Attachment 2 POTTER Brand Technical Specifications.pdf

PDF 7 MB Posted

Attached to
Fire Alarm System Upgrade/Replacement Federal contract opportunity
Solicitation number
1305M325Q0090
Issued by
Department of Commerce National Oceanic and Atmospheric Administration

About this file

This file is a comprehensive technical specification document for Potter Electric Signal Company's fire alarm and safety system components. The document includes detailed technical specifications for multiple product lines, such as:

  1. Digital Alarm Communicator (UD-2000): A device that provides up to two phone lines for communication with a monitoring station, compatible with SIADCS and Ademco Contact ID protocols. It operates at 22-24V, has a standby current of 16mA, and can be installed in fire alarm control panels. 2. Photoelectric Smoke/Heat Detectors (PAD300-PHD): An analog addressable detector with a sensitivity range of 1.1 to 3.5% per foot, featuring drift compensation, a fixed temperature alarm threshold of 135°F, and compatibility with Potter addressable fire alarm control panels. 3. Power Supplies (PSN Series): Offering 6-10 amps of regulated power with 4-6 outputs, these supplies support notification appliance circuits, have trouble relays, and can synchronize horns/strobes from multiple manufacturers. 4. Additional components include addressable pull stations, duct detectors, heat detectors, and various module types for fire alarm system integration.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

8830146 - REV B • 6/19 page 1 OF 3

Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com

UD-2000

Digital Alarm Communicator

Description The UD-2000 Digital alarm Communicator Transmitter (DaCT) provides for up to two (2) phone lines for communication to a monitoring station. The UD-2000 communicates using the SIa- DCS or ademco Contact ID protocols. When enabled, the DaCT automatically monitors each phone line or voltage and has the ability to seize the line and connect with a remote receiver. Once the communication is complete, the DaCT will hang up.

The DaCT is provided with terminal blocks for each phone line and two RJ45 cords. In order for the DaCT to work properly, it must be installed on a plain old telephone service (pOTS) line or equivalent deemed by the authority having jurisdiction. The DaCT must be installed before any other equipment to ensure it can seize the phone line.

phone lines are high voltage and should be run in a separate conduit from other circuits. The wire conductors connecting the DaCT to the phone system should be 26 aWg or larger.

Technical Specifications Operating Voltage 22.0-24.0V Standby Current 16ma alarm Current 23ma Max UD-2000s per panel 1 Dimensions 4”W * 6”H * 1-5/8”D Operating Tempuratures 0°C - 49°C (32°F- 120°F)

Operating Humidity Range 10% - 93% @ 30°C (86°F) (non-condensing)

Mounting Options In FaCp Behind keypad Shipping Weight 0.47 lbs

Features

• allows for communication to Monitoring Station

• Communicates using SIa-DCS or ademco Contact ID protocols

• For use with Ipa, aFC, and aRC series addressable panels and pFC-4064 Conventional panel

• Status LeDs indicate operation of DaCT card

• Installs with ease behind main panel LCD display via User Interface bracket

• Device address is set internally to address 1

• Includes two (2) RJ45 phone cords

PAD300-PHD

Photoelectric Smoke/Heat Detector

8830218 - REV C • 07/24 PAGE 1 OF 2

Potter Electric Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal.com

Description The PAD300-PHD is a listed Analog Addressable smoke detector and a rate of rise and/or fixed temperature heat detector compatible with fire alarm control panels that utilize the Potter Addressable Device (PAD) protocol. The PAD300-PHD is a low profile smoke/heat sensor with a wide sensitivity range. The heat sensing portion utilizes a proven thermistor for accurate and reliable heat detection. The detector and base are made of a durable plastic in an off-white color to blend in with the ceiling.

The PAD300-PHD is UL listed and has a sensitivity range of 1.1 to 3.5% per foot with a fix temperature alarm threshold of 135°F and can be used for rate of rise applications. See detector spacing limitations below. The PAD300-PHD features drift compensation and has built in dirty detector warning. The PAD300-PHD and the control panel communicate over a proven and robust digital communication path and the system analyzes the information at the particular device. The total polling speed is less than five (5) seconds, well under the UL requirements.

The detector is compatible with any of the PAD300 series detector bases and simply twists on. The PAD300-PHD is addressed using DIP switches in the rear of the detector and can be easily programmed in the field without special tools.

Setting the Address Each addressable device on the SLC loop must have a unique address from 1 to 127 to function properly. The address is set using DIP switches.

Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to SLC or device. Verify the following:

1. Power to the device is removed.

2. Field wiring is correctly installed.

3. Field wiring has no open or short circuits.

Technical Specifications

Operating Voltage 24 VDC

Detector Current Draw 300 µA

Alarm indicator 1 LED

Alarm set-point range for Smoke 1.1 to 3.5%/ft (3.6 to 11%/m)

Alarm set-point for Heat 135°F

Rate of Rise Detection (Selectable Option) 15°F/min. (8.3°C/min.)

Installation temperature range 32°F to 115°F (0°C to 46°C)

Operating relative humidity range 0% to 93% (Non-condensing)

Start-up time Max. 1 sec.

Maximum number of addresses per loop 127

Maximum number of lighted indicators in alarm per loop. 30

Color Eggshell White

Weight (without base) 91 g (3.25 oz)

Dimensions (without base) Height: 1.7 in (43 mm) Diameter 3.93 in (100 mm)

Features

• Photoelectric Smoke Detection compliant with UL 268 7th Edition

• Selectable Rate of Rise and/or Fixed Heat Detector

• Reliable detection technology

• Wide selectable smoke sensitivity range of 1.1 to 3.5%/foot

• Detector communicates sensitivity to control panel

• UL listed smoke calibration and sensitivity

• Ambient temperature listing of 32 ° F to 115 ° F

• Optional locking tab to prevent unwanted removal

• Simple DIP switch address setting, no programming tool required

• LED alarm indicator

• Magnetic test switch

• Product includes 5-year warranty

• UUKL Listed for Smoke Control

8830218 - REV C • 07/24 PAGE 2 OF 2

Potter Electric Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal.com

PAD300-PHD

Photoelectric Smoke/Heat Detector

Air Velocity Ratings

Operation

Detector Sensitivity

Spacing

Compatible Bases

Model Description Stock No.

