Attachment 2 Kearneysville Chiller Final Drawings.pdf
PDF 9 MB Posted
- Attached to
- Chiller Replacement Federal contract opportunity
- Solicitation number
- 12305B25R0005
About this file
These are detailed engineering design drawings for a chiller replacement project at the USDA Agricultural Research Service's Appalachian Fruit Research Station in Kearneysville, West Virginia. The comprehensive 15-sheet technical drawings cover mechanical, electrical, and demolition plans for replacing existing water-cooled chillers and associated pumping systems. The project includes three primary bid options: a base bid for chiller replacement, an optional bid for replacing condenser water pumps, and an optional bid for replacing chilled water pumps. The drawings specify technical details for equipment removal, new equipment installation, piping configurations, electrical connections, and system integration, with careful consideration for maintaining facility operations during construction. The contract number is 12305B21D0013/12305B22F0240, and the design is prepared by Johnson-McAdams Architects/Engineers.
The technical specifications include detailed equipment schedules for water-cooled helical rotary chillers and end suction centrifugal pumps, with specific requirements for electrical connections, performance parameters, and installation guidelines. The design emphasizes maintaining existing control systems, minimizing facility disruption, and following strict safety and installation protocols. Electrical work involves carefully managing existing electrical infrastructure, with specific instructions for demolition, circuit preservation, and new equipment connections. The drawings indicate the project will use Variable Frequency Drives (VFDs) and require precise coordination with existing mechanical and electrical systems to ensure seamless integration of new equipment.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 5 Amendment 0002 Questions and Answers 27JUN2025.pdf | ||
| Sol_12305B25R0005_Amd_0002.pdf | ||
| Sol_12305B25R0005_Amd_0001.pdf | ||
| Site Visit Information.pdf | ||
| Attachment 1 Kearneysville Chiller Final Specifications.pdf | ||
| Attachment 3 Wage Determination WV20250037.pdf | ||
| Attachment 4 Schedule of Pricing (MS Excel Interactive Document).xlsx | XLSX spreadsheet | |
| Solicitation 12305B25R0005.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P.A.
FIRM
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
CHILLER REPLACEMENT
USDA
VICINITY MAPLOCATION MAP NO SCALE NO SCALE
APPALACHIAN FRUIT RESEARCH STATION
2217 WILTSHIRE ROAD.
KEARNEYSVILLE, WV
INDEX OF DRAWINGS
NORTH NORTH
CHARLESTON
KEARNEYSVILLE
TITLE SHEET
T-101
U.S. DEPARTMENT OF AGRICULTURE
AGRICULTURAL RESEARCH SERVICE
APPALACHIAN FRUIT RESEARCH STATION
KEARNEYSVILLE, WV
SHEET NO. DRAWING NO. TITLE
T-100 1 OF 15 TITLE SHEET
M-001 2 OF 15 ABBREVIATIONS AND LEGEND
MD101 3 OF 15 HVAC DEMOLITION PLAN
MD102 4 OF 15 HVAC DEMOLITION DETAILS
M-101 5 OF 15 HVAC FLOOR PLAN
M-501 6 OF 15 WATER FLOW DIAGRAM
M-502 7 OF 15 DETAILS
M-601 8 OF 15 HVAC EQUIPMENT SCHEDULES
MP101 9 OF 15 MECHANICAL PIPING PLAN
ED000 10 OF 15 ELECTRICAL DEMOLITION LEGEND
ED100 11 OF 15 ELECTRICAL DEMOLITION PLAN
ED600 12 OF 15 ELECTRICAL DEMOLITION PANEL SCHEDULE
E-000 13 OF 15 ELECTRICAL NEW WORK LEGEND
E-100 14 OF 15 ELECTRICAL NEW WORK PLAN
E-600 15 OF 15 ELECTRICAL NEW WORK PANEL SCHEDULE
GENERAL NOTES:
1. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS
PRIOR TO PERFORMING WORK OR FABRICATION OR PURCHASE OF EQUIPMENT,
MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE BROUGHT TO THE
CONTRACTING OFFICER'S ATTENTION FOR RESOLUTION BEFORE PROCEEDING WITH ANY
CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
2. THE FACILITY WILL REMAIN IN OPERATION DURING ALL PHASES OF CONSTRUCTION. ALL
MEANS OF EGRESS MUST REMAIN FREE AND CLEAR.
3. COORDINATE CONSTRUCTION ACCESS AND STAGING AREA(S) WITH CONTRACTING
OFFICER PRIOR TO COMMENCING WORK.
CONTRACT NO: 12305B21D0013/12305B22F0240
ABBREVIATIONS AND LEGEND
M-001
P.A.
FIRM
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
SCHEMATIC
MECHANICAL LEGEND GENERAL NOTES
1. THIS PROJECT IS A RENOVATION OF AN EXISTING FACILITY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE BROUGHT TO THE CONTRACTING OFFICERS ATTENTION FOR RESOLUTION BEFORE PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
2. FACILITY RESEARCH WORK WILL REMAIN ACTIVE WHILE CONSTRUCTION WORK IS IN PROGRESS. ALL WORK SHALL BE PERFORMED SO THAT IT MINIMIZES DISRUPTION OF THE OPERATION OF THE FACILITY.
3. WORK SEQUENCING WILL BE REQUIRED TO ALLOW THE FACILITY TO REMAIN OCCUPIED AND OPERATIONAL
DURING THE WORK.
4. PROVIDE SAFETY BARRIERS AND FOLLOW ALL SAFETY REQUIREMENTS OF OSHA AND USDA-ARS TAKE
PRECAUTIONS TO ENSURE THE SAFETY OF ALL PERSONNEL.
5. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS (DO NOT SCALE FOR LOCATIONS). THE CONTRACTOR SHALL PROVIDE A COMPLETE AND FUNCTIONAL HEATING, VENTILATING, AND AIR CONDITIONING SYSTEM (HVAC) AS INDICATED WITH ALL NECESSARY
EQUIPMENT, APPURTENANCES AND CONTROLS AS INDICATED.
6. CONTRACTOR SHALL EMPLOY PERSONNEL WHO ARE TRAINED AND EXPERIENCED IN NECESSARY SKILLS TO
PERFORM MECHANICAL CONSTRUCTION AND DEMOLITION WORK.
7. CONTRACTOR SHALL USE APPROPRIATE TOOLS AND SHALL NOT IMPART EXCESSIVE VIBRATIONS TO THE
EXISTING STRUCTURE OR OTHER BUILDING COMPONENTS.
8. COORDINATE DUCTWORK AND PIPING WITH EXISTING STRUCTURAL, ELECTRICAL, PLUMBING, AND COMMUNICATION. MAKE OFFSETS AND TRANSITIONS TO COORDINATE WITH EXISTING CONSTRUCTION OTHER TRADES WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER. CONTRACTOR SHALL PROVIDE
COORDINATION DRAWINGS OF TRADES.
