZONTAL CABLING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Category 6 twisted pair cable.
2. Category 6A twisted pair cable.
3. Twisted pair cable hardware, including plugs and jacks.
4. Coaxial Cable.
5. Grounding provisions for twisted pair cable.
1.2 COPPER HORIZONTAL CABLING DESCRIPTION
A. Horizontal cabling system shall provide interconnections between the patch panels in the telecommunications rooms, and the equipment outlet. Cabling system consists of horizontal cables, intermediate and main cross-connects, mechanical terminations, and patch cords or jumpers used for horizontal-to-horizontal cross-connection.
B. The maximum allowable horizontal cable length is 90 meters. This maximum allowable length does not include an allowance for the length of 10 meters used for patching.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product used on this project, provide cut sheet with highlighted part number of product. A separate submittal is required for each specification section. Do not combine or merge specification sections.
B. Submittal requires example work area outlet labeling scheme and physical cable labels to be used on project.
1.4 INFORMATIONAL SUBMITTALS
A. Qualification Data: For installers and installation supervisor.
1.5 CLOSEOUT SUBMITTALS
A. Maintenance data.
B. As-built drawings.
C. Test results.
D. Warranty certificate.
Section 27 1513 Communications Copper Horizontal Cabling 2 of 6
1.6 COORDINATION
A. Coordinate layout and installation of telecommunications pathways and cabling with Owner's telecommunications and LAN equipment and service suppliers.
1.7 INSTALLER QUALIFICATIONS
A. Installer Qualifications: Division 27 sub-contractor shall be a manufacturer certified contractor and will be required to provide a minimum 25-year performance warranty on parts and labor for all Category 6 and Category 6A cabling and systems. Proof of the sub-contractor’s ability to provide such a warranty shall be submitted to the General Contractor at the time of bidding and to the Owner prior to the Notice To Proceed. This warranty shall cover the patch panels, horizontal cabling, work area outlets, and patch cords.
B. Contractor shall employ, in conjunction with construction of the project, a capable, experienced, and reliable foreperson and such skilled workers as may be required for the various classes of work to be performed. Contractor shall be required to submit evidence of foreperson's skilled experience on ANSI/TIA certified structured cabling systems. Evidence of experience shall be submitted to Owner with submittal of bid. Minimum experience for any workman involved in cabling work shall be cable pulling and termination work on projects for a minimum of 5 years and completion of training (40 hrs. minimum) which certifies the person’s work in copper cabling installations. Training can be a combination of BICSI and manufacturer training.
PART 2 - PRODUCTS
2.1 REQUIREMENTS
A. General Performance: Horizontal cabling system shall comply with transmission standards in TIA-568.1-E, when tested according to test procedures of this standard.
B. Telecommunications Pathways and Spaces: Comply with TIA-569-E.
C. Grounding: Comply with TIA-607-D.
2.2 GENERAL CABLE CHARACTERISTICS
A. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with the applicable standard and NFPA 70 for the following types:
1. Communications, Non-plenum: Type CMR
B. RoHS compliant.
2.3 CATEGORY 6 TWISTED PAIR CABLE
A. Description: Four-pair, balanced-twisted pair cable, certified to meet transmission characteristics of Category 6 cable at frequencies up to 350 MHz. No minimum specification cable will be accepted. See drawings for additional details.
B. Manufacturers: Subject to compliance with requirements. Available manufacturers offering products that may be incorporated into the Work include the following:
http://www.specagent.com/Lookup?ulid=12523 Gretchen Highlight Communications, Non-plenum: Type CMR
Section 27 1513 Communications Copper Horizontal Cabling 3 of 6
1. CommScope, Inc.
2. Leviton.
3. The Siemon Company.
C. Standard: Comply with NEMA WC 66/ICEA S-116-732 and TIA-568.2-E for Category 6 cables.
D. Conductors: 100-ohm, 23 AWG solid copper.
E. Shielding/Screening: Unshielded twisted pairs (UTP).
F. Cable Rating: Riser.
G. Jacket: Blue.
2.4 INDOOR/OUTDOOR TWISTED PAIR CATEGORY 6 TWISTED PAIR CABLE
A. Description: Four-pair, balanced-twisted pair cable, certified to meet transmission characteristics of Category 6 cable at frequencies up to 350 MHz. No minimum specification cable will be accepted. See drawings for additional details.
