This document is a product specification sheet for the Altronix ACM Series Power Supply/Chargers with Multi-Output Access Power Controllers. The ACM series provides eight independently controlled outputs that convert 115VAC, 60Hz input into 12VDC or 24VDC fused power outputs for access control systems and accessories. These units can power devices like mag locks, electric strikes, and magnetic door holders, with outputs operating in fail-safe or fail-secure modes and featuring fire alarm disconnect capabilities.

The product line includes multiple models (AL400ULACM, AL600ULACM, AL1012ULACM, AL1024ULACM) with varying input current draw and output current capabilities. Key features include eight independently controlled outputs, output fuse protection, battery charging for sealed lead acid or gel batteries, AC and battery failure supervision, and UL listings for access control system units. The units are available in standard and "J" enclosure sizes, accommodate 12AH or 18AH batteries, and offer a lifetime warranty. Operating temperature ranges from 0°C to 49°C, with relative humidity of 85% +/- 5%, and they are designed for use in access control and security applications.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

- Eight (8) independently controlled outputs

Output options:
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs;
b) Eight (8) form “C” 5A rated relay outputs;
c) Any combination of the above

- Eight (8) auxiliary power outputs (unswitched)

- Output fuses are rated @ 3.5A

- Filtered and electronically regulated outputs

-Supervision:
- AC Fail
- Battery Fail and Battery Presence
-Fire Alarm disconnect (latching or non-latching) is individually
selectable for any or all of the eight (8) outputs

- Alarm output relay indicates that FACP input is triggered

-Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry contact input
b) Polarity reversal input from FACP signaling circuit

- Built-in charger for sealed lead acid or gel type batteries

- Instantaneous transfer to stand-by batteries

- UL Listed in the U.S. and Canada

- Lifetime Warranty

Altronix Model Number

115VAC

60Hz Input

Current Draw

12VDC

Total

Output Current

24VDC

Total

Output Current

Class 2 Rated

Power- Limited Outputs

Fused Outputs

Individual Output Rating

Power Supply Board Input Fuse

Rating

Power Supply Board Battery Fuse

Rating

Batteries Accommodated by

Enclosure

AL400ULACM

3.5A 4A 3A P

8 2.5A

5A/ 250V

15A/ 32V

Up to two (2) 12AH / 12VDC

AL400ULACMJ Up to two (2) 18AH / 12VDC

AL600ULACM

3.5A 6A 6A

Up to two (2) 12AH / 12VDC

AL600ULACMJ Up to two (2) 18AH / 12VDC

AL1012ULACM

2.6A 10A –

15A/ 32V

Up to two (2) 12AH / 12VDC

AL1012ULACMJ Up to two (2) 18AH / 12VDC

AL1024ULACM

4.2A – 10A 6.3A/

250V Up to two (2) 12AH / 12VDC

AL1024ULACMJ Up to two (2) 18AH / 12VDC

Key Features

AL600ULACM

Lifetime Warranty Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com

ACM Series Power Supply/Chargers with Multi-Output Access Power Controllers

Altronix ACM series distribute and switch power to access control systems and accessories.

They convert a 115VAC, 60Hz input into eight (8) independently controlled 12VDC or 24VDC fuse protected outputs. These power outputs can be converted to dry form “C” contacts.

Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.

Rev. 06222023

ACM Series Power Supply Configuration Reference Chart

Input

Voltage115VAC, 60Hz
Input FuseVaries, see Reference Chart

Outputs

Voltage12VDC or 24VDC, see Reference Chart
CurrentVaries, depending on the model
ProtectionFused 3.5A
Auxiliary3.5A (unswitched)
OtherOvervoltage protection
Filtered and regulated outputs

Battery Charging

Capacity12AH/12VDC (1 or 2 within enclosure)
18AH/12VDC (requires larger “J” enclosure)
40AH/65AH (requires separate enclosure)
TypeSealed lead acid or gel type
Fuse Rating15A/32V
AL600ULACM(J) doesn’t have a battery fuse
FailoverUpon AC loss, instantaneous
Batteries are sold separately

Fire Alarm Disconnect

Latching or non-latching, individually
selectable for any or all of the
eight (8) outputs

Supervision

AC FailureForm “C” contacts (rated 1A @ 28VDC)
BatteryForm “C” contacts (rated 1A @ 28VDC)

Indicators (LED)

Input115VAC is present
DC OutputPowered
BatteryDischarged or not connected
RelaysIndividual LEDs indicate outputs are
triggered (relays energized)
FACPIndicates FACP disconnect is triggered

Agency Listings

All Models:
UL:
UL294Access Control System Units
cUL:
CSA C22.2 No.205Signal Equipment
AL400ULACM(J), AL600ULACM(J) only:
CSFMCalifornia State Fire Marshall Approved