9. ALL DUCTWORK SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS UNLESS OTHERWISE NOTED.
10. PROVIDE AND INSTALL THERMOSTATS OR TEMPERATURE SENSORS WHERE SHOWN ON THE DRAWINGS.
MOUNT DEVICE AT 4'-6" ABOVE THE FINISHED FLOOR UNLESS OTHERWISE NOTED.
11. CONTRACTOR SHALL PROVIDE NEW HARDWARE, SOFTWARE AND PROGRAMMING REQUIRED TO CONNECT NEW EQUIPMENT TO EXISTING CONTROLS SYSTEM. EXISTING CONTROL SEQUENCES AND POINTS SHALL
MAINTAINED FOR OPERATION OF NEW EQUIPMENT.
ABBREVIATIONS
COMMON TERMS
GLOBE VALVE
GATE VALVE OR BALL VALVE
CHECK VALVE
PRESSURE GAUGE
FLEXIBLE CONNECTION
PLUG VALVE
GAUGE
CONNECT TO EXISTING
TEMPERATURE SENSORT
CO2 SENSORC
VERTICAL FIRE DAMPER
BACKFLOW PREVENTER
1 REFER TO KEYNOTES
THERMOMETER
PETE'S PLUG
HYDRONIC PUMP
3-WAY VALVE
2-WAY CONTROL VALVE
M
3-WAY MOTORIZED VALVE
SMOKE DETECTOR
MANUAL VOLUME DAMPER
SD
HORIZONTAL FIRE DAMPER
FD
FD
POINT OF DEMOLITION
CHWS
CHWR
CWS
CWR
A.F.F./AFF ABOVE FINISHED FLOOR G.P.H. GALLONS PER HOUR
ACCU AIR COOLED CONDENSING UNIT G.P.M. GALLONS PER MINUTE
AHU AIR HANDLING UNIT GA. GAUGE
AP ACCESS PANEL GAL. GALLONS
APPROX. APPROXIMATE GEN. GENERAL
AS AIR SEPARATOR GF GLYCOL FEED
AS AIR SEPARATOR HR. HOUR
ASD ADJUSTABLE SPEED DRIVE OR
VARIABLE FREQUENCY DRIVE
HWS HOT WATER SUPPLY
C.V. CHECK VALVE HWR HOT WATER RETURN
CF CHEMICAL FEED HX HEAT EXCHANGER
CFM CUBIC FEET PER MINUTE IN INCHES
CHWR CHILLED WATER RETURN K.W. KILOWATT
CHWS CHILLED WATER SUPPLY LAT LEAVING AIR TEMPERATURE
CL CENTER LINE LB POUND
CLG CEILING LWT LEAVING WATER TEMPERATURE
CONC. CONCRETE MAX. MAXIMUM
CONT. CONTINUATION MECH. MECHANICAL
CP CONDENSER WATER PUMP MFR. MANUFACTURER
CT COOLING TOWER MIN. MINIMUM OR MINUTE
CU CONDENSING UNIT NC NORMALLY CLOSED
CWP CHILLED WATER PUMP NO NORMALLY OPENED
CWR CONDENSER WATER RETURN NPT NATIONAL PIPE THREAD
CWS CONDENSER WATER SUPPLY Ø DIAMETER
dB DECIBELS O.D. OUTSIDE DIMENSION
DET. DETAIL P PUMP
DIA. DIAMETER PH PHASE
DIFF. DIFFUSER PRV PRESSURE REDUCING VALVE
DIM. DIMENSION PSI POUNDS PER SQUARE INCH
DN. DOWN R/A RETURN AIR
DWG. DRAWING RAD RADIUS
DWH DOMESTIC WATER HEATER RAR RETURN AIR REGISTER
E/A EXHAUST AIR RED. REDUCER
EA. EACH RED. REDUCER
EAG EXHAUST AIR GRILLE REINF. REINFORCING
EAT ENTERING AIR TEMPERATURE REQ'D. REQUIRED
ECC ECCENTRIC RPM REVOLUTIONS PER MINUTE
EF EXHAUST FAN SD SMOKE DETECTOR
EFF EFFICIENCY SEN SENSIBLE
ELEC. ELECTRICAL SF SQUARE FEET
ELEV. ELEVATION SQ. SQUARE
ET EXPANSION TANK TA TRANSFER AIR
EWT ENTERING WATER TEMPERATURE TEMP TEMPERATURE
F FAHRENHEIT TH THERMOMETER
F/SD FIRE/SMOKE DAMPER TYP. TYPICAL
FCO FLOOR CLEAN OUT U.N.O./UNO UNLESS NOTED OTHERWISE
FCU FAN COIL UNIT UC UNIT COOLER
FDC FIRE DEPARTMENT CONNECTION UH UNIT HEATER
FIN. FINISHED V VOLTS, VENT
FLR FLOOR V.T.R. VENT THRU ROOF
FPM FEET PER MINUTE VA VALVE
FT. FOOT VAV VARIABLE AIR VOLUME (BOX)
G NATURAL GAS PIPING VFD VARIABLE FREQUENCY DRIVE OR
ADJUSTABLE SPEED DRIVE
FPM FEET PER MINUTE W/ WITH
FT. FOOT WT WEIGHT
G NATURAL GAS PIPING
CH-1 CH-2
P-1
P-2
P-4
P-3
CU-6
BOILERBOILER
6" C
H W
S 8"
C H
W S
P-6
2-1/2" CW
10" CWS
10" CWR
6" CW
6" CW
6" CWR
HX-2 HX-1
4" CHWR
4" CHWS
3" CHWS
3" CHWR
C H
W S
C H
W R
H W
R
2" HWR
2" HWS
1/2" SCW
4" CW
ET-2
DWH
DWH
8"
8"
5"
HWS
1-1/2"
1"
4"
4"
3"
3/ 4"
4"
6"AS-1
GF-1
6" CHWS
FAN
O.A. INTAKE
FAN
HWP HWP
P-5
P-8
6"
P-7
4" CW
BFP-2
6" CW
4" HWS
8" CHWS
& CHWR
CF-2
GF-2
1" MAKE-UP WATER
ASSEMBLY (BFP-4)
CRU-5
2"V
MAKE-UP WATER
ASSEMBLY (BFP-3)
1-1/2"
6"
2"V
2"V
6" CHWR
1"
6"
6"
4"
AS-2
ET-1
CF-1
4"
PKG HW CONV.
CHEMICAL
WATER
TREATMENT
SYSTEM
SERVICE SINK
VFD'S (SEE
ELECTRICAL)
1-1/4"
HVAC FLOOR PLAN - DEMO
MD101
PLAN
NORTH
SCALE:
HVAC FLOOR PLAN - DEMO
1/4" = 1'-0"
MD101 PLAN
NORTH
GENERAL NOTES
GRAPHIC SCALE
1. BASE BID: DISMANTLE REMOVE AND DISCARD THE
EXISTING WATER COOLED CHILLERS. DISCONNECT
AND REMOVE POWER AND CONTROL WIRING AS
SHOWN ON ELECTRICAL PLANS. REMOVE EXISTING
PIPING AS REQUIRED FOR INSTALLATION OF THE
NEW CHILLERS. EXISTING HOUSEKEEPING PAD TO
REMAIN IN PLACE.