PAD300-PHD Photoelectric Smoke/Heat Detector 3992777

Ordering Information

The PAD300-PHD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute.

The PAD300-PHD is an analog addressable detector that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel.

The unit communicates with the control panel as it is polled. The LEDs flash every time the unit is polled and they will flash rapidly if the unit is in an active status. The polling LED can be turned off if desired for less conspicuous operation.

The system has a maximum of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on, the PAD300-PD will operate even though the LED may not illuminate.

The PAD300-PHD with the PAD300-4DB or PAD300-6DB has a low profile to blend into the surrounding environment. The detector includes an insect screen to prevent foreign objects from reaching the chamber and can be cleaned to restore operation of a dirty detector.

The PAD300-PHD and the compatible control panel work in tandem to keep the sensitivity consistent. As the detector is installed over time, the detector compensates for the dirt in the unit until it is out of range. At that time, the panel will indicate a dirty detector. The detector will then have to be cleaned or replaced.

The PAD300-PHD can be programmed to provide a maintenance alert prior to reaching the dirty detector level which will allow for intervention prior to the detector going into trouble. This allows for detector replacement or cleaning prior to a nuisance trouble occurs.

NOTE: As required by NFPA, do not install the detectors until all construction is complete and the work area has been thoroughly cleaned. If the detectors have been installed in a construction environment, they should be cleaned or replaced before the system is placed into service.

The PAD300-PHD is UL listed with a recommended maximum spacing of 30 feet. Refer to NFPA 72 for specific information regarding detector spacing, placement and special applications.

All bases will mount on a single gang, 3-1/2” octagon, 3-1/2” square, double gang, 4” octagon, 4” square, 50mm c/c, 60mm c/c and 70mm c/c boxes

Device Description Stock No.

PAD300-4DB 4” Detector Base 3992781 PAD300-6DB 6” Detector Base 3992782 PAD300-IB 6” base with an isolator module included 3992783 PAD300-RB 6” base with one Form-C relay contact. 2A @ 30VDC, 0.5A @ 125VAC 3992784 PAD300-SB 6" base with sounder module included. Sound pattern is provided from external source 3992785 PAD300-LFSB 6” base wih 520Hz sounder module included. Sound pattern is provided from external source 3992786

PAD100-OROI

One Relay One Input Module

8830081 - REV D • 12/18 page 1 OF 2

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

Description The paD100-OROI uses one (1) SLC loop address when monitoring one (1) Class B circuit and providing one (1) Form C relay contact.

The module mounts on either a 4” square or double gang box. The module is capable of monitoring one (1) Class B circuit. The paD100- OROI includes one red LeD to indicate the module’s status. In normal condition, the LED flashes when the device is being polled by the control panel. When a the input is activated, the LED will flash at a fast rate.

Application ThepaD100-OROI is compatible with potter’s Ipa and aFC/aRC series addressable fire alarm control panels. The PAD100-OROI is an interface module used to monitor dry contact devices such as sprinkler waterflow, valve tamper switches, or conventional pull stations. The module is capable of monitoring one Class B circuit. The paD100- OROI also provides one (1) form C relay contact.

Setting the Address each addressable SLC device must be assigned an address. The address is set using the DIp switch located on the paD100-OROI.

When the paD100- OROI is used to monitor one Class B circuit a single device address is assigned, the input and relay are then identified as a sub-point of the module address. For example, if the address number is assigned as “8”, the RLY1 relay will be “8.1” and the IN1 input will be “8.2”.

Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device:

1. power to the device is removed.

2. Field wiring is correctly installed.

3. Field wiring has no open or short circuits.

Technical Specifications Operating Voltage 24.0V Max SLC Standby Current 240μA

Max SLC alarm Current 240μA

Relay Contacts 2a @30VDC, 0.5a @125VaC Max Wiring Resistance of IDC 100 Ω

Max Wiring Capacitance of IDC 1μF eOL Resistor 5.1K Ω Operating Temperature Range 32 to 120ºF (0 to 49ºC)

Operating Humidity Range 0 to 93% (non-condensing)

Max no. of Module per Loop 127 units

Dimensions 4.17” (106mm)L × 4.17” (106mm)W × 1.14” (29mm)D

Mounting Options Standard 4” Square or Double gang Box

Shipping Weight 0.6 lbs

Features

• One (1) Class B monitoring input

• One (1) Form C relay contact

• SLC Class a, Class X & Class B

• Mounts in a standard 4” or double gang box

• Wiring terminals accessible when mounted in box

• all wiring terminals accept 22 to 12 aWg

• product includes a 5 year warranty

• UUKL Listed for Smoke Control

NOTE: This addressable module does not support 2-wire smoke detectors.

8830081 - REV D • 12/18 page 2 OF 2

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

PAD100-OROI

One Relay One Input Module

Installation Using Compatible Electrical Box

Wiring Diagram PAD100-OROI With One Class B Circuit Fig 2

Fig 1

Model Description Stock No.

paD100-OROI One Relay One Input Input Module 3992702

Ordering Information

It is possible that the internal relay in the paD100-OROI may be shipped in the non-normal / activated state. To ensure that the internal relay is set to the normal state, connect the module to the SLC loop and reset the control panel before terminating the wiring to the modules output.

ONE (1) FORM C

RELAY CONTACT

FROM FACP OR

PREVIOUS MODULE

END-OF-LINE RESISTOR

5.1K OHM 1/2 W

Part #3005013

LED-16 Series LED Annunciator

8830096 - Rev D • 12/18 page 1 OF 2

Potter Electric Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal.com

LED-16 Flush Mount LED-16 Surface Mount

Description The LeD-16 Series is a LeD remote annunciator for various potter addressable fire control panels. The LED-16 Series communicates using a RS-485 (P-Link) connection to the main panel providing zone specific indication of Alarm, Supervisory, Trouble conditions.

