attachment-2-rfp-2026-09cm.pdf

PDF 4 MB Posted

Attached to
Belknap County Jail Infrastructure Improvements
Solicitation number
RFP 2026-09CM
Issued by
Belknap County, New Hampshire

About this file

This file comprises technical construction drawings and specifications for plumbing and mechanical infrastructure improvements at the Belknap County Jail in Laconia, New Hampshire. The project, identified as RFP 2026-09CM with project number 26038, involves comprehensive renovations across two main building areas (designated Areas B and C) on the first floor, with additional work in the attic space. The scope includes demolition and removal of existing systems not designated for reuse, installation of new plumbing fixtures including security-grade combination lavatory/toilet units, water closets, showers, and lavatories manufactured by Willoughby Industries or approved equivalents. Mechanical work encompasses HVAC system modifications, internal duct and equipment cleaning per NADCA standards, replacement of hot water coil three-way valves, thermostat replacement, exhaust fan repairs and belt replacements, and integration of existing systems into a building controls system to be coordinated with Granite State Automation. The project document date is July 15, 2026, with preparation by WV Engineering Associates PA (consulting engineers) located in Keene, New Hampshire.

The specifications detail comprehensive technical requirements including copper pipe materials (ASTM B88 Type K, L, M, or DWV) with no-lead solder, PVC piping for sanitary and vent systems, PEX tubing options for branch distribution, and press-connect fittings compliant with ASTM F3226. Domestic water piping must be tested at 125 PSI hydrostatic pressure for two hours with written certification of successful completion. All work must comply with the International Building Code as adopted by New Hampshire and amended by Laconia, OSHA requirements, the National Electrical Code (NFPA 70), and the Life Safety Code (NFPA 101). Shop drawings must be submitted in PDF format within 30 days of contract award, organized by specification section number. The contractor is responsible for obtaining required permits and inspections, paying associated fees, maintaining existing building systems during construction operations, and providing three instruction and maintenance portfolios with manufacturer details and emergency operating procedures prior to final payment.

View the file

Other files

File Type Posted
rfp-2026-10cm.pdf PDF
attachment-1-rfp-2026-09cm.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U P

A C E

%(1&+

U P

AutoCAD SHX Text

%%UPLUMBING FIRST FLOOR PLAN AREA "B"

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

%%UPROJECT

AutoCAD SHX Text

%%UNORTH

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text

EXISTING BUILDING

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

JAN.

AutoCAD SHX Text

EXST

AutoCAD SHX Text

CORRIDOR 4

AutoCAD SHX Text

EXST

AutoCAD SHX Text

JAN.

AutoCAD SHX Text

EXST

AutoCAD SHX Text

AutoCAD SHX Text

CELL 4

AutoCAD SHX Text

HOLDING

AutoCAD SHX Text

AutoCAD SHX Text

CELL 3

AutoCAD SHX Text

HOLDING

AutoCAD SHX Text

AutoCAD SHX Text

CELL 2

AutoCAD SHX Text

HOLDING

AutoCAD SHX Text

JAN.

AutoCAD SHX Text

EXST

AutoCAD SHX Text

PREVENTION 1

AutoCAD SHX Text

EXST. SUICIDE

AutoCAD SHX Text

PREVENTION 1

AutoCAD SHX Text

SUICIDE

AutoCAD SHX Text

PREVENTION 2

AutoCAD SHX Text

SUICIDE

AutoCAD SHX Text

CORRIDOR 2

AutoCAD SHX Text

EXST

AutoCAD SHX Text

MED. SECURITY

AutoCAD SHX Text

EXST

AutoCAD SHX Text

MED. SECURITY

AutoCAD SHX Text

EXST

AutoCAD SHX Text

SEC. VEST.

AutoCAD SHX Text

EXIST.

AutoCAD SHX Text

HOLDING 3

AutoCAD SHX Text

EXST

AutoCAD SHX Text

HOLDING 2

AutoCAD SHX Text

EXST

AutoCAD SHX Text

HOLDING 1

AutoCAD SHX Text

EXST

AutoCAD SHX Text

CORRIDOR 3

AutoCAD SHX Text

EXST

AutoCAD SHX Text

VEST.

AutoCAD SHX Text

EXST

AutoCAD SHX Text

CORRIDOR 1

AutoCAD SHX Text

EXST

AutoCAD SHX Text

VISITATION

AutoCAD SHX Text

VIDEO

AutoCAD SHX Text

MAX SECURITY

AutoCAD SHX Text

EXST

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

TRAINING

AutoCAD SHX Text

BOOKING

AutoCAD SHX Text

EXST

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

PROP.

AutoCAD SHX Text

PROCESSING RM

AutoCAD SHX Text

EXST

AutoCAD SHX Text

GENERATOR ROOM

AutoCAD SHX Text

EXST

AutoCAD SHX Text

ELECT ROOM

AutoCAD SHX Text

EXST

AutoCAD SHX Text

MECH ROOM

AutoCAD SHX Text

EXST

AutoCAD SHX Text

MAX SECURITY

AutoCAD SHX Text

EXST

AutoCAD SHX Text

MED. SECURITY

AutoCAD SHX Text

EXST

AutoCAD SHX Text J114

AutoCAD SHX Text

ARRAIGNMENT

AutoCAD SHX Text

VIDEO

AutoCAD SHX Text J113

AutoCAD SHX Text

SEARCH

AutoCAD SHX Text

WORK RELEASE

AutoCAD SHX Text J112

AutoCAD SHX Text

BREAK RM

AutoCAD SHX Text

EXIST.

AutoCAD SHX Text J111

AutoCAD SHX Text

LIBRARY

AutoCAD SHX Text J109

AutoCAD SHX Text

CELL 1

AutoCAD SHX Text

HOLDING

AutoCAD SHX Text J107

AutoCAD SHX Text

ROOM 1

AutoCAD SHX Text

PROGRAM

AutoCAD SHX Text J108

AutoCAD SHX Text

ROOM 2

AutoCAD SHX Text

PROGRAMING

AutoCAD SHX Text J105

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

ATTORNEY

AutoCAD SHX Text J106

AutoCAD SHX Text

SUPERVISOR

AutoCAD SHX Text

SHIFT

AutoCAD SHX Text J104

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

ASST. SUPR.

AutoCAD SHX Text J102

AutoCAD SHX Text

VEST.

AutoCAD SHX Text

EXIST.

AutoCAD SHX Text J103

AutoCAD SHX Text R.R.

AutoCAD SHX Text

EXIST.

AutoCAD SHX Text J100

AutoCAD SHX Text

VEST.

AutoCAD SHX Text

EXIST.

AutoCAD SHX Text J101

AutoCAD SHX Text

LOBBY

AutoCAD SHX Text

EXIST.

AutoCAD SHX Text

%%UDRAWING NOTES:

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WH

AutoCAD SHX Text

WATER HYDRANT

AutoCAD SHX Text S,W

AutoCAD SHX Text

BELOW GROUND/SLAB

AutoCAD SHX Text

SANITARY SOIL AND WASTE

AutoCAD SHX Text

HWR

AutoCAD SHX Text

HOT WATER RECIRC

AutoCAD SHX Text

SYMBOLS

AutoCAD SHX Text

ABBREVIATION

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

SANITARY SOIL AND WASTE

AutoCAD SHX Text

ABOVE GROUND

AutoCAD SHX Text

SANITARY VENT

AutoCAD SHX Text

COLD WATER

AutoCAD SHX Text

HOT WATER

AutoCAD SHX Text

SHUTOFF VALVE

AutoCAD SHX Text

SHUTOFF VALVE

AutoCAD SHX Text

CHECK VALVE

AutoCAD SHX Text

FLOW (BALANCING VALVE)