2. BID OPTION 1: DISMANTLE REMOVE AND DISCARD
THE EXISTING CONDENSER WATER PUMPS. REMOVE
ALL EQUIPMENT, COUPLINGS, GUARDS, PIPING, PIPE
SUPPORTS, MANUAL VALVES, PIPING SPECIALTY
ITEMS, GAUGES, INSULATION, AND ALL OTHER
ACCESSORIES. EXISTING HOUSEKEEPING PAD TO
REMAIN IN PLACE.
3. BID OPTION 2: DISMANTLE REMOVE AND DISCARD
THE EXISTING CHILLED WATER PUMPS. REMOVE ALL
EQUIPMENT, COUPLINGS,GUARDS, PIPING, PIPE
SUPPORTS, MANUAL VALVES, PIPING SPECIALTY
ITEMS, GAUGES, INSULATION, AND ALL OTHER
ACCESSORIES. EXISTING HOUSEKEEPING PAD TO
REMAIN IN PLACE.
P.A.
FIRM
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
KEY PLAN
KEY NOTES#
1. ALL PIPING AND EQUIPMENT SHOWN IS EXISTING TO
REMAIN UNLESS NOTED OTHERWISE.
LEGEND
ITEMS TO BE DEMOLISHED AS INDICATED
IN KEY NOTES.
PIPPING TO BE DEMOLISHED AS INDICATED
IN KEY NOTES.
DETAILS
MD102
SCALE:
DETAIL PHOTO 1
NOT TO SCALE
MD102
P.A.
FIRM
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
SCALE:
DETAIL PHOTO 2
NOT TO SCALE
MD102
SCALE:
DETAIL PHOTO 3
NOT TO SCALE
MD102 SCALE:
DETAIL PHOTO 4
NOT TO SCALE
MD102
P-6 P-4
P-5
CHWR
CHWS
CHWS
P-6 P-5
CHWR
P-6
P-5
CHWR
P- 1
P-2
GATE VALVE
GATE VALVE
CWS
GATE VALVE
GATE VALVE
GATE VALVE
EXISTING PAD TO REMAIN
LEGEND
ITEMS TO BE DEMOLISHED AS INDICATED
WITH HATCHING.
EXISTING PAD TO REMAIN (TYP)
EXISTING PAD TO REMAIN (TYP)
CH-1 CH-2
P-1
P-2
P-5
P-4
P-3
P-6
4"SERVICE SINK
EXISTING
VFD'S (SEE
ELECTRICAL)
CH-1 CH-2
P-1
P-2
P-4
P-3
CU-6
BOILERBOILER
6" C
H W
S 8"
C H
W S
P-6
2-1/2" CW
10" CWS
10" CWR
6" CW
6" CW
6" CWR
HX-2 HX-1
4" CHWR
4" CHWS
3" CHWS
3" CHWR
C H
W S
C H
W R
H W
R
2" HWR
2" HWS
1/2" SCW
4" CW
ET-2
DWH
DWH
8"
8"
5"
HWS
1-1/2"
1"
1-1/4" 1-1/4"
4"
4"
3"
3/ 4"
4"
6"AS-1
GF-1
6" CHWS FAN
O.A. INTAKE
FAN
HWP HWP
P-5
P-8
6"
P-7
4" CW
BFP-2
6" CW
4" HWS
8" CHWS
& CHWR
CF-2
GF-2
1" MAKE-UP WATER
ASSEMBLY (BFP-4)
CRU-5
2"V
MAKE-UP WATER
ASSEMBLY (BFP-3)
1-1/2"
6"
2"V
2"V
6" CHW
1"
6"
6"
4"
AS-2
ET-1
CF-1
4"
PKG HW CONV.
CHEMICAL
WATER
TREATMENT
SYSTEM
SERVICE SINK
HVAC FLOOR PLAN
M-101
PLAN
NORTH
SCALE:
HVAC FLOOR PLAN
1/4" = 1'-0"
M-101 PLAN
NORTH
KEY NOTES
GRAPHIC SCALE
1. BASE BID: FURNISH AND INSTALL NEW WATER
COOLED CHILLERS ON EXISTING HOUSEKEEPING
PADS. REFER TO DETAIL 2/M-502.
2. BID OPTION 1: FURNISH AND INSTALL NEW END
SUCTION CENTRIFUGAL CONDENSER WATER PUMPS.
REFER TO DETAIL 1/M-502.
3. BID OPTION 2: FURNISH AND INSTALL NEW END
SUCTION CENTRIFUGAL CHILLED WATER PUMPS.
REFER TO DETAIL 1/M-502.
P.A.
FIRM
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
KEY PLAN
CHILLED CONDENSER
WATER FLOW DIAGRAM
M-501
SCALE:
CHILLED CONDENSER WATER FLOW DIAGRAM
NOT TO SCALE
M-501
P.A.
FIRM
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
P-4P-3
CWR
EXISTING
CT-1
CWS
P-2
CH
-1
CH
-2
P-1
AS-1
ET-1
CHWR
CHWS CHWS
CHWR
BRIDGE
P-5
P-6
EXISTING MAKE-UP
WATER ASSEMBLY
1" SCW
8" EXISTING BUILDING
LOAD CONNECTIONS
EXISTING CHEMICAL FEEDER
8" 8"
6"
8"
8"
8"
6"
6"
6" 6"
6"
8"8" 10"
10"8"
8"
6" 8" 8"
6"
8"
EXISTING
EXISTING
EXISTING PIPING (TYP)
DETAILS
M-502
P.A.
FIRM
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
CHWR
CHWS
CONNECT TO SUPPLY AND RETURN
PIPING
PRESSURE GAUGE (TYP)
THERMOMETER
TRIPLE DUTY VALVE
FLEXIBLE CONNECTION (TYP.)
END SUCTION PUMP
ASSEMBLY
CONTINUE FULL SIZE LINE OF CASING TAPPING TO HUB
DRAIN AND TURN DOWN
END SUCTION
DIFFUSER
PET COCK (TYP.)
BUTTERFLY VALVE
2" DRAIN W/
BALL VALVE
HOUSEKEEPING PAD
FINISHED FLOOR
4" X 4" X 3/8" STEEL PLATE
BOLTED TO CONCRETE
INERTIA PAD
VIBRATION ISOLATION PADS
EXISTING HOUSEKEEPING PAD
FLOW SWITCHDRAIN VALVE W/CAP (TYP)
GAUGE WITH COCK
AND SNUBBER.
RELIEF DEVICE
(TYP.)
SHUTOFF
VALVE (TYP)
NOTES:
1. BOTH CONDENSER AND EVAPORATOR SHELLS SHALL HAVE MARINE
WATER BOXES, THEY ARE NOT INDICATED ABOVE FOR CLARITY.