The LeD-16 Series features 2 slide-in labels allowing each of the 16 zones to be customized for any application. It can be flush mounted or surface mounted. It can be mounted on a single gang electrical box or a four-square electrical box. The annunciator utilizes a sheet metal enclosure secured with a Potter lock.

Technical Specifications Standby Current 20 ma Alarm Current 25 ma

Operating Temperature 0°C-49°C (32°F-120°F)

Operating Humidity Range 0 to 93% (non-condensing)

Maximum Wire Length 6500 ft.

Maximum Annunciators 31 Flush Mount Size (WxHxD) 11 3/8” x 9-1/4” x 7/8”

Surface Mount Size (WxHxD) 11 3/8” x 9-1/4” x 3 1/8”

Wire Gauge 12 AWG-22 AWG

Compatible Panels

IPA Series AFC/ARC Series

PFC-4064

p-Series* PFC-6000 Addressable Series*

*Legacy Product

Features

• Capable of displaying alarms, supervisory, trouble status for 16 zones

• System Silence and Reset buttons

• Common LEDs for status indication

• Maximum 31 LED-16s for:

PFC-6800, P400(R), IPA-4000, and AFC-1000.

• Maximum 10 LED-16s for:

PFC-6030/6075(R)/6200, P100/200/300, IPA-60, IPA-100, AFC-

50, AFC/ARC-100 and PFC-4064

• Maximum P-Link wire length of 6,500 feet

• available in four colors

• Product includes a 5 year warranty

• UUKL Listed for Smoke Control

NOTE: LED PWR can be provided by any fire listed source. Output power must be 16 VDC–33 VDC and must be power limited.

7305-0328:0200 UOXX.S2930

8830096 - Rev D • 12/18 page 2 OF 2

Potter Electric Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal.com

LED-16 Series LED Annunciator

LED PWR P-Link

- + - + A B

P-Link from control panel

Example:

Powered by control panel

Power from auxiliary supply

LED PWR P-Link

- + - + A B

P-Link from control panel

Example:

Powered by auliliary supply

The LED-16 Series is connected to the fire alarm control panel using a four wire RS-485 connection. The connection is power limited and supervised.

Up to 31 LED-16 Series LED annunciators can be connected on PFC series, Potter Plus Series, AFC and IPA series panels.

Installation

Wiring Diagrams

Fig 1

Fig 2

Model Description Stock No.

LeD-16F LeD annunciator Flush Mount 3992727

LeD-16 LeD annunciator Surface Mount 3992666

Ordering Information

Zone labels may be inserted here

Wiring LED-16 Series to Control Panel or Auxiliary Power Example

LED-16 Series Module Showing Front Cover and Board

PSN Series Power Supplies

8910013 - REV G • 07/24 PAGE 1 OF 3

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

Features

• PSN-64 has 6 amps regulated with 4 outputs

• PSN-106 has 10 amps regulated with 6 outputs

• May be configured as up to three class “A” Style “Z” notification circuits

• Two Trouble relays (5A at 30VDC) General System Trouble

(programmable for AC delay) Low AC Trouble with optional delay settings

• Diagnostic LED’s Status LED’s for Active NAC and NAC Trouble conditions.

• Quadrasync feature synchronizes horns/strobes from AMSECO, Gentex, Cooper-Wheelock and System Sensor

• May be connected to any manufacturers UL864 listed FACP/ Unit for activation and supervision

• Configurable output circuits (DIP switch sets options for each circuit)

• Reference EOL allows 2K – 27K EOL value to be used

• Pass Thru mode allows the outputs to match the input signal from FACP

Size (H x W x D) 16 1/8” W x 16 ¾” H x 3 ½” D

Enclosure Eighteen (18) gauge sheet steel with hinged, locked door

Power Input

120VAC @ 60Hz 220/240VAC @ 50Hz

5.1 Amps @ 120 VAC

2.5 Amps @ 240 VAC

Current 75mA Standby & Alarm (no external load)

Input Voltage Trigger

15mA @ 8 – 33 VDC

Terminals 18-12 AWG

Temperature 32° F to 120°F (0°C to 49°C) with a maximum humidity of 93% non-condensing

NAC Output 3 Amp max per NAC, Regulated

Battery Charging 27.3 @ 1A, can support 7 – 55Ah batteries

Description The PSN series of notification power supplies offers reliable notification power with unprecedented versatility. The power supplies offer either 6 or 10 amps of continuous power through 4 or 6 outputs respectively. Each output is rated at 3 amps and it may be used continuously without any derating. The power supply operates on either 120 VAC or 220 VAC power input and has a regulated 24 VDC output. In addition, the power supply can charge up to 55 AH batteries and leads the industry in housing up to 18 AH batteries. The cabinet is constructed out of 18 gauge cold rolled steel and has a durable red powder coat finish. In addition, a key lock is provided for securing the door. Ample electrical knockouts are provided on the sides and the top, allowing the installer options for running wires and maintaining the correct separations.

The power supply offers an industry leading Quadrasync function that allows for multiple strobe circuits of different brands to be synchronized to flash at the same time. The power supply can have four different brands each connected to its own circuit and all the strobes flash together. Each output can independently be configured to provide one of four synchronizations or steady power. This provides unequivocal flexibility in new and retrofit installations. The power supply can be configured to synchronize AMSECO®, Gentex®, Wheelock® and System Sensor® strobe devices. Each output can be configured to the same sync protocol or set independently. In addition, the power supply has an input Pass Thru mode which allows the outputs to follow the input signal from a non-supported synchronization protocol. The power supply will recognize the type of input being supplied and pass this through to the outputs with

Technical Specifications the same pattern. This input pass through can be selected on each output independently. The power supply contains simple dipswitch programming and LED indicators providing the installer the ability to correct any possible faults. A Trouble Memory is provided to allow an installer to review past troubles and make the necessary repairs. Each output has an LED to pinpoint the exact circuit where a trouble may have occurred. Relays are provided for monitoring the general system and AC failure. Each output and be independently configured for various applications and installations. Each output can be independently configured for Class A or Class B operation, constant power, ANSI Temporal Code 3, Single, Multiple or Combo Inputs or Door Holder Power.