B. Manufacturers: Subject to compliance with requirements. Available manufacturers offering products that may be incorporated into the Work include the following:
1. CommScope, Inc.
2. Leviton.
3. The Siemon Company.
C. Standard: Comply with NEMA WC 66/ICEA S-116-732 and TIA-568.2-E for Category 6 cables.
D. Conductors: 100-ohm, 23 AWG solid copper.
E. Shielding/Screening: Unshielded twisted pairs (UTP).
F. Cable Rating: Indoor/Outdoor.
G. Jacket: Blue.
H. For use with camera monitoring the runway.
2.5 CABLE HARDWARE
A. Description: Hardware designed to connect, splice, and terminate twisted pair copper communications cable. No minimum specification grade hardware will be accepted.
B. Manufacturers: Subject to compliance with requirements, provide products by the following:
1. CommScope, Inc.
2. Leviton.
3. The Siemon Company.
C. General Requirements for Twisted Pair Cable Hardware:
1. Comply with the performance requirements of Category 6 and Category 6A.
2. Comply with TIA-568.2-E, IDC type, with modules designed for punch-down caps or tools.
3. Cables shall be terminated with connecting hardware of same category or higher.
http://www.specagent.com/Lookup?uid=123457076948 http://www.specagent.com/Lookup?ulid=12523 http://www.specagent.com/Lookup?uid=123457076948 http://www.specagent.com/Lookup?ulid=2346 http://www.specagent.com/Lookup?uid=123457076937 Gretchen Highlight Riser
Gretchen
Blue.
Section 27 1513 Communications Copper Horizontal Cabling 4 of 6
4. No minimum specification hardware will be accepted.
D. Patch Panel: Modular panels housing numbered jack units with IDC-type connectors at each jack location for permanent termination of pair groups of installed cables.
1. Features:
a. Universal T568A and T568B wiring labels.
b. Labeling areas adjacent to conductors.
c. Replaceable connectors.
d. 48 ports.
2. Construction: 16-gauge steel and mountable on 19-inch equipment racks.
3. Number of Jacks per panel: 48.
E. Patch Cords: Provide one factory terminated Category 6 patch cord for each horizontal cable terminated within the patch panels. See drawings for additional details. The patch cable lengths shall be field measured before ordering (typical lengths are 3’ and 5’). Provide two factory terminated Category 6 patch cord for each duplex outlet indicated on the plans and four for each quad outlet indicated on the plans. The patch cable lengths shall be field measured before ordering (typical lengths are 5’ – 9’). Division 27 contractor to provide all patching within the telecommunications room. Field verify prior to ordering.
1. Patch cords shall have bend-relief-compliant boots and color-coded icons to ensure performance. Patch cords shall have latch guards to protect against snagging.
2. Patch cords to be 28 AWG, UNO.
a. Permanent links that exceed 83 meters shall use 24 AWG patch cords.
b. Patch cords shall not exceed a combined length on both ends of 10m for 24 AWG patch cords, or 6m for 28 AWG patch cords.
3. Provide all patching required for a complete and operational system.
F. Plugs and Plug Assemblies:
1. Male; eight position; color-coded modular telecommunications connector designed for termination of a single four-pair, 100-ohm, unshielded or shielded twisted pair cable.
2. Standard: Comply with TIA-568.2-E.2.
3. Marked to indicate transmission performance.
G. Jacks and Jack Assemblies:
1. Female; eight position; modular; fixed telecommunications connector designed for termination of a single four-pair, 100-ohm, unshielded or shielded twisted pair cable.
2. Designed to snap-in to a patch panel or faceplate.
3. Standard: Comply with TIA-568.2-E.
4. Marked to indicate transmission performance.
5. Color to be determined at time of submittal.
H. Faceplates:
1. Two, Four, and Six port, vertical single gang faceplates designed to mount to double gang wall boxes with single gang mud rings.
