This is a technical specification document (Section 09 90 00 - Paints and Coatings) for interior painting work at a federal facility, dated July 2025. The specification covers comprehensive painting requirements including surface preparation, material standards, application procedures, and quality assurance for interior commercial facility wall surfaces. Key requirements include using only Master Painters Institute (MPI) approved products with GPS-1-14 green certification and minimum E2 environmental rating, compliance with federal regulations prohibiting lead content over 0.06%, and adherence to strict environmental and safety standards including prohibition of asbestos, mercury, chromates, and carbon-based fibers.

The document specifies detailed coating systems for different substrates including concrete, metal (ferrous and non-ferrous), and gypsum board/plaster surfaces, with minimum dry film thickness requirements of 1.5 mils per coat. Contractors must demonstrate previous experience with similar interior commercial painting projects and provide qualified personnel meeting OSHA safety requirements. The specification includes extensive surface preparation requirements for existing coated surfaces (including Zolatone polychromatic coatings), application procedures for various coating types (latex, alkyd, epoxy), and detailed paint tables with specific MPI system numbers for different substrates and finish levels. Quality control measures include inspection standards, waste management protocols, and requirements for indoor air quality certifications.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 09 90 00 Page 1

SECTION TABLE OF CONTENTS

DIVISION 09 - FINISHES

SECTION 09 90 00

PAINTS AND COATINGS

07/25

PART 1 GENERAL

1.1 RELATED REQUIREMENTS

1.1.1 Painting Included

1.1.1.1 Interior Painting

1.1.2 Painting Excluded

1.2 REFERENCES

1.3 DEFINITIONS

1.3.1 Qualification Testing

1.3.2 Batch Quality Conformance Testing

1.3.3 Coating

1.3.4 DFT or dft

1.3.5 DSD

1.3.6 INTERIOR

1.3.7 Loose Paint

1.3.8 micron / microns

1.3.9 mil / mils

1.3.10 mm

1.3.11 MPI Gloss Levels

1.3.12 MPI System Number

1.3.13 Paint

1.3.14 RIN

1.4 SUBMITTALS

1.5 QUALITY ASSURANCE

1.5.1 Regulatory Requirements

1.5.1.1 Environmental Protection

1.5.1.2 Lead Content

1.5.1.3 Chromate Content

1.5.1.4 Asbestos Content

1.5.1.5 Mercury Content

1.5.1.6 Silica

1.5.1.7 Human Carcinogens

1.5.1.8 Carbon Based Fibers / Tubes

1.5.2 Coating Contractor's Qualification

1.5.3 Approved Products List

1.5.4 Paints and Coatings Indoor Air Quality Certifications

1.6 PACKAGING, LABELING, AND STORAGE

1.6.1 Toxic Materials

1.7 ENVIRONMENTAL REQUIREMENTS

1.7.1 Coatings

1.7.2 Post-Application

PART 2 PRODUCTS

2.1 MATERIALS

2.2 COLOR SELECTION OF FINISH COATS

PART 3 EXECUTION

SECTION 09 90 00 Page 2

3.1 PROTECTION OF AREAS AND SPACES NOT TO BE PAINTED

3.2 SURFACE PREPARATION

3.2.1 Additional Requirements for Preparation of Surfaces With

Existing Coatings

3.2.2 Existing Coated Surfaces with Minor Defects

3.2.3 Substrate Repair

3.3 PREPARATION OF METAL SURFACES

3.3.1 Existing and New Ferrous Surfaces

3.3.2 Final Ferrous Surface Condition:

3.3.2.1 Tool Cleaned Surfaces

3.3.2.2 Abrasive Blast Cleaned Surfaces

3.3.2.3 Waterjet Cleaned Surfaces

3.3.3 Galvanized Surfaces

3.3.4 Non-Ferrous Metallic Surfaces

3.3.5 Terne-Coated Metal Surfaces

3.3.6 Existing Surfaces with a Bituminous or Mastic-Type Coating

3.4 PREPARATION OF CONCRETE AND CEMENTITIOUS SURFACE

3.4.1 Concrete and Masonry

3.4.2 Gypsum Board, Plaster, and Stucco

3.4.2.1 Surface Cleaning

3.4.2.2 Repair of Minor Defects

3.4.2.3 Allowable Moisture Content

3.4.3 Existing Asbestos Cement Surfaces

3.5 PREPARATION OF WOOD AND PLYWOOD SURFACES

3.5.1 New[, Existing Uncoated,][ and][ Existing Coated] Plywood and

Wood Surfaces, Except Floors:

3.5.2 Wood Floor Surfaces, Natural Finish

3.5.3 Interior Wood Surfaces, Stain Finish

3.5.4 Water Blasting of Existing Coated Wood Surfaces:

3.6 APPLICATION

3.6.1 Coating Application

3.6.2 Mixing and Thinning of Paints

3.6.3 Two-Component Systems

3.6.4 Coating Systems

3.7 COATING SYSTEMS FOR METAL

3.8 COATING SYSTEMS FOR CONCRETE AND CEMENTITIOUS SUBSTRATES

3.9 COATING SYSTEMS FOR WOOD AND PLYWOOD

3.10 PIPING IDENTIFICATION

3.11 INSPECTION AND ACCEPTANCE

3.12 WASTE MANAGEMENT

3.13 PAINT TABLES

3.13.1 Exterior Paint Tables

3.13.1.1 MPI Division 3: Exterior Concrete Paint Table

3.13.1.2 MPI Division 4: Exterior Concrete Masonry Units Paint

Table

3.13.1.3 MPI Division 5: Exterior Metal, Ferrous and Non-Ferrous

Paint Table

3.13.1.4 MPI Division 6: Exterior Wood; Dressed Lumber, Paneling, Decking, Shingles Paint Table

3.13.1.5 MPI Division 9: Exterior Stucco Paint Table

3.13.1.6 MPI Division 10: Exterior Cloth Coverings and Bituminous

Coated Surfaces Paint Table

3.13.2 Interior Paint Tables

3.13.2.1 MPI Division 3: Interior Concrete Paint Table

3.13.2.2 MPI Division 4: Interior Concrete Masonry Units Paint

Table

3.13.2.3 MPI Division 5: Interior Metal, Ferrous and Non-Ferrous

Paint Table

3.13.2.4 MPI Division 6: Interior Wood Paint Table

3.13.2.5 MPI Division 9: Interior Plaster, Gypsum Board, Textured

SECTION 09 90 00 Page 3

Surfaces Paint Table

-- End of Section Table of Contents --

SECTION 09 90 00 Page 4

PART 1 GENERAL

1.1 RELATED REQUIREMENTS

1.1.1 Painting Included

Where a space or surface is indicated to be painted, include the following unless indicated otherwise.

a. Surfaces behind portable objects and surface mounted articles readily detachable by removal of fasteners, such as screws and bolts.

b. New factory finished surfaces that require identification or color coding and factory finished surfaces that are damaged during performance of the work.

c. Existing coated surfaces that are damaged during performance of the work.