8910013 - REV G • 07/24 PAGE 2 OF 3

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

PSN Series Power Supplies

PSN-106 Wiring Diagram

N GH

Comm

Low Battery AC Power

Gnd Fault

Battery -

Battery connection (non-power limited).

Use two (2) 12V batteries connected in series.

Common relays are non-power limited.

120VAC 50Hz~60Hz 240VAC 50Hz~60Hz Connect to separate unswitched AC circuit

LOW AC

RELAY

NC COM NO

TROUBLE

RELAY

NC COM NO Battery +

White Black

Ground

IN2

- + EOL

IN1

- + EOL

REF

EOL

DC PWR

NAC6

NAC4

NAC3

NAC1

NAC2

NAC5

S1

S2

S3

S4

S5

S6

S8S7

Trigger

NAC1 NAC4 NAC5 NAC6NAC3NAC2 DC PWR

COMM

DC Power

Status LED's

E.O.L.

ON

E.O.L.

OFF

Bulk Options

120/240 VAC

Jumper Position

GND FAULT

DETECT ENABLE

Optional Reference

E.O.L.

Factory Installed Interconnect.

0|

0|

Fuse

Note: PSN-64 and PSN-106 draw 15 mA when polarity reverses and the power supply is triggered. There is no current draw in Standby Mode.

Ordering Information

Model Description Stock No.

PSN-106 10 A Power Supply, 6 NAC Circuits, Red Enclosure 3006437

PSN-106B 10 A Power Supply, 6 NAC Circuits, Black Enclosure

3006446

PSN-64 6 A Power Supply, 4 NAC Circuits, Red Enclosure

3006436

8910013 - REV G • 07/24 PAGE 3 OF 3

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

PSN Series Power Supplies

The contractor shall supply and install the Potter PSN power supply.

The power supply shall operate on either 120 or 240 VAC input.

The panel shall be capable of continuous load power without any degradation to the main supply or the distribution board. The cabinet shall be capable of housing up to 18AH batteries and the panel shall be capable of charging up to 55 AH batteries in an external cabinet.

The panel shall have dip switches for simplistic configuration of the system and LEDs to provide visual indication to the installer of the status of the system. The dip switches shall allow for AC power delay selection, Class A/B operation per output, Door Holder Power options, constant auxiliary power, trigger input type, ANSI Code 3 Temporal Code, Pass Thru (input tracking), AMSECO® sync, Gentex® Sync, System Sensor® Sync or Wheelock® sync. The LEDs shall provide indication of communication between the power supply and distribution circuit assemblies. The LEDs shall have distinct flash patterns to provide further indication of the troubles present. The panel shall have selectable Trouble Memory to provide the installer an indication that a past trouble existed on a circuit for diagnostic purposes.

Each output of the power supply shall be capable of 3 amps of continuous power without degradation overtime. The power supply shall provide for multiple circuits of strobe appliances. The power supply shall synchronize the flashes of any of the above listed strobe appliances on a per circuit basis. Up to four different strobe circuits may be connected and all the strobes shall flash in unison as required by UL 864. In addition to this Quadrasync feature, the panel shall allow any of the four above mentioned sync patterns as an input and pass this signal through and synchronize the outputs to match the input flash pattern.

Engineering Specifications

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

8830054-REV D 5/24

S-24 & HS-24

Selectable Candela Strobe & Horn/Strobes

S3247

Features

• 24VDC units have field selectable candela options of 15, 30, 60, 75 & 110

• Super-Slide® Bracket - Ease of Supervision Testing

• Checkmate® - Instant Voltage Verification

• Synchronize strobe and/or horn with AVSM Control Module

• Prewire entire system, install mounting bracket, then install signals

• Documented lower installation and operating costs

• Switch selection for high or low dBA

• Switch for chime, whoop, mechanical and 2400Hz tone

• Tamperproof re-entrant style grill

• Switch for continuous or temporal 3 tone (not available on whoop tone)

• Silence audible while visual appliance will remain flashing (for use in accepted jurisdictions)

• Faceplate available in red or off-white

Description The S-24/HS-24 Series is a low profile strobe and horn/ strobe combination that offers dependable audible and visual alarms and the absolute lowest current available. The S-24 & HS-24 Series 24VDC offers tamperproof field selectable candela options of 15, 30, 60, 75, and 110 candela. The Strobe and Horn/Strobe offers a continuous or sync temporal three in 2400Hz and mechanical tone, a chime and whoop tone. All tones are easy for the professional to change in the field by the use of switches. The S-24 & HS-24 Series has a minimal operating current and has a minimum flash rate of 1Hz regardless of input voltage.

This Series is shipped with a standard 4” metal mounting plate which incorporates the popular Super-Slide® feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing.

The S-24/HS-24 also features the patented Checkmate® - Instant Voltage Verification feature which allows the installer to check the voltage drop draw and match it to the blueprint.

The S-24 & HS-24 Series appliances are ANSI/UL 464 and ANSI/UL 1971, listed for use with fire protective systems and are warranted for three years from date of purchase.

Technical Specifications

Mounting Options Single or Double gang, 4” square box, and AVBB surface mount back box

Terminals Screw-Clamp Type

Wire Gauge 18 – 12 AWG

Operating Temp 32°F – 120°F (0° – 49°C)

Dimensions Height – 5.6” Width – 4.5” Depth – 2.7”

Shipping Weight 1.05 lbs

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

S-24 & HS-24

Selectable Candela Strobe & Horn/Strobes

8830054-REV D 5/24

TONE

SWITCH POSITION

3 4 5

Mechanical Temporal 3 ON ON ON Mechanical Continuous OFF ON ON 2400 Hz Temporal 3 ON OFF ON 2400 Hz Continuous OFF OFF ON Chime Temporal 3 ON ON OFF Chime Continuous OFF ON OFF Whoop ON OFF OFF Whoop OFF OFF OFF

NOTE:

• Switch Positions 1The and 2 in the OFF position to select isolated horn and strobe power inputs

• Switch Position 6 ON = HIGH dBA

• Switch Position 6 OFF = LOW dBA

Candela selection slider switch. Depress center and slide switch to desired brightness level.

