This document is a mechanical information sheet and drawing index for a federal contract involving hot water and chilled water pump replacement at the National Historic Trails Interpretive Center located at 1501 N. Poplar Street in Casper, Wyoming. The project is managed by the United States Department of the Interior, Bureau of Land Management.

The scope of work requires removal and replacement of four pump and motor combinations: two hot water pumps and two chiller water pumps. The specified equipment is Armstrong model 3X2X8 4030 pumps with 140 GPM capacity at 45 feet of head and 7.08-inch impeller diameter, paired with 3HP, 3-phase motors operating at 208-230/460V and 1800 RPM. Motors must be either Baldor (part number M3211T) or Dayton (part number 2NKY8B) manufactured units. Additional requirements include replacement of variable frequency drives (VFDs) for both hot water and chiller pump systems with units 100 percent compatible with the new motors, removal of the motor starter on chiller water pumps and installation of new VFDs, reprogramming of the Johnson Controls Building Solutions Metasys graphic interface for newly installed hardware, verification and analysis of chemical composition in both water systems with maintenance recommendations, replacement of the air handling unit VFD drive, and verification of shaft alignment following installation. All four pumps, motors, and VFDs must be from the same manufacturer.

View the file

Other files

File Type Posted
Attachment_4-__Wage_Determination_2015-5413_Rev30_posted_8-22-26.pdf PDF
Attachment_1-_Statement_of_Work.docx DOCX document
Attachment_2-_Quote_Schedule.xlsx XLSX spreadsheet
Sol_140L6226Q0034.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HOT WATER AND CHILLER PUMP SPECIFICATIONS:

1. PUMP MANUFACTURE - ARMSTRONG

2. PUMP MODEL NUMBER - 3X2X8 4030

3. PUMP CAPACITY - 140 GPM - 45 FEET

4. PUMP IMPELLER DIAMETER 7.08

5. PUMP CONSTRUCTION - BF

6. MOTOR - 3HP- 3 PHASE 208-230/460V AT 1800 RPM

7. MOTOR MANUFACTURE - BALDOR OR DAYTON

8. BALDOR MOTOR - PART NUMBER M3211T

9. DAYTON MOTOR - PART NUMBER 2NKY8B

GENERAL NOTES:

1. REMOVE AND REPLACE PUMP AND MOTOR COMBINATION.

2. VERIFY SHAFT ALIGNMENT AFTER NEW MOTOR / PUMP COMBINATION ARE INSTALLED.

3. TWO HOT WATER AND TWO CHILLER PUMP MOTOR COMBINATIONS ARE TO BE

REPLACED.

4. REMOVE AND REPLACE THE VARIABLE FREQUENCY DRIVES FOR THE HOT WATER

PUMPS. VFD'S ARE TO 100 PERCENT COMPARABLE WITH MOTOR ON THE NEW PUMPS.

5. REMOVE THE MOTOR STARTER ON THE CHILLER WATER PUMPS AND INSTALL NEW

VARIABLE FREQUENCY DRIVES FOR THE CHILLER PUMPS. VFD'S ARE TO BE 100

PERCENT COMPATIBLE WITH MOTOR ON THE NEW PUMPS.

6. REPROGRAM THE JOHNSON CONTROLS BUILDING SOLUTIONS (JCBS) METASYS

GRAPHIC INTERFACE FOR THE NEWLY INSTALLED HARDWARE.

7. VERIFY CHEMICAL COMPOSITION OF THE WATER IN BOTH THE CHILLER AND HOT

WATER SYSTEM IS CHEMICAL TREATED CORRECTLY AND PROPOSE

RECOMMENDATIONS FOR MAINTENANCE.

8. ALL FOUR PUMPS, MOTORS AND VFD'S ARE TO BE THE SAME MANUFACTURE.

9. REMOVE AND REPLACE THE AIR HANDLING UNIT (AHU) VFD DRIVE..

AHU MOTOR

COVER SHEET (1)
M1.0