2. INSTALL VENT AND DRAIN VALVES IN PLUGS PROVIDED IN MARINE
WATER BOXES.
3. VENT REFRIGERANT RELIEF VALVES ON CONDENSER AND COOLER
(3 TOTAL ON BASIS OF DESIGN UNIT) PER ASHRAE 15 PROVIDE
CLEANABLE, VERTICAL LEG TRAP. SIZE RELIEF PIPE PER MFR'S
INSTRUCTIONS OF CHILLER FURNISHED.
SCALE:
END SUCTION PUMP WITH END SUCTION DIFFUSER DETAIL
NOT TO SCALE
M-502 SCALE:
CENTRIFUGAL CHILLER PIPING DETAIL
NOT TO SCALE
M-502
VENT THRU ROOF TO
OUTDOORS WITH ELBOW
TURNED DOWN. SEE NOTE 3.
THERMOMETER
FLEX. PIPE
CONNECTOR
(TYP.)
BRAIDED STAINLESS
FLEX CONNECTOR.
CWS
CWR
OIL COOLER
BALANCE VALVE
HVAC EQUIPMENT SCHEDULES
M-601
GENERAL NOTES
1. BASIS OF DESIGN SHOWN TO ESTABLISH A
STANDARD OF QUALITY AND PERFORMANCE,
NOT TO LIMIT COMPETITION. EQUIVALENT
EQUIPMENT OF OTHER MANUFACTURERS
SHALL BE ACCEPTABLE.
2. SUBSTITUTED EQUIPMENT MANUFACTURERS
SHALL HAVE A WELL ESTABLISHED FACTORY
SERVICE TEAM AVAILABLE IN THE AREA OF THE
PROJECT.
3. ALL EQUIPMENT FURNISHED FOR THIS
PROJECT MUST COMPLY WITH THE "BUY
AMERICAN ACT".
P.A.
FIRM
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
NOTES
1. PROVIDE 150 LB FLANGED INLET AND OUTLET CONNECTIONS.
2. PROVIDE STAINLESS STEEL IMPELLER.
3. PROVIDE INLET AND OUTLET ISOLATION VALVES.
4. PROVIDE INLET AND OUTLET FLEX CONNECTIONS.
5. VARIABLE SPEED PUMPS SHALL BE SIZED TO DELIVER RATED FLOW AT 90% SPEED (54 HZ).
6. PRELIMINARY PUMP SIZING SHOWN. CONTRACTOR TO VERIFY FINAL PRESSURE DROP BASED ON ACTUAL PIPE ROUTING AND SIZING.
CONTRACTOR TO SIZE PUMPS PER MANUFACTURER'S RECOMMENDATION. PROVIDE PUMP OF SUFFICIENT CAPACITY TO DELIVER SCHEDULED FLOW RATE AT LISTED HEAD. SELECT MOTOR HP BASED ON PUBLISHED NON OVERLOADING HP AT ACTUAL
CONDITIONS.
PUMP SCHEDULE
MARK
BASIS OF DESIGN PUMP DATA ELECTRICAL DATA
WEIGHT
(LB) NOTES BID
OPTIONMANUFACTURER MODEL NO. TYPE
FLOW
(GPM)
TOTAL
HEAD
(FT WG)
RPM
EFFI-
CIENCY
INLET
SIZE
(IN.)
OUTLET
SIZE
(IN.)
IMPELLER
SIZE
(IN.)
MOTOR
POWER
(HP)
DUTY
POINT
POWER
(HP)
VOLTAGE
(VOLTS/PH)
P-1 BELL & GOSSETT e1510-3BD END SUCTION 389 65 1800 80.5 4 3 8.5 10 7.9 460 / 3 398 ALL BID OPTION 1
P-2 BELL & GOSSETT e1510-3BD END SUCTION 389 65 1800 80.5 4 3 8.5 10 7.9 460 / 3 398 ALL BID OPTION 1
P-3 BELL & GOSSETT e1510-3BD END SUCTION 358 50 1800 78.4 4 3 7.75 7.5 6.28 460 / 3 377 ALL BID OPTION 2
P-4 BELL & GOSSETT e1510-3BD END SUCTION 358 50 1800 78.4 4 3 7.75 7.5 6.28 460 / 3 377 ALL BID OPTION 2
P-5 BELL & GOSSETT e1510-4GC END SUCTION 680 100 1800 77.4 5 4 11 30 23.3 460 / 3 883 ALL BID OPTION 2
P-6 BELL & GOSSETT e1510-4GC END SUCTION 680 100 1800 77.4 5 4 11 30 23.3 460 / 3 883 ALL BID OPTION 2
WATER COOLED HELICAL ROTARY CHILLER SCHEDULE
MARK
BASIS OF DESIGN GENERAL DATA EVAPORATOR DATA CONDENSER DATA ELECTRICAL DATA
OPERATING
WEIGHT
(LB)
BID
OPTION
MANUFACTURER MODEL NO.
CAPACITY
(TONS)
COMPRESSOR
DATA REFRIGERATION
COOLING
EFFICIENCY
(kW/TON)
FLUID
DESIGN
FLOW
(GPM)
MINIMUM
FLOW
(GPM)
PRESSURE
DROP @
DESIGN
FLOW
(FT H2O)
ENTERING
FLUID
TEMP
(°F)
LEAVING
FLUID
TEMP
(°F)
FLUID
DESIGN
FLOW
(GPM)
MINIMUM
FLOW
(GPM)
PRESSURE
DROP @
DESIGN
FLOW
(FT H2O)
ENTERING
FLUID
TEMP
(°F)
LEAVING
FLUID
TEMP
(°F)
VOLTAGE
(VOLTS/PH)
POWER
CONNECTIONS
STARTER
TYPE
COMPRESSOR UNIT
TYPE QTY REFRIGERANT
TYPE CIRCUITS RLA
LRA
(A)
POWER
(kW)
MCA
(A)
MOCP
(A)
SCCR
(A)
CH-1
CH-2 TRANE RTWD130 133.7 SCREW 2 R-513A 2 0.791
30%
ETHYLENE
GLYCOL
350.3 130.0 26.4 55 45 WATER 388.9 191 20.1 85 95 460V/3Ø 1 WYE-
DELTA
A: 72 B: 72
A: 184
B: 184 105.7 164.0 225.0 65,000 6,543 BASE BID
NOTES
1. PROVIDE FULL FACTORY REFRIGERANT CHARGE.
2. SHELL AND TUBE EVAPORATOR AND CONDENSER WITH ASME PRESSURE VESSEL RATING.
3. GROOVED PIPE CONNECTIONS.
4. FACTORY INSTALLED CONTROL TRANSFORMER.
5. 3/4" FACTORY INSTALLED INSULATION ON ALL COLD SURFACES.