Break off pin and insert into hole at the bottom of the selector to lock candela setting. Signal must be removed from bracket and pin pushed forward from backside out of hole to change candela.

The access holes are provided in the back of the terminal block to allow the voltage to be measured directly without removing the device. Typically this would be done at the end of the line to confirm design criteria. Most measure-ments will be taken using the S+ and S- locations although access is provided to other locations. NOTE: Care should be taken to not short the test probes.

Super Slide® Mounting Bracket Allows the installer to pre-wire the system, test for system supervision, remove the signal head until occupancy, switch out signals without changing mounting brackets and has locking edge connector for snap-in-place installation.

To remove bezel, grip both sides of bezel and pull in a downward and outward motion.

Candela Selection Checkmate™ - Instant Voltage Verification

Switch Locations

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

S-24 & HS-24

Selectable Candela Strobe & Horn/Strobes

8830054-REV D 5/24

S-24 24 VDC Selectable Candela, Low Profile Evacuation Strobe

Model Number Part Number Nominal

Voltage Candela (ANSI/UL

1971)

S-24WR 4890010 24 VDC 15, 30, 60, 75, 110

S-24WW 4890011 24 VDC 15, 30, 60, 75, 110

HS-24 24 VDC Selectable Candela, Low Profile Evacuation Strobe

Model Number Part Number Nominal Voltage Candela (ANSI/

UL 1971)

Reverberant dBA at 10 ft, per ANSI/UL 464

In Anechoic Room at 10 ft

HS-24WR 4890030 24 VDC 15, 30, 60, 75, 110 62-82 100

HS-24WW 4890031 24 VDC 15, 30, 60, 75, 110 62-82 100

S-24 & HS 24 Strobe Current Ratings 24 VDC (16 - 33 Volts)

Candela 24 VDC UL Max 15 cd 30 mA 42 mA 30 cd 35 mA 58 mA 60 cd 66 mA 97 mA 75 cd 80 mA 116 mA

110 cd 103 mA 161 mA

Model Designations:

W = Wall mount R = Red Faceplate W=White Faceplate

All units are available in plain (no lettering) Plain units are non-returnable.

“ALERT” bezel available for order.

“AGENT” bezel available for order.

S-24 & HS-24 Horn Ratings

Horn Mode Horn Decibel Levels Horn Current Ratings

Minimum SPL at 10 ft, per

ANSI/UL 464 (HIGH)

Minimum SPL at 10 ft, per ANSI/UL 464 (LOW)

Regulated 24 VDC Max Operating @ High Setting (mA)

Temp 3 (2400 Hz) 78 dBA 71* dBA 28 mA Temp 3 (Mechanical) 76 dBA 70* dBA 25 mA Temp 3 (Chime) 70* dBA 66* dBA 15 mA Continuous (2400 Hz) 81 dBA 74* dBA 28 mA Continuous (Mechanical) 80 dBA 72* dBA 25 mA Continuous (Chime) 70* dBA 66* dBA 15 mA Whoop 82 dBA 69* dBA 56 mA

NOTES:

• For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power see installation manual.

• Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products.

• The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode.

* Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode).

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

S-24 & HS-24

Selectable Candela Strobe & Horn/Strobes

8830054-REV D 5/24

S-24 & HS-24 Series Wiring Diagram

Notes:

All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits.

However, use of the Potter AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn, and/or mute the horn.

• FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC TECHNICAL SUPPORT AT 1-866-956-1211

Architect & Engineering Specifications The audible and/or visible signal shall be Potter S-24 strobe and Potter HS-24 horn/strobe Series or approved equal and shall be listed by Underwriters Laboratories, Inc. per ANSI/UL 1971 and/or ANSI/UL 464. The notification appliance shall also be listed with Factory Mutual Listing Service (FM) and the California State Fire Marshal (CSFM).

The notification appliance (combination audible/visible) shall produce a peak sound output of 100dBA or greater at 24VDC as measured in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized.

Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel.

The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage. The strobe appliance shall have an operating current of 42mA or less at 24VDC for the 15Cd strobe circuit.

The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power for 24VDC models.

The appliance shall be capable of testing supervision without disconnecting wires, verify voltage without removing unit and be capable of mounting to a surface back box.

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

8830229-REV A 2/24

PE-HN, PE-HS, PE-ST Series Horns, Horn/Strobes, and Strobes

Features

• LED Technology for Energy Efficiency:

• Industry’s lowest current draw, ensuring energy efficiency.

• Requires fewer power supplies and smaller wire gauge, reducing wire runs.

• 6 field-selectable settings for both wall and ceiling models.

• Wall: 15 cd - 185 cd / Ceiling: 15 cd - 177 cd

• 3 horn patterns (Continuous, T3, T3/T4) for fire and CO signaling in one device.

• Strobe synchronization with Potter fire alarm control panels and power supplies. Ability to mix xenon and LED strobes in the same field of view.

Description The Potter PE Series feature advanced LED technology with a range of low and high candela settings for indoor wall and ceiling-mount applications. Crafted with a low-profile design, these devices seamlessly complement building interiors.

Rich in features, the devices offer 6 candela settings and 3 horn patterns within a single unit. Installation is simplified with pre-wire/pre-test capabilities via a hinged mounting plate. Wall models follow a single-gang design, allowing tool-free setting changes. The PE Series is designed for 24V operations. The PE-HN can also be used in 12V applications.

High Efficiency, LED Technology The PE series of LED strobes utilize LED technology and optical design to improve efficiency and reduce overall power consumption. Strobe models offer six candela settings (15, 30, 75, 1010, 135, 185 cd for wall models and 15, 30, 75, 110, 150, 177 cd for ceiling models).

Product Listing:

• UL Listed

• FM Approved

• CSFM

Technical Specifications

Mounting Options (Indoor Only)

Mounting plate included with all models.

Wall-Mount Applications:

• PE-HS and PE-ST are suitable for wall-mount applications only.

• Wall mounting options include single-gang, PE-SBB backboxes, or to 4” square with an adapter kit.

• PE-HN can be used for both wall and ceiling-mount applications.

