Attachment 2_Drawings Full Set.pdf
PDF 12 MB Posted
- Solicitation number
- 1240LU26Q0111
- Issued by
-
Department of Agriculture Forest Service
About this file
These are the 100% Construction Documents for the Building 24 Basement Remodel project located at 26 Fort Missoula Road, Missoula, Montana 59804, prepared by Mosaic Architecture P.C. The documents include comprehensive architectural, mechanical, plumbing, electrical, and ICT (Information and Communications Technology) specifications and drawings for a basement renovation serving as office space for the U.S. Forest Service.
The project is divided into separate East Wing and West Wing bid packages. Key scope includes demolition of existing systems, new wall construction with fire-rated partitions, suspended ceiling systems with seismic bracing, LED lighting with occupancy sensors and daylight harvesting controls, HVAC modifications with finned-tube radiators and hydronic piping, plumbing fixtures installation, electrical power and lighting distribution, fire alarm system integration, and structured cabling infrastructure with Category 6A twisted-pair copper horizontal cabling and work area outlets. The mechanical systems operate at 3,150-foot elevation with heating hot water at 170°F. All work must comply with the 2021 International Building Code and associated standards. Contractor qualifications include licensing by the State of Montana for electrical work, manufacturer certification for cabling installation with a minimum 25-year performance warranty, and NICET Level 4 design/Level 2 installation for fire alarm systems. Testing and commissioning requirements are extensive, including 100% field certification testing of all cabling links with Level IV accuracy testers and comprehensive documentation of results prior to project acceptance.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
@ at A.B. anchor bolt A/C air conditioning ACC PNL access panel ACOUST acoustical ACT acoustical ceiling tile AD area drain ADJ adjacent AFF above finished floor AIB air infiltration barrier ALT alternate ALUM aluminum ANOD anodized APPROX approximate ARCH architect AUTO automatic BBD bulletin board BD board BITUM bituminuous BL building line BLDG building BLK block BLKG blocking BM beam/bench mark BO by CONTRACTING OFFICER B.O. bottom of BOT bottom BRG bearing BSBD baseboard BTWN between B.O.W. bottom of wall BU built up CAB cabinet CAP capacity CB catch basin CL centerline C.C. center to center CDX exterior grade plywood CG corner guard CH channel CI cast iron/cubic inches CJ control joint CLG ceiling C.L.L. contract limit line CL center line
ABBREVIATIONS:
GA gauge GB grab bar GALV galvanized G.C. general contractor GEN general GFRG glass fiber reinforced gypsum GI galvanized iron GL glass GLU LAM or G.L.B. glue laminated beam GRD grade/grid GWB gypsum wall board GYP gypsum HB hose bib HC hollow core/handicapped HD BD Hard board HDR header HOR horizontal HR hour HT height HTG heating HVAC heating, ventilation, air conditioning HW hot water
PART.BD.particle board PART’N partition PC precast concrete PFM prefinished metal PL plate P.LAM plastic laminate PLWD plywood PNL panel PR pair PSL parallel strand lumber PT point PTD paper towel dispenser
T tread/thermostat TB towel bar TEL telephone TEMP temperature T&G tongue and groove THK thick THRU through TJI Truss Joist Incorporated
CLR clear CMU concrete masonry unit
CO CONTRACTING OFFICER
COL column CONC concrete COND condition CONF conference CONN connection CONST construction CTRD centered CONT continuous CONTR contractor CORR corridor CPT carpet CT ceramic tile CUH cabinet unit heater CW curtain wall system CY cubic yard DBL double DEPT department DF drinking fountain DIA diameter DIAG diagonal DIM dimension DISP dispenser DN down DR door DWR drawer DS downspout DTL detail DWG drawing E east EA each EIFS exterior insulation finish system E.J. expansion joint EL/ELEV elevation - height/elevator ELEC electrical ENCL enclosure EO electrical outlet EP electrical panel EQ equal EQUIP equipment EWA/EW exterior wall assembly EWC electrical water cooler EWH electrical water heater (E)/EXISTexisting EXH exhaust EXP expansion EXT exterior
IN inch INCL included INFO information INSUL insulation INT interior IWA/IW interior wall assembly
T.O. top of T.O.B. top of beam T.O.C. top of concrete T.O.P. top of plate T.O. FTG top of footing T.O.S. top of steel T.O.SL. top of slab T.O.W. top of wall TPD toilet paper dispenser TR tread TS tubular steel TV television TYP typical UG underground UNO unless noted otherwise UR urinal VAC vacuum outlet VAR varies VB vapor barrier VCT vinyl composition tile VERT vertical VEST vestibule VFY verify VT vinyl tile VWC vinyl wall covering W west/women/width W/ with W/O without WC water closet WD wood W/D washer/dryer WH water heater WNDW window WP waterproof WR water resistant WRB weather resistive barrier WT weight WWF welded wire fabric WWM welded wire mesh X by YD yard
REINF reinforcing REQD required RES resilient RM room RO rough opening RV roof vent R&S rod and shelf S south SACT suspended acoustical ceiling tile SC solid core SCD seat cover dispenser SCHED schedule SD soap dispenser SECT section SF square feet SGL single SHT sheet SHTG sheathing SHWR shower SIM. similar S.I.P. structural insulated panel SLNT sealant SOG slab on grade SPEC specifications S.S. stainless steel SS service sink SSM solid surface material STD standard STF storefront STL steel STOR storage STRUCT structural SUBFLR subfloor SUSP suspended SV sheet vinyl SY square yard
M men's MAT material MAX maximum MECH mechanical MDF medium density fiber board MEMB membrane MEZZ mezzanine MFR manufacturer MH manhole MIN minimum MIR mirror MISC miscellaneous MO masonry opening MTL metal MULL mullion N north NA not applicable NIC not in contract NO number NTS not to scale
OFCI CONTRACTING OFFICER
furnished/contractor installed OC on center OD outside diameter OH overhead/opposite hand OPNG opening OPP opposite
FLR/FL floor FLUOR fluorescent FND feminine napkin dispenser/disposal FOC face of concrete FOF face of finish FOS face of stud FOW face of wall FT foot or feet FTG footing
QTY quantity R/RAD radius R riser RA roof/ceiling assembly RB rubber base RD roof drain RE regarding REF reference/refrigerator
JAN janitor JST joist JT joint LAV lavatory LF lineal foot LTG lighting
FA fire alarm/floor-ceiling assembly FAH fire alarm horn FAS fire alarm station FD floor drain FDN/FND foundation FE fire extinguisher FEC fire extinguisher cabinet FF finished floor FFHB frost free hose bib FG finish grade FH fire hydrant FIN. FLR top of floor sheathing FIN finish FIXT fixture F.O. face of
PTD/R paper towel dispenser/receptacle PVMT pavement PVC polyvinylchloride
SCALE
BUILDING SECTIONS
WALL SECTIONS
EXTERIOR ELEVATION
DETAIL CALLOUT
INTERIOR ELEVATION
DOOR NUMBER
WINDOW TYPE
ROOM NAME, NUMBER, AND
AREA
GRID LINES:
LETTERS LEFT TO RIGHT
NUMBERS TOP TO BOTTOM
WALL TYPE
ELEVATION TAG, FLOOR = 100' - 0"
REFERENCE SYMBOLS:
DRAWING TITLE
STOREFRONT/CURTAINWALL
CALLOUT
TEXT INDICATES STOREFRONT
SYSTEM:
iSF = INTERIOR STOREFRONT
SF = EXTERIOR STOREFRONT
CW = CURTAINWALL
FIRE EXTINGUISHER, SEE CODE
PLANS
SHEET
NUMBER
DRAWING
NUMBER
SHEET
NUMBER
DRAWING
NUMBER
SHEET NUMBER
DRAWING
NUMBER
SHEET NUMBER
DRAWING
NUMBER
SHEET NUMBER
DRAWING NUMBER
FE
WITH CABINET
WALL-HUNG, NO
CABINET
ROOF TYPE
-SEE ELEVATIONS FOR HEIGHTS
"SIM" INDICATES SIMILAR
CONDITION; SEE NOTES
FLOOR TYPE
A7-14
A3-8
A5-2
23 VIEW NAME
1/8" = 1'-0"
A
Room name
A
101A
A1-1
A1-1
FA1
Name Elevation
RA1
SIM
cw1 i1
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING DIMENSIONS & CONDITIONS. EXISTING DIMENSIONS SHOWN ARE APPROXIMATE AND MUST BE FIELD VERIFIED.
REFER TO SPECIFICATIONS FOR DETAILED DESCRIPTIONS & REQUIREMENTS OF CONSTRUCTION.
GENERAL CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES, PROVIDE ON-SITE SUPERVISION & BE RESPONSIBLE FOR COMPLIANCE WITH ALL SAFETY PRECAUTIONS, CODES AND REGULATIONS.
PROTECT EXISTING UTILITIES, SITE IMPROVEMENTS & PLANTING TO REMAIN.
PATCH ANY SURFACES DAMAGED DURING CONSTRUCTION. SURFACES ARE TO BE PATCHED FLUSH WITH EXISTING. MATCH EXISTING ADJACENT FINISH OR APPLY NEW FINISH AS SCHEDULED.
PROVIDE SOLID BACKING FOR ALL WALL-MOUNTED ITEMS.
IN GENERAL, REPETITIVE DETAILS DRAWN ARE SHOWN IN FULL ONLY ONCE. REPETITIONS MAY NOT BE COMPLETE IN EVERY DETAIL AS SHOWN IN THE ORIGINAL DETAIL.
DIMENSIONS ARE SHOWN ON THE DRAWINGS. DO NOT SCALE THE DRAWINGS.
ALL HEIGHTS ARE DIMENSIONED FROM THE TOP OF FINISH FLOOR UNLESS NOTED OTHERWISE.
WHERE COLUMNS & STUD WALLS ALIGN, GYPSUM BOARD TO BE CONTINUOUS OVER COLUMNS OR BOXED AROUND COLUMN IF COLUMN PROJECTS BEYOND WALL.
BRING TO THE ATTENTION OF THE ARCHITECT/CONTRACTING OFFICER ANY CONDITION OR AREA OF FINISH THAT IS IN QUESTION OR NOT NOTED.
SEAL ALL PENETRATIONS OF WALLS, FLOORS AND CEILINGS WITH A FIRE RATING EQUIVALENT TO THE CONSTRUCTION PENETRATED AND PER DETAILS & SPECIFICATIONS.
DUST BARRIERS MUST BE INSTALLED WHEREVER NEW WORK IS ADJACENT TO OCCUPIED AREAS. BARRIERS MUST BE SEALED TO INSURE NO DUST TRANSMISSION TO OCCUPIED SPACES.
COORDINATE LAYOUT, CLEARANCES, PENETRATIONS, BACKING & FASTENERS WITH WORK TO FOLLOW.
