This solicitation seeks a contractor to perform exterior envelope renovation work at the FAA QJQ Air Route Surveillance Radar facility located in Pico Del Este, Puerto Rico. The selected contractor will be responsible for furnishing all labor, equipment, and materials to complete removal and replacement of the exterior wall panels and insulation on the existing steel decking walls. Additional work includes refurbishing the existing exterior staircase and platform, and installing exterior lighting. The contractor must accomplish all work items identified in the solicitation, specifications, drawings and provisions. The Department of Transportation Federal Aviation Administration Southwestern Region is the issuing agency.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
ENGINEERING SERVICES
OPS INFRASTRUCTURE
ARSR
ELECTRICAL ONE-LINE DIAGRAM
FACILITY EXTERIOR LIGHTING
EXTERIOR BUILDING RESTORATION PROJECT
PR PICO DEL ESTE
NXS
SP
PROJECT ENGINEER MGR: ENGINEERING - CENTER A
06/25/2021 21001848
QJQ-21001848-E003
q jq -2
-e
.d g n
THIS DRAWING PRODUCED ON ASO REGION MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS EASTERN SERVICE AREA
C O
N S
T R
U
IO
/2
:2
:3
A
M P lo tt e d b y
V
-C
E
G -E
D
B
F
H
8 7 6 5 4 3 2 1
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
REDLINE
APVD
IS
PANEL
E/G
CB 23
LIGHT FIXTURE
LED
3 #12AWG
/4" RMC3
POLE MOUNTED
20AMP
PANEL A
20AMP
CONTROL
LIGHTING
SENSOR
MOTION
6 #12AWG
1 " RMC
4 #12AWG
3/4" EMT
J BOX
LED LIGHT FIXTURE
ON SHELTER
ON WALK PATH
LIGHT FIXTURES
POLE MOUNTED
CB 2
CB 1
MOTION SENOR
NOT TO SCALEE003
ONE-LINE GATE AREA
NOT TO SCALEE003
ONE-LINE SHELTER AND WALK PATH AREA
NOT TO SCALEE001
THREE SENSOR INSTALLED IN PARALLEL 4 CONDUCTORS PER SENSOR
BE DE-ENERGIZED.
HOT WORK NOT AUTHORIZED ALL PANELS SHALL 8.
TO TERMINAL THE CONDUCTORS IN PANEL E/G.
E/G PANEL COORDINATE SHUTDOWN WITH FAA RE 7.
AND INSTALL 1 DOUBLE POLE CIRCUIT BREAKER.
ARSR PANEL A REMOVE 2 SINGLE POLE 20 AMP BREAKER 6.
CONDUIT ENTERING AND EXITING TVSS SHALL BE SEALED 5.
NFPA 70. FAA -C-1217.
ALL INSTALLATION SHALL BE IN ACCORDANCE WITH 4.
SHALL BE WEATHER PROOFED
ALL PENETRATIONS FOR CONDUITS EXITING BUILDINGS 3.
WEATHER PROOFED.
ALL PENETRATIONS TO MOUNT FIXTURES SHALL BE 2.
INSTALLED PER FAA STD-019
ALL RSG CONDUIT SHALL HAVE GROUNDING BUSHING 1.
GENERAL NOTES
qjq-21001848-e003
2021-06-24T20:21:36-0400
HENRY B NEWCOMB
2021-06-24T09:56:55-0400
PAUL E PATNOAD
ELECTRICAL CONDUIT RUNS
QJQ-21001848-E004
lo tt e
PARKING
PLATFORM
ANTENNA
X
BUILDING
GENERATOR
ENGINE
FUEL
TA
NK
BLDG NO 3002
RADOME
GATE
3/4" RMC
3409.41
3405.20
EE
NOTE 1
NOTE 2
NOTE 3
XX
3409.29
PAVEMENT
NOT TO SCALEE004
ONE-LINE GATE AREA
INCHES BELOW FINISH GRADE.
BURIED AT NOT LESS THAN 24
THE TOP OF THE CONDUIT IS
CONDUIT SHALL BE INSTALLED SO
DEPTH OF UNDERGROUND9.
PER FAA-STD-019
COUNTERPOISE SHALL BE GROUNDED
RMC CONDUIT THAT CROSSED8.
GROUNDED PER NFPA 70
LIGHT POLE SHALL BE7.
BONDED WITH GROUND CONDUCTOR.
BONDING BUSHINGS INSTALLED AND
ALL RSC CONDUITS SHALL HAVE6.
VIOLATE NEC OR FAA-C-1217
CONDUITS INSTALLATION SHALL NOT
ALL ELECTRICAL WIRING AND5.
PROOFED.
PENETRATIONS SHALL BE WEATHER
EXTERIOR OF SIDING. ALL ANCHOR
LIGHTS SHALL BE RUN ON
CONDUITS FOR WALL MOUNTED4.
EXACT LOCATION TBD.
INSTALLED AT BASE OF SHELTER
MINIMUM SIZS 12 x12x8 SHALL BE
JUNCTION BOX NEMA 4 RATED3.
11" X 18' X 12' OPEN BOTTOM
22 RATED AND MINIMUM SIZE OF
HANDHOLD SHALL BE ANSI TIER2.
LIQUIDTIGHT CONDUIT AS WHIP TO
BOX. CONTRACTOR CAN UTLIZE
4" X 4" NEMA 4 RATED JUNCTION
STEEL CONDUIT TO A MINIMUM SIZE
CONTRACTOR SHALL USE RIGID1.
qjq-21001848-e004
2021-06-24T20:22:28-0400
HENRY B NEWCOMB
2021-06-24T09:58:08-0400
PAUL E PATNOAD
LIGHTING CONTROL PANEL
QJQ-21001848-E005
K1
TB 1
CONTROL SW1
GROUND BUS BAR
:4 lo tt e
HAND OFF AUTO
LIGHTING PANEL PARTS LIST
ITEM DESCRITION PART # SUGGESTED MANUFACTURE SUGGESTED VENDOR
K1 120 VAC COIL 30AMP CONTACTS TWO POLE 8910DP32V02 SQUARE D GRAINGER
SW1 3 POSTION SELECTOR SWITCH XB4BD33 SQUARE D GRAINGER
LEGEND
PLATE
HAND-OFF-AUTO ZBY2387 SQUARE D GRAINGER
TB1 TERMINAL BLOCK 30A AMP 9080GMB6 SQAURE D GRAINGER
TB1 TERMIANL BLOCK END CAP 9080GM6B SQUARE D GRAINGER
TB1 DIN RAIL 9080GH236 SQUARE D GRAINGER
GROUND BAR BROUND BAR KIT PK9GTA SQUARE D GRAINGER
ENCLOSURE NEMA 1 12"X12"X6" A12N126 HOFFMAN GRAINGER
THE CABINET DOOR SHALL BE BONDED TO THE CABINET 3.
BUS BAR.
MAIN CABINET BOX SHALL BE BONDED TO THE GROUND 2.
12 AWG.
ALL INTERNAL WIRING FOR PANEL SHALL BE MINIMUM 1.
qjq-21001848-e005
2021-06-24T20:23:29-0400
HENRY B NEWCOMB
2021-06-24T09:59:16-0400
PAUL E PATNOAD
LIGHTING CONTROL PANEL WIRING
QJQ-21001848-E006
:5 lo tt e
1 2 3 4 5 6 7 8 9 10 1112 1314 15 16
L1 L2 N G
17 18 19 20
K1-1A
K1-2A
K1-1B
K1-2B
PANEL CASE
FROM HINGED DOOR TO
BAR. INSTALL JUMPER
BONDED TO GROUND BUS
NOTE: PANEL CASE IS
L1
ARSR PANEL
L2 N
RELAY
OFF
HAND
AUTO
SENSOR
MOTION
CONTACT
NO
K1-1
2 POLE
20A
120V 120V
FIXTURES
MOUNTED
EXTERIOR WALL
CONTACT
NO
K1-2
ON WALKWAY
FIXTURES
EXTERIOR POLE
1 POLE
1 POLE
SW1
OFF
INTERNAL CONTACT
MOTION SENSOR WITH
TB1
TERMINAL # BOTTOM TERMINAL TOP TERMINAL NOTES
1 L1 K1-1A & JUMPER TO TB1-6
2 L2 K1-2A
3 NEUTRAL K1 COIL
4 GROUND GROUND BUS BAR
5 NOT USED NOT USED
6 SW1 HAND
JUMPER FROM TB1-1 JUMPER TO
TB1-8
7 SW1 COMMON K1 COIL
8 MOTION SENSOR JUMPER FROM TB1-6
9 MOTION SENSOR JUMPER TO TB1-10
10 SW1 AUTO JUMPER FROM TB1-9
11 NOT USED NOT USED
12 CURCUIT 1 L1 K1-1B
13 CIRCUIT 1 N JUMPER FROM TB1-8
14 CIRCUIT 1 GND FROM GROUND BUS BAR
15 CIRCUIT 2 L2 K1-2B
16 CIRCUIT 2 N JUMPER FROM TB1-13
17 CIRCUIT 2 GND FROM GROUND BUS BAR
18 NOT USED NOT USED
19 NOT USED NOT USED
20 NOT USED NOT USED
PANEL WIRING DIAGRAM
NOT TO SCALE
LOGIC LADDER DIAGRAM
LIGHT CONTROL PANEL
SEQUENCE OF OPERATION
K1 COIL.