1.1.1.1 Interior Painting

Includes existing coated surfaces of the building and appurtenances as indicated and existing coated surfaces made bare by cleaning operations.

Where a space or surface is indicated to be painted, include the following items, unless indicated otherwise.

a. Exposed columns, girders, beams, joists, and metal deck; and

b. Other contiguous surfaces.

1.1.2 Painting Excluded

Do not paint the following unless indicated otherwise.

a. Surfaces concealed and made inaccessible by panelboards, fixed ductwork, machinery, and equipment fixed in place.

b. Surfaces in concealed spaces. Concealed spaces are defined as enclosed spaces above suspended ceilings, furred spaces, attic spaces, crawl spaces, elevator shafts and chases.

c. Copper, stainless steel, aluminum, anodized aluminum, brass, and lead except existing coated surfaces.

d. Fire extinguisher sprinkler systems.

e. Hardware, fittings, and other factory finished items.

1.2 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN CONFERENCE OF GOVERNMENTAL INDUSTRIAL HYGIENISTS (ACGIH)

ACGIH 0100 (2017; Suppl 2020) Documentation of the

Threshold Limit Values and Biological

SECTION 09 90 00 Page 5

Exposure Indices

AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)

ASME A13.1 (2023) Scheme for the Identification of

Piping Systems

ASTM INTERNATIONAL (ASTM)

ASTM C920 (2018; R 2024) Standard Specification for

Elastomeric Joint Sealants

ASTM D235 (2022) Standard Specification for Mineral

Spirits (Petroleum Spirits) (Hydrocarbon

Dry Cleaning Solvent)

ASTM D523 (2014; R 2018) Standard Test Method for

Specular Gloss

ASTM D2824/D2824M (2018) Standard Specification for

Aluminum-Pigmented Asphalt Roof Coatings, Non-Fibered, and Fibered without Asbestos

ASTM D4214 (2007; R 2015) Standard Test Method for

Evaluating the Degree of Chalking of

Exterior Paint Films

ASTM D4263 (1983; R 2018) Standard Test Method for

Indicating Moisture in Concrete by the

Plastic Sheet Method

ASTM D4444 (2013; R 2018) Standard Test Method for

Laboratory Standardization and Calibration of Hand-Held Moisture Meters

ASTM D6386 (2022) Standard Practice for Preparation of Zinc (Hot-Dip Galvanized) Coated Iron and Steel Product and Hardware Surfaces

SECTION 09 90 00 Page 6 for Painting

ASTM F1869 (2023) Standard Test Method for Measuring

Moisture Vapor Emission Rate of Concrete

Subfloor Using Anhydrous Calcium Chloride

CENTERS FOR DISEASE CONTROL AND PREVENTION (CDC)

Intelligence Bulletin 65 (2013) Occupational Exposure to Carbon

Nanotubes and Nanofibers

MASTER PAINTERS INSTITUTE (MPI)

MPI 1 (2012) Aluminum Paint

MPI 2 (2012) Aluminum Heat Resistant Enamel (up to 427 C and 800 F

MPI 3 (2016) Primer, Alkali Resistant, Water

Based

MPI 4 (2016) Interior/Exterior Latex Block Filler

MPI 5 (2015) Primer, Exterior Alkyd Wood

MPI 6 (2015) Primer, Exterior Latex Wood

MPI 8 (2016) Alkyd, Exterior Flat (MPI Gloss

Level I)

MPI 9 (2016) Alkyd, Exterior Gloss (MPI Gloss

Level 6)

MPI 10 (2016) Latex, Exterior Flat (MPI Gloss

Level 1)

MPI 11 (2016) Latex, Exterior Semi-Gloss, MPI

Gloss Level 5

MPI 13 (2016) Stain, Exterior Solvent-Based, Semi-Transparent

MPI 16 (2016) Stain, Exterior, Water Based, Solid

Hide

MPI 17 (2016) Primer, Bonding, Water Based

MPI 19 (2012) Primer, Zinc Rich, Inorganic

MPI 21 (2012) Heat Resistant Coating, (Up to

205°C/402°F), MPI Gloss Level 6

MPI 22 (2012) Aluminum Paint, High Heat (up to

590° C/1100° F)

MPI 23 (2015) Primer, Metal, Surface Tolerant

MPI 27 (2016) Floor Enamel, Alkyd, Gloss (MPI

Gloss Level 6)

SECTION 09 90 00 Page 7

MPI 31 (2012) Varnish, Polyurethane, Moisture

Cured, Gloss (MPI Gloss Level 6)

MPI 38 (2016) Elastomeric Coating, Exterior, Water Based, Non-Flat

MPI 39 (2018) Primer, Latex, for Interior Wood

MPI 42 (2012) Textured Coating, Latex, Flat

MPI 44 (2016) Latex, Interior, (MPI Gloss Level 2)

MPI 45 (2016) Primer Sealer, Interior Alkyd

MPI 46 (2016) Undercoat, Enamel, Interior

MPI 47 (2016) Alkyd, Interior, Semi-Gloss (MPI

Gloss Level 5)

MPI 48 (2016) Alkyd, Interior, Gloss (MPI Gloss

Level 6-7)

MPI 49 (2015) Alkyd, Interior, Flat (MPI Gloss

Level 1)

MPI 50 (2015) Primer Sealer, Latex, Interior

MPI 51 (2016) Alkyd, Interior, (MPI Gloss Level

3)2

MPI 52 (2016) Latex, Interior, (MPI Gloss Level 3)

MPI 54 (2016) Latex, Interior, Semi-Gloss (MPI

Gloss Level 5)

MPI 56 (2012) Varnish, Interior, Polyurethane, Oil Modified, Gloss

MPI 57 (2012) Varnish, Interior, Polyurethane, Oil Modified, Satin

MPI 59 (2016) Floor Paint, Alkyd, Low Gloss

MPI 60 (2016) Floor Paint, Latex, Low Gloss

MPI 68 (2016) Floor Paint, Latex, Gloss

MPI 71 (2012) Varnish, Polyurethane, Moisture

Cured, Flat (MPI Gloss Level 1)

MPI 72 (2016) Polyurethane, Two-Component, Pigmented, Gloss (MPI Gloss Level 6-7)

MPI 76 (2016) Primer, Alkyd, Quick Dry, for Metal

MPI 77 (2015) Epoxy, Gloss

MPI 79 (2016) Primer, Alkyd, Anti-Corrosive for

SECTION 09 90 00 Page 8

Metal

MPI 90 (2012) Stain, Semi-Transparent, for

Interior Wood

MPI 94 (2016) Alkyd, Exterior, Semi-Gloss (MPI

Gloss Level 5)

MPI 95 (2015) Primer, Quick Dry, for Aluminum

MPI 101 (2016)

