Attachment 3 Drawings.pdf

PDF 3 MB Posted

Attached to
Pendleton Building Repairs Project E (Adams, OR) Federal contract opportunity
Solicitation number
1232SA26Q0209
Issued by
Department of Agriculture Agricultural Research Service

About this file

This document is a set of mechanical and electrical design drawings for the Pendleton Building Repairs Project E at the USDA Agricultural Research Service Columbia Plateau Conservation Research Center in Adams, Oregon. The project modifies the HVAC system in Building 003 to accommodate installation of new fume hoods and includes supplemental heating and cooling systems.

The base bid scope includes installing an exhaust system for an owner-furnished Labconco 6-foot wide acid digestion fume hood in Room 306 and a future fume hood in Room 312, providing supplemental heating and cooling systems to replace pre-heat and pre-cooling losses, and designing an exterior structural platform for the fume hood blower with electrical connections. Alternate 01 adds installation of a complete fume hood and exhaust system in Room 312. Key mechanical specifications include a propane hydronic boiler (Lochinvar WHB199L), variable refrigerant flow (VRF) cooling system with Daikin split units, exhaust fans with unistrut piping support systems, and ductwork meeting SMACNA standards. Electrical work encompasses new panelboard 003-F (125A) with circuits for mechanical equipment including VRF units (AC-003-01 through AC-003-06), exhaust fans (EF-003-01 through EF-003-03), fume hoods (FH-003-01 and FH-003-02), boiler (B-003-03), and hot water pump (HWP-003-05). The project includes seismic restraint provisions per ASCE 7 with equipment mounted on appropriate bases and isolation systems. Design conditions specify Pendleton's Climate Zone 5B with summer outdoor design of 97.1°F DB/64.7°F WB and winter design of -2.0°F DB. Final turnover documentation is dated February 28, 2025.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJ. NO.

DRAWN

CHECKED

DATE

COFFMAN ENGINEERS INC.C

48037 TUBBS RANCH ROAD

ADAMS, OR 97810

231290

02/28/2025

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

FINAL

TURNOVER

P:

\S

PO

\23

JO

BS

\23

A

RS

P

EN

DL

ET

ON

B

UI

LD

IN

G

RE

PA

IR

S\ 0.0

D W

GS

\G

\P

RO

JE

CT

E

BL

DG

3\2

0_ E_

G-

1.D W

G.

_E _G

-0

: C

AM

PB

EL

L, RO

B : L

AS

T

SA

VE

D:

F eb ru ar y 2

8, : P

LO

T

DA

TE

: 2 /28

/25 www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

PENDLETON

BUILDING

REPAIRS

PROJECT E

REV DATE DESCRIPTION

TAH

RKC

COVER SHEET

G-001

OREGON STATE SITE MAP

48037 TUBBS RANCH ROAD

ADAMS, OR 97810

UMATILLA COUNTY

COLUMBIA PLATEAU CONSERVATION

RESEARCH CENTER

USDA AGRICULTURAL RESEARCH SERVICE

PENDLETON BUILDING REPAIRS PROJECT E

BUILDING 003 BUILDING 002 BUILDING 011

BUILDING 001

PROJECT SUMMARY

COLUMBIA PLATEAU CONSERVATION

RESEARCH CENTER

THE USDA RESEARCH CENTER IN PENDLETON CONSISTS OF MULTIPLE BUILDINGS, PROJECT E MODIFIES THE HVAC SYSTEM IN BUILDING 003. THIS PROJECT WILL MODIFY THE EXISTING SYSTEM TO ACCOMODATE

THE INSTALLATION OF NEW FUME HOODS.

THE ITEMS TO BE INCLUDED IN THE BASE BID VS ALTERNATE 01 IS IDENTIED THROUGHOUT THE BID

DOCUMENTS AND LISTED HERE:

BASE BID

INSTALL AN EXHAUST SYSTEM TO ACCOMODATE A OWNER-FURNISHED LABCONCO 6FT WIDE ACID

DIGESTION FUME HOOD IN ROOM 306 OF BUILDING 003, AND FOR A FUTURE FUME HOOD IN ROOM 312 OF

A SIMILAR TYPE.

INSTALL SUPPLEMENTAL HEATING AND COOLING SYSTEMS FOR BUILDING 003 TO REPLACE PRE-HEAT AND PRE-COOLING LOST BY ROOM AIR BEING DIVERTED FROM ENERGY RECOVERY MODULE TO NEW

FUME HOODS.

PROVIDE ELECTRICAL CONNECTIONS FOR NEW MECHANICAL EQUIPMENT.

DESIGN EXTERIOR STRUCTURAL PLATFORM FOR FUME HOOD BLOWER.

ALTERNATE 01

INSTALL A LABCONCO 6FT WIDE ACID DIGESTION FUME HOOD AND EXHAUST SYSTEM IN ROOM 312.

PROVIDE ELECTRICAL CONNECTIONS FOR NEW MECHANCIAL EQUIPMENT.

DESIGN EXTERIOR STRUCTURAL PLATFORM FOR FUME HOOD BLOWER.

THE NEW EQUIPMENT WILL MEET CURRENT APPLICABLE CODE AND USER REQUIREMENTS.

SHEET INDEX

SHEET NUMBER SHEET TITLE

GENERAL

G-001 COVER SHEET

MECHANICAL

M-001 GENERAL MECHANICAL NOTES

M-002 GENERAL MECHANICAL LEGENDS

M-101 MECHANICAL DEMO PLAN

M-201 MECHANICAL PLAN

MP-201 MECHANICAL PIPING PLAN

M-501 MECHANICAL DETAILS

M-502 MECHANICAL DETAILS

M-601 MECHANICAL DIAGRAMS

M-602 MECHANICAL CONTROL DIAGRAMS

M-701 MECHANICAL SCHEDULES

M-702 MECHANICAL SCHEDULES

ELECTRICAL

E-001 ELECTRICAL SHEET INDEX LEGENDS, NOTES. SYMBOLS AND ABBREVIATIONS

E-101 BUILDING 003 - ELECTRICAL PLANS

E-102 MECHANCIAL & PANEL SCHEDULES

E-601 BUILDING 003 - NEW AND EXISTING ONE-LINE DIAGRAMS

2-28-25

CHECKED

DATE

COFFMAN ENGINEERS INC.C

48037 TUBBS RANCH ROAD

ADAMS, OR 97810

231290

02/28/2025

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

FINAL

TURNOVER

P:

\S

PO

\23

JO

BS

\23

A

RS

P

EN

DL

ET

ON

B

UI

LD

IN

G

RE

PA

IR

S\ 0.0

D W

GS

\M

\P

RO

JE

CT

E

BL

DG

3\2

0_ M-

1.D

W G.

_M

-0

: C

AM

PB

EL

L, RO

B : L

AS

T

SA

VE

D:

F eb ru ar y 2

8, : P

LO

T

DA

TE

: 2 /28

/25 www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

PENDLETON

BUILDING

REPAIRS

PROJECT E

REV DATE DESCRIPTION

TAH

DJP

GENERAL

MECHANICAL NOTES

M-001

GENERAL MECHANICAL NOTES

1. CONTRACTOR SHALL SECURE, MAINTAIN, AND PAY FOR ALL REQUIRED PERMITS, LICENSES, AND

INSPECTIONS FOR DURATION OF WORK UNLESS DIRECTED OTHERWISE.

2. ALL WORK SHALL COMPLY WITH THE OWNER'S REQUIREMENTS, AND WITH ALL APPLICABLE

STATE AND LOCAL CODES, OR AUTHORITY HAVING JURISDICTION.

3. SUBSTITUTIONS OF EQUIPMENT OTHER THAN AS SPECIFIED SHALL BE THE COMPLETE

RESPONSIBILITY OF THE CONTRACTOR, ANY ADDITIONAL ELECTRICAL, STRUCTURAL,

MECHANICAL, OR ARCHITECTURAL REQUIREMENTS SHALL BE PROVIDED AT NO ADDITIONAL

EXPENSE TO THE OWNER.

4. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT ATTEMPT TO SHOW ALL REQUIRED

OFFSETS. COORDINATE WITH OTHER TRADES AND PROVIDE ALL NECESSARY OFFSETS. REFER

TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR CONSTRUCTION DETAILS.

5. REFER TO PROJECT MANUAL (SPECIFICATIONS) FOR ADDITIONAL REQUIREMENTS. PLANS AND SPECIFICATIONS SHALL BE TAKEN TOGETHER. PROVIDE ALL WORK CALLED FOR IN EITHER. IN CASE OF CONFLICT BETWEEN SPECIFICATIONS AND PLANS THE MORE STRINGENT SHALL APPLY.

6. ALL EQUIPMENT AND MATERIAL ON THE JOB SITE PRIOR TO INSTALLATION SHALL BE COVERED

AND PROTECTED FROM RAIN, DIRT, DUST, AND DAMAGE.

7. VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT ACCESS CLEARANCES CAN BE

MET. COORDINATE FINAL EQUIPMENT LOCATIONS W/ GENERAL CONTRACTOR AND OTHER

TRADES TO ALLOW FOR REQUIRED MECHANICAL EQUIPMENT CLEARANCES.

8. PROVIDE AN UNOBSTRUCTED PASSAGEWAY MEASURING NO LESS THAN 36" WIDE BY 80" HIGH

FROM DOOR INTO THE SPACE TO SERVICEABLE MECHANICAL EQUIPMENT. A LEVEL WORKING

SPACE MEASURING NO LESS THAN 30" WIDE BY 36" DEEP MUST BE PROVIDED IN FRONT OF

CONTROL SIDE OF EQUIPMENT FOR SERVICING.

9. PROVIDE NEC CODE MINIMUM HORIZONTAL AND VERTICAL WORKING CLEARANCES FOR ALL

ELECTRICAL PANELS AND EQUIPMENT. OFFSET MECHANICAL WORK AS REQUIRED.

10. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF INSTALLATION STANDARDS AND

CONSTRUCTION CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND

EXISTING CONDITIONS PRIOR TO SHOP FABRICATION AND/OR FIELD INSTALLATION.

DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE CONSTRUCTION DRAWINGS SHALL BE

CALLED TO THE ATTENTION OF THE ENGINEER.

11. ALL MECHANICAL EQUIPMENT, MATERIALS, AND INSTALLATION SHALL BE PROVIDED BY THE

CONTRACTOR. ALL EQUIPMENT SHALL BE COMPLETE, INSTALLED, AND FULLY FUNCTIONAL

PRIOR TO FINAL ACCEPTANCE OF THE WORK.

12. INSTALL ALL EQUIPMENT PER MANUFACTURERS RECOMMENDATIONS AND REQUIREMENTS. ANY

CONFLICTS BETWEEN THE MANUFACTURERS DOCUMENTATION AND THE CONTRACT

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER.

13. DO NOT ALLOW ANY WORK TO BE COVERED UP OR ENCLOSED UNTIL INSPECTED, TESTED AND

APPROVED BY OWNER'S REPRESENTATIVE OR AUTHORITY HAVING JURISDICTION.

14. PIPES AND WIRING IN PLENUM SHALL BE RATED FOR PLENUM USE. PVC, ABS, AND PLASTIC

PIPING IS NOT ACCEPTABLE IN PLENUM APPLICATIONS.

15. MECHANICAL EQUIPMENT SHALL NOT BE USED FOR TEMPORARY HEAT DURING CONSTRUCTION.

16. ALL DETAILS ARE TYPICAL UNLESS NOTED OTHERWISE.

GENERAL HVAC NOTES

1. SHEET METAL DUCTWORK AND COMPONENTS INCLUDING HANGING, SEALING, PLENUMS, &

ACCESSORIES SHALL BE CONSTRUCTED IN STRICT ACCORDANCE WITH THE LATEST EDITION OF

SMACNA STANDARDS FOR HVAC DUCT CONSTRUCTION, NFPA 90A, & 90B STANDARDS.

