Attachment 2 - Project Plans~3.pdf
PDF 3 MB Posted
- Solicitation number
- 26-422DNR-REALT-B-49021
- Issued by
- Clinton County, Illinois
About this file
This is an electrical improvements design set for the Lincoln Log Cabin Site, prepared by Fehr Graham Engineering & Environmental for the Lincoln Log Cabin Foundation located in Lerna, Illinois, within Coles County. The project involves electrical infrastructure upgrades, including underground service entrance, utility connections, and site electrical system improvements. The design documents include detailed electrical plans, a site layout, utility coordination, electrical symbols, mounting height notes, and a typical one-line electrical diagram.
The electrical improvements encompass fountain pump and control system electrical infrastructure, with a total design load of 9.5 kVA at 80 amps. The project includes specific electrical components such as a new single-phase utility service, underground conduit routing, grounding systems, and a pedestal-mounted electrical distribution setup. The design adheres to National Electrical Code standards and includes specifications for wiring, conduit installation, equipment grounding, and protective measures. The documents are prepared for bid and provide comprehensive technical details for potential contractors to understand the scope and technical requirements of the electrical system upgrades at the Lincoln Log Cabin Site.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 1 - Project Special Provisions~1.pdf | ||
| Standard Illinois Certifications V 26-1.docx | DOCX document | |
| Scope of Work - Small 1 UPDATED~1.docx | DOCX document | |
| Standard Terms and Conditions V23.2~83.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AutoCAD SHX Text G:\C3D\24\24-4168\Plans\ELEC\Title-Electrical.dwg, TITLE
AutoCAD SHX Text
REV. NO.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
ORIGINAL SET FOR PROJECT:
AutoCAD SHX Text
DATE CREATED:
AutoCAD SHX Text
HORIZONTAL
AutoCAD SHX Text
HORIZONTAL
AutoCAD SHX Text
VERTICAL
AutoCAD SHX Text
VERTICAL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
15 FEET
AutoCAD SHX Text
30 FEET
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
15 FEET
AutoCAD SHX Text
60 FEET
AutoCAD SHX Text
FOR
AutoCAD SHX Text
PLAN & PROFILE
AutoCAD SHX Text
CROSS SECTIONS
AutoCAD SHX Text
COLES COUNTY
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
%%ULOCATION MAP
AutoCAD SHX Text
ILLINOIS
AutoCAD SHX Text
IOWA
AutoCAD SHX Text
WISCONSIN
AutoCAD SHX Text
ILLINOIS PROFESSIONAL DESIGN FIRM NUMBER: 184003525
AutoCAD SHX Text
LINCOLN LOG CABIN SITE ELECTRICAL IMPROVEMENTS
AutoCAD SHX Text
LINCOLN LOG CABIN FOUNDATION
AutoCAD SHX Text
FOR BID
AutoCAD SHX Text
LERNA, IL, ILIL
AutoCAD SHX Text W
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text
PLOT DATE: 2/26/252/26/25
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text
AutoCAD SHX Text 24-4138
AutoCAD SHX Text 02/10/2025
AutoCAD SHX Text
2025 FEHR GRAHAM FEHR GRAHAM
AutoCAD SHX Text
STATE OF ILLINOIS
AutoCAD SHX Text
UTILITIES
AutoCAD SHX Text
UTILITY TYPE
AutoCAD SHX Text
COMMON NAME
AutoCAD SHX Text
WATER
AutoCAD SHX Text
ONSITE WELL
AutoCAD SHX Text
ELECTRIC
AutoCAD SHX Text
COLES-MOULTRIE ELECTRIC COOPERATIVE
AutoCAD SHX Text
GAS
AutoCAD SHX Text
AMEREN
AutoCAD SHX Text
(CONTRACTOR TO BE RESPONSIBLE FOR COORDINATING ANY ADJUSTMENTS TO BE MADE.)
AutoCAD SHX Text
INDEX OF SHEETS
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL PLAN
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL NOTES
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL DETAILS
AutoCAD SHX Text 062-061675
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text
OF
AutoCAD SHX Text
LICENSED
AutoCAD SHX Text 1/17/2025
AutoCAD SHX Text
EXP. 11/30/2025
IDNR# 03-25-020
ENGINEERING & ENVIRONMENTAL
Ó
AutoCAD SHX Text G:\C3D\24\24-4168\Plans\ELEC\Electrical_site.dwg, ELECTRICAL PLAN
AutoCAD SHX Text
LINCOLN LOG CABIN FOUNDATION 402 S LINCOLN HIGHWAY LERNA, IL 62440
AutoCAD SHX Text
MAD
AutoCAD SHX Text
MJ
AutoCAD SHX Text 02/10/2025
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text
ELECTRICAL PLAN
AutoCAD SHX Text 24-4138
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LINCOLN LOG CABIN SITE ELECTRICAL IMPROVEMENTS LERNA, IL, ILIL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
60 FEET
AutoCAD SHX Text W
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text
PLOT DATE: 2/26/252/26/25
AutoCAD SHX Text
PROJECT AND LOCATION:
AutoCAD SHX Text
OWNER/DEVELOPER:
AutoCAD SHX Text
DRAWING:
AutoCAD SHX Text
APPROVED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
JOB NUMBER:
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text of
AutoCAD SHX Text
REV. NO.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
2025 FEHR GRAHAM FEHR GRAHAM
AutoCAD SHX Text
ILLINOIS DESIGN FIRM NO. 184-003525
AutoCAD SHX Text
ILLINOIS
AutoCAD SHX Text
IOWA
AutoCAD SHX Text
WISCONSIN
AutoCAD SHX Text
SET TYPE:
AutoCAD SHX Text
FOR BID
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
POND
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
SHELTER #2
AutoCAD SHX Text
EXISTING PARKING LOT
AutoCAD SHX Text EXISTING UNDERGROUND ELECTRICAL CONDUIT TO BE REMOVED BY OTHERS OR ABANDONED TO ACCOMMODATE IMPROVEMENTS
AutoCAD SHX Text
LEVITON 1PH24-13 PUMP RECEPTACLE
AutoCAD SHX Text
CP-1
AutoCAD SHX Text
CP-2
AutoCAD SHX Text
CP-3
AutoCAD SHX Text
CP-4
AutoCAD SHX Text THE SURVEY CONTROL PROVIDED IN THESE CONSTRUCTION PLANS WAS SET FOR THE PURPOSE OF TOPOGRAPHICAL SURVEYING FOR THE DESIGN OF THIS SITE. AT THE TIME THE SURVEY WORK WAS COMPLETED, THESE CONTROL POINTS WERE FOUND TO BE CORRECT AND SUFFICIENT CONTROL HAS BEEN PROVIDED FOR THE PURPOSE OF CONSTRUCTION LAYOUT USING CONVENTIONAL CONSTRUCTION LAYOUT METHODS. DUE TO CIRCUMSTANCES BEYOND THE CONTROL OF THE SURVEYOR AND ENGINEER, THE CONTROL PROVIDED MAY BE DISTURBED AFTER FIELD WORK HAS BEEN COMPLETED AND PRIOR TO THE START OF CONSTRUCTION. THE CONTROL, AS PROVIDED, NEEDS TO BE VERIFIED BY THE CONTRACTOR PRIOR TO BEGINNING ANY CONSTRUCTION. IF, UPON VERIFYING THE CONTROL, THE CONTRACTOR FINDS THAT THE CONTROL PROVIDED IN THE PLANS IS MISSING, THE CONTRACTOR SHALL NOTIFY THE ENGINEER PRIOR TO BEGINNING ANY CONSTRUCTION. IF THE CONTROL IS RECOVERED AND DISCREPANCIES ARE FOUND WITH THE CONTROL, THEY WILL NEED TO BE DISCLOSED PRIOR TO ITS USE FOR CONSTRUCTION. IF THE CONTRACTOR INTENDS TO USE ALTERNATIVE METHODS, OTHER THAN CONVENTIONAL CONSTRUCTION LAYOUT METHODS, OR FINDS THAT ADDITIONAL CONTROL IS NECESSARY, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ESTABLISH ANY ADDITIONAL CONTROL NECESSARY
AutoCAD SHX Text
CONTROL POINTS
AutoCAD SHX Text CP-1 1/2" REBAR W/ ORANGE CAP N 988593.45 E 1019879.70 ELEV. = 678.52 = 678.52 CP-2 MAG NAIL N 988720.32 E 1019834.89 ELEV. = 675.50 = 675.50 CP-3 1/2" REBAR W/ ORANGE CAP N 988476.49 E 1019465.90 ELEV. = 687.03 = 687.03 CP-4 1/2" REBAR W/ ORANGE CAP N 988588.32 E 101945.04 ELEV. = 683.06 = 683.06
AutoCAD SHX Text
C901 POLYETHYLENE WATER SUPPLY PIPE WITH TRACER TAPE BY OTHERS
AutoCAD SHX Text
1.5 IN C901 POLYETHYLENE WATER SUPPLY PIPE BY OTHERS
AutoCAD SHX Text
MATCHLINE
AutoCAD SHX Text
ENTRANCE ROAD
AutoCAD SHX Text
OPEN TRENCH UTILITIES IN EXISTING ROADWAY
AutoCAD SHX Text
EXISTING ELECTRICAL LOAD CENTER FOR SHELTER #2
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
SHELTER #1
AutoCAD SHX Text
MATCHLINE
AutoCAD SHX Text E.C. TO PROVIDE PAD AND GROUNDING TO PROVIDE PAD AND GROUNDING PER COLES-MOULTRIE ELECTRIC CO-OP REQUIREMENTS
AutoCAD SHX Text E.C. TO PROVIDE EQUIPMENT AND RACK TO PROVIDE EQUIPMENT AND RACK PER COLES-MOULTRIE ELECTRIC CO-OP REQUIREMENTS
AutoCAD SHX Text
EV POWER (2) #10 & #12 GND IN 3/4"C
AutoCAD SHX Text
(3)#1 & (1)#6 GND IN 2-1/2" PVC
AutoCAD SHX Text
100A FD NEMA 4X (REFEED PAVILION #1)
AutoCAD SHX Text
100A FD NEMA 4X
AutoCAD SHX Text KWH METER 20/240 1p 3w 200A
AutoCAD SHX Text 25 kVA
AutoCAD SHX Text
MILBANK PEDESTAL U5200-XL-75 (1) 100A 2/P 100A 2/P (3) 20 A 1/P20 A 1/P
AutoCAD SHX Text E.C. TO TRENCH RUN 4" SCH40 TO TRENCH RUN 4" SCH40 CONDUIT (1) #4/0 15 kV EPR WITH CONCENTRIC NEUTRAL
AutoCAD SHX Text E.C. TO CONTACT UTILITY CO. (COLES-MOULTRIE ELECTRIC TO CONTACT UTILITY CO. (COLES-MOULTRIE ELECTRIC CO-OP) TO PROVIDE O.H. TO U.G SINGLE PHASE POWER SERVICE 7200v TO NEW UTILITY PAD TRANSFORMER ~~25kVA 120/240V 1P SEC.