2. Eight, Ten, and Twelve port, vertical double gang faceplates designed to mount to double gang wall boxes.
3. Plastic Faceplate: High-impact plastic.
4. Metal Faceplate: Stainless steel.
5. For use with snap-in jacks accommodating any combination of twisted pair, optical fiber, and coaxial work area cords.
6. Snap-in, clear-label covers and machine-printed inserts.
7. Color to be determined at time of submittal.
Gretchen Highlight No minimum specification hardware will be accepted
Gretchen
Patch Cords:
Section 27 1513 Communications Copper Horizontal Cabling 5 of 6
2.6 COAXIAL CABLE
A. Description: Series-6 and Series-11 quad shield
B. Manufacturers: Subject to compliance with requirements, provide products by the following:
1. CommScope, Inc.
2. General Cable.
3. Belden.
C. Standard: Comply with TIA-568.4-E Broadband Coaxial Cabling and Components
D. Conductors: 75-ohm, 18 AWG solid copper.
E. Shielding/Screening: Quad Shield 90% braid
F. Cable Rating: Plenum.
G. Termination: Compression F connectors
H. Jacket: Black or White.
2.7 GROUNDING
A. Comply with TIA-607-D.
PART 3 - EXECUTION
3.1 INSTALLATION OF TWISTED-PAIR HORIZONTAL CABLES
A. Comply with NECA 1 and ANSI/TIA 568.
B. Wiring Method: Install cables in j-hooks, raceways and cable trays. Conceal raceway and cables, except in unfinished spaces.
1. Install plenum cable in environmental air spaces, including plenum ceilings.
C. Wiring within Enclosures: Bundle, lace, and train cables within enclosures. Connect to terminal points with no excess and without exceeding manufacturer's limitations on bending radii.
Provide and use lacing bars and distribution spools. Install conductors parallel with or at right angles to sides and back of enclosure.
D. General Requirements for Cabling:
1. Comply with TIA-568.1-E.
2. Install 110-style IDC termination hardware unless otherwise indicated.
3. Do not untwist twisted pair cables more than 1/2 inch from the point of termination to maintain cable geometry.
4. Terminate all conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels.
5. Cables may not be spliced. Secure and support cables at intervals not exceeding 48” and not more than 6 inches from cabinets, boxes, fittings, outlets, racks, frames, and terminals.
6. Install lacing bars to restrain cables, prevent straining connections, and prevent bending cables to smaller radii than minimums recommended by manufacturer.
Section 27 1513 Communications Copper Horizontal Cabling 6 of 6
7. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii. Use hook and loop Velcro for all cable bundling.
8. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation, and replace it with new cable.
9. Cold-Weather Installation: Bring cable to room temperature before dereeling. Heat lamps shall not be used for heating.
10. In the telecommunications room, install a 10’ long service loop. At the work area outlet, install a 12” long service loop.
E. Separation from EMI Sources:
1. Comply with recommendations from BICSI's "Telecommunications Distribution Methods
Manual" and TIA-569-E for separating unshielded copper communication cable from potential EMI sources, including electrical power lines and equipment.
3.2 FIRESTOPPING
A. Comply with TIA-569-E.
3.3 GROUNDING
A. Comply with TIA-607-D.
B. Locate grounding bus bar to minimize the length of bonding conductors. Fasten to wall, allowing at least a 2-inch clearance behind the grounding bus bar. Connect grounding bus bar to suitable electrical building ground, using a minimum No. 6 AWG grounding electrode conductor.
C. Bond metallic equipment to the grounding bus bar, using not smaller than a No. 6 AWG equipment grounding conductor.
D. Bonding busbar shall be 12” x 4” x 1/4”.
3.4 IDENTIFICATION
A. Cable and Wire Identification:
1. Label each cable within 2” of each termination with a mechanically generated label.
2. Label each patch panel, patch panel port, and each faceplate port with a mechanically generated label.
3. Labels shall be preprinted or computer-printed type, with a printing area and font color that contrast with cable jacket color but still comply with TIA-606-D.
a. Provide vinyl substrate with white printing area and a clear 'tail' that self laminates the printed area when wrapped around the printed area. If cable is white in color, a different color shall be used.
3.5 FIELD QUALITY CONTROL
A. Perform tests per section 271700.
END OF SECTION 27 1513