EXTERNAL PHOTO CELL WILL ENERGIZE
FRONT PANEL SWITCH PLACED IN AUTO. 3.
BREAKER
PROCEDURES AND SECURE INPUT CIRCUIT
IS STILL IN CABINET. USE PROPER LOTO
K1 COIL IS ENERGIZED. NOTE ELECTRICAL POWER
FRONT PANEL SWITCH PLACED IN OFF , CIRCUIT TO 2.
K1-1 AND K1-2
ENERGIZED CLOSING NORMALLY OPEN CONTACTS
FRONT SWITCH PLACE IN HAND POSITION. K1 COIL 1.
ALL CONDUCTOR SHALL BE LABLELD 4.
CABINET
THE CABINET DOOR SHALL BE BONDED TO THE 3.
GROUND BUS BAR
MAIN CABINET BOX SHALL BE BONDED TO THE 2.
MINIMUM 12 AWG
ALL INTERNAL WIRING FOR PANEL SHALL BE 1.
qjq-21001848-e006
2021-06-25T14:03:03-0400
HENRY B NEWCOMB
2021-06-24T10:00:47-0400
PAUL E PATNOAD
DETAILS
QJQ-21001848-E007
:0 lo tt e
ANSI 7-PIN RECEPTACLE.
HOUSE-SIDE SHIELD, PHOTOCELL, INTEGRAL MOTION SENSOR, AND
OPTIONS - MOUNTING ARM LENGTH, LIGHT DISTRIBUTION,7.
MOUNTING - ARM-MOUNTED ON POLE.6.
COMPLIES WITH IES LM79, LM80 AND TM21 TESTING STANDARDS.
CERTIFICATION - UL LISTED FOR WET LOCATION, ROHS COMPLIANT.5.
PER IEEE.
LUMINAIRE SCHEDULE. MEETS ELEVATED 10KV/10KA REQUIREMENTS
AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS INDICATED IN
COMPLIANCE : FCC TITLE 47 PART 15 CLASS B. ON-OFF CONTROL
THERMAL MANAGEMENT, AND < 10% THD. ELECTROMAGNETIC
DRIVER WITH MINIMUM 0.95 PF, OPERATING VOLTAGE OF 120-277V,
DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE4.
INITIAL LUMEN OUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.
CRI UON, AND MINIMUM EFFICACY OF 100 LUMENS/WATT UON.
LIGHT SOURCE - SOLID STATE LEDS, 3000K CCT UON, MINIMUM 703.
RATING AS DETERMINED BY LIGHTING ZONE INSTALLED.
V DISTRIBUTIONS. BUG UPLIGHT RATING OF U0, WITH GLARE
OPTICS - INJECTION MOLDED OPTICS WITH TYPE I, II, III, IV, OR2.
FINISH.
HOUSING - DIE-CAST ALUMINUM HOUSING WITH POWDER COAT1.
LUMINAIRE REQUIREMENTS
INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO
NOTE:THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE
ANSI 7-PIN RECEPTACLE.
HOUSE-SIDE SHIELD, PHOTOCELL, INTEGRAL MOTION SENSOR, AND
OPTIONS - MOUNTING ARM LENGTH, LIGHT DISTRIBUTION,7.
MOUNTING - ARM-MOUNTED ON POLE.6.
ELEVATED 10KV/10KA REQUIREMENTS PER IEEE.
MINIMUM OR AS INDICATED IN LUMINAIRE SCHEDULE. MEETS
COMPLIANCE : FCC TITLE 47 PART 15 CLASS B. DOWN TO 10%
THERMAL MANAGEMENT, AND < 10% THD. ELECTROMAGNETIC
CRI UON, AND MINIMUM EFFICACY OF 100 LUMENS/WATT UON.
V DISTRIBUTIONS. BUG UPLIGHT RATING OF U0, WITH GLARE
OPTICS - INJECTION MOLDED OPTICS WITH TYPE I, II, III, IV, OR2.
FINISH.
HOUSING - DIE-CAST ALUMINUM HOUSING WITH POWDER COAT1.
LUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTS LUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTS
SENSOR, PHOTOCELL, BATTERY BACK-UP.
OPTIONS - VARIOUS LIGHT DISTRIBUTIONS. INTEGRAL MOTION7.
HARDWARE.
MOUNTING - SURFACE MOUNTED WITH STAINLESS STEEL MOUNTING6.
LUMINAIRE SCHEDULE.
AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS INDICATED IN
COMPLIANCE : FCC TITLE 47 PART 15 CLASS B. ON-OFF CONTROL
THERMAL MANAGEMENT, AND < 10% THD. ELECTROMAGNETIC
CRI UON, AND MINIMUM EFFICACY OF 80 LUMENS/WATT UON.
IV DISTRIBUTIONS. BUG UPLIGHT RATING OF U0, WITH GLARE
OPTICS - PRECISION MOLDED ACRYLIC LENS WITH TYPE II, III, OR2.
INTO HOUSING OR DRIVER COMPARTMENT.
PASSIVE COOLING MECHANISM. HEAT SINK INCORPORATED DIRECTLY
HOUSING - DIE-CAST OR EXTRUDED ALUMINUM WITH INTEGRAL1.
LED AREA LUMINAIRE
LED PARKING LOT LUMINAIRE
LED WALL PACK
qjq-21001848-e007
2021-06-24T20:26:06-0400
HENRY B NEWCOMB
2021-06-24T10:01:37-0400
PAUL E PATNOAD
LIGHT POLE DETAILS
QJQ-21001848-E008
:0 lo tt e
"U"
POLE
TYPE
TENON OPTION - 2-3/8" TENON WITH PROVISION
FOR WIRING. COORDINATE WITH LUMINAIRE.
XL-26
MAST ARM OPTION - COORDINATE WIRING AND BOLT HOLES
WITH MAST ARM PROVIDED.
DIM
"U
9"
12"
HEIGHT
8'-12'
13'-20'
21'-30'
36"
42"
12"
31'-40'
72"
78"
16"
24"
30"
"A
"B"
FINISHED GRADE
BASE 1/2"
CHAMFER ALL EDGES OF CONCRETE
SPECIFICATION
HANDHOLE - SEE POLE SKETCH AND
POLE - SEE POLE SKETCH AND
REQUIRED
HANDHOLE; NUMBER AND SIZE AS
CONDUIT STUBBED UP ADJACENT TO
GRADE
FOUNDATION 4" ABOVE
SET TOP OF CONCRETE
CONDUCTOR.
SUPPLY PHASE
SIZE AND TYPE AS
CONDUCTOR TO BE SAME
TO INTERIOR OF POLE.
INTERNAL LUG WELDED
CONDUCTOR - ATTACH TO
GROUNDING
COPPER EQUIPMENT
SOURCE OR NEXT POLE
AND CONDUIT TO POWER
CIRCUIT CONDUCTORS
CONCRETE PER
SOURCE OR NEXT POLE
AND CONDUIT TO POWER
CIRCUIT CONDUCTORS
MANUFACTURER OF POLE
RECOMMENDED BY
ANCHOR BOLTS AS
EACH FACE
#4 BARS VERTICAL AT 6"
HORIZONTALLY
#3 BARS AT 12" ON CENTER
SECTIONAL SHAPE AND COLOR AS INDICATED.
TAPERED OR STRAIGHT STEEL OR ALUMINUM POLE. CROSS
NOTES:
COVER AND STAINLESS STEEL SCREWS.
WIRING HANDHOLE MINIMUM 2 1/2" X 5" CLEAR OPENING WITH
INTERNAL GROUNDING LUG.
TERMINATE C0NDUITS INTERNALLY, ADJACENT TO HANDHOLE.
FULL BASE COVER - TW0 PIECE GALVANIZED STEEL.