AutoCAD SHX Text
DIRECT BORE 240 LF 2-1/2" CONDUIT
AutoCAD SHX Text E.C. TO TRENCH RUN 4" SCH40 TO TRENCH RUN 4" SCH40 CONDUIT (1) #4/0 15 kV EPR WITH CONCENTRIC NEUTRAL
AutoCAD SHX Text
COORDINATE UTILITY TRENCHING SCHEDULE WITH CIVIL SITE CONTRACTOR
AutoCAD SHX Text
COORDINATE UTILITY TRENCHING SCHEDULE WITH CIVIL SITE CONTRACTOR
SYMBOL DESCRIPTION
S
GFI
J
J
P A N E L S C H E D U L E
V
H
DSD
WF
TS
S
RTS
F
F
TC
P
J
M
V
V WP
WP
M E C H A N I C A L E Q U I P M E N T N O T E S
B
6'-8" -to bottom or 6" below finished ceiling whichever is lower. fire alarm signal in toilet rooms or for seperate sinks not in casework starters, thermostats, wall-mounted wiremold and g.f.i. receptacles wall mounted electrical device lighting switches, manual motor top of flush and surface mounted electrical lighting or power top of back-mounted wall exit fixtures (not mounted above top of highest electrical safety disconnect switches, magnetic electrical receptacles within mechanical spaces, electrical and wall mounted intercom, telephone and pay stations.
fire alarm pull stations, ADA compliant device rough in
(maximum side reach height ADA)
COORDINATE WITH ARCHITECTURAL DETAILS AND CASEWORK CONTRACTOR
THE ABOVE MOUNTING HEIGHTS SHALL BE ADHERED TO UNLESS SPECIFICALLY NOTED OR
CONTRUCTION THE ABOVE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO
MOUNTING HEIGHTS TO CENTER OF OUTLETS UNLESS OTHERWISE NOTED. IN MASONRY
MOUNTING HEIGHT NOTES:
DETAILED OTHERWISE ON THE DRAWING OR SPECIFICATIONS.
NEAREST BLOCK OR BRICK COURSING.
4.
3.
2.
finished floor
3'-6"
6'-0"
6'-3"
6'-6" of device elevator rooms.
panelboards and telephone cabinets.
devices and illuminated fire signals starters, contactors.
doors).
00"
4'-6"
18"
2'-0"
4'-0" battery lighting units and remote wall mounted light heads (or wall-mounted clocks, program bells, (or as shown on architectural
8'-6"
10'-0" finish ceiling 9" below pendant-hung industrial and strip lighting fixtures.
1'-0" below finished ceiling of top of unit).
details)
(maximum side reach height ADA) electrical receptacles, telephone outlets, television outlets, computer outlets, intercom outlet for desks, wall-mounted wiremold not located above casework
FOR DEVICES MOUNTED ABOVE CASEWORK.
GFI
ELECTRICAL SYMBOLS
ELECTRICAL GENERAL NOTES
TAG
NO
AutoCAD SHX Text G:\C3D\24\24-4168\Plans\ELEC\Elec_Sym_notes.dwg, ELECTRICAL NOTES
AutoCAD SHX Text
LINCOLN LOG CABIN FOUNDATION 402 S LINCOLN HIGHWAY LERNA, IL 62440
AutoCAD SHX Text
MAD
AutoCAD SHX Text
MJ
AutoCAD SHX Text 02/10/2025
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text
ELECTRICAL SYMBOLS AND NOTES
AutoCAD SHX Text 24-4138
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LINCOLN LOG CABIN SITE ELECTRICAL IMPROVEMENTS LERNA, IL, ILIL
AutoCAD SHX Text
PLOT DATE: 2/26/252/26/25
AutoCAD SHX Text
PROJECT AND LOCATION:
AutoCAD SHX Text
OWNER/DEVELOPER:
AutoCAD SHX Text
DRAWING:
AutoCAD SHX Text
APPROVED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
JOB NUMBER:
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text of
AutoCAD SHX Text
REV. NO.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
2025 FEHR GRAHAM FEHR GRAHAM
AutoCAD SHX Text
ILLINOIS DESIGN FIRM NO. 184-003525
AutoCAD SHX Text
ILLINOIS
AutoCAD SHX Text
IOWA
AutoCAD SHX Text
WISCONSIN
AutoCAD SHX Text
SET TYPE:
AutoCAD SHX Text
FOR BID
AutoCAD SHX Text
RED
AutoCAD SHX Text
BLACK
AutoCAD SHX Text
BLUE
AutoCAD SHX Text
WHITE
AutoCAD SHX Text
- UNDERGROUND FEEDER AND BRANCH CIRCUIT WIRING (CROSS-LINKED POLYETHYLENE INSULATION) ONLY.
AutoCAD SHX Text
- FEEDER AND BRANCH CIRCUIT WIRE IN FINISHED FLOORS OR AREAS SUBJECT TO MOISTURE - ONLY.
AutoCAD SHX Text
- FEEDER AND BRANCH CIRCUIT WIRING ABOVE FINISHED FLOORS AND AREAS NOT SUBJECT TO MOISTURE.
AutoCAD SHX Text 19.
AutoCAD SHX Text 20.
AutoCAD SHX Text
"THHN"
AutoCAD SHX Text
"USE-RHW"
AutoCAD SHX Text
A-PHASE:
AutoCAD SHX Text
B-PHASE:
AutoCAD SHX Text
C-PHASE:
AutoCAD SHX Text
NEUTRAL:
AutoCAD SHX Text 21.
AutoCAD SHX Text 23.
AutoCAD SHX Text 24.
AutoCAD SHX Text 25.
AutoCAD SHX Text 27.
AutoCAD SHX Text 28.
AutoCAD SHX Text 26.
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text 4.
AutoCAD SHX Text 3.
AutoCAD SHX Text
A). PROJECT: NAME AND LOCATION.