Physical and Environmental

Enclosure Dimensions (H x W x D)
AL400ULACM, AL600ULACM, AL1012ULACM, AL1024ULACM:
Enclosure:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Shipping:
16.5” x 13.5” x 6” (419.1mm x 342.9mm x 152.5mm)
AL400ULACMJ, AL600ULACMJ, AL1012ULACMJ,
and AL1024ULACMJ:
Enclosure:
18” x 14.5” x 4.625” (457.2mm x 368.3mm x 117.5mm)
Shipping:
21.75” x 18.25” x 5.75” (552.5mm x 463.6mm x 146.1mm)
Weight (approx.)

Model Product Weight Shipping Weight AL400ULACM 10.7 lb. (4.85 kg) 12 lb. (5.44 kg) AL400ULACMJ 14 lb. (6.35 kg) 15 lb. (6.8 kg) AL600ULACM 10.3 lb. (4.67 kg) 11.6 lb. (5.26 kg) AL600ULACMJ 14.85 lb. (6.74 kg) 17.1 lb. (7.76 kg) AL1012ULACM 10.7 lb. (4.85 kg) 12 lb. (5.44 kg) AL1012ULACMJ 14.1 lb. (6.40 kg) 15 lb. (6.80 kg) AL1024ULACM 11.75 lb. (5.33 kg) 13.05 lb. (5.92 kg) AL1024ULACMJ 14.9 lb. (6.76 kg) 16.1 lb. (7.3 kg)

Temperature
Operating:0ºC to 49ºC (32ºF to 120ºF)
Storage:– 20ºC to 70ºC (– 4ºF to 158ºF)
Relative Humidity85% +/– 5%
BTU/Hr. (approx.)

Model 12VDC BTU/Hr. 24VDC BTU/Hr.

AL400ULACM(J) 25 37

AL600ULACM(J) 37 74

AL1012ULACM(J) 61 N/A

AL1024ULACM(J) N/A 123

Specifications

Lifetime Warranty Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com

ACM Series Power Supply/Chargers with Multi-Output Access Power Controllers

Lifetime Warranty Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com

ACM Series Power Supply/Chargers with Multi-Output Access Power Controllers

AL400ULACM, AL600ULACM, AL1012ULACM, AL1024ULACM Dimensions (H x W x D approximate) 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)

Dimensions and Drawing

1.5” (38.1mm)

1.5” (38.1mm)

4.615” (117.2mm) 4.615” (117.2mm)

1.5” (38.1mm)

1.5” (38.1mm)

4.615” (117.2mm) 4.615” (117.2mm)

1.75” (44.5mm)

1.75” (44.5mm)

1.375” (34.9mm)

1.125” (28.6mm)

1.5” (38.1mm)

1.5” (38.1mm)

5.0” (127.0m m

5.0” (127.0m m

4.5” (114.3mm)4.5” (114.3mm) 1.25” (31.8mm)

1.25” (31.8mm)

0.79” (20.1m m

0.91” (23.1m m

0.91” (23.1m m

15.5” (393.7m m

1.1” (27.9mm)

1.1” (27.9mm)

1.1” (27.9mm) 12.23” (310.6mm)

2.0” (50.8mm)

2.0” (50.8mm)

1.25” (31.8mm)1.25” (31.8mm)

Lifetime Warranty Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com

ACM Series Power Supply/Chargers with Multi-Output Access Power Controllers

AL400ULACMJ, AL600ULACMJ, AL1012ULACMJ, and AL1024ULACMJ Dimensions (H x W x D approximate) 18” x 14.5” x 4.625” (457.2mm x 368.3mm x 117.5mm)

Dimensions and Drawing

6.

0”

(1

.4 m m

1.

5”

(3 8.

1m m

2.

5” (6

3.

5m m

1.0” (25.4mm)

2.75” (69.9mm)

2.75” (69.9mm)

4.5” (114.3mm) 4.5” (114.3mm)

14.5” (368.3mm)

1.0” (25.4mm)

1.

5”

(3 8.

1m m

8.

5” (2

.9 m m

.0

(4

.2 m m

.0

(4

.2 m m

.0

(4

.2 m m

1.25” (31.75mm) 1.25” (31.75mm)

1.5” (38.1mm) 1.5” (38.1mm)

1.5” (38.1mm)

1.5” (38.1mm)

2.5” (63.5mm)

2.5” (63.5mm)

14.5” (368.3mm)

14.5” (368.3mm)

4.

5”

(1

.3 m m

1.0” (25.4mm)

1.0” (25.4mm)

1.0” (25.4mm)1.0” (25.4mm)