AutoCAD SHX Text

CONTROL VALVE

AutoCAD SHX Text

WATER METER

AutoCAD SHX Text

PIPING DROP OR

AutoCAD SHX Text

DOWN THROUGH FLOOR

AutoCAD SHX Text

PIPING RISE OR

AutoCAD SHX Text

UP THROUGH CEILING

AutoCAD SHX Text

CLEANOUT

AutoCAD SHX Text

WALL CLEANOUT

AutoCAD SHX Text

DECK PLATE CLEANOUT

AutoCAD SHX Text

FLOOR OR ROOF DRAIN

AutoCAD SHX Text

WATER HAMMER ARRESTER

AutoCAD SHX Text

FUEL GAS

AutoCAD SHX Text

PRESSURE & TEMPERATURE

AutoCAD SHX Text

RELIEF VALVE

AutoCAD SHX Text

PRESSURE RELIEF VALVE

AutoCAD SHX Text

STRAINER

AutoCAD SHX Text

UNION

AutoCAD SHX Text

PRESSURE GAUGE

AutoCAD SHX Text

THERMOMETER

AutoCAD SHX Text G

AutoCAD SHX Text

RV

AutoCAD SHX Text

PTV

AutoCAD SHX Text G

AutoCAD SHX Text

WHA

AutoCAD SHX Text

FD, RD

AutoCAD SHX Text

DPCO

AutoCAD SHX Text

WCO

AutoCAD SHX Text

CO

AutoCAD SHX Text

RISE, UP

AutoCAD SHX Text

DROP, DN

AutoCAD SHX Text

WM

AutoCAD SHX Text

CLV

AutoCAD SHX Text

FBV

AutoCAD SHX Text

CV

AutoCAD SHX Text

HW

AutoCAD SHX Text

CW

AutoCAD SHX Text V

AutoCAD SHX Text S,W

AutoCAD SHX Text

PLUMBING SYMBOL LIST

AutoCAD SHX Text

ALL SYMBOLS ARE NOT NECESSARILY USED

AutoCAD SHX Text

NEW TO EXISTING CONNECTION

AutoCAD SHX Text

VENT BELOW GROUND/SLAB

AutoCAD SHX Text V

AutoCAD SHX Text

GLOBE VALVE

AutoCAD SHX Text

GLV

AutoCAD SHX Text

PRESSURE REDUCING VALVE

AutoCAD SHX Text

PRV

AutoCAD SHX Text

PRV

AutoCAD SHX Text

HOSE BIBB

AutoCAD SHX Text

HB

AutoCAD SHX Text

LIQUID PETROLEUM GAS

AutoCAD SHX Text

LPG

AutoCAD SHX Text

LPG

AutoCAD SHX Text

PUMPED CONDENSATE

AutoCAD SHX Text

PC

AutoCAD SHX Text

PUMPED DISCHARGE

AutoCAD SHX Text

PD

AutoCAD SHX Text

COMPRESSED AIR

AutoCAD SHX Text

CA

AutoCAD SHX Text

DEIONIZED WATER

AutoCAD SHX Text

DI

AutoCAD SHX Text

VACUUM

AutoCAD SHX Text

VAC

AutoCAD SHX Text

ARGON

AutoCAD SHX Text

AR

AutoCAD SHX Text

NITROGEN

AutoCAD SHX Text N2

AutoCAD SHX Text

OXYGEN

AutoCAD SHX Text O2

AutoCAD SHX Text

COIL CONDENSATE

AutoCAD SHX Text

COND

AutoCAD SHX Text

NEW TO FUTURE CONNECTION

AutoCAD SHX Text

RADON

AutoCAD SHX Text R

AutoCAD SHX Text

FIXTURE CONNECTION SCHEDULE

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

HOT

AutoCAD SHX Text

COLD

AutoCAD SHX Text

VENT

AutoCAD SHX Text

WASTE

AutoCAD SHX Text

MINIMUM BRANCH SIZE

AutoCAD SHX Text

FIXTURE

AutoCAD SHX Text

SYM

AutoCAD SHX Text 1-1/2

AutoCAD SHX Text

AutoCAD SHX Text 1-1/2

AutoCAD SHX Text

AutoCAD SHX Text 1/2

AutoCAD SHX Text 1-1/4

AutoCAD SHX Text 1/2

AutoCAD SHX Text

AutoCAD SHX Text

SUP

AutoCAD SHX Text

TRP

AutoCAD SHX Text P-

AutoCAD SHX Text P-

AutoCAD SHX Text P-

AutoCAD SHX Text

WATER CLOSET

AutoCAD SHX Text

LAVATORY

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text

AutoCAD SHX Text 1-1/4

AutoCAD SHX Text

AutoCAD SHX Text 3/8

AutoCAD SHX Text

WALL HUNG, ADA COMPLIANT

AutoCAD SHX Text

REAR OUTLET

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text P-

AutoCAD SHX Text

AutoCAD SHX Text 1-1/2

AutoCAD SHX Text 1/2

AutoCAD SHX Text 1/2

AutoCAD SHX Text 1-1/2

AutoCAD SHX Text 1/2

AutoCAD SHX Text P-

AutoCAD SHX Text

AutoCAD SHX Text

WATER CLOSET

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1-1/4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FLOOR OUTLET

AutoCAD SHX Text 1-1/2

AutoCAD SHX Text 1-1/2

AutoCAD SHX Text 1-1/4

AutoCAD SHX Text 1/2

AutoCAD SHX Text

COMBINATION LAV/TOILET

AutoCAD SHX Text 1-1/4

AutoCAD SHX Text

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text P-4

AutoCAD SHX Text P-1

AutoCAD SHX Text

AutoCAD SHX Text P-6

AutoCAD SHX Text

AutoCAD SHX Text P-6

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text

AutoCAD SHX Text P-4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text

AutoCAD SHX Text P-4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text P-4

AutoCAD SHX Text

AutoCAD SHX Text P-4

AutoCAD SHX Text

AutoCAD SHX Text P-4

AutoCAD SHX Text

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text P-4

AutoCAD SHX Text

AutoCAD SHX Text P-6

AutoCAD SHX Text G9

AutoCAD SHX Text G4

AutoCAD SHX Text

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D9

AutoCAD SHX Text

MED. SECURITY

AutoCAD SHX Text

EXST

AutoCAD SHX Text A7

AutoCAD SHX Text B6

AutoCAD SHX Text P-6

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text P-6

AutoCAD SHX Text C5

AutoCAD SHX Text

AutoCAD SHX Text P-6

AutoCAD SHX Text issue

AutoCAD SHX Text remark

AutoCAD SHX Text date

AutoCAD SHX Text revisions

AutoCAD SHX Text mk

AutoCAD SHX Text sheet

AutoCAD SHX Text project no.

AutoCAD SHX Text drawn by

AutoCAD SHX Text checked by

AutoCAD SHX Text doc. date

AutoCAD SHX Text 26038

AutoCAD SHX Text 07/15/26

AutoCAD SHX Text

BELKNAP COUNTY

AutoCAD SHX Text

LACONIA, NEW HAMPSHIRE

AutoCAD SHX Text

COUNTY DRIVE

AutoCAD SHX Text

COMMUNITY CORRECTIONS

AutoCAD SHX Text wv engineering associates pa

AutoCAD SHX Text 26038

AutoCAD SHX Text

PERMIT

AutoCAD SHX Text 603 352 7007 fax 352 7005

AutoCAD SHX Text 11 king court keene, nh. 03431

AutoCAD SHX Text consulting engineers

AutoCAD SHX Text mechanical

AutoCAD SHX Text www.wvengineering.com

AutoCAD SHX Text electrical

AutoCAD SHX Text P-1

AutoCAD SHX Text

PLUMBING SUPPLY

AutoCAD SHX Text

FIRST FLOOR

AutoCAD SHX Text

AREA "B" PLAN

AutoCAD SHX Text

GSB

AutoCAD SHX Text

RAP

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text P-4

AutoCAD SHX Text

AutoCAD SHX Text REMOVE & REPLACE EXISTING SHOWER HEAD, MIXING VALVES, CONTROLS, AND SHOWER DRAIN. MEASURE EXISTING SHOWER, THOROUGHLY CLEAN AND ACID ETCH EXISTING GLAZED TILE AND CONCRETE SHOWER FLOOR. INSTALL 1/2" CORIAN SHEET STOCK TO WALLS USING CONSTRUCTION GRADE SILICON CAULKING. PROVIDE MULTI-LAYER WATER PROOF AND SLIP RESISTANT EPOXY PAINT AT SHOWER FLOOR.

AutoCAD SHX Text REMOVE & REPLACE EXISTING SHOWER HEAD & CONTROLS, & ACRYLIC SHOWER SURROUND. THOROUGHLY CLEAN AND ACID ETCH EXISTING GLAZED TILE AND CONCRETE SHOWER FLOOR. INSTALL 1/2" CORIAN SHEET STOCK TO WALLS USING CONSTRUCTION GRADE SILICON CAULKING.

AutoCAD SHX Text REMOVE & REPLACE EXISTING SECURITY FIXTURE WITH SPECIFIED FIXTURE. AFTER REMOVING FIXTURE, INSPECT S.S. FIXTURE SHROUD INTEGRITY & NOTIFY OWNER OF ANY VISIBLE DAMAGE.

AutoCAD SHX Text REMOVE EXISTING WALL MOUNTED CHINA LAVATORY AND WATER CLOSET. REPLACE WITH SPECIFIED SECURITY FIXTURE. MODIFY EXISTING PIPING AS REQUIRED FOR REPLACEMENT FIXTURE.

AutoCAD SHX Text

EXISTING FIXTURES TO REMAIN.

AutoCAD SHX Text FOR CORIAN PRODUCT SUPPORT AND INSTALLATION CONTACT TYLER @ WS DENNISON (603) 224-8434 OR MARK @ CREATIVE COUNTERS 800-417-3003 .

AutoCAD SHX Text FOR EPOXY PAINT PRODUCT SUPPORT AND INSTALLATION CONTACT ASSOCIATED CONCRETE COATINGS (603) 669-2780.

AutoCAD SHX Text

AutoCAD SHX Text P-

AutoCAD SHX Text 1-1/2

AutoCAD SHX Text 1-1/2

AutoCAD SHX Text 1-1/4

AutoCAD SHX Text 1/2

AutoCAD SHX Text

COMBINATION LAV/TOILET

AutoCAD SHX Text 1-1/4

AutoCAD SHX Text

AutoCAD SHX Text

FLOOR MOUNTED, REAR OUTLET

AutoCAD SHX Text

FLOOR MOUNTED, FLOOR OUTLET

1 1

A C F P Q

DOUBLE

U

AutoCAD SHX Text

%%UPLUMBING FIRST FLOOR PLAN AREA "C"

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

%%UPROJECT

AutoCAD SHX Text

%%UNORTH

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text

JAN.

AutoCAD SHX Text

EXST

AutoCAD SHX Text

NURSE

AutoCAD SHX Text

EXST

AutoCAD SHX Text J116

AutoCAD SHX Text

VEST.

AutoCAD SHX Text

QUT.

AutoCAD SHX Text

MEDICAL EXAM

AutoCAD SHX Text

EXST

AutoCAD SHX Text

LAUNDRY RM

AutoCAD SHX Text

EXST

AutoCAD SHX Text

CORRIDOR 6

AutoCAD SHX Text

EXST

AutoCAD SHX Text

STAFF BATHRM

AutoCAD SHX Text

EXST. WOMEN'S

AutoCAD SHX Text

STAFF BATHRM

AutoCAD SHX Text

EXST. MEN'S

AutoCAD SHX Text

STAFF RM

AutoCAD SHX Text

EXST

AutoCAD SHX Text

LIBRARY

AutoCAD SHX Text

EXST

AutoCAD SHX Text

CORRIDOR 5

AutoCAD SHX Text

EXST

AutoCAD SHX Text

MED. SECURITY

AutoCAD SHX Text

EXST

AutoCAD SHX Text

MED. SECURITY

AutoCAD SHX Text

EXST

AutoCAD SHX Text

MED. SECURITY

AutoCAD SHX Text

EXST

AutoCAD SHX Text

MED. SECURITY

AutoCAD SHX Text

EXST

AutoCAD SHX Text

NURSE

AutoCAD SHX Text

EXST

AutoCAD SHX Text

STAIR

AutoCAD SHX Text

EXST

AutoCAD SHX Text

STAIR

AutoCAD SHX Text

EXST

AutoCAD SHX Text J118

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

MAINTENANCE

AutoCAD SHX Text J117

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

LITE

AutoCAD SHX Text J120

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

MECH

AutoCAD SHX Text J119

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

BATH

AutoCAD SHX Text J118

AutoCAD SHX Text

REC.