2. ALL DUCTWORK OPENINGS SHALL BE COVERED DURING CONSTRUCTION.

3. ALL DAMPERS SHALL BE SET FULLY OPEN PRIOR TO BALANCING.

4. CONTRACTOR TO PROVIDE TRANSITION TO CONNECT TO ALL MECHANICAL EQUIPMENT. PROVIDE

FLEXIBLE CONNECTION ON INTAKE AND DISCHARGE OF ALL MECHANICAL EQUIPMENT.

5. DUCT DIMENSIONS SHOWN ARE INSIDE SHEET METAL DIMENSIONS OR CLEAR OPENING INSIDE

LINED DUCT.

6. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT ATTEMPT TO SHOW ALL REQUIRED

OFFSETS. COORDINATE WITH OTHER TRADES AND PROVIDE ALL NECESSARY OFFSETS.

7. PROVIDE 1" THICK DUCT LINER IN ALL TRANSFER AIR DUCTWORK UNLESS NOTED OTHERWISE.

8. ALL ELBOWS SHALL BE LONG RADIUS ELBOWS WHEREVER POSSIBLE, OR SHALL HAVE TURNING

VANES WHERE INDICATED ON PLANS. NO SQUARE THROAT OR ZERO RADIUS ELBOWS ALLOWED.

9. ALL DUCT BRANCH CONNECTIONS TO DIFFUSER OR GRILLES, TO OR FROM MAIN DUCTS, SHALL INCLUDE MANUAL VOLUME DAMPERS. ALL SPIN-IN FITTINGS SHALL BE CONICAL, RECTANGULAR

BRANCH DUCT TAKEOFFS SHALL HAVE 45° TAKEOFFS.

10. PROVIDE CONCEALED DAMPER REGULATORS OR ACCESS DOORS FOR ALL MANUAL VOLUME

DAMPERS LOCATED THAT ARE INACCESSIBLE. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING

TYPES. ALL FINAL ACCESS DOOR LOCATIONS SHALL BE APPROVED BY ARCHITECT PRIOR TO

INSTALLATION.

11. 24"x24" ACCESS DOORS SHALL BE PROVIDED FOR ALL MECHANICAL EQUIPMENT LOCATED ABOVE

GYPSUM BOARD CEILINGS. ALL FINAL ACCESS DOOR LOCATIONS SHALL BE APPROVED BY

ARCHITECT PRIOR TO INSTALLATION.

12. PROVIDE DIFFUSER AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES AND COORDINATE LOCATIONS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN AND ELECTRICAL

LIGHTING LAYOUT.

13. ALL DUCTWORK VISIBLE THROUGH RETURN OR SUPPLY GRILLES TO BE PAINTED FLAT BLACK.

14. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTS SHALL HAVE THE TRANSVERSE JOINTS,

LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS SEALED AIRTIGHT WITH DUCT SEALANT

(SMACNA SEAL CLASS "A").

15. COORDINATE EXACT LOCATIONS OF ALL ROOM THERMOSTATS AND/OR ROOM TEMPERATURE

SENSORS WITH ARCHITECT/OWNER PRIOR TO INSTALLATION.

16. BALANCE AIR SYSTEM TO QUANTITIES SHOWN, AND SUBMIT A COPY OF THE BALANCE REPORT TO

THE ENGINEER FOR REVIEW.

GENERAL ABBREVIATIONS

ø ROUND or DIAMETER

AAV AUTOMATIC AIR VENT

ABV ABOVE

AD ACCESS DOOR

AFF ABOVE FINISH FLOOR

AHU AIR HANDLING UNIT

AL ACOUSTIC LINED

AP ACCESS PANEL

APD AIR PRESSURE DROP

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

AWT AVERAGE WATER TEMPERATURE

BB BASEBOARD

BBD BACKDRAFT DAMPER

BFF BELOW FINISH FLOOR

BHP BRAKE HORSEPOWER

BG BELOW GROUND/GRADE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNITS PER HOUR

C CENTIGRADE

CC COOLING COIL

CD CEILING DIFFUSER

CFM CUBIC FEET PER MINUTE

CG CEILING GRILLE

CI CAST IRON

CLG CEILING

CO CLEANOUT

CMU CONCRETE MASONRY UNIT

CM CONDENSATE METER

CONC CONCRETE

CONN CONNECT or CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION

(D) DEMOLISH

DB DECIBEL or DRY BULB

DDC DIRECT DIGITAL CONTROL

DIA DIAMETER

DIM DIMENSION

DN DOWN

DPR DAMPER

DPS DIFFERENTIAL PRESSURE SWITCH

DWG DRAWING

(E) EXISTING

EA EACH

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EG EXHAUST GRILLE

ELEC ELECTRIC or ELECTRICAL

ELEV ELEVATION

EMCS ENERGY MANAGEMENT CONTROL

SYSTEM

ERV ENERGY RECOVERY VENTILATOR

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXST EXISTING

F FAHRENHEIT

FCO FLOOR CLEANOUT

FCU FAN COIL UNIT

FD FLOOR DRAIN

FD FIRE DAMPER

FFD FUNNEL FLOOR DRAIN

FF FINAL FILTER

FLR FLOOR

FPM FEET PER MINUTE

FPS FEET PER SECOND

FS FLOOR SINK

FSD COMBINATION FIRE/SMOKE DAMPER

FT FOOT/FEET

FTR FINNED TUBE RADIATION

FV FACE VELOCITY

GA GAGE or GAUGE

GAL GALLON

GALV GALVANIZED

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GRD GRILLE, REGISTER, OR DIFFUSER

H HEIGHT

HB HOSE BIBB

HD HEAD

HP HORSEPOWER

HRV HEAT RECOVERY VENTILATOR

HTG HEATING

HVAC HEATING, VENTILATION AND

AIR CONDITIONING

HWG HIGH WALL GRILLE

HWR HIGH WALL REGISTER

HZ HERTZ

ID INSIDE DIAMETER

IE INVERT ELEVATION

IN INCH or INCHES

INSUL INSULATION

INV INVERT

KH KICKSPACE HEATER

KW KILOWATT

KWH KILOWATT HOUR

L LENGTH

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LF LINEAR FOOT/FEET

LVG LEAVING

LWG LOW WALL GRILLE

LWR LOW WALL REGISTER

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MAV MANUAL AIR VENT

MBH 1000 BRITISH THERMAL UNITS

PER HOUR

MCA MINIMUM CIRCUIT AMPACITY

MCC MOTOR CONTROL CENTER

MFR MANUFACTURER

MOP MAXIMUM OVERCURRENT

PROTECTION

MUA MAKEUP AIR UNIT

MIN MINIMUM

MISC MISCELLANEOUS

MTD MOUNTED

MTG MOUNTING

(N) NEW

(NL) NEW LOCATION

N/A NOT APPLICABLE

N/C NORMALLY CLOSED

N/O NORMALLY OPEN

NC NOISE CRITERIA

N.I.C. NOT IN CONTRACT

NPT NATIONAL PIPE THREAD

NTS NOT TO SCALE

OA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

O/C ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

PVC PRESSURE CONTROL VALVE

PD PRESSURE DROP

PH PHASE

PLCS PLACES

POC POINT OF CONNECTION

POUA POINT OF USE ALARM

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH (GAGE)

(REL) RELOCATE/RELOACTED

RA RETURN AIR

RAG RETURN AIR GRILLE

REQD REQUIRED

R.O. ROUGH OPENING

RPBP REDUCED PRESSURE BACKFLOW

PREVENTER

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SD SMOKE DETECTOR

SF SUPPLY FAN

SHT SHEET

SIM SIMILAR

SL SOUNDLINING

SP STATIC PRESSURE

SQ SQUARE

SQ FT SQUARE FOOT/FEET

SS STAINLESS STEEL

STD STANDARD

TAB TESTING, ADJUSTING & BALANCING

THK THICK

TP TRAP PRIMER or TEST PLUG

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

TU TERMINAL UNIT

UBC UNIFORM BUILDING CODE

UFC UNIFORM FIRE CODE

UMC UNIFORM MECHANICAL CODE

UPC UNIFORM PLUMBING CODE

UG UNDERGROUND

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

VA VALVE

VAC VACUUM

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VRF VARIABLE REFRIGERANT FLOW

VTR VENT THRU ROOF

W WIDE

W/ WITH

W/O WITHOUT

WB WET BULB

WC WATER COLUMN

WCO WALL CLEANOUT

WG WATER GAGE

WGE WASTE GAS EVACUATION

WH WALL HYDRANT

WPD WATER PRESSURE DROP

WT WEIGHT

GENERAL PLUMBING NOTES

1. PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY TO CONSTRUCT A COMPLETE, OPERATIONAL PLUMBING SYSTEM FOR THE ENTIRE PROJECT AS SHOWN ON THESE DRAWINGS, INCLUDING ALL NECESSARY FEES AND PERMITS.

2. THE ENTIRE INSTALLATION SHALL CONFORM TO THE MOST RECENTLY ADOPTED REQUIREMENTS

OF THE PLUMBING CODE, AND ALL OTHER APPLICABLE CITY, COUNTY, STATE, AND FEDERAL

CODES AND REGULATIONS IN EFFECT AT THE DATE OF THE BID. CONFORM TO ANY CODES,

RULES, REGULATIONS AND REQUIREMENTS THAT THE PROJECT OWNER HAS.

3. PRIOR TO FABRICATION AND INSTALLATION, THE CONTRACTOR SHALL COORDINATE THE

INSTALLATION OF ALL PLUMBING WORK WITH ALL OTHER TRADES INCLUDING THE MECHANICAL

CONTRACTOR, FIRE PROTECTION CONTRACTOR, ELECTRICAL CONTRACTOR, GENERAL

CONTRACTOR, AND ANY CONTRACTOR HIRED DIRECTLY BY THE OWNER. WHERE CONFLICTS MAY

OCCUR, THEY SHALL BE RESOLVED PRIOR TO INSTALLATION.

4. THE WORKING DRAWINGS ARE DIAGRAMMATIC. BECAUSE OF THE SMALL SCALE OF THE

DRAWINGS, THEY DO NOT SHOW EVERY OFFSET, BEND OR ELBOW NECESSARY FOR THE

COMPLETE INSTALLATION IN THE SPACE PROVIDED. ALL LOCATIONS FOR PLUMBING EQUIPMENT

AND PIPING SHALL BE CHECKED AND COORDINATED WITH THE ARCHITECTURAL, MECHANICAL,

STRUCTURAL AND ELECTRICAL DRAWINGS.

5. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT

MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL FITTINGS, TRANSITIONS, VALVES, WORKING

CLEARANCES, AND OTHER DEVICES AND ACCESSORIES REQUIRED FOR A COMPLETE, WORKABLE

INSTALLATION.

6. PROVIDE PROPER PROVISIONS FOR EXPANSION OR MOVEMENT OF ALL PIPING.

7. PROVIDE WATER HAMMER ARRESTORS (SHOCK ABSORBERS) AT ALL PIPE LOCATIONS WHERE

VALVE CLOSURES MAY CAUSE WATER HAMMER OR RESULT IN EXCESSIVE PIPE VIBRATION OR

MOVEMENT (EXAMPLES INCLUDE FLUSH VALVES, SENSOR FAUCETS, AND WASHING MACHINES).