6. FACTORY INSTALLED DISCONNECT SWITCH WITH CIRCUIT BREAKER.
7. FACTORY INSTALLED BACNET INTERFACE CARD COMPATIBLE WITH EXISTING CONTROL SYSTEM.
8. FACTORY INSTALLED CHILLED WATER AND CONDENSER WATER FLOW SENSORS.
9. FACTORY INSTALLED COMPRESSOR HEATERS.
10. FACTORY INSTALLED PHASE PROTECTION.
11. FACTORY INSTALLED SOUND REDUCTION PACKAGE.
12. PROVIDE LOOSE SHIPPED ELASTOMERIC ISOLATORS.
13. MECHANICAL CONTRACTOR SHALL INTERLOCK CHILLED WATER PUMPS WITH CHILLER.
14. EACH REFRIGERANT CIRCUIT SHALL HAVE A MINIMUM OF COMPRESSOR SUCTION AND DISCHARGE SERVICE VALVES, REMOVABLE CORE FILTER, CHARGING PORT, SIGHT GLASS AND AN ELECTRONIC EXPANSION VALVE.
15. PROVIDE FACTORY START-UP. FIVE YEARS COMPLETE PARTS, REFRIGERANT, LABOR AND SERVICE WARRANTY.
16. CHILLER SHALL BE CERTIFIED BASED ON AHRI AND ASHRAE 90.1 STANDARDS.
17. CHILLER MUST BE SHIPPED COMPLETELY WRAPPED IN HEAVY DUTY BAG TO PROTECT FROM ROAD DAMAGE, ROAD SALT, AND CONSTRUCTION DIRT.
18. 150 PSIG RATING FOR ALL CONDENSER AND EVAPORATOR BUNDLES.
P-5
SERVICE SINK
EXISTING
VFD'S (SEE
ELECTRICAL)
P-5
P-8
6"
P-7
4" CW
BFP-2
6" CW
4" HWS
8" CHWS
& CHWR
CF-2
GF-2
1" MAKE-UP WATER
ASSEMBLY (BFP-4)
CRU-5
2"V
MAKE-UP WATER
ASSEMBLY (BFP-3)
1-1/2"
6"
2"V
2"V
6" CHW
1"
6"
6"
4"
AS-2
ET-1
CF-1
4"
PKG HW CONV.
CHEMICAL
WATER
TREATMENT
SYSTEM
SERVICE SINK
CH-1 CH-2
P-1
P-2
P-4
P-3
P-6
4"
CH-2
P-1
P-2
P-4
P-3
CU-6
BOILERBOILER
6" C
H W
S 8"
C H
W S P-6
2-1/2" CW
10" CWS
10" CWR
6" CW
6" CW
HX-2 HX-1
4" CHWR
4" CHWS
3" CHWS
3" CHWR
C H
W S
C H
W R
H W
R
2" HWR
2" HWS
1/2" SCW
4" CW
ET-2
DWH
DWH
8"
8"
5"
HWS
1-1/2"
1"
1-1/4" 1-1/4"
4"
4"
3"
3/ 4"
4"
6"AS-1
GF-1
FAN
O.A. INTAKE
FAN
HWP HWP
CH-1
MECHANICAL PIPING FLOOR PLAN
MP101
PLAN
NORTH
SCALE:
MECHANICAL PIPING FLOOR PLAN
1/4" = 1'-0"
MP101 PLAN
NORTH
KEY NOTES
GRAPHIC SCALE
1. BASE BID: FURNISH AND INSTALL NEW WATER
COOLED CHILLERS ON EXISTING HOUSEKEEPING
PADS. REFER TO DETAIL 2/M-502.
2. BID OPTION 1: FURNISH AND INSTALL NEW END
SUCTION CENTRIFUGAL CONDENSER WATER PUMPS.
REFER TO DETAIL 1/M-502.
3. BID OPTION 2: FURNISH AND INSTALL NEW END
SUCTION CENTRIFUGAL CHILLED WATER PUMPS.
REFER TO DETAIL 1/M-502.
P.A.
FIRM
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
KEY PLAN
NEW WORK
CWS
CWR
CHWS
CHWR
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
ED000
EXISTING PANELBOARD TO REMAIN.
EXISTING DEVICE TO REMAIN.
EXISTING DEVICE TO BE RELOCATED.
EXISTING DEVICE TO BE REMOVED PRIOR TO DEMOLITION,
STORED IN A PROTECTED AREA DURING CONSTRUCTION,
AND REINSTALLED AT THE END OF CONSTRUCTION.
ETR
RL
RR
EXISTING DEVICE TO BE DEMOLISH.
EXISTING VFD TO REMAIN.
EXISTING VFD TO BE DEMOLISHED.
CONDUCTORS IN CONDUIT CONCEALED WITHIN WALL OR CEILING. TIC
MARKS INDICATE NUMBER OF CONDUCTORS. THE EQUIPMENT
GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE PROVIDED.
SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND THE CONDUIT
PER THE NEC. THE ABSENCE OF TIC MARKS SIGNIFIES THAT TWO
CONDUCTORS PLUS AN EQUIPMENT GROUNDING CONDUCTOR
SHOULD BE PROVIDED. FOR EXAMPLE, THE MARKINGS TO THE LEFT
SIGNIFY THAT THREE CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED.
CIRCUITRY RUN IN STRAIGHT LINE SEGMENTS SIGNIFIES EXPOSED
SURFACE-MOUNTED RACEWAY (SEE SPECIFICATIONS) TO BE
DEMOLISHED.
ELECTRICAL DEMOLITION LEGEND
10 15
A. PRIOR TO BEGINNING WORK, SURVEY EXISTING ELECTRICAL SYSTEMS. DOCUMENT, IN WRITING, SIGNED BY THE CONTRACTING OFFICER, ANY PORTIONS OF THE EXISTING SYSTEMS THAT ARE NOT OPERATING PROPERLY BEFORE CONSTRUCTION BEGINS. ANY ELECTRICAL SYSTEMS FOUND INOPERABLE AT THE END OF THE CONSTRUCTION PROCESS THAT HAVE NOT BEEN SO DOCUMENTED SHALL BE REPAIRED BY THE CONTRACTOR AT HIS OWN EXPENSE.
B. PRIOR TO BEGINNING THE DEMOLITION PROCESS, CONDUCT A COMPREHENSIVE SITE SURVEY WITH THE ASSISTANCE OF OWNER'S REPRESENTATIVE.
IDENTIFY AND MARK ALL EXISTING EQUIPMENT TO REMAIN AND ALL EXISTING RACEWAYS AND CIRCUITRY THAT ARE PRESENTLY PASSING THROUGH THE
CONSTRUCTION AREA THAT ARE FEEDING EXISTING EQUIPMENT TO REMAIN.
C. FOR MECHANICAL EQUIPMENT BEING DEMOLISHED, EXISTING RACEWAYS SHALL BE RETAINED AND REUSED TO EXTENT PRACTICAL. CONDUCTORS SHALL
BE REPLACED UNLESS NOTED OTHERWISE.