Metal

Primer, Epoxy, Anti-Corrosive, for

MPI 107 (2016) Primer, Rust-Inhibitive, Water Based

MPI 108 (2015) Epoxy, High Build, Low Gloss

MPI 113 (2018) Elastomeric, Pigmented, Exterior, Water Based, Flat

MPI 116 (2012) Block Filler, Epoxy

MPI 119 (2016) Latex, Exterior, Gloss (MPI Gloss

Level 6)

MPI 120 (2020) Epoxy, High Build, Self Priming, Low Gloss

MPI 134 (2015) Primer, Galvanized, Water Based

MPI 138 (2016) Latex, Interior, High Performance

Architectural, (MPI Gloss Level 2)

MPI 139 (2016) Latex, Interior, High Performance

Architectural, (MPI Gloss Level 3)

MPI 140 (2016) Latex, Interior, High Performance

Architectural, (MPI Gloss Level 4)

MPI 141 (2016) Latex, Interior, High Performance

Architectural, Semi-Gloss (MPI Gloss Level

5)

MPI 144 (2016) Latex, Interior, Institutional Low

Odor/VOC, (MPI Gloss Level 2)

MPI 145 (2016) Latex, Interior, Institutional Low

Odor/VOC, ( MPI Gloss Level 3)

MPI 146 (2016) Latex, Interior, Institutional Low

Odor/VOC, (MPI Gloss Level 4)

MPI 147 (May 2016) Latex, Interior, Institutional

Low Odor/VOC, Semi-Gloss (MPI Gloss Level

5)

MPI 149 (2016) Primer Sealer, Interior, Institutional Low Odor/VOC

SECTION 09 90 00 Page 9

MPI 151 (2016) Light Industrial Coating, Interior, Water Based (MPI Gloss Level 3)

MPI 153 (2016) Light Industrial Coating, Interior, Water Based, Semi-Gloss (MPI Gloss Level 5)

MPI 154 (2016) Light Industrial Coating, Interior, Water Based, Gloss (MPI Gloss Level 6)

MPI 161 (2016) Light Industrial Coating, Exterior, Water Based ( MPI Gloss Level 3)

MPI 163 (2016) Light Industrial Coating, Exterior, Water Based, Semi-Gloss (MPI Gloss Level 5)

MPI 164 (2016) Light Industrial Coating, Exterior, Water Based, Gloss (MPI Gloss Level 6)

MPI 177 (2020) Epoxy, Semi-Gloss (MPI Gloss Level

5)

MPI 214 (2016) Latex, Exterior (MPI Gloss Level 2)

MPI ASM (2019) Architectural Painting

Specification Manual

MPI GPS-1-14 (2014) Green Performance Standard GPS-1-14

MPI GPS-2-14 (2014) Green Performance Standard GPS-2-14

MPI MRM (2015) Maintenance Repainting Manual

SOCIETY FOR PROTECTIVE COATINGS (SSPC)

SSPC 7/NACE No.4 (2007) Brush-Off Blast Cleaning

SSPC Glossary (2011) SSPC Protective Coatings Glossary

SSPC Guide 6 (2021) Guide for Containing Surface

Preparation Debris Generated During Paint

Removal Operations

SSPC Guide 7 (2015) Guide to the Disposal of

Lead-Contaminated Surface Preparation

Debris

SSPC PA 1 (2024) Shop, Field, and Maintenance

Coating of Metals

SSPC QP 1 (2019) Standard Procedure for Evaluating the Qualifications of Industrial/Marine

Painting Contractors (Field Application to

Complex Industrial Steel Structures and

Other Metal Components)

SSPC SP 1 (2015) Solvent Cleaning

SSPC SP 2 (2024) Hand Tool Cleaning

SECTION 09 90 00 Page 10

SSPC SP 3 (2024) Power Tool Cleaning

SSPC SP 6/NACE No.3 (2007) Commercial Blast Cleaning

SSPC SP 10/NACE No. 2 (2015) Near-White Blast Cleaning

SSPC VIS 1 (2002; E 2004) Guide and Reference

Photographs for Steel Surfaces Prepared by

Dry Abrasive Blast Cleaning

SSPC VIS 3 (2004) Guide and Reference Photographs for

Steel Surfaces Prepared by Hand and Power

Tool Cleaning

SSPC VIS 4/NACE VIS 7 (1998; E 2000; E 2004) Guide and Reference

Photographs for Steel Surfaces Prepared by

Waterjetting

SSPC-SP WJ-1/NACE WJ-1 (2012) Clean to Bare Substrate, Waterjet

Cleaning of Metals

SSPC-SP WJ-2/NACE WJ-2 (2012) Very Thorough Cleaning, Waterjet

Cleaning of Metals

SSPC-SP WJ-3/NACE WJ-3 (2012) Thorough Cleaning, Waterjet

Cleaning of Metals

SSPC-SP WJ-4/NACE WJ-4 (2012) Light Cleaning, Waterjet Cleaning of Metals

SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)

SAE AMS-STD-595A (2017) Colors used in Government

Procurement

U.S. ARMY CORPS OF ENGINEERS (USACE)

EM 385-1-1 (2024) Safety -- Safety and Occupational

Health (SOH) Requirements

U.S. DEPARTMENT OF DEFENSE (DOD)

MIL-PRF-680 (2010; Rev C; Notice 1 2015) Degreasing

Solvent

MIL-STD-101 (2014; Rev C) Color Code for Pipelines and for Compressed Gas Cylinders

U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)

EPA Method 24 (2000) Determination of Volatile Matter

Content, Water Content, Density, Volume

Solids, and Weight Solids of Surface

Coatings

U.S. FEDERAL AVIATION ADMINISTRATION (FAA)

FAA AC 70/7460-1 (2016; Rev L; Change 2) Obstruction

Marking and Lighting

SECTION 09 90 00 Page 11

U.S. GENERAL SERVICES ADMINISTRATION (GSA)

FED-STD-313 (2018) Material Safety Data, Transportation Data and Disposal Data for

Hazardous Materials Furnished to

Government Activities

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

29 CFR 1910.1000 Air Contaminants

29 CFR 1910.1001 Asbestos

29 CFR 1910.1025 Lead

29 CFR 1926.62 Lead

1.3 DEFINITIONS

1.3.1 Qualification Testing

Qualification testing is the performance of all test requirements listed in the product specification. This testing is accomplished by MPI to qualify each product for the MPI Approved Product List, and may also be accomplished by Contractor's third-party testing lab if an alternative to

Batch Quality Conformance Testing by MPI is desired.

1.3.2 Batch Quality Conformance Testing

Batch quality conformance testing determines that the product provided is the same as the product qualified to the appropriate product specification. This testing must be accomplished by an MPI testing lab.

1.3.3 Coating

SSPC Glossary; (1) A liquid, liquefiable, or mastic composition that is converted to a solid protective, decorative, or functional adherent film after application as a thin layer; (2) Generic term for paint, lacquer, enamel.

1.3.4 DFT or dft

Dry film thickness, the film thickness of the fully cured, dry paint or coating.