Ceiling-Mount Applications:

• PE-HSC and PE-STC are designed for ceiling-mount applications only.

• Ceiling mounting options include PE-

SPKBB-C backboxes or to 4” square, 1 1/2” or 2 1/8”and Octagonal, 1 ½” or 2 1/8” deep.

Wire Gauge # 12 through # 18 AWG

Operating Temp 32°F to 122°F (0°C to 50°C) maximum humidity 93%

Dimensions Wall: 4.79”H x 2.76”W x 1.18”D Trimplate: 5.25”H x 4.58”W x 0.32”D Ceiling: 6.27” Diameter x 1.69”D

Operating Voltage

12 VDC/VFWR: 8 - 17.5 VDC/VFWR

24 VDC/VFWR: 16 - 33 VDC/VFWR (12 VDC

PE-HN/PE-HNC only)

Strobe Output Rating

UL 1971, UL 1638, ULC S526. Selectable candela outputs for wall models (15, 30, 75, 110, 135, 185) and ceiling models (15, 30, 75, 110, 150, 177).

Synchronization Models

Strobes can be synchronized with Potter fire alarm control panels and power supplies using Wheelock® sync protocol.

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

PE-HN, PE-HS, PE-ST Series Horns, Horn/Strobes, and Strobes

8830229-REV A 2/24

PE-HSC and PE-STC Switch Locations

PE-HS and PE-ST Switch Locations

Candela

CANDELA

(Right Side)

Switch Up down

Sound

PE-HS and PE-ST Switch Locations

(Left Side) Cover

Removed

T3/T4(L) T3l

CONT(L)

T3/T4(H)

T3(H)

CONT(H)

Switch Up down

Dimensions

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

PE-HN, PE-HS, PE-ST Series Horns, Horn/Strobes, and Strobes

8830229-REV A 2/24

PE-STR & PE-HS Strobe Current Ratings 24 VDC (16 - 33 Volts)

Model Number 15 cd 30 cd 75 cd 110 cd 135 cd 150 cd 177 cd 185 cd

PE-ST 0.022 0.030 0.060 0.086 0.125 0.185

PE-STC 0.022 0.030 0.060 0.086 0.125 0.185

At Anechoic High Continuous

PE-HS 0.037 0.046 0.077 0.109 0.146 0.208

PE-HSC 0.037 0.046 0.077 0.109 0.146 0.208

At Anechoic Low Continuous

PE-HS 0.030 0.039 0.070 0.102 0.139 0.201

PE-HSC 0.030 0.039 0.070 0.102 0.139 0.201

PE-HN & PE-HS Horn Ratings

Regulated Voltage Range VDC

Model Number Regulated Voltage Range VDC High dB Low dB

PE-HN 8.0 - 17.5 0.025 0.020

PE-HN 16.0 - 33.0 0.028 0.021

PE-HN & PE-HS dBA Sound Output

Description Reverberant dBA Per UL 464

Volume PE-HN @ 12V PE-HN, PE-HS @ 24V

Continuous Horn High 80 80 Low 78 78

Notes:

When the application requires T4; field devices must be set to T3/T4 Horn setting and in the Potter Programming Software the corresponding circuit be set to Wheelock T4

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

PE-HN, PE-HS, PE-ST Series Horns, Horn/Strobes, and Strobes

8830229-REV A 2/24

Model Number Part Number Mounting Strobe Candela Red White Lettering Horn Strobes PE-HSR 4871006 Wall 15, 30, 75, 110, 135, 185 X Fire PE-HSW 4871007 Wall 15, 30, 75, 110, 135, 185 X Fire PE-HSRC 4871008 Ceiling 15, 30, 75, 110, 150, 177 X Fire PE-HSWC 4871009 Ceiling 15, 30, 75, 110, 150, 177 X Fire Strobes PE-STR 4871002 Wall 15, 30, 75, 110, 135, 185 X Fire PE-STW 4871003 Wall 15, 30, 75, 110, 135, 185 X Fire PE-STRC 4871004 Ceiling 15, 30, 75, 110, 150, 177 X Fire PE-STWC 4871005 Ceiling 15, 30, 75, 110, 150, 177 X Fire Horns PE-HNR 4871000 Wall X No Lettering PE-HNW 4871001 Wall X No Lettering

Accessories Model Number Part Number Description Mounting Red White PE-SBB-R 4871022 PE Series Backbox Wall X PE-SBB-W 4871023 PE Series Backbox Wall X PE-SPKBB-CR 4871026 PE Series Backbox Ceiling X PE-SPKBB-CW 4871027 PE Series Backbox Ceiling X

Specification & Ordering Information

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

PE-HN, PE-HS, PE-ST Series Horns, Horn/Strobes, and Strobes

8830229-REV A 2/24

Architect & Engineering Specifications The notification appliances shall be Potter PE-HS audible visual strobe appliances, PE-ST visual strobe appliances and PE-HN audible appliances for wall and ceiling-mount applications with a low-profile design or approved equals. The PE-HS and PE-ST strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection Service and UL 1638 (Visible Signaling Devices. The PE-HS and PE-HN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All models shall meet the requirements of FCC Part 15 and ICES-003. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 16 to 33 VDC/

VFWR.

The PE-HS audible strobe and PE-ST strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Light Emitting Diode (LED) as the light source with a rugged Lexan® lens. The appliances shall be of low current design. The LED strobe flash duration shall be 20 ms. Where Multi-Candela appliances are specified, the strobe intensity shall have 6 field selectable settings at 15, 30, 75, 110, 135 and 185 candela for wall mount applications and 15, 30, 75, 110, 150 and 177 for ceiling applications. The selector switch for selecting the candela shall be tamper resistant. Appliances with candela settings shall show the candela selection in a visible location at all times when installed.

The audible shall have a choice of three (3) horn patterns (high & low output): Continuous, T3, and T3/T4 for fire (T3) and CO (T4) signaling.