HEATING, PLUMBING AND ELECTRICAL PLANS WHERE SHOWN DIAGRAMMATICALLY ARE INTENDED TO INDICATE CAPACITY, SIZE, LOCATION & GENERAL ARRANGEMENTS. ALL NECESSARY FEATURES OF RELATED CONSTRUCTION WILL BE
REQUIRED AS IF SHOWN IN DETAIL.
WHERE MECHANICAL & ELECTRICAL EQUIPMENT LOCATIONS CONFLICT ELECTRICAL, LIGHT FIXTURE LOCATIONS SHALL TAKE PRECEDENCE.
PROVIDE SUFFICIENT STUD DEPTH TO CONCEAL MECHANICAL & ELECTRICAL WORK IN WALLS.
PROVIDE ALL NEW MATERIALS (U.N.O.) AND QUALIFIED CRAFT PERSONS TO COMPLETE THE WORK.
CONSTRUCTION DOCUMENTS SHOW THE DESIGN INTENT OF THE PROJECT AND MAY NOT SHOW MINOR DETAILS OF PROPOSED INSTALLATIONS. THE INCLUSION OF THESE MINOR DETAILS IS IMPLIED TO PROVIDE A COMPLETE PROJECT
AND ARE TO BE INCLUDED AS A PART OF A BID.
REFER TO MECHANICAL & ELECTRICAL DRAWINGS FOR COORDINATION OF WORK.
IN THE CASE OF CONTRADICTIONS BETWEEN DRAWINGS OR BETWEEN DRAWINGS & SPECIFICATIONS, ASSUME THE MORE COSTLY APPROACH FOR BIDDING PURPOSES. BRING ALL CONTRADICTIONS TO THE ATTENTION OF THE
ARCHITECT/CONTRACTING OFFICER.
CONTRACTOR SHALL PROMPTLY REMOVE ALL WASTE MATERIALS AND LEAVE PREMISES AND SITE CLEAN.
THE CONTRACTOR SHALL PROVIDE ALL CEILING AND/OR WALL ACCESS PANELS/DOORS AS REQUIRED BY THE AIR CONDITIONING, PLUMBING & ELECTRICAL SYSTEMS, PROVIDE APPROVED ASSEMBLIES W/ SELF-CLOSING DEVICES IN
RATED CONSTRUCTION. (PAINT TO MATCH ADJACENT WALL COLOR)
ELECTRICAL OUTLETS AND LIGHTING ARE ONLY SHOWN ON ARCHITECTURAL "A" SHEETS WHERE PLACEMENT OF SUCH IS CRITICAL TO PARTICULAR AESTHETICS. SEE ELECTRICAL DRAWINGS FOR ALL ELECTRICAL AND DATA FEATURES.
DRAWING SET NOTE: THESE DRAWINGS ARE TO BE UTILIZED AS A COMPLETE SET FOR BIDDING & CONSTRUCTION. INDIVIDUAL SECTIONS OF DRAWINGS SHOULD NOT BE SEPARATED FROM THE ENTIRE SET. IMPORTANT NOTES FOR ONE AREA OF WORK MAY BE INCLUDED IN OTHER AREAS IN THE DRAWINGS. ALL CONTRACTORS & SUPPLIERS MUST REVIEW ENTIRE DRAWING SET & SPECIFICATIONS.
GENERAL NOTES:
DATE:
SHEET:
317 N. Cruse Ave., Suite 201 Helena, Montana 59601 406.449.2013phone www.mosaicarch.com
D
AT
E
ST
AM
P:
a r c h i t e c t u r e - p l a n n i n g -d e s i g n
7/
/2
2:
:1
PM
05.19.2026
AD-000
COVER
26 FORT MISSOULA RD, MISSOULA,
MT
BUILDING 24
REMODEL
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
BUILDING 24 - BASEMENT REMODEL
24 H RD.
MISSOULA, MT 59804
MOSAIC ARCHITECTURE, P.C.
317 CRUSE AVE., SUITE 201
HELENA, MT 59601
(406) 449-2013 CONTACT: KATIE BRODOWY, AIA katie@mosaicarch.com
ARCHITECT:ARCHITECT:
THESE DRAWINGS WERE PREPARED BY MOSAIC ARCHITECTURE, P.C. FOR CONSTRUCTION OF THE PROJECT DESCRIBED HEREIN. AS SUCH, THE DOCUMENTS ARE THE PROPERTY OF MOSAIC ARCHITECTURE, P.C. & MAY NOT BE REPRODUCED, COPIED OR USED IN ANY WAY WITHOUT PRIOR APPROVAL FROM MOSAIC ARCHITECTURE, P.C.
SHEET INDEX
PROJECT DIRECTORY
VICINITY MAP
PROJECT SITE
ARCHITECTURAL DRAWINGS
AD-000 COVER
AD-001 CODE INFORMATION & TYP. ASSEMBLIES
AD-101 DEMOLITION PLAN - BASEMENT
AD-102 FLOOR PLAN & RCP - BASEMENT
AD-701 FINISH PLAN & SCHEDULE- BASEMENT
MECHANICAL/PLUMBING ENGINEERING:
MORRISON MAIERLE
1055 Mount Avenue
MISSOULA MT 59801
(406) 751-5867 CONTACT: CHANDRA MCCARTHY , PE CMCCARTHY@m-m.net
ELECTRICAL/ICT ENGINEERING:
CONTACT: GARTH STEVENS, PE gstevens@m-m.net CONTACT: PAUL HEFFERNAN, PE pheffernan@m-m.net
MORRISON MAIERLE
1055 Mount Avenue
MISSOULA MT 59801
(406) 751-5867
EAST APPROACH
PLUMBING DRAWINGS
P001 PLUMBING LEGEND AND NOTES
P002 PLUMBING SPECIFICATIONS, SCHEDULES & DETAILS
P101 PLUMBING DEMO PLAN - BASEMENT
P201 PLUMBING FLOOR PLAN - BASEMENT
MECHANICAL DRAWINGS
M001 MECHANICAL LEGEND & NOTES
M002 MECHANICAL SPECIFICATIONS, SCHEDULES & DETAILS
M101 MECHANICAL DEMO PLAN - BASEMENT
M201 MECHANICAL FLOOR PLAN - BASEMENT
ELECTRICAL DRAWINGS
E0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E0.2 ELECTRICAL SPECIFICATIONS
E0.3 ELECTRICAL SPECIFICATIONS
E0.4 ELECTRICAL DETAILS
E0.5 ELECTRICAL SCHEDULES
E101 ELECTRICAL DEMO PLAN
E102 ELECTRICAL BASEMENT PLAN- POWER AND SIGNAL
E103 ELECTRICAL BASEMENT PLAN- LIGHTING
ICT DRAWINGS
T001 ICT SYMBOLS AND ABBREVIATIONS
T002 ICT DETAILS
T003 ICT SPECIFICATIONS
T004 ICT SPECIFICATIONS
T101 ICT BASEMENT DEMO PLAN
T102 ICT BASEMENT PLAN
PROJECT TO BE SPLIT INTO SEPARATE AREAS, THE PROJECT EAST WING AND PROJECT WEST
WING WILL BE BID SEPARATELY.
CONTRACTING OFFICER:
CONTACT: TANNER GRIMSTAD, FS TANNER.GRIMSTAD@USDA.GOV
US FOREST SERVICE
24 H RD.
MISSOULA, MT 59804
# DATE REVISION
NONRATED WALL: WITH NO OPENING PROTECTION REQUIRED AT DOORS,
WINDOWS, DUCTS, PENETRATIONS, AND JOINTS UON. SEE WALL TYPES.
EXIT SIGN W/ INTEGRATED DIRECTIONAL ARROW WHERE OCCURS AT ALL
EXITS, EVERY 100' IN CORRIDORS, AND IN SPACES WHERE 2 MEANS OF
EGRESS ARE REQUIRED PER S §1006. SEE ELECTRICAL DRAWINGS. (W/
POCHE IN QUADRANT INDICATING "EXIT" TEXT SIDE OF SIGN.) SIGNS
SHOWN IN CORRIDORS ARE CEILING HUNG. SIGNS SHOWN ON WALL ARE
WALL HUNG.
1-HOUR FIRE WALL, FIRE BARRIER, FIRE PARTITION, OR SMOKE BARRIER
WALL: OR COMBINATION OF (WHERE OCCURS) CONFORMING TO THE MOST
STRINGENT REQUIREMENTS OF EACH. SEE CODE ANALYSIS PLANS FOR
SPECIFIC NAMES OF IBC WALL DESIGNATIONS. ALL WITH FIRE-RESISTIVE
OPENING PROTECTION AT DOORS, WINDOWS, DUCTS (WITH EXCEPTIONS),
PENETRATIONS, AND PROTECTION AT JOINTS. SEE WALL TYPES, DOOR AND
WINDOW SCHEDULES, MECHANICAL DRAWINGS, PENETRATION DETAILS, AND
JOINT DETAILS WHERE APPLICABLE.
2-HOUR FIRE WALL OR FIRE BARRIER: OR COMBINATION OF (WHERE
OCCURS) CONFORMING TO THE MOST STRINGENT REQUIREMENTS OF EACH.
SEE CODE ANALYSIS PLANS FOR SPECIFIC NAMES OF IBC WALL
DESIGNATIONS. ALL WITH FIRE-RESISTIVE OPENING PROTECTION AT
DOORS, WINDOWS, DUCTS (WITH EXCEPTIONS), PENETRATIONS, AND
PROTECTION AT JOINTS. SEE WALL TYPES, DOOR AND WINDOW
SCHEDULES, MECHANICAL DRAWINGS, PENETRATION DETAILS, AND JOINT
DETAILS WHERE APPLICABLE.
PORTABLE CLASS ABC FIRE EXTINGUISHER IN ADA-COMPLIANT SEMI-
RECESSED CABINET
FE
Wmin MINIMUM EGRESS WIDTH (INCHES) BASED ON ACCUMULATIVE NUMBER OF
OCCUPANTS SERVED AT INDICATED EGRESS COMPONENT, PER SECTION
1005.3: .3 INCHES/OCC FOR STAIRWAYS(NONSPRINKLERED BUILDINGS); .2
INCHES/OCC FOR OTHER EGRESS COMPONENTS (NONSPRINKLERED BLDGS).
MOER:2 MEANS OF EGRESS REQUIRED (QUANTITY). ONLY DESIGNATED WHERE
(2) MEANS OF EGRESS ARE REQUIRED, PER §1006.2.1.
IU INCIDENTAL USE W/ REQUIRED SEPARATION PER TABLE 509.1. SHALL NOT
OCCUPY >10% OF FLOOR AREA OF STORY IN WHICH LOCATED, AND IS
CALCULATED AS PART OF OCCUPANCY IN WHICH IT IS LOCATED.
ACCESSORY OCCUPANCY AREA: W/ NO SEPARATION REQUIRED AND
CALCULATED AS PART OF MAIN OCCUPANCY IF TOTAL ACCESSORY
OCCUPANCIES WITHIN A STORY OCCUPY LESS THAN 10% OF AREA OF THAT
STORY, PER SECTION 508.2.3.
