This document provides details on a federal solicitation for multiple award task order contracts to provide real property repair, maintenance, and minor construction services for Army installations in Alaska. The solicitation was issued by the Department of the Army Materiel Command Army Contracting Command on behalf of the Directorate of Public Works Alaska. The solicitation seeks an indefinite delivery/indefinite quantity type contract with a one year base period and four one-year options to acquire a wide range of repair, maintenance, and construction services for Army facilities in Alaska. Responses are due by the date listed on the solicitation. Pricing will be obtained through future task orders issued against the multiple award contracts. The attached file appears to include sample electrical design drawings but no other context or description.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS G E N. E L E C . L E G E N D GENERAL NOTES

A AMPERE

AC ALTERNATING CURRENT

AF AMPERE FRAME

AGL ABOVE GROUND LEVEL

AHU AIR HANDLING UNIT

AIC

ANT ANTENNA

AT AMPERE TRIP

AUTO AUTOMATIC

AWG AMERICAN WIRE GAUGE

BC

BRKR

BTU

BATT BATTERY

BARE COPPER

BLDG BUILDING

BREAKER

BRITISH THERMAL UNIT

C

CB

CKT

CLG

CONC

COND

CURRENT TRANSFORMER

CONDUIT

CATV CABLE TELEVISION

CIRCUIT BREAKER

CIRCUIT

CEILING

CONCRETE

CONDUCTOR

CONT CONTROL

CORR CORRIDOR

CT

CONN CONNECTION

DB

DC

DEG

DIA

DIAG

DECIBEL

DIAMETER

DISC

DETAIL(S)

DIRECT BURIAL

dB

DIRECT CURRENT

DEGREE

DF DEMAND FACTOR

DIAGRAM

DET(S)

DISCONNECT

DWG(S) DRAWING(S)

EA

ENCL

EXH

EXST

EXHAUST

EACH

ELEC ELECTRICAL

EMER EMERGENCY

ENCLOSURE

EQUIP EQUIPMENT

EXT EXTERIOR

EXISTING

FXTR

FCP

F-C FOOTCANDLE

FLUOR

FIXTURE

FIRE ALARM

FIRE ALARM CONTROL PANEL

FL FLOOR

FG FINISH GRADE

FLUORESCENT

FT FOOT (FEET)

FU FUSE

GALV

GEN GENERATOR

(G)

GL

GROUNDING CONDUCTOR

GALVANIZE

GROUND LEVEL

GND GROUND OR GROUNDING

GFCI

GF/CI

GF/GI

HORSEPOWER

HDBC

HR

HANDHOLE

HARD DRAWN BARE COPPER

HH

HP

HOUR

HV HIGH VOLTAGE

HZ HERTZ

IN

JB JUNCTION BOX

JC

KV

KVA

KILOWATT

LA

MAN

MAX MAXIMUM

MS

MTS

MOUNTED/MOUNTING

NEMA

MOTOR STARTER

MANUAL TRANSFER SWITCH

OC

PAR

O/H

PARALLEL

PVC

PWR

PROTECTIONPROT

PF

RPM

SAF

SCHED

SIG

SQ

SN

INCH

INCAND INCANDESCENT

INCL INCLUDE

INSTL INSTALLATION

INTERCOM

JANITOR CLOSET

J-SIIDS

K KILO

KILOVOLT

KILOVOLT-AMPERE

KW

L LONG

LIGHTNING ARRESTER

MANUAL

MECH MECHANICAL

MED MEDIUM

MH

MINIMUMMIN

MTD/MTG

MTR METER

NOT IN CONTRACTN.I.C

NO NUMBER

OVERCURRENT

OVERHEAD

OL OVERLOAD

PH PHASE

PA PUBLIC ADDRESS

PRI

PANELBOARDPNLBD

PRIMARY

POWER

POWER FACTOR

QTY

QUANTITY

REPL

RCPT RECEPTACLE

REPLACE

REQ'D REQUIRED

RM ROOM

REVOLUTIONS PER MINUTE

SAFETY

SCHEDULE

SECT

SEC SECONDARY

SECTION

SELECTORSEL

SERV SERVICE

SH SHEET

SIGNAL

SOLID NEUTRAL

SPEC SPECIFICATION

SQUARE

TEL

TER

TTC

TELECOMMUNICATION ROOM

THK

TMR

UPS

TELEPHONE

TEMP TEMPERATURE

THICK

TIMER

TYP

TYPICAL

TV

TELEVISION

U/G UNDERGROUND

V VOLT

VA VOLT-AMPERE

XFR

WHM

W/O

PHASE

W WATT

W/ WITH

WITHOUT

KILOWATT-HOUR METER

WP WEATHERPROOF

TRANSFER

XFMR TRANSFORMER

& AND

NUMBER

o

EQL EQUAL

EP EXPLOSION PROOF

RR REMOVE & REINSTALL

HPS HIGH PRESSURE SODIUM

INTR INTERIOR

INTERCOMMUNICATIONS

FA

THOUSAND CIRCULAR MILS

LIGHTING

LG LENGTH

LV LOW VOLTAGE

LAN LOCAL AREA NETWORK

LTG

SS

STA STATION

STD STANDARD

STL

STOR STORAGE

SWITCH

STEEL

SURF SURFACE

SW

SYS SYSTEM

STAINLESS STEEL

AMPERE INTERRUPTING

CAPACITY

JOINT-SERVICE INTERIOR

INTRUSION DETECTION

SYSTEM

GOVERNMENT FURNISHED/

GOVERNMENT INSTALLED

GOVERNMENT FURNISHED/

CONTRACTOR INSTALLED

GROUND FAULT CIRCUIT

INTERRUPT

POLYVINYL CHLORIDE

CONDUIT OR DUCT

TELEPHONE TERMINAL

CABINET

UNINTERRUPTED POWER

SUPPLY

KCMIL

RGS

RIGID ZINC-COATED

STEEL CONDUIT

NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

MOUNTING HEIGHTS

MOUNTING HEIGHTS ABOVE FINISHED FLOOR SHALL BE AS FOLLOWS

UNLESS OTHERWISE NOTED.