AutoCAD SHX Text ANY MENTION OF A SPECIFIC VOLTAGE ON THE ELECTRICAL DRAWINGS SHALL NOT RELIEVE THE ELECTRICAL CONTRACTOR OF THE RESPONSIBILITY TO VERIFY THE VOLTAGE PRIOR TO THE PURCHASING OR ROUGH-IN WORK. THE ELECTRICAL CONTRACTOR SHALL SUBMIT A "VOLTAGE & LOAD COORDINATION" FORM TO ALL PARTIES FURNISHING EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS. THE FORM SHALL HAVE THE FOLLOWING INFORMATION:
AutoCAD SHX Text THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO FURNISH AND INSTALL A COMPLETE ELECTRICAL SYSTEM. WHERE ITEMS/DEVICES ARE INDICATED AND THERE IS NO MENTION OF THE RESPONSIBLE PARTY FOR A SPECIFIC ITEM/DEVICE TO BE FURNISHED, INSTALLED OR WIRED ON THE ELECTRICAL DRAWINGS, THE ELECTRICAL CONTRACTOR WILL BE COMPLETELY RESPONSIBLE FOR THE PURCHASE OF ALL MATERIALS AND PROVIDING ALL LABOR FOR A COMPLETE OPERATING SYSTEM FOR THIS ITEM/DEVICE.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL CAREFULLY EXAMINE THE DRAWINGS AND SPECIFICATIONS, VISIT THE SITE OF THE WORK, AND FULLY BECOME INFORMED AS TO ALL CONDITIONS AND MATTERS THAT CAN, IN ANY WAY, AFFECT THE WORK OR THE COST THEREOF. SHOULD THIS CONTRACTOR FIND DISCREPANCIES BETWEEN EXISTING CONDITIONS AND NEW WORK, OR BETWEEN ELECTRICAL WORK AND THE WORK OF OTHER TRADES AND IN, OR OMISSIONS FROM THE DRAWINGS, SPECIFICATIONS OR OTHER DOCUMENTS, OR BE IN DOUBT AS TO THEIR MEANING, NOTIFY THE ARCHITECT AT ONCE, IN WRITING, OF ANY DISCREPANCIES OBTAIN CLARIFICATION PRIOR TO SUBMITTING ANY BID. ABSENCE OF SUCH NOTIFICATION SHALL BE INTERPRETED TO INDICATE NO DISCREPANCIES OR CONFLICTS EXIST. ADDITIONAL COMPENSATION WILL NOT BE GRANTED AFTER AWARD OF CONTRACT FOR ANY WORK NECESSARY TO COMPLY WITH THESE REQUIREMENTS.
AutoCAD SHX Text THIS CONTRACTOR SHALL REVIEW ENTIRE SET OF CONTRACT DOCUMENTS; INCLUDING BUT NOT NECESSARILY LIMITED TO ALL ARCHITECTURAL, ALL STRUCTURAL, ALL MECHANICAL, ALL ELECTRICAL, ALL PLUMBING DRAWINGS, FIRE PROTECTION DRAWINGS AND ALL MISCELLANEOUS DRAWINGS AND DOCUMENTS. ELECTRICAL CONTRACTOR SHALL ACKNOWLEDGE AND INCLUDE IN THE SCOPE OF WORK (CONTRACT) ALL CONDITIONS PERTINENT TO THE COMPLETION OF THE WORK. ELECTRICAL CONTRACTOR SHALL FULLY COORDINATE ELECTRICAL WORK WITH THE INSTALLATION OF WORK BY ALL OTHER TRADES AND MAKE NECESSARY FIELD ADJUSTMENTS AS REQUIRED TO ACCOMMODATE THE ELECTRICAL INSTALLATION. ALL OF THE ABOVE SHALL BE INCLUDED IN THE SCOPE OF WORK AT NO ADDITIONAL COST TO OWNER.
AutoCAD SHX Text
B). THE PARTY FURNISHING THE EQUIPMENT: NAME, ADDRESS, CONTACT, PHONE NUMBER.
AutoCAD SHX Text
C). THE ELECTRICAL CONTRACTORS: NAME, ADDRESS, CONTACT, PHONE NUMBER.
AutoCAD SHX Text 29.
AutoCAD SHX Text 30.
AutoCAD SHX Text 31.
AutoCAD SHX Text 33.
AutoCAD SHX Text 34.
AutoCAD SHX Text 32.
AutoCAD SHX Text 35.
AutoCAD SHX Text 36.
AutoCAD SHX Text 38.
AutoCAD SHX Text 37.
AutoCAD SHX Text 39.
AutoCAD SHX Text 40.
AutoCAD SHX Text 5.
AutoCAD SHX Text 6.
AutoCAD SHX Text 7.
AutoCAD SHX Text 8.
AutoCAD SHX Text 9.
AutoCAD SHX Text 10.
AutoCAD SHX Text 11.
AutoCAD SHX Text 12.
AutoCAD SHX Text 14.
AutoCAD SHX Text 13.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL TEMPORARY WIRING FOR HAND TOOLS AND CONSTRUCTIONS LIGHTING PER LATEST OSHA STANDARDS AND INCLUDE ALL COSTS IN THE BASE BID.
AutoCAD SHX Text THE ELECTRICAL CONTRACTOR SHALL PAY ALL PERMIT FEES, PLAN REVIEW FEES, LICENSE FEES, INSPECTIONS AND TAXES APPLICABLE TO THIS DIVISION AND SHALL BE INCLUDED IN THE BASE BID AS PART OF THIS CONTRACT.
AutoCAD SHX Text THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR SCHEDULING DELIVERY, RECEIVING, UNLOADING, STORING, UNCRATING, SETTING IN PLACE, AND PROTECTING FROM DAMAGE, VANDALISM, THEFT OR WEATHER DURING CONSTRUCTION FOR ALL NEW EQUIPMENT FURNISHED BY THIS CONTRACTOR OR FURNISHED BY OTHER PARTIES TO THE ELECTRICAL CONTRACTOR FOR INSTALLATION BY THE ELECTRICAL CONTRACTOR. COORDINATE ALL DELIVERIES TO MEET THE PROJECT COMPLETION DATES AS ESTABLISHED BY THE OWNER.
AutoCAD SHX Text ALL WORK AREAS WILL BE KEPT CLEAN BY THE CONTRACTOR WITH THOROUGH CLEAN UP AT THE END OF EACH DAY'S WORK. UPON COMPLETION OF THE WORK, THE ELECTRICAL CONTRACTOR SHALL REVIEW AND CHECK THE ENTIRE PORTION OF WORK, CLEAN EQUIPMENT AND DEVICES, REMOVE SURPLUS MATERIALS AND RUBBISH FROM THE OWNER'S PROPERTY, LEAVING THE WORK IN NEAT AND CLEAN ORDER AND IN COMPLETE WORKING CONDITION. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL OF ANY CARTON, DEBRIS, ETC., FOR EQUIPMENT FURNISHED AND INSTALLED BY THIS CONTRACTOR OR FURNISHED BY OTHER PARTIES AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
AutoCAD SHX Text UPON COMPLETION OF THE DENOTED WORK, THE ARCHITECT WILL PERFORM A PUNCH LIST IN ORDER TO VERIFY COMPLIANCE TO ALL PLANS, DETAILS AND SPECIFICATIONS. THE WRITTEN REPORT WILL BE ISSUED TO THE OWNER DESCRIBING ANY FOUND DISCREPANCIES. THE OWNER WILL ISSUE THIS REPORT TO THE ELECTRICAL CONTRACTOR FOR IMMEDIATE CORRECTIONS. UPON COMPLETION OF ALL PUNCH LIST ITEMS, THE ELECTRICAL CONTRACTOR SHALL NOTIFY THE OWNER WHO WILL THEN CONTACT THE ARCHITECT FOR A FINAL WALK-THRU. IF ANY ITEMS ARE NOT CORRECTED TO THE OWNERS/ARCHITECTS SATISFACTION, THE ELECTRICAL CONTRACTOR SHALL ONCE AGAIN BY CONTACTED TO CORRECT THE PUNCH LIST ITEMS. IF ANY ADDITIONAL PUNCH LIST WALK-THRUS ARE REQUIRED BY THE ARCHITECT TO VERIFY ADHERENCE TO THE PUNCH LIST ITEMS, THE ELECTRICAL CONTRACTOR SHALL BE INVOICED AT A TIME AND MATERIAL BASIS AT THE RATE OF $100.00 PER HOUR UNTIL ALL ITEMS ARE CORRECTED. MONIES FOR THIS ADDITIONAL SERVICE SHALL BE DEDUCTED FROM THE ELECTRICAL CONTRACTORS QUOTED FEES.