CONCRETE FOUNDATION
COORDINATE TOTAL EPA WITH SPECIFICATIONS.
ANCHOR BASE STEEL/ALUMINUM POLE
ANCHOR BASE POLE FOUNDATION
OF 10 FEET.
ALL LAMP POLES INSTALLED SHALL BE AT MAXIMUM HEIGHT 4.
LAMP POLE
CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR SPECIFIED 3.
PLACE.
LEDGE. REBAR ANCHORS SHALL BE FULLY GROUTED IN
OF 6 INCHES PROTRUDING ABOVE THE WITH A MINIMUM
LEDGE. DRILL A MINIMUM OF 6 INCHES INTO THE LEDGE
CONTRACTOR SHALL DRILL AND PIN #4 REBAR INTO THE
REACHING THE DESIRED FOUNDATION DEPTH, THE
IN THE EVENT CONTRACTOR ENCOUNTERS LEDGE BEFORE 2.
STRENGTH 4,000 PSI
CONCRETE SHALL BE MINIMUM 28 DAY COMPRESSIVE 1.
qjq-21001848-e008
2021-06-24T20:26:57-0400
HENRY B NEWCOMB
2021-06-24T10:02:39-0400
PAUL E PATNOAD
PROPOSED CONDUIT RUN IN GENERATOR BUILDING
QJQ-21001848-E009
E/G PANEL
DAY TANK
SPLIT HVAC UNIT CONDENSOR
SPLIT HVAC
3 /4" CONDUIT
CONTROL PANEL
PROPOSED LIGHTING
:1 lo tt e
DEHUMIDIFIER
DEHUMIDIFIER
ATS
ALL EXTERIOR PENETRATIONS SHALL BE WEATHER PROOFED. 4.
PENETRATIONS ON INTERIOR WALL SHALL BE FIRE PROOFED .3.
.SHALL BE INSTALLED IN ACCORDANCE TO FAA-STD-1217
SHALL BE RSG , GROUNDING BUSHINGS SHALL BE INSTALLED. CONDUIT
3/4" CONDUIT FROM LIGHTING CONTROL PANEL TO EXTERIROR WALL 2.
INSTALLED IN ACCRODANCE WITH FAA-STD-1217.
GROUNDING BUSHING SHALL BE INSTALLED. CONDUIT SHALL BE
3/4" CONDUIT FROM E/G TO LIGHTING CONTROL PANEL SHALL BE RSG , 1.
ENGINE GENERATOR BUILDING LAYOUT
qjq-21001848-e009
2021-06-24T20:27:48-0400
HENRY B NEWCOMB
2021-06-24T10:03:27-0400
PAUL E PATNOAD
PROPOSED CONDUIT RUN IN ARSR BUILDING
QJQ-21001848-E010
PANEL A
1" RMC
LIGHTING CONTROLPANEL
lo tt e
TVSS
UP
UNISTRUT
4X2 J-BOX
LIGHT FIXTURE MOUNT
3 /4" RMC CONDUIT
PROPOSED J-BOX
CONDUIT UNDER BUILDING SHALL BE SECURED.5.
ALL INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 70 . FAA -C-1217.4.
PROOFED
ALL PENETRATIONS FOR CONDUITS EXITING BUILDINGS SHALL BE WEATHER 3.
ALL PENETRATIONS TO MOUNT FIXTURES SHALL BE WEATHER PROOFED.2.
FAA STD-019
ALL RMC CONDUIT SHALL HAVE GROUNDING BUSHING INSTALLED PER 1.
PROPOSED LAMP MOUNTING ON ARSR LAYOUT
1ST FLOOR ARSR BUILDING LAYOUT
qjq-21001848-e010
2021-06-24T20:28:35-0400
HENRY B NEWCOMB
2021-06-24T10:05:21-0400
PAUL E PATNOAD
MOTION DETECTION SENSOR
QJQ-21001848-E011
SEPTIC TANK
I.E. 3384.48 T.E. 3388.81
HEADWALL
I.E. = 3377.88
18" DIA ENDS PIPE
I.E .= 3392.50 I.E. = 3394.82
CATCH BASIN
CONCRETE SLAB
CONCRETE
" 50'-0"
30'-0"
PEDESTAL
ELECTRIC
15" DIA ENDS PIPE I.E. = 3419.86
I.E. = 3423.94 lo tt e
X X X X
X X
" D
IA
L
IF
3406.10
X3405.20
3400.33
X3395.92
3396.49
3395.19
X3394.98
3393.98
3394.33
3389.95
X3387.95
3392.05
3393.33
.R
3403.23
W
R
IN
SS
(BLDG NO. 311)
FOUNDATION
(BLDG NO. 3036)
FOUNDATION (BLDG NO. 3012)
EDG
CLI
FF
BRONZE. CONTRACTOR SHALL SUBMIT COLOR SAMPLE FOR APPROVAL.
COLOR OF LIGHT FIXTURE BE NON-REFLECTIVE BLACK OR DARK 5.
MAXIMUM TIME PER SENSOR IS 5 MINUTES
MOTION SENSOR SHALL BE ON BUILDING SHALL BE WIRED IN PARALLEL 5.
APPROVED EQUIVALENT.
DESIGN BASED ON RAB LIGHTING STL2000 MOTION DETECTION OR 4.
15 CLASS B
THD 10% MAXIMUM ELECTROMAGNETIC COMPLIANCE FCC TITLE 47 PART
FIXTURES SHALL BE LED. LIGHT FIXTURE LED 40K RS3 PF .95 MAXIMUM 3.
ALL PENETRATIONS TO MOUNT FIXTURES SHALL BE WEATHER PROOFED.2.
OF EIGHT FEET.
CONTRACTOR SHALL MOUNT ALL LIGHT FIXTURES AT A MINIMUM HEIGHT 1.
SITE PLAN
PIR MOTION DETECTORS FOR LIGHTS ON BUILDINGSITE PLAN
SCALE: 1" = 20'
20' 40'020'
PIR MOTION DETECTORS LOOK-OUT ZONES
PIR MOTION DETECTORS LOOK-DOWN ZONE
qjq-21001848-e011
2021-06-24T20:29:24-0400
HENRY B NEWCOMB
2021-06-24T12:37:47-0400
PAUL E PATNOAD
COVER SHEET
QJQ-21001848-G001
-g lo tt e
T OF TRANSPO
T A
IC
OF
STATES
IT
TM
EN
AVIA
I
LAR
TRAT
SI
NI
QJQ/ARSR - PICO DEL ESTE, PUERTO RICO
qjq-21001848-g001
2021-06-25T14:03:59-0400
HENRY B NEWCOMB
2021-06-28T09:07:25-0400
SUSHMA H PATEL
INDEX SHEET
QJQ-21001848-G002
lo tt e
DRAWING LIST
DRAWING NO. REV. DATE DESCRIPTION
QJQ-21001848-E011
QJQ-21001848-E010
QJQ-21001848-E009
QJQ-21001848-E008
QJQ-21001848-E007
QJQ-21001848-E006
QJQ-21001848-E005
QJQ-21001848-E004
QJQ-21001848-E003
QJQ-21001848-E002
QJQ-21001848-E001
QJQ-21001848-D001
QJQ-21001848-C010
QJQ-21001848-C009
QJQ-21001848-C008
QJQ-21001848-C007
QJQ-21001848-C006
QJQ-21001848-C005
QJQ-21001848-C004
QJQ-21001848-C003
QJQ-21001848-C002
QJQ-21001848-C001
QJQ-21001848-G002
QJQ-21001848-G001
06/25/2021
FACILITY EXTERIOR LIGHTING MOTION DETECTION SENSOR
FACILITY EXTERIOR LIGHTING PROPOSED CONDUIT RUN IN ARSR BUILDING
FACILITY EXTERIOR LIGHTING PROPOSED CONDUIT RUN IN GENERATOR BUILDING
FACILITY EXTERIOR LIGHTING LIGHT POLE DETAILS
FACILITY EXTERIOR LIGHTING DETAILS
FACILITY EXTERIOR LIGHTING LIGHTING CONTROL PANEL WIRING
FACILITY EXTERIOR LIGHTING LIGHTING CONTROL PANEL
FACILITY EXTERIOR LIGHTING ELECTRICAL CONDUIT RUNS
FACILITY EXTERIOR LIGHTING ELECTRICAL ONE-LINE DIAGRAM
FACILITY EXTERIOR LIGHTING PHOTOMETRICS
FACILITY EXTERIOR LIGHTING PLAN
DEMO PLAN
STAIRCASE DETAILS SHEET 2 OF 2
STAIRCASE DETAILS SHEET 1 OF 2
WALL SECTIONS I THRU L
WALL SECTIONS E THRU H
WALL SECTIONS A THRU D
PROPOSED WALL SECTON DETAIL
PROPOSED WALL SECTIONS
EXISTING WALL SECTION DETAILS
BUILDING WALL SECTION LAYOUT PLAN
INDEX SHEET
COVER SHEET
qjq-21001848-g002
2021-06-25T14:05:26-0400
HENRY B NEWCOMB
2021-06-28T09:08:52-0400
SUSHMA H PATEL
EXISTING WALL SECTION DETAILS
QJQ-21001848-C003
-c
EXISTING LOUVER
CORRUGATED SIDING
/16"PVC 3X/16"14.2X
REMOVE EXISTING
Y
13'-0"
'-0
CORRUGATED PANEL
REMOVE EXISTING INSULATION MATERIAL BEHIND PVC
RIGID INSULATION
PANELS
PVC CORRUGATED
PANELS
INSULATION BETWEEN
EXISTING 1.5" RIGID
RADOME LOWER WALL
EXISTING CATWALK
GIVT
STEEL DECKING
WALL 16 GAUGE 3N
EXISTING INTERIOR
IN PLACE
EXISTING GIVT TO STAY
COMPOUND OR APPROVED EQUAL.