AutoCAD SHX Text

INDOOR

AutoCAD SHX Text J116

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

QUARANTINE

AutoCAD SHX Text

%%UDRAWING NOTES:

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text P-6

AutoCAD SHX Text P-2

AutoCAD SHX Text P-3

AutoCAD SHX Text P-2

AutoCAD SHX Text P-5

AutoCAD SHX Text P-5

AutoCAD SHX Text P-5

AutoCAD SHX Text P-6

AutoCAD SHX Text P-6

AutoCAD SHX Text P-6

AutoCAD SHX Text issue

AutoCAD SHX Text remark

AutoCAD SHX Text date

AutoCAD SHX Text revisions

AutoCAD SHX Text mk

AutoCAD SHX Text sheet

AutoCAD SHX Text project no.

AutoCAD SHX Text drawn by

AutoCAD SHX Text checked by

AutoCAD SHX Text doc. date

AutoCAD SHX Text 26038

AutoCAD SHX Text 07/15/26

AutoCAD SHX Text

BELKNAP COUNTY

AutoCAD SHX Text

LACONIA, NEW HAMPSHIRE

AutoCAD SHX Text

COUNTY DRIVE

AutoCAD SHX Text

COMMUNITY CORRECTIONS

AutoCAD SHX Text wv engineering associates pa

AutoCAD SHX Text 26038

AutoCAD SHX Text

PERMIT

AutoCAD SHX Text 603 352 7007 fax 352 7005

AutoCAD SHX Text 11 king court keene, nh. 03431

AutoCAD SHX Text consulting engineers

AutoCAD SHX Text mechanical

AutoCAD SHX Text www.wvengineering.com

AutoCAD SHX Text electrical

AutoCAD SHX Text P-2

AutoCAD SHX Text

PLUMBING SUPPLY

AutoCAD SHX Text

FIRST FLOOR

AutoCAD SHX Text

AREA "C" PLAN

AutoCAD SHX Text

GSB

AutoCAD SHX Text

RAP

AutoCAD SHX Text

AutoCAD SHX Text REMOVE & REPLACE EXISTING SHOWER HEAD, MIXING VALVES, CONTROLS, AND SHOWER DRAIN. MEASURE EXISTING SHOWER, THOROUGHLY CLEAN AND ACID ETCH EXISTING GLAZED TILE. INSTALL 1/2" CORIAN SHEET STOCK TO WALLS USING CONSTRUCTION GRADE SILICON CAULKING. EXISTING TERRAZZO SHOWER BASE TO REMAIN.

AutoCAD SHX Text

REMOVE & REPLACE EXISTING SECURITY FIXTURE WITH SPECIFIED FIXTURE.

AutoCAD SHX Text REMOVE EXISTING WALL MOUNTED CHINA LAVATORY AND FLOOR MOUNTED WATER CLOSET. REPLACE WITH SPECIFIED SECURITY FIXTURE. MODIFY EXISTING PIPING AS REQUIRED FOR REPLACEMENT FIXTURE.

AutoCAD SHX Text REMOVE EXISTING WALL MOUNTED CHINA LAVATORY AND WATER CLOSET. REPLACE WITH SPECIFIED SECURITY FIXTURE. MODIFY EXISTING PIPING AS REQUIRED FOR REPLACEMENT FIXTURE.

AutoCAD SHX Text

EXISTING FIXTURES TO REMAIN.

AutoCAD SHX Text FOR CORIAN PRODUCT SUPPORT AND INSTALLATION CONTACT TYLER @ WS DENNISON (603) 224-8434 OR MARK @ CREATIVE COUNTERS 800-417-3003 .

AutoCAD SHX Text P-5

AutoCAD SHX Text P-5

AutoCAD SHX Text P-5

AutoCAD SHX Text P-3

P-6 issue

AutoCAD SHX Text remark

AutoCAD SHX Text date

AutoCAD SHX Text revisions

AutoCAD SHX Text mk

AutoCAD SHX Text sheet

AutoCAD SHX Text project no.