AutoCAD SHX Text THE ARCHITECT MAY MAKE PERIODIC VISITS TO THE JOB SITE TO OBSERVE THE PROGRESS OF THE WORK AND TO OBSERVE WHETHER OR NOT IT IS BEING PERFORMED IN ACCORDANCE WITH THE CONTRACT DRAWINGS AND SPECIFICATIONS. THIS DOES NOT IN ANY WAY MEAN THAT THE ARCHITECT IS A GUARANTOR OF THE CONTRACTOR'S WORK, OR RESPONSIBLE FOR SAFETY IN, ON, OR ABOUT THE JOB SITE, IN CONTROL OF THE SAFETY OR ADEQUACY OF ANY SHIPMENT, BUILDING, SCAFFOLDING, FORMS OR OTHER WORK AIDS, OR FOR SUPERINTENDING, DIRECTING OR HAVING CHARGE AT THE ERECTION AND/OR CONSTRUCTION OF THE WORK.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL ESTABLISH SAFE WORKING PROCEDURES FOR THE PROTECTION OF THE WORKMEN IN ALL PHASES OF WORK, COMPLYING WITH THE APPLICABLE PROVISIONS OF THE CITY, STATE AND FEDERAL SAFETY LAWS (OSHA), AND AS RECOMMENDED IN THE "MANUAL OF ACCIDENT PREVENTION IN CONSTRUCTION" AS ISSUED BY THE ASSOCIATION OF GENERAL CONTRACTORS OF AMERICA, INC., 20TH AND E. STREETS, N.W. WASHINGTON, D.C.
AutoCAD SHX Text ELECTRICAL CONTRACTOR TO IMMEDIATELY COORDINATE WITH LOCAL UTILITY COMPANIES UPON AWARD OF CONTRACT. EXPEDITE ALL AGREEMENTS WITH UTILITY COMPANIES TO PREVENT ANY DELAY OF ENERGIZATION OF NEW SERVICE(S). INCLUDE ALL COSTS IN BASE BID.
AutoCAD SHX Text ALL INSTRUMENTS, APPARATUS AND EQUIPMENT SHALL BE TESTED AND PROVED TO BE ELECTRICALLY AND MECHANICALLY WITHOUT DEFECTS. THE ELECTRICAL SYSTEM SHALL BE TESTED FOR GROUNDS OR SHORTS. IF THE TROUBLE IS WITHIN THE CIRCUIT WIRING, ALL SHORTED OR GROUNDED WIRES SHALL BE REPLACED AND THEN RETESTED. ALL METERS, CABLES, EQUIPMENT OR APPARATUS NECESSARY FOR MAKING ALL TESTS SHALL BE FURNISHED AND PROVIDED BY THIS CONTRACTOR.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL VERIFY ALL OUTLET MOUNTING ARRANGEMENTS, HEIGHTS AND LOCATIONS PRIOR TO ROUGH-IN. ANY MENTION OF A SPECIFIC MOUNTING ARRANGEMENT, HEIGHT OR LOCATION SHALL NOT RELIEVE THE ELECTRICAL CONTRACTOR OF THE RESPONSIBILITY TO VERIFY THE SPECIFIC REQUIREMENT WITH THE EQUIPMENT FURNISHED OR THE COORDINATION WITH OTHER DEVICES OR TRADES WORKING IN THE SAME AREA. NO ADDITIONS TO THE CONTRACT SUM WILL BE PERMITTED FOR OUTLETS IN WRONG LOCATIONS, IN CONFLICT WITH OTHER WORK AND ETC. THE OWNER RESERVES THE RIGHT TO RELOCATE ANY DEVICE 10'-0" PRIOR TO ROUGH-IN WITHOUT ANY ADDITIONAL CHARGE BY THE ELECTRICAL CONTRACTOR.
AutoCAD SHX Text THIS FORM SHALL BE SUBMITTED VIA THE GENERAL CONTRACTOR IN A MANNER SIMILAR TO SUBMITTING SHOP DRAWINGS. THE COMPLETED APPROVED FORM SHALL THEN BE SUBMITTED TO THE ARCHITECT. ADDITIONAL COMPENSATION WILL NOT BE GRANTED FOR LACK OF COORDINATION BETWEEN THE FURNISHING PARTY AND THE ELECTRICAL CONTRACTOR.
AutoCAD SHX Text D). EQUIPMENT: TAG, DESCRIPTION, VOLTAGE, LOAD, FURNISHING PARTY'S OKAY FOR EACH ITEM.
AutoCAD SHX Text ALL DEVICES (SWITCHES, RECEPTACLES, TELEPHONE/DATA, ETC.) FINISH COLOR SHALL BE WHITE. ALL COVER PLATES FOR DEVICES IN FINISHED AREAS SHALL BE STEEL WITH WHITE CRACKLE FINISH. ALL COVER PLATES FOR DEVICES IN EXPOSED UNFINISHED AREAS SHALL BE GARVIN FINISH. ALL RECEPTACLES, TELEPHONE & DATA OUTLETS SHALL BE MOUNTED HORIZONTALLY IN JUNCTION BOX.
AutoCAD SHX Text THESE ARE SCOPE DRAWINGS TO GIVE THE GENERAL INTENT OF THE ELECTRICAL REQUIREMENTS. THIS CONTRACTOR SHALL PREPARE CERTIFIED PERMIT DRAWINGS AND SUBMIT AND OBTAIN ALL PERMITS AS MAY BE REQUIRED. IN ADDITION, THIS CONTRACTOR SHALL SUBMIT SAME TO ARCHITECT FOR THE REVIEW AND COMMENT.
AutoCAD SHX Text RECEPTACLES INDICATED FOR G.F.I. PROTECTION SHALL PROTECT THE RECEPTACLE INDICATED ONLY. AT LOCATIONS WHERE G.F.I. RECEPTACLES ARE INDICATED WITHIN SIGHT OF EACH OTHER, ELECTRICAL CONTRACTOR MAY ELECT TO USE ONE "FEED-THRU" G.F.I. RECEPTACLE TO FEED "SLAVE" G.F.I. RECEPTACLE(S). G.F.I. CIRCUIT BREAKERS WILL NOT BE PERMITTED TO PROTECT RECEPTACLES INDICATED FOR G.F.I. PROTECTION UNLESS SPECIFICALLY CALLED FOR. ALL "SLAVE" G.F.I. RECEPTACLES SHALL BE MARKED TO INDICATE THEY ARE PROTECTED BY UPSTREAM G.F.I. RECEPTACLES.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL PROVIDE CIRCUITS AND FINAL POWER CONNECTIONS FOR FIRE PROTECTION FLOW SWITCHES AND ALARM BELLS AS REQUIRED.
AutoCAD SHX Text FINAL EQUIPMENT CONNECTION TO PILOT CONTROL DEVICES SHALL BE MADE WITH 1'-0" MINIMUM LENGTH OF FLEXIBLE CONDUIT CONNECTION (I.E., SOLENOID VALVES, MOTORIZED DAMPERS, ETC.).
AutoCAD SHX Text NO HOLES OR RECESSES MAY BE CUT IN WALLS, FLOORS, CEILINGS, OR ANY PART OF THE BUILDING TO ADMIT CONDUIT OR OTHER WORK OF THIS CONTRACT WITHOUT PRIOR SUBMISSION TO AND REVIEW AND APPROVAL BY THE OWNER. WORK SHALL BE PERFORMED BY A COMPETENT MECHANIC SKILLED IN THIS FIELD IN A NEAT AND CRAFTSMAN LIKE MANNER. THE PORTIONS CUT MUST BE RESTORED TO THEIR ORIGINAL CONDITION AT THE EXPENSE OF THIS CONTRACTOR. THIS CONTRACTOR SHALL INCLUDE ALL COSTS FOR ALL CUTTING AND PATCHING REQUIRED FOR THE ELECTRICAL WORK IN THE BASE BID.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL FIREPROOF ALL CONDUIT OPENINGS BETWEEN FLOORS AND ANY INTERSPACE FIRE SEPARATION BLOCK WALLS WITH AN ARCHITECT APPROVED U.L. LISTED FIRE RETARDANT MATERIAL. ELECTRICAL CONTRACTOR SHALL WEATHERPROOF ALL PENETRATIONS THRU FOUNDATION AND EXTERIOR WALLS.
AutoCAD SHX Text NO CONDUITS SHALL BE ROUTED ON ROOF. ELECTRICAL CONTRACTOR SHALL COORDINATE ROOF PENETRATIONS WITH MECHANICAL PIPE CURBS. WHERE CONDUIT MUST BE RUN ON ROOF, IT SHALL BE RACKED WITH OTHER TRADES WHERE POSSIBLE OR PROVIDED WITH ITS OWN ROOF RACK SUPPORT SYSTEM WITH PROPER ROOF PLATE SO AS NOT TO CAUSE DAMAGE TO ROOF COVERING. PROVIDE SUBMITTAL OF PROPOSED SYSTEM.