8. PROVIDE CLEANOUTS AS REQUIRED BY CODE, INCLUDING AT ALL SINKS, URINALS AND END OF

RUNS.

MECHANICAL SCOPE OF WORK

BASE BID:

- DEMOLISH DUCTWORK.

- CONSTRUCT NEW EXHAUST DUCTWORK, COMPRESSED AIR AND VACUUM PIPING, AND AIR

DEVICES FOR FUME HOOD AND MISCELLANEOUS LAB EQUIPMENT.

- INSTALL OWNER-PURCHASED FUME HOOD IN ROOM 306.

- INSTALL OWNER-PURCHASED FUME HOOD BLOWER ON EXTERIOR PLATFORM.

- SUPPLEMENT EXISTING HEATING SYSTEM WITH A NEW WALL-MOUNT HYDRONIC BOILER

AND NEW VRF MULTI-ZONE COOLING SYSTEM.

- RE-BALANCE EXISTING HVAC TO MAINTAIN NECESSARY ROOM PRESSURE DIFFERENTIALS

ALTERNATE 01:

- CONSTRUCT NEW EXHAUST DUCTWORK, COMPRESSED AIR AND VACUUM PIPING, AND AIR

DEVICES FOR FUME HOOD.

- INSTALL FUME HOOD IN ROOM 312.

- INSTALL FUME HOOD BLOWER ON EXTERIOR PLATFORM.

- RE-BALANCE EXISTING HVAC TO MAINTAIN NECESSARY ROOM PRESSURE DIFFERENTIALS

DESIGN CONDITIONS

LOCATION PENDLETON, OR

CLIMATE ZONE 5B (UMATILLA COUNTY)

OUTDOORS

SUMMER 97.1°F DB / 64.7°F WB

WINTER -2.0°F DB

INDOOR

COOLING 72°F

HEATING 70°F

VENTILATION PER ASHRAE 62.1-2022

ELEVATION 1,486 FT ABOVE SEA LEVEL

SHEET INDEX

SHEET NUMBER SHEET TITLE

MECHANICAL

M-001 GENERAL MECHANICAL NOTES

M-002 GENERAL MECHANICAL LEGENDS

M-101 MECHANICAL DEMO PLAN

M-201 MECHANICAL PLAN

MP-201 MECHANICAL PIPING PLAN

M-501 MECHANICAL DETAILS

M-502 MECHANICAL DETAILS

M-601 MECHANICAL DIAGRAMS

M-602 MECHANICAL CONTROL DIAGRAMS

M-701 MECHANICAL SCHEDULES

M-702 MECHANICAL SCHEDULES

CHECKED

DATE

COFFMAN ENGINEERS INC.C

48037 TUBBS RANCH ROAD

ADAMS, OR 97810

231290

02/28/2025

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

FINAL

TURNOVER

P:

\S

PO

\23

JO

BS

\23

A

RS

P

EN

DL

ET

ON

B

UI

LD

IN

G

RE

PA

IR

S\ 0.0

D W

GS

\M

\P

RO

JE

CT

E

BL

DG

3\2

0_ M-

2.D

W G.

_M

-0

: C

AM

PB

EL

L, RO

B : L

AS

T

SA

VE

D:

N ov em be r 2

7, : P

LO

T

DA

TE

: 2 /28

/25 www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

PENDLETON

BUILDING

REPAIRS

PROJECT E

REV DATE DESCRIPTION

TAH

DJP

GENERAL

MECHANICAL

LEGENDS

M-002

GENERAL LEGEND

THERMOSTAT. ADJACENT NUMBER

INDICATES TERMINAL UNIT CONTROLLED

HUMIDISTAT

SENSOR

CO2 SENSORCO2

T

H

S

PLUMBING FIXTURE TAG, SEE PLUMBING SCHEDULES

NOTES:

XX-X

SPECIFIC TO LOCATION(S) INDICATED.

A. NOTE APPLIES TO ENTIRE SHEET.

EXISTING

NEW

(E)

(N)

EXISTING (THIN)

NEW (MEDIUM)

POINT OF CONNECTION (POC)

EXISTING TO BE DEMOLISHED

MECHANICAL EQUIPMENT, SEE MECHANICAL SCHEDULES.XX-X

x

SD DUCT SMOKE DETECTOR

SP DUCT STATIC PRESSURE

LINETYPES:

B A

A B

DETAIL SYMBOL:

A = IDENTIFYING NUMBER

B = SHEET WHERE DETAIL IS SHOWN

SECTION SYMBOL:

A = IDENTIFYING NUMBER

B = SHEET WHERE DETAIL IS SHOWN

NEW LOCATION(NL)

RELOCATED(REL)

HVAC DUCTWORK LEGEND

DUCTWORK

24x12 S/A

DUCT SIZE

INSULATED DUCT

SOUND LINED DUCT

24x12ø

24ø ROUND DUCT

18ø24x12

SUPPLY AIR (SA)

OUTSIDE AIR (OSA)

RETURN AIR (RA)

EXHAUST AIR (EA)

DAMPERS

FIRE DAMPER (FD)

SMOKE DAMPER (SD)

BACKDRAFT DAMPER

MOTORIZED DAMPER

DUCT SYSTEM ABBREVIATIONS

M

SUPPLY AIRSA

OUTSIDE AIROSA

COMBUSTION AIRCA

RETURN AIRRA

TRANSFER AIRTA

EXHAUST AIREA

FLEXIBLE DUCT

DUCT SYMBOLS

DUCT END CAP

DUCT ACCESS DOOR

AD

EXHAUST AIR (EA) TERMINAL

X

CFM

AIRFLOW DIRECTION

SOUND ATTENUATOR

DUCT SIZES SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS OF DUCT. DUCT SIZE

SHOWN DOES NOT INCLUDE INSULATION OR LINING UNLESS NOTED OTHERWISE. SEE

BELOW FOR DUCT SIZE TAG LEGEND.

GRILLE, REGISTER, OR OPEN

DUCT

AIR TERMINAL

IDENTIFICATION

FLAT OVAL DUCT SIZE

(INCHES) FIRST

DIMENSION IS SIDE OF

DUCT SHOWN

DUCT SYSTEM ABBREVIATION

(NOT ALWAYS BE SHOWN)

RECTANGULAR DUCT

SIZE (INCHES) FIRST

DIMENSION IS SIDE OF

DUCT SHOWN

RECTANGULAR DUCT

TURNED UP/SECTION

ROUND/FLAT OVAL DUCT

TURNED UP/SECTION

RECTANGULAR DUCT

TURNED DOWN/AWAY

ROUND/FLAT OVAL DUCT

TURNED DOWN/AWAY

RECTANGULAR DUCT

TURNED UP/SECTION

ROUND/FLAT OVAL DUCT

TURNED UP/SECTION

RECTANGULAR DUCT

TURNED DOWN/AWAY

ROUND/FLAT OVAL DUCT

TURNED DOWN/AWAY

RECTANGULAR DUCT

TURNED UP/SECTION

ROUND/FLAT OVAL DUCT

TURNED UP/SECTION

RECTANGULAR DUCT

TURNED DOWN/AWAY

ROUND/FLAT OVAL DUCT

TURNED DOWN/AWAY

SUPPLY AIR (SA)

TERMINAL

RETURN AIR (RA) OR

TRANSFER AIR (TA) TERMINAL

FIRE/SMOKE DAMPER

(FSD)

VOLUME/BALANCING

DAMPER

CHANGE IN DUCT SIZE

AND/OR SHAPE

PIPING LEGEND

CS

CR

CWS

CWR

CONDENSER

WATER SUPPLY

CONDENSER

WATER RETURN

CHILLED WATER

SUPPLY

CHILLED WATER

RETURN

HWS

HWR

HEATING HOT

WATER SUPPLY

HEATING HOT

WATER RETURN

HGS

HGR

HEATING GLYCOL

SUPPLY

HEATING GLYCOL

RETURN

FOS

FOR

FUEL OIL SUPPLY

FUEL OIL RETURN

SMS

SMR

SNOWMELT

GLYCOL SUPPLY

SNOWMELT

GLYCOL RETURN

RL REFRIGERANT

LIQUID LINE

RS REFRIGERANT

SUCTION LINE

HRS

HIGH PRESSURE

REFRIGERANT

SUCTION LINE

GWS

GWR

GEOTHERMAL

WATER SUPPLY

GEOTHERMAL

WATER RETURN

G NATURAL GAS

PG PROPANE GAS

LPG LIQUID PETROLEUM

GAS

CA COMPRESSED AIR

LPS LOW PRESSURE

STEAM SUPPLY

LPR LOW PRESSURE

STEAM RETURN

LPC LOW PRESSURE

CONDENSATE

MPS MEDIUM PRESSURE

STEAM SUPPLY

MPR MEDIUM PRESSURE

STEAM RETURN

MPC MEDIUM PRESSURE

CONDENSATE

HPS HIGH PRESSURE

STEAM SUPPLY

HPR HIGH PRESSURE

STEAM RETURN

HPC HIGH PRESSURE

CONDENSATE

D CONDENSATE

DRAIN (D)

VAC VACUUM (VAC)

PLUMBING LEGEND

COLD WATER (CW) W SANITARY WASTE

ABOVE GRADE (W)

HOT WATER (HW)

HOT WATER

CIRCULATING (HWC)

140° HOT WATER

(HW)

140° HOT WATER

CIRCULATING (HWC)

140 HW

140 HWC

INDUSTRIAL COLD

WATER (ICW)ICW

IHW INDUSTRIAL HOT

WATER (IHW)

SOFT COLD WATER

(SCW)SCW

COLD WATER

FLUSHING SYSTEM

(FCW)

FCW

TEMPERED WATER

(TW)TW

NON-POTABLE

WATER (NPW)NPW

IRRIGATION

WATER (IW)IW

DEIONIZED WATER

(DI)DI

DISTILLED WATER

(DW)DW

BGW

SANITARY WASTE

BELOW GRADE

(BGW)

PW PUMPED WASTE

(PW)

OW OILY WASTE (OW)

V VENT - SANITARY (V)

AW ACID WASTE (AW)

AV ACID VENT (AV)

RV RELIEF VENT (RV)

RAIN LEADER (RD)RD

OVERFLOW RAIN

LEADER (ORD)ORD

STORM DRAIN (SD)SD

TRAP PRIMER (TP)TP

NATURAL GAS (G)G

PROPANE GAS

(PG)PG

PLUMBING SYMBOLS & FIXTURE TAGS

2" FD-1

4" FCO

4" RD-1

4" COG

4" ORD-1

WC-1

DRAIN SIZE (SEE PLANS)

DRAIN TYPE (SEE SCHEDULE)

CLEANOUT SIZE (SEE PLANS)

CLEANOUT TYPE (SEE SCHEDULE)

2 DFU DRAINAGE FIXTURE UNITS

(MAY NOT BE SHOWN)

400 SQFT

DRAIN SIZE (SEE PLANS)

DRAIN TYPE (SEE SCHEDULE)

AREA SERVED (MAY NOT BE SHOWN)

FIXTURE TYPE (SEE SCHEDULE)

2 CWFU

4 DFU

L-1

2 CWFU

2 HWFU

4 DFU

COLD WATER FIXTURE UNITS

HOT WATER FIXTURE UNITS

DRAINAGE FIXTURE UNITS

(SEE PLANS FOR

FIXTURE SYMBOL)

(FIXTURE UNITS MAY

NOT BE SHOWN)

