Attachment 2 Statement of Work Solicitation 1232SA26Q1417.docx
DOCX document 55 KB Posted
- Solicitation number
- 1232SA26Q1417
About this file
This is a Statement of Work (SOW) for annual fire protection and life safety system inspections at eight USDA Agricultural Research Service (ARS) locations in Colorado and Wyoming over a five-year period, consisting of a one-year base period and four one-year option periods. The contractor must perform comprehensive annual inspections of portable fire extinguishers, fire sprinkler systems, fire alarm systems, and backflow prevention devices across the specified facilities, with inspection quantities ranging from 3 to 81 devices per location depending on the site. All work must comply with National Fire Protection Association standards (NFPA 10, NFPA 25, and NFPA 72) and local regulations, with inspections performed by qualified personnel who apply inspection tags and submit written reports documenting findings, deficiencies, and recommended corrective actions.
The contractor is responsible for ensuring facility compliance with federal safety standards while the Government provides facility access, system documentation, and environmental maintenance. The vendor is restricted from performing major repairs, system redesigns, or work requiring specialized equipment exceeding six feet without prior authorization. Deliverables include inspection reports for each system and facility, documentation of test results, deficiency listings with corrective action recommendations, and Compliance Engine submissions where applicable. All work must follow USDA-ARS security procedures, access protocols, and site safety requirements. This is a Total Small Business Set-Aside acquisition under NAICS code 561621 with a small business size standard of $25.0 million.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US Department of Agriculture (USDA)
Statement of Work
Contents
| Project | 3 | |
| General Information | 3 | |
| 1.0 | Scope of Work | 3 |
| 2.0 Background | 3 | |
| Contractor Requirements | 3 | |
| 3.0 Technical Requirements / Tasks | 3 | |
| 4.0 Government Responsibilities | 4 | |
| 5.0 Deliverables / Schedule | 4 | |
| 6.0 Quality Assurance and Acceptance Criteria | 4 | |
| 7.0 Security Requirements | 4 |
Project Annual Fire Protection/ Life Safety System Inspections for eight (8) USDA, ARS locations combined as specified in this Statement of Work (SOW) consisting of one (1) one-year base period and four (4) one-year option periods. The total duration of this contract shall not exceed five (5) years.
General Information
1.0 Scope of Work
The vendor must perform annual inspections of fire protection and life safety systems at all sites as specified in this Statement of Work (SOW). All inspections must be performed in strict accordance with requirements as outlined below under Contractor Requirements.
2.0 Background
The USDA, ARS operates multiple research, administrative, and field facilities across Colorado and Wyoming. To ensure compliance with federal safety standards and National Fire Protection Association (NFPA) codes, each facility requires recurring annual inspections of its life safety systems. The vendor-provided inspection documentation defines the technical baseline for required inspections across eight ARS locations.
Contractor Requirements
3.0 Technical Requirements / Tasks
· Annual portable fire extinguisher inspections.
· Annual fire sprinkler system inspections (as applicable).
· Annual fire alarm system inspections (as applicable).
· Annual backflow prevention device inspections (as applicable).
· Inspection tagging for each device/system.
· Written inspection reports for all inspections performed.
· Documentation of identified deficiencies and recommended corrective actions.
The vendor must:
· Ensure personnel performing inspections are qualified and properly equipped.
· Perform inspections in accordance with NFPA 10, NFPA 25, NFPA 72, and local/state regulations.
· Perform minor onsite repairs only when pre-authorized by the Government.
· Apply inspection tags to all inspected systems/devices.
· Provide written inspection reports for each system and each facility.
· Documentation of sprinkler, alarm, and backflow testing results.
· Deficiency listings and recommended corrective actions.
· Compliance Engine submissions for applicable facilities.
· Follow all USDA, ARS access, security, and safety procedures.
The vendor will not perform:
· Major repairs or system redesign.
· Work requiring specialized equipment such as scaffolding >6 ft without prior coordination.
· Work in unsafe or inaccessible areas without approval.
· Any items explicitly excluded in vendor inspection documentation.
Applicable Standards All inspections must comply with National Fire Protection Association:
· NFPA 10 – Portable Fire Extinguishers
· NFPA 25 – Water-Based Fire Protection Systems
· NFPA 72 – National Fire Alarm and Signaling Code Local regulations.
USDA, ARS Safety Requirements and Facility Procedures.
4.0 Government Responsibilities
The Government will:
· Provide facility access for all inspection locations.
· Notify building occupants of alarms or system activity during inspections.
· Maintain appropriate environmental conditions to prevent system impairment (e.g., freezing).
· Provide system documentation (as-builts, device lists, etc.) when available.
5.0 Deliverables / Schedule
Locations & Inspection Requirements:
1. Center for Agricultural Resources Research (CARR) – Fort Collins, CO
· Annual inspection of 31 portable extinguishers
2. High Plains Grasslands Research Station (HPGRS) - Cheyenne, WY
· Annual inspection of 42 portable extinguishers
3. Central Plains Experimental Range (CPER) - Nunn, CO
· Annual inspection of 42 portable extinguishers
4. Fort Collins Research Farm (FCRF) - Wellington, CO
· Annual inspection of 40 portable extinguishers
5. Limited Irrigation Research Farm (LIRF) - Greeley, CO
· Annual inspection of 40 portable extinguishers
6. Central Great Plains Research Station (CGPRS) - Akron, CO
· Annual inspection of 81 portable extinguishers
7. Crops Research Laboratory (CRL) - Fort Collins, CO
· Annual fire sprinkler inspection
· Annual fire alarm inspection
· Annual inspection of 3 backflow devices
· Annual inspection of 12 portable extinguishers
8. National Laboratory for Genetic Resources Preservation (NLGRP) - Fort Collins, CO
· Annual fire sprinkler inspection
· Annual fire alarm inspection
· Annual inspection of 7 backflow devices
· Annual inspection of 20 portable extinguishers
6.0 Quality Assurance and Acceptance Criteria
Inspection work will be accepted when:
· All inspections for each facility are completed.
· Reports are submitted, accurate, and approved by the Government.
· All devices/systems are properly tagged.
7.0 Security Requirements
The vendor must comply with all USDA-ARS:
· Security check-in procedures
· Escort requirements (if applicable)
· Site safety protocols
Vendor-caused delays must be promptly reported for rescheduling or coordination.