Attachment 2 - MAHG231035 Repair Well 10 __ Specifications.pdf
PDF 195 KB Posted
- Attached to
- Repair Well #10 Federal contract opportunity
- Solicitation number
- FA301025R0026
About this file
This is a technical specification document titled "Section 26 05 00 - Basic Electrical Materials and Methods" for a federal construction project at Well 10 Building 7301, Keesler Air Force Base, Mississippi, under contract FA301025R0026 (MAHG231035). The document establishes baseline requirements and standards for electrical work across Division 26 "Electrical" sections of the project specification, referencing industry standards including NFPA 70 (2020 National Electrical Code), IEEE C2 (2017 National Electrical Safety Code), and various NEMA standards for electrical equipment enclosures and safety.
Key requirements include mandatory compliance with electrical codes and standards, submittal requirements for shop drawings and product data, quality assurance provisions requiring products to have 2 years of satisfactory commercial use prior to bid opening, and detailed specifications for electrical equipment marking and identification systems. The specification mandates factory-applied finishes meeting NEMA 250 corrosion-resistance standards, field-fabricated laminated plastic nameplates with specific dimensions and lettering requirements, polyethylene cable tags with detailed labeling protocols, and warning signs for high-voltage equipment exceeding 600 volts. Additional requirements include posted operating instructions for maintenance personnel, manufacturer nameplates on all equipment, instruction services for government personnel, and warranty support through reasonably located service organizations during the contract warranty period.
View the file
Other files for this federal contract opportunity
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Well 10 Bldg 7301, KEESLER AFB, MS Attachment 2
FA301025R0026
MAHG231035
SECTION 26 05 00
BASIC ELECTRICAL MATERIALS AND METHODS
12/23
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM D 709 (2022) Laminated Thermosetting Materials
ELECTRONIC INDUSTRIES ALLIANCE (EIA)
TIA/EIA-606-A (2006) Administration Standard for the Telecommunications Infrastructure
(ANSI/TIA/EIA-606-A)
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C2 (2017) National Electrical Safety Code
IEEE Std 100 (2015) IEEE Standard Dictionary of Electrical and Electronics Terms
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2018) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA C57.12.28 (2010) Pad-Mounted Equipment - Enclosure Integrity
NEMA C57.12.29 (2014; E 2000) Pad-Mounted Equipment - Enclosure Integrity for Coastal Environments
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2020) National Electrical Code
1.2 RELATED REQUIREMENTS
This section applies to certain sections of Division 2, "Site Construction," Division 11, "Equipment," Division 13, "Special Construction," and Division 14, "Conveying Systems" and Division 23, "Mechanical". This section applies to all sections of Division 26, "Electrical," of this project specification unless specified otherwise in the individual sections. This section has been incorporated into, and thus, does not apply to, and is not referenced in the following sections.
Related: Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM
SECTION 26 05 00 Page 1
1589327582E Cross-Out
Well 10 Bldg 7301, KEESLER AFB, MS MAHG231035
Related: Section 26 51 00 INTERIOR LIGHTING
1.3 DEFINITIONS
a. Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, shall be as defined in IEEE Std 100.
b. The technical sections referred to herein are those specification sections that describe products, installation procedures, and equipment operations and that refer to this section for detailed description of submittal types.
c. The technical paragraphs referred to herein are those paragraphs in PART 2 - PRODUCTS and PART 3 - EXECUTION of the technical sections that describe products, systems, installation procedures, equipment, and test methods.
1.4 Not Used
1.5 ADDITIONAL SUBMITTALS INFORMATION
Submittals required in other sections that refer to this section must conform to the following additional requirements as applicable.
1.5.1 Shop Drawings (SD-02)
Include wiring diagrams and installation details of equipment indicating proposed location, layout and arrangement, control panels, accessories, piping, ductwork, and other items that must be shown to ensure a coordinated installation. Wiring diagrams shall identify circuit terminals and indicate the internal wiring for each item of equipment and the interconnection between each item of equipment. Drawings shall indicate adequate clearance for operation, maintenance, and replacement of operating equipment devices.
1.5.2 Product Data (SD-03)
Submittal shall include performance and characteristic curves.