CODE PLAN LEGEND
OCCUPANCY GROUP B AREA
EXIT ACCESS TRAVEL DISTANCE (E.A.T.D.) - MAXIMUM 200' FOR 'B'
OCCUPANCY W/OUT SPRINKLER SYSTEM, PER TABLE 1017.2. MAXIMUM
DISTANCE FOR EACH STORY SHOWN.
COMMON PATH OF EGRESS TRAVEL (C.P.E.T.) - MAXIMUM 75' FOR 'B'
OCCUPANCY W/OUT SPRINKLER SYSTEM, OCC LOAD >30, PER TABLE 1006.2.1.
ROOM AREA
OCCUPANT
LOAD
MAX. FLOOR
AREA PER
OCCUPANT
FROM TABLE
1004.5
SF
ROOM NAME
OCCUPANT LOADS FOR FUNCTIONS DESIGNATED NET
FLOOR AREA IN TABLE 1004.5 ARE IDENTIFIED FOR
ACTUAL OCCUPIED AREAS.
OCCUPANT LOADS FOR FUNCTIONS DESIGNATED GROSS
FLOOR AREA ARE IDENTIFIED FOR ENTIRE AREA OF THE
FUNCTION W/ DEDUCTIONS ONLY FOR AREA OF
EXTERIOR WALLS, VENT SHAFTS AND INTERIOR COURTS.
AO
OCCUPANCY GROUP B WITH ACCESSORY SMALL ASSEMBLY SPACE WITH
OCCUPANT LOAD <50 OR AREA <750 SF, CLASSIFIED AS PART OF GROUP B
OCCUPANCY PER 303.1.2
REQUIRED EXIT AND EXIT EGRESS DIRECTION WITH ACCUMULATIVE
NUMBER OF OCCUPANTS SERVED. (DESIGNATED WHERE (2) MEANS OF
EGRESS ARE REQUIRED PER TABLE §1006.2.1)
OCCUPANCY GROUPS:
(CHAPTER 3)
B - BUSINESS
ACCESSORY OCCUPANCIES PER SEC. 508.2 WHERE OCCUR.
INCIDENTAL USES PER TABLE 509 WHERE OCCUR.
NONSEPARATED OCCUPANCIES:
(SEC. 508.3.2)
CONSTRUCTION TYPE:
(TABLE 601)
TYPE IIIB, SPRINKLERED
ALLOWABLE FLOOR AREA (At):
(TABLE 506.2)
B: 57,000 SF
ALLOWABLE FLOOR AREA:
SINGLE OCCUPANCY
MULTISTORY BLDG: (Aa)
(SEC. 506.2.1)
S-1:
ALLOWABLE NO. OF STORIES / HEIGHT:
(TABLE 504.4/504.3)
B:
3 STORIES / 55 FT
OCCUPANT LOAD : BUSINESS AREAS: 28 occu
SEE CODE ANALYSIS PLANS THIS SHEET.
SUMMARY CODE REVIEW
PROJECT DESCRIPTION: REMODEL EXISTING OFFICE SPACE FOR UPDATED OFFICE NEEDS,
OCCUPANCY USE AND TYPE DOES NOT CHANGE.
ACTUAL NO. OF STORIES / HEIGHT: 2 STORY / 43 FT; OK
OCCUPANT LOADS FOR EGRESS DESIGN:
(SEC. 1004 + TABLE 1004.5)
ASSEMBLY - UNCONCENTRATED 15 NET
BUSINESS: 150 GROSS
STORAGE/MECHANICAL EQUIPMENT 300 GROSS
SEE CODE ANALYSIS PLAN. OCCUPANT LOADS BASED ON MAX. FLOOR
AREA IN SQ FT PER OCCUPANT FROM TABLE 1004.5:
EGRESS WIDTH PER OCCUPANT SERVED:
(SEC. 1005.3)
STAIRWAYS:
OTHER EGRESS
COMPONENTS:
0.3 INCHES / OCCUPANT
0.2 INCHES / OCCUPANT
INTERIOR FINISH REQUIREMENTS:
(TABLE 803.13)
INTERIOR EXIT STAIRWAYS, EXIT RAMPS & EXIT PASSAGEWAYS: CLASS A.
CORRIDORS & ENCLOSURE FOR EXIT ACCESS STAIRWAYS & EXIT ACCESS RAMPS: CLASS B.
ROOMS AND ENCLOSED SPACES: CLASS C
THIS MIXED OCCUPANCY BUILDING INCORPORATES NONSEPARATED
OCCUPANCIES. NO OCCUPANCY SEPARATIONS ARE PROVIDED, AND
THE ALLOWABLE AREA AND HEIGHT OF THE BUILDING IS BASED ON
THE REQUIREMENTS OF THE MOST RESTRICTIVE OCCUPANCY.
Aa = [At + (NS x If)] x Sa Aa = 57,000 + [57,000 x .75] x 4 Aa = 228,000 SF
ACTUAL FLOOR AREA: BASEMENT: 14,240 SF
1-2 LEVELS: 28,480 SF
42,720 SF < 228,000 SF ALLOWABLE; OK
EXSTING:
44" AT STAIRWAYS (36" WHERE OCC LOAD < 50) [IBC §1011.2];
32" CLEAR AT DOORS [§1010.1.1],
44" AT CORRIDORS, AISLES & EXIT PASSAGEWAYS (36" for occupant load
<50) [§ 1020.2; 1018.3, 1018.5; 1024.2 RESPECTIVELY], PROVIDED.
EGRESS WIDTH MINIMUMS BY
COMPONENT (USE WHERE EXCEED
MINIMUMS BY OCCUPANT LOAD):
CORRIDOR FIRE RESISTANCE RATING:
(TABLE 1020.2)
B OCCUPANCY, OCC LOAD >30: 0-HOUR (SPRINKLERED)
FRONTAGE INCREASE (If) :
(TABLE 506.3.3)
>30' OPEN SPACE FOR 100% OF BLDG PERIMETER:
If = .75
TOTAL OCCUPANTS: 28 occu
EXIT ACCESS TRAVEL:
(TABLE 1017.2)
B- 300' SPRINKLERED
THIS PROJECT SHALL COMPLY WITH THE LATEST EDITION OF CODES ADOPTED BY THE STATE
OF MONTANA:
2021 International Building Code (IBC) 2021 International Mechanical Code (IMC) 2021 International Fuel Gas Code (IFGC) 2021 Uniform Plumbing Code (IAMPO) 2020 National Electrical Code (NEC) 2012 International Fire Code (IFC) 2021 International Energy Conservation Code (IECC)
APPLICABLE BUILDING CODES
IECC COMPLIANCE FOR COMMERCIAL PROJECTS
CLIMATE ZONE: 6
INSULATION REQUIREMENTS - IECC 2021 TABLE C402.1.3/C402.4 AND MT AMENDMENTS
ROOFS R-30 CONTINUOUS ABOVE DECK, R-49 AT ATTICS
METAL FRAMED WALLS, ABOVE GRADE R-13 CAVITY + R-12.5 CONTINUOUS
WOOD FRAMED WALLS, ABOVE GRADE R-13 CAVITY + R-7.5 CONTINUOUS OR R-20 + R-3.8 CONTINUOUS
MASS WALLS, ABOVE GRADE: R-15.2 CONTINUOUS
BELOW GRADE WALLS: R-15 CONTINUOUS
FLOORS - JOIST/FRAMING: R-38 (R-38 FOR STEEL FLOOR JOISTS)
UN-HEATED SLAB: R-20 VERTICAL FOR 48" BELOW (FULL HEIGHT OF THICKENED SLAB EDGE)
HEATED SLAB: R-15 FOR 36" BELOW + R-5 FULL SLAB
OPAQUE SWINGING DOORS: U-0.37
SKYLIGHT U-FACTOR: 0.50, MAXIMUM
FIXED FENESTRATION U-FACTOR: 0.34, MAXIMUM
OPERABLE FENESTRATION U FACTOR 0.42 MAXIMUM
ENTRANCE DOOR: 0.63, MAXIMUM
SHGC 0.41 WITH ADJUSTMENT FOR PROJECTION FACTOR >.2
INSULATION TO BE PROVIDED - REQUIREMENTS IN OTHER AREAS OF DRAWINGS OR SPECIFICATIONS TAKE
PRECEDENCE OVER THE FOLLOWING REQUIREMENTS:
ROOFS R-30 BLOWN-IN ATTIC INSULATION
WOOD FRAMED WALLS: R-21 CAVITY + R3.8 CONTINUOUS
UNHEATED SLAB: R-10 VERTICAL FOR 24" BELOW (FULL HEIGHT OF THICKENED SLAB EDGE)
OPAQUE SWINGING DOORS: U-0.37
ROLL UP OR SLIDING DOORS R-4.75
FENESTRATION U-FACTOR (FIXED): 0.34 MAXIMUM
FENESTRATION U-FACTOR (OPERABLE): 0.42, MAXIMUM
ENTRANCE DOOR: 0.63, MAXIMUM
SHGC 0.40 WITH PROJECTION FACTOR <.2
REQUIRED SPECIAL INSPECTIONS:
IN ADDITION TO REGULAR INSPECTIONS, THE FOLLOWING ITEMS WILL ALSO REQUIRE SPECIAL INSPECTIONS AND TESTING IN ACCORDANCE WITH SECTIONS 1704 AND 1705 OF THE 2018 INTERNATIONAL BUILDING CODE.
SEE STRUCTURAL FOR SPECIFIC REQUIREMENTS. COPIES OF 3RD PARTY REPORTS TO BE SENT TO
BUILDING DEPARTMENT & COPIES KEPT ON-SITE FOR INSPECTOR REVIEW.
a) SPECIAL INSPECTIONS:
- INSPECTION OF FABRICATORS (1704.2.5)
- STEEL CONSTRUCTION (1705.2)
- CONCRETE CONSTRUCTION (1705.3)
- MASONRY CONSTRUCTION (1705.4)
- WOOD CONSTRUCTION (1705.5)
- SOILS (1705.6)
- SPECIAL CASES (1705.1.1)
EPOXY SET ANCHORS
POWDER-ACTUATED FASTENERS
CONCRETE EXPANSION ANCHORS
b) SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE (1705.12):
- STRUCTURAL STEEL (1705.12.1)
- STRUCTURAL WOOD (1705.12.2)
- COLD-FORMED STEEL LIGHT-FRAME CONSTRUCTION (1705.12.3)
KKGG
JJ
FFDD
II
EECCBBAA
HH
GROSS
2406 SF
17150
GROSS
1589 SF
11150
NEW FURR-OUT
COLUMN DETAIL
5/8" GYPSUM
(E) 6 5/8" STEEL COLUMN
2x4 BACKING STUD
INTERIOR PARTITION
NON-RATED SOUND WALL
f1 GENERAL WALL NOTES 1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
WALL TYPE CONSTRUCTION IS CONTINUOUS FROM SLAB TO ROOF FRAMING ABOVE UNLESS INDICATED
OTHERWISE.