4" WCO

CONDENSATE

DRAIN (D)D

VACUUM (VAC)VAC

COMPRESSED AIR

(CA)CA

2" FS-1

PLUMBING/PIPING SYMBOLS LEGEND

VALVE

GATE VALVE

BALL VALVE

GLOBE VALVE

PLUG VALVE

BUTTERFLY VALVE

SPECIALTY VALVE

OS & Y VALVE

STOP COCK

PRESSURE REDUCING

VALVE

PRESSURE REGULATING

VALVE

CHECK VALVE

SPRING CHECK VALVE

STRAINER

STRAINER W/

BLOWDOWN

BACKFLOW PREVENTER

BALANCING VALVE

AUTOMATIC BALANCING

VALVE

A

RELIEF VALVE

FUEL ANTI-SIPHON

VALVE

F

FUSIBLE OIL SAFETY

VALVE

MOTORIZED VALVE

NEEDLE VALVE

M M

SOLENOID VALVE

S S

AUTOMATIC CONTROL

VALVE

FLOW SWITCH

PRESSURE SWITCH

FS

PS

PIPE ELBOW DOWN

(OR AWAY)

PIPE ELBOW UP

(OR TOWARDS)

PIPE TEE DOWN

(OR AWAY)

PIPE TEE UP

(OR AWAY)

FLOW DIRECTION

PIPE SLOPE

& DIRECTION

REDUCER, CONCENTRIC

REDUCER, ECCENTRIC

UNION

FLANGES

BLIND FLANGE

END CAP

PT PLUG (TEST PORT)

FLEX CONNECTOR/

COUPLING

EXPANSION JOINT

EXPANSION GUIDE

PIPE ANCHOR

HOSE QUICK

DISCONNECT

HOSE THREAD DRAIN

BALL VALVE

HOSE BIBB

WALL HYDRANT

HOSE THREAD DRAIN

VALVE

FIRE DEPARTMENT

CONNECTION

WATER HAMMER

ARRESTOR

THERMOWELL

THERMOMETER

DIAL THERMOMETER

T

PRESSURE GAUGE

W/ COCK

P

PRESSURE GAUGE

W/ COCK & SIPHON

P

AIR VENT

A - AUTOMATIC

C - COIN

M - MANUAL

H - HIGH VOLUME

A

BASKET STRAINER

AIR FILTER W/

COALESCER & DRAIN

AIR FILTER W/

COALESCER, DRAIN,

REGULATOR & GAUGE

PUMP (SYMBOLIC -

ARROW INDICATES

FLOW DIRECTION)

WATER METERM

WATER HAMMER

ARRESTOR (PLAN)

V#

S=2%

A

B

2.3 23 1.7

AGRONOMY

LAB

S102

SHOWER

S101

REST.

S100

MECH.

S104

HALL

S107

OFFICE 1

S106

OFFICE 2 / STORAGE

HYDROLOGY

LAB

(E) AHU-003-01

8x8 x1

12"ø

(E) HWC-003-01

16"ø

"ø

16"ø

20x20

16"ø 16"ø 12"ø x1

S

(E) HWC-003-02

(E) HWC-003-03

S x1

2 E A

AB

OV

E/ x1 2 S

A

BE

LO

W

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

10"ø

8"ø 8"ø

8x8 10x10

30x12

24x12

10"ø10"ø

S

(E) EQ-003-01

(E) EQ-003-02

(E) EQ-003-03

DESIGN ALT 1:

DO NOT DEMO

DUCTWORK IN

THIS ROOM

PROJ. NO.

DRAWN

CHECKED

DATE

COFFMAN ENGINEERS INC.C

48037 TUBBS RANCH ROAD

ADAMS, OR 97810

231290

02/28/2025

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

FINAL

TURNOVER

P:

\S

PO

\23

JO

BS

\23

A

RS

P

EN

DL

ET

ON

B

UI

LD

IN

G

RE

PA

IR

S\ 0.0

D W

GS

\M

\P

RO

JE

CT

E

BL

DG

3\2

0_ M-

1.D

W G.

_M

-1

: C

AM

PB

EL

L, RO

B : L

AS

T

SA

VE

D:

F eb ru ar y 2

8, : P

LO

T

DA

TE

: 2 /28

/25 www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

PENDLETON

BUILDING

REPAIRS

PROJECT E

REV DATE DESCRIPTION

TAH

DJP

MECHANICAL DEMO

PLAN

M-101

KEY NOTES

1. CAP VERTICAL DUCT CONNECTED TO LAB SNORKEL ARMS FOR

CONNECTION TO NEW EXHAUST DUCT.

SCALE:1 MECHANICAL DEMO PLAN

1/4" = 1'-0"

GENERAL DEMO NOTES

A. THESE DRAWINGS HAVE BEEN PREPARED USING OWNER PROVIDED

RECORD DRAWINGS AND THROUGH FIELD OBSERVATIONS. VERIFY

EXISTING CONDITIONS AS THEY APPLY TO THIS PROJECT AND INCLUDE

IN BID A SUFFICIENT ALLOWANCE TO COVER ANY DISCREPANCY

BETWEEN THE DRAWINGS AND THE ACTUAL CONDITIONS AS THEY

CURRENTLY EXIST.

B. EXISTING WORK IS SHOWN WITH LIGHT LINES AND DEMO WORK IS

SHOWN WITH BOLD BROKEN LINES, TYP.

C. CONTRACTOR SHALL COORDINATE ANY SHUT DOWN OF SYSTEMS WITH

OWNER.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OF ANY

EQUIPMENT THE OWNER DOES NOT WISH TO RETAIN FOR FUTURE USE.

B

2.3 23 1.7

AGRONOMY

LAB

S102

SHOWER

S101

REST.

S100

MECH.

S104

HALL

S107

OFFICE 1

S106

OFFICE 2 / STORAGE

HYDROLOGY

LAB

(E) AHU-003-01

8x8 x1

12"ø

(E) HWC-003-01

16"ø

"ø

16"ø

20x20

16"ø 16"ø 12"ø x1

S

(E) HWC-003-02

(E) HWC-003-03

S x1

2 E A

AB

OV

E/ x1 2 S

A

BE

LO

W

"ø

"ø

"ø

"ø

"ø

"ø

"ø

"ø

10"ø

8"ø 8"ø

8x8 10x10

24x12

S

(E) EQ-003-01

(E) EQ-003-02

(E) EQ-003-03

AC-003-01

AC-003-02

CU-003-01

B-003-03

EF-003-02

FH-003-02

12"ø

AC-003-03

AC-003-04AC

-0

-0

AC

-0

-0

EF-003-01

"ø

E A

"ø

E A

EF-003-03

5'-0"

MIN.

5'- 0"

MI

N.

12"ø DN

1180 CFM

1180 CFM

DESIGN ALTERNATE 1

HWP-003-05

DESIGN ALT 1:

REBALANCE (E)

GRILLE TO 470 CFM

1-1/4" HHWS

1-1/4" HHWR

3"ø EA UP THRU ROOF 3"ø OA UP THRU ROOF

30x12 (E) GRILLE

135 CFM

T AC-003-06

T

AC-003-05

TAC-003-03

AC-003-04

24x24 (E)

DIFFUSER

375 CFM

TYP. 4

335 CFM

24x24 (E)

DIFFUSER

375 CFM

TYP. 4

TAC-003-01

AC-003-02

(E) HWC-003-01

24x24 (E)

DIFFUSER

250 CFM

(E) HWC-002

24x24 (E)

GRILLE

175 CFM

TYP. 2

24x24 (E)

DIFFUSER

175 CFM

TYP. 2

(E) HWC-03

(E) TRANSFER GRILLE

150 CFM TYP. 2

FH-003-01

24x24 (E)

GRILLE

150 CFM

36x12

1R (36x12)

1650 CFM

PROJ. NO.

DRAWN

CHECKED

DATE

COFFMAN ENGINEERS INC.C

48037 TUBBS RANCH ROAD

ADAMS, OR 97810

231290

02/28/2025

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

FINAL

TURNOVER

P:

\S

PO

\23

JO

BS

\23

A

RS

P

EN

DL

ET

ON

B

UI

LD

IN

G

RE

PA

IR

S\ 0.0

D W

GS

\M

\P

RO

JE

CT

E

BL

DG

3\2

0_ M-

1.D

W G.

_M

-2

: C

AM

PB

EL

L, RO

B : L

AS

T

SA

VE

D:

F eb ru ar y 2

8, : P

LO

T

DA

TE

: 2 /28

/25 www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

PENDLETON

BUILDING

REPAIRS

PROJECT E

REV DATE DESCRIPTION

TAH

DJP

MECHANICAL PLAN

M-201

GENERAL NOTES

KEY NOTES

1. DESIGN OF PLATFORMS FOR EF-003-01 AND EF-003-02 SHALL BE

DEFERRED TO THE CONTRACTOR. REFER TO DETAILS FOR ROUGH

DIMENSIONS.

2. DUCT SHALL BE TYPE 1 UNPLASTICIZED PVC. SLOPE AT 1/2" PER 1'-0"

TOWARDS FUME HOOD FOR DRAINAGE.

3. LAB EQUIPMENT EXHAUST SHALL BE AT LEAST 30 FT FROM AHU-003-01 OA

OPENING. BOILER FLUE SHALL BE AT LEAST 10 FT FROM AHU-003-01

OPENING.

4. LAB EQUIPMENT EXHAUST CONNECTED BY MOVEX ME-75 LOCAL FUME

EXTRACTION ARMS. EXHAUST FLOW RATE SHALL BE CONSTANT EVEN

WHEN ARMS ARE NOT IN USE.

5. CONNECT NEW WALL-MOUNT BOILER TO EXISTING BOILER SYSTEM. SEE

DETAIL FOR PIPING CONFIGURATION. COORDINATE LOCATION WITH

EXISTING ELECTRICAL PANEL. ROUTE PIPES SUCH THAT THEY DO NOT

PASS OVER ELECTRICAL EQUIPMENT.

6. AIR BALANCE FOR ROOM 306 IS (- 150) CFM.

7. AIR BALANCE FOR ROOM 312 IS (- 150) CFM FOR BOTH THE BASE DESIGN

AND DESIGN ALT 1.

8. LOCATE CONDENSING UNIT SUCH THAT ROOF OVERHANG DOES NOT

DRIP INTO UNIT. PROVIDE 12" TALL STAND AND CONCRETE SLAB

UNDERNEATH UNIT, INSTALL ACCORDING TO DETAIL 4/M-502.

9. PROVIDE DUCT SUPPORTS AT NO LESS THAN 10' INTERVALS. PROVIDE

DUCT SUPPORTS FOR VERTICAL AND HORIZONTAL (WIND) LOADS. USE

SUPPORT METHODS AND MATERIALS FROM SMACNA DUCT

CONSTRUCTION STANDARDS, AND SUBMIT FOR GOVERNMENT REVIEW.

10. REPLACE EXISTING GRILLE AND BRANCH DUCT WITH A LARGER GRILLE,

DUCWORK, AND BALANCING DAMPER FOR BASE BID ONLY.

11. NEW HEATING WATER PIPING FOR NEW BOILER SHALL CONNECT TO

EXISTING BOILER HEADER PIPING ON THE PRIMARY LOOP.

CLOSELY-SPACED TEE CONNECTING PRIMARY AND SECONDARY LOOPS

SHALL REMAIN UNMODIFIED.

A. EXISTING WORK IS SHOWN WITH LIGHT LINES AND NEW WORK IS SHOWN

WITH BOLD CONTINUOUS LINES, TYP. VERIFY THERMOSTAT PLACEMENT

WITH OWNER PRIOR TO ROUGH-IN. COORDINATE PLACEMENT WITH

ELECTRICAL CONTRACTOR AND LIGHT SWITCH LOCATIONS.