1.3.5 DSD

Degree of Surface Degradation, the MPI system of defining degree of surface degradation. Five levels are generically defined under the

Assessment sections in the MPI MRM, MPI Maintenance Repainting Manual.

1.3.6 INTERIOR

MPI short term designation for an interior coating system.

1.3.7 Loose Paint

Paint or coating that can be removed with a dull putty knife.

SECTION 09 90 00 Page 12

1.3.8 micron / microns

The metric measurement for 0.001 mm or one one-thousandth of a millimeter.

1.3.9 mil / mils

The English measurement for 0.001 in or one one-thousandth of an inch.

1.3.10 mm

The metric measurement for millimeter, 0.001 meter or one one-thousandth of a meter.

1.3.11 MPI Gloss Levels

MPI system of defining gloss. Seven gloss levels (G1 to G7) are generically defined under the Evaluation sections of the MPI Manuals.

Traditionally, Flat refers to G1/G2, Eggshell refers to G3, Semigloss refers to G5, and Gloss refers to G6.

Gloss levels are defined by MPI as follows:

Gloss Level Description Units at 60 degree angle

Units at 80 degree angle

G1 Matte or Flat 0 to 5 10 max

G2 Velvet 0 to 10 10 to 35

G3 Eggshell 10 to 25 10 to 35

G4 Satin 20 to 35 35 min

G5 Semi-Gloss 35 to 70

G6 Gloss 70 to 85

G7 High Gloss

Gloss is tested in accordance with ASTM D523. Historically, the

Government has used Flat (G1 / G2), Eggshell (G3), Semi-Gloss (G5), and

Gloss (G6).

1.3.12 MPI System Number

The MPI coating system number in each MPI Division found in either the MPI

Architectural Painting Specification Manual or the Maintenance Repainting

Manual and defined as an exterior (EXT/REX) or interior system (INT/RIN).

1.3.13 Paint

SSPC Glossary; (1) Any pigmented liquid, liquefiable, or mastic composition designed for application to a substrate in a thin layer that is converted to an opaque solid film after application. Used for protection, decoration, identification, or to serve some other functional purposes; (2) Application of a coating material.

1.3.14 RIN

MPI short term designation for an interior coating system used in repainting projects or over existing coating systems.

SECTION 09 90 00 Page 13

1.4 SUBMITTALS

Reference Statement of Work for submittal requirements and procedures.

1.5 QUALITY ASSURANCE

1.5.1 Regulatory Requirements

1.5.1.1 Environmental Protection

In addition to requirements specified elsewhere for environmental protection, provide coating materials that conform to the restrictions of the local Air Pollution Control District and regional jurisdiction.

Notify Contracting Officer of any paint specified herein which fails to conform.

1.5.1.2 Lead Content

Do not use coatings having a lead content over 0.06 percent by weight of nonvolatile content.

1.5.1.3 Chromate Content

Do not use coatings containing zinc-chromate or strontium-chromate.

1.5.1.4 Asbestos Content

Provide asbestos-free materials.

1.5.1.5 Mercury Content

Provide materials free of mercury or mercury compounds.

1.5.1.6 Silica

Provide abrasive blast media containing no free crystalline silica.

1.5.1.7 Human Carcinogens

Provide materials that do not contain ACGIH 0100 confirmed human carcinogens (A1) or suspected human carcinogens (A2).

SECTION 09 90 00 Page 14

1.5.1.8 Carbon Based Fibers / Tubes

a. Materials must not contain carbon based fibers such as carbon nanotubes or carbon nanofibers. Intelligence Bulletin 65 ranks toxicity of carbon nanotubes on a par with asbestos.

1.5.1.9 Compliance with Laws and Regulations: The contractor shall comply with all applicable Interstate, Federal, State, and Local laws, regulations, and requirements regarding environmental protection. In the event environmental laws/regulations change during the term of this contract, the contractor is required to comply as such laws come into effect.

1.5.1.10 Environmental Spills: If the contractor spills or releases any substance contained in 40 CFR 302 (or other applicable environmental statute or regulation) into the environment, the contractor shall immediately report the incident to the Emergency Response Services at

911 or 937-257-9111 when using a cell phone. Additionally, the contractor or its agent shall immediately notify the 88th Air Base

Wing (88 ABW) Office of Environmental Management (EM) at 257-7455

(after duty hours 937-269-3463). The liability for the spill or release of such substances rests solely with the contractor. If the contractor detects spills or releases of any substance that they did not spill or release, the contractor shall accomplish all reporting requirements. The contractor shall obtain and maintain appropriate materials and kits for hazardous material spill containment and cleanup, which may occur in the hazardous material storage and laboratory areas. The contractor shall use these materials (and associated kits) in order to contain and clean-up hazardous material spills.

1.5.1.11 Material Storage and Use. The contractor shall follow manufacturer’s guidelines and professional recommendations for control of humidity, temperature, cleanliness and material handling relative to storage and use of all hazardous materials (HM). The contractor shall procure, use, handle and store all HM in accordance with (IAW) all Federal, State, Local and Air Force laws, policies, regulations and procedures.

Mandatory regulatory documents include the following: AFI 32-7086, Hazardous Material Management; WPAFB Hazardous Material Management

Plan (HMMP) Playbook; and the WPAFB HM Management Plan.

1.5.2 Coating Contractor's Qualification

Submit the name, address, telephone number, and e-mail address of the

Contractor that will be performing all surface preparation and coating application. Submit evidence that key personnel have successfully performed surface preparation and application of coatings on pre-painted interior commercial facility interior wall surfaces on a minimum of three similar projects within the past three years. List information by individual and include the following:

a. Name of individual and proposed position for this work.

b. Information about each previous assignment including:

Position or responsibility

Employer (if other than the Contractor)

SECTION 09 90 00 Page 15

Name of facility owner

Mailing address and telephone number of facility owner

Name of individual in facility owner's organization who can be contacted as a reference

Location, size and description of structure Dates work was carried out

Description of work carried out on structure

1.5.3 Ensure that employees are physically qualified to perform their assigned duties in a safe manner to include operators of vehicles and equipment.

Provide operating instructions for all equipment.

1.5.4 Do not allow employees to work whose ability or alertness is impaired because of drugs, fatigue, illness, intoxication, or other conditions that may expose themselves or others to injury.

1.5.5 Accident Reporting: The Contractor shall report all accidents to the CO and COR as soon as safely possible and assist the CO and COR and other officials as required in the investigation of the accident.

1.5.6 First Aid: Provide access to first aid for the number of employees and appropriate to the hazards associated with the types of ongoing construction work at the site.

1.5.7 Personal Protective Equipment (PPE): It is the Contractor's responsibility to require all those working on or visiting the site to wear necessary protective equipment at all times. PPE must meet requirements of applicable ANSI standards. Selection shall conform to

OSHA29 CFR 1926 Subpart E.B. A hard hat use area shall be designated by the Contractor. The hard hat area shall be posted by the Contractor in a manner satisfactory to the Contracting Officer. All PPE will be serviceable at all times. At a minimum, maintain 2 sets of PPE and all other VPP required equipment.