AutoCAD SHX Text NO WIREWAY OR TROUGHS ARE PERMITTED UNLESS INDICATED ON THE ELECTRICAL DRAWINGS FOR A SPECIFIC USE. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL PROPERLY SIZED JUNCTION OR PULL BOXES WHERE REQUIRED. PULL AND JUNCTION BOXES SHALL BE HELD TO A MINIMUM.
AutoCAD SHX Text ALL CONDUIT RACEWAYS SHALL BE CONCEALED IN OR WITHIN: WALLS, CEILING CAVITY, ROOF CONSTRUCTION (WHERE APPROVED), SLAB, GRADE, ETC., UNLESS NOTED OTHERWISE. RACEWAYS ARE TO BE INSTALLED IN THE METHOD INDICATED SYMBOLICALLY ON THE ELECTRICAL DRAWINGS. ANY DEVIATION TO THE INDICATED METHOD OR FOR A RACEWAY THAT IS PROPOSED TO BE ROUTED EXPOSED SHALL BE APPROVED IN WRITING BY THE ARCHITECT PRIOR TO THE INSTALLATION. ALL CONDUIT SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALLS AND STRUCTURAL MEMBERS WITH 90 BENDS WHERE REQUIRED AND SHALL BE RACKED. UNDERFLOOR RACEWAYS SHALL NOT BE PERMITTED UNLESS SO INDICATED ON THE ELECTRICAL DRAWINGS.
AutoCAD SHX Text ALL SUSPENDED CONDUITS SHALL BE RIGIDLY SUPPORTED FROM THE BUILDING STRUCTURE BY MEANS OF APPROVED CONDUIT FASTENERS, HANGERS, STRAPS, SUPPORTS, CLAMPS, ETC., FIRMLY ANCHORED IN PLACE AND SPACED AT INTERVALS NOT TO EXCEED 10'-0". THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL RODS, ANGLES, RAILS, STRUTS, BRACE PLATES, PLATFORMS, ETC., REQUIRED FOR SUSPENSION OR SUPPORT OF CONDUIT AND EQUIPMENT AND ALL STRAPS, CLAMPS, THREADED RODS, TURNBUCKLES, ANCHORS, ETC. AND MISCELLANEOUS SPECIALTIES REQUIRED FOR THE ATTACHMENT OF HANGERS AND SUPPORTS TO THE STRUCTURE. ALL CONDUIT FASTENERS, STRAPS, SUPPORTS AND ETC., SHALL BE "BOLT-ON" GALVANIZED STEEL ON EXPOSED CONSTRUCTION AND IN WET AREAS. SNAP-ON METAL "CADDY" CLIPS IN METAL PARTITION WALLS AND INDEPENDENTLY SUPPORTED ABOVE THE SUSPENDED CEILINGS WILL BE PERMITTED. ALL DEVICES/EQUIPMENT UTILIZED FOR THE SUPPORT OF CONDUIT SHALL BE U.L. LISTED FOR THE USE.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL INSTALL SIZE OF CONDUIT SHOWN ON PLANS AND SHALL NOT REDUCE SIZING OF CONDUITS TO SUIT WIRE FILL CAPACITY.
AutoCAD SHX Text ALL UNDERFLOOR, UNDERGROUND, EXPOSED-TO-WEATHER OR IN SLAB CONDUIT SHALL BE HEAVYWALL GALVANIZED RIGID STEEL (G.R.S.), MINIMUM 3/4".
AutoCAD SHX Text ALL WIRE SHALL BE INSTALLED IN THINWALL, ELECTRICAL METALLIC TUBING (E.M.T.) CONDUIT UNLESS OTHERWISE NOTED. MINIMUM SIZE SHALL BE 3/4" FOR BRANCH CIRCUIT WIRING. DROPS TO SWITCHES AND BRANCH DEVICES MAY BE 1/2" UNLESS OTHERWISE NOTED ON DRAWINGS. ALL THINWALL FITTINGS SHALL BE OF THE STEEL COMPRESSION GLAND TYPE. PVC NOT ALLOWED.
AutoCAD SHX Text ALL 15 OR 20 AMPERE BRANCH CIRCUIT HOMERUNS 100' OR LONGER SHALL BE #10 AWG (MINIMUM) OR LARGER, SIZED TO LIMIT VOLTAGE DROP TO CODE REQUIREMENTS.
AutoCAD SHX Text PROVIDE COLOR OF ALL BUILDING WIRING FOR IDENTIFICATION OF THE SYSTEM VOLTAGE. SUGGESTED COLOR CODING SCHEME AS FOLLOWS:
AutoCAD SHX Text ALL WIRE AND CABLE SHALL BE COPPER WITH 600 VOLT INSULATION. MINIMUM WIRE SIZE SHALL BE SIZE #12 AWG (WITH THE EXCEPTION OF CONTROL WIRING WHICH MAY BE SIZE #14 AWG). WIRE SIZE #10 AWG AND SMALLER SHALL BE SOLID AND ALL CABLE SIZE #8 AWG AND ABOVE SHALL BE STRANDED, WITH "TYPES" AS FOLLOWS:
AutoCAD SHX Text "THWN" or "XHHW"
AutoCAD SHX Text %%uSYSTEM VOLTAGE%%u: %%u120/208V.%%u
AutoCAD SHX Text 15.
AutoCAD SHX Text 16.
AutoCAD SHX Text 17.
AutoCAD SHX Text 18.
AutoCAD SHX Text ALL EQUIPMENT/DEVICES FURNISHED BY THIS CONTRACTOR SHALL BE NEW AND OF FIRST QUALITY AND SHALL BEAR THE APPROPRIATE UL OR CSA APPROVED LABELS FOR SPECIFIC PURPOSE. ALL MATERIALS SHALL CONFORM TO THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE.
AutoCAD SHX Text THE ELECTRICAL INSTALLATION IS TO BE IN THE STRICT ACCORDANCE WITH ALL APPLICABLE LOCAL, STATE AND FEDERAL RULES, REGULATIONS, AND CODES OR ANY OTHER AUTHORITIES HAVING LAWFUL JURISDICTION, INCLUDING ANY LOCAL UTILITY COMPANY REQUIREMENTS.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL FURNISH CONTRACT RECORD DOCUMENTS TO THE ARCHITECT BEFORE FINAL PAYMENT WILL BE ISSUED. THE CONTRACT RECORD DOCUMENTS SHALL DIAGRAMMATICALLY INDICATE THE INSTALLED CONDITION FOR ALL WORK AND BE IN REPRODUCIBLE DRAWING FORM.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS FOR A PERIOD OF ONE FULL YEAR AFTER FINAL ACCEPTANCE BY THE ARCHITECT AND OWNER.
AutoCAD SHX Text B.O.
AutoCAD SHX Text A.F.F.
AutoCAD SHX Text A.F.G.
AutoCAD SHX Text B.P.S.
AutoCAD SHX Text
CB
AutoCAD SHX Text E.C.
AutoCAD SHX Text
E.U.CO.
AutoCAD SHX Text F.B.O.
AutoCAD SHX Text F & I
AutoCAD SHX Text
BY OTHERS
AutoCAD SHX Text
CIRCUIT BREAKER
AutoCAD SHX Text
FURNISHED BY OTHERS
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
ABOVE FINISHED GRADE
AutoCAD SHX Text
GFI
AutoCAD SHX Text S/C
AutoCAD SHX Text
T.U. CO.
AutoCAD SHX Text G or GND
AutoCAD SHX Text
WP
AutoCAD SHX Text W & I
AutoCAD SHX Text
TELEPHONE UTILITY CO.
AutoCAD SHX Text
SEPARATE CIRCUIT
AutoCAD SHX Text
WIRED AND INSTALLED
AutoCAD SHX Text
WEATHERPROOF
AutoCAD SHX Text
GROUND (INDICATES GREEN GROUND CONDUCTOR).
AutoCAD SHX Text
ELECTRICAL CONTRACTOR
AutoCAD SHX Text
FURNISHED AND INSTALLED
AutoCAD SHX Text
GROUND FAULT INTERRUPTER
AutoCAD SHX Text
ELECTRIC UTILITY COMPANY
AutoCAD SHX Text
BOLTED PRESSURE SWITCH
AutoCAD SHX Text %%uSUBSCRIPT
AutoCAD SHX Text
"D" - LETTER INDICATE ON/OFF WITH LED DIMMER
AutoCAD SHX Text
SPECIFICATION GRADE.
AutoCAD SHX Text
SINGLE POLE TOGGLE SWITCH, 20 AMPERE, 120 (277) VOLT RATED,
AutoCAD SHX Text
(SIZE AS REQUIRED PER CODE)
AutoCAD SHX Text
(SIZE AS REQUIRED PER CODE)
AutoCAD SHX Text
JUNCTION BOX, CEILING MOUNTED.