IF A WALL TYPE IS NOT INDICATED, PROVIDE WALL TYPE OF MOST SIMILAR CONDITION - VERIFY WITH CO/
ARCHITECT.
IN CASES OF CONFLICT BETWEEN SECTIONS AND WALL TYPES, CLARIFY WITH ARCHITECT PRIOR TO BIDDING WHEN TIME ALLOWS, OTHERWISE ASSUME THE MOST EXPENSIVE CONDITION FOR BIDDING PURPOSES.
STRUCTURAL NOTES, SPECIFICATIONS, STUD GAUGE NOTATIONS ETC. TAKE PRECEDENCE OVER
ARCHITECTURAL WALL TYPES.
FOR LIGHT GAUGE (NON-STRUCTURAL) METAL FRAMING, PROVIDE MIN. 22 GAUGE STUDS UNLESS THE CONTRACTOR CAN PROVIDE MANUFACTURER'S DATA SUPPORTING LIGHTER GAUGE STUDS BASED ON HEIGHT
AND FINISH MATERIALS.
ALL VOIDS IN EXTERIOR WALLS - INCLUDING IN NON-VISIBLE LOCATIONS - TO BE FILLED TIGHT WITH
INSULATION. SMALL CRACKS & VOIDS TO BE CAULKED OR SPRAY-FOAMED FOR TIGHT SEAL.
ALL EXTERIOR WALLS TO RECEIVE VAPOR BARRIER UNDER INTERIOR FINISH. ALL SEAMS OF VAPOR BARRIER MUST BE TAPED/SEALED TIGHT AND ALL JOINTS MUST BE TAPED/ SEALED TIGHT WITH MATERIALS AND
METHODS APPROVED BY VAPOR BARRIER MFR.
TYPE "X" GYPSUM WALL BOARD SPECIFIED THROUGHOUT. PROVIDE WATER-RESISTANT TYPE "X" GYPSUM BOARD ON ENTIRE WALL WHERE PLUMBING FIXTURES OCCUR. PROVIDE TILE BACKER BOARD TYPE "X" ON ALL
WALLS WITH TILE.
WALLS INDICATED WITH ACOUSTICAL INSULATION TO MEET AN STC RATING OF 48 OR MORE, UNLESS
OTHERWISE INDICATED.
PROVIDE SOUND ATTENUATION INSULATION ON TOP OF ACT WHERE WALLS TERMINATE AT CEILING OR 6" ABOVE CEILING. EXTEND 5 FEET TO BOTH SIDES OF WALL. HOLD INSULATION 7" AWAY FROM LIGHT FIXTURES.
PROVIDE BACKER ROD & CAULKING JOINT AT ABUTMENT OF ALL DISSIMILAR MATERIALS.
PROVIDE STEEL "J" EDGE METAL AND 1/4" CAULK JOINT AT PERIMETER OF ALL GYPSUM BOARD WALLS WHERE
ABUTTING DIFFERENT MATERIALS.
PROVIDE CORNER BEADS AT ALL EXTERNAL GYPSUM BOARD CORNERS.
PENETRATIONS OF FIRE-RESISTIVE WALLS, HORIZONTAL ASSEMBLIES SHALL BE PROTECTED AS REQUIRED IN
IBC SECTION 714.
PROVIDE FIRE, SMOKE AND CEILING RADIATION DAMPERS AT DUCT PENETRATIONS AND AIR TRANSFER
OPENINGS IN FIRE RATED ASSEMBLIES PER IBC SECTION 717.
NOTE: SEE ELEVATIONS AND FINISH SCHEDULES FOR
WALL FINISHES, TYPICAL ALL WALL TYPESINTERIOR WALL TYPES
INTERIOR PARTITION INTERIOR PARTITION
NON-RATED NON-RATED
5/8" GYPSUM
BOARD
2x4 STUDS @ 16" O.C.
5/8" GYPSUM
BOARD
5/8" GYPSUM
BOARD
2x6 STUDS @ 16" OC
5/8" GYPSUM
BOARD
i1 i2
SUSPENDED CEILING
ACOUSTIC INSULATION
WHERE OCCURS - SEE WALL
TYPE
PROVIDE SEALANT @ BASE OF
ALL WALLS W/ ACOUSTIC
INSUL.
WALL TYPE PER PLANS
STRUCTURE
6"
ATTACH TO STRUCTURE W/ 3/8"Ø
EXPANSION ANCHORS @ CONCRETE OR
3/8"Ø X 3" LAG BOLTS @ WOOD
PARTITION WALL TO STRUCTURE
INTERIOR PARTITION
NON-RATED SOUND WALL
FINISH FLOOR
NEW WALLS TO
HAVE BASETRIM TO
MATCH EXISTING-
VERIFY DIMS IN
FIELD
4" 2"
DATE:
SHEET:
317 N. Cruse Ave., Suite 201 Helena, Montana 59601 406.449.2013phone www.mosaicarch.com
D
AT
E
ST
AM
P:
a r c h i t e c t u r e - p l a n n i n g -d e s i g n
7/
/2
2:
:1
PM
05.19.2026
AD-001
CODE INFORMATION &
TYP. ASSEMBLIES
26 FORT MISSOULA RD, MISSOULA,
MT
BUILDING 24
REMODEL
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
1/16" = 1'-0"
CODE REVIEW - BASEMENT1
1.
2.
3.
4.
5.
DIMENSIONS ARE TO FACE OF STUD, EXISTING WALL FINISH,
MASONRY, OR DOOR/WINDOW OPENINGS. DIMENSIONS OF EXISTING
CONSTRUCTION ARE NOT SHOWN ON DRAWINGS - VERIFY
DIMENSIONS OF ALL EXISTING CONSTRUCTION IN THE FIELD.
DIMENSIONS TO OPENINGS ARE NOMINAL. VERIFY ALL OPENINGS
WITH ROUGH OPENING REQUIREMENTS.
ALL DOOR OPENINGS PERPENDICULAR TO A WALL ARE 4" TO THE
WALL FRAMING UNO.
EXISTING CONSTRUCTION TO REMAIN SHOWN SHADED, NEW
CONSTRUCTION SHOWN SOLID.
SEE SHEET A-002 FOR WALL TYPES. IN AREAS WITH SUSPENDED
ACOUSTICAL TILE CEILINGS, GYPSUM WALL BOARD MAY BE
TERMINATED 6" ABOVE THE CEILING.
VERIFY EXISTING WALL CONSTRUCTION.
GENERAL FLOOR PLAN NOTES
NEW CONSTRUCTION
EXISTING ELEMENTS TO REMAIN
LINEWORK LEGEND
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
VERIFY ALL CONDITIONS AND COORDINATE WITH ALL DISCIPLINES OF CONTRACT.
UNDOCUMENTED FIELD CHANGES MAY HAVE OCCURRED AND ARE TO BE BROUGHT TO
THE ATTENTION OF THE CO/ARCHITECT WHEN DISCOVERED.
SEE CIVIL DRAWINGS FOR SITE DEMOLITION.
SEE MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR DEMOLITION WORK OF
THOSE TRADES.
WHERE DEMOLITION IS INDICATED, WALLS SHALL BE REMOVED AND CEILING SHALL BE
PATCHED, REPAIRED AND PAINTED TO MATCH EXISTING.
CONTRACTOR SHALL MAINTAIN A TEMPORARY WEATHER TIGHT ENCLOSURE AS ITEMS
ARE BEING REMOVED.
COORDINATE ALL MECHANICAL, ELECTRICAL, FIRE SYSTEMS, COMMUNICATIONS AND
UTILITY SHUT-DOWNS WITH CONTRACTING OFFICER PRIOR TO REMOVING AND OR
RELOCATING.
DEMOLITION IS NOT NECESSARILY LIMITED TO WHAT IS SHOWN ON DRAWINGS. THE
INTENT IS TO INDICATE THE GENERAL SCOPE OF DEMOLITION REQUIRED TO COMPLETE
THE WORK IN ACCORDANCE WITH THE CONTRACT DRAWINGS.
SEE HAZARDOUS MATERIALS ABATEMENT DRAWINGS FOR ADDITIONAL INFORMATION
AND COORDINATION.
ANY MATERIALS LEFT ON WALLS TO BE REMOVED AND RETURNED TO FOREST SERVICE
ALL EXISTING FURNITURE TO BE REMOVED BY FOREST SERVICE COORDINATE ANY
ADDITIONAL ITEMS TO BE REMOVED WITH CONTRACTING OFFICER.
GENERAL DEMOLITION NOTES
DEMOLITION KEYNOTES
NOTE: SEE MECH/ELEC/STRUCT AND CIVIL DRAWINGS FOR ADDITIONAL DEMOLITION
INFORMATION.
REMOVE EXISTING INTERIOR WALL COMPLETELY, INCLUDING BRACING ABOVE CEILING
WHERE OCCURS. REPAIR ALL ADJACENT SURFACES TO RECEIVE NEW FINISHES.
REMOVE DOOR, FRAME AND HARDWARE. WHERE REQUIRED INFILL TO MATCH EXISTING
CONSTRUCTION
REMOVE PORTION OF WALL NECESSARY TO RECEIVE NEW DOOR AND FRAME.
REROUTE ELECTRICAL AS REQUIRED.
REMOVE COLUMN WRAP IN ITS ENTIRETY. ONLY STEEL SUPPORT COLUMN TO REMAIN,
REMOVE EXISTING FLOORING AND PREPARE FOR INSTALLATION OF NEW FLOORING.
REMOVE SUSPENDED CEILING SYSTEM, INCLUDING ALL ASSOCIATED SUPPORT CABLE &
PERIMETER T-BAR. COORDINATE EXTENT OF DEMOLITION WITH REMODEL PLANS.
REMOVE ALL ASSOCIATED LIGHT FIXTURES, DIFFUSERS AND RETURN GRILLES. LEAVE
ANY SMOKE DETECTORS ACTIVATED & DANGLING AFTER CEILING REMOVAL FOR
REINSTALLATION. ENSURE DUCTWORK TO REMAIN IS PROPERLY SUPPORTED. -
PORTION OF CEILING ABOVE MAY NEED TO BE REMOVED TO BRACE NEW CEILING.
COUNTERTOP AND CABINETS TO BE REMOVED
REMOVE LIGHT FIXTURES TO BE DEMOLISHED, SEE ELEC.
REMOVE SUSPENDED CEILING TILES AND LIGHT FIXTURES PER ELEC. EXISTING GRID
AND ASSOCIATED BRACING TO REMAIN AND BE REUSED
REMOVE PLUMBING FIXTURE - SEE PLUMBING FOR ADDNL INFO
REMOVE ACOUSTIC MATERIAL ON CEILING SYSTEM, PROTECT REMAINING GYP CEILING
WHERE POSSIBLE.