AutoCAD SHX Text drawn by

AutoCAD SHX Text checked by

AutoCAD SHX Text doc. date

AutoCAD SHX Text 26038

AutoCAD SHX Text 07/15/26

AutoCAD SHX Text

BELKNAP COUNTY

AutoCAD SHX Text

LACONIA, NEW HAMPSHIRE

AutoCAD SHX Text

COUNTY DRIVE

AutoCAD SHX Text

COMMUNITY CORRECTIONS

AutoCAD SHX Text wv engineering associates pa

AutoCAD SHX Text 26038

AutoCAD SHX Text

PERMIT

AutoCAD SHX Text 603 352 7007 fax 352 7005

AutoCAD SHX Text 11 king court keene, nh. 03431

AutoCAD SHX Text consulting engineers

AutoCAD SHX Text mechanical

AutoCAD SHX Text www.wvengineering.com

AutoCAD SHX Text electrical

AutoCAD SHX Text P-3

AutoCAD SHX Text

PLUMBING

AutoCAD SHX Text

SPECIFICATIONS

AutoCAD SHX Text

RAP

AutoCAD SHX Text

GS

SECTION 22/23 00 10 - BASIC PLUMBING AND MECHANICAL REQUIREMENTS 1.0 PART 1 - GENERAL 1.1 CONTRACT DOCUMENTS: SECTIONS OF THIS DIVISION SHALL COMPLY WITH INSTRUCTIONS TO BIDDERS, GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION AIA DOCUMENT A201, SUPPLEMENTARY GENERAL CONDITIONS, DIVISION 1. GENERAL REQUIREMENTS AND OTHER CONTRACT DOCUMENTS. 1.2 INTENT OF DOCUMENTS: LABOR, TOOLS, MATERIALS, PLANT, TRANSPORTATION, TAXES, RELATED ITEMS, ESSENTIAL FOR INSTALLATION OF THE WORK. SYSTEMS COMPLETE AND LEFT IN GOOD OPERATING CONDITION. APPARATUS, APPLIANCE, MATERIAL, WORK AND ACCESSORIES, REASONABLY INFERABLE FROM CONTRACT DOCUMENTS, NECESSARY TO MAKE WORK COMPLETE AND READY FOR OPERATION. NEW EQUIPMENT AND MATERIAL UNLESS OTHERWISE CALLED FOR. WORK SHALL BE INSTALLED PER WRITTEN MANUFACTURER'S INSTRUCTIONS. NOTES OR INSTRUCTIONS INCLUDED IN THE SPECIFICATIONS AND/OR SHOWN ON ANY ONE DRAWING, APPLY WHERE APPLICABLE, TO ALL OTHER DRAWINGS. WHERE THERE ARE DISCREPANCIES IN THE CONTRACT DOCUMENTS, THE GREATER QUANTITY, THE GREATER QUALITY AND THE GREATER TOTAL VALUE SHALL BE PROVIDED AS PART OF THE CONTRACT WORK. 1.3 REFERENCES TO CODES, SPECIFICATIONS AND STANDARDS CALLED FOR IN THE SPECIFICATION SECTIONS AND ON THE DRAWINGS MEAN THE LATEST EDITION, AMENDMENT AND REVISION OF SUCH REFERENCED STANDARD IN EFFECT ON THE DATE OF THESE CONTRACT DOCUMENTS. 1.4 CODE COMPLIANCE: THE INTERNATIONAL BUILDING CODE AS ADOPTED BY THE STATE OF NEW HAMPSHIRE AND AMENDED BY TOWN OF LACONIA. OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA). NATIONAL ELECTRICAL CODE, NFPA 70. LOCAL CODES AND ORDINANCES. LIFE SAFETY CODE, NFPA 101. CONTRACT DOCUMENTS IN EXCESS OF CODE/REGULATION REQUIREMENTS AND NOT CONTRARY TO SAME. 1.5 LICENSING: IF REQUIRED BY LOCAL LAWS OR ORDINANCES, THE CONTRACTOR SHALL HOLD A LICENSE TO PERFORM THE WORK AS ISSUED BY THE LOCAL JURISDICTION. 1.6 PERMITS: APPLY FOR AND OBTAIN REQUIRED PERMITS AND INSPECTIONS, PAY FEES AND CHARGES FOR SAME, INCLUDING OTHER SERVICE CHARGES. 1.7 FEES: APPLY FOR AND PAY FEES AND CHARGES FOR UTILITY METERS AND SERVICES. 1.8 GLOSSARY ACI AMERICAN CONCRETE INSTITUTE AGA AMERICAN GAS ASSOCIATION AGCA ASSOCIATED GENERAL CONTRACTORS OF AMERICA, INC. AIA AMERICAN INSTITUTE OF ARCHITECTS AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION ABMA AMERICAN BEARING MANUFACTURER'S ASSOCIATION AMCA AIR MOVING AND CONTROL ASSOCIATION, INC. ANSI AMERICAN NATIONAL STANDARDS INSTITUTE ARI AIR-CONDITIONING AND REFRIGERATION INSTITUTE ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING & AIR CONDITIONING ENGINEERS, INC. ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS ASTM AMERICAN SOCIETY FOR TESTING MATERIALS AWSC AMERICAN WELDING SOCIETY CODE AWWA AMERICAN WATER WORKS ASSOCIATION CX COMMISSIONING CXA COMMISSIONING AGENT FM FACTORY MUTUAL INSURANCE COMPANY IBR INSTITUTE OF BOILER & RADIATION MANUFACTURERS IEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS IRI INDUSTRIAL RISK INSTITUTE NEC NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL MANUFACTURERS' ASSOCIATION NESC NATIONAL ELECTRICAL SAFETY CODE NFPA NATIONAL FIRE PROTECTION ASSOCIATION SBI STEEL BOILER INSTITUTE SMACNA SHEET METAL & AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION UFPO UNDERGROUND FACILITIES PROTECTIVE ORGANIZATION UL UNDERWRITERS' LABORATORIES, INC. OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION APPROVAL/APPROVED WRITTEN PERMISSION TO USE A MATERIAL OR SYSTEM AS CALLED FOR MATERIALS, EQUIPMENT INCLUDING THE EXECUTION SPECIFIED/SHOWN IN THE CONTRACT DOCUMENTS CODE REQUIREMENTS MINIMUM REQUIREMENTS CONCEALED WORK INSTALLED IN PIPE AND DUCT SHAFTS, CHASES OR RECESSES, INSIDE WALLS, ABOVE CEILINGS, IN SLABS OR BELOW GRADE EXPOSED WORK NOT IDENTIFIED AS CONCEALED EQUAL OR EQUIVALENT EQUALLY ACCEPTABLE AS DETERMINED BY OWNER'S REPRESENTATIVE FINAL ACCEPTANCE OWNER ACCEPTANCE OF THE PROJECT FROM CONTRACTOR UPON CERTIFICATION BY OWNER'S REPRESENTATIVE FURNISH SUPPLY AND DELIVER TO INSTALLED LOCATION FURNISHED BY OTHERS RECEIVE DELIVERY AT JOB SITE OR WHERE CALLED FOR AND INSTALL INSPECTION VISUAL OBSERVATIONS BY OWNER'S SITE REPRESENTATIVE INSTALL MOUNT AND CONNECT EQUIPMENT AND ASSOCIATED MATERIALS READY FOR USE LABELED REFERS TO CLASSIFICATION BY A STANDARDS AGENCY OR APPROVED EQUAL APPROVED EQUAL OR EQUIVALENT AS DETERMINED BY OWNER'S REPRESENTATIVE OWNER'S REPRESENTATIVE THE PRIME PROFESSIONAL, AN ARCHITECT OR ENGINEER PRIME PROFESSIONAL ARCHITECT OR ENGINEER HAVING A CONTRACT DIRECTLY WITH THE OWNER FOR PROFESSIONAL SERVICES PROVIDE FURNISH, INSTALL AND CONNECT READY FOR USE RELOCATE DISASSEMBLE, DISCONNECT, AND TRANSPORT EQUIPMENT TO NEW LOCATIONS, THEN CLEAN, TEST AND INSTALL READY FOR USE REPLACE REMOVE AND PROVIDE NEW ITEM REVIEW A GENERAL CONTRACTUAL CONFORMANCE CHECK OF SPECIFIED PRODUCTS ROUGHING PIPE, DUCT, CONDUIT, EQUIPMENT LAYOUT AND INSTALLATION SATISFACTORY AS SPECIFIED IN CONTRACT DOCUMENTS SITE REPRESENTATIVE OWNER'S INSPECTOR OR "CLERK OF WORKS" AT THE WORK SITE 1.9 EQUIPMENT AND MATERIAL INSTALLATION: POTABLE WATER SYSTEMS AND EQUIPMENT SHALL BE BUILT ACCORDING TO AWWA STANDARDS. ELECTRICAL EQUIPMENT AND SYSTEMS SHALL MEET UL STANDARDS AND REQUIREMENTS OF THE NEC. EQUIPMENT AND MATERIAL FOR WHICH THERE IS A LISTING SERVICE SHALL BEAR A UL LABEL. GAS-FIRED EQUIPMENT AND SYSTEMS SHALL MEET AGA REGULATIONS AND SHALL HAVE AGA LABEL. MATERIALS SHALL HAVE A FLAME SPREAD RATING OF 25 OR LESS AND A SMOKE DEVELOPED RATING OF 50 OR LESS. CAREFULLY CHECK MANUFACTURER'S DRAWINGS AND SPECIFICATIONS AS THEY AFFECT THEIR PARTICULAR EQUIPMENT; FOLLOW FACTORY INSTRUCTIONS FOR ROUGHING, INSTALLATION, CONNECTION, FILLING, LUBRICATION, TESTING, BALANCING, ADJUSTING, ALIGNMENT, WIRING, AND START-UP OPERATION. 1.10 PROTECTION OF PERSONS AND PROPERTY: FOR REQUIREMENTS RELATING TO THIS CONTRACT, REFER TO "GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION". CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR CONSTRUCTION SAFETY. PROVIDE AS PART OF CONTRACT, TRENCH OR BUILDING SHORING, SCAFFOLDING, SHIELDING, DUST/FUME PROTECTION, MECHANICAL/ELECTRICAL PROTECTION, SPECIAL GROUNDING, SAFETY RAILINGS, BARRIERS, AND OTHER SAFETY FEATURES REQUIRED TO PROVIDE SAFE CONDITIONS FOR WORKMEN AND SITE VISITORS. 1.11 CONTINUITY OF SERVICES: THE EXISTING BUILDING WILL BE IN USE DURING CONSTRUCTION OPERATIONS. MAINTAIN EXISTING SYSTEMS IN OPERATION THROUGHOUT BUILDING. REFER TO SPECIFICATIONS FOR TEMPORARY FACILITIES FOR ADDITIONAL CONTRACT REQUIREMENTS. SCHEDULES FOR VARIOUS PHASES OF CONTRACT WORK SHALL BE COORDINATED WITH OTHER TRADES AND WITH OWNER'S REPRESENTATIVE. PROVIDE, AS PART OF CONTRACT, TEMPORARY MECHANICAL AND ELECTRICAL CONNECTIONS AND RELOCATIONS AS REQUIRED TO ACCOMPLISH THE ABOVE. OBTAIN APPROVAL IN WRITING AS TO DATE, TIME, AND LOCATION FOR SHUT-DOWN OF EXISTING MECHANICAL/ELECTRICAL FACILITIES OR SERVICES. 2.0 PART 2 - SHOP DRAWINGS/PRODUCT DATA/SAMPLES 2.1 SUBMIT PDF COPIES OF SHOP DRAWINGS WITHIN 30 DAYS AFTER AWARD, OF ITEMS OF EQUIPMENT AND MATERIALS TO BE FURNISHED AND INSTALLED. SUBMISSION OF SHOP DRAWINGS AND SAMPLES SHALL BE ACCOMPANIED BY A TRANSMITTAL LETTER, STATING NAME OF PROJECT AND CONTRACTOR, NUMBER OF DRAWINGS, TITLES AND OTHER PERTINENT DATA CALLED FOR IN INDIVIDUAL SECTIONS. 