AutoCAD SHX Text
JUNCTION BOX WITH FLEXIBLE CONDUIT CONNECTION.
AutoCAD SHX Text
FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
JUNCTION BOX, WALL MOUNTED.
AutoCAD SHX Text
FUSED DISCONNECT SWITCH, SIZE AND RATING AS NOTED ON DRAWINGS.
AutoCAD SHX Text
3/4" EMPTY CONDUIT 6" INTO ACCESSIBLE CEILING (U.N.O.).
AutoCAD SHX Text
RATED, SPECIFICATION GRADE
AutoCAD SHX Text
TO MECHANICAL EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
AS NOTED ON DRAWINGS. REFER TO MECHANICAL EQUIPMENT SCHEDULE
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text PROMPTLY AFTER AWARD OF CONTRACT AND PRIOR TO ORDERING ALL LISTED EQUIPMENT BELOW, THE ELECTRICAL CONTRACTOR SHALL SUBMIT THREE (3) SETS OF SHOP DRAWINGS FOR ARCHITECT REVIEW. SHOP DRAWINGS SHALL CONSIST OF MANUFACTURER'S CATALOG CUTS AND/OR DESCRIPTIVE DATA SHEETS FOR ALL SPECIFIED EQUIPMENT. THE ELECTRICAL CONTRACTORS BID SHALL BE BASED ON THE EQUIPMENT SPECIFIED BELOW. IF THE ELECTRICAL CONTRACTOR PROPOSES ALTERNATE SELECTIONS, THEY MUST BE LISTED ON THE BID PROPOSAL AS A DEDUCTIVE ALTERNATE. CATALOG CUTS FOR ALL PROPOSED ALTERNATE SELECTIONS SHALL BE SUBMITTED WITH THE BID PROPOSAL. ALTERNATE EQUIPMENT SELECTIONS WILL NOT BE PERMITTED AFTER AWARD OF CONTRACT.
AutoCAD SHX Text ALL PANELBOARDS SHALL BE MANUFACTURED BY ONE MANUFACTURER. ALL EQUIPMENT INDICATED IS BASED ON SQUARE "D" COMPANY. ARCHITECT APPROVED ALTERNATE PANEL MANUFACTURERS WILL BE APPROVED ONLY IF THEY DO NOT EXCEED THE PHYSICAL PANEL DIMENSIONS INDICATED ON THE DRAWINGS.
AutoCAD SHX Text
MOTOR CONNECTION.
AutoCAD SHX Text
EXTERIOR WALL LIGHT FIXTURE
AutoCAD SHX Text
4 FT. INDUSTRIAL FLUORESCENT LIGHTING FIXTURE
AutoCAD SHX Text
INDICATES PLAN NOTE TAG NUMBER
AutoCAD SHX Text
INDICATES MECHANICAL EQUIPMENT TYPE AND NUMBER TAG
AutoCAD SHX Text
ALL EMERGENCY LIGHTING TO CONFORM TO ALL LOCAL CODES.
AutoCAD SHX Text
DUCT SMOKE DETECTOR
AutoCAD SHX Text
EMERGENCY LIGHT FIXTURE
AutoCAD SHX Text
FIRE ALARM SMOKE AND CO2 DETECTOR
AutoCAD SHX Text
VISUAL (ADA) UNIT, 80" A.F.F. (U.N.O.)
AutoCAD SHX Text
FIRE ALARM SYSTEM COMBINATION ALARM HORN AND
AutoCAD SHX Text
SPRINKLER SYSTEM FLOW SWITCH
AutoCAD SHX Text
SPRINKLER SYSTEM TAMPER SWITCH
AutoCAD SHX Text
REMOTE TEST SWITCH FOR DUCT DETECTORS
AutoCAD SHX Text
FIRE ALARM SYSTEM MANUAL PULL STATION, 42" A.F.F. (U.N.O.)
AutoCAD SHX Text
FIRE ALARM SYSTEM ALARM VISUAL UNIT (ADA), 80" A.F.F. (U.N.O.)
AutoCAD SHX Text 4.
AutoCAD SHX Text 5.
AutoCAD SHX Text 6.
AutoCAD SHX Text 8.
AutoCAD SHX Text 7.
AutoCAD SHX Text 9.
AutoCAD SHX Text 10.
AutoCAD SHX Text 12.
AutoCAD SHX Text 13.
AutoCAD SHX Text 11.
AutoCAD SHX Text ALL METERBANK AND PANELBOARDS SHALL BE FURNISHED WITH FULL RATED COPPER BUS AND BRACED FOR THE AVAILABLE FAULT CURRENT WITH MINIMUM RATINGS AS INDICATED ON THE PANEL SCHEDULES AND ELECTRICAL RISER DIAGRAMS.
AutoCAD SHX Text ALL CIRCUIT BREAKERS SHALL BE OF THE BOLT-ON TYPE, RATED FOR SWITCHING DUTY AND RATED FOR THE AVAILABLE FAULT CURRENT WITH MINIMUM RATING AS INDICATED ON THE PANEL SCHEDULES AND ELECTRICAL RISER DIAGRAMS.
AutoCAD SHX Text ALL CIRCUIT BREAKERS OF A 2-POLE OR 3-POLE CONFIGURATION SHALL HAVE A COMMON TRIP MECHANISM. HANDLE TIES WILL NOT BE PERMITTED.
AutoCAD SHX Text ALL CIRCUIT BREAKERS SERVING HEATING, AIR CONDITIONING OR REFRIGERATION EQUIPMENT SHALL BE "HACR" RATED.
AutoCAD SHX Text ALL CIRCUIT BREAKERS SIZES AND QUANTITIES INDICATED ON SCHEDULE ARE FOR THE CONVENIENCE OF THE BIDDERS ONLY. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING AND SUPPLYING ALL REQUIRED BRANCH BREAKERS.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ENGRAVED PLASTIC NAMEPLATES, BLACK FACE WITH MINIMUM OF 1/2" HIGH WHITE LETTERS SCREWED TO THE COVERS OF ALL PANELBOARDS INDICATING THE PANEL TAG AND ON ALL SWITCH UNITS INDICATING THE EQUIPMENT SERVED.
AutoCAD SHX Text ALL PANELBOARDS SHALL BE FURNISHED WITH REMOVABLE TYPED-CARD DIRECTORIES WITH THE PROPER DESIGNATION OF THE EQUIPMENT SERVED INDICATED FOR EACH BRANCH CIRCUIT. ALL DIRECTORIES SHALL BE LOCATED IN A HOLDER WITH A CLEAR VIEWING PANEL. GLUE ON TYPE DIRECTORIES ARE NOT ACCEPTABLE. DIRECTORIES SHALL BE TYPED.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL BALANCE ALL PHASES OF ALL METERBANKS AND PANELS TO ENSURE PROPER LOADING.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL FOLLOW NEMA #PB-1-1990 AND PB2-1989 PUBLICATION, PART V PRIOR TO ENERGIZATION OF ANY SWITCHGEAR.
AutoCAD SHX Text ALL METERBANK SHALL CONFORM TO ALL LOCAL ELECTRICAL CODE AND ELECTRIC UTILITY COMPANY REQUIREMENTS.
AutoCAD SHX Text 3.
AutoCAD SHX Text METERBANK SHALL BE MANUFACTURED BY ONE MANUFACTURER. ALL EQUIPMENT INDICATED IS BASED ON ERICKSON. ARCHITECT APPROVED ALTERNATE METERBANK MANUFACTURERS WILL BE APPROVED ONLY IF THEY DO NOT EXCEED THE PHYSICAL PANEL DIMENSIONS INDICATED ON THE DRAWINGS.
AutoCAD SHX Text
NON-FUSED DISCONNECT SWITCH, SIZE AND RATING AS NOTED ON DRAWINGS.
AutoCAD SHX Text
SINGLE GANG TELEPHONE OUTLET, HORIZONTALLY MOUNTED. STUB
AutoCAD SHX Text
DUPLEX RECEPTACLE, 120 VOLT, 20 AMPERE RATED, HOSPTIAL GRADE
AutoCAD SHX Text
DUPLEX RECEPTACLE, GROUND FAULT INTERRUPTER TYPE, 120 VOLT, 20A
AutoCAD SHX Text
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH, SIZE AND RATING
AutoCAD SHX Text
ELECTRICAL PANEL, REFER TO PANELBOARD SCHEDULE FOR CHARACTERISTICS.