D. WHERE CIRCUITS ARE NOT BEING COMPLETELY DEMOLISHED, REMOVE RACEWAYS AND CIRCUITRY BACK TO A JUNCTION BOX OR OTHER COMMON CONNECTION POINT AND RECIRCUIT EXISTING ELECTRICAL EQUIPMENT TO REMAIN AS REQUIRED. WHERE NECESSARY, COMPLETELY REFEED EXISTING ELECTRICAL EQUIPMENT THAT IS TO REMAIN IF REQUIRED. IT IS THE INTENT OF THESE DOCUMENTS THAT ALL EXISTING EQUIPMENT TO REMAIN SHALL BE KEPT COMPLETELY OPERABLE DURING CONSTRUCTION AND LEFT COMPLETELY OPERABLE AT THE END OF THE CONSTRUCTION PROCESS.
E. THE ELECTRICAL EQUIPMENT SHOWN IS PROVIDED TO CONVEY THE APPROXIMATE SCOPE OF THE WORK. PERFORM SITE SURVEY PRIOR TO DEMOLITION
TO DETERMINE EXACT EXISTING CONDITION.
F. PERFORM DEMOLITION WORK AS FOLLOWS:
· DEMOLISH DEVICE OR END OF LINE EQUIPMENT.
· DEMOLISH RACEWAYS AND CIRCUITRY FEEDING END OF LINE EQUIPMENT (INCLUDING ALL RACEWAYS AND CIRCUITRY ASSOCIATED WITH CONTROLS).
· LEAVE ALL RACEWAYS AND CIRCUITRY THAT COMPLETELY PASS-THROUGH THE SPACE FULLY OPERABLE BY REROUTING THE CIRCUITS AS REQUIRED.
CU-6
BOILERBOILER
HX-2 HX-1
ET-2
DWH
DWH
AS-1
GF-1
HWP HWP
P-5
P-8 P-7
CF-2
GF-2
CRU-5
ET-1
CF-1
ENGINEERING PLANT
ENGINEERING SHOP
OFFICE
SHOP OFFICE
P-6 P-4
P-3
P-2
P-1
CH-1
CH-2
DP1-10
DP1-12
DP1-11
DP1-9
DP1-7
DP1-8
MDP-#2 MDP-#1
MCC
T
K
ATS-1
EM-1
DP1
FA
EM-1A
DPP
CH-2
CONTROL
PANEL
CH-1
CONTROL
PANEL
7 5
EXISTING CONDUIT AND
CIRCUITRY TO REMAIN.
EXISTING CONDUIT AND
CIRCUITRY TO REMAIN.
EXISTING CONDUIT AND
CIRCUITRY TO BE
DEMOLISHED.
EXISTING CONDUIT AND
CIRCUITRY TO REMAIN.
225/3
ETR
ETR
ETR
ETR
ETR
ETR
DEMOLISH 5HP VFD.
PROVIDE NEW 7.5HP VFD.
P.A.
FIRM
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
ED100
PLAN
NORTH
SCALE:
ELECTRICAL DEMOLITION PLAN
1/4" = 1'-0"
ED100 PLAN
NORTH
5. PUMP #3 IS FED FROM A 20A, 3-POLE BREAKER IN PANEL
DP1, CIRCUIT #9. BREAKER AND CIRCUITRY SHALL BE
EXISTING TO REMAIN. REPLACE VFD AS SHOWN ON NEW
WORK PLAN. DISCONNECT EXISTING PUMP. RECONNECT
NEW PUMP EXTENDING CIRCUITRY AS REQUIRED
EXACTLY MATCHING EXISTING CONDUIT AND CIRCUITRY.
6. PUMP# 4 IS FED FROM A 20A, 3-POLE BREAKER IN PANEL
DP1, CIRCUIT #10. BREAKER, CIRCUITRY AND VFD SHALL
BE EXISTING TO REMAIN. DISCONNECT EXISTING PUMP.
RECONNECT NEW PUMP EXTENDING CIRCUITRY AS
REQUIRED EXACTLY MATCHING EXISTING CONDUIT AND
CIRCUITRY.
7. PUMP #5 IS FED FROM A 60A, 3-POLE BREAKER IN PANEL
DP1, CIRCUIT #11. BREAKER, CIRCUITRY AND VFD SHALL
BE EXISTING TO REMAIN. DISCONNECT EXISTING PUMP.
RECONNECT NEW PUMP EXTENDING CIRCUITRY AS
REQUIRED MATCHING EXISTING CONDUIT AND CIRCUITRY
EXACTLY.
8. PUMP #6 IS FED FROM A 60A, 3-POLE BREAKER IN PANEL
DP1, CIRCUIT #12. BREAKER, CIRCUITRY AND VFD SHALL
BE EXISTING TO REMAIN. DISCONNECT EXISTING PUMP.
RECONNECT NEW PUMP EXTENDING CIRCUITRY AS
REQUIRED EXACTLY MATCHING EXISTING CONDUIT AND
CIRCUITRY.
ELECTRICAL DEMOLITION PLAN
11 15
KEY NOTES
GRAPHIC SCALE
BASE BID
BID OPTION 1
BID OPTION 2
1. CHILLER NO.1 IS FED FROM A 225A, 3-POLE BREAKER IN
SWITCHBOARD MDP #1. BREAKER AND CIRCUITRY
FEEDING CHILLER NO.1 SHALL BE EXISTING TO REMAIN
AND REUSED FOR NEW CHILLER. DISCONNECT EXISTING
CHILLER. RECONNECT NEW CHILLER. EXTEND EXISTING
FEEDER AS REQUIRED TO CONNECT TO NEW CHILLER
EXACTLY MATCH EXISTING CONDUIT AND CIRCUITRY.
2. CHILLER NO.2 IS FED FROM A 300A, 3-POLE BREAKER IN
PANEL DPP. BREAKER AND CIRCUITRY FEEDING CHILLER
NO.2 SHALL BE DEMOLISHED.
3. PUMP #1 IS FED FROM A 20A, 3-POLE BREAKER IN PANEL
DP1, CIRCUIT #7. BREAKER, CIRCUITRY AND VFD SHALL
BE EXISTING TO REMAIN. DISCONNECT EXISTING PUMP.
RECONNECT NEW PUMP EXTENDING CIRCUITRY AS
REQUIRED EXACTLY MATCHING EXISTING CONDUIT AND
CIRCUITRY.
4. PUMP #2 IS FED FROM A 30A, 3-POLE BREAKER IN PANEL
DP1, CIRCUIT #8. BREAKER, CIRCUITRY AND VFD SHALL
BE EXISTING TO REMAIN. DISCONNECT EXISTING PUMP.
RECONNECT NEW PUMP EXTENDING CIRCUITRY AS
REQUIRED EXACTLY MATCHING EXISTING CONDUIT AND
CIRCUITRY.
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
ED600
SCALE:
ELECTRICAL DEMOLITION PANEL SCHEDULE
NONE
ED600
KEY NOTES
1. CHILLER NO.1 IS FED FROM A 225A, 3-POLE BREAKER
IN SWITCHBOARD MDP #1. BREAKER AND CIRCUITRY
FEEDING CHILLER NO.1 SHALL BE EXISTING TO
REMAIN AND REUSED FOR NEW CHILLER.