1.5.8

Submit the name, address, telephone number, and e-mail address of the

Contractor that will be performing all surface preparation and coating application. Submit evidence that key personnel have successfully performed surface preparation and application of coatings on pre-painted interior commercial facility interior wall surfaces on a minimum of three similar projects within the past three years. List information by individual and include the following:

a. Name of individual and proposed position for this work.

b. Information about each previous assignment including:

Position or responsibility

Employer (if other than the Contractor)

Name of facility owner

SECTION 09 90 00 Page 16

Mailing address and telephone number of facility owner

Name of individual in facility owner's organization who can be contacted as a reference

Location, size and description of structure

Dates work was carried out

Description of work carried out on structure

1.5.3 Approved Products List

The current MPI, "Approved Product List" which lists paint by brand, label, product name and product code as of the date of Contract award, will be used to determine compliance with the submittal requirements of this specification. The Contractor may choose to use a subsequent MPI

"Approved Product List", however, only one list may be used for the entire

Contract and each coating system is to be from a single manufacturer.

Provide all coats on a particular substrate from a single manufacturer.

No variation from the MPI Approved Products List is acceptable.

1.5.4 Paints and Coatings Indoor Air Quality Certifications

Provide paint and coating products certified to meet indoor air quality requirements by MPI GPS-1-14, MPI GPS-2-14 or provide certification by other third-party programs. Provide current product certification documentation from certification body.

Provide certification of Indoor Air Quality for Paints and Primers.

Submit required indoor air quality certifications in one submittal package.

1.6 PACKAGING, LABELING, AND STORAGE

Provide paints in sealed containers that legibly show the Contract specification number, designation name, formula or specification number, batch number, color, quantity, date of manufacture, manufacturer's formulation number, manufacturer's directions including any warnings and special precautions, and name and address of manufacturer. Furnish pigmented paints in containers not larger than 5 gallons. Store paints and thinners in accordance with the manufacturer's written directions, and as a minimum, stored off the ground, under cover, with sufficient ventilation to prevent the buildup of flammable vapors, and at temperatures between 40 to 95 degrees F.

Deliver all painting materials in sealed, original labeled containers bearing manufacturer's name, brand name, type of paint or coating and color designation, standard compliance, materials content as well as mixing and/or reducing and application requirements.

Store all paint materials in original labeled containers in a secure

(lockable), dry, heated and well ventilated single designated area meeting the minimum requirements of both paint manufacturer and authorities having jurisdiction and at a minimum ambient temperature of 45 degrees F (7 degrees C). Only material used on this project to be stored on site.

Where toxic and/or volatile / explosive / flammable materials are being used, provide adequate fireproof storage lockers and take all necessary precautions and post adequate warnings (e.g. no smoking) as required.

SECTION 09 90 00 Page 17

Take all necessary precautionary and safety measures to prevent fire hazards and spontaneous combustion and to protect the environment from hazard spills. Materials that constitute a fire hazard (paints, solvents, drop clothes, etc.) shall be stored in suitable closed and rated containers and removed from the site on a daily basis.

1.6.1 Toxic Materials

Submit two sets of Material Safety Data Sheets (MSDS) prior to commencement of work for review and for posting at job site as required to protect personnel from overexposure to toxic materials. Conform to the most stringent guidance of:

a. The applicable MSDS or local regulation.

b. 29 CFR 1910.1000.

c. ACGIH 0100, threshold limit values.

1.7 ENVIRONMENTAL REQUIREMENTS

Comply, at minimum, with manufacturer recommendations for space ventilation during and after installation.

Perform no repainting work unless a minimum lighting level of 323 Lux

(30-foot candles) is provided on surfaces to be repainted. Adequate lighting facilities shall be provided by the General Contractor.

1.7.1 Coatings

Do not apply coating when air or substrate conditions are:

a. Less than 5 degrees F above dew point;

b. Below 50 degrees F or over 95 degrees F, unless specifically pre-approved by the Contracting Officer and the product manufacturer.

Do not, under any circumstances, violate the manufacturer's application recommendations.

SECTION 09 90 00 Page 18

PART 2 PRODUCTS

2.1 MATERIALS

Conform to the coating specifications and standards referenced in PART 3.

Submit Product Data Sheets for specified coatings and solvents. Provide preprinted cleaning and maintenance instructions for all coating systems.

Submit Manufacturer's Instructions on Mixing: Detailed mixing instructions, minimum and maximum application temperature and humidity, pot life, and curing and drying times between coats.

2.2 COLOR SELECTION OF FINISH COATS

Provide colors of finish coats as indicated or specified. Allow

Contracting Officer to select colors not indicated or specified.

Manufacturers' names and color identification are used for the purpose of color identification only. Named products are acceptable for use only if they conform to specified requirements.

Provide color, texture, and pattern of wall coating systems as indicated in the statement of work. Submit manufacturer's samples of paint colors.

Cross reference color samples to color scheme as indicated. Submit color stencil codes. Tint each coat progressively darker to enable confirmation of the number of coats.

SECTION 09 90 00 Page 19

PART 3 EXECUTION

3.1 PROTECTION OF AREAS AND SPACES NOT TO BE PAINTED

Prior to surface preparation and coating applications, remove, mask, or otherwise protect hardware, hardware accessories, machined surfaces, radiator covers, plates, lighting fixtures, public and private property, and other such items not to be coated that are in contact with surfaces to be coated. Following completion of painting, reinstall removed items by workmen skilled in the trades. Restore surfaces contaminated by coating materials, to original condition and repair damaged items.

Protect all adjacent interior surfaces and areas, including rating and instruction labels on doors, frames, equipment, piping, etc., from repainting operations and damage by drop cloths, shields, masking, templates, or other suitable protective means and make good any damage caused by failure to provide such protection.

3.2 SURFACE PREPARATION

Existing paint surfaces are a mix of latex interior and Zolatone coatings.

Zolatone is a polychromatic, modified nitrocellulose coating. Follow surface preparation requirements in the MPI ASM and MPI MRM in all areas with Zolatone coatings and undercoating (previously re-painted areas).

Remove dirt, splinters, loose particles, grease, oil, disintegrated coatings, and other foreign matter and substances deleterious to coating performance as specified for each substrate before application of paint or surface treatments. Remove oil and grease prior to mechanical cleaning.

Schedule cleaning so that dust and other contaminants will not fall on wet, newly painted surfaces. Spot-prime exposed ferrous metals such as nail heads on or in contact with surfaces to be painted with water-thinned paints, with a suitable corrosion-inhibitive primer capable of preventing flash rusting and compatible with the coating specified for the adjacent areas. Refer to MPI ASM and MPI MRM for additional more specific substrate preparation requirements.