AutoCAD SHX Text
MAGNETIC MOTOR STARTER, SIZE AND RATING AS NOTED ON DRAWINGS. REFER
AutoCAD SHX Text
EXIT LIGHT FIXTURE WITH FACES AND ARROWS AS INDICATED ON PLANS, DUAL
AutoCAD SHX Text
VOLTAGE, SELF-CONTAINED MOUNTED WHERE INDICATED
AutoCAD SHX Text BRAIDED WIRE SHALL ONLY BE ATTACHED VIA SCREW TERMINALS; SOLID WIRE MAY USE PUSH-TYPE CONNECTION. AFTER CONNECTION HAS BEEN MADE, SWITHCES AND/OR RECEPTACLES SHALL BE WRAPPED WITH FRICTION OR PVC TAPE IN A MANNER THAT COVERS THE SCREW TERMINALS.
AutoCAD SHX Text 41.
AutoCAD SHX Text
NO CONDUITS SHALL BE ROUTED THROUGH H.V.A.C. AIR DUCTS.
AutoCAD SHX Text PROVIDE A SEPARATE GREEN GROUND CONDUCTOR IN ALL FLEXIBLE CONDUIT CONNECTIONS TO EQUIPMENT.
AutoCAD SHX Text FURNISH AND INSTALL SLEEVES FOR PENETRATIONS THRU BLOCK OR CONCRETE WALLS AND FLOORS.
AutoCAD SHX Text ALL CONDUITS 2" OR LARGER SHALL BE GALVANIZED RIGID STEEL OR INTERMEDIATE METAL CONDUIT (I.M.C.).
AutoCAD SHX Text 22.
AutoCAD SHX Text
USE OF ROMEX OR BX WILL NOT BE PERMITTED.
AutoCAD SHX Text
EXTERIOR WALL DECORATIVE LIGHT
AutoCAD SHX Text
MTD.
AutoCAD SHX Text
MOUNTED
AutoCAD SHX Text
LCP
AutoCAD SHX Text
LIGHTING CONTROL PANEL
AutoCAD SHX Text
FACP
AutoCAD SHX Text
FIRE ALARM CONTROL PANEL
AutoCAD SHX Text
AIC
AutoCAD SHX Text
AMPERE INTERRUPTING CURRENT
AutoCAD SHX Text
MCB
AutoCAD SHX Text
MAIN CIRCUIT BREAKER
AutoCAD SHX Text
CKT
AutoCAD SHX Text
CIRCUIT
AutoCAD SHX Text
RGS
AutoCAD SHX Text
RIGID GALVANIZED STEEL
AutoCAD SHX Text
TIMECLOCK
AutoCAD SHX Text
PHOTOCELL
AutoCAD SHX Text
ELECTRIC METER
AutoCAD SHX Text
GROUND CONNECTION
AutoCAD SHX Text
EXTERIOR WHITE STROBES TO BE TIED TO THE FIRE ALARM AND ACTIVATED
AutoCAD SHX Text
UPON ALARM CONDITION WITHIN THE TENANT SPACE; "WP" DENOTES
AutoCAD SHX Text
WEATHERPROOF
AutoCAD SHX Text
EXTERIOR RED STROBES TO BE TIED TO THE FIRE ALARM AND ACTIVATED
AutoCAD SHX Text
UPON ALARM CONDITION WITHIN THE FIRE PROTECTION SYSTEM;
AutoCAD SHX Text
"WP" DENOTES WEATHERPROOF
AutoCAD SHX Text WHERE A BUILDING HAS ANY COMBINATION OF FEEDERS, BRANCH CIRCUITS, OR SERVICES PASSING THROUGH IT OR SUPPLING IT A PERMANENT PLAQUE OR DIRECTORY SHALL BE INSTALLED AT EACH FEEDER AND BRANCH CIRCUIT DISCONNECT LOCATION DENOTING ALL OTHER SERVICES, FEEDERS, OR BRANCH CIRCUITS SUPPLING THAT BUILDING OR STRUCTURE AND THE AREA SERVED BY EACH.
AutoCAD SHX Text
AutoCAD SHX Text
BUZZER PUSHBUTTON
AutoCAD SHX Text
BUZZER, MOUNTED 6" ABOVE CEILING. COORDINATE EXACT LOCATION WITH
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text 3.
AutoCAD SHX Text 5.
AutoCAD SHX Text 4.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL PROVIDE LOCAL REMOTE DISCONNECTING MEANS FOR ALL ELECTRIC HEATING EQUIPMENT IF REQUIRED BY THE LOCAL ELECTRICAL CODE.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL COORDINATE THE ROUTING OF POWER WIRING TO ROOF-MOUNTED EQUIPMENT WITH MECHANICAL PIPE CURB ASSEMBLY. NO SEPARATE ROOF PENETRATIONS WILL BE PERMITTED.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL SUBMIT THREE (3) SETS OF CATALOG CUTS FOR ALL EQUIPMENT FURNISHED BY THIS CONTRACTOR FOR ARCHITECT REVIEW.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL REFER TO ALL HVAC, PLUMBING AND ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND CHARACTERISTICS OF ALL EQUIPMENT LISTED ON DRAWINGS. ANY MODIFICATION AND/OR ADDITIONAL WORK NECESSARY SHALL BE INCLUDED IN THE BASE BID.
AutoCAD SHX Text
THE TENANT.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL CHECK THE ROTATION OF ALL THREE PHASE MOTORS AND CORRECT THE ROTATION IF REVERSED.
AutoCAD SHX Text
1. STANDARD MOUNTING HEIGHTS: (COORDINATE WITH ARCH DRAWINGS)
AutoCAD SHX Text
ALL MOUNTING HEIGHTS SHALL BE AS INDICATED BY ARCHITECT. IF NOT INDICATED BY
AutoCAD SHX Text
ARCHITECT THEN PROVIDE AS NOTED ABOVE
AutoCAD SHX Text
RATED, SPECIFICATION GRADE TAMPER RESISTANT
AutoCAD SHX Text
QUAD RECEPTACLE, 120 VOLT, 20 AMPERE RATED, SPECIFICATION GRADE,
AutoCAD SHX Text
QUAD RECEPTACLE, GROUND FAULT INTERRUPTER TYPE, 120 VOLT, 20A
AutoCAD SHX Text
TAMPER RESISTANT
AutoCAD SHX Text
TAMPER RESISTANT
AutoCAD SHX Text
ORANGE
AutoCAD SHX Text
BROWN
AutoCAD SHX Text
YELLOW
AutoCAD SHX Text
GRAY
AutoCAD SHX Text %%U480/277V
AutoCAD SHX Text G:\C3D\24\24-4168\Plans\ELEC\Elec_Details.dwg, ELECTRICAL DETAILS
AutoCAD SHX Text
LINCOLN LOG CABIN FOUNDATION 402 S LINCOLN HIGHWAY LERNA, IL 62440
AutoCAD SHX Text
MAD
AutoCAD SHX Text
MJ
AutoCAD SHX Text 02/10/2025
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text
ELECTRICAL DETAILS
AutoCAD SHX Text 24-4138
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LINCOLN LOG CABIN SITE ELECTRICAL IMPROVEMENTS LERNA, IL, ILIL
AutoCAD SHX Text
PLOT DATE: 2/26/252/26/25
AutoCAD SHX Text
PROJECT AND LOCATION:
AutoCAD SHX Text
OWNER/DEVELOPER:
AutoCAD SHX Text
DRAWING:
AutoCAD SHX Text
APPROVED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
JOB NUMBER:
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text of
AutoCAD SHX Text
REV. NO.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
2025 FEHR GRAHAM FEHR GRAHAM
AutoCAD SHX Text
ILLINOIS DESIGN FIRM NO. 184-003525
AutoCAD SHX Text
ILLINOIS
AutoCAD SHX Text
IOWA
AutoCAD SHX Text
WISCONSIN
AutoCAD SHX Text
SET TYPE:
AutoCAD SHX Text
FOR BID
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
100A FD
AutoCAD SHX Text
PER UTILITY
AutoCAD SHX Text
TYPICAL ONE-LINE DIAGRAM
AutoCAD SHX Text
(3) #3/0 & (1) #2 G IN 2-1/2"C
AutoCAD SHX Text
(3) #1 & (1) #6 GND IN 1-1/2"C.
AutoCAD SHX Text
GROUND. SEE SPECIFICATIONS.
AutoCAD SHX Text
GROUND ROD AND WATER PIPE
AutoCAD SHX Text
SERVICE GROUND. 1 #8CU. TO
AutoCAD SHX Text 120/240V
AutoCAD SHX Text 100A
AutoCAD SHX Text
NEMA 4X
AutoCAD SHX Text
NEW
AutoCAD SHX Text M
AutoCAD SHX Text
REQUIRMENTS
AutoCAD SHX Text
METER BASE
AutoCAD SHX Text
PROVIDE
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
METER BASE
AutoCAD SHX Text
CONDUIT TO EXTEND MIN.