The PE-HS audible strobe, PE-ST strobe, and PE-HN audible shall include a hinged mounting plate. Mounting options shall include PE-SBB backboxes, single-gang backbox and to 4” square with adapter kit for wall-mount models and PE-SPKBB backboxes, 4” square, 1 1/2” or 2 1/8”deep and 4” Octagonal, 1 ½” or 2 1/8”deep for ceiling models. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). All notification appliances shall be backwards compatible.

The PE-HS, PE-HN, and PE-ST wall models shall have a low profile measuring 4.79”H x 2.76”W x 1.18”D. The PE-HSC and PE-STC ceiling models shall have a low profile measuring 6.27” Diameter with 1.69”D.

When synchronization is required, the appliance shall be compatible with Potter fire alarm control panels and power supplies with built-in Wheelock® sync protocol The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate, the strobe shall revert to a non-synchronized flash-rate and still maintain (1) flash per second over its Regulated Voltage Range.

PAD100-SLCE

Addressable Loop Expander

8830091 - REV E • 9/19 page 1 OF 2

Potter Electric Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal.com

Description The Signaling Line Circuit expander paD100-SLCe allows up to thirty one additional loops. each loop adds 127 addressable sensors or modules in any combination. The PAD100-SLCE may be configured for Class a or Class B wiring without the need for additional modules.

The paD100-SLCe communicates with the control panel via the potter p-Link communication bus. The loop adder is mounted in either the control panel cabinet, the intelligent power supply, ae-2, ae-8 or the ae-14 expander cabinet. each card is mounted to the exclusive Stacker Bracket for secure and accessible mounting.

Technical Specifications

Standby Current 50ma alarm Current 50ma Operating Temperature 0°C–49°C (32°F–120°F) Operating Humidity Range 10% - 93% (non-condensing) Max no. of paD100-SLCe 31 Dimensions (W x H x D) 4” x 6” x 1-1/8”

Features

• No special wiring for SLC or p-Link connection

• SLC Class a, X or B capable

• Mounts with included stacker bracket

• May mount in panel, accessory cabinet, or pSN-1000/e power Supply

• product includes a 5 year warranty

• UUKL Listed for Smoke Control

Installation The paD100-SLCe is connected to the Ipa and aFC/aRC series panels using a four wire RS-485 connection. This connection is power limited and supervised. The paD100-SLCe can be installed in the ae-2 accessory enclosure, ae-8 accessory enclosure, ae-14 accessory enclosure or inside the large Ipa or aFC series enclosure using the supplied bracket.

8830091 - REV E • 9/19 page 2 OF 2

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

PAD100-SLCE

Addressable Loop Expander

PAD100-SLCE Class B P-LINK Wiring Example PAD100-SLCE Class A P-LINK Wiring Example Fig 2Fig 1

Model Description Stock No.

paD100-SLCe addressable Loop expander 3992722

Ordering Information

To the next device

A

B

Expansion Device

P-LINK

- + A B

Panel Connection

Expansion Device

Device

P-LINK

- + A B

P-LINK

- + A B

Panel Connection

Class A Expander Connection

Device

PAD100-MIM

Micro Input Module

8830079 - REV E • 9/23 PAGE 1 OF 2

Potter Electric Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal.com

Description The PAD100-MIM is used to monitor the status of an initiating device(s) that contain a normally open set of dry contacts. The module is enclosed in a plastic case to protect against inadvertent shorts and ground faults. The case can be mounted using a single screw. The PAD100-MIM has a status indicator LED to indicate communication and alarm condition. In normal condition, the LED flashes when the device is being polled by the control panel. When the input is activated, the LED will flash at a fast rate.

Application The micro input module (PAD100-MIM) is compatible with Potter’s IPA and AFC/ARC series addressable fire alarm control panels.

Generally the PAD100-MIM is used to monitor pull stations and other devices where the module is installed in an electrical box or enclosure behind the device being monitored.

Technical Specifications Operating Voltage 24.0V Max SLC Standby Current 200μA

Max SLC Alarm Current 200μA

IDC Input Circuit Wiring Class B

Max Wiring Resistance of IDC 100 Ω

Max Wiring Capacitance of IDC 1μF

EOL Resistor 5.1K Ω Operating Temperature Range 32 to 120ºF (0 to 49ºC)

Operating Humidity Range 0 to 93% (non-condensing)

Max no. of Module Per Loop 127 units

Dimensions 1.75” (44.5mm)L × 1.36” (34.5mm)W× .43” (11mm)D

Mounting Options 2-1/2” (64mm) deep single-gang box

Shipping Weight 0.3 lbs

Features

• One Class B contact monitoring input

• Small size allows mounting in most electrical boxes

• SLC Class A, Class X & Class B

• 6” Pigtail wiring connections

• Product includes a 5 year warranty

8830079 - REV E • 9/23 PAGE 2 OF 2

Potter Electr ic Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal .com

PAD100-MIM

Micro Input Module

Setting the Address

Wiring Diagram

Each addressable SLC device must be assigned an address. The address is set using the DIP switch located on the front of the PAD100-MIM. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device:

1. Power to the device is removed.

2. Field wiring is correctly installed.

3. Field wiring has no open or short circuits.

Fig 1

Model Description Stock No.

PAD100-MIM Micro Input Module 3992700

Ordering Information

FROM FACP OR PREVIOUS

DEVICE AND TO NEXT DEVICE

TO NORMALLY OPEN

MONITORED DEVICE

5.1K OHM REQUIRED

Part #3005013

PAD300-DUCTR

Analog Addressable Duct Detector

8830209 - REV C • 07/24 PAGE 1 OF 2

Potter Electric Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal.com

Description The PAD300-DUCTR is designed and built to meet all local requirements, as well as the NFPA regulations regarding duct smoke detectors. Air sampling is accomplished by two (2) tubes which protrude into the duct. An exhaust tube of one (1) standard length (7”) is supplied in the installation kit with the smoke duct unit. Once the duct width has been determined, the air intake sampling tubes must be ordered. Sampling tubes are supplied in three standard lengths: 2.5 ft., 5 ft., and 10 ft. and cut to size to fit the duct. Mounting the duct smoke unit is accomplished by the use of a template and two (2) sheet metal screws, which are provided. Mounting can be achieved without the removal of the clear cover which is secured by four (4) capture screws.