PANEL, ZRC COLD GALVANIZING REPAIR
ENTIRE SURFACE OF THE EXISTING INTERIOR
APPLY A CORROSION INHIBITING COATING TO THE
DEFORMED WALL PANEL TO ORIGINAL ALIGNMENT.
WALL PANEL ARE DEFORMED POP-OUT THE
BOARD AND GLUE. IF SOME PORTIONS OF THE
REMOVE ALL RESIDUAL OFF OLD INSULATION
THOROUGHLY CLEAN THE OUTER SURFACE.
EXISTING INTERIOR WALL PANEL TO STAY IN PLACE.
OR DUCT COVER
REMOVE EXISTING LOUVER
INSULATION MATERIAL
REMOVE EXISTING 1.5" RIGID
/16"X2" DIA 24" WELDED TO EXIST. METAL SIDING 3
REMOVE EXISTING CONTINUOUS GALV. PLATE
FASTENERS
S/S GROMMENT SEAL
/8" X12" ALUM. FLASHING 1
GALV PLATE
WELDED CORNER
FOAM)
1.5" RIGID INSULATION (STEREO
REMOVE EXISTING CONTINUOUS
WASHER
SEALING
W/BONDED
DRILL
SELF-
SIDING
EXISTING METAL
FASTENERS
S/S GROMMENT SEAL
SEALING WASHER
SELF-DRILL W/BONDED
EXISTING METAL SIDING
SELF-DRILL W/BONDED SEALING WASHER
"X2" DIA 24" WELDED TO EXIST. METAL SIDING /163
REMOVE EXISTING CONTINUOUS GALV. PLATE
CHANNEL
EXISTING
ANGEL WELDED TO
2"X2" GALV/16" X3
REMOVE
PVC CORRUGATED SIDING
/16"3/16"X14.2X
EXISTING OUTER WALL
PVC CORRUGATED SIDING
/16"3/16"X1OUTER WALL 4.2X
UNDAMAGED EXISTING
REMOVE DAMAGED AND
/0 lo tt e
NOTES
WALL SECTIONS.
ADJACENT REPLACE THE WALL PANEL JOINT COVER BETWEEN THE 6.
GALVANIZING REPAIR COMPOUND OR APPROVED EQUAL.
SURFACE OF THE EXISTING INTERIOR PANEL, ZRC COLD
iv) APPLY A CORROSION INHIBITING COATING TO THE ENTIRE
REPAIR WALL PANEL.
iii) IF SECTIONS OF THE WALL PANEL ARE DAMAGED/CORRODED
. THE DEFORMED WALL PANEL TO ORIGINAL ALIGNMENT
ii) IF SOME PORTIONS OF THE WALL PANEL ARE DEFORMED POP-OUT
RESIDUAL OF OLD INSULATION BOARD AND GLUE.
i) THOROUGHLY CLEAN THE OUTER SURFACE. REMOVE ALL
EXISTING INTERIOR WALL PANEL TO STAY IN PLACE. 5.
MATERIAL.REMOVE AND DISPOSE OF THE EXISTING INSULATION 4.
REMOVE AND DISPOSE OF THE EXTERIOR WALL PANEL..3
REMOVAL.
LOUVER/HOOD/WALL DUCTS. CONFIRM WITH COR PRIOR TO
REMOVE AND DISPOSE OF ANY DAMAGED/OBSTACLE .2
EXTERIOR WALL RETROFIT.
RESTORATION WORK SECTION BY SECTION FOR THE TOWER
EXTERIOR ENVIRONMENT, DURING THE EXTERIOR BUILDING
THE IN ORDER TO PROTECT THE TOWER FROM OVER-EXPOSURE TO 1.
EXISTING WALL SECTION - DEMOLITION
EXTERIOR BUILDING RESTORATION
EXTERIOR
INTERIOR
C003
D - 16 GAUGE 3N STEEL DECKING
C - EXISTING 1.5" RIGID INSULATION IN STEEL DECKING CHANNEL
B - EXISTING INSULATION
A - EXISTING PVC CORRUGATED SIDING - OUTER WALL
DETAIL 3
NOT TO SCALEC003
EXTERIOR CORRUGATED SIDING PANEL PLAN 2
EXISTING BOTTOM PVC SIDING INSTALLATION SECTION 3
EXISTING CORNER SIDING DETAIL
EXISTING WALL SECTIONS4
EXISTING TOWER WALL
qjq-21001848-c003
2021-08-04T09:10:26-0400
HENRY B NEWCOMB
2021-08-04T15:11:14-0400
YING XIA CAI
PROPOSED WALL SECTIONS
QJQ-21001848-C004
RADOME LOWER WALL
GIVT
APPROVED EQUAL.
COMPOUND OR
GALVANIZING REPAIR
PANEL, ZRC COLD
SURFACE OF THE
TO THE ENTIRE
INHIBITING COATING
APPLY A CORROSION
ALIGNMENT.
PANEL TO ORIGINAL
THE DEFORMED WALL
DEFORMED. POP-OUT
WALL PANEL ARE
PORTIONS OF THE
AND GLUE. IF SOME
INSULATION BOARD
RESIDUAL OF OLD
REMOVE ALL
THE OUTER SURFACE.
THOROUGHLY CLEAN
IN PLACE.
WALL PANEL TO STAY
PANEL AND SCREW IN PLACE.
INTERIOR OVERLAP ONTO WALL
SAME SIZE AS EXISTING
STEEL DECKING WALL PANEL.
INSTALL NEW 16 GAUGE 3N
CATWALK
CHANNEL.
TOP TO BOTTOM OF
VALUE OF 7 FROM
AN APPROXIMATE R
INSULATION WITH
ENGINEERED RIGID
INSTALL NEW 1"
BOTTOM.
AREAS FROM TOP TO
4 COVERING ALL SURFACE
APPROXIMATE R VALUE OF
INSULATION WITH AN
ENGINEERED FANFOLD
/8"3INSTALL NEW
COLOR
FOREST GREEN
SIDING PANEL
CORRUGATED
/16" PVC 3X
/16"1
OUTER WALL 4.2X
INSTALL NEW
DECKING CHANNEL.
BOTTOM OF STEEL
OF 5 FROM TOP TO
APPROXIMATE R VALUE
INSULATION WITH AN
ENGINEERED RIGID
/2" 1INSTALL NEW
WALL 16 GAUGE 3N
BEAM
CONCRETE FOUNDATION
/0 lo tt e
CORNER SECTIONS.
INSTALL NEW CORNER SIDING ALUMINUM FLASHING AT EACH 8.
FROM TOP TO BOTTOM.
EXTERIOR SURFACE NEEDS TO COVER ALL TOWER WALL SECTIONS
INSTALL NEW PVC CORRUGATED WALL PANEL. THIS IS THE 7.
FROM TOP TO BOTTOM. ADHERE IN BETWEEN INSULATION MATERIAL.
APPROXIMATE R VALUE OF 4. TO COVER ALL TOWER WALL SECTIONS
" FANFOLD INSULATION WITH AN 8
INSTALL NEW ENGINEERED 6.
INSULATION WITH AN APPROXIMATE R VALUE OF 5.