3.2.1 Additional Requirements for Preparation of Surfaces With Existing

Coatings

Before application of coatings, perform the following on surfaces covered by soundly-adhered coatings, defined as those which cannot be removed with a putty knife:

a. Test existing finishes for lead before sanding, scraping, or removing. If lead is present, refer to paragraph Toxic Materials.

b. Wipe previously painted surfaces to receive solvent-based coatings, rough surfaces clean with a clean, dry cloth saturated with mineral spirits, ASTM D235 or as specified in MPI MRM. Wipe the surfaces dry with a clean, dry, lint free cloth. Wipe immediately preceding the application of the first coat of any coating, unless specified otherwise.

c. Sand existing glossy surfaces to be painted to reduce gloss. Brush, and wipe clean with a damp cloth to remove dust.

d. The requirements specified are minimum. Comply also with the application instructions of the paint manufacturer and specific surface preparation requirements as outlined in MPI MRM Exterior

Surface Preparation and Interior Surface Preparation.

SECTION 09 90 00 Page 20

e. Thoroughly clean previously painted surfaces of all grease, dirt, dust or other foreign matter.

f. Remove blistering, cracking, flaking and peeling or otherwise deteriorated coatings.

g. Roughen slick surfaces. Repair damaged areas such as, but not limited to, nail holes, cracks, chips, and spalls with suitable material to match adjacent undamaged areas.

h. Feather and sand smooth edges of chipped paint.

i. Clean rusty metal surfaces in accordance with SSPC requirements. Use solvent, mechanical, or chemical cleaning methods to provide surfaces suitable for painting.

j. Provide new, proposed coatings that are compatible with existing coatings.

3.2.2 Existing Coated Surfaces with Minor Defects

Sand, spackle, and treat minor defects to render them smooth. Minor defects are defined as scratches, nicks, cracks, gouges, spalls, alligatoring, chalking, and irregularities due to partial peeling of previous coatings. Remove chalking by sanding so that when tested in accordance with ASTM D4214, the chalk rating is not less than 8.

3.2.3 Substrate Repair

a. Repair substrate surface damaged during coating removal. Sand edges of adjacent soundly-adhered existing coatings so they are tapered as smooth as practical to areas involved with coating removal; and

b. Clean and prime the substrate as specified.

3.5 PREPARATION OF METAL SURFACES

3.5.1 Existing and New Ferrous Surfaces

a. Ferrous Surfaces including Shop-coated Surfaces and Small Areas That

Contain Rust, Mill Scale and Other Foreign Substances: Solvent clean or detergent wash in accordance with SSPC SP 1 to remove oil and grease. Where shop coat is missing or damaged, clean according to [SSPC SP 2, ][SSPC SP 3, ][SSPC SP 6/NACE No.3, ] or [

SSPC SP 10/NACE No. 2].[ Brush-off blast remaining surface in accordance with SSPC 7/NACE No.4]; Protect shop-coated ferrous surfaces from corrosion by treating and touching up corroded areas immediately upon detection.

3.5.2 .1 Tool Cleaned Surfaces

Comply with SSPC SP 2 and SSPC SP 3. Use as a visual reference, photographs in SSPC VIS 3 for the appearance of cleaned surfaces.

3.5.2.2 Abrasive Blast Cleaned Surfaces

Comply with SSPC 7/NACE No.4, SSPC SP 6/NACE No.3, and

SSPC SP 10/NACE No. 2. Use as a visual reference, photographs in

SSPC VIS 1 for the appearance of cleaned surfaces.

SECTION 09 90 00 Page 21

3.5.2.3 Waterjet Cleaned Surfaces

Comply with SSPC-SP WJ-1/NACE WJ-1, SSPC-SP WJ-2/NACE WJ-2, SSPC-SP WJ-3/NACE WJ-3 or SSPC-SP WJ-4/NACE WJ-4. Use as a visual reference, photographs in SSPC VIS 4/NACE VIS 7 for the appearance of cleaned surfaces.

3.5.3 Gypsum Board, Plaster, and Stucco

3.5.3.1 Surface Cleaning

Verify that gypsum board is dry. Remove loose dirt and dust by brushing with a soft brush, rubbing with a dry cloth, or vacuum-cleaning prior to application of the first coat material. A damp cloth or sponge may be used if paint is water-based.

3.5.3.2 Repair of Minor Defects

Prior to painting, repair joints, cracks, holes, surface irregularities, and other minor defects with patching plaster or spackling compound and sand smooth.

3.6 APPLICATION

3.8.1 Coating Application

a. Comply with applicable federal, state and local laws enacted to ensure compliance with Federal Clean Air Standards. Apply coating materials in accordance with SSPC PA 1. SSPC PA 1 methods are applicable to all substrates, except as modified herein.

b. At the time of application, paint must show no signs of deterioration. Maintain uniform suspension of pigments during application.

c. Unless otherwise specified or recommended by the paint manufacturer, paint may be applied by brush, roller, or spray. Use trigger operated spray nozzles for water hoses. Use rollers for applying paints and enamels of a type designed for the coating to be applied and the surface to be coated. Wear protective clothing and respirators when applying oil-based paints or using spray equipment with any paints.

d. Only apply paints, except water-thinned types, to surfaces that are completely free of moisture as determined by sight or touch.

n. Thoroughly work coating materials into joints, crevices, and open spaces. Pay special attention to ensure that all edges, corners, crevices, welds, and rivets receive a film thickness equal to that of adjacent painted surfaces.

o. Apply each coat of paint so that dry film is of uniform thickness and free from runs, drops, ridges, waves, pinholes or other voids, laps, brush marks, and variations in color, texture, and finish. Completely hide all blemishes.

p. Apply each coat of paint so that dry film is of uniform thickness and free from runs, drops, ridges, waves, pinholes or other voids, laps, brush marks, and variations in color, texture, and finish. Completely hide all blemishes.

SECTION 09 90 00 Page 22

q. Touch up damaged coatings before applying subsequent coats. Clean and clear dust from interior areas before and during the application of coating material.

r. Drying Time: Allow time between coats, as recommended by the coating manufacturer, to permit thorough drying, but not to present topcoat adhesion problems. Provide each coat in specified condition to receive next coat.

s. Primers, and Intermediate Coats: Do not allow primers or intermediate coats to dry more than 30 days, or longer than recommended by manufacturer, before applying subsequent coats. Follow manufacturer's recommendations for surface preparation if primers or intermediate coats are allowed to dry longer than recommended by manufacturers of subsequent coatings. Cover each preceding coat or surface completely by ensuring visually perceptible difference in shades of successive coats.

t. Finished Surfaces: Provide finished surfaces free from runs, drops, ridges, waves, laps, brush marks, and variations in colors.

u. Thermosetting Paints: Apply topcoats over thermosetting paints

(epoxies and urethanes) within the overcoat window recommended by the manufacturer.

3.8.2 Mixing and Thinning of Paints

Reduce paints to proper consistency by adding fresh paint, except when thinning is mandatory to suit surface, temperature, weather conditions, application methods, or for the type of paint being used. Obtain written permission from the Contracting Officer to use thinners. Verify that the written permission includes quantities and types of thinners to use.