THERMOSTAT SHALL BE AT THE SAME ELEVATION AS LIGHT SWITCHES

(BETWEEN 30"-48" AFF)

B. MAINTAIN ACCESS TO ALL EXISTING DAMPERS FOR MAINTENANCE

PURPOSES.

SCALE:1 MECHANICAL PLAN

1/4" = 1'-0"

B

2.3 23 1.7

AGRONOMY

LAB

S102

SHOWER

S101

REST.

S100

MECH.

S104

HALL

S107

OFFICE 1

S106

OFFICE 2 / STORAGE

HYDROLOGY

LAB

1/2" VAC DN1/2" CA DN(E) 3/4" VAC DN

(E) 3/4" CA DN

1/2" CA DN1/2" VAC DN

AC-003-01

AC-003-02

CU-003-01

B-003-03

FH-003-02

AC-003-03

AC-003-04

1" CD

RL / RG

RL

/R

G

RL

/R G

1" CD

3/4 " C

D

RL / RG

RL / RG

RL / RG

RL / RG

1" C

D 1"

C D

1" CD

1" CD

1" C

D 1"

C D

1 1

HWP-003-05

(E) FS

3/4" CD

4 1/2" PG

DESIGN ALTERNATE 1

3/4" CD

3/4 " C

D 1/2

" P G

(E ) V

AC

(E ) C

A

1/2" CA DN

1/2" VAC DN FH-003-01

3/4" CD

(E) CA

(E) VAC

(N ) 1

/2" V

AC

AC

-0

-0

AC

-0

-0

5 PROJ. NO.

DRAWN

CHECKED

DATE

COFFMAN ENGINEERS INC.C

48037 TUBBS RANCH ROAD

ADAMS, OR 97810

231290

02/28/2025

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

FINAL

TURNOVER

P:

\S

PO

\23

JO

BS

\23

A

RS

P

EN

DL

ET

ON

B

UI

LD

IN

G

RE

PA

IR

S\ 0.0

D W

GS

\M

\P

RO

JE

CT

E

BL

DG

3\2

0_

MP

-2

.D W

G.

_M P-

1 :

C

AM

PB

EL

L, RO

B : L

AS

T

SA

VE

D:

F eb ru ar y 2

8, : P

LO

T

DA

TE

: 2 /28

/25 www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

PENDLETON

BUILDING

REPAIRS

PROJECT E

REV DATE DESCRIPTION

TAH

JTT

MECHANICAL PIPING

PLAN

MP-201

GENERAL NOTES

KEY NOTES

1. TERMINATE DRAIN PIPE 18" ABOVE GRADE WITH ELBOW TURNED DOWN.

2. PROVIDE FACTORY DESIGNED JOINTS FOR THE BRANCHING WITHIN THE

REFRIGERANT PIPING NETWORK. BASIS-OF-DESIGN IS DAIKIN "REFNET".

3. REFER TO DETAIL FOR COMPRESSED AIR AND VACUUM CONNECTIONS TO

FUME HOODS.

4. CONNECT NEW PROPANE PIPING TO EXISTING MANIFOLD.

A. VERIFY THERMOSTAT PLACEMENT WITH OWNER PRIOR TO ROUGH-IN.

COORDINATE PLACEMENT WITH ELECTRICAL CONTRACTOR AND LIGHT

SWITCH LOCATIONS. THERMOSTAT SHALL BE AT THE SAME ELEVATION

AS LIGHT SWITCHES (BETWEEN 30"-48" AFF).

B. MAINTAIN ACCESS TO ALL EXISTING DAMPERS FOR MAINTENANCE

PURPOSES.

SCALE:1 PIPING PLAN

1/4" = 1'-0"

'-0

H

EI

GH

T

TO

S

TR

UC

TU

RE

1/2" TURN BALL VALVE

AT REACHABLE HEIGHT

CONNECTION TO

VALVES IN HOOD

PANEL

SCALE:1

COMPRESSED AIR AND VACUUM

CONNECTIONS TO FUME HOOD

NTS

SCALE:3 FUME EXHAUST FAN SUPPORT STRUCTURE

NTS

'-2

SCALE:2 SUSPENDED PIPING (HYDRONIC)

NTS

FTG 7'-2"x7'-2"x1'-0"

W/ #5@12" OC EA WAY,

BOTTOM

1/2" VAC LINE1/2" CA LINE

FUME HOOD

D

EG

MA

X

NOTES

HANGER RODS WITH STIFFENERS.

ANGLE IRON OR MANUFACTURED STRUT

CROSS MEMBER.

RIGID BRACE (SHOWN) OR MULTIPLE CABLE

BRACES.

END VIEWEND VIEW

SIDE VIEW

SIDE VIEW

3 1 1

13 13

PIPE

PIPE

PIPE

ALL INSULATED PIPE 1-1/4"

AND LESS, CONTINUOUS

FIBERGLASS

UNISTRUT P1000

20 GA. GALVANIZED SHEET

METAL SLEEVE, 12" LONG MIN.

20 GA. GALVANIZED SHEET

METAL SLEEVE, 6" LONG MIN.

UNISTRUT P1843 HINGE CONNECTOR

TYPICAL EA. END

UNISTRUT P1000

LATERAL BRACECLEVIS RING

BLINE MODEL B2000 SERIES,

OR EQUIVALENT, PIPE CLAMPS

ALL INSULATED PIPE 1-1/2" AND LARGER IN

DIAMETER USE HYDROUS CALCIUM SILICATE LOAD

BEARING SUPPORT EQUAL TO CLEMENT TYPE HW

OR HIGH DENSITY POLYISOCYANURATE

(8) #5 VERTS W/ STD, 10"

LONG HOOK INTO FTG

(3) #3 TIES IN TOP 5" OF

PIER, REMAINDER AT 8"

OC

(4) 3/4" HEADED ANCHORS

@ 9" SQUARE. CENTERED

IN EA PIER. (10" EMBED)

FOUNDATION NOTES:

1. CONCRETE SHALL HAVE A MINIMUM 28-DAY

COMPRESSIVE STRENGTH OF 3000PSI. MAX

AGGREGATE SIZE SHALL BE 1" WITH 5-7% AIR

ENTRAINMENT.

2. MECHANICALLY VIBRATE ALL CONCRETE.

3. ANCHOR BOLTS SHALL BE HEADED OR HAVE A NUT AT

THE BOTTOM END. ANCHORS SHALL BE ASTM F1554,

GRADE 36. ALL BOLTS AND ANCHORS SHALL HAVE

A563 NUTS AND F436 WASHERS.

4. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR

STRUCTURAL ENGINEER REVIEW PRIOR TO

FABRICATION, ERECTION, INSTALLATION. SUBMIT

DRAWINGS FOR REINFORCING STEEL, GROUT, AND

CONCRETE MIX DESIGN.

5. DEFERRED SUBMITTAL FOR SUPPORT FRAME SHALL

BE DESIGNED BY OTHERS AND SUBMITTED FOR

REVIEW. DEFERRED SUBMITTAL SHALL BEAR THE

SEAL OF A CIVIL OR STRUCTURAL ENGINEER

REGISTERED WITHIN THE AUTHORITY HAVING

JURISDICTION.

6. FOUNDATION DESIGN IS BASED ON AN ASSUMED

ALLOWABLE SOIL BEARING PRESSURE OF 1500PSF.

7. BOTTOM OF FOUNDATION SHALL ALIGN WITH

EXISTING FOUNDATION AS SHOWN. BOTTOM OF

FOUNDATION SHALL BE A MINIMUM OF 2'-0" BELOW

ADJACENT GRADE FOR FROST PROTECTION. DO NOT

UNDERMINE EXISTING BUILDING FOUNDATION DURING

CONSTRUCTION.

8. ALL EXTERIOR STEEL SHALL BE HOT-DIP GALVANIZED

IN ACCORDANCE WITH ASTM A123 AND A365. ALL

FIELD-CUT STEEL, FIELD DRILLED HOLES, OR DAMAGE

TO GALVANIZING SHALL BE REPAIRED PER ASTM A780.

9. ALL REINFORCING STEEL SHALL BE ASTM A615 GRADE

60. ALL TIES SHALL USE 135DEG HOOKS AT THE

CORNER.

10. #5 BARS SHALL USE CLASS "B" TENSION LAP SPLICES

PER ACI. SPLICE LENGTH SHALL BE A MINIMUM OF 3'-4"

FOR #5 BARS.

NOTE:

THE STAND, CONNECTION OF THE STAND TO THE

FOUNDATION, AND CONNECTION OF THE BLOWER AND

EXHAUST STACK TO THE STAND ARE A DELEGATED

DESIGN. CONTRACTOR SHALL PROVIDE A DEFERRED

SUBMITTAL FOR THE STRUCTURAL DESIGN AND

DETAILING OF THE STAND, ANCHORAGE OF THE

BLOWER AND EXHAUST STACK TO THE STAND, AND

ANCHORAGE OF THE STAND TO THE SLAB. PROVIDE

CALCULATIONS STRUCTURAL DRAWINGS AND AND

DETAILS SHALL BE STAMPED BY A STRUCTURAL

ENGINEER LICENSED WITHIN THE AUTHORITY HAVING

JURISDICTION

10'-0" MINIMUM EXHAUST

STACK SUPPORTED BY

FRAME

EXISTING GRADE

9" F

IE

LD

VE

RI

FY

(E) BLDG

FOUNDATION

2'- 6"

F

IE

LD

VE

RI

FY

3"

1-1/2" NON-SHRINK

GROUT

16" SQ PIERS.

TYP (4) PLCS

BLOWER SUPPORT

PLATFORM 72"Wx70"L

(DEFERRED DESIGN)

3" GAP

MIN.

PIPE COLLAR AND BRACING

BY FRAME DESIGNER.

(E) BLDG

2" CLR

BOND BREAKER

BETWEEN NEW AND

EXISTING CONCRETE,

BY CONTRACTOR

3" C

LR

NOTES:

1. UNLESS NOTED OTHERWISE, LAP SPLICES IN CONCRETE BEAMS, WALLS, SLABS AND

FOOTINGS SHALL BE CLASS "B" TENSION LAP SPLICES AND LAP SPLICES IN CONCRETE

COLUMNS SHALL BE COMPRESSION LAP SPLICES.

2. STAGGER ALTERNATE SPLICES A MINIMUM OF ONE LAP LENGTH.

3. TOP BARS ARE ANY HORIZONTAL BARS PLACED SO THAT MORE THAN 12" OF FRESH

CONCRETE IS CAST IN THE MEMBER BELOW THE REINFORCEMENT.

4. REINFORCING YIELD STRENGTH Fy = 60 KSI.

5. FOR BEAMS AND COLUMNS ACI 25.4.2.2 CASE 1 APPLIES (CONCRETE COVER AT LEAST

ONE BAR DIAMETER AND CENTER TO CENTER SPACING AT LEAST TWO BAR DIAMETERS).

6. FOR ALL OTHER MEMBERS CASE 1 APPLIES (CONCRETE COVER AT LEAST ONE BAR

DIAMER NAD CENTER TO CENTER SPACING AT LEAST THREE BAR DIAMETERS).

INSTALL FUME HOOD(S) PER

MANUFACTURER'S

INSTRUCTIONS

'-0

PROJ. NO.

DRAWN

CHECKED

DATE

COFFMAN ENGINEERS INC.C

48037 TUBBS RANCH ROAD

ADAMS, OR 97810

231290

02/28/2025

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

FINAL

TURNOVER

P:

\S

PO

\23

JO

BS

\23

A

RS

P

EN

DL

ET

ON

B

UI

LD

IN

G

RE

PA

IR

S\ 0.0

D W

GS

\M

\P

RO

JE

CT

E

BL

DG

3\2

0_ M-

1.D

W G.