" 2
APPROXIMATE R VALUE OF 7 ADHERED TO THE 2ND LAYER OF
TOGETHER. 1ST LAYER OF 1" ENGINEERED INSULATION WITH AN
FROM TOP TO BOTTOM. 2 LAYERS OF INSULATION ADHERED
CHANNEL INSTALL NEW INSULATION MATERIAL IN STEEL DECKING 5.
ADJACENT WALL SECTIONS.
THE REPAIR OR REPLACE THE WALL PANEL JOINT COVER BETWEEN 4.
WHOLE SECTION/HEIGHT.
WALL PANEL WITH NEW STEEL DECKING PANEL COVERING THE
INTERIOR INSTALL NEW STEEL DECKING PANEL. OVERLAP EXISTING 3.
COMPOUND OR APPROVED EQUAL.
OF THE EXISTING INTERIOR PANEL, ZRC COLD GALVANIZING REPAIR
iv) APPLY A CORROSION INHIBITING COATING TO THE ENTIRE SURFACE
DAMAGED/CORRODED WALL PANEL/SHELL.
FOR INTERIOR WALL SECTIONS REPAIR REPAIR WALL PANEL.
IF SECTIONS OF THE WALL PANEL ARE DAMAGED/CORRODED iii)
. THE DEFORMED WALL PANEL TO ORIGINAL ALIGNMENT
POP-OUT IF SOME PORTIONS OF THE WALL PANEL ARE DEFORMED ii)
OF OLD INSULATION BOARD AND GLUE.
RESIDUAL THOROUGHLY CLEAN THE OUTER SURFACE. REMOVE ALL i)
EXISTING INTERIOR WALL PANEL TO STAY IN PLACE. 2.
BEGIN WITH.
CONSULT AND CONFIRM WITH ONSITE COR WHICH SECTION TO
WALL RETROFIT, CONSTRUCT SECTION BY SECTION A THRU L.
EXTERIOR ENVIRONMENT DURING THE TOWER SHELL/EXTERIOR
THE IN ORDER TO PROTECT THE TOWER FROM OVER-EXPOSURE TO 1.
INSTALL NEW WALL SECTION
NOT TO SCALEC004
PROPOSED TOWER WALL SECTIONS
qjq-21001848-c004
2021-08-04T09:11:31-0400
HENRY B NEWCOMB
2021-08-04T15:12:57-0400
YING XIA CAI
QJQ-21001848-C001
I.E. = 3377.88
18" DIA ENDS PIPE
CONCRETE SLAB
I.E .= 3392.50 I.E. = 3394.82
SEPTIC TANK
PEDESTAL
ELECTRIC
15" DIA ENDS PIPE
I.E. = 3419.86 lo tt e
X X X
3409.31
X8
SPOT ELEVATION
CONTOUR ELEVATION
DIRECTION OF FLOW
EDGE OF CLIFF
WATER LINE
VALVE AND VALVE BOX
POST INDICATOR VALVE
FIRE HYDRANT
HEADWALL WITH WING WALLS
CATCH BASIN OR CURB INLET
STORM SEWER DRAIN
SANITARY DRAIN LINE
CLEAN OUT
POWER POLE
LIGHTING POLE
COMMUNICATION POLE
LIGHTING ROD
OVERHEAD ELECTRIC LINE
OVERHEAD TELEPHONE LINE
UNDERGROUND ELECTRIC DUCT
CONCRETE CURB
UNDERGROUND STRUCTURE
FENCE
SURVEY STATION
SURVEY POINT
BENCHMARK
x x x
UNDERGROUNDU/G
TYPICALTYP
TOP ELEVATIONTE
NUMBERNU
NORTHN
INVERT ELEVATIONIE
GREEN AREAGA
GALVANIZEDGALV
FINISHED FLOOR ELEVATIONFFE
EASTE
DIAMETERO
CONCRETECONC
BUILDINGBLDG
ES
STREET LIGHT, FIBERGLASS
POWERLINE
GROUNDING WIRE
GROUNDING ROD
TL
PL
LR
CP
LP
PP
EW
OH
15.5015.50
PALMER
SAN VINCENTE
CAMPAMENTO DE NINOS
RAMOS
SABANA
MARGARITA
BARTOLO LAS TRES T
CTRA 3
MALPICA
LA DOLORES
CAMPAMENTO ELIZA COLBERG
PICO RADAR
PLAYA FORTUNA
LUQUILLO
RIO GRANDE
HATO CANDAL
DESCRIPTIONELEVATIONCOORDINATESGEOGRAPHICAL
COORDINATES
LAMBERT
STATION
N E LATITUDE LONGITUDE FEET
1 158,397.4828 734,033.9795 18°16'06.1472" 65°45'31.4878" 3,410.459 RAILROAD SPIKE
PICO 21966(13) 158,455.6900 733,987.3954 18°16'06.7258" 65°45'31.9691" 3,435.032 USNHO DISK
2 158,406.7271 734,104.1666 18°16'06.2363" 65°45'30.7592" 3,406.527 CONCRETE MONUMENT
3 158,401.9196 733,979.0054 18°16'06.1933" 65°45'32.0581" 3,421.220 CONCRETE MONUMENT
4 158,489.0829 733,923.0744 18°16'07.0593" 65°45'32.6352" 3,424.156 CONCRETE MONUMENT
5 158,518.9519 734,002.8763 18°16'07.3526" 65°45'31.8059" 3,429.944 CONCRETE MONUMENT
6 158,585.9561 734,096.8331 18°16'08.0155" 65°45'30.8284" 3,394.780 RAILROAD SPIKE
7 158,608.7727 734,025.6610 18°16'08.2423" 65°45'31.5661" 3,392.722 ZINC NAIL
8 158,671.4070 733,987.3788 18°16'08.8646" 65°45'31.9609" 3,389.266 RAILROAD SPIKE
9 158,562.8597 733,923.6351 18°16'07.7908" 65°45'32.6265" 3,418.014 CONCRETE MONUMENT
ABBREVIATIONS
PUERTO RICO VICINITY MAP
LEGEND
,8
734, 000
.R
I.E. 3384.48 T.E. 3388.81
HEADWALL
3387.95
3389.95
(BLDG NO. 311)
3394.33
3393.98 3394.98
3395.19
734,200N
,6
3395.92
IF
3411.62
3412.27
3413.51
3412.69
3411.08 3410.36
3409.31
734,000
,4
R
GALVANIZED PIPE
4" DIA
" D
(PICO 1966)
B.M. NO. 1
3407.74
3410.29 qjq-21001848-c001
2021-06-25T13:55:48-0400
HENRY B NEWCOMB
2021-06-28T08:24:28-0400
SUSHMA H PATEL
BUILDING WALL SECTION LAYOUT PLAN
QJQ-21001848-C002
J
K lo tt e
OFFICER REPRESENTATIVE (COR).
COMMUNICATE AND CONFIRM WITH ONSITE CONTRACTING
START WITH THE SECTION OF WALL WITH MOST DAMAGE. 3.
POTENTIAL WATER LEAKING.
THE BOTTOM OF THE WALL TO THE BOTTOM OF DOME, TO AVOID
FROM FOR EACH WALL SECTION, THE WALL WILL BE RETROFITTED 2.
BY SECTION, FOR ALL SECTIONS A THRU L.
ENVIRONMENT, THE WALL RETROFIT WILL BE COMPLETED SECTION
TO AVOID OVER-EXPOSURE OF TOWER WALL SECTIONS TO THE 1.
UP
1ST LEVEL
2ND LEVEL
ANTENNA DECK
NOT TO SCALEC002
RADOME BUILDING FIRST FLOOR LAYOUT PLAN
NOT TO SCALEC002
EXISTING CORNER SIDING DETAIL
qjq-21001848-c002
2021-06-24T19:59:17-0400
HENRY B NEWCOMB
2021-06-24T17:01:04-0400
YING XIA CAI
PROPOSED WALL SECTION DETAIL
QJQ-21001848-C005
TO EXIST. METAL SIDING
WELDED /16"X2" DIA 24" 3INSTALL CONTINUOUS GALV. PLATE
FLASHING
VERTICALLY EACH SIDE OF CORNER
SELF-DRILLING SCREW 6" O.C.