2.2 SHOP DRAWINGS SHALL BE DATED AND CONTAIN: NAME OF PROJECT; NAME OF PRIME PROFESSIONAL; NAME OF PRIME CONTRACTOR; DESCRIPTION OR NAMES OF EQUIPMENT, MATERIALS AND ITEMS; AND COMPLETE IDENTIFICATION OF LOCATIONS AT WHICH MATERIALS OR EQUIPMENT ARE TO BE INSTALLED. NUMBER EACH SUBMITTAL BY TRADE. INDICATE DEVIATIONS FROM CONTRACT REQUIREMENTS ON LETTER OF TRANSMITTAL. 2.3 SUBMITTALS SHALL BE PACKAGED BASED ON CONTRACT DOCUMENT SPECIFICATION NUMBER. SUBMITTALS PACKAGED BY VENDOR, SUBCONTRACTOR GROUPING OR OTHER RANDOM ASSEMBLY ARE NOT ACCEPTABLE (I.E. IF A VENDOR IS SUPPLYING EQUIPMENT, PIPING, AND INSULATION, THE SUBMITTAL SHOULD BE REGROUPED TO BE UNDER THE APPROPRIATE SPECIFICATION NUMBER, NOT GROUPED TOGETHER). THE SHOP DRAWING SUBMITTAL COVER SHEET SHOULD INCLUDE THE SPECIFICATION SECTION NUMBER. 2.4 WHERE SHOP DRAWINGS FOR SIMILAR ITEMS, SUCH AS PLUMBING FIXTURES, VALVES, FITTINGS OR OTHER REPETITIVE EQUIPMENT ARE INVOLVED, SUBMIT IN A BOUND BROCHURE FORM. INDIVIDUAL PIECEMEAL OR INCOMPLETE SUBMITTALS WILL NOT BE ACCEPTED. SIMILAR ITEMS, (TYPES SPECIFIED) SHALL BE SUBMITTED AT ONE TIME. 2.5 EACH SUBMITTAL WILL BE RETURNED TO THE CONTRACTOR STAMPED OR MARKED AS FOLLOWS: PROVIDE AS SUBMITTED: THE CONTRACTOR IS ADVISED THAT THIS MEANS THAT FABRICATION, MANUFACTURE AND/OR CONSTRUCTION MAY PROCEED PROVIDING THE WORK IS IN COMPLIANCE WITH THE CONTRACT DOCUMENTS. PROVIDE AS NOTED: THE CONTRACTOR IS ADVISED THAT THIS MEANS THAT FABRICATION, MANUFACTURE AND/OR CONSTRUCTION MAY PROCEED PROVIDING THE WORK IS IN COMPLIANCE WITH THE MARKED NOTATIONS AND THE CONTRACT DOCUMENTS. ALSO, THE SUBMITTAL SHOULD BE CORRECTED AND RESUBMITTED FOR FINAL DISTRIBUTION. REVISE AND RESUBMIT: THE CONTRACTOR IS ADVISED THAT THIS MEANS NO WORK SHALL BE FABRICATED, MANUFACTURED AND/OR CONSTRUCTED AND THAT THE CONTRACTOR SHALL MAKE A NEW SUBMITTAL FOR THE PROJECT. PRODUCT SUBMISSIONS MARKED WITH THIS ACTION OR NOTATION WILL NOT BE PERMITTED ON THE SITE. REJECTED: THE CONTRACTOR IS ADVISED TO REVISE AND RESUBMIT. PRODUCT SUBMISSIONS MARKED WITH THIS ACTION OR NOTATION WILL NOT BE PERMITTED ON THE SITE. 2.6 IN THE CASE OF SHOP DRAWINGS RETURNED IN THE FORM OF MANUFACTURER'S DESCRIPTIVE LITERATURE, CATALOG CUTS AND BROCHURES STAMPED PROVIDE AS SUBMITTED OR PROVIDE AS NOTED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR DISTRIBUTING THEM IN THE FIELD AND TO THE SUBCONTRACTORS. IF THE RETURNED SHOP DRAWINGS ARE STAMPED REVISE AND RESUBMIT OR SUBMIT SPECIFIED ITEM, THE CONTRACTOR SHALL SUBMIT NEW COPIES OF COMPLETE SHOP DRAWINGS REVISED TO SHOW COMPLIANCE. 2.7 SHOP DRAWINGS WILL BE GIVEN A GENERAL REVIEW ONLY. CORRECTIONS OR COMMENTS MADE ON THE SHOP DRAWINGS DURING THE REVIEW DO NOT RELIEVE CONTRACTOR FROM COMPLIANCE WITH REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS. SHOP DRAWING CHECK IS INTENDED SOLELY FOR REVIEW OF GENERAL CONFORMANCE WITH THE DESIGN CONCEPT OF THE PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATION GIVEN IN THE CONTRACT DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR: CONFIRMING AND CORRECTING QUANTITIES; CHECKING ELECTRICAL CHARACTERISTICS AND DIMENSIONS; SELECTING FABRICATION PROCESSES AND TECHNIQUES OF CONSTRUCTION; COORDINATING HIS WORK WITH THAT OF OTHER TRADES; AND PERFORMING HIS WORK IN A SAFE AND SATISFACTORY MANNER. 2.8 SUBMIT OPERATING AND MAINTENANCE MANUALS AND PARTS LISTS. 3.0 PART 3 - EXECUTION 3.1 EQUIPMENT ARRANGEMENTS: SINCE EQUIPMENT OF EQUAL CAPACITY IS NOT NECESSARILY OF SAME ARRANGEMENT, SIZE OR CONSTRUCTION, THE CONTRACT DOCUMENTS ARE PREPARED ON BASIS OF ONE MANUFACTURER AS "DESIGN EQUIPMENT", EVEN THOUGH OTHER MANUFACTURERS' NAMES ARE MENTIONED. IF CONTRACTOR ELECTS TO USE EQUIPMENT OTHER THAN "DESIGN EQUIPMENT" WHICH DIFFERS IN ARRANGEMENT AND SIZE: SUBMIT DETAILED DRAWINGS, INDICATING PROPOSED INSTALLATION OF EQUIPMENT. SHOW MAINTENANCE CLEARANCES SERVICE REMOVAL SPACE REQUIRED, AND OTHER PERTINENT REVISIONS TO THE DESIGN ARRANGEMENT. MAKE REQUIRED CHANGES IN THE WORK OF OTHER TRADES, AT NO INCREASE IN CONTRACT. IF REQUIRED, PROVIDE LARGER MOTORS, AND EQUIPMENT, ADDITIONAL CONTROL DEVICES, VALVES, FITTINGS AND OTHER MISCELLANEOUS EQUIPMENT REQUIRED FOR PROPER OPERATION, AND ASSUME RESPONSIBILITY FOR PROPER LOCATION OF ROUGHING AND CONNECTIONS BY OTHER TRADES. IF REVISED ARRANGEMENT SUBMITTAL IS REJECTED, REVISE AND RESUBMIT, OR SUBMIT SPECIFIED ITEM WHICH CONFORMS TO CONTRACT DOCUMENTS. 3.2 TRADE COORDINATION: INSTALL WORK ONLY AFTER COORDINATION WITH EXISTING CONDITIONS AND OTHER TRADES. IN GENERAL, EACH TRADE SHALL COORDINATE AND ROUTE ITS WORK AS CLOSE TO CEILING DECK AS POSSIBLE TO PERMIT: CEILING HEIGHTS AS CALLED FOR. LOCATION OF EXPOSED OR FINISH ELEMENTS AS SHOWN. ACCESS TO SERVICE POINTS. CROSSING OF PIPING, DUCTWORK AND CONDUITS. CONVENIENT REMOVAL OF AT LEAST ONE 2' X 4' CEILING TILE WITHIN EACH SPACE OR EVERY 200 SQUARE FEET OF AREA FOR ACCESS TO ABOVE CEILING COMPONENTS. COORDINATION AND WORK REQUIRED TO ACCOMPLISH ABOVE SHALL BE PROVIDED AS PART OF THE CONTRACT WORK WITH NO ADDITIONAL COST TO THE OWNER. WORK TO INCLUDE: OFFSET OF PIPING, DUCTWORK AND CONDUITS AS REQUIRED (BETWEEN ROOMS). ROUTING CHANGES WITHIN ROOMS OR SPACES TO AVOID CONFLICTS. 3.3 SUBSTITUTIONS: REFER TO SUPPLEMENTARY GENERAL CONDITIONS. THE DESIGN EQUIPMENT CALLED FOR IS THE REQUIRED STANDARD OF QUALITY AND FUNCTION. IF CONTRACTOR DESIRES TO BID ON ANOTHER KIND, TYPE, BRAND, MODEL, OR MANUFACTURER OF MATERIAL OR EQUIPMENT OTHER THAN THOSE NAMED IN SPECIFICATIONS; SUBMIT COMPLETE INFORMATION IN DETAILED TABULATED FORM, COMPARING (ITEM-FOR-ITEM)MATERIAL OR EQUIPMENT OFFERED WITH DESIGN MATERIAL OR EQUIPMENT. INCLUDE SUFFICIENT INFORMATION TO PERMIT QUICK AND THOROUGH COMPARISON, AND INCLUDE PERFORMANCE CURVES ON SAME BASIS, CAPACITIES, POWER REQUIREMENTS, CONTROLS, MATERIALS, METAL GAUGES, FINISHES, DIMENSIONS AND WEIGHTS OF MAJOR PARTS. OWNER'S REPRESENTATIVE SHALL BE THE SOLE JUDGE WHETHER OR NOT TO ACCEPT PROPOSED SUBSTITUTION. 3.4 SUBCONTRACTORS AND MATERIALS: SUBMIT A SUBCONTRACT AND MATERIAL LIST SHEET, WITHIN TWO WEEKS AFTER CONTRACT AWARD, AND INCLUDE NAME OF MANUFACTURER OF EQUIPMENT PROPOSED TO BE INSTALLED; INDICATING ONLY ONE MAKE FOR EACH ITEM, NAME OF EACH SUBCONTRACTOR AND MATERIALS TO BE USED, SHOP DRAWING SUBMITTAL SCHEDULE SHOWING DATES OF EACH REQUIRED SUBMITTAL, AFTER LIST IS REVIEWED, DESIGNATED NAMES WILL BE REQUIRED TO BE USED BY SUCCESSFUL BIDDER AND WILL BE CONSIDERED A PART OF CONTRACT. REVIEW OF PRODUCT MANUFACTURER'S NAME DOES NOT CONSTITUTE APPROVAL OF SPECIFIC EQUIPMENT FOR CONSTRUCTION PURPOSES. PROVIDE SHOP DRAWINGS FOR REVIEW AS CALLED FOR. 3.5 STORAGE AND PROTECTION OF MATERIALS: REFER TO GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION. STORE MATERIALS: ON DRY BASE, AT LEAST 6 IN. ABOVE GROUND OR FLOOR; IN ORDERLY MANNER SO AS NOT TO INTERFERE WITH OTHER WORK OR OBSTRUCT ACCESS TO BUILDINGS OR FACILITIES; WITH WATERPROOF/WINDPROOF COVERING. REMOVE AND PROVIDE SPECIAL STORAGE FOR ITEMS SUBJECT TO MOISTURE DAMAGE; WITH PROTECTION AGAINST THEFT OR DAMAGE FROM ANY CAUSE; REPLACE ITEMS STOLEN OR DAMAGED, AT NO COST TO OWNER. 3.6 REMOVAL WORK: WHERE EXISTING EQUIPMENT REMOVALS ARE CALLED FOR, SUBMIT COMPLETE LIST TO OWNER'S REPRESENTATIVE. ITEMS THAT OWNER WISHES TO RETAIN (THAT DO NOT CONTAIN ASBESTOS OR PCB MATERIAL) SHALL BE DELIVERED TO LOCATION DIRECTED BY OWNER. ITEMS THAT OWNER DOES NOT WISH TO RETAIN SHALL BE REMOVED FROM SITE AND LEGALLY DISPOSED OF. WHERE EQUIPMENT IS CALLED FOR TO BE RELOCATED, CONTRACTOR SHALL CAREFULLY REMOVE, CLEAN AND RECONDITION, THEN REINSTALL. REMOVE ABANDONED PIPING, WIRING, EQUIPMENT, LIGHTING, DUCTWORK, TUBING, SUPPORTS AND FIXTURES. VISIT EACH ROOM, CRAWL SPACE, ROOF AND SITE TO DETERMINE TOTAL SCOPE OF WORK. REMOVAL AND DISPOSAL OF MATERIAL CONTAINING ASBESTOS AND/OR PCBS SHALL BE IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAW REQUIREMENTS. PROVIDE ADEQUATE TEMPORARY LIGHTING, BARRICADES, PROTECTIVE COVERS, DUST BARRIERS, OR OTHER NECESSARY FEATURES REQUIRED FOR SAFE WORKING CONDITIONS. FILL ABANDONED OPENINGS. MATCH EXISTING MATERIAL. MAINTAIN FIRE RESISTANCE RATING OF ENTIRE STRUCTURE. 