Application The Potter Electric PAD300-DUCTR duct smoke detector provides early detection of smoke and products of combustion present in air moving through HVAC ducts in commercial, industrial and residential applications. The PAD300-DUCTR is compatible with the IPA and AFC/ARC series addressable fire alarm control panels.

Technical Specifications Duct Detector Model Number PAD300-DUCTR Operating Voltage 24 VDC Current Draw 500 μA Detector Head Model PAD300-DD Detector Head Type Photoelectric Alarm Set Point Fixed at 2.5%/ft (8%/m) Sensitivity Test Method Self Diagnostic Test Air Velocity 300 ft/min to 4000 ft/min Ambient Temperature 32°F to 120°F (0°C to 49°C)

Humidity 10% to 85% Relative Humidity (Non-condensing)

Housing Material Plastic Backbox, Clear Plastic Cover

Finish Gray Backbox with Clear Cover Dimensions 13 1/2” L x 4 1/2” W x 2 1/4” H Maximum Net Weight 2 lbs.

Sampling Tubes 2.5 ft, 5 ft, or 10 ft

Relay Contact Rating 8A@30 VDC, 10A@120 VAC, 10A@250 VAC

Features

• Detects Smoke in Building HVAC Ducts

• Ships Complete with Housing and Head

• Compatible with Addressable IPA and AFC/ARC Series Panels

• SLC Class A, Class X & Class B

• Installation Without Removing the Head

• Listed Air Velocity of 300 to 4,000 ft/minute

• No Screens or Filters in Housing

• Durable Plastic Enclosure and Clear Cover

• Integrated Cover Tamper Switch

• Utilizes Simple Snap in Sampling Tubes STN Series

• One Form C Relay

• UUKL Listed for Smoke Control

• Compatible with Supervised PAD100-DRTS Remote Test Switch, MS-RA, MS-KA/R, MS-KA/P/R Remote Indicators

8830209- REV C • 07/24 PAGE 2 OF 2

Potter Electric Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal.com

PAD300-DUCTR

Analog Addressable Duct Detector

Air duct smoke detectors shall be Potter Electric PAD300-DUCTR Series. The detectors are certified by UL per 268 by Underwriters Laboratories. The detectors shall operate at air velocities from 300 feet per minute to 4000 feet per minute. The duct detector housings shall be of plastic construction and complete mechanical installation may be performed without removal of detector cover. Visual indication of alarm and power must be provided on detector front. Detector heads shall not require additional filters or screens which must be maintained. The housing shall contain a detector base and PAD300-DD duct smoke detector head. Terminal connections shall be of the screw type and be a minimum of #12 screw. All wiring must comply with local codes and regulations. Detector shall use the STN series of sampling tubes.

Engineering Specifications

Wiring Diagrams

Fig 1 Fig 2

Model Description Stock No.

PAD300-DUCTR Analog Addressable Duct Detector 3992796 PAD100-DRTS Duct Remote Test Switch 3992711 MS-RA Remote Annunciator 1000256

MS-KA/R Remote Annunciator with Test/Reset Switch 1000254

MS-KA/P/R Remote Annunciator with Test Switch 1000253

Model Description Stock No.

STN-2.5 2.5’ Sampling Tube 1000274 STN-5 5’ Sampling Tube 1000275 STN-10 10’ Sampling Tube 1000276

Ordering Information

PAD300-DRTS Wiring MS-KA/P/R Wiring

TO 24VDC

POWER

FORM C RELAY

10A, 250VAC

TO NEXT MODULE

FROM FACP OR

PREVIOUS MODULE

PAD100-DRTS

SUPERVISION OPTION

TO PAD100-DRTS

Note: Keep jumper in “On” position when using the PAD100-DRTS for full wiring supervision.

24VDC FROM FACP OR

PREVIOUS MODULE

FORM C RELAY

10A, 250VAC

TO NEXT MODULE

FROM FACP OR

PREVIOUS MODULE

Note: Jumper must be in “O�” position when using the MS-KA/P/R.

24VDC TO FACP OR

NEXT MODULE

TO MS-RA (RED WIRE)

TO MS-RA (BLACK WIRE)

SUPERVISION OPTION

SHOWN IN “OFF” POSITION

PAD300-HD

Heat Detector

8830210 - REV D • 07/24 PAGE 1 OF 2

Potter Electric Signal Company, LLC • St . Louis, MO • Phone: 800-325-3936 • www.pottersignal.com

Description The PAD300-HD is a listed analog addressable rate of rise and/or fixed temperature heat detector compatible with any fire alarm control panel that has the Potter Addressable Device (PAD) protocol. The heat sensing portion utilizes a proven thermistor for accurate and reliable heat detection. The detector and base (not included) are made of a durable plastic in an off-white to blend in with the ceiling.

The PAD300-HD is UL listed with a selectable fixed temperature point from 135° to 185° Fahrenheit and can be used for rate of rise applications. See detector spacing limitations below. This flexibility allows the installer to cover a wide variety of applications with a single unit.

The PAD300-HD and the control panel communicate over a proven and robust digital communication path and the system analyzes the information at the particular device. The total polling speed is less than five (5) seconds, well under the UL requirements.

The detector is compatible with any of the PAD300 series detector bases and simply twists on. The PAD300-HD is addressed using DIP switches in the rear of the detector and can be easily programmed in the field without special tools.

Setting the Address Each addressable device on the SLC loop must have a unique address from 1 to 127 to function properly. The address is set using DIP switches.

Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to SLC or device. Verify the following:

1. Power to the device is removed.

2. Field wiring is correctly installed.

3. Field wiring has no open or short circuits.

Technical Specifications Operating Voltage 24 VDC Detector Current Draw 300 µA Alarm Indicator 1 LED Alarm Set-point Range 135°F to 185°F (57°C to 85°C) Rate of Rise Detection (Selectable Option) 15°F/min. (8.3°C/min.)

Installation Temperature Range 32°F to 150°F (0°C to 66°C)

Operating Relative Humidity Range 0% to 93% (Non-condensing)

Start-up Time Max. 1 sec.

Ma…