This Statement of Work (SOW) details the fire alarm system installation requirements for Building 71, a 4,500 square foot facility lacking an existing fire alarm system. The project requires a comprehensive fire alarm system installation with specific technical specifications, including a Monaco Analog Addressable+ (MAAP(+)) Fire Alarm Control Panel, integrated radio transceiver, antenna assembly, wall-mounted speaker/horn strobe, pull stations, smoke detectors, and monitor modules. The vendor must provide conduit pathways, install 3/4" conduit with pull strings, use isolated SLC circuits, and comply with multiple military engineering standards including dafi32-2001 and ufc_3_600_01_2016_c5. Additionally, the contractor must submit detailed design layouts to the Fire Protection Engineer for certification, complete the entire installation within 30 calendar days of contract award, and provide operational training and user instruction manuals. The project also includes security requirements mandating that the contractor follow all security precautions briefed by Security Forces upon base access.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF WORK

FOR

Fire Alarm System Installation, B71

31 July 2025

SCOPE OF WORK

GENERAL

Building 71 is approximately 4,500 square feet and does not have a fire alarm system required for occupancy. Building 71 also requires conduit pathways through the building for the fire alarm system’s wiring. Installation of the fire alarm system must comply with current dafi32-2001, Fire And Emergency Service (F&ES) Program, and ufc_3_600_01_2016_c5, Fire Protection Engineering For Facilities.

FIRE ALARM & CONDUIT SPECIFICATIONS

- Deliverables:

-3/4” Conduit with a pull string installed the entire length of the conduit run required for the Fire Alarm System based of its requirement/design -Isolated SLC Circuit which will be designated for Fire Alarm Systems only -NO Bundling or Stub-ups on the SLC Circuit -Design & Layout: Vendor will install in accordance with an approved fire alarm circuit layout design and certification prior to installation

FIRE ALARM & CONDUIT SPECIFICATIONS

- Deliverables:

-Monaco Analog Addressable+ (MAAP(+)) FACP with Integrated Radio Transceiver -Monaco Antenna Assembly (BSA-1 VHF Antenna, Omnidirectional, P/N 190-400-00) -Monaco Antenna Mount -Monaco Antenna Lightning Arrestor (198-021-xx, 198-022-xx) -Monaco - Wall Mount Speaker / Horn Strobe -Monaco - Pull Stations -Monaco - Smoke Detectors with Standard Base -Monaco - Monitor Module (Flow, Tamper & PIV) -Lot # 16/2 SLC Cable -Lot # 14/2 NAC Cable -Lot # 16/4 LOC Cable -Vendor shall provide operational training on system operation, what to do in case of an alarm or trouble condition.

-Vendor shall provide user instruction manual.

-Design & Layout: Vendor is required to complete fire alarm layout design and certification prior to installation. Designs and design analysis must meet the requirements of UFC 3-580-01, Telecommunications Building Cabling Systems Planning and Design, ETL 02-12, Communications and Information System Criteria for Air Force Facilities, NSTISSAM TEMPEST/2-95, NSTISSI 7003, Protected Distribution Systems, AFI 31- 101, Integrated Defense, and ICD 705, Sensitive Compartmented Information Facilities (As necessary). Designs shall be submitted to the project Fire Protection Engineer to review the design submission of plans and specifications for written certification.

-Installation: Vendor shall provide installation. Required equipment should be acquired and installed within 30 calendar days of contract award.

SECURITY

- The Contractor shall abide by all security precautions as briefed with Security Forces upon gaining visitor access to the base.

EXAMPLE FIRE ALARM SYSTEM AND CONDUIT LAYOUT FOR ELECTRICIANS

Fire Alarm System Installation, B71
GENERAL
FIRE ALARM & CONDUIT SPECIFICATIONS
FIRE ALARM & CONDUIT SPECIFICATIONS
SECURITY
- The Contractor shall abide by all security precautions as briefed with Security Forces upon gaining visitor access to the base.