1.6 QUALITY ASSURANCE
1.6.1 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Equipment, materials, SECTION 26 05 00 Page 2 installation, and workmanship shall be in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
1.6.2 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Products shall have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2-year period shall include applications of equipment and materials under similar circumstances and of similar size. The product shall have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period. Where two or more items of the same class of equipment are required, these items shall be products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in the technical section.
1.6.2.1 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.6.2.2 Material and Equipment Manufacturing Date
Products manufactured more than 3 years prior to date of delivery to site shall not be used, unless specified otherwise.
1.7 WARRANTY
The equipment items shall be supported by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
1.8 POSTED OPERATING INSTRUCTIONS
Provide for each system and principal item of equipment as specified in the technical sections for use by operation and maintenance personnel. The operating instructions shall include the following:
a. Wiring diagrams, control diagrams, and control sequence for each principal system and item of equipment.
b. Start up, proper adjustment, operating, lubrication, and shutdown procedures.
c. Safety precautions.
d. The procedure in the event of equipment failure.
e. Other items of instruction as recommended by the manufacturer of each system or item of equipment.
Print or engrave operating instructions and frame under glass or in approved laminated plastic. Post instructions where directed. For operating instructions exposed to the weather, provide weather-resistant
SECTION 26 05 00 Page 3
Continued: materials or weatherproof enclosures. Operating instructions shall not fade when exposed to sunlight and shall be secured to prevent easy removal or peeling.
1.9 MANUFACTURER'S NAMEPLATE
Each item of equipment shall have a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
1.10 FIELD FABRICATED NAMEPLATES
ASTM D 709. Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as specified in the technical sections or as indicated on the drawings. Each nameplate inscription shall identify the function and, when applicable, the position. Nameplates shall be melamine plastic, 0.125 inch thick, white with black center core.
Surface shall be matte finish. Corners shall be square. Accurately align lettering and engrave into the core. Minimum size of nameplates shall be one by 2.5 inches. Lettering shall be a minimum of 0.25 inch high normal block style.
1.11 WARNING SIGNS
Provide warning signs for the enclosures of electrical equipment including substations, pad-mounted transformers, pad-mounted switches, generators, and switchgear having a nominal rating exceeding 600 volts.
a. When the enclosure integrity of such equipment is specified to be in accordance with NEMA C57.12.28 or NEMA C57.12.29, such as for pad-mounted transformers and pad-mounted SF6 switches, provide self-adhesive warning signs on the outside of the high voltage compartment door(s). Sign shall be a decal and shall have nominal dimensions of 7 by 10 inches with the legend "DANGER HIGH VOLTAGE" printed in two lines of nominal 2 inch high letters. The word "DANGER" shall be in white letters on a red background and the words "HIGH VOLTAGE" shall be in black letters on a white background. Decal shall be Panduit No. PPSO710D72 or approved equal.
b. When such equipment is guarded by a fence, mount signs on the fence. Provide metal signs having nominal dimensions of 14 by 10 inches with the legend "DANGER HIGH VOLTAGE KEEP OUT" printed in three lines of nominal 3 inch high white letters on a red and black field.
1.12
Provide tags for each power cable or wire located on this project.
The tags shall be polyethylene. Do not provide handwritten letters.
The first position on the power cable tag shall denote the voltage.
The second through sixth positions on the tag shall identify the circuit.
The next to last position shall denote the phase of the circuit and shall include the Greek "phi" symbol. The last position shall denote the cable size.
As an example, a tag could have the following designation: "11.5 NAS 1-8(Phase A)500," following designation: "11.5 NAS 1-8(Phase A)500," denoting that the tagged cable is on the 11.5kV system circuit number NAS 1-8, underground, Phase A, sized at #1 wire. The labeling of telecommunications cable tags
SECTION 26 05 00 Page 4 shall comply with TIA/EIA-606-A. Tag legend shall be as indicated.
1.12.1 Polyethylene Cable Tags
Provide tags of polyethylene that have an average tensile strength of 3250 pounds per square inch; and that are 0.08 inch thick (minimum), non-corrosive non-conductive; resistive to acids, alkalis, organic solvents, and salt water; and distortion resistant to 170 degrees F.
