This document is a Fire Alarm Annual Inspection Report for the Northeast Fisheries Science Center Milford CT Lab, conducted by Johnson Controls on January 10, 2023. The comprehensive inspection revealed several device deficiencies across multiple building zones, including broken pull station covers, a non-functioning remote key switch, and a fire alarm panel battery that failed both visual inspection and load testing due to its expiration date of 08/2016. Out of 176 total devices inspected, 170 passed, 5 failed, and 1 could not be inspected (a heat detector in the elevator mechanical room).
The key deficiencies included a pull station in the attic with broken hinges, a remote key switch by the roof-top access that was not working and corroded, a garage pull station with a broken cover held by a tie wrap, a rear shop pull station with a broken cover, and a fire alarm panel battery in the telephone room that failed load testing and had an outdated manufacture date. The inspection was performed by Chester Zebrowski from Johnson Controls, with the facility contact being Dom Capomolla, Facilities Engineer at the Northeast Fisheries Science Center. The report includes detailed images documenting each deficient device and its specific failure reason.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 1305M325Q0090 Questions and Answers.pdf | ||
| Sol_1305M325Q0090_Amd_0003.pdf | ||
| SOW Appendix 2 - Milford floor plans.pdf | ||
| Sol_1305M325Q0090_Amd_0002.pdf | ||
| Sol_1305M325Q0090_Amd_0001.pdf | ||
| Attachment 3 SCA Wage Determination 2025-4113 Rev 32 dated 08July2025.pdf | ||
| Attachment 2 POTTER Brand Technical Specifications.pdf | ||
| Sol_1305M325Q0090.pdf | ||
| Attachment 1 Statement of Work - Milford Fire Alarm System Upgrades.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CUSTOMER NAME: Northeast Fisheries Science Center Milford CT Lab BUILDING NAME: Northeast Fisheries Science Center Milford CT Lab BUILDING ADDRESS: 212 Rogers Ave, Milford, CT 06460 CONTACT NAME: Dom Capomolla CONTACT E-MAIL: domenick.capomolla@noaa.gov CONTACT ROLE: Facilities Engineer
CONTACT PHONE: 2036270994
INSPECTION TYPE: Fire Alarm v2 FREQUENCY: Annual
WORK ORDER: 53643484
INSPECTION START DATE: 01/10/2023
INSPECTION END DATE: 01/10/2023
INSPECTOR: Chester Zebrowski
INSPECTOR LICENSE: CT ELC 0189852-L6
ACCOUNT NAME: Johnson Controls North America OFFICE ADDRESS: 27 Inwood Road Rocky Hill, CT 06067
OFFICE PHONE: 860-602-3200
OFFICE LICENSE: CT FRP-0040801-F1 / CT ELC 018746-E1 / MA SC-00786 / MA 17359A
TIMEZONE: GMT-05:00
FIRE ALARM INSPECTION REPORT
Building Notes
1. 01/10/2023-All devices inspected and tested. Deficiencies are noted in this report.
DEVICE DEFICIENCIES
LOCATION DESCRIPTION ADDRESS DEVICE MAKE MODEL BARCODE DATE OF TEST TYPE IMAGES
Attic (Building #02) Attic Zone 06 Pull Station — — — 01/10/2023 VISUAL FAILURE
DEFICIENCY
IMAGES APPENDIX
1.1
FAILURE REASON: Cover hinges broken
Penthouse (Building #01) By roof- top access Zone 04 Remote Key Switch — — — 01/10/2023
FUNCTIONAL
FAILURE,VISUAL
FAILURE
DEFICIENCY
IMAGES APPENDIX
1.2
FAILURE REASON: Switch not working and is corroded.
Basement (Building #01) Garage Zone 01 Pull Station — — — 01/10/2023 VISUAL FAILURE
DEFICIENCY
IMAGES APPENDIX
1.3
FAILURE REASON: Broken cover. Being held by tie wrap
Floor 01 (Building #03) Rear shop Zone 08 Pull Station — — — 01/10/2023 VISUAL FAILURE
DEFICIENCY
IMAGES APPENDIX
1.4
FAILURE REASON: Broken cover
Basement (Building #01)
Telephone Rm FACP Panel Battery — Battery — — — 01/10/2023
FUNCTIONAL
FAILURE,VISUAL
FAILURE
DEFICIENCY
IMAGES APPENDIX
1.5
FAILURE REASON: Failed load test and expiration date code of 08/2016.