_M

-5

: C

AM

PB

EL

L, RO

B : L

AS

T

SA

VE

D:

F eb ru ar y 2

8, : P

LO

T

DA

TE

: 2 /28

/25 www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

PENDLETON

BUILDING

REPAIRS

PROJECT E

REV DATE DESCRIPTION

TAH

DJP

MECHANICAL

DETAILS

M-501

2.28.2025 Detail 3/M-501 only

CEILING CASSETTE UNIT

CEILING

STRUCTURE

REFRIGERANT PIPING,

SIZING BY MANUFACTURER

CONDENSATE DRAIN, SEE PIPING

PLANS FOR SIZE AND ROUTING.

SLOPE PIPING AT 1/8"=1'-0" TYP.

NOTES

HANGER RODS WITH STIFFENERS.

RIGID BRACE (SHOWN) OR MULTIPLE CABLE

BRACES.

SEE STRUCTURAL FOR MEMBER SIZING

AND TYPE.

END VIEW

SIDE VIEW

PIPE

CLEVIS RING

PIPE

SCALE:2 SEISMIC BRACING FOR REFRIGERANT PIPING

NTS

SCALE:3 BOILER SCHEMATIC

NTS

SCALE:4 VRF HEAT PUMP MOUNTING

NTS

SCALE:1 VRF FAN COIL UNIT CEILING CASSETTE

NTS

6" DRIP LEG WITH CAP

CONNECTION TO

EQUIPMENT

CERTIFIED PG FLEX LINE

PG SUPPLY LINE

G

PG SUPPLY LINE

CONNECTION TO

EQUIPMENT

CERTIFIED PG FLEX LINE

6" DRIP LEG WITH CAP

LISTED PG VALVE

UNION

PIPE REDUCER,

IF REQUIRED

UNION G

LISTED PG

VALVE

PIPING FROM

ABOVE

SUPPLY FROM ABOVE

HORIZONTAL SUPPLY

VERTICAL OFFSET

FOR DRIP LEG

VRF HEAT PUMP UNIT

SECURE HEAT PUMP TO STAND

ANCHOR BOLTS, TYP. OF 2 EACH LEG

CRUSHED ROCK EXTENDING AT LEAST 12" BEYOND

EDGE OF CONCRETE PAD TO ALLOW CONDENSATE

TO DRAIN WHEN UNIT ENTERS DEFROST MODE.

NOTE:

CONTRACTOR SHALL PROVIDE A DEFERRED

SUBMITTAL DETAILING ANCHORAGE OF UNIT TO

STAND AND STAND TO SLAB. CALCULATIONS

AND DETAILS SHALL BE STAMPED BY A

STRUCTURAL ENGINEER LICENSED IN THE

STATE OF OREGON.

5" THICK W/ #3 REBAR @ 12" OC, CENTERED. PAD

SHALL EXTEND BEYOND THE STAND BY A MINIMUM

OF 6" IN ALL DIRECTIONS.

12" TALL STAND, DIVERSITECH

OR EQUAL.

MUST SUPPORT UNIT WEIGHT

WITH FACTOR OF SAFETY OF 2.0.

1 1/4"

BOILER F

FLOW

SWITCH STRAINER

FLOW MEASURING

& BALANCE VALVE

CHECK VALVE

PUMP

DRAIN WITH HOSE FITTING

ASME

RELIEF VALVE

ROUTE TO (E)

GLYCOL TANK

ROUTE

TO DRAIN

ACID NEUTRALIZATION

TANK

D

SCALE:5 PROPANE EQUIPMENT CONNECTION

NTS

CONCRETE SHALL HAVE A MINIMUM 28-DAY

COMPRESSIVE STRENGTH OF 3000 PSI. MAX

AGGREGATE SIZE SHALL BE 1" WITH 5-7% AIR

ENTAINMENT.

HWP-003-05

B-003-03

PROJ. NO.

DRAWN

CHECKED

DATE

COFFMAN ENGINEERS INC.C

48037 TUBBS RANCH ROAD

ADAMS, OR 97810

231290

02/28/2025

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

FINAL

TURNOVER

P:

\S

PO

\23

JO

BS

\23

A

RS

P

EN

DL

ET

ON

B

UI

LD

IN

G

RE

PA

IR

S\ 0.0

D W

GS

\M

\P

RO

JE

CT

E

BL

DG

3\2

0_ M-

2.D

W G.

_M

-5

: C

AM

PB

EL

L, RO

B : L

AS

T

SA

VE

D:

F eb ru ar y 2

8, : P

LO

T

DA

TE

: 2 /28

/25 www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

PENDLETON

BUILDING

REPAIRS

PROJECT E

REV DATE DESCRIPTION

TAH

RKC

MECHANICAL

DETAILS

M-502

SCALE:1

BUILDING SYSTEM AIR FLOW DIAGRAM

NTS

1180 335

EF-003-01 EF-003-03

FH-003-01

AC-003-01

AC-003-02

1351500 1180

EF-003-02

FH-003-01

AC-003-03

AC-003-04

16501500

DESIGN

ALT 1

DESIGN ALT 1

150 150

AC-003-05 AC-003-06

175175 175175

306 CLEAN 312 DIRTY S101 RESTROOM/

S102 SHOWER

S104 HALLWAY S106 OFFICE S107 OFFICE

AHU-003-01

PROJ. NO.

DRAWN

CHECKED

DATE

COFFMAN ENGINEERS INC.C

48037 TUBBS RANCH ROAD

ADAMS, OR 97810

231290

02/28/2025

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

FINAL

TURNOVER

P:

\S

PO

\23

JO

BS

\23

A

RS

P

EN

DL

ET

ON

B

UI

LD

IN

G

RE

PA

IR

S\ 0.0

D W

GS

\M

\P

RO

JE

CT

E

BL

DG

3\2

0_ M-

1.D

W G.

_M

-6

: C

AM

PB

EL

L, RO

B : L

AS

T

SA

VE

D:

F eb ru ar y 1

2, : P

LO

T

DA

TE

: 2 /28

/25 www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

PENDLETON

BUILDING

REPAIRS

PROJECT E

REV DATE DESCRIPTION

TAH

RKC

MECHANICAL

DIAGRAMS

M-601

GENERAL EXHAUST FAN CONTROL DIAGRAM

(EF-003-03)

SEQUENCE OF OPERATION:

DDC SHALL INITIATE MODES OF OPERATION. FAN SHALL RUN 24/7/365.

ALARMS REPORTED AT THE OPERATOR WORK STATION:

FAN FAILURE

DOSTART/STOP

DISTATUS

SCALE:2 EXHAUST FAN CONTROL DIAGRAM

NTS

SPLIT SYSTEM CONTROL DIAGRAM

(TYP ALL)

SEQUENCE OF OPERATION:

SPLIT SYSTEMS ARE PART OF THE VARIABLE REFRIGERANT FLOW

SYSTEM AND HAVE INTEGRAL CONTROLS. THE BAS SHALL MONITOR

STATUS, POINTS, AND FAULTS THROUGH BACNET.

THE SPLIT SYSTEM SHALL PROVIDE SUPPLEMENTAL COOLING WHEN

THE CENTRAL AC IS UNABLE TO MEET THE SETPOINT OF 72°F

THERMOSTAT SETPOINTS:

- OCCUPIED MODE: COOLING 75°F, 5°F DEADBAND.

- UNOCCUPIED MODE: COOLING 80°F (ADJ)

POINTS TO MONITOR:

- SPACE TEMPERATURE

- COOLING SIGNAL

FUME EXHAUST CONTROL DIAGRAM

(TYP EF-003-01 AND EF-003-02)

SEQUENCE OF OPERATION:

FUME EXHAUST FANS ARE CONTROLLED BY THE LABCONCO FUME

HOODS. THE BAS SHALL MONITOR STATUS.

FUME HOODS AND FANS SHALL RUN 24/7/365.

POINTS TO MONITOR:

- - STATUS

BDD

BOILER

B-003-01

RESET

ALARM

A R

AO-0-

B1-4-

ALARMRB1-5-

HW

P-

3-

HW

P-

3-

HW

P-

3-

ALARMRB1-#-

START/STOP

PUMP STATUS

R R

BO-0-

B1-2-

START/STOP

PUMP STATUS

R R

BO-1-

B1-3-

HWP-003-03

HWP-003-04

TAI-0-

TAI-1-

HWR FROM

SYSTEM

HWR TO

SYSTEMHOT WATER

SUPPLY TEMP

HOT WATER

RETURN TEMP

SCALE:1

HOT WATER SYSTEM DIAGRAM

NTS

BOILER SEQUENCE OF OPERATION:

2" HWR

2" HWR 2" HWS 2" HWS 2" HWS

1 1 /4"

H W

S

1 1 /4"

H W

S

1 1 /4"

H W

S

1 1/4" HWR

BOILER

B-003-02

BOILER

B-003-03

EXHAUST AIR

OUTSIDE

AIR

M

EA DAMPER

T

AO

T

AO

AO

M

DP

AI

EXHAUST

DISCHARGE

AIR TEMP

OSA

DAMPER

DOSTART/STOP

AOFAN SPEED

DIFAN STATUS

T

AI

HRU

DISCHARGE

AIR TEMP

X

D

C

H

M

DI

COMPRESSOR

FAULTAO

COOLING

STAGE

T

DO

LOW LIMIT

SWITCH

AO VALVE

POSITION

AO

START/STOPDO

FAN SPEED

DI FAN STATUS

T

AI

DISCHARGE

AIR TEMP

DP

AI

DP

AI

T

AI

RETURN

AIR TEMP

RETURN AIR

SUPPLY AIR

PLATE HEAT

EXCHANGER

HWR

HWS

AIR HANDLING UNIT (AHU-003-01) CONSTANT VOLUME, HW COIL/DX COOLING COIL, 100% OA:

EXISTING SYSTEM POINTS/CONTROLS ARE TO REMAIN UNCHANGED, EXCEPT WHERE MODIFIED BY THE REQUIREMENTS IN

THIS SEQUENCE OF OPERATION.

1. GENERAL: UNIT TO OPERATE UNDER THE FOLLOWING MODES: OCCUPIED, SHUTDOWN, AND UNOCCUPIED. HOA

SWITCHES ON GRAPHIC SCREENS OR TEXT DIALOG BOXES MAY OVERRIDE ON/OFF EQUIPMENT.

A. EQUIPMENT CONTROLLER TO RECEIVE SIGNAL FROM BAS, WHICH INITIATES MODE.

2. OCCUPIED MODE:

A. OCCUPIED MODE INITIATED FROM CONTROLLER BASED ON TIME OF DAY OR OPERATOR INPUT.

B. NORMALLY CLOSED OUTSIDE AIR INTAKE DAMPER AND EXHAUST AIR DAMPER OPENS. PROVIDE SUFFICIENT

DELAY IN FAN START/STOP TO ALLOW DAMPERS TO OPEN/CLOSE WITHOUT CAUSING DAMAGE.

C. SUPPLY FAN RUNS CONTINUOUSLY AT SCHEDULED AIRFLOW.

D. EXHAUST FAN RUNS CONTINUOUSLY AT SCHEDULED AIRFLOW.

E. DISCHARGE AIR TEMPERATURE SETPOINT: OPERATE THE HEATING COIL AND DX COOLING COIL IN SEQUENCE

TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT.