4.0 PART 4 - OBSTACLES, INTERFERENCE COORDINATION AND ROUGHING 4.1 OBSTACLES, INTERFERENCE COORDINATION AND ROUGHING: PROVIDE WORK IN COMPLIANCE WITH GENERAL DESIGN ARRANGEMENT. INSTALL WORK SUBSTANTIALLY AS CALLED FOR. BEFORE INSTALLING, VERIFY EXACT LOCATION AND ELEVATIONS AT WORK SITE. DO NOT SCALE PLANS. DUE TO SMALL SCALE OF DRAWINGS, IT IS NOT POSSIBLE TO INDICATE OFFSETS, FITTINGS, CHANGES IN ELEVATIONS AND INTERFERENCES. MAKE NECESSARY CHANGES IN CONTRACT WORK AND EQUIPMENT LOCATIONS AS PART OF CONTRACT TO ACCOMMODATE WORK TO OBSTACLES AND INTERFERENCES ENCOUNTERED. IF FIELD CONDITIONS, DETAILS, CHANGES IN EQUIPMENT ON SHOP DRAWING INFORMATION REQUIRE AN IMPORTANT REARRANGEMENT, REPORT SAME TO OWNER'S REPRESENTATIVE FOR REVIEW. OBTAIN WRITTEN APPROVAL FOR MAJOR CHANGES BEFORE INSTALLING. SUBMIT FIVE COPIES OF DRAWINGS, DETAILING ALL SUCH DEVIATIONS OR CHANGES. 4.2 INTERFERENCE: INSTALL WORK SO THAT ITEMS ARE OPERABLE AND SERVICEABLE. ELIMINATE INTERFERENCE WITH REMOVAL OF COILS, MOTORS, FILTERS, BELT GUARDS AND/OR OPERATION OF DOORS. PROVIDE EASY, SAFE AND CODE MANDATED CLEARANCES AT CONTROLLERS, MOTOR STARTERS, VALVE ACCESS, AND OTHER EQUIPMENT REQUIRING MAINTENANCE AND OPERATION. 4.3 INTERFERENCE FROM EXISTING PIPING, DUCTS, CONDUIT, WIRING, AND EQUIPMENT: EXPOSED: CONTRACTOR SHALL RELOCATE, REVISE, OR REMOVE EXISTING WORK IN WAY OF NEW CONSTRUCTION. VISIT SITE BEFORE BIDDING TO DETERMINE SCOPE OF WORK. PROVIDE NEW MATERIALS, INCLUDING NEW PIPING AND INSULATION FOR RELOCATED WORK. CONCEALED: WHERE CONTRACTOR COULD NOT REASONABLY BE EXPECTED TO FIND SUCH TRADE INTERFERENCES DUE TO CONCEALMENT IN WALLS, WITHIN INACCESSIBLE CEILINGS OR FLOORS, SUCH RELOCATIONS WILL BE DONE BY CHANGE ORDER, IF NOT INCLUDED IN CONTRACT WORK. 4.4 COORDINATION: COORDINATE WORK WITH OTHER TRADES AND DETERMINE EXACT ROUTE OR LOCATION OF EACH DUCT, PIPE AND CONDUIT BEFORE FABRICATION AND INSTALLATION. COORDINATE WITH ARCHITECTURAL DRAWINGS. OBTAIN FROM OWNER'S REPRESENTATIVE EXACT LOCATION OF EQUIPMENT IN FINISHED AREAS, SUCH AS THERMOSTAT, FIXTURE AND SWITCH MOUNTING HEIGHTS AND EQUIPMENT MOUNTING HEIGHTS. OBTAIN AND COORDINATE WORK WITH ARCHITECT AND ARCHITECTURAL REFLECTED CEILING PLANS. MECHANICAL AND ELECTRICAL DRAWINGS SHOW DESIGN ARRANGEMENT ONLY FOR DIFFUSERS, GRILLES, REGISTERS, AIR TERMINALS, LIGHTING FIXTURES, SPRINKLERS, SPEAKERS AND OTHER ITEMS. 4.5 ROUGHING: BEFORE ROUGHING FOR EQUIPMENT FURNISHED BY OWNER OR IN OTHER DIVISIONS, OBTAIN FROM OWNER AND OTHER CONTRACTORS, APPROVED ROUGHING DRAWINGS GIVING EXACT LOCATION FOR EACH PIECE OF EQUIPMENT. DO NOT "ROUGH-IN" SERVICES WITHOUT FINAL LAYOUT DRAWINGS APPROVED FOR CONSTRUCTION. COOPERATE WITH OTHER TRADES TO INSURE PROPER LOCATION AND SIZE OF CONNECTIONS TO INSURE PROPER FUNCTIONING OF SYSTEMS AND EQUIPMENT. FOR EQUIPMENT AND CONNECTIONS PROVIDED IN THE CONTRACT, OBTAIN EQUIPMENT ROUGHING DRAWINGS AND DIMENSIONS IN AMPLE TIME, THEN PREPARE ROUGHING-IN DRAWINGS. IF SUCH INFORMATION IS NOT AVAILABLE IN TIME, OBTAIN AN ACKNOWLEDGMENT IN WRITING, THEN MAKE SPECIAL ARRANGEMENTS AS REQUIRED WITH OWNER'S REPRESENTATIVE. 4.6 CHASES, RECESSES AND OPENINGS IN EXISTING BUILDINGS: FLOOR AND/OR ROOF SLAB HOLES TO BE DRILLED. MULTIPLE PIPES SMALLER THAN 1 INCH PROPERLY SPACED AND SUPPORTED MAY PASS THROUGH WITHIN 6 INCH OR SMALLER DIAMETER OPENING. SEAL VOIDS IN FIRE RATED ASSEMBLIES WITH A FIRE STOPPING SEAL SYSTEM TO MAINTAIN THE FIRE RESISTANCE OF THE ASSEMBLY. SEAL VOIDS IN NON-FIRE RATED ASSEMBLIES WITH FLEXIBLE, NON- CURING, PAINTABLE CAULK. PROVIDE 18 GAUGE GALVANIZED SLEEVES AT FIRE RATED ASSEMBLIES. WALL OPENINGS TO BE DRILLED OR CUT TO SUIT. OMIT SLEEVES. EXCEPTION: PROVIDE 18 GAUGE GALVANIZED SLEEVES AT SHAFTS AND FIRE RATED ASSEMBLIES. PROVIDE FIRE STOPPING SIMILAR TO THAT FOR FLOOR OPENINGS. 4.7 CUTTING AND PATCHING: INCLUDE CUTTING AND PATCHING WORK IN THIS CONTRACT. REFER TO "GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION", FOR ADDITIONAL REQUIREMENTS. CUT AND DRILL FROM BOTH SIDES OF WALLS AND/OR FLOORS TO ELIMINATE SPLAYING. CUT OPENINGS IN PREFABRICATED CONSTRUCTION UNITS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. REPLACE UNITS WHICH ARE IMPROPERLY CUT OR DRILLED. TAKE CARE AT VAPOR BARRIERS AND AT INSULATION SYSTEMS. RESEAL/RE-PATCH SUCH BARRIERS TO BE AIRTIGHT TO OCCUPIED SIDE OF INSULATION. CLEAN UP ANY DEBRIS OR INSULATION ABOVE ACT CEILINGS OR IN OCCUPIED SPACES. 4.8 ACCESS PANELS (BY MECHANICAL CONTRACTORS): ACCESS PANELS FOR MECHANICAL EQUIPMENT SHALL BE FURNISHED BY THIS CONTRACTOR AND INSTALLED BY GENERAL CONTRACTOR. LOCATION AND SIZE SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR. THIS CONTRACTOR SHALL BEAR COST OF CONSTRUCTION CHANGES NECESSARY DUE TO IMPROPER INFORMATION OR FAILURE TO PROVIDE PROPER INFORMATION IN AMPLE TIME. ACCESS PANELS OVER 324 SQ. IN. SHALL HAVE TWO CAM LOCKS. CONTRACTOR SHALL PROVIDE PROPER FRAME AND DOOR TYPE FOR VARIOUS WALL OR CEILING FINISHES. ACCESS PANELS SHALL BE EQUAL TO "MILCO" AS MANUFACTURED BY INLAND STEEL PRODUCTS CO., MILWAUKEE, WISCONSIN. PROVIDE GENERAL CONTRACTOR WITH A SET OF ARCHITECTURAL BLACK AND WHITE PRINTS WITH SIZE AND APPROXIMATE LOCATIONS OF ACCESS PANELS MARKED THEREON. OBTAIN APPROVAL OF OWNER'S REPRESENTATIVE FOR ACCESS PANEL SIZE AND LOCATION PRIOR TO ROUGH IN OF EQUIPMENT WHICH REQUIRES ACCESS PANEL. 5.0 PART 5 - CLOSEOUT 5.1 TEST REPORT(S): SUBMIT TEST REPORT(S) FOR REVIEW PRIOR TO SUBSTANTIAL COMPLETION. LIST TESTING PROCEDURE, EQUIPMENT AND MODEL NO. USED, AND DEFICIENCIES CORRECTED FOR EACH TEST PROCEDURE. 5.2 OWNER INSTRUCTIONS: BEFORE FINAL ACCEPTANCE OF THE WORK, FURNISH NECESSARY SKILLED LABOR TO OPERATE SYSTEMS FOR A PERIOD OF NOT LESS THAN ONE (1) DAY. INSTRUCT DESIGNATED PERSON ON PROPER OPERATION, CARE OF SYSTEMS/EQUIPMENT. REPEAT INSTRUCTIONS, IF NECESSARY. OBTAIN WRITTEN ACKNOWLEDGMENT FROM PERSON INSTRUCTED, PRIOR TO FINAL PAYMENT. CONTRACTOR IS FULLY RESPONSIBLE FOR SYSTEMS UNTIL FINAL ACCEPTANCE, EVEN THOUGH OPERATED BY OWNER'S PERSONNEL, UNLESS OTHERWISE AGREED IN WRITING. LIST OPERATING, MAINTENANCE AND STARTING PRECAUTION PROCEDURES TO BE FOLLOWED BY OWNER FOR OPERATING SYSTEMS AND EQUIPMENT. PROVIDE DIGITAL VIDEO RECORDING OF INSTRUCTIONS FOR SYSTEMS CALLED FOR. 5.3 INSTRUCTION PORTFOLIO: PREPARE THREE (3) INSTRUCTION AND MAINTENANCE PORTFOLIOS. INCLUDE ONE COPY EACH OF APPROVED SHOP DRAWINGS, WIRING DIAGRAMS, PIPING DIAGRAMS, SPARE PARTS LISTS, MANUFACTURER'S INSTRUCTIONS AND BALANCE REPORTS. INCLUDE TYPEWRITTEN INSTRUCTIONS, DESCRIBING EQUIPMENT, STARTING/OPERATING PROCEDURES, EMERGENCY OPERATING INSTRUCTIONS, PRECAUTIONS AND RECOMMENDED MAINTENANCE PROCEDURES. INCLUDE NAME, ADDRESS, AND TELEPHONE NUMBER OF SUPPLIER, MANUFACTURER'S REPRESENTATIVE AND SERVICE AGENCY FOR ALL MAJOR EQUIPMENT ITEMS. BIND ABOVE ITEMS IN A THREE RING BINDER WITH NAME OF PROJECT ON THE COVER. DELIVER TO OWNER'S REPRESENTATIVE FOR REVIEW BEFORE REQUEST FOR FINAL ACCEPTANCE. OBTAIN WRITTEN ACKNOWLEDGMENT FROM PERSON INSTRUCTED, PRIOR TO FINAL PAYMENT. 5.4 RECORD DRAWINGS: UTILITIES BELOW GRADE: RECORD DRAWING DATA, KEEP ACCURATE RECORDS OF FINAL LOCATION AND INVERTS OF OUTSIDE UNDERGROUND SERVICES AND MAIN UTILITIES BENEATH GRADE AND BELOW FLOORS. TAKE DIMENSIONS FROM GIVEN, FIXED BENCH MARK, SUCH AS CORNER OF BUILDING. MECHANICAL RECORD DRAWING DATA SHALL BE PROVIDED TO THE OWNER FOR HEATING, VENTILATING, AND AIR CONDITIONING, PLUMBING, FIRE PROTECTION, AND OTHER SYSTEMS ON THE ORIGINAL CONTRACT DOCUMENTS AND ADJUSTMENTS MADE VIA ASI, CHANGE ORDER OR COORDINATION DRAWINGS. NEATLY AND CLEARLY INDICATE RECORD DRAWING DATA. PAY COST OF MAKING REQUIRED CORRECTIONS. PROVIDE SCANNED PDF COPIES AND FILES. END OF SECTION 22/23 00 10