2. CHILLER NO.2 IS FED FROM A 300A BREAKER IN
PANEL DPP. BREAKER AND CIRCUITRY FEEDING
CHILLER NO.2 SHALL BE DEMOLISHED.
3. ALL PUMPS BREAKERS SHALL BE EXISTING TO
REMAIN FROM PANEL DP1.
ELECTRICAL DEMOLITION
PANEL SCHEDULE
12 15
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
E-000
ALL EXISTING PANELBOARD TO REMAIN.
EXISTING DEVICE TO REMAIN.
EXISTING DEVICE TO BE RELOCATED.
EXISTING DEVICE TO BE REMOVED PRIOR TO DEMOLITION, STORED
IN A PROTECTED AREA DURING CONSTRUCTION, AND REINSTALLED
AT THE END OF CONSTRUCTION.
EXISTING DEVICE TO BE DEMOLISH.
EXISTING VFD TO REMAIN.
EXISTING VFD TO BE DEMOLISHED.
ELECTRICAL NEW WORK LEGEND
CONDUCTORS IN CONDUIT CONCEALED WITHIN WALL OR CEILING.
TIC MARKS INDICATE NUMBER OF CONDUCTORS. THE EQUIPMENT
GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE PROVIDED.
SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND THE CONDUIT
PER THE NEC. THE ABSENCE OF TIC MARKS SIGNIFIES THAT TWO
CONDUCTORS PLUS AN EQUIPMENT GROUNDING CONDUCTOR
SHOULD BE PROVIDED. FOR EXAMPLE, THE MARKINGS TO THE LEFT
SIGNIFY THAT THREE CONDUCTORS PLUS AN EQUIPMENT
GROUNDING CONDUCTOR SHOULD BE PROVIDED.
THE TEXT INSIDE THE ARC INDICATES THE AWG SIZE OF THE
CONDUCTORS THAT SHALL BE RUN IN THE CONDUIT. THE ABSENCE
OF TEXT SIGNIFIES THAT THE CONDUCTORS SHOULD BE #12 AWG.
CIRCUITRY RUN IN STRAIGHT LINE SEGMENTS SIGNIFIES EXPOSED
SURFACE-MOUNTED RACEWAY (SEE SPECIFICATIONS).
Voltage Circuit Length Conductor Size (AWG)
120 < 50' #12
120 > 50' #10
120 > 90' #8
120 > 140' #6
277 < 130' #12
277 > 130' #10
277 > 200' #8
277 > 330' #6
VOLTAGE DROP CHART NOTES:
1) CIRCUIT SIZES INDICATED ON THE DRAWINGS ARE MINIMUM
REQUIREMENTS. REFER TO THIS CHART FOR UPSIZING CONDUCTORS AS NEEDED.
2) DO NOT CONNECT CONDUCTORS LARGER THAN #10 DIRECTLY TO A
RECEPTACLE OR A SWITCH. PROVIDE A JUNCTION BOX TO DOWNSIZE THE
CONDUCTOR TO #12 AT THE DEVICE.
3) FOR CIRCUITS LONGER THAN THOSE LISTED ABOVE, CONSULT WITH THE
ENGINEER FOR CONDUCTOR SIZES.
FINISH FLOOR
SUPPORT AND INSTALL ALL CONDUITS PER THE
LATEST EDITION OF THE NATIONAL ELECTRICAL
CODE (NEC)
OUTLET BOXES SHALL BE RIGIDLY AND SECURELY
FASTENED IN PLACE TO BUILDING STRUCTURE OR
BRACES.
SUPPORT GROUPS OF CONDUITS WITH ELECTRICAL STRUT
SUPPORTED BY THREADED RODS ANCHORED TO BUILDING
STRUCTURE.
JUNCTION & PULL BOXES SHALL BE RIGIDLY AND
SECURELY FASTENED IN PLACE TO BUILDING
STRUCTURE OR BRACES.
NOTE: JUNCTION, PULL AND OUTLET BOXES
SHALL BE 4" x 4" x 2-1/8" OR LARGER. SEE
SPECIFICATION FOR FLOOR, MASONRY AND
OTHER BOX TYPES.
SUPPORT WIRES SHALL NOT BE USED FOR SUPPORT OF
CONDUITS. ROD & WIRE FASTENERS (BATWING CLIPS) SHALL NOT
BE USED FOR SUPPORT OF CONDUITS.
SUPPORT SINGLE CONDUITS WITH CONDUIT
HANGER STRAPS AND THREADED RODS
ANCHORED TO BUILDING STRUCTURE.
WALL STUD
NOTE: EMT CONDUIT FITTINGS SHALL BE HOT GALVANIZED STEEL.
DIE CAST FITTINGS WILL NOT BE ALLOWED FOR ANY SIZE.
USE SCHEDULE 40 POLYVINYL CHLORIDE
(PVC) CONDUIT FOR CIRCUITS
UNDERGROUND.
USE PVC-COATED GALVANIZED RIGID STEEL
ELBOWS.
USE GALVANIZED RIGID STEEL OR
INTERMEDIATE METAL CONDUITS WHERE
CIRCUITS ARE EXPOSED TO ABRASION.
USE PVC-COATED GALVANIZED RIGID STEEL
CONDUIT FOR ALL VERTICAL RUNS
EXTENDING 6" ABOVE GRADE.
USE INTERMEDIATE METAL CONDUITS OR
ELECTRICAL METALLIC TUBING FOR ALL
BRANCH CIRCUITS, FEEDERS, AND
AUXILIARY CIRCUITS REQUIRING 1-1/4"
NOMINAL TRADE SIZE OR LARGER IN DRY
LOCATIONS.
UNDERGROUND CONDUIT. NOTE: GALVANIZED RIGID STEEL CONDUIT
COATED WITH TWO COMPLETE COATS OF
ASPHALTUM OR BITUMINOUS PAINT MAY BE
USED IN LIEU OF PVC-COATED GALVANIZED
RIGID STEEL CONDUITS.
USE GALVANIZED RIGID STEEL CONDUITS
WHERE CIRCUITS ARE RUN ABOVE GROUND
EXPOSED TO WEATHER.
GRADE OR
SLAB ON GRADE
SERVICES, CONDUITS FOR PRIMARY
CONDUCTORS, AND CONDUITS RUN
UNDER ROADWAYS SHALL BE BURIED
NO LESS THAN 48" DEEP.
NOTE: GRS & IMC CONDUIT THREADS SHALL
BE GALVANIZED AFTER CUTTING.
EMT CAN BE USED ON ALL DRY LOCATIONS.
USE PVC-COATED
GALVANIZED RIGID
STEEL ELBOWS.
USE PVC-COATED GALVANIZED RIGID STEEL
CONDUIT FOR ALL VERTICAL RUNS
EXTENDING 6" ABOVE GRADE.