/8" X12" ALUM. FLASHING 1INSTALL NEW
WELDED CORNER GALV PLATE
INSTALL NEW 1" RIGID INSTALLATION
S/S GROMMENT SEAL FASTENERS
WELDED TO EXIST. METAL SIDING
/16"X2" DIA 24" 3INSTALL CONTINUOUS GALV. PLATE
EXISTING CHANNEL
ANGEL WELDED TO CHANNEL
SUITABLE TO THE ENVIRONMENT Z
GA OR STAINLESS STEEL AS
GALVANIZED 18/16" X 2"X2"3INSTALL
CORRUGATED SIDING
/16"PVC /16"X31 INSTALL 4.2X
Y
/16" 3/16 "X1 INSTALL 4.2X
CURVED PLATE
EXISTING CATWALK
SIDING. 1" BELOW CATWALK CURVED PLATE
NEW METAL SIDING TO OVERLAP EXISTING METAL
DECKING /2" RIGID INSULATION IN STEEL 1NEW
CORRUGATED SIDING PANEL
/16 "PVC 3/16 "X1 INSTALL 4.2X
SEALANT
TO THE ENVIRONMENT
GALVANIZED 18 GA OR STAINLESS STEEL AS SUITABLE
INSTALL NEW C-SHAPE WATER PREVENTION PLATE
TBD
/8" FANFOLD INSULATION3NEW
NEW 1" RIGID INSULATION IN STEEL DECKING
NEW METAL SIDING TO OVERLAP EXISTING METAL SIDING.
/2" RIGID INSULATION IN STEEL DECKING CHANNEL1NEW
/8" FANFOLD INSULATION3NEW
NEW 1" RIGID INSULATION IN STEEL DECKING CHANNEL
INSTALL NEW METAL SIDING
W/BONDED
SELF-DRILL
/2" RIGID INSTALLATION1INSTALL NEW
/8" FANFOLD INSTALLATION3INSTALL NEW INSTALL BUTYL LIQUID RUBBER
STAINLESS STEEL Z ANGEL
WALL SIDING AND GALVANIZED 18 GA OR
INSTALL BUTYL TAPE ADHERED BETWEEN
ENVIRONMENT Z ANGEL WELDED TO CHANNEL
STAINLESS STEEL AS SUITABLE TO THE
OR/16" X 2"X2" GALVANIZED 18 GA3INSTALL
8" O.C. HORIZONTAL
ABOVE EXIST. CHANNEL AT
SEALING WASHER. 1-1/2"
VERTICAL
HORIZONTAL AND 18" O.C.
EXIST. CHANNEL AT 8" O.C.
SEALING WASHER. 1" ABOVE
HEIGHT OF TOWER
CORRUGATED SIDING PANEL, ENTIRE
CORNER SIDING PANEL AND PVC
INSTALL BUTYL TAPE ADHERED BETWEEN
PANEL, ENTIRE HEIGHT OF TOWER
AND PVC CORRUGATED SIDING
BETWEEN CORNER SIDING PANEL
INSTALL BUTYL TAPE ADHERED
/16" 3/16 "X1 INSTALL 4.2X
INSULATION.
RIGID /2" 1NEW
INSULATION ADHERED TO
/8" FANFOLD 3NEW
SIDING
CORRUGATED SIDING PANEL TO THE METAL
VERTICALLY SECURING THE PVC
SELF-DRILLING SCREW 2" LONG O.C.
HEIGHT.
WIDE ENTIRE WALL
INSTALL BUTYL TAPE 1.5"
INSTALL NEW 1" RIGID INSTALLATION
INSTALL NEW METAL SIDING
1/2" RIGID INSTALLATIONINSTALL NEW
/8" FANFOLD INSTALLATION3INSTALL NEW
" SIDING
CORRUGATED SIDING PANEL TO THE METAL
VERTICALLY SECURING THE PVC
SELF-DRILLING SCREW 2" LONG O.C.
TOP WALL COVER
BOTTOM WALL COVER
1"
RIGID INSULATION.
ADHERED TO NEW 1"
INSULATION
NEW 1/2" RIGID
SIDING, TO OVERLAP EXISTING SIDING.
SAME SIZE AS EXISTING METAL
INSTALL NEW METAL SIDING.
METAL SIDING
SECURING NEW AND EXISTING
VERTICALLY IN THE TROUGH
24" O.C. HORIZONTALLY AND
DRILLING, PAN HEAD SCREW @
PIN-IN TORX DRIVE SELF-
INSULATION TO METAL SIDING
IN EACH TROUGH SECURING
2" LONG @ 36" O.C. VERTICALLY
SELF-DRILLING SCREW
WALL LENGTH.
INSTALL BUTYL TAPE 1.5" WIDE ENTIRE
1"
BOTTOM OR TOP END OF WALL COVER
lo tt e
CORRUGATED PANEL AS SHOWN IN DETAIL.
AS WELL AS 1" AWAY FROM TOP AND BOTTOM END OF PVC
CORRUGATED VALLEY HORIZONTALLY AND VERTICALLY AT 24" O.C.
DRILLING FASTENERS SHALL CONNECT TO METAL SIDING EVERY 2ND
FOR PVC CORRUGATED SELF DRILLING SCREW DETAIL. SELF-7.
MINIMUM 1" AWAY FROM THE OUTER LAP AS SHOWN IN DETAIL.
INSTALL SELF- DRILLING SCREWS EVERY 2ND CORRUGATE AT
WHEN END LAP IS NECESSARY, THE END LAP SHALL BE 6" MINIMUM.
LAP FOR END LAP DETAIL ONLY USE IF NEEDED. AVOID VERTICAL 6.
CAULK.
AND ALL SELF-DRILLING SCREWS WILL BE SEALED WITH WASHER 5.
EQUAL.
HVF MANUFACTURING CORP'S STANDARD FASTENERS OR APPROVED
METAL SIDING SHALL BE SGSF-TYPE GROMMET SEAL FASTENERS OF
TO SELF-SECURING SCREW TO BE USED FOR SECURING PVC PANEL 4.
FASTENERS OR APPROVED EQUAL.
FASTENERS OF HVF MANUFACTURING CORP'S STANDARD
PVC PANELS TO METAL SIDING SHALL BE SSA-TYPE OR SSB-TYPE
CORRUGATED SELF-DRILLING SCREW TO BE USED FOR SECURING 3.
OR APPROVED EQUAL.
INSULATION INSULATION SHALL BE CARLISLE ENGINEERED R-TECH 2.
PVC CORRUGATED PANEL SHALL BE FOREST GREEN IN COLOR.1.
INSTALL NEW WALL SECTION
MIN. SIDE LAP
2 CORR.
EVERY 2ND
CORRUGATE
VALLEY
EVERY 2ND
CORRUGATE
VALLEY
NOT TO SCALEC005
TOP PVC SIDING INSTALLATION SECTION
CORNER SIDING DETAIL
CLOSE UP OF SIDE LAP (JOINT) OF WALL COVER
SELF DRILLING SCREW
PVC CORRUGATED PANEL
END LAP WALL SECTION
BOTTOM PVC SIDING INSTALLATION SECTION
qjq-21001848-c005
2021-06-24T20:02:03-0400
HENRY B NEWCOMB
2021-06-24T17:05:52-0400
YING XIA CAI
WALL SECTIONS A THRU D
QJQ-21001848-C006
CAMERAS
SECURITY
J - BOX
ELECTRICAL
CONDUIT
PVC
OVERHANG
CABLE
STEEL
STRUCTURAL
VENT
CONTAINER
WATER
CATWALK HOODS
LOUVER
HOOD
HOODS
UNIT PLATFORM
HVAC CONDENSING
UNIT
CONDENSING
HVAC
SWITCH
DISCONNECT
UNIT PLATFORM
HVAC CONDENSING
UNIT CONDUIT
UNIT CONDUIT
STAIRCASE
lo tt e
NOT TO SCALEC006
WALL SECTION A 2
WALL SECTION B
WALL SECTION C 4
WALL SECTION D
THROUGHOUT CONSTRUCTION, FROM DEBRIS AND DAMAGE.
CONTRACTOR SHALL PROTECT THE RADAR SYSTEM AND ANTENNAS 10.
DAMAGE.
CONDENSING UNITS THROUGHOUT CONSTRUCTION, FROM DEBRIS AND
CONTRACTOR SHALL PROTECT THE HVAC SYSTEM AND THE EXTERIOR 9.
DAMAGED CONTRACTOR IS RESPONSIBLE TO INSTALL NEW IMMEDIATELY.
CONNECTED TO THE EXTERIOR WALL PANELS. IF ANY ITEMS ARE
RESPONSIBLE TO REMOVE AND REINSTALL ALL ELECTRICAL ITEMS
DURING THE EXTERIOR BUILDING RESTORATION CONTRACTOR IS 8.
IS DAMAGED, INSTALL NEW PVC PIPE.
IF THE PVC PIPE FOR THE LIGHTNING PROTECTION DOWN CONDUCTORS
DURING REMOVAL AND REPLACEMENT OF EXTERIOR BUILDING PANELS 7.