F. WHEN THE LAT FROM THE ENERGY RECOVERY CORE IS 2°F LOWER THAN THE DAT SETPOINT, MODULATE THE

3-WAY HEATING CONTROL VALVE AS NECESSARY TO MAINTAIN THE DAT SETPOINT.

G. WHEN THE LAT FROM THE ENERGY RECOVERY CORE IS 2°F HIGHER THAN THE DAT SETPOINT, THE DX COOLING

COIL AND COMPRESSORS RUN AS NECESSARY VIA INTERNAL CONTROLS TO MAINTAIN THE UNIT DAT.

H. DISCHARGE AIR TEMPERATURE TO BE CONTINUOUSLY RESET BASED ON ZONE DEMAND. THE DISCHARGE AIR

TEMPERATURE SETPOINT SHALL BE RESET TO THE LOWEST DAT TO SATISFY SPACE TEMPERATURE

SETPOINTS.

3. SHUTDOWN MODE:

A. SUPPLY FAN IS OFF.

B. EXHAUST FAN IS OFF.

C. OUTSIDE AIR AND EXHAUST AIR DAMPERS CLOSE.

D. DX COOLING OFF.

E. HEATING WATER CONTROL VALVE POSITIONED TO BYPASS HEATING COIL.

4. UNOCCUPIED MODE:

A. MORNING WARM UP/COOL DOWN: OPTIMAL START PROGRAM INITIATES MORNING WARM UP/COOL DOWN

CONTROL. UNIT TO OPERATE IN OCCUPIED MODE UNTIL RETURN AIR TEMPERATURE REACHES 70 °F FOR 30

MINUTES PRIOR TO SCHEDULED OCCUPIED MODE.

B. NIGHT SETBACK/SETUP: WHEN ANY SPACE TEMPERATURE DROPS TO 60°F OR BELOW (HEATING) OR RISES TO 85F OR ABOVE (COOLING), UNIT TO OPERATE IN OCCUPIED MODE UNTIL RETURN AIR TEMPERATURE REACHES 70°F FOR 30 MINUTES PRIOR TO SCHEDULED OCCUPIED MODE UNTIL SPACE TEMPERATURE RISES TO 63°F

(HEATING) OR LOWERS TO 82°F (COOLING).

C. NIGHT PURGE: INITIATED WHEN OUTDOOR AIR TEMPERATURE IS 65°F OR BELOW AND ANY SPACE TEMPERATURE IS 75°F OR ABOVE. SUPPLY FANS AND DAMPERS TO OPERATE IN OCCUPIED MODE. 3-WAY HEATING COIL TO CONTROL VALVE TO BE CLOSED TO HEATING COIL AND DX COOLING COIL TO BE DISABLED.

WHEN SPACES ARE 70°F OR BELOW FOR 30 MINUTES, SWITCH TO SHUTDOWN MODE.

D. UNOCCUPIED MODE OVERRIDE: UPON RECEIVING AN OVERRIDE SIGNAL FROM A SPACE MOUNTED TEMPERATURE SENSOR, CONTROLLER CHANGE BUILDING TO OCCUPIED MODE FOR PERIOD OF 2 HOURS (ADJ.).

5. ALARMS/SAFETIES:

A. WHEN SMOKE DETECTOR IN RETURN DUCT DETECTS SMOKE IN AIRSTREAM, CONTROLLER INITIATES

SHUTDOWN MODE AND GENERATES ALARM.

B. WHEN LOW LIMIT DETECTION THERMOSTAT UPSTREAM OF COOLING COIL DETECTS TEMPERATURE BELOW

38°F, CONTROLLER INITIATES SHUTDOWN MODE AND GENERATES ALARM.

C. CURRENT TRANSFORMER IN SUPPLY FAN AND EXHAUST FAN CIRCUITS SIGNALS FAN/CONTROLLER FAILURE.

D. DIFFERENTIAL PRESSURE SWITCHES LOCATED ACROSS EACH FILTER BANK GENERATES AN ALARM WHEN

STATIC PRESSURE DROP EXCEEDS 0.75" W.G. FOR PRE-FILTERS AND 1.20" W.G. FOR FINAL FILTERS.

SCALE:3 (E) AIR HANDLING UNIT CONTROL DIAGRAM

NTS

GENERAL: BOILER B-003-01 AND BOILER B-003-02 OPERATE IN

- LEAD-STANDBY ORDER. BOILER B-003-03 PROVIDES

ADDITIONAL HEAT WHEN THE LEAD BOILER ALONE CANNOT

MEET THE HOT WATER SUPPLY TEMPERATURE SETPOINT.

- EQUIPMENT CONTROLLER TO RECEIVE SIGNAL FROM BAS,

WHICH INITIATES EITHER OCCUPIED, UNOCCUPIED, OR

SHUTDOWN MODE.

- BAS TO ROTATE LEAD-STANDBY BOILER ORDER TO MAINTAIN

EVEN RUNTIME.

OCCUPIED MODE:

- UPON PROOF OF LEAD PUMP OPERATION FROM BOILER FLOW

SWITCH, LEAD BOILER IS ENABLED TO MAINTAIN HOT WATER

SUPPLY TEMPERATURE OF 180 °F (ADJ).

- IF HOT WATER SUPPLY TEMPERATURE FALLS BELOW 170°F,

BOILER B-003-03 IS ENABLED UNTIL HOT WATER SUPPLY TEMP

MEETS SETPOINT (+/- 5°F).

- STANDBY BOILER TO BE ENABLED IF LEAD BOILER FAILS.

- WHEN A BOILER IS SHUTDOWN, IT'S RESPECTIVE PRIMARY

PUMP SHALL OPERATE FOR AN ADDITIONAL 5 MINUTES (ADJ.)

BEFORE ALSO SHUTTING DOWN.

- THE STATUS FOR THE PRIMARY PUMP AT EACH BOILER SHALL

BE MONITORED. IF THE LEAD PUMP IS COMMANDED ON AND

FAILS, IT'S ASSOCIATED BOILER SHALL BE LOCKED OUT AND

ALARMED AT THE OPERATOR WORKSTATION, LAG BOILER AND

PUMP SHALL THEN BE ENABLED.

- THE BOILER HEATING WATER SUPPLY TEMPERATURE

SETPOINT IS TO BE RESET BY BAS SIGNAL ON A LINEAR SCALE,

WITH THE MAXIMUM AND MINIMUM SUPPLY TEMPERATURES AS

FOLLOWS.

OUTSIDE AIR TEMP. HEATING WATER SUPPLY TEMP.

20°F OR LOWER 180°F (MAX)

65°F AND ABOVE 155°F (MIN)

UNOCCUPIED MODE:

- LEAD BOILER IS OFF

- IF ONE ZONE CALLS FOR HEAT AND THE OUTSIDE AIR

TEMPERATURE IS 60°F OR BELOW, LEAD BOILER SHALL BE

ENABLED UPON PROOF OF LEAD PUMP OPERATION.

- LEAD BOILER TO OPERATE WHEN UNIT IS IN MORNING

WARM-UP.

SHUTDOWN:

- ALL BOILERS OFF.

- ALL PUMPS OFF.

ALARM:

- BOILER FAILURE.

- PUMP FAILURE.

EXISTING SYSTEM POINTS/CONTROLS ARE TO REMAIN UNCHANGED,

EXCEPT WHERE MODIFIED BY THE REQUIREMENTS IN THIS SEQUENCE

OF OPERATION.

GENERAL: UNIT TO OPERATE UNDER THE FOLLOWING MODES:

OCCUPIED, SHUTDOWN, AND UNOCCUPIED. HOA SWITCHES ON

GRAPHIC SCREENS OR TEXT DIALOG BOXES MAY OVERRIDE ON/OFF

EQUIPMENT.

- EQUIPMENT CONTROLLER TO RECEIVE SIGNAL FROM BAS,

WHICH INITIATES MODE.

- BAS TO ROTATE LEAD-STANDBY PUMP ORDER TO MAINTAIN

EVEN RUNTIME.

OCCUPIED MODE:

- LEAD HEATING AFTER PUMP TO OPERATE WHEN OUTDOOR AIR

TEMPERATURE IS 60°F OR BELOW.

- STANDBY HEATING WATER PUMP TO BE ENABLED IF LEAD

PUMP FAILS.

UNOCCUPIED MODE:

- LEAD PUMP IS OFF.

- LEAD PUMP TO OPERATE WHENEVER OUTSIDE AIR

TEMPERATURE IS 60°F OR BELOW AND ONE OR MORE ZONES

ARE CALLING FOR HEAT.

- LEAD HEATING WATER PIMP TO OPERATE WHEN UNIT IN

MORNING WARM UP.

SHUTDOWN:

- LEAD PUMP IS OFF.

- STANDBY PUMP IS OFF.

ALARMS:

- CURRENT TRANSFORMER IN PUMP CIRCUIT SIGNALS PUMP

FAILURE.

(E) HEATING WATER PUMPS (HWP-003-03 & 04):

PROJ. NO.

DRAWN

CHECKED

DATE

COFFMAN ENGINEERS INC.C

48037 TUBBS RANCH ROAD

ADAMS, OR 97810

231290

02/28/2025

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

FINAL

TURNOVER

P:

\S

PO

\23

JO

BS

\23

A

RS

P

EN

DL

ET

ON

B

UI

LD

IN

G

RE

PA

IR

S\ 0.0

D W

GS

\M

\P

RO

JE

CT

E

BL

DG

3\2

0_ M-

2.D

W G.

_M

-6

: C

AM

PB

EL

L, RO

B : L

AS

T

SA

VE

D:

F eb ru ar y 2

8, : P

LO

T

DA

TE

: 2 /28

/25 www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

PENDLETON

BUILDING

REPAIRS

PROJECT E

REV DATE DESCRIPTION

TAH

RKC

MECHANICAL

CONTROL

DIAGRAMS

M-602

SEISMIC AND VIBRATION CONTROL SEISMIC RESTRAINT PROVISIONS

TAG EQUIPMENT LEVEL RESTRAINTS BASE FLEXIBLE

CONNECTORS

VIBRATION

ISOLATORS DEFLECTION (IN)

SEISMIC SUPPORTS ARE REQUIRED FOR THIS PROJECT FOR ALL MECHANICAL AND ELECTRICAL EQUIPMENT AND DISTRIBUTION SYSTEMS. SEISMIC RESTRAINT CALCULATIONS MUST BE PROVIDED BY THE PRODUCT MANUFACTURER FOR ALL CONNECTIONS OF EQUIPMENT TO THE STRUCTURE. ALL RESTRAINING DEVICES SHALL HAVE TESTING DATA TO VALIDATE MAXIMUM RESTRAINT RATINGS. PREAPPROVALS BASED ON INDEPENDENT TESTING ARE PREFERRED TO PREAPPROVALS BASED ON CALCULATIONS. CALCULATIONS (INCLUDING THE COMBINING OF TENSILE AND SHEAR LOADING) TO SUPPORT SEISMIC RESTRAINT DESIGNS MUST BE STAMPED BY A REGISTERED PROFESSIONAL ENGINEER LICENSED IN OREGON. THE ENGINEERING ANALYSIS MUST INDICATE CALCULATED DEAD LOADS, STATIC SEISMIC LOADS, AND CAPACITY OF MATERIALS UTILIZED FOR CONNECTIONS TO EQUIPMENT STRUCTURE. ANALYSIS MUST DETAIL ANCHORING METHODS, BOLT

DIAMETER, EMBEDMENT, AND/OR WELDED LENGTH.