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Address: 212 Rogers Ave, Milford, CT 06460
Fire Alarm v2 | 01/10/2023 Page 1 of 15
INSPECTION RESULTS SUMMARY
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT
Annunciator 1 1 0 0
Battery 1 0 1 0
Duct Detector 3 3 0 0
Heat Detector 82 81 0 1
Panel 1 1 0 0
Pull Station 21 18 3 0
Remote Key Switch 3 2 1 0
Smoke Detector 22 22 0 0
Audible Visible Device 32 32 0 0
Visible Notification Device 10 10 0 0
TOTAL 176 170 5 1
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 2 of 15
Panels/Initiating Devices
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT
Annunciator 1 1 0 0
Battery 1 0 1 0
Duct Detector 3 3 0 0
Heat Detector 82 81 0 1
Panel 1 1 0 0
Pull Station 21 18 3 0
Remote Key Switch 3 2 1 0
Smoke Detector 22 22 0 0
FACP PANELS
# LOCATION DESCRIPTION MANUFACTURER MODEL DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Basement (Building #01)
Fire panel room across from elevator Simplex 4100ES Panel — Chester John
Zebrowski 01/10/2023 Passed
Is the panel in a normal condition at the start of the inspection? Yes
Alarm, Supervisory, and Trouble Signals (Inputs) Yes
Circuit Supervisory (Including Opens, Shorts & Ground Faults) Yes
POWER SUPPLY SUPV - LOSS OF AC POWER/BATTS Yes
Fuses/Lamps/LED Tested & Verified Yes
INTERFACE EQUIP VERIFICATION OF REQUIRED SIGNALS Yes
MAIN POWER SUPPLY TESTED UNDER FULL LOAD Yes
REMOTE ANNUNCIATOR(S) - OPERATION/VERIFICATION Yes
INITIATING DEVICES TEST Yes
ELEVATOR RECALL FUNCTION & SHUNT TRIP OPERATION Yes
HVAC SHUT DOWN Yes
MASTERBOX / CENTRAL STATION CONNECTION TESTED Yes
MASTERBOX / CENTRAL STATION ACCOUNT # FACP-Simplex 4100 U
Acct # 107-3150 Monitored by: JCI
ALARM NOTIFICATION APPLIANCES TESTED Yes
MULTIPLEX COMMUNICATIONS TESTED Yes
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 3 of 15
BATTERIES
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Basement (Building #01)
Telephone Rm FACP Panel Battery Battery — Chester John Zebrowski 01/10/2023 Failed
Quantity (Enter 2 if answering for a set) 2
Amp hour rating 33 AH
Visual inspection Fail
* Date code expiration fail
Batteries less than 5 years? Fail
Manufacturer Date Code 08/2016
Voltage with charger 26.5
Voltage without charger 25.0
Load Voltage Test Fail
Load Voltage Test Results (%) <40
Reason for failure: (Functional Failure,Visual Failure) Failed load test and expiration date code of 08/2016.