REMOVE EXISTING INTERIOR WINDOWS, FRAME AND HARDWARE WHERE NOTED, INFILL
WALL TO MATCH SURROUNDING CONSTRUCTION AS SHOWN ON REMODEL PLANS.
REMOVE SOFFIT WHERE INDICATED ON PLANS, PROTECT REMAINING SOFFIT
SAVE ALL WALL BASE FOR REINSTALL
REMOVE PICTURE RAIL - RETAIN FOR REINSTALL ON NEW WALL
DEMOLITION MAY BE REQUIRED FOR PLUMBING REPLACEMENT - VERIFY EXTENTS WITH
PLUMBING DRAWINGS
KKGG
JJIIHH
OFFICE
IT
HERITAGE STORAGE
PIPE TO REMAIN
FLOORING IN THIS AREA CONTAINS ASBESTOS. REFER TO
ASBESTOS REPORT FOR ADDITIONAL INFORMATION PRIOR
TO DEMOLITION.
DD EECCBBAA
KITCHEN
1 2
STORAGE
4 4
4 45
KKGG
JJIIHH
IT
OFFICE
OFFICE
OFFICE
DD EECCBBAA
KITCHEN
STORAGE
8 8 8
12 12
DATE:
SHEET:
317 N. Cruse Ave., Suite 201 Helena, Montana 59601 406.449.2013phone www.mosaicarch.com
D
AT
E
ST
AM
P:
a r c h i t e c t u r e - p l a n n i n g -d e s i g n
7/
/2
2:
:2
PM
05.19.2026
AD-101
DEMOLITION PLAN -
BASEMENT
26 FORT MISSOULA RD, MISSOULA,
MT
BUILDING 24
REMODEL
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
3/32" = 1'-0"
DEMO - EAST2
3/32" = 1'-0"
DEMO - WEST4
3/32" = 1'-0"
DEMO - RCP - EAST1
3/32" = 1'-0"
DEMO - RCP - WEST3
1/4" = 1'-0"
DEMO - OFFICE5
1/4" = 1'-0"
DEMO - KITCHEN7
1/4" = 1'-0"
DEMO - KITCHEN WALL8
1/4" = 1'-0"
DEMO - BASEMENT10 1/4" = 1'-0"
DEMO - BASEMENT 211 1/4" = 1'-0"
DEMO - BACK ROOM9
1/4" = 1'-0"
DEMO - IT6
e2s
WALL TYPE
WALL HEIGHT
WALL STUD & FINISH HEIGHT
a GWB TO 6" ABOVE CEILING; FRAME OR BRACE TO STRUCTURE b TO STRUCTURE
WALL TYPE TAG
1.
2.
3.
SEE FLOOR PLAN FOR WALL TYPES AND WALLS THAT EXTEND
FULL HEIGHT TO STRUCTURE.
CEILING FIXTURES ARE SHOWN FOR REFERENCE ONLY FOR
COORDINATION WITH CEILING FINISH SYSTEM.
SPOT ELEVATIONS ARE FROM FINISH FLOOR TO SURFACE FINISH
OF CEILING AND ARE ROUNDED TO THE NEAREST INCH.
GENERAL CEILING NOTES
CEILING LAYOUT NOTES: LAY-IN CEILINGS ARE SHOWN CONCEPTUALLY.
IT IS THE INTENT THE CEILINGS AREA CENTERED WITHIN THE ROOM. IN
ODD SHAPED ROOMS, PRIMARY VISUAL AREA TO BE CENTERED. CEILING
INSTALLER SHOULD CONSULT WITH THE CO IN THE FIELD FOR ANY AREAS
IN WHICH THEY WOULD LIKE TO MODIFY THE LAYOUT FROM THAT SHOWN
ON THE PLAN. MODIFICATIONS MAY BE ALLOWED, AT THE DISCRETION
OF THE CONTRACTING OFFICER, TO EASE INSTALLATION, SAVE CUTTING,
OR INCREASE VISUAL APPEAL.
CEILING LEGEND
GWB 5/8" TYPE "X" GYPSUM WALLBOARD ON
STL. FRAMING - SEE DETAILS. PAINT P1
UNO
ACT2 2x2 CEILING TILES - ONLY
ACT-G 2x2 ACT SYSTEM: 2X2 TILES WITH 15/15"
HEAVY DUTY GRID. SEE SEISMIC
INSTALLATION REQ'TS AND DETAILS.
ACT1 2x4 CEILING TILES - ONLY
1.
2.
3.
4.
5.
DIMENSIONS ARE TO FACE OF STUD, EXISTING WALL FINISH,
MASONRY, OR DOOR/WINDOW OPENINGS. DIMENSIONS OF EXISTING
CONSTRUCTION ARE NOT SHOWN ON DRAWINGS - VERIFY
DIMENSIONS OF ALL EXISTING CONSTRUCTION IN THE FIELD.
DIMENSIONS TO OPENINGS ARE NOMINAL. VERIFY ALL OPENINGS
WITH ROUGH OPENING REQUIREMENTS.
ALL DOOR OPENINGS PERPENDICULAR TO A WALL ARE 4" TO THE
WALL FRAMING UNO.
EXISTING CONSTRUCTION TO REMAIN SHOWN SHADED, NEW
CONSTRUCTION SHOWN SOLID.
SEE SHEET A-002 FOR WALL TYPES. IN AREAS WITH SUSPENDED
ACOUSTICAL TILE CEILINGS, GYPSUM WALL BOARD MAY BE
TERMINATED 6" ABOVE THE CEILING.
VERIFY EXISTING WALL CONSTRUCTION.
GENERAL FLOOR PLAN NOTES
NEW CONSTRUCTION
EXISTING ELEMENTS TO REMAIN
LINEWORK LEGEND
12 ga. HANGER WIRE @ 4'-0" O.C.
SPLAY BRACING WIRES
CROSS TEE OR HAT
CHANNEL
_45o MAX
TYPICAL FOR 4
MAIN RUNNER TEE OR
HOT ROLLED CHANNELNOTES:
1. HANGING WIRES SHALL BE ATTACHED TO SUSPENDED MEMBERS
WITH A MINIMUM OF THREE TIGHT TURNS IN 1-1/2". BOTH ENDS OF WIRE.
2. BRACING WIRES SHALL BE ATTACHED TO SUSPENDED MEMBERS
WITH A MINIMUM OF FOUR TIGHT TURNS IN 1-1/2". BOTH ENDS OF WIRE.
3. COMPLY WITH CCR TITLE 24 REQUIREMENTS.
ROOF FRAMING OR BLOCKING AS REQUIRED
EYEBOLT SCREWED TO ROOF FRAMING
OR BLOCKING ABOVE, TYP.
VERTICAL COMPRESSION STRUT DESIGNED
FOR 200LBS. COMPRESSION FORCE ATTACH
TOP & BOT. W/ ONE 1/4" DIA. BOLT
CROSS TEES (FOR ACOUST TILES) OR 7/8"-26
ga. FURRINGG HAT CHANNELS @ 2'-0" O.C.
(FOR GYP. BD)
MAIN RUNNER TEES (FOR ACOUSTICAL TILES)
OR 1-1/2" HOT ROLLED MAIN RUNNER CHANNELS
@ 3'-0" O.C. (FOR GYP. BD)
NOTE:
FOR LOCATION OF BRACING AND ADDITIONAL
REQUIREMENTS, SEE ACOUSTICAL CEILING DETAIL
1" WALL CHANNEL TYPICAL AT PERIMETER
HANGER WIRE (12 ga> GALVANIZED STEEL WIRE).
WRAP 3 FULL TIMES
1" 16 ga. COLD ROLLED
CHANNEL AT 48" O.C.
DIAGONAL BRACING AS PER
IBC SEISMIC REQUIREMENTS
GYP. WALL BD. FASTEN W/ TYPE "S"1"
BUGLE HEAD SCREWS AT 12" O.C. MAX
18 ga. STEEL HAT CHANNEL FURRING
AT 16" O.C.
NOTE:
1. 1/4 OF THE LENGTH OF THE END RUNNER, WHICHEVER IS LEAST
2. PROVIDE SPACER @ FREE END WHERE THE FIRST RUNNER IS 12" OR MORE FROM WALL
WALL ANGLE - ATTACH AT EACH STUD W/ 1-1/4" LONG S-12 PANCAKE HEAD
SCREW, PROVIDE BLKG WHERE CLG. DOESN'T TERMINATE ON A STUD
1/2"
8" MAX OR NOTE (1)8" MAX OR NOTE (1)
MAIN RUNNER
OR CROSS "T"MIN. 3 TIGHT
TURNS IN 1 1/2"
NOTE (2)
ACOUSTICAL PANEL1/8" POP RIVET AT EACH MEMBER
PER RCP
PER RCP
6"
MI
N.
GYP. BD CONTINUOUS AT B.O.
STRUCTURE WHERE APPLICABLE
GYP. BD CONTINUOUS TO
STRUCTURE ABOVE WHERE
INDICATED IN ACOUSTIC LAYOUT
PLAN
CORNER BEAD
ALIGN W. FACE OF WALL
BEYOND WHERE OCCURS
5/8" GYP BD ON 3 5/8" STL
STUD FRAMING
CEILING TILE AND TRACK OR OTHER
CEILING TYPE, HT. PER RCP
PERIMETER CLOSURE ANGLE 2" MIN WIDTH
LATERAL BRACING SYSTEM @ 12'-0" O.C. EA WAY. BEGIN
BRACING WITHIN 6'-0" OF PERIMETER & 2" FROM CROSS
MEMBER. BRACING SYSTEM INCLUDES COMPRESSION
STRUT W/ (1) HANGER WIRE THRU CTR & (4) HANGER
WIRES SPLAYED IN (4) DIRECTIONS @45 o MAX
6'-0" MAX 4'-0" MAX 4'-0" MAX2" 2"
12'-0" O.C.
MAIN RUNNERS W/ #12 WIRES
TO STRUCT @ 4'-0" O.C.
3/4" SEISMIC JOINT @
PERIMETER WALLS
ADDITIONAL HANGERS ALL
MEMBERS W/ IN 8" OF PERIMETER
PROVIDE (2) SLACK WIRES TO EA.
FIXTURE. PROVIDE POSITIVE CLIP FROM
FIXTURE TO MAIN RUNNERS. FIXTURE
WEIGHT NOT TO EXCEED 56LBS.
MAIN RUNNERS W/ #12 WIRES
TO STRUCT @ 4'-0" O.C.