ALL SEISMIC RESTRAINT DEVICES SHALL BE DESIGNED TO ACCEPT, WITHOUT FAILURE, THE FORCES PRESCRIBED PER THE ASCE 7 ACTING THROUGH THE EQUIPMENT CENTER OF GRAVITY. OVERTURNING MOMENTS MAY EXCEED FORCES AT GROUND LEVEL AND MAY BE RESISTED BY SEISMIC RESTRAINTS, SUPPORT, OR ANCHORAGE. ANCHORAGE TO CONCRETE MUST HAVE AN ICC TESTING REPORT THAT ADHERES TO THE REQUIREMENTS OF THE IBC AND MUST BE RATED FOR SEISMIC RESTRAINT IN CRACKED CONCRETE USING THE APPROPRIATE REDUCTION FACTORS PER ACI 318 APPENDIX D. ACCEPTABLE ANCHORS INCLUDE THE HILTI KWIK BOLT TZ AND SIMPSON STRONG BOLT WEDGE ANCHORS OR HILTI HIT-RE 500-SD AND SIMPSON SET XP EPOXY ANCHORS. EPOXIES ARE NOT ACCEPTABLE FOR USE IN

OVERHEAD APPLICATIONS.

EF-003-01 UPBLAST FUME HOOD EXHAUST FAN ABOVE ROOF A D Y 3 0.75

EF-003-02 UPBLAST FUME HOOD EXHAUST FAN ABOVE ROOF A D Y 3 0.75

EF-003-03 WALL-MOUNT FUME EXHAUST FAN CEILING A A Y 2 0.25

B-003-03 PROPANE HYDRONIC BOILER GRADE A A Y 1 0.25

HWP-003-05 BOILER CIRCULATOR ROOM NR A Y 2 0.25

AC-003-01 VRF CEILING CASSETTE CEILING AM A Y 3 0.25

AC-003-02 VRF CEILING CASSETTE CEILING AM A Y 3 0.25

AC-003-03 VRF CEILING CASSETTE CEILING AM A Y 3 0.25

AC-003-04 VRF CEILING CASSETTE CEILING AM A Y 3 0.25

AC-003-05 VRF WALL MOUNT UNIT ROOM AM A Y 2 0.25

AC-003-06 VRF WALL MOUNT UNIT ROOM AM A Y 2 0.25 RISK CATEGORY II

CU-003-01 VRF OUTDOOR CONDENSING UNIT GRADE AM D Y 1 0.25 SITE CLASS "D" DESIGN SPECTRAL RESPONSE ACCELERATION AT SHORT PERIODS (0.2 SECOND):

SEISMIC IMPORTANCE FACTOR FOR BUILDING, I = 1.0 SDS = 0.376 G.

COMPONENT RESPONSE MODIFICATION AND AMPLIFICATION FACTORS DESIGN SPECTRAL RESPONSE ACCELERATION AT 1-SECOND PERIOD:

RESTRAINTS BASE TYPE SHALL BE DETERMINED IN ACCORDANCE WITH ASCE 7, TABLE 13.6-1. SD1 = 0.212 G.

NOTESA = ANCHOR A = ISOLATOR ATTACHED TO EQUIPMENT DIRECTLY

AM = ANCHOR SPECIFIED BY EQUIPMENT MANUFACTURER B = STRUCTURAL STEEL RAILS OR BASE 1 CONCRETE PAD MASS TO EQUAL AT LEAST 75% OF EQUIPMENT B = RESTRAINING BASE WITH SNUBBER C = CONCRETE INERTIA BASE 2 NR=NOT REQUIRED, NA=NOT APPLICABLE Y = REQUIRED PER SPECIFICATION 23 05 40 D = CURB-MOUNTED BASE 3 PIPING TO BE BRACED LATERALLY A MINIMUM OF EVERY 40' AND LONGITUDINALLY EVERY 80' REGARDLESS OF SEISMIC REQUIREMENTS.

ISOLATOR TYPE 4 SEE SPECIFICATION SECTION 23 05 40 FOR DESCRIPTION AND REQUIREMENTS OF BASES, ISOLATORS, AND RESTRAINTS.

5 ALL PIPING GREATER THAN 1" MUST BE RESTRAINED

1. PAD: RUBBER, GLASS FIBER 4. RESTRAINED SPRING ISOLATOR 6 EQUIPMENT VENDOR TO DETERMINE DEFLECTION

2. RUBBER ISOLATOR, FLOOR OR HANGER 5. THRUST RESTRAINT

3. SPRING ISOLATOR, FLOOR OR HANGER 6. AIR SPRING

AIR HANDLING UNIT SCHEDULE

TAG LOCATION MANUFACTURER/ MODEL

SUPPLY FAN EXHAUST FAN HW HEATING COIL DX COOLING COIL UNIT POWER REQMTS

APPROX DIM

(LxWxH)

UNIT WT.

(LBS)COOLING

CFM

HEATING

CFM

MIN OA

CFM

ESP

(IN WC)

TSP

(IN WC)

MOTOR DATA

TOTAL

CFM

ESP

(IN WC)

TSP

(IN WC)

MOTOR DATA MIN

CAP

(MBH)

EWT

(F)

LWT

(F)

EAT

(F)

LAT

(F)

FACE

VELOCITY

(FPM)

APD

(IN WC)

GPM WPD

HW MIN

BRANCH

PIPE SIZE

TOTAL

MBH

SENS.

MBH

EAT (F) LAT (F) FACE

VELOCITY

(FPM)

APD

(IN WC)HP BHP RPM FLA HP BHP RPM DB WB DB WB VOLTS Ø MCA FLA

(E) AHU-003-01

BLDG 003

METAL SHOP DAIKIN / DPS012 3,680 3,680 3,680 1.50 3.88 8 3.79 1,574 13.5 2,680 0.50 2.40 4 <0.33 600 181 180.0 150 41.0 86 680.0 0.26 12.7 3.10 1" 136.7 135.8 87 65 54.0 53.0 500.0 0.19 208 3 63.2 58.8 181x97x57 4,000

AIR HANDLING UNIT SCHEDULE - CONTINUED

TAG

COMPRESSOR #1 COMPRESSOR #2 AIR COOLED CONDENSOR ENERGY RECOVERY - WINTER ENERGY RECOVERY - SUMMER OUTDOOR AIR FILTER EXHAUST AIR FILTER

REMARKS

TYPE

AMBIENT

TEMP

(°F DB)

RLA LRA TYPE

AMBIENT

TEMP

(°F DB)

RLA LRA TYPE

AMBIENT

TEMP

(°F DB)

QTY FANS HP (EACH

FAN)

SUPPLY AIR EXHAUST AIR ENERGY

RECOVERED

(MBH)

TOTAL

EFF.

SUPPLY AIR EXHAUST AIR ENERGY

RECOVERED

(MBH)

TOTAL EFF. MERV FACE VEL

(FPM)

INITIAL PD

(IN H2O)

MERV FACE VEL

(FPM)

INITIAL PD

(IN H2O)EAT (F) LAT (F) EAT (F) EAT (F) LAT (F) EAT (F)

DB WB DB WB DB WB DB WB DB WB DB WB

(E) AHU-003-01

INVERTER SCROLL +

FIXED SCROLL 105 15.0 <1.0 INVERTER SCROLL +

FIXED SCROLL 105 17.5 93.1 AIR COOLED 105 2 1 0 -2 41 31 70 50 187 0.57 105 71 87 65 75 62 67.7 0.58 8 409 0.20 8 409 0.20 1, 2, 3

REMARKS:

1. BALANCE EXISTING EQUIPMENT FOR NEW EXHAUST AIRFLOWS.

2. HEATING COIL FLUID: 30% GLYCOL.

3. REFRIGERANT: R-410A

DUCTWORK CONSTRUCTION AND LEAKAGE TESTING

SYSTEM

ROUND/ OVAL RECTANGULAR

REMARKSPRESS. CLASS

(IN WC)

DUCT SEAL

CLASS

PRESS. CLASS

(IN WC)

DUCT SEAL

CLASS

GENERAL EXHAUST DUCT

FROM FAN TO LOUVER 4 A 4 A

SPECIALTY/FUME EXHAUST

DUCT -4 A - - 1

SPECIALTY/FUME EXHAUST

DUCT -4 A - - 2

NOTES:

A. REFER TO SECTION 23 05 90 "TESTING ADJUSTING AND BALANCING" FOR LEAKAGE TEST REQUIREMENTS.

REMARKS:

1. WELDED 316L STAINLESS STEEL DUCTWORK.

2. TYPE 1 UNPLASTICIZED (RIGID) PVC DUCTWORK.

GRILLES, REGISTERS, DIFFUSERS SCHEDULE

TAG TYPE MANUFACTURER/ MODEL GRILLE SIZE MATERIAL FRAME STYLE FINISH NOTES

1R RETURN TITUS/

350R 36X12 STEEL DUCT MOUNT WHITE 1

1. SEE FLOOR PLANS FOR CONNECTION SIZE.

PROJ. NO.

DRAWN

CHECKED

DATE

COFFMAN ENGINEERS INC.C

48037 TUBBS RANCH ROAD

ADAMS, OR 97810

231290

02/28/2025

SHEET TITLE:

SHEET NO:

A

B

C

D

A

B

C

D

1 2 3 4 5

2 3 4 5

FINAL

TURNOVER

P:

\S

PO

\23

JO

BS

\23

A

RS

P

EN

DL

ET

ON

B

UI

LD

IN

G

RE

PA

IR

S\ 0.0

D W

GS

\M

\P

RO

JE

CT

E

BL

DG

3\2

0_ M-

1.D

W G.

_M

-7

: C

AM

PB

EL

L, RO

B : L

AS

T

SA

VE

D:

F eb ru ar y 2

6, : P

LO

T

DA

TE

: 2 /28

/25 www.coffman.com ph 509.328.2994

221 N. Wall Street

Spokane, WA 99201 Suite 500

PENDLETON

BUILDING

REPAIRS

PROJECT E

REV DATE DESCRIPTION

TAH

DJP

MECHANICAL

SCHEDULES

M-701

SPECIALTY EXHAUST LABORATORY EQUIPMENT CONNECTION SCHEDULE

TAG EQUIPMENT SERVES SERVED BY MANUFACTURER / MODEL LENGTH (FT) TYPE EXHAUST

CONN. (IN)

DESIGN CFM SASH

OPENING (IN)

UNIT POWER

REQUIREMENTS RESPONSIBILITY

REMARKS

VOLTS Ø FLA PROVIDE INSTALL

(N) FH-003-01 FUME HOOD BLDG 003 CLEAN 306 EF-003-01 LABCONCO/

PROTECTOR 14161000033444 6 FUME 12 1180 28 115 1 20 OWNER CONTRACTOR 1, 3

(N) FH-003-02 FUME HOOD BLDG 003 DIRTY 312 EF-003-02 LABCONCO/

PROTECTOR 14161000033444 6 FUME 12 1180 28 115 1 20 CONTRACTOR CONTRACTOR 1, 4

(E) EQ-003-01 SPECTROMETER BLDG 003 CLEAN 306 EF-003-03 PLASMIQUANT - FUME 3 155 - - - - - - 2, 3

(E) EQ-003-02 AUTOSAMPLER BLDG 003 CLEAN 306 EF-003-03 TELEDYNE - FUME 3 90 - - - - - - 2, 3

(E) EQ-003-03 MICROWAVE BLDG 003 CLEAN 306 EF-003-03 ANTON PAAR - FUME 3 90 - - - - - - 2, 3

1. PROVIDE HOOD WITH PRE-PLUMBED SERVICE FIXTURES WITH FORGED COPPER VALVES, COPPER TUBING FOR GAS.

2. EXHAUSTED INDIRECTLY THROUGH A SNORKEL…