SMOKE DETECTORS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Floor 02 (Building #01) Elevator lobby Zone 03 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
2 Floor 01 (Building #01) Elevator lobby Zone 02 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
3 Floor 02 (Building #01)
Elevator lobby (Recall) M1-7 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
4 Floor 01 (Building #01)
Elevator lobby (Recall) M1-8 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
5 Basement (Building #01)
Elevator lobby (Recall) M1-9 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
6 Basement (Building #01) Elevator mech rm Zone 01 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
7 Basement (Building #01) Hall by elevator Zone 01 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
8 Floor 01 (Building #02)
Hall by main entrance Zone 05 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
9 Floor 02 (Building #01) Hall by rear stair Zone 03 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
10 Floor 01 (Building #02) Hall by rm 1 Zone 05 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
11 Floor 01 (Building #02) Hall by rm 5 Zone 05 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
12 Floor 01 (Building #01) Hall by rm 10 Zone 02 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
13 Floor 02 (Building #02) Hall by rm 15 Zone 06 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
14 Floor 02 (Building #02) Hall by rm 17 Zone 06 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
15 Floor 01 (Building #01) Hall by rm 19 Zone 02 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
16 Floor 02 (Building #01) Hall by rm 20 Zone 03 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
17 Floor 01 (Building #10) Kitchen Zone 09 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 4 of 15
SMOKE DETECTORS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
18 Floor 02 (Building #01) Rm 32 Zone 03 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
19 Basement (Building #01)
Telephone Rm (FACP room) Zone 01 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
20 Floor 02 (Building #01) Top of main stair Zone 03 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
21 Penthouse (Building #01) Top of stair Zone 04 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
22 Floor 02 (Building #10) Top of stair Zone 09 Smoke Detector — Chester John
Zebrowski 01/10/2023 Passed
HEAT DETECTORS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Attic (Building #02) Attic (center high) Zone 06 Heat Detector — Chester John Zebrowski 01/10/2023 Passed
Notes:
•Zone tested due to height
2 Attic (Building #02) Attic (left) Zone 06 Heat Detector — Chester John Zebrowski 01/10/2023 Passed
3 Attic (Building #02) Attic (right) Zone 06 Heat Detector — Chester John Zebrowski 01/10/2023 Passed
4 Floor 02 (Building #03)
Attic storage (Center) Zone 08 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
5 Floor 02 (Building #03) Attic storage (left) Zone 08 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
6 Floor 02 (Building #03) Attic storage (Right) Zone 08 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
7 Basement (Building #01) Boiler rm Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
8 Basement (Building #01) Boiler rm Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
9 Penthouse (Building #01) By water tanks Zone 04 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
10 Basement (Building #01) Elevator mech rm Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Cannot Inspect
Reason cannot inspect: Elevator technician needed for this inspection
11 Basement (Building #01)
Fish culture hatchery room (left) Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
12 Basement (Building #01)
Fish culture hatchery room
(right) Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
13 Floor 01 (Building #03) Front Shop Zone 08 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
14 Floor 01 (Building #02)
Furnace rm by main entrance Zone 05 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
15 Basement (Building #01) Garage Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
16 Basement (Building #01) Garage Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
17 Basement (Building #01) Garage Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 5 of 15
HEAT DETECTORS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
18 Basement (Building #01)
Janitors closet by restroom Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
19 Floor 01 (Building #01)
Janitors closet by rm 19 (Button Heat) Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
20 Floor 02 (Building #01)
Janitors closet in elevator lobby Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
21 Basement (Building #01)
Main electrical rm (off of boiler rm) Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
22 Basement (Building #01) Main fish culture rm Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
23 Basement (Building #01) Main fish culture rm Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
24 Basement (Building #01)
Mechanical rm 1 (off of boiler rm) Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
25 Basement (Building #01)
Mechanical rm by elevator lobby Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
26 Floor 01 (Building #03) Pump room Zone 08 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
27 Floor 01 (Building #03) Rear shop Zone 08 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
28 Basement (Building #01) Receiving office Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
29 Floor 01 (Building #02)
Restroom by main entrance (sprinkler
rm) Zone 05 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
30 Floor 01 (Building #02) Rm 1 Zone 05 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
31 Floor 01 (Building #02) Rm 1 left office Zone 05 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
32 Floor 01 (Building #02) Rm 1 right office Zone 05 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
33 Floor 01 (Building #02) Rm 5 Zone 05 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
34 Floor 01 (Building #02) Rm 6 Zone 05 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
35 Floor 01 (Building #01) Rm 10 Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
36 Floor 01 (Building #01) Rm 10 office Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
37 Floor 01 (Building #01) Rm 11 Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
38 Floor 01 (Building #01) Rm 11 office Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
39 Floor 01 (Building #01) Rm 12 Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
40 Floor 01 (Building #01) Rm 12 office Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
41 Floor 01 (Building #01) Rm 13 Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
42 Floor 01 (Building #01) Rm 13 office Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
43 Floor 01 (Building #01) Rm 14 Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 6 of 15