Provide 0.05 inch (minimum) thick black polyethylene tag holder. Provide a one-piece nylon, self-locking tie at each end of the cable tag. Ties shall have a minimum loop tensile strength of 175 pounds. The cable tags shall have black block letters, numbers, and symbols one inch high on a yellow background. Letters, numbers, and symbols shall not fall off or change positions regardless of the cable tags' orientation.
1.13 ELECTRICAL REQUIREMENTS
Electrical installations shall conform to IEEE C2, NFPA 70, and requirements specified herein.
1.14 INSTRUCTION TO GOVERNMENT PERSONNEL
Where specified in the technical sections, furnish the services of competent instructors to give full instruction to designated Government personnel in the adjustment, operation, and maintenance of the specified systems and equipment, including pertinent safety requirements as required.
Instructors shall be thoroughly familiar with all parts of the installation and shall be trained in operating theory as well as practical operation and maintenance work. Instruction shall be given during the first regular work week after the equipment or system has been accepted and turned over to the Government for regular operation. The number of man-days (8 hours per day) of instruction furnished shall be as specified in the individual section.
When more than 4 man-days of instruction are specified, use approximately half of the time for classroom instruction. Use other time for instruction with equipment or system. When significant changes or modifications in the equipment or system are made under the terms of the contract, provide additional instructions to acquaint the operating personnel with the changes or modifications.
PART 2 PRODUCTS
2.1 FACTORY APPLIED FINISH
Electrical equipment shall have factory-applied painting systems which shall, as a minimum, meet the requirements of NEMA 250 corrosion-resistance test and the additional requirements specified in the technical sections.
PART 3 EXECUTION
3.1 FIELD APPLIED PAINTING
Paint electrical equipment as required to match finish of adjacent surfaces or to meet the indicated or specified safety criteria. Painting shall be as specified in the section specifying the associated electrical equipment.
3.2 FIELD FABRICATED NAMEPLATE MOUNTING
Provide number, location, and letter designation of nameplates as indicated. Fasten nameplates to the device with a minimum of two
SECTION 26 05 00 Page 5 sheet-metal screws or two rivets.
3.3 WARNING SIGN MOUNTING, TEMPORARY
Provide the number of signs required to be readable from each accessible side, but space the signs a maximum of one on each wall and at each doorway.
3.4 CABLE TAG INSTALLATION
Install cable tags as specified, including each splice. Install cable tags including at each splice. Install cable tags over the fireproofing, if any, and locate the tags so that they are clearly visible without disturbing any cabling or wiring anywhere on this project.
-- End of Section --
SECTION 26 05 00 Page 6
| 16050 - BASIC ELECTRICAL MATERIALS AND METHODS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 RELATED REQUIREMENTS |
| 1.3 DEFINITIONS |
| 1.4 ELECTRICAL CHARACTERISTICS |
| 1.5 ADDITIONAL SUBMITTALS INFORMATION |
| 1.5.1 Shop Drawings SD-02 |
| 1.5.2 Product Data SD-03 |
| 1.6 QUALITY ASSURANCE |
| 1.6.1 Regulatory Requirements |
| 1.6.2 Standard Products |
| 1.6.2.1 Alternative Qualifications |
| 1.6.2.2 Material and Equipment Manufacturing Date |
| 1.7 WARRANTY |
| 1.8 POSTED OPERATING INSTRUCTIONS |
| 1.9 MANUFACTURER'S NAMEPLATE |
| 1.10 FIELD FABRICATED NAMEPLATES |
| 1.11 WARNING SIGNS |
| 1.12 CABLE TAGS IN MANHOLES, HANDHOLES, AND VAULTS |
| 1.12.1 Polyethylene Cable Tags |
| 1.13 ELECTRICAL REQUIREMENTS |
| 1.14 INSTRUCTION TO GOVERNMENT PERSONNEL |
| PART 2 PRODUCTS |
| 2.1 FACTORY APPLIED FINISH |
| PART 3 EXECUTION |
| 3.1 FIELD APPLIED PAINTING |
| 3.2 FIELD FABRICATED NAMEPLATE MOUNTING |
| 3.3 WARNING SIGN MOUNTING |
| 3.4 CABLE TAG INSTALLATION |