AutoCAD SHX Text
OF 3' BELOW SURFACE
AutoCAD SHX Text
WITH PROTECTIVE
AutoCAD SHX Text
BUSHING. CONDUIT MUST
AutoCAD SHX Text
EXTEND BEYOND PAVED
AutoCAD SHX Text
OR CONCRETED AREAS.
AutoCAD SHX Text
COORDINATE WITH
AutoCAD SHX Text
UTILITY CO.
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
CONDUIT TO BE RIGIDLY
AutoCAD SHX Text
FASTENED TO BLDG.
AutoCAD SHX Text 6'-0"
AutoCAD SHX Text
MAX
AutoCAD SHX Text
TYPICAL UNDERGROUND SERVICE ENTRANCE
AutoCAD SHX Text
NTS
AutoCAD SHX Text 12"
AutoCAD SHX Text 8"
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
GROUND ROD DETAIL
AutoCAD SHX Text %%uGROUND ROD INSTALLATION%%u
AutoCAD SHX Text
LONG COPPER CLAD STEEL
AutoCAD SHX Text
GROUND ROD
AutoCAD SHX Text
3/4" DIA. X 10'-0"
AutoCAD SHX Text
GROUND BUS TAP
AutoCAD SHX Text
PIPE BODY
AutoCAD SHX Text
8" DIA. CONCRETE
AutoCAD SHX Text
BUS
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
ROD CLAMP
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
2" THICK CONCRETE COVER
AutoCAD SHX Text
1" DIA. HOLE
AutoCAD SHX Text T
AutoCAD SHX Text
UTILITY APPROVED 7200V CABLE W/ NEU IN 4"C
AutoCAD SHX Text
100A FD
AutoCAD SHX Text 120/240V
AutoCAD SHX Text 100A
AutoCAD SHX Text
NEMA 4X
AutoCAD SHX Text
NEW
AutoCAD SHX Text
TO SHELTER #2
AutoCAD SHX Text
TO PUMP PEDESTAL
AutoCAD SHX Text
%%UELECTRICAL LOAD SUMMARY
AutoCAD SHX Text
CONNECTED
AutoCAD SHX Text
LOAD
AutoCAD SHX Text
LOAD
AutoCAD SHX Text
FACTOR
AutoCAD SHX Text
DESIGN
AutoCAD SHX Text
LOAD
AutoCAD SHX Text
FOUNTAIN PUMPS AND EV PWR
AutoCAD SHX Text
4 KVA
AutoCAD SHX Text
2 KVA
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
1.0 =
AutoCAD SHX Text
1.0 =
AutoCAD SHX Text
4 KVA
AutoCAD SHX Text
2 KVA
AutoCAD SHX Text
SUB-TOTAL LOAD (3) NEW 1 HP PUMPS =
AutoCAD SHX Text
6 KVA
AutoCAD SHX Text
TOTAL DESIGN LOAD =
AutoCAD SHX Text
9.5 KVA,
AutoCAD SHX Text
80 AMPS
AutoCAD SHX Text
2. (75) = CIRCUIT LENGTH IN FEET.
AutoCAD SHX Text
3. ALL WORK SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text 1.
AutoCAD SHX Text
= AVAILABLE 3%%C FAULT CURRENT (RMS, SYM. AMPS).
AutoCAD SHX Text 65000
AutoCAD SHX Text
CONTROLS / STRIP HEATER
AutoCAD SHX Text
2-#10, 1-#12 GND
AutoCAD SHX Text 3/4" C. (10)
AutoCAD SHX Text
20AT
AutoCAD SHX Text
PEDESTAL
AutoCAD SHX Text
100AF
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MILBANK U5200-XL-75
AutoCAD SHX Text
100AS
AutoCAD SHX Text
100AT
AutoCAD SHX Text
AutoCAD SHX Text 22kaic
AutoCAD SHX Text M
AutoCAD SHX Text
SPECIFIC NOTES
AutoCAD SHX Text
ALL WIRING SHALL BE XHHW-2
AutoCAD SHX Text
ALL CONDUIT SHALL BE HEAVY WALLED GALVANIZED EXPOSED
AutoCAD SHX Text
PROVIDE EYS SEAL OFFS FOR CONDUITS ENTERING CONFINED SPACE
AutoCAD SHX Text
EC TO FURNISH AND INSTALL ALL REQUIRED POWER AND CONTROL
AutoCAD SHX Text
CABLEING AND CONDUIT
AutoCAD SHX Text
ALL CONDUITS SHALL TERMINATE IN TOP OR BOTTOM OF ENCLOSURES
AutoCAD SHX Text
EC TO PROVIDE MEYERS HUBS FOR ALL CONNECTING TO OUTDOOR EQUIPMENT
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text 3.
AutoCAD SHX Text 4.
AutoCAD SHX Text 5.
AutoCAD SHX Text 6.
AutoCAD SHX Text 7.
AutoCAD SHX Text 8.
AutoCAD SHX Text
EC TO PROVIDE GALV.. UNISTRUT RACK TO SUPPORT OUTDOOR SERVICE EQUIPMENT
AutoCAD SHX Text
20AT
AutoCAD SHX Text
100AF
AutoCAD SHX Text
AutoCAD SHX Text 3/4" C. (30)
AutoCAD SHX Text
3-#10, 1-#12 GND
AutoCAD SHX Text 7200V
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
25_KVA
AutoCAD SHX Text #2
AutoCAD SHX Text S
AutoCAD SHX Text
3-#1, 1-#6 GND
AutoCAD SHX Text 2-1/2" C. (200)
AutoCAD SHX Text
AutoCAD SHX Text
SHELTER #1
AutoCAD SHX Text 2-1/2" C. (50)
AutoCAD SHX Text
3-#1, 1-#6 GND
AutoCAD SHX Text
3-#1, 1-#6 GND
AutoCAD SHX Text 2-1/2" C. (200)
AutoCAD SHX Text 2-1/2" C. (50)
AutoCAD SHX Text
3-#1, 1-#6 GND
AutoCAD SHX Text 120-240V
AutoCAD SHX Text
20AT
AutoCAD SHX Text
100AF
AutoCAD SHX Text
2-#10, 1-#12 GND
AutoCAD SHX Text 3/4" C. (10)
AutoCAD SHX Text 5-20R
AutoCAD SHX Text
GFI
AutoCAD SHX Text 5-20R
AutoCAD SHX Text
GFI
AutoCAD SHX Text
PUMP CORD
AutoCAD SHX Text P-1
AutoCAD SHX Text
AutoCAD SHX Text
(1) 3"C (20)
AutoCAD SHX Text
PUMP CORD
AutoCAD SHX Text P-2
AutoCAD SHX Text
AutoCAD SHX Text 3"C (20)
AutoCAD SHX Text
PUMP CORD
AutoCAD SHX Text P-3
AutoCAD SHX Text
AutoCAD SHX Text
PEDESTAL
AutoCAD SHX Text
LEVITON 2PH18
AutoCAD SHX Text 5-20R
AutoCAD SHX Text
GFI
AutoCAD SHX Text
90W HTR
AutoCAD SHX Text
EV
AutoCAD SHX Text
EX. 3 PHASE O.H.
AutoCAD SHX Text
NEW SINGLE PHASE FUSE
AutoCAD SHX Text
OH. TO UG. (TRENCH ACROSS ROAD)
AutoCAD SHX Text
NEW SINGLE PHASE XFMR
AutoCAD SHX Text 120/240V 1P 200A
AutoCAD SHX Text
EX. 3 PHASE O.H.
AutoCAD SHX Text
SCH 40 PVC BURIED
AutoCAD SHX Text
COORDINATE ALL WORK WITH OWNER AND UTILITY
AutoCAD SHX Text
SUB-TOTAL LOAD SHELTER #1 =
AutoCAD SHX Text
3.5 KVA
AutoCAD SHX Text
20AT
AutoCAD SHX Text
100AF
AutoCAD SHX Text
2-#10, 1-#12 GND
AutoCAD SHX Text 3/4" C. (10)
AutoCAD SHX Text 5-20R
AutoCAD SHX Text
GFI
AutoCAD SHX Text
(3)#3/0 & (1)#6 GND
AutoCAD SHX Text
UTILITY APPROVED METER 200A
| Sheets and Views |
| 1 TITLE |
| 2 ELECTRICAL PLAN |
| 3 ELECTRICAL NOTES |
| 4 ELECTRICAL DETAILS |
File details come from the government source that posted it. Updated .