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
44 Floor 01 (Building #01) Rm 14 office Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
45 Floor 01 (Building #01) Rm 15 Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
46 Floor 01 (Building #01) Rm 15 office Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
47 Floor 01 (Building #01) Rm 16 Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
48 Floor 01 (Building #01) Rm 17 Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
49 Floor 01 (Building #01) Rm 17 office Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
50 Floor 01 (Building #01) Rm 18 Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
51 Floor 01 (Building #01) Rm 18 office Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
52 Floor 01 (Building #01) Rm 19 Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
53 Floor 01 (Building #01) Rm 19 office Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
54 Floor 02 (Building #01) Rm 20 Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
55 Floor 02 (Building #01) Rm 20 boiler rm Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
56 Floor 02 (Building #01) Rm 21 Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
57 Floor 02 (Building #01) Rm 21 office Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
58 Floor 02 (Building #01) Rm 22 Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
59 Floor 02 (Building #01) Rm 22 office Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
60 Floor 02 (Building #01) Rm 23 Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
61 Floor 02 (Building #01) Rm 23 office Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
62 Floor 02 (Building #01) Rm 24 Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
63 Floor 02 (Building #01) Rm 24 A Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
64 Floor 02 (Building #01) Rm 24 B Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
65 Floor 02 (Building #01) Rm 24 elec closet Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
66 Floor 02 (Building #01) Rm 25 Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
67 Floor 02 (Building #01) Rm 25 Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
68 Floor 02 (Building #01) Rm 26 Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
69 Floor 02 (Building #01) Rm 26 - office Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 7 of 15
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
70 Floor 02 (Building #01) Rm 28 Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
71 Floor 02 (Building #01) Rm 29 Zone 03 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
72 Floor 02 (Building #02) Room 11 Zone 06 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
73 Floor 02 (Building #02) Room 13 Zone 06 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
74 Floor 02 (Building #02)
Room 14 Women’s room Zone 06 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
75 Floor 02 (Building #02) Room 15 Zone 06 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
76 Floor 02 (Building #02)
Room 16 Men’s room Zone 06 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
77 Floor 02 (Building #02) Room 17 Zone 06 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
78 Floor 02 (Building #02) Room 18 Zone 06 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
79 Floor 02 (Building #02) Room 20 Zone 06 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
80 Floor 01 (Building #01)
Storage closet by rm 19 (Button Heat) Zone 02 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
81 Floor 01 (Building #02)
Storage rm by main entrance Zone 05 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
82 Basement (Building #01)
Storage / sinks rm by receiving office Zone 01 Heat Detector — Chester John
Zebrowski 01/10/2023 Passed
DUCT DETECTORS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Penthouse (Building #01) By roof- top access Zone 04 Duct Detector — Chester John
Zebrowski 01/10/2023 Passed
2 Floor 02 (Building #01) Elevator lobby Zone 03 Duct Detector — Chester John
Zebrowski 01/10/2023 Passed
3 Basement (Building #01)
Mechanical rm 1 (off of boiler rm) Zone 01 Duct Detector — Chester John
Zebrowski 01/10/2023 Passed
PULL STATIONS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Attic (Building #02) Attic Zone 06 Pull Station — Chester John Zebrowski 01/10/2023 Failed
Reason for failure: (Visual Failure) Cover hinges broken
2 Basement (Building #01) Boiler rm exit Zone 01 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
3 Floor 02 (Building #02) By Stair Zone 06 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
4 Penthouse (Building #01) By water tanks Zone 04 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
5 Floor 01 (Building #01) Elevator lobby Zone 02 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
6 Floor 01 (Building #02) Front entrance Zone 05 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 8 of 15
PULL STATIONS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
7 Floor 01 (Building #03) Front shop Zone 08 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
8 Basement (Building #01) Garage Zone 01 Pull Station — Chester John
Zebrowski 01/10/2023 Failed
Reason for failure: (Visual Failure) Broken cover. Being held by tie wrap
9 Basement (Building #01)
Gas cyclinder storage rm Zone 02 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
10 Basement (Building #01) Hall by elevator Zone 01 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
11 Floor 02 (Building #01) Hall by elevator Zone 03 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
12 Floor 02 (Building #01) Hall by rear stair Zone 03 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
13 Floor 01 (Building #01) Hall by rm 19 Zone 02 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
14 Floor 01 (Building #10) Main entrance Zone 09 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
15 Floor 01 (Building #01) Main entrance Zone 02 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
16 Floor 01 (Building #03)
Pump house entrance Zone 08 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
17 Floor 01 (Building #10) Rear door by patio Zone 09 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
18 Floor 01 (Building #02) Rear entrance Zone 05 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
19 Floor 01 (Building #03) Rear shop Zone 08 Pull Station — Chester John
Zebrowski 01/10/2023 Failed
Reason for failure: (Visual Failure) Broken cover
20 Basement (Building #01) Receiving area Zone 01 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
21 Floor 01 (Building #10)
Side exit by Bsmt hatch Zone 09 Pull Station — Chester John
Zebrowski 01/10/2023 Passed
MISCELLANEOUS ALARM & SUPERVISORY DEVICES
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Penthouse (Building #01) By roof- top access Zone 04 Remote Key Switch — Chester John
Zebrowski 01/10/2023 Failed
Reason for failure: (Functional Failure,Visual Failure) Switch not working and is corroded.