AutoCAD SHX Text remark

AutoCAD SHX Text date

AutoCAD SHX Text revisions

AutoCAD SHX Text mk

AutoCAD SHX Text sheet

AutoCAD SHX Text project no.

AutoCAD SHX Text drawn by

AutoCAD SHX Text checked by

AutoCAD SHX Text doc. date

AutoCAD SHX Text 26038

AutoCAD SHX Text 07/15/26

AutoCAD SHX Text

BELKNAP COUNTY

AutoCAD SHX Text

LACONIA, NEW HAMPSHIRE

AutoCAD SHX Text

COUNTY DRIVE

AutoCAD SHX Text

COMMUNITY CORRECTIONS

AutoCAD SHX Text wv engineering associates pa

AutoCAD SHX Text 26038

AutoCAD SHX Text

PERMIT

AutoCAD SHX Text 603 352 7007 fax 352 7005

AutoCAD SHX Text 11 king court keene, nh. 03431

AutoCAD SHX Text consulting engineers

AutoCAD SHX Text mechanical

AutoCAD SHX Text www.wvengineering.com

AutoCAD SHX Text electrical

AutoCAD SHX Text P-4

AutoCAD SHX Text

PLUMBING

AutoCAD SHX Text

SPECIFICATIONS

AutoCAD SHX Text

RAP

AutoCAD SHX Text

GS

SECTION 22 40 00 - PLUMBING SPECIFICATION 1.0 PART 1 - GENERAL 1.1 THE SCOPE OF WORK IS TO PROVIDE LABOR, MATERIALS, SERVICES, SUPPLIES, TOOLS, EQUIPMENT, PERMITS, TRANSPORTATION AND FACILITIES NECESSARY FOR DEMOLITION AND REMOVAL OF EXISTING SYSTEMS NOT NOTED TO BE REUSED, TO FURNISH AND MODIFY EXISTING AND INSTALL THE COMPLETE AND OPERABLE SYSTEMS AS CALLED FOR. 1.2 REFER TO SPECIFICATION SECTION 22/23 00 10 FOR BASIC REQUIREMENTS OF THE CONTRACT FOR THIS WORK. 1.3 THESE DRAWINGS ARE DIAGRAMMATIC ONLY AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS AND EQUIPMENT. BASIC DESIGN CONCEPTS MUST BE FOLLOWED OR BETTERED. DO NOT SCALE DRAWINGS, FIELD VERIFY DIMENSIONS AND FIELD CONDITIONS. 1.4 IT IS NOT INTENDED THAT DRAWINGS SHOW EVERY DETAIL. PROVIDE OFFSETS, CHANGES IN ELEVATION AND ITEMS NECESSARY FOR PROPER INSTALLATION AND OPERATION OF SYSTEM SO THAT WORK WILL BE COMPLETE AND READY FOR OPERATION. 1.5 COORDINATE WORK WITH OTHER TRADES, BUILDING CONDITIONS AND STRUCTURAL CONDITIONS PRIOR TO INSTALLATION. 1.6 IN THE EVENT OF A DISCREPANCY, IMMEDIATELY NOTIFY THE OWNER'S REPRESENTATIVE. DO NOT PROCEED WITH INSTALLATION IN AREAS OF DISCREPANCY UNTIL SUCH DISCREPANCIES HAVE BEEN RESOLVED. 2.0 PART 2 - PIPING AND PIPING ACCESSORIES 2.1 COPPER PIPE AND SOLDER FITTINGS: HARD TEMPER, ASTM B88; TYPE K, L, M, OR DWV, AS CALLED FOR. COPPER IS NOT ALLOWED FOR URINAL WASTE. WROUGHT COPPER OR CAST BRONZE; SOLDER END CONNECTIONS; ASTM B62, ANSI B16.22. UNIONS FOR 2 INCH AND SMALLER, SOLDER TYPE, CAST BRONZE, GROUND JOINT, 150 LB. SWP. FLANGES FOR 2-1/2 INCH AND LARGER, CAST BRONZE, COMPANION TYPE, ASME DRILLED, SOLDER CONNECTION, 150 LB. SWP. SOLDER MATERIALS, NO-LEAD SOLDER, USING ALLOYS MADE FROM TIN, COPPER, SILVER AND NICKEL. HARRIS "STAY-SAFE 50" AND "BRIGHT", ENGLEHART "SILVERBRIGHT 100", WILLARD INDUSTRIES "SOLDER SAFE (SILVER BEARING), CANFIELD "WATERSAFE". COPPER OR COPPER ALLOY MECHANICAL COUPLINGS ASME B16.18 OR ASME B16.22, EPDM SEALING ELEMENT, INSTALLED WITH MANUFACTURERS APPROVED CLAMPING TOOL. 2.2 COPPER PRESS-CONNECT FITTINGS 1/2"-4" 300 PSI, 0 TO 250F, VIEGA PROPRESS SHALL BE LISTED TO ASTM F3226, ASME B16.51, ICC-ES AC156 AND NSF 61-372. 1/2 INCH THRU 4 INCH FOR USE WITH ASTM B88 COPPER TUBE TYPE L. PRESS CONNECT FITTINGS SHALL HAVE EPDM SEALING ELEMENT AND SMART CONNECT TECHNOLOGY TO DETECT UNPRESSED FITTINGS INTEGRATED INTO THE BODY OF THE FITTING. THE MANUFACTURER'S INSTALLATION INSTRUCTIONS SHALL BE STRICTLY ADHERED TO, IN ACCORDANCE WITH ASTM B 1029 INCLUDING TWO STEP PRESSURE TEST. THE MANUFACTURER SHALL CREDENTIAL INSTALLERS WITHIN THE LAST THREE YEARS. JOIN TUBE AND PRESS-CONNECT FITTINGS WITH RECOMMENDED TOOLING. 2.3 THERMOPLASTIC (PVC) PIPE AND FITTINGS: ASTM D1784 MATERIAL MANUFACTURED TO ASTM D1785 STANDARDS. SEAMLESS SCHEDULE 40 POLYVINYL CHLORIDE (PVC) TYPE 1, GRADE 1. SOCKET TYPE WELD COUPLINGS ASTM D2466, DR WITH INTEGRAL BELL END FOR SOLVENT CEMENTING ASTM D2672. SOLVENT CEMENT - ASTM D2564. 2.4 PEX TUBING AND FITTINGS: CROSS-LINKED POLYETHYLENE TUBING, SUITABLE FOR DOMESTIC WATER SYSTEM AND LONG-TERM CHLORINATED WATER, ASTM F876/F877. FULL SIZED ASTM F1960 COMPLAINANT COLD EXPANSION FITTINGS OF SAME MATERIAL AS PIPING MATERIALS, INSTALLED WITH MANUFACTURERS APPROVED EXPANSION TOOL. DISTRIBUTION MANIFOLD WITH INTEGRAL STOP VALVES AND UNION CONNECTIONS FOR EACH BRANCH RUN. UPONOR "AQUAPEX", VIEGA, WATTS,, REHAU. 2.5 HANGERS SHALL BE ADJUSTABLE, WROUGHT MALLEABLE IRON OR STEEL. COPPER PLATED OR PVC COATED WHERE IN CONTACT WITH COPPER PIPING. CHROMIUM PLATED OR GALVANIZED FOR EXTERIOR. ADJUSTABLE RING TYPE WHERE PIPING IS INSTALLED DIRECTLY ON HANGER FOR PIPING 3-1/2 INCH AND SMALLER. ADJUSTABLE STEEL CLEVIS TYPE FOR PIPING 4 INCH AND LARGER. SIZED TO PASS THROUGH INSULATION FOR DOMESTIC WATER PIPING. PIPE SIZE COPPER PLASTIC PEX ROD SIZE 3/4" TO 1" 6' 3' 32" 3/8" 1-1/4" TO 2" 8' 3' 4' 3/8" 2-1/2" TO 4" 10' 4' 4' 1/2" 2.6 SUPPORTS SPACED FOR A MAXIMUM OF 1000 LBS.: "DRILL-IN" INSERTS EQUAL TO PHILLIPS "RED HEAD" "U" CHANNEL, BEAM CLAMPS OR OTHER STRUCTURALLY REVIEWED SUPPORT. THE FACTOR OF SAFETY SHALL BE AT LEAST FOUR. 2.7 SLEEVES TWO PIPE SIZES LARGER THAN PIPE, SCHEDULE 40 BLACK STEEL PIPE SLEEVES, TWO PIPE SIZES LARGER THAN THE PIPE, FOR STRUCTURAL SURFACES, PVC SLEEVES OR 18 GAUGE SHEET METAL SLEEVES FOR NONSTRUCTURAL SURFACES, EXTEND 1/4" ABOVE WATERPROOF FLOORS, SIZE TO PASS THROUGH INSULATION FOR DOMESTIC WATER PIPING, PACK VOID WITH LOOSE FIBERGLASS AND SEAL WITH WATERPROOF FIRE STOP MATERIAL, ASTM 814. WRAP DRAIN PIPING IN TWO LAYERS OF WATERPROOF "SILL SEAL" AT SLAB ON GRADE PENETRATIONS. 2.8 PIPING MATERIALS SCHEDULE: SERVICE PIPE MATERIALS FITTINGS CONNECTIONS DOMESTIC WATER TYPE L COPPER MECHANICAL FITTINGS PRESS FITTINGS INTERIOR HOT, INSTALLED IN COLD AND COMPLIANCE WITH CIRCULATING MANUFACTURER DOMESTIC WATER PEX TUBING MANUFACTURERS FITTINGS INSTALLED INTERIOR HOT, FITTINGS IN COMPLIANCE COLD AND WITH MANUFACTURER CIRCULATING (OPTIONAL FOR BRANCH PIPING TO FIXTURES, WHERE CONCEALED ONLY) SANITARY, VENT SCHEDULE 40 PVC SOCKET TYPE SOLVENT WELDED (BELOW AND NOTE 1 ABOVE GRADE) EXTENSION OF MATCH EXISTING MATCH EXISTING EMPLOY MATERIALS EXISTING PIPING AND METHODS TO MATCH EXISTING SYSTEMS NOTE 1: PROVIDE "THROUGH PENETRATION" PROTECTION AT FIRE RATED ASSEMBLIES, WRAP WITH INSULATION OR PROVIDE CAST IRON PIPE WHERE LOCATED IN RETURN AIR PLENUMS. 