When thinning is allowed, thin paints immediately prior to application with not more than 0.125 L one pint of suitable thinner per liter gallon.

The use of thinner does not relieve the Contractor from obtaining complete hiding, full film thickness, or required gloss. Thinning cannot cause the paint to exceed limits on volatile organic compounds. Do not mix paints of different manufacturers.

3.8.3 Two-Component Systems

Mix two-component systems in accordance with manufacturer's instructions.

Follow recommendation by the manufacturer for any thinning of the first

SECTION 09 90 00 Page 23 coat to ensure proper penetration and sealing for each type of substrate.

3.8.4 Coating Systems

a. Systems by Substrates: Apply coatings that conform to the respective specifications listed in the following Tables:

Table for Interior Applications

MPI Division Substrate Application

MPI Division 5 Interior Metal, Ferrous and Non-Ferrous

Paint Table

SECTION 09 90 00 Page 24

Table for Interior Applications

MPI Division 9 Interior Plaster, Gypsum Board, Textured

Surfaces Paint Table

b. Minimum Dry Film Thickness (DFT): Apply paints, primers, varnishes, enamels, undercoats, and other coatings to a minimum dry film thickness of 0.038 mm 1.5 mil each coat unless specified otherwise in the Tables. Coating thickness, where specified, refers to the minimum dry film thickness.

c. Coatings for Surfaces Not Specified Otherwise: Coat unspecified surfaces the same as surfaces having similar conditions of exposure.

d. Existing Surfaces Damaged During Performance of the Work, Including

New Patches In Existing Surfaces: Coat surfaces with the following:

(1) One coat of primer.

(2) One coat of undercoat or intermediate coat.

(3) One topcoat to match adjacent surfaces.

e. Existing Coated Surfaces To Be Painted: Apply coatings conforming to the respective specifications listed in the Tables herein, except that pretreatments, sealers and fillers need not be provided on surfaces where existing coatings are soundly adhered and in good condition. Do not omit undercoats or primers.

3.9 COATING SYSTEMS FOR METAL

Apply coatings of Tables in MPI Division 5 for Exterior and Interior.

a. Apply specified ferrous metal primer to steel surfaces on the same day that surface is cleaned, to surfaces that meet all specified surface preparation requirements at time of application.

b. Inaccessible Surfaces: Prior to erection, use one coat of specified primer on metal surfaces that will be inaccessible after erection.

c. Shop-primed Surfaces: Touch up exposed substrates and damaged coatings to protect from rusting prior to applying field primer.

d. Surface Previously Coated with Epoxy or Urethane: Apply MPI 101,

0.038 mm 1.5 mils DFT immediately prior to application of epoxy or urethane coatings.

e. Exposed Nails, Screws, Fasteners, and Miscellaneous Ferrous Surfaces.

On surfaces to be coated with water thinned coatings, spot prime exposed nails and other ferrous metal with latex primer MPI 107.

3.12 INSPECTION AND ACCEPTANCE

3.12.1 Standard of Acceptance

Repainted interior surfaces shall be considered to lack uniformity and soundness if any of the following defects are apparent to the Painting

Inspection Agency inspector:

a. brush / roller marks, streaks, laps, runs, sags, drips, heavy

SECTION 09 90 00 Page 25 stippling, hiding or shadowing by inefficient application methods, skipped or missed areas, and foreign materials in paint coatings.

b. evidence of poor coverage at rivet heads, plate edges, lap joints, crevices, pockets, corners and reentrant angles.

c. damage due to touching before paint is sufficiently dry or any other contributory cause.

d. damage due to application on moist surfaces or caused by inadequate protection from the weather.

e. damage and/or contamination of paint due to blown contaminants (dust, spray paint, etc.).

Repainted interior surfaces shall be considered unacceptable if any of the following are evident under final lighting source conditions:

a. visible defects are evident on vertical surfaces when viewed at 90 degrees to the surface from a distance of 1000 mm (39”).

b. visible defects are evident on horizontal surfaces when viewed at 45 degrees to the surface from a distance of 1000 mm (39”).

c. visible defects are evident on ceiling surfaces when viewed at 45 degrees to the surface.

d. when the final coat on any surface exhibits a lack of uniformity of sheen across full surface area.

Repainted surfaces rejected by the inspector shall be made good at the expense of the Contractor. Small affected areas may be touched up; large affected areas or areas without sufficient dry film thickness of paint shall be repainted. Runs, sags of damaged paint shall be removed by scraper or by sanding prior to application of paint.

In addition to meeting previously specified requirements, demonstrate mobility of moving components, including swinging and sliding doors, cabinets, and windows with operable sash, for inspection by the

Contracting Officer. Perform this demonstration after appropriate curing and drying times of coatings have elapsed and prior to invoicing for final payment.

3.13 WASTE MANAGEMENT & CLEAN-UP

As specified in the Waste Management Plan and as follows. Do not use kerosene or any such organic solvents to clean up water based paints.

Properly dispose of paints or solvents in designated containers. Close and seal partially used containers of paint to maintain quality as necessary for reuse. Store in protected, well-ventilated, fire-safe area at moderate temperature. Place materials defined as hazardous or toxic waste in designated containers. Where local options exist for leftover paint recycling, collect all waste paint by type and provide for delivery to recycling or collection facility for reuse by local organizations.

To reduce the amount of contaminants entering waterways, sanitary / storm drain systems or into the ground the following procedures shall be strictly adhered to:

e. Retain cleaning water for water-based materials to allow sediments to be filtered out. In no case shall equipment be cleaned using free draining water.

SECTION 09 90 00 Page 26

f. Retain cleaners, thinners, solvents and excess paint and place in designated containers and ensure proper disposal.

g. Return solvent and oil-soaked rags used during painting operations for contaminant recovery, proper disposal, or appropriate cleaning and laundering.

h. Dispose of contaminants in an approved legal manner in accordance with hazardous waste regulations.

i. Empty paint cans are to be dry prior to disposal or recycling (where available).

j. Close and seal tightly partly used cans of materials including sealant and adhesive containers and store protected in well ventilated fire-safe area at moderate temperature.

3.14.1 On-site waste disposal is not available. Contractor use of facility dumpsters is not permitted.

1.5.4.2 3.14.1 Cleanup areas: Cleanup areas are extremely limited. The sole location for project related cleanup is the utility cabinet/sink located in men’s restroom (W201) on the second floor. This utility cabinet/sink is for limited handwashing/brush cleaning. Paint disposal at this cleanup location is prohibited. Reference paragraph

3.4 for waste/paint disposal.

Clean-up

Cleanup areas: Cleanup areas are extremely limited. The sole location for project related cleanup is the utility cabinet/sink located in men’s restroom (W201) on the second floor. This utility cabinet/sink is for limited handwashing/brush cleaning. Paint disposal at this cleanup location is prohibited. Reference paragraph 3.4 for waste/paint disposal.