2 Floor 02 (Building #01) Elevator lobby Zone 03 Remote Key Switch — Chester John
Zebrowski 01/10/2023 Passed
3 Basement (Building #01)
Mechanical rm 1 (off of boiler rm) Zone 01 Remote Key Switch — Chester John
Zebrowski 01/10/2023 Passed
ANCILLARY FIRE ALARM DEVICES
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Floor 01 (Building #01) Main entrance Annunciator — Chester John Zebrowski 01/10/2023 Passed
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 9 of 15
Notification Devices
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT
Audible Visible Device 32 32 0 0
Visible Notification Device 10 10 0 0
AUDIBLE VISIBLE DEVICES W/DB
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Floor 02 (Building #03) Attic storage Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
2 Floor 02 (Building #03) Attic storage (left) Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
3 Basement (Building #01) Boiler rm Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
4 Attic (Building #02) By stairs Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
5 Penthouse (Building #01) By water tanks Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
6 Basement (Building #01)
Fish culture hall by hatchery 2 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
7 Basement (Building #01) Fish culture rm Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
8 Floor 01 (Building #02) Front entrance Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
9 Basement (Building #01) Garage Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
10 Basement (Building #01)
Gas cyclinder storage rm Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
11 Floor 02 (Building #01) Hall by elevator Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
12 Basement (Building #01) Hall by hatchery 1 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
13 Floor 02 (Building #01) Hall by rear stair Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
14 Floor 02 (Building #02) Hall by rm 15 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
15 Floor 01 (Building #01) Hall by rm 19 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
16 Floor 02 (Building #01) Hall by rm 20 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
17 Attic (Building #02) Left wall by fish tanks Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
18 Floor 01 (Building #10) Living rm / office Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
19 Basement (Building #01) Mechanical rm Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
20 Out (Building #11) Outside Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
21 Penthouse (Building #01)
Outside thru roof top access Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
22 Basement (Building #01) Receiving area Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
23 Floor 01 (Building #01) Rm 16 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
24 Floor 02 (Building #01) Rm 18 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
25 Floor 02 (Building #01) Rm 24 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
26 Floor 02 (Building #01) Rm 25 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
27 Floor 02 (Building #01) Rm 26 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 10 of 15
Notification Devices
AUDIBLE VISIBLE DEVICES W/DB
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
28 Floor 02 (Building #01) Rm 28 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
29 Floor 02 (Building #01) Rm 29 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
30 Floor 02 (Building #01) Rm 31 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
31 Floor 02 (Building #01) Rm 32 Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
32 Floor 02 (Building #10) Top of stair Audible Visible Device — Chester John Zebrowski 01/10/2023 Passed
DEVICES
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Basement (Building #01) Mens bathroom Visible Notification
Device — Chester John Zebrowski 01/10/2023 Passed
2 Floor 02 (Building #01) Mens bathroom Visible Notification Device — Chester John Zebrowski 01/10/2023 Passed
3 Floor 01 (Building #02) Mens restroom by main entrance
Visible Notification Device — Chester John Zebrowski 01/10/2023 Passed
4 Floor 02 (Building #01) Rm 20 Visible Notification Device — Chester John Zebrowski 01/10/2023 Passed
5 Floor 02 (Building #01) Rm 21 Visible Notification Device — Chester John Zebrowski 01/10/2023 Passed
6 Floor 02 (Building #01) Rm 22 Visible Notification Device — Chester John Zebrowski 01/10/2023 Passed
7 Floor 02 (Building #01) Rm 23 Visible Notification Device — Chester John Zebrowski 01/10/2023 Passed