NEW EXTERIOR SYSTEM.
INSTALL NEW LIGHTNING PROTECTION CONNECTORS/HARDWARE ON 6.
IT IS DAMAGED OR DISRUPTED THE CONTRACTOR SHALL FIX IMMEDIATELY.
SHALL BE MAINTAINED THROUGHOUT THE PROJECT. IF AT ANY POINT
NEEDED. THE INTEGRITY OF THE LIGHTENING PROTECTION SYSTEM
REMOVE AND RECONNECT LIGHTNING PROTECTION EACH DAY AS
DURING THE REMOVAL AND REPLACEMENT OF EACH WALL SECTION, 5.
ABANDONED IN PLACE. CONFIRM WITH ONSITE COR PRIOR TO REMOVAL.
REMOVE AND DISPOSE OF ANY LIGHT / SECURITY CAMERAS THAT IS 4.
DUCTS. CONFIRM WITH ONSITE COR PRIOR TO REMOVAL.
REMOVE AND DISPOSE OF ANY DAMAGED/OBSTACLE LOUVER/HOOD/WALL 3.
REPLACEMENT.
EACH ITEM ON THE WALL SECTION PRIOR TO THE WALL SECTION
THE CONTRACTOR. THE CONTRACTOR IS RESPONSIBLE TO VERIFY
WALL SECTION IMAGES AND CALLOUTS ON THIS PAGE ARE TO ASSIST 2.
EXTERIOR RETROFIT.
RESTORATION, WORK SECTION BY SECTION FOR THE TOWER
EXTERIOR ENVIRONMENT DURING THE EXTERIOR BUILDING
IN ORDER TO PROTECT THE TOWER FROM OVER-EXPOSURE TO THE 1.
LOUVER HOOD
LIGHTS
HANDRAIL
DOOR
ENTRANCE
qjq-21001848-c006
2021-06-25T13:56:53-0400
HENRY B NEWCOMB
2021-06-28T08:27:55-0400
SUSHMA H PATEL
WALL SECTIONS E THRU H
QJQ-21001848-C007
3" PIPECONDUIT
NOT TO BE TOUCHED OR MOVED
TO STAY IN PLACE AND OPERATIONAL
RADAR SATELLITE EQUIPMENT
DRAIN PIPE
MOUNTED LIGHT
LIGHT
CAMERA
NOT TO BE TOUCHED OR MOVED
TO STAY IN PLACE AND OPERATIONAL
SATELLITE RADAR EQUIPMENT
EQUIPMENT
SATELLITE RADAR
LADDER
STRUCTURAL STEEL
PIPE
lo tt e
NOT TO SCALEC007
WALL SECTION E 2
WALL SECTION F
WALL SECTION G 4
WALL SECTION H
qjq-21001848-c007
2021-06-25T13:58:08-0400
HENRY B NEWCOMB
2021-06-28T08:36:58-0400
SUSHMA H PATEL
WALL SECTIONS I THRU L
QJQ-21001848-C008
SYSTEM
PLATFORM WITH
WALL SECTION
WITH EXTERIOR
TO BE COVERED
ENTRANCE DOOR
CABLE TRAY
SUPPORT
CABLE TRAY
LIFT ARM
DOCK
LOADING
LOADING DOCK
WITH HANDRAIL
CONDUITS
MOUNTED LIGHT
CONDUIT FOR
2ND FLOOR
HANDRAIL SYSTEM
1ST FLOOR ENTRANCE
1ST FLOOR
lo tt e
NOT TO SCALEC008
WALL SECTION I 2
WALL SECTION J
WALL SECTION K 4
WALL SECTION L
STAIRCASE WITH
WIND SCREEN
qjq-21001848-c008
2021-06-25T14:06:39-0400
HENRY B NEWCOMB
2021-06-28T08:58:13-0400
SUSHMA H PATEL
SHEET 1 OF 2
STAIRCASE DETAILS
QJQ-21001848-C009
GALVANIZED METAL
"1/2REFURBISH 1"X
4'-0" 8'- 8 3/8" 4'-0" 1' 0"
/8
2ND FLOOR ENTRANCE
COLUMNS/FRAMES
SUPPORTING
WITH
ALUMINUM SHEET.
PERFORATED
GAUGE
SCREEN - 14
WIND SHIELD
SYSTEM ALONG
6"
STEPS
GRATE
STEPS
GRATE
EXISTING STAIRCASE
ALL SIDES.
FASTENERS AT 6" O.C. ALONG
SHEET WITH SELF-DRILLING
SECURE NEW ALUMINUM
lo tt e
PRODUCTS INTERNATIONAL OR APPROVED EQUAL.
RUST GRIP A POLYURETHANE COATING PRODUCT BY SUPERIOR
PAINT ALL SURFACES OF THE STEEL MEMBERS WITH 2 COATS OF 13.
SECTION LOSS.
- REINFORCE CORRODED STEEL MEMBERS WITH SIGNIFICANT
STRUCTURE RETROFIT THE EXISTING EXTERIOR STEEL STAIRCASE 12.
ABATEMENT PER OSHA AND LOCAL REGULATIONS.
LEAD BASED PAINT. CONTRACTOR NEEDS TO PERFORM LEAD
STAIRCASE. BE ADVISED EXISTING PAINT TESTED POSITIVE FOR
CLEAN ALL THE CORRODED STEEL OF THE STRUCTURAL STEEL 11.
AT 6" O.C. ALONG ALL SIDES.
FASTENERS SECURE NEW ALUMINUM SHEET WITH SELF-DRILLING 10.
MANUFACTURE NUMBER 03063125r188S 36X40 OR APPROVED
STAGGERED HOLE PATTERN GRAINGER ITEM#5PDA6
INSTALL NEW 14 GAUGE PERFORATED ALUMINUM SHEET, 9.
SUPERIOR PRODUCTS INTERNATIONAL OR APPROVED EQUAL.
FRAME WITH RUST GRIP A POLYURETHANE COATING PRODUCT BY
SUPPORTING PAINT ALL SURFACES OF THE WIND SHIELD SCREEN 8.
SURFACE FRAME.
SUPPORTING BRUSH CLEAN THE EXISTING WIND SHIELD SCREEN 7.
SHIELD SCREENS AND SCREWS.
SCREEN AND EXISTING SCREWS. REPLACE THEM WITH NEW WIND
REMOVE ALL EXISTING CORRODED/DAMAGED WIND SHIELD 6.
RUST GRIP.
ON ALL HANDRAILS PRIOR TO THE APPLICATION OF 2ND LAYER OF
APPLICATION CONTRACTOR SHALL BRUSH A LAYER OF SHARK GRIP
EQUAL. 2 COATINGS OF RUST GRIP SHALL BE APPLIED. AFTER 1ST
PRODUCT BY SUPERIOR PRODUCTS INTERNATIONAL OR APPROVED
GRATING STEPS WITH RUST GRIP A POLYURETHANE COATING
PAINT ALL SURFACES OF THE EXTERIOR STAIRCASE SYSTEM, 5.
COATINGS OF RUST GRIP SHALL BE APPLIED. AFTER 1ST
BY SUPERIOR PRODUCTS INTERNATIONAL OR APPROVED EQUAL. 2
AND RAILS WITH RUST GRIP A POLYURETHANE COATING PRODUCT
POST PAINT ALL SURFACES OF THE EXTERIOR HANDRAIL SYSTEM, 4.
CONTRACTOR SHALL INSTALL STAINLESS STEEL MATERIAL.
INSTALLED FOR THE HANDRAIL SYSTEM TO BE IN COMPLIANT,
ADDITIONAL RAILING/TOE BROADS OR MATERIAL NEED TO BE
MEET OSHA REGULATIONS PER 1910.29 FALL PROTECTION. IF
STAIRCASES AND PLATFORMS AROUND THE EXTERIOR BUILDING
CONTRACTOR SHALL ENSURE ALL HANDRAIL SYSTEMS FOR 3.
FOR LEAD BASED PAINT. CONTRACTOR NEEDS TO PERFORM LEAD
ADVISED EXISTING PAINT ON HANDRAIL SYSTEM TESTED POSITIVE
CLEAN ALL THE CORRODED HANDRAIL SYSTEM SURFACES. BE 2.
PLATFORMS AROUND THE EXTERIOR OF THE BUILDING.
PRESSURE WASH CLEAN CONCRETE STEPS, GRATING AND ALL 1.
AROUND THE EXTERIOR OF ARSR BUILDING.