13 15
SCALE:
JUNCTION AND OUTLET BOX DETAIL
NONE
E-000
SCALE:
CONDUIT DETAIL
NONE
E-000
P-5
CU-6
HX-2 HX-1
ET-2
HWP HWP
P-8 P-7
CF-2
GF-2
CRU-5
BOILERBOILER
ENGINEERING PLANT
ENGINEERING SHOP
SHOP OFFICE
OFFICE
P-5
CF-1
P-6 P-4
P-3
P-2
P-1
CH-1
CH-2
DP1-10
DP1-12
DP1-11
DP1-9
DP1-7
DP1-8
MDP-#2 MDP-#1
MCC
DPP
CH-2
CONTROL
PANEL
CH-1
CONTROL
PANEL
7 5
EXISTING CONDUIT AND
CIRCUITRY TO REMAIN.
EXISTING CONDUIT AND
CIRCUITRY TO REMAIN.
4#4/0, #4(G), 2-1/2"C.
EXISTING CONDUIT AND
CIRCUITRY TO REMAIN.
225/3
ETR
ETR
ETR
ETR
ETR
ETR
DEMOLISH 5HP VFD.
PROVIDE NEW 7.5HP VFD.
T
K
ATS-1
EM-1
DP1
FA
EM-1A
P.A.
FIRM
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
E-100
PLAN
NORTH
SCALE:
ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
E-100 PLAN
NORTH
ELECTRICAL NEW WORK PLAN
14 15
5. PUMP #3 IS FED FROM A 20A, 3-POLE BREAKER IN PANEL
DP1, CIRCUIT #9. BREAKER AND CIRCUITRY SHALL BE
EXISTING TO REMAIN AND REUSED FOR NEW PUMP#3.
REPLACE VFD AS SHOWN ON THIS DRAWING. DISCONNECT
EXISTING PUMP, RECONNECT NEW PUMP. EXTEND EXISTING
FEEDER AS REQUIRED TO CONNECT TO NEW PUMP
EXACTLY MATCH EXISTING CONDUIT AND CIRCUITRY.
6. PUMP# 4 IS FED FROM A 20A, 3-POLE BREAKER IN PANEL
DP1, CIRCUIT #10. BREAKER, CIRCUITRY AND VFD SHALL BE
EXISTING TO REMAIN AND REUSED FOR NEW PUMP#4.
DISCONNECT EXISTING PUMP, RECONNECT NEW PUMP.
EXTEND EXISTING FEEDER AS REQUIRED TO CONNECT TO
NEW PUMP EXACTLY MATCH EXISTING CONDUIT AND
CIRCUITRY.
7. PUMP #5 IS FED FROM A 60A, 3-POLE BREAKER IN PANEL
DP1, CIRCUIT #11. BREAKER, CIRCUITRY AND VFD SHALL BE
EXISTING TO REMAIN AND REUSED FOR NEW PUMP#5.
DISCONNECT EXISTING PUMP, RECONNECT NEW PUMP.
EXTEND EXISTING FEEDER AS REQUIRED TO CONNECT TO
NEW PUMP EXACTLY MATCH EXISTING CONDUIT AND
CIRCUITRY.
8. PUMP #6 IS FED FROM A 60A, 3-POLE BREAKER IN PANEL
DP1, CIRCUIT #12. BREAKER, CIRCUITRY AND VFD SHALL BE
EXISTING TO REMAIN AND REUSED FOR NEW PUMP#6.
DISCONNECT EXISTING PUMP, RECONNECT NEW PUMP.
EXTEND EXISTING FEEDER AS REQUIRED TO CONNECT TO
NEW PUMP EXACTLY MATCH EXISTING CONDUIT AND
CIRCUITRY.
KEY NOTES
GRAPHIC SCALE
BASE BID
BID OPTION 1
BID OPTION 2
1. CHILLER NO.1 IS FED FROM A 225A, 3-POLE BREAKER IN
SWITCHBOARD MDP #1. BREAKER AND CIRCUITRY FEEDING
CHILLER NO.1 SHALL BE EXISTING TO REMAIN AND REUSED
FOR NEW CHILLER. DISCONNECT EXISTING CHILLER.
RECONNECT NEW CHILLER. EXTEND EXISTING FEEDER AS
REQUIRED TO CONNECT TO NEW CHILLER. EXACTLY MATCH
EXISTING CONDUIT AND CIRCUITRY.
2. NEW CHILLER NO.2 SHALL BE FED FROM A NEW 225A, 3-POLE
BREAKER IN PANEL DPP, SEE NEW WORK PANEL SCHEDULE
ON SHEET E-600. PROVIDE NEW CIRCUITRY AS SHOWN ON
THIS DRAWING.
1. PUMP #1 IS FED FROM A 20A, 3-POLE BREAKER IN PANEL DP1,
CIRCUIT #7. BREAKER, CIRCUITRY AND VFD SHALL BE
EXISTING TO REMAIN AND REUSED FOR NEW PUMP#1.
DISCONNECT EXISTING PUMP, RECONNECT NEW PUMP.
EXTEND EXISTING FEEDER AS REQUIRED TO CONNECT TO
NEW PUMP EXACTLY MATCH EXISTING CONDUIT AND
CIRCUITRY.
2. PUMP #2 IS FED FROM A 30A, 3-POLE BREAKER IN PANEL DP1,
CIRCUIT #8. BREAKER, CIRCUITRY AND VFD SHALL BE
EXISTING TO REMAIN AND REUSED FOR NEW PUMP#2.
DISCONNECT EXISTING PUMP, RECONNECT NEW PUMP.
EXTEND EXISTING FEEDER AS REQUIRED TO CONNECT TO
NEW PUMP EXACTLY MATCH EXISTING CONDUIT AND
CIRCUITRY.
U
D A
S
THE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
E-600
KEY NOTES
1. CHILLER NO.1 IS FED FROM A 225A, 3-POLE BREAKER
IN SWITCHBOARD MDP #1. BREAKER AND CIRCUITRY
FEEDING CHILLER NO.1 SHALL BE EXISTING TO
REMAIN AND REUSED FOR NEW CHILLER.
2. PROVIDE NEW 225A, 3-POLE BREAKER TO FEED NEW
CHILLER NO. 2. MATCH THE NEW BREAKER IN TYPE
AND AIC RATING AS EXISTING BREAKERS.
3. ALL BREAKERS FEEDING PUMPS IN PANEL DP1 SHALL
BE EXISTING TO REMAIN AND BE REUSED TO FEED
ALL NEW PUMPS.
ELECTRICAL NEW WORK
PANEL SCHEDULE
SCALE:
ELECTRICAL NEW WORK PANEL SCHEDULE
NONE
E-600
15 15
| TITLE |
| T-100 |
| MECHANICAL |
| M-001 |
| MD101 |
| MD102 |
| M-101 |
| M-501 |
| M-502 |
| M-601 |
| MP101 |
| ELECTRICAL |
| ED000 |
| ED100 |
| ED600 |
| E-000 |
| E-100 |
| E-600 |
File details come from the government source that posted it. Updated .