8 Floor 02 (Building #02) Room 14 Womensroom Visible Notification Device — Chester John Zebrowski 01/10/2023 Passed
9 Floor 02 (Building #02) Room 16 Mensroom Visible Notification Device — Chester John Zebrowski 01/10/2023 Passed
10 Floor 02 (Building #01) Womens bathroom Visible Notification Device — Chester John Zebrowski 01/10/2023 Passed
Inspector Signature
Inspector Name Chester Zebrowski Date 01/10/2023
Signature of the
Inspector
Printed name of the Inspector Riley Arthur Date 01/10/2023
Signature of the
Facilities Manager
Printed name of the Facilities Manager Dom Capomolla Date 01/10/2023
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 11 of 15
Terms And Conditions
1. Limitation of Liability; Limitations Of Remedy. It is understood and agreed by the Customer that Company is not an insurer and that insurance coverage, if any, shall be obtained by the Customer and that amounts payable to Company hereunder are based upon the value of the services and the scope of liability set forth in this agreement and are unrelated to the value of the Customer's property and the property of others located on the premises. Customer agrees to look exclusively to the Customer's insurer to recover for injuries or damage in the event of any loss or injury and that Customer releases and waives all right of recovery against Company arising by way of subrogation. Company makes no guaranty or Warranty, including any implied warranty of merchantability or fitness for a particular purpose that equipment or services supplied by Company will detect or avert occurrences or the consequences there from that the equipment or service was designed to detect or avert.<br />It is impractical and extremely difficult to fix the actual damages, if any, which may proximately result from failure on the part of Company to perform any of its obligations under this agreement. Accordingly, Customer agrees that, Company shall be exempt from liability for any loss, damage or injury arising directly or indirectly from occurrences, or the consequences therefrom, which the equipment or service was designed to detect or avert. Should Company be found liable for any loss, damage or injury arising from a failure of the equipment or service in any respect, Company's liability shall be limited to an amount equal to the agreement price (as increased by the price for any additional work) or where the time and material payment term is selected, Customer's time and material payments to Company. Where this agreement covers multiple sites, liability shall be limited to the amount of the payments allocable to the site where the incident occurred. Such sum shall be complete and exclusive. If Customer desires Company to assume greater liability, the parties shall amend this agreement by attaching a rider setting forth the amount of additional liability and the additional amount payable by the Customer for the assumption by Company of such greater liability, provided however that such rider shall in no way be interpreted to hold Company as an insurer. IN NO EVENT SHALL COMPANY BE LIABLE FOR ANY DAMAGE, LOSS, INJURY, OR ANY OTHER CLAIM ARISING FROM ANY SERVICING, ALTERATIONS, MODIFICATIONS, CHANGES, OR MOVEMENTS OF THE COVERED SYSTEM(S) OR ANY OF ITS COMPONENT PARTS BY THE CUSTOMER OR ANY THIRD PARTY. COMPANY SHALL NOT BE LIABLE FOR INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED TO DAMAGES ARISING FROM THE USE, LOSS OF THE USE, PERFORMANCE, OR FAILURE OF THE COVERED SYSTEM(S) TO PERFORM. The limitations of liability set forth in this agreement shall inure to the benefit of all parents, subsidiaries and affiliates of Company, whether direct or indirect, Company's employees, agents, officers and directors.
2. Limited Warranty. COMPANY WARRANTS THAT ITS WORKMANSHIP AND MATERIAL FURNISHED UNDER THIS AGREEMENT WILL BE FREE FROM DEFECTS FOR A PERIOD OF NINETY
(90) DAYS FROM THE DATE OF FURNISHING. Where Company provides product or equipment of others, Company will warrant the product or equipment only to the extent warranted by such third party. EXCEPT AS EXPRESSLY SET FORTH HEREIN, COMPANY DISCLAIMS ALL WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE SERVICES PERFORMED OR THE PRODUCTS, SYSTEMS OR EQUIPMENT, IF ANY, SUPPORTED HEREUNDER. COMPANY MAKES NO WARRANTY OR REPRESENTATION, AND UNDERTAKES NO OBLIGATION TO ENSURE BY THE SERVICES PERFORMED UNDER THIS AGREEMENT, THAT COMPANY'S PRODUCTS OR THE SYSTEMS OR EQUIPMENT OF THE CUSTOMER WILL CORRECTLY HANDLE THE PROCESSING OF CALENDAR DATES BEFORE OR
AFTER DECEMBER 31, 1999.