2.9 BALL VALVES: 2 INCH AND UNDER, LEAD FREE CAST BODY WITH TYPE 316 STAINLESS STEEL STEM AND BALL, PTFE SEATS, END ENTRANCE, 225 PSI WP, W.O.G. SCREWED ENDS, WATTS LFB 6000, SOLDER ENDS, WATTS OR JAMESBURY, NIBCO, POWELL. 2.10 HOSE THREAD DRAIN VALVES: BRONZE BODY WITH TYPE 316 STAINLESS STEEL BALL, TEFLON SEATS, END ENTRANCE, 225 PSI WP, W.O.G. SCREWED ENDS, WATTS FIG. #B6400-SS, SOLDER ENDS, WATTS FIG. #B6401-SS OR JAMESBURY, NIBCO, POWELL, 1/8 INCH BODY WITH HOSE THREAD END, BRASS CAP AND CHAIN. 2.11 PIPE INSULATION (GLASS FIBER): FOUR POUND NOMINAL DENSITY FIBERGLASS. WHITE KRAFT OUTER JACKET BONDED TO ALUMINUM FOIL WITH FIBERGLASS YARN REINFORCEMENT. MAXIMUM THERMAL CONDUCTIVITY (K) SHALL BE 0.25 BTU/SQ. FT. HR. DEGREE F/INCH AT 75 DEGREE F MEAN TEMPERATURE. PREMOLDED "ZESTON" FITTING COVERS. CERTAINTEED, KNUAF, MANVILLE, OWENS-CORNING. 2.12 PIPE INSULATION (FLEXIBLE ABOVE GRADE): FLEXIBLE UNICELLULAR ELASTOMERIC FORM TYPE, FIRE RETARDANT INSULATION, 1/2 INCH THICKNESS. MAXIMUM THERMAL CONDUCTIVITY (K) ON A FLAT SURFACE, SHALL BE 0.25 BTU/SQ. FT. HR. OF INCH AT 75 DEGREES F MEAN TEMPERATURE. ARMSTRONG, MANVILLE, RUBATEX. 2.13 PIPE INSULATION MATERIALS SCHEDULE: SERVICE MATERIAL THICKNESS REMARKS DOMESTIC COLD GLASS FIBER 1-1/4 IN AND SMALLER...1/2 IN NOTES 1 WATER 1-1/2 IN AND LARGER......1 IN AND 2 DOMESTIC HOT GLASS FIBER 1-1/4 IN AND SMALLER.....1 IN NOTE 1 AND CIRCULATION 1-1/2 IN AND LARGER..1-1/2 IN WATER NOTE 1: FLEXIBLE PIPE INSULATION OF SAME THICKNESS CALLED FOR MAY BE USED ON PIPING 2" AND SMALLER WHERE CONCEALED. NOTE 2: CONTINUOUS UNBROKEN VAPOR BARRIER. 2.14 STERILIZATION: IN ACCORDANCE WITH AWWA C652 AND REQUIREMENTS OF STATE OF NEW HAMPSHIRE, PUBLIC WATER SUPPLY GUIDES, DIVISION OF SANITARY ENGINEERING, BUREAU OF PUBLIC WATER SUPPLY. 2.15 DOMESTIC WATER PIPING TESTS: PROVIDE ALL NECESSARY ITEMS TO COMPLETE PROPER TESTING OF ALL WATER PIPING. ISOLATE EXISTING SYSTEMS. TEST DOMESTIC WATER PIPING AT 125 PSI HYDROSTATIC FOR TWO HOURS. FLUSH PIPING TO REMOVE DEBRIS, SEDIMENT, ETC. 2.16 PROVIDE WRITTEN CERTIFICATION THAT TESTS HAVE BEEN CONDUCTED AND SUCCESSFULLY COMPLETED. SUBMIT TO OWNER'S REPRESENTATIVE. PAY ALL COSTS OF TEST. 3.0 PART 3 - EQUIPMENT 3.1 TYPE P-1 WATER CLOSET: WILLOUGHBY INDUSTRIES ETWS-1490 SERIES WALL MOUNTED WATER CLOSET, REAR OUTLET 14 GAUGE, 304 STAINLESS STEEL, WELDED, LIGATURE-RESISTANT CONSTRUCTION, #4 SATIN FINISH. ADA COMPLIANT. ELONGATED BOWL WITH CONTOURED INTEGRAL SEAT, TOP SPUD, INTEGRAL WALL CARRIER, MANUAL RESET OVERFLOW PREVENTER. WILLOUGHBY INDUSTRIES, ACORN, BRITEX. 3.2 TYPE P-2 WATER CLOSET: WILLOUGHBY INDUSTRIES ETF-1490-FM FA SERIES FLOOR-MOUNTED WATER CLOSET, FLOOR OUTLET 14-GAUGE, 304 STAINLESS STEEL, WELDED, LIGATURE-RESISTANT CONSTRUCTION, #4 SATIN FINISH. ADA COMPLIANT. ELONGATED BOWL WITH CONTOURED INTEGRAL SEAT, TOP SPUD, MANUAL RESET OVERFLOW PREVENTER. WILLOUGHBY INDUSTRIES, ACORN BRITEX. 3.3 TYPE P-3 LAVATORY: P-3 LAVATORY: WILLOUGHBY INDUSTRIES WBLS-2018-HC- FA SERIES LAVATORY. WALL-MOUNTED 14-GAUGE 304 STAINLESS STEEL LIGATURE-RESISTANCE CONSTRUCTION, #4 SATIN FINISH. ADA COMPLIANT. OVAL-SHAPED 14X9X5 LAVATORY, LIGATURE-RESISTANT BUBBLER/FILLER, DUAL TEMPERATURE PNEUMATIC METERING VALVE AND PUSH BUTTONS, AND SELF-DRAINING SOAP DISH. WILLOUGHBY INDUSTRIES, ACORN, BRITEX. 3.4 TYPE P-4 COMBINATION LAVATORY/TOILET: WILLOUGHBY INDUSTRIES 1806 SERIES, REAR OUTLET 14-GAUGE, 304 STAINLESS STEEL, WELDED, LIGATURE- RESISTANT CONSTRUCTION, #4 SATIN FINISH. OVAL-SHAPED 13X9.5X6 LAVATORY, LIGATURE-RESISTANT BUBBLER/FILLER, DUAL TEMPERATURE PNEUMATIC METERING VALVE AND PUSH BUTTONS, AND SELF-DRAINING SOAP DISH. 1.28 GPF HYDRAULIC FLUSH VALVE, AUTO RESET OVERFLOW PREVENTER, RECESSED TISSUE HOLDER, AND NO TOWEL HOOK. FIELD VERIFY TOILET ORIENTATION PRIOR TO ORDERING. WILLOUGHBY INDUSTRIES, ACORN, BRITEX. 3.5 TYPE P-5 COMBINATION LAVATORY/TOILET: WILLOUGHBY INDUSTRIES 1806 SERIES, FLOOR OUTLET, 14-GAUGE, 304 STAINLESS STEEL, WELDED, LIGATURE- RESISTANT CONSTRUCTION, #4 SATIN FINISH, REMOVABLE ACCESS PANELS ATTACHED WITH SECURITY SCREWS. OVAL-SHAPED 13 X 9.5 X 6 LAVATORY, LIGATURE-RESISTANT BUBBLER/FILLER, DUAL TEMPERATURE PNEUMATIC METERING VALVE AND PUSH BUTTONS, AND SELF-DRAINING SOAP DISH. 1.28 GPF HYDRAULIC FLUSH VALVE, AUTO RESET OVERFLOW PREVENTER, RECESSED TISSUE HOLDER, AND NO TOWEL HOOK. FIELD VERIFY TOILET ORIENTATION PRIOR TO ORDERING. WILLOUGHBY INDUSTRIES, ACORN, BRITEX. 3.6 TYPE P-6 SHOWER: WILLOUGHBY INDUSTRIES CWSMS SERIES, SURFACE- MOUNTED 18-GAUGE, 304 STAINLESS STEEL, WELDED, LIGATURE-RESISTANT CONSTRUCTION, #4 SATIN FINISH. LIGATURE-RESISTANT TEMPERATURE/PRESSURE BALANCING MIXING VALVE CONTROL. 1.5 GPM LIGATURE-RESISTANT SHOWER HEAD, RECESSED SOAP DISH. LRFD SERIES LIGATURE-RESISTANT FLOOR DRAIN; FIELD-VERIFY EXISTING DRAIN COVER DIAMETER TO MATCH. WILLOUGHBY INDUSTRIES, ACORN, BRITEX. END OF SECTION 22 40 00

1 1

A C F P Q

DOUBLE

U

AutoCAD SHX Text

%%UMECHANICAL FIRST FLOOR PLAN AREA "C"

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

%%UPROJECT

AutoCAD SHX Text

%%UNORTH

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text

JAN.

AutoCAD SHX Text

EXST

AutoCAD SHX Text

NURSE

AutoCAD SHX Text

EXST

AutoCAD SHX Text J116

AutoCAD SHX Text

VEST.

AutoCAD SHX Text

QUT.

AutoCAD SHX Text

MEDICAL EXAM

AutoCAD SHX Text

EXST

AutoCAD SHX Text

LAUNDRY RM

AutoCAD SHX Text

EXST

AutoCAD SHX Text

CORRIDOR 6

AutoCAD SHX Text

EXST

AutoCAD SHX Text

STAFF BATHRM

AutoCAD SHX Text

EXST.

This is the start of the file's text. The full file is on GovTribe.