CROSS RUNNERS FIT
BETWEEN MAIN RUNNERS
BLDG STRUCT
COUNTERSLOPE HANGERS IF MORE
THAN 1:6 OUT OF PLUMB
TRAPEZE HANGER WIRES @ DUCTWORK & OTHER LG. OBSTRUCTIONS
KKGG
JJIIHH
OFFICE
IT
OFFICE
OFFICE
i2 i1
PIPE TO REMAIN
HERITAGE STORAGE
9"
19' - 6 1/2"
6' - 8"
WD WALL BASE AT
ALL COLUMNS - TYP
8 7/16"
1'
- 3
3/
DD EECCBBAA
L104
KITCHEN
STORAGE
OPENING
(72x84)
0"
ALIGN SINK WITH
EXISTING PLUMBING
AD-701
AD-701
2' - 0"
12' - 3"
AD
-7
AD
-7
6' - 0"
ALIGN WALL
WITH COLUMN
WD WALL BASE AT
ALL COLUMNS - TYP
4 5 /8"
KKGG
JJIIHH
IT
OFFICE
OFFICE
OFFICE
TRAINING
ACT-G
8' - 0"
GYP
7' - 11"
ACT-G
8' - 0"
ACT2
8' - 0"
ACT1
8' - 0"
ACT2
8' - 0"
NEW SOFFIT HEIGHT TO MATCH EXISTING
GYP
7' - 11"
PROVIDE TRIM AT COLUMN
ACT CEILING INTERFACE - TYP
EXISTING CEILING TO
REMAIN- PATCH AS
REQUIRED - PAINT
DD EECCBBAA
STORAGE
KITCHEN
ACOUSTIC CEILING
PANEL- BEIGE
7/8" HAT CHANNELS BEYOND
AD-102
CEILING TO BE PATCHED AT
WALL REMOVAL MATCH
SURROUNDING TEXTURE
DOOR TYPES
F
STANDARD FRAME
SEE DETAIL
SCHEDULE
PER .
PE
R
SC
HE
DU
LE
SE
E D
ET
AIL
DOOR FRAME TYPES
SEE PLAN AND SCHEDULE FOR ALL DOOR SIZES
F
FLUSH
HL
FLUSH W HALF LITE
1/4" LAMINATED SAFETY GLASS
GLAZING LEGEND
ALUM
ANOD
F
FACT
HL
HM
MFR
SF
STL
WD
ABBREVIATIONS
ALUMINUM
ANODIZED FINISH - DK BRONZE
FLUSH
FACTORY FINISH
HALF LITE
HOLLOW METAL
MANUFACTURER
ALUMINUM STOREFRONT
STEEL
WOOD - SOLID CORE
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
ALL DOOR LOCATIONS NOT SPECIFICALLY DIMENSIONED TO BE
PLACED 4 INCHES FROM ADJACENT WALL SURFACE. IF THERE IS NO
DIRECTLY ADJACENT SIDEWALL, CONTACT ARCHITECT FOR PROPER
PLACEMENT.
ALL DOORS TO HAVE ADA COMPLIANT THRESHOLDS WITH 1/2"
MAXIMUM RISE UNLESS SPECIFICALLY DETAILED OTHERWISE.
ALL METAL DOORS AND FRAMES TO BE PRIMED AND PAINTED. VERIFY
COLOR WITH ARCHITECT.
ALL EXTERIOR DOORS TO BE FULLY INSULATED.
ALL EXTERIOR DOORS TO HAVE FULL PERIMETER
WEATHERSTRIPPING.
ALL HARDWARE ON FIRE-RATED DOORS MUST BE APPROVED FOR
SUCH USE AND INSTALLED AS REQUIRED TO MAINTAIN SYSTEM FIRE
RATING.
ALL DOORS/FRAMES TO HAVE RESILIENT SILENCERS.
CONTRACTOR TO USE ARCHITECT'S DOOR TYPE PLAN DESIGNATION
NUMBER IN ADDITION TO THE ROOM NUMBER ON ALL SHOP DRAWING
SUBMITTALS
FIRE RATING FOR FRAMES MUST MATCH RATING FOR DOORS.
SEE WINDOW ELEVATIONS FOR DETAILS.
ALL EGRESS DOORS SHALL BE READILY OPENABLE FROM THE
EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE
OR EFFORT.
GENERAL DOOR NOTES
PER WALL ASSEMBLY
SEE FLOOR PLANS
FOR WALL TYPE
CAULK JOINT
TYPICAL EA SIDE
WOOD CASING
DOOR PER SCHEDULE
JAMB BEYOND DOOR STOP
SHIM
3"
ACOUSTIC INSULATION
SEE FLOOR PLANS
FOR WALL TYPE
DOOR PER SCHEDULE
WOOD CASING
CAULK JOINT, TYP.
EACH SIDE
WOOD CASING
DOOR STOP
3"
7/8" HAT CHANNEL- SPACING PER MANF.
ACOUSTIC PANEL
SCREW AND WASHER PER
MANF. COLOR MATCH TO PANEL
(E) CEILING
1.
2.
3.
4.
5.
6.
7.
ALL DOOR LOCATIONS NOT SPECIFICALLY DIMENSIONED TO BE PLACED
4 INCHES FROM ADJACENT WALL SURFACE. IF THERE IS NO DIRECTLY
ADJACENT SIDEWALL, CONTACT ARCHITECT FOR PROPER PLACEMENT.
ALL DOORS TO HAVE ADA COMPLIANT THRESHOLDS WITH 1/2" MAXIMUM
RISE UNLESS SPECIFICALLY DETAILED OTHERWISE.
ALL METAL DOORS AND FRAMES TO BE PRIMED AND PAINTED. VERIFY
COLOR WITH ARCHITECT.
ALL DOORS/FRAMES TO HAVE RESILIENT SILENCERS.
CONTRACTOR TO USE ARCHITECT'S DOOR TYPE PLAN DESIGNATION
NUMBER IN ADDITION TO THE ROOM NUMBER ON ALL SHOP DRAWING
SUBMITTALS
SEE WINDOW ELEVATIONS FOR FRAME TYPES FOR ALUMINUM FRAMES.
ALL EGRESS DOORS SHALL BE READILY OPENABLE FROM THE EGRESS
SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE OR EFFORT.
GENERAL DOOR NOTES
Hardware Group No. 01 For use on Door #(s): 01, 02
Provide each SGL door(s) with the following:
QTY DESCRIPTION CATALOG NUMBER FINISH MFR
3 EA HINGE BAA 5BB1 SERIES (WEIGHT, SIZE, NRP AS REQ'D) F695 IVE
1 EA ENTRANCE LOCK ND53 (LEVER PREP AS REQ'D) RHO BA 606 SCH
1 EA CYLINDER MATCH EXISTING KEY SYSTEM 606
1 EA WALL STOP WS406/407CCV 606 IVE
3 EA SILENCER SR64/SR65 AS REQ'D BY FRAME MATERIAL GRY IVE
DOOR HARDWARE
DATE:
SHEET:
317 N. Cruse Ave., Suite 201 Helena, Montana 59601 406.449.2013phone www.mosaicarch.com
D
AT
E
ST
AM
P:
a r c h i t e c t u r e - p l a n n i n g -d e s i g n
7/
/2
2:
:2
PM
05.19.2026
AD-102
FLOOR PLAN & RCP -
BASEMENT
26 FORT MISSOULA RD, MISSOULA,
MT
BUILDING 24
REMODEL
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T
SDOOR SCHEDULE
MARK ROOM NAME
DOOR
TYPE WIDTH HEIGHT THICKNESS DOOR MAT'L DOOR FINISH
FRAME
TYPE FRAME MAT'L FRAME FINISH DOOR HDWR GROUP FIRE RAT'G COMMENTS
01 OFFICE HL 3' - 0" 6' - 8" 1 3/4" WD FACT F WD PAINT 01 NONE
02 OFFICE F 3' - 0" 6' - 8" 1 3/4" WD FACT F WD PAINT 01 NONE
1 1/2" = 1'-0"
FOUR WAY TEE BRACING13
1 1/2" = 1'-0"
SUSPENDED CEILING BRACING11
1 1/2" = 1'-0"
SUSPENDED GWB CEILING12
1 1/2" = 1'-0"
ACOUSTIC CEILING DETAIL8
1 1/2" = 1'-0"
SOFFIT DETAIL - MTL STUD10
1/2" = 1'-0"
SEISMIC CEILING ASSEMBLY7
3/32" = 1'-0"
FLOOR PLAN - BASEMENT - PLAN EAST2
3/32" = 1'-0"
FLOOR PLAN - BASEMENT - PLAN WEST4
3/32" = 1'-0"
RCP - PLAN EAST1
3/32" = 1'-0"
RCP - PLAN WEST3
3" = 1'-0"
INTERIOR WOOD DOOR FRAME HEAD5
3" = 1'-0"
INTERIOR WOOD DOOR JAMB6
1 1/2" = 1'-0"
ACOUSTIC PANEL DETAIL9
UP
ROOM FINISH LEGEND
CPT1: CARPET TILE - INTERFACE, STYLE 'STEP IT UP', COLOR - ASH
LVT: LUXURY VINYL TILE - INTERFACE, 22 MIL, STYLE: 'RIDGE', COLOR: AGATE
CNCR: EXISTING CONCRETE TO BE CLEANED AND CRACKS FILLED
(E): EXISTING FINISH - NO WORK
FLOOR FINISHES
1.
2.
3.
4.
5.
FLOOR AND BASE FINISH NOTES:
SEE SPECIFICATIONS FOR FINISH MANUFACTURER.
ALL FLOORING TO BE INSTALLED ON MANUFACTURERED APPROVED SUB FLOOR.
INSTALL FACTORY-PROVIDED TRANSITION STRIP OR AS DETAILED AT ALL FLOORING CHANGES.
CHANGE FLOORING WHERE INDICATED ON PLANS, CHANGE FLOOR CENTERED UNDER DOOR AT
ROOM TO ROOM CHANGES, U.N.O
AT CASEWORK, CONTINUE BASE AROUND ENDPANELS AND TOE-KICKS, U.N.O.
PAINT NOTE: MANUF. SHOWN ARE BASIS OF DESIGN ONLY. SUBSTITUTIONS ALLOWED WITH APPROVAL; SEE SPEC SECTION ON SUBSTITUTIONS. VERIFY FINAL PAINT COLORS AND LOCATIONS W/ CO PRIOR TO
INSTALLATION.
P1: PAINT - COLOR: WHITE - MAIN WALLS - COORDINATE WITH PROJECT CO
WALL FINISHES
RB1: 6" RUBBER BASE - JOHNSONITE TRADITIONAL VINYL BASE - COLOR: BY CO
WB: MATCH EXISTING - 6" WOOD BASE TRIM WITH 1" TRIM PIECE- PAINT TO MATCH EXISTING
BASE FINISHES
CPT1
1.
2.
3.
4.
5.
PL1: PLASTIC LAMINATE 1 - WILSONART PREMIUM LAMINATE - COLOR: HARVEST MAPLE
PL2: PLASTIC LAMINATE 2 - WILSONART PREMIUM LAMINATE - COLOR: CANYON ZEPHYR
COUNTERTOP AND CASEWORK FINISHES NOTES:
SEE SPECIFICATION FOR MANUFACTURER.
PLASTIC LAMINATE COUNTERTOPS TO HAVE LAMINATE EDGES, U.N.O. NOTED IN DETAILS.