3. Indemnity. Customer agrees to indemnify, hold harmless and defend Company against any and all losses, damages, costs, including expert fees and costs, and expenses including reasonable defense costs, arising from any and all third party claims for personal injury, death, property damage or economic loss, including specifically any damages resulting from the exposure of workers to Hazardous Conditions whether or not Customer pre-notifies Company of the existence of said hazardous conditions, arising in any way from any act or omission of Customer or Company relating in any way to this agreement, including but not limited to the Services under this agreement, whether such claims are based upon contract, warranty, tort (including but not limited to active or passive negligence), strict liability or otherwise. Company reserves the right to select counsel to represent it in any such action.
4. Hazardous Materials. Customer represents that, except to the extent that Company has been given written notice of the following hazards prior to the execution of this agreement, to the best of Customer's knowledge there is no:
a. "permit confined space," as defined by OSHA, or space in which work must be performed that, because of its construction, location, contents or work activity therein, accumulation of a hazardous gas, vapour, dust or fume or the creation of a risk of infectious disease
b. need for air monitoring, respiratory protection, or other medical risk
c. asbestos, asbestos-containing material, formaldehyde or other potentially toxic or otherwise hazardous material contained in or on the surface of the floors, walls, ceilings, insulation or other structural components of the area of any building
d. All of the above are hereinafter referred to as "Hazardous Conditions". Company shall have the right to rely on the representations listed above. If hazardous conditions are encountered by Company during the course of Company's work, the discovery of such conditions shall constitute an event beyond Company's control and Company shall have no obligation to further perform in the area where the hazardous conditions exist until the area has been made safe by Customer as certified in writing by an independent testing agency, and Customer shall pay disruption expenses and re-mobilization expenses as determined by Company. This agreement does not provide for the cost of capture, containment or disposal of any hazardous waste materials, or hazardous materials, encountered in any of the Covered System(s) and/or during performance of the Services. Said materials shall at all times remain the responsibility and property of Customer. Company shall not be responsible for the testing, removal or disposal of such hazardous materials.
5. Equipment Disconnections. This represents Company's notice to you that the system(s)/device(s) listed on the face of this agreement as temporarily or permanently disconnected are no longer in service and, thus, cannot detect, perform and/or report
6. General. Unless otherwise specified, work shall be performed during company's regular business hours,, exclusive of Saturdays, Sundays and Company holidays. All work is subject to review and rebilling in accordance with the terms and conditions of Customer's agreement/contract with Company, if one is in effect. Company shall not be responsible for failure to render services due to causes beyond its control, including but not limited to material shortages, work stoppages, fires, civil disobedience or unrest, severe weather, fire or any other cause beyond the control of Company. Customer is aware that the Limitation of Liability and other provisions set forth in any existing agreement/contract, if one is in effect, or set forth above, apply to services performed and materials supplied. The terms of this agreement shall govern notwithstanding any inconsistent or additional terms and conditions in any purchase order or other document submitted by Customer.
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 12 of 15
DEFICIENCY IMAGE APPENDICES
LOCATION DESCRIPTION DEVICE BARCODE TYPE IMAGES
Attic (Building #02) Attic Pull Station — VISUAL FAILURE DEFICIENCY IMAGES APPENDIX 1.1
FAILURE REASON: Cover hinges broken
Penthouse (Building #01) By roof- top access Remote Key Switch — FUNCTIONAL FAILURE,VISUAL FAILURE DEFICIENCY IMAGES APPENDIX 1.2
FAILURE REASON: Switch not working and is corroded.
Basement (Building #01) Garage Pull Station — VISUAL FAILURE DEFICIENCY IMAGES APPENDIX 1.3
FAILURE REASON: Broken cover. Being held by tie wrap
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 13 of 15
Floor 01 (Building #03) Rear shop Pull Station — VISUAL FAILURE DEFICIENCY IMAGES APPENDIX 1.4
FAILURE REASON: Broken cover
Basement (Building #01) Telephone Rm FACP Panel Battery Battery — FUNCTIONAL FAILURE,VISUAL FAILURE DEFICIENCY IMAGES APPENDIX 1.5
FAILURE REASON: Failed load test and expiration date code of 08/2016.
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 14 of 15
DEVICE NOTE IMAGE APPENDICES
Fire Alarm v2–Annual
Customer: Northeast Fisheries Science Center Milford CT Lab Building: Northeast Fisheries Science Center Milford CT Lab
Fire Alarm v2 | 01/10/2023 Page 15 of 15