Remove all paint where spilled, splashed, splattered or sprayed as work progresses using means and materials that are not detrimental to affected surfaces.

Keep work area free from an unnecessary accumulation of tools, equipment, surplus materials and debris.

Remove combustible rubbish materials and empty paint cans each day and safely dispose of same in accordance with requirements of authorities having jurisdiction.

Clean equipment and dispose of wash water / solvents as well as all other cleaning and protective materials (e.g. rags, drop cloths, masking papers, etc.), paints, thinners, paint removers/strippers in accordance with the safety requirements of authorities having jurisdiction.

3.14 PAINT TABLES

All DFT's are minimum values. Use only materials with a MPI GPS-1-14 green check mark having a minimum MPI "Environmentally Friendly" E2 rating based on VOC (EPA Method 24) content levels. Acceptable products are listed in the MPI Green Approved Products List, available at https://www.mpi.net/APL/index.asp.

3.14.1 Interior Paint Tables

http://www.mpi.net/APL/index.asp

SECTION 09 90 00 Page 27

Epoxy

3.14.1.1 MPI Division 3: Interior Concrete Paint Table

A. Existing, previously painted Concrete, vertical surfaces, not specified otherwise

Latex

New, uncoated

Existing

Existing, previously painted

Primer Intermediate Topcoat System DFT

MPI INT 3.1A-G2

(Flat)

MPI RIN 3.1A-G2

(Flat)

MPI 3 MPI 44 MPI 44 100 microns4 mils

MPI INT 3.1A-G3

(Eggshell)

MPI RIN 3.1A-G3

(Eggshell)

MPI 3 MPI 52 MPI 52 100 microns4 mils

MPI INT 3.1A-G5 MPI RIN 3.1A-G5

(Semigloss)

MPI 3 MPI 54 MPI 54 100 microns4 mils

Topcoat: Coating to match adjacent surfaces.

High Performance Architectural Latex

Existing

Existing, previously painted

Primer Intermediate Topcoat System DFT

MPI INT 3.1C-G2

(Flat)

MPI RIN 3.1J-G2

(Flat)

MPI 3 MPI 138 MPI 138 100 microns4 mils

MPI INT 3.1C-G3

(Eggshell)

MPI RIN 3.1J-G3

(Eggshell)

MPI 3 MPI 139 MPI 139 100 microns4 mils

MPI INT 3.1C-G4

(satin)

MPI RIN 3.1J-G4 MPI 3 MPI 140 MPI 140 100 microns4 mils

MPI INT 3.1C-G5

(Semigloss)

MPI RIN 3.1J-G5

(Semigloss)

MPI 3 MPI 141 MPI 141 100 microns4

SECTION 09 90 00 Page 28

Existing

Existing, previously painted

Primer Intermediate Topcoat System DFT

MPI INT 3.1F-G6

(Gloss)

MPI RIN 3.1E-G6

(Gloss)

MPI 77 MPI 77 MPI 77 100 microns4

Note: Primer may be reduced for penetration per manufacturer's instructions.

3.14.1.2 MPI Division 5: Interior Metal, Ferrous and Non-Ferrous Paint

Table

A. Interior Steel / Ferrous Surfaces

(1) Metal,[ Mechanical,][ Electrical,][ Fire extinguishing sprinkler systems including valves, conduit, hangers, supports,][ Surfaces adjacent to painted surfaces (Match surrounding finish),][ exposed copper piping,][ and miscellaneous metal items] not otherwise specified except floors, hot metal surfaces, and new prefinished equipment

High Performance Architectural Latex

New, uncoated Existing Primer Intermediate Topcoat System DFT

MPI INT 5.1R-G2 (Flat) MPI 76 MPI 138 MPI 138 125 microns

5 mils

MPI INT 5.1R-G3

(Eggshell)

MPI 76 MPI 139 MPI 139 125 microns

5 mils

MPI INT 5.1R-G5

(Semigloss)

MPI 76 MPI 141 MPI 141 125 microns

5 mils

Alkyd

MPI INT 5.1E-G2 (Flat) MPI 76 MPI 49 MPI 49 131 microns5.25 mils

MPI INT 5.1E-G3

(Eggshell)

MPI 76 MPI 51 MPI 51 131 microns5.25 mils

MPI INT 5.1E-G5

(Semigloss)

MPI 76 MPI 47 MPI 47 131 microns5.25 mils

MPI INT 5.1E-G6 (Gloss) MPI 76 MPI 48 MPI 48 131 microns5.25

SECTION 09 90 00 Page 29

3.14.1.3 MPI Division 9: Interior Plaster, Gypsum Board, Textured

Surfaces Paint Table

A. Interior Existing, previously painted Wallboard not otherwise specified

Latex

Existing, previously painted

Primer Intermediate Topcoat System DFT

RIN 9.2A-G2 (Flat) MPI 50 MPI 44 MPI 44 100 microns4 mils

RIN 9.2A-G3

(Eggshell)

MPI 50 MPI 52 MPI 52 100 microns4 mils

RIN 9.2A-G5

(Semigloss)

MPI 50 MPI 54 MPI 54 100 microns4 mils

High Performance Architectural Latex - High Traffic Areas

New Existing, previously painted

Primer Intermediate Topcoat System DFT

MPI INT 9.2B-G2

(Flat)

MPI RIN 9.2B-G2

(Flat)

MPI 50 MPI 138 MPI 138 100 microns4 mils

MPI INT 9.2B-G3

(Eggshell)

MPI RIN 9.2B-G3

(Eggshell)

MPI 50 MPI 139 MPI 139 100 microns4 mils

MPI INT 9.2B-G5

(Semigloss)

MPI RIN 9.2B-G5

(Semigloss)

MPI 50 MPI 141 MPI 141 100 microns4

SECTION 09 90 00 Page 30

Institutional Low Odor / Low VOC Latex, Existing, previously painted

Institutional Low Odor / Low VOC Latex

Existing, previously painted

Primer Intermediate Topcoat System DFT

MPI RIN 9.2M-G2 (Flat) MPI 144 MPI 144 MPI 144 100 microns4 mils

MPI RIN 9.2M-G3

(Eggshell)

MPI 144 MPI 145 MPI 145 100 microns4 mils

MPI RIN 9.2M-G4 (Satin) MPI 144 MPI 146 MPI 146 100 microns4 mils

MPI RIN 9.2M-G5

(Semigloss)

MPI 144 MPI 147 MPI 147 100 microns4 mils

Epoxy, New, uncoated Existing

MPI INT 9.2E-G6 (Gloss) MPI 50 MPI 77 MPI 77 100 microns4 mils

Epoxy, Existing, previously painted

Existing, previously painted

Primer Intermediate Topcoat System DFT

MPI RIN 9.2D-G6 (Gloss) MPI 17 MPI 77 MPI 77 100 microns4 mils

-- End of Section --