PROVIDE FINISHED END PANELS WHERE EXPOSED TO VIEW, PROVIDE SCRIBE STRIP AT ALL WALL ABUTMENTS.
WHERE NOTED ON ELEVATIONS, PROVIDE 4" BACKSPLASH W/ SQUARE EDGES, MATCH ADJ. COUNTERTOP
MATERIAL.
FOR BIDDING PURPOSES ASSUME EACH DRAWER AND/OR DOOR HAS A PULL, EVEN IF NOT SHOWN IN
ELEVATIONS
COUNTERTOPS, CASEWORK SURFACES, TRIM
1.
2.
3.
4.
WALL FINISHES NOTES:
SEE INTERIOR ELEVATIONS AND/OR DETAILS FOR INTERIOR WINDOWS, SPECIAL WALL
FINISHES, TRIM, ETC.
FINISH SCHEDULE APPLIES TO GENERAL AREA: THERE MAYBE SPECIFIC FINISH
REQUIREMENTS SHOWN ON DETAILS, DRAWINGS OR SPECIFICATIONS.
SEE SPECIFICATIONS FOR LEVEL(S) OF FINISH AT GWB SURFACES.
ALL WALLS/CEILINGS P1 UNLESS OTHERWISE NOTED ON PLANS &/OR ELEVATIONS.
CEILING FINISHES
CNCR
SEE RCP
(E)LVT
1.
2.
3.
4.
5.
6.
IF FINISHES ARE NOT CLEARLY INDICATED FOR AN AREA, CLARIFY INTENT WITH CO.
PROVIDE APPROPRIATE TRANSITION TRIM AT ALL MATERIAL CHANGES.
PROVIDE EXTRUDED ALUMINUM EDGE METAL AT TERMINATION OF ALL CERAMIC TILE AREAS.
TEST ALL SUBSTRATES TO VERIFY COMPLIANCE WITH FINISH MANUFACTURER'S SPECIFICATIONS
PRIOR TO FLOORING INSTALLATION.
PATCH, REPAIR, AND/OR GRIND ALL SUBSTRATES TO ACCEPTABLE LEVEL OF
SMOOTHNESS/LEVELNESS PRIOR TO FLOORING INSTALLATION.
FLOORING CHANGES FROM ROOM TO ROOM TO OCCUR DIRECTLY UNDER THE DOOR LOCATION.
SEE FINISH SCHEDULE FOR LISTING OF MATERIALS .
FLOOR FINISH NOTES:
1.
2.
3.
4.
5.
6.
IF FINISHES ARE NOT CLEARLY INDICATED FOR AN AREA, CLARIFY INTENT WITH CONTRACTING
OFFICER/ARCHITECT.
PROVIDE APPROPRIATE TRANSITION TRIM AT ALL MATERIAL CHANGES.
PROVIDE CLEAN, CONSISTENT CAULK JOINTS AT ABUTMENTS OF DISSIMILAR MATERIALS.
PROVIDE METAL EDGING AT ALL GYPSUM BOARD EDGES THAT ABUT DISSIMILAR MATERIALS.
PROVIDE BULLNOSE TILES AT ALL EXPOSED TILE EDGES.
WALL FINISH LEVEL AND TEXTURE TO MATCH EXISTING
WALL FINISH NOTES:
1.
2.
3.
IF FINISHES ARE NOT CLEARLY INDICATED FOR AN AREA, CLARIFY INTENT WITH CO.
PROVIDE APPROPRIATE TRANSITION TRIM AT ALL MATERIAL CHANGES.
PROVIDE CLEAN, CONSISTENT CAULK JOINTS AT ABUTMENTS OF DISSIMILAR MATERIALS.
CEILING FINISH NOTES:
GENERAL FINISH NOTES:
1.
2.
3.
4.
ALL PAINTING, WALLCOVERING & GYPSUM WALLBOARD FINISHING PER SPECIFICATIONS
AND DECORATING CONTRACTORS OF AMERICA.
PROVIDE SAMPLES OF SPECIFIED FINISHES TO ARCHITECT/CONTRACTING OFFICER FOR
APPROVAL PRIOR TO APPLICATION
PROVIDE TO CONTRACTING OFFICER APPROXIMATELY 5% OF ADDITIONAL FINISH
MATERIAL FOR FUTURE REPAIR AND MAINTENANCE. (I.E. - PAINT, VINYL FLOORING,
RUBBER BASE, ETC.)
WALL FINISH LEVEL AND TEXTURE TO MATCH EXISTING
EXISTING CARPET NEW CARPET
SQUARE CAP METAL TRIM
KKGG
JJ
FFDD
II
EECCBBAA
HH
KITCHEN
OFFICE
NO WORK BEING DONE IN THIS ZONE
OFFICE
OFFICE
IT
STORAGE
TRAINING
AD-701
PL2
HERITAGE STORAGE
AD-701
1' - 8" 2'
- 1 0"
3/4" PLAM 1
1' - 11 1/8"
WHITE MELAMINE INTERIOR
COUNTERTOP & BACKSPLASH - PLAM 2
PROVIDE BLOCKING WHERE REQUIRED TYP.
2'
- 1
0"
BACKING IN WALL
2' - 0" 1/2"
VERIFY PER LAV. SPEC
1' - 9"
PLAM 2
PLAM 1
3 1 /2"
2' - 0 1/2"
4" BACKSPLASH - PLAM 2
2' - 0" 1"
WHITE MELAMINE INTERIOR
4" 2'
- 6
1/4" D MORTIS, 1"
VERTICAL SPACING
WIRE PULL
COUNTERTOP & BACKSPLASH - PLAM 2
1/4
3"
WHITE MELAMINE INTERIOR
PROVIDE BLOCKING WHERE REQUIRED TYP.
EXISTING CONCRETE
NEW CARPET
TARKETT CTA-XX-P
3' - 1" 3' - 1" 3' - 1" 3' - 1 5/8"
OPEN BELOW OPEN BELOW OPEN BELOW
3' - 0" 3' - 0" 3' - 0" 3' - 0" 2' - 0" 3' - 0"
OPEN BELOW
2X4 WOOD FRAMED WALL-
WRAP WITH 5/8" GYP AND
PAINT TO MATCH WALL
PLAM 2
PLAM 1
DATE:
SHEET:
317 N. Cruse Ave., Suite 201 Helena, Montana 59601 406.449.2013phone www.mosaicarch.com
D
AT
E
ST
AM
P:
a r c h i t e c t u r e - p l a n n i n g -d e s i g n
7/
/2
2:
:3
PM
05.19.2026
AD-701
FINISH PLAN &
SCHEDULE-
BASEMENT
26 FORT MISSOULA RD, MISSOULA,
MT
BUILDING 24
REMODEL
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
ROOM FINISH SCHEDULE
NO. ROOM NAME AREA FLOOR FINISH BASE FINISH NORTH WALL EAST WALL SOUTH WALL WEST WALL COMMENTS 10 HERITAGE STORAGE 221 SF (E) WD (e) P1 P1 P1 P1 REUSE EXISTING WALL BASE WHERE POSSIBLE 11 IT 268 SF CNCR WD (e) P1 P1 P1 P1 REUSE EXISTING WALL BASE WHERE POSSIBLE
12 TRAINING 215 SF CPT1 WD P1 P1 P1 P1
13 OFFICE 1209 SF CPT1 WD (e) P1 P1 P1 P1 REUSE EXISTING WALL BASE WHERE POSSIBLE 14 OFFICE 161 SF CPT1 WD (e) P1 P1 P1 P1 REUSE EXISTING WALL BASE WHERE POSSIBLE 15 OFFICE 171 SF CPT1 WD (e) P1 P1 P1 P1 REUSE EXISTING WALL BASE WHERE POSSIBLE
16 KITCHEN 1138 SF CPT1 WD P1 P1 P1 P1
17 STORAGE 279 SF CNCR RB P1 P1 P1 P1
1/2" = 1'-0"
KITCHEN CABINETRY - AT SINK6 1" = 1'-0"
DRAWER BASE5
1" = 1'-0"
TYP. BASE4
3" = 1'-0"
CARPET TRANSITION3
1/16" = 1'-0"
BASEMENT - FINISH PLAN1
3" = 1'-0"
CARPET TO CON. TRANS.2
1/4" = 1'-0"
KITCHEN ELEVATION7
VALVES
DUCT UP (PLAN VIEW)
DUCT DOWN (PLAN VIEW)
R INCLINED RISE - IN DIRECTION OF AIRFLOW
D INCLINED DROP - IN DIRECTION OF AIRFLOW
INTERNAL DUCT LINING
ELBOW WITH TURNING VANES
RADIUS ELBOW
SUPPLY DUCT (SECTION VIEW)
RETURN DUCT (SECTION VIEW)
EXHAUST DUCT (SECTION VIEW)
OUTDOOR AIR DUCT (SECTION VIEW)
MANUAL VOLUME DAMPER
BACKDRAFT DAMPER
ZONE DAMPER
BYPASS DAMPER
MOTORIZED DAMPER
FIRE DAMPER
FIRE/SMOKE DAMPER
SMOKE DAMPER
Z B
M F
F S
S
REMOTE VOLUME DAMPER
HVAC DUCTWORK (CONT.)ANNOTATION SYMBOLS
X
X
X
X
CFM
X
DETAIL NUMBER
SHEET NUMBER
SECTION NUMBER
SHEET NUMBER
AIR DEVICE MARK AND CFM
ME-# MECHANICAL EQUIPMENT MARK
POINT OF NEW CONNECTION
POINT OF DISCONNECTION
CFM
X AIR DEVICE MARK AND CFM -
PROVIDE OPPOSED BLADE DAMPER
OBD
CFM
X AIR DEVICE MARK AND CFM -
PROVIDE RADIAL DAMPER
RD
X
X
3D VIEW NUMBER
SHEET NUMBER
MECHANICAL LEGEND
R B
D
PIPE FITTINGS
HVAC CONTROL SYMBOLS
NOTE: THIS IS A STANDARD LEGEND. NOT ALL PIPE TYPES AND
SYMBOLS ARE NECESSARILY UTILIZED IN THE DRAWINGS.