SHIELD SCREEN, EXTERIOR ENTRANCES/EQUIPMENT PLATFORMS
RETROFIT THE EXISTING STAIRCASE HANDRAIL SYSTEM, WIND
NOT TO SCALEC009
SIDE VIEW STAIR RADIATION SHIELD DETAIL
PLAN VIEW MAIN ENTRY STAIR SYSTEM
WIND SHIELD SCREEN SUPPORTING FRAME
qjq-21001848-c009
2021-06-24T20:13:05-0400
HENRY B NEWCOMB
2021-06-24T14:49:29-0400
YING XIA CAI
WITH HANDRAIL
GRATE STEPS
CONCRETE STEPS
SHEET 2 OF 2
STAIRCASE DETAILS
QJQ-21001848-C010
lo tt e
PRODUCTS INTERNATIONAL OR APPROVED EQUAL.
RUST GRIP A POLYURETHANE COATING PRODUCT BY SUPERIOR
PAINT ALL SURFACES OF THE STEEL MEMBERS WITH 2 COATS OF 13.
SECTION LOSS.
- REINFORCE CORRODED STEEL MEMBERS WITH SIGNIFICANT
STRUCTURE RETROFIT THE EXISTING EXTERIOR STEEL STAIRCASE 12.
LEAD BASED PAINT. CONTRACTOR NEEDS TO PERFORM LEAD
STAIRCASE. BE ADVISED EXISTING PAINT TESTED POSITIVE FOR
CLEAN ALL THE CORRODED STEEL OF THE STRUCTURAL STEEL 11.
AT 6" O.C. ALONG ALL SIDES.
FASTENERS SECURE NEW ALUMINUM SHEET WITH SELF-DRILLING 10.
MANUFACTURE NUMBER 03063125r188S 36X40 OR APPROVED
STAGGERED HOLE PATTERN GRAINGER ITEM#5PDA6
INSTALL NEW 14 GAUGE PERFORATED ALUMINUM SHEET, 9.
SUPERIOR PRODUCTS INTERNATIONAL OR APPROVED EQUAL.
FRAME WITH RUST GRIP A POLYURETHANE COATING PRODUCT BY
SUPPORTING PAINT ALL SURFACES OF THE WIND SHIELD SCREEN 8.
SURFACE FRAME.
SUPPORTING BRUSH CLEAN THE EXISTING WIND SHIELD SCREEN 7.
SHIELD SCREENS AND SCREWS.
SCREEN AND EXISTING SCREWS. REPLACE THEM WITH NEW WIND
REMOVE ALL EXISTING CORRODED/DAMAGED WIND SHIELD 6.
EQUAL. 2 COATINGS OF RUST GRIP SHALL BE APPLIED. AFTER 1ST
PRODUCT BY SUPERIOR PRODUCTS INTERNATIONAL OR APPROVED
GRATING STEPS WITH RUST GRIP A POLYURETHANE COATING
PAINT ALL SURFACES OF THE EXTERIOR STAIRCASE SYSTEM, 5.
COATINGS OF RUST GRIP SHALL BE APPLIED. AFTER 1ST
BY SUPERIOR PRODUCTS INTERNATIONAL OR APPROVED EQUAL. 2
AND RAILS WITH RUST GRIP A POLYURETHANE COATING PRODUCT
POST PAINT ALL SURFACES OF THE EXTERIOR HANDRAIL SYSTEM, 4.
CONTRACTOR SHALL INSTALL STAINLESS STEEL MATERIAL.
INSTALLED FOR THE HANDRAIL SYSTEM TO BE IN COMPLIANT,
ADDITIONAL RAILING/TOE BROADS OR MATERIAL NEED TO BE
MEET OSHA REGULATIONS PER 1910.29 FALL PROTECTION. IF
STAIRCASES AND PLATFORMS AROUND THE EXTERIOR BUILDING
CONTRACTOR SHALL ENSURE ALL HANDRAIL SYSTEMS FOR 3.
FOR LEAD BASED PAINT. CONTRACTOR NEEDS TO PERFORM LEAD
ADVISED EXISTING PAINT ON HANDRAIL SYSTEM TESTED POSITIVE
CLEAN ALL THE CORRODED HANDRAIL SYSTEM SURFACES. BE 2.
PLATFORMS AROUND THE EXTERIOR OF THE BUILDING.
PRESSURE WASH CLEAN CONCRETE STEPS, GRATING AND ALL 1.
AROUND THE EXTERIOR OF ARSR BUILDING.
SHIELD SCREEN, EXTERIOR ENTRANCES/EQUIPMENT PLATFORMS
RETROFIT THE EXISTING STAIRCASE HANDRAIL SYSTEM, WIND
NOT TO SCALEC010
STAIRCASE ENTRANCE 3
LOADING DOCK PLATFORM VIEW 2
LOADING DOCK PLATFORM VIEW 1
qjq-21001848-c010
2021-06-25T14:01:58-0400
HENRY B NEWCOMB
2021-06-28T09:05:20-0400
SUSHMA H PATEL
DEMO PLAN
QJQ-21001848-D001
-d
-d lo tt e
GENERAL NOTE
WIRING.
FIXTURES AND ALL ASSOCIATED CONDUIT AND
LAMP , CONTRACTOR SHALL REMOVE EXISTING
REUTILIZE EXISTING POLE FOR REPLACEMENT
EXISTING LAMP POLE , CONTRACTOR SHALL 1.
qjq-21001848-d001
2021-06-24T20:18:24-0400
HENRY B NEWCOMB
2021-06-24T09:52:49-0400
PAUL E PATNOAD
PLAN
QJQ-21001848-E001
lo tt e
0.1 FC
EDGE
X 3395.92
GALVANIZED PIPE
4" DIA
(PICO 1966)
B.M. NO. 1
(BLDG NO. 3012)
NOTE 2
20 FC
10 FC
5 FC
1 FC
0.5 FC
SAMPLE FOR APPROVAL.
BLACK 0R DARK BRONZE. CONTRACTOR TO SUBMIT COLOR
COLOR OF LIGHT FIXTURE AND LAMP POLE NON-REFLECTIVE 4.
VP-S-36L-80-3K-7-FR-BC OR APPROVED EQUIVALENT.
DESIGNED BASED ON HUBBELL LIGHTING SMALL VIPER 3.
COMPLIANCE FCC TITLE 47 PART 15 CLASS B.
3K PF .95 MAXIMUM THD 10% MAXIMUM ELECTROMAGNETIC
BE INSTALLED AT 0 DEGREE ELEVATION. LIGHT FIXTURE LED
LAMP POLE SHALL BE RATED FOR 150 MPH WINDS . LAMPS SHALL 2.
COMPLIANCE FCC TITLE 47 PART 15 CLASS B.
3K PF .95 MAXIMUM THD 10% MAXIMUM ELECTROMAGNETIC
INSTALLED AT 0 DEGREES ELEVATION. LIGHT FIXTURE LED
POLE FOR REPLACEMENT LAMPS. ALL LAMPS SHALL BE
EXISTING LAMP POLE , CONTRACTOR SHALL REUTILIZE EXISTING 1.
NOT TO SCALEE001
POLE LIGHT PHOTOMETRIC
qjq-21001848-e001
2021-06-24T20:19:23-0400
HENRY B NEWCOMB
2021-06-24T09:54:44-0400
PAUL E PATNOAD
PHOTOMETRICS
QJQ-21001848-E002
I.E. = 3419.86 lo tt e
R
20 FC
10 FC
5 FC
1 FC
0.5 FC
0.1 FC
PHOTOMETRIC LIGHTS ON BUILDING
SUBMIT COLOR SAMPLE FOR APPROVAL.
BLACK OR DARK BRONZE. CONTRACTOR SHALL
COLOR OF LIGHT FIXTURE BE NON-REFLECTIVE 5.
EQUIVALENT.
VIPER VP-S-36L-80-3K-7-FR-BC OR APPROVED
DESIGNED BASED ON HUBBELL LIGHTING SMALL4.
PART 15 CLASS B
ELECTROMAGNETIC COMPLIANCE FCC TITLE 47
LED 3K PF .95 MAXIMUM THD 10% MAXIMUM
FIXTURES SHALL BE LED 3K WITH LIGHT FIXTURE 3.
WEATHER PROOFED.
ALL PENETRATIONS TO MOUNT FIXTURES SHALL BE 2.
A MINIMUM HEIGHT OF EIGHT FEET.
CONTRACTOR SHALL MOUNT ALL LIGHT FIXTURES AT 1.
qjq-21001848-e002
2021-06-24T20:20:19-0400
HENRY B NEWCOMB
2021-06-24T09:55:52-0400
PAUL E PATNOAD