ID INSIDE DIAMETER
IFB INTEGRAL FACE & BYPASS
IGV INLET GUIDE VANES
IPS IRON PIPE SIZE
IU INDUCTION UNIT
KW KILOWATTS
KWH KILOWATT HOUR
LAT LEAVING AIR TEMPERATURE (°F)
LF LINEAR FEET
LWT LEAVING WATER TEMPERATURE (°F)
M MOTOR OPERATED
MAU MAKEUP AIR UNIT
MB MIXING BOX
MBH 1000 BTU/HR
MC MECHANICAL CONTRACTOR
MFR MANUFACTURER
MS MINI-SPLIT
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NL NEW LOCATION
NO NORMALLY OPEN
NPS NOMINAL PIPE SIZE
OA OUTSIDE AIR
OAD OUTSIDE AIR DAMPER
OBD OPPOSED BLADE DAMPER
P PUMP
PC PLUMBING CONTRACTOR
PD PRESSURE DROP
PH PHASE
PHC PREHEAT COIL
PPM PART PER MILLION
PROP PROPELLER
PRV PRESSURE REDUCING VALVE
PSIA PSI, ABSOLUTE
PSIG PSI, GAUGE
QTY QUANTITY
R REGISTER
RA RETURN AIR
RD RADIAL DAMPER
RF RETURN/RELIEF AIR FAN
RH RELATIVE HUMIDITY
RHC REHEAT COIL
SA SUPPLY AIR
SAF SUPPLY AIR FAN
SC SENSIBLE COOLER
SCFM CFM, STANDARD CONDITIONS
SD SMOKE DETECTOR
SEER SEASONAL ENERGY EFFICIENCY RATIO
SENS SENSIBLE
SP STATIC PRESSURE
SPS STATIC PRESSURE SENSOR
SS STAINLESS STEEL
T THERMOSTAT
TA TRANSFER AIR
TCC TEMPERATURE CONTROL CONTRACTOR
TCP TEMPERATURE CONTROL PANEL
TG TRANSFER GRILL
TOS TOP OF STEEL
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UH UNIT HEATER
UNC UNDERCUT
UV UNIT VENTILATOR
VA VOLT-AMPERE
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
WB WET BULB TEMPERATURE (°F)
WC WATER COLUMN
WG WATER GAUGE
WSHP WATER SOURCE HEAT PUMP
ΔT TEMPERATURE DIFFERENCE (°F)
ACC AIR COOLED CONDENSER
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
ADJ ADJUSTABLE
AF AIR FOIL
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFR ABOVE FINISHED ROOF
AFS AIR FLOW STATION
AHU AIR HANDLING UNIT
AP ACCESS PANEL
ATC AUTOMATIC TEMPERATURE CONTROL
ATM ATMOSPHERE
AWG AMERICAN WIRE GAUGE
B BOILER
BB BASEBOARD
BC BACKWARD CURVED
BD BACKDRAFT DAMPER
BF BOILER FEED
BHP BRAKE HORSEPOWER
BI BACKWARD INCLINED
BMS BUILDING MANAGEMENT SYSTEM
BOD BOTTOM OF DUCT
BOJ BOTTOM OF JOIST
BOS BOTTOM OF STEEL
BTU BRITISH THERMAL UNIT
C COMMON
CAV CONSTANT AIR VOLUME
CC COOLING COIL
CCW COUNTER CLOCKWISE
CFM CUBIC FEET PER MINUTE
CH CHILLER
C&I CONTROLS & INSTRUMENTATION
CLG CEILING
CMU CONCRETE MASONRY UNIT
CND CONDENSATE
CONT CONTINUATION
CORR CORRIDOR
CT COOLING TOWER
CU CONDENSING UNIT
CH CABINET HEATER
CV CONTROL VALVE
CVS CONTROL VALVE STATION
CW CLOCKWISE
dB DECIBEL
DB DRY BULB TEMPERATURE (°F)
DDC DIRECT DIGITAL CONTROL
DH DUCT HEATER
DP DEW POINT TEMPERATURE (°F)
DX DIRECT EXPANSION
E EXHAUST
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE (°F)
EC ELECTRICAL CONTRACTOR
EDR EQUIVALENT DIRECT RADIATION
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
ELEV ELEVATION
ERV ENERGY RECOVERY VENTILATOR
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EWT ENTERING WATER TEMPERATURE (°F)
F&T FLOAT & THERMOSTATIC
FA FACE AREA
FC FORWARD CURVED
FC FAN COIL
FP FIRE PROTECTION
FPM FEET PER MINUTE
FT FEET
GA GAUGE OR GAGE
GC GENERAL CONTRACTOR
GEN GENERATOR
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
H HUMIDIFIER
HC HEATING COIL
HG MERCURY
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HR HOUR
HX HEAT EXCHANGER
ABBREVIATIONS
(E) ME-# EXISTING MECHANICAL EQUIPMENT
(D) ME-# DEMOLISHED MECHANICAL EQUIPMENT
PIPING SPECIALTIES
AUTOMATIC AIR VENT
MANUAL AIR VENT
PRESSURE / TEMPERATURE PORT
TEMPERATURE SENSOR
PRESSURE SENSOR
PIPE WELL - EMPTY
FLOW SWITCH
PRESSURE SWITCH
PRESSURE GAUGE, SNUBBER & NEEDLE VALVE
TEMPERATURE GAUGE
FLEXIBLE CONNECTOR
THERMAL/SEISMIC EXPANSION LOOP
FLOW METER
UNION OR FLANGE
ISOLATION VALVE
MANUAL BALANCING VALVE
3-WAY TEMPERATURE CONTROL VALVE
AUTOMATIC BALANCING VALVE
HOSE-END DRAIN W/ CAP
STRAINER
2-WAY TEMPERATURE CONTROL VALVE
SOLENOID VALVE
TEMPERATURE AND/OR PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
BACKFLOW PREVENTER
CHECK VALVE
STEAM TRAP
GAS PRESSURE REGULATOR
BOILER DRAIN W/ CAP
VENTURI VALVE
MANUAL 3-WAY VALVE
BOTTOM CONNECTION, TEE FITTING DOWN
CAPPED OUTLET OR BLIND FLANGE
CHANGE IN ELEVATION OF PIPE
ELBOW
PIPE BREAK
PIPE UP
PIPE DOWN
SIDE CONNECTION, TEE FITTING
TOP CONNECTION, TEE FITTING UP
CONCENTRIC REDUCER
ANCHOR
PIPE GUIDES
RECTANGULAR DUCT
WIDTH x DEPTH
W"xD"
ROUND DUCT
DIAMETER
X"ø
X"ø
FLEXIBLE DUCT
DIAMETER
W"/D"
OVAL DUCT
WIDTH/DEPTH
FLOOR/CEILING SUPPLY DIFFUSER
FLOOR/CEILING RETURN GRILLE
FLOOR/CEILING EXHAUST GRILLE
SIDEWALL SUPPLY DIFFUSER
SIDEWALL RETURN/EXHAUST GRILLE
HVAC DUCTWORK
CND STEAM CONDENSATE RETURN
LPS
MPS
HPS
LOW PRESSURE STEAM
MEDIUM PRESSURE STEAM
HIGH PRESSURE STEAM
HWR
HWS
HEATING WATER RETURN
HEATING WATER SUPPLY
REFRIGERANT (LIQUID AND SUCTION)REF
HPWR
HPWS
HEAT PUMP WATER RETURN
HEAT PUMP WATER SUPPLY
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
ATV ATMOSPHERIC VENT
CTR
CTS
COOLING TOWER RETURN
COOLING TOWER SUPPLY
HVAC PIPING
(E) NAME
(D) NAME
DIRECTION OF FLOW
EXISTING PIPE TO BE DEMOLISHED
EXISTING PIPE TO REMAIN
NAME NEW PIPING
GENERAL
ADJUSTABLE THERMOSTAT
CARBON MONOXIDE / NITRIC OXIDE SENSORCO/NO
STATIC PRESSURE SENSORSP
DIFFERENTIAL PRESSURE SENSORDP
BUILDING PRESSURE SENSORP
ADJUSTABLE HUMIDISTATH
ADJUSTABLE THERMOSTAT W/ LOCKABLE COVERT
ADJUSTABLE THERMOSTAT W/ EQUIPMENT MARK T
ADJUSTABLE CO2 SENSOR
HUMIDITY SENSOR
CO2 SENSOR
$ WALL SWITCH
TEMPERATURE SENSOR
T
H
C
C
T
INSTALLATION:
A. NEW PIPING, DUCTWORK AND EQUIPMENT TO BE INSTALLED IN
ACCORDANCE WITH THE CURRENTLY ADOPTED INTERNATIONAL
MECHANICAL AND INTERNATIONAL BUILDING CODES.
B. EQUIPMENT SHALL BE INSTALLED LEVEL, PLUMB, AND FIRMLY ANCHORED IN
LOCATIONS INDICATED ON PLAN. OBSERVE MANUFACTURER'S
INSTALLATION INSTRUCTIONS AND RECOGNIZED INDUSTRY PRACTICES TO
ENSURE THAT PRODUCTS SERVE THEIR INTENDED FUNCTION.
C. INSTALL EQUIPMENT, DUCTWORK, AND PIPING SO AS TO MAINTAIN CODE
REQUIRED CLEARANCES FOR ELECTRICAL AND TELECOMMUNICATION
EQUIPMENT.
D. ELEMENTS PENETRATING BUILDING COMPONENTS (ROOF ASSEMBLIES,
WALL ASSEMBLIES, ETC.) SHALL BE SEALED WEATHER AND WATER TIGHT.
COORDINATE PENETRATIONS WITH GENERAL CONTRACTOR TO PATCH TO
THE SATISFACTION OF THE ARCHITECT OR ENGINEER.
E. EQUIPMENT MANUFACTURED AFTER 1/1/2023 SHALL MEET MINIMUM SEER2
RATINGS.
COORDINATION:
A. IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO
FIELD COORDINATE THE LOCATION OF EQUIPMENT, ROUTING OF
DUCTWORK, AND ROUTING OF PIPING WITH OTHER TRADES.
B. IT SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO
REVIEW THE DRAWINGS OF OTHER DISCIPLINES AND PROVIDE THE
NECESSARY LABOR AND MATERIALS REQUIRED FOR A COMPLETE
INSTALLATION.
C. COORDINATE THE INSTALLATION OF GRILLES, REGISTERS AND DIFFUSERS
WITH THE ARCHITECTURAL REFLECTED CEILING PLANS, THE ELECTRICAL
LIGHTING PLANS, AND IF RELEVANT, THE TELECOMMUNICATION AND FIRE
SPRINKLER PLANS.
ELECTRICAL COORDINATION:
A. SEE THE MEP COORDINATION SCHEDULE FOR ELECTRICAL INFORMATION.
COORDINATE WITH OTHER TRADES TO ENSURE THAT ELECTRICAL
DISCONNECTS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES,
CONTROLS, AND ELECTRICAL ACCESSORIES ARE FURNISHED AND/OR
INSTALLED BY THE APPROPRIATE TRADE.
FREEZE PROTECTION:
A. THE MECHANICAL CONTRACTOR SHALL FILL THE HYDRONIC SYSTEMS WITH
THE FOLLOWING SOLUTION:
a. HEATING HOT WATER SYSTEM: 0% PROPYLENE GLYCOL & 100%
DISTILLED WATER - GLYCOL SHALL INCLUDE CORROSION INHIBITORS.
B. SEE SPECIFICATIONS FOR ADDITIONAL CHEMICAL TREATMENT
REQUIREMENTS.
SITE ELEVATION:
A. EQUIPMENT SHALL BE…
This is the start of the file's text. The full file is on GovTribe.