MOUNTING HEIGHTS

72" TO TOP OF THE ENCL.

48" TO BOTTOM OF THE OUTLET

LAN OUTLET

60" TO CENTER OF THE ENCL.

60" TO CENTER OF THE ENCL.

SEE LTG. FXTR. SCHEDULE

12" ABOVE FLOOR

TEL TERMINAL BOARD

18" TO BOTTOM OF THE OUTLET

PANELBOARD

LIGHTING FIXTURES

SAFETY SWITCH

TELEPHONE OUTLET

WALL SWITCH

MOTOR CONTROLLER

18" TO BOTTOM OF THE OUTLET

18" TO BOTTOM OF THE OUTLET

18" TO BOTTOM OF THE OUTLET

RECEPTACLE (OFFICES)

RECEPTACLE (CORRIDORS)

48" TO BOTTOM OF THE OUTLET

RECEPTACLE

(SHOPS & LABORATORIES)

RECEPTACLE (REST ROOMS)

48" TO BOTTOM OF THE OUTLET

3. ANY CIRCUIT OF TELEPHONE SYSTEM SHALL BE 4PAIR, UNSHIELDED

TWISTED PAIR (UTP), CATEGORY 6 CABLE IN 1 INCH CONDUIT

1. ALL ELECTRICAL MATERIAL AND WORKMANSHIP SHALL COMPLY WITH

ALL THE REQUIRMENTS OF THE NATIONAL ELECTRICAL CODE 2017

4. ALL SEPARATE GROUNDING CONDUCTORS SHALL BE PROVIDED FOR

ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.

ALSO THE STEEL STRUCTURES SHALL BE BONDED TO THE

ELECTRICAL SYSTEM GROUNDING.

6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING

ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES

TO THEIR ORIGINAL CONDITION AND OPERATION DURING

AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.

THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE

WIDTH OF DUCT EXCAVATION.

7. THE CONTRACTOR SHALL NOTIFY CONTRACTING OFFICE,

AND DPW IN WRITING A MINIMUM OF 30 DAYS PRIOR TO THE

ANY SCHEDULED POWER OUTAGE. THE GOVERNMENT RESERVE

THE RIGHT TO POSTPONE THE REQUESTED POWER OUTAGE

UP TO 8 HOURS PRIOR TO REQUESTED POWER OUTAGE.

5. THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL SYSTEM

SHALL BE 25 OHMS OR LESS. ADDITIONAL GROUND RODS SHALL

BE ADDED TO OBTAIN THE REQUIRED SOIL RESISTANCE.

2. FIBER OPTIC CABLE INTO BUILDING MUST BE TERMINATED IN CABINET.

ALL FIBER TERMINATION EQUIPMENT MUST BE EXACTLY THE SAME

AS IS INSTALLED IN THIS SITE

LIGHTING SYMBOLS

PHOTOCELL SENSOR

OCCUPANCY SENSOR

J

POWER SYMBOLS

COMBINATION MAG. MOTOR STARTER

QUADUPLUX RECEPTACLE

JUNCTION BOX

DISCONNECT SAFETY SWITCH

DUPLEX RECEPTACLE

MOTOR

MAGNETIC MOTOR STARTER

M

MANUAL MOTOR STARTER

MANUAL MOTOR STARTER, 115V

DISCONNECT SAFETY SWITCH, FUSIBLE

F

A

S

SPECIAL RECEPTACLE

GFCI DUPLEX RECEPTACLE

POWER ONE-LINE LEGEND

M

CIRCUIT BREAKER

TRANSFORMER

GROUND

CURRENT TRANSFORMER

METER

MANUAL TRANSFER SWITCH

AFF ABOVE FINISHED FLOOR

N NEW

NORM NORMAL

G

BRANCH CIRCUIT HOMERUN; PANEL & CIRCUIT AS SHOWN

BRANCH-CIRCUIT PANELBOARD; RECESSED, SURFACE

FLOOR MOUNTED DUPLEX RECEPTACLE

RECESSED LUMINAIRE, 2'x4'

RECESSED LUMINAIRE, 2'x4' EMERGENCY

WALL MOUNTED LUMINAIRE

CEILING MOUNTED EXIT SIGN, ARROW AS INDICATED

WALL MOUNTED EXIT SIGN, ARROW AS INDICATED

WALL MOUNTED EXIT SIGN W/EMERGENCY LIGHTING UNIT

SURFACE MOUNTED LUMINAIRE, 1'x4'

SURFACE MOUNTED LUMINAIRE, 1'x4' EMERGENCY

WALL MOUNTED LUMINAIRE, EMERGENCY

SINGLE POLE SWITCH

THREE-WAY SWITCH3

CEILING MOUNTED LUMINAIRE

WALL MOUNTED EMERGENCY LIGHTING UNIT

WALL MOUNTED EXIT SIGN, ARROW AS INDICATED W/EMERGENCY

LIGHTING UNIT

TELECOMMUNICATION SYMBOLS

COMMUNICATIONS SYSTEM OUTLET: TELEPHONE AND DATA

CABLE TELEVISION OUTLET (CATV)

FLOOR MOUNTED RACK

T

ELECTRICAL CONDUIT AND CONDUCTORS

FLOOR MOUNTED OPEN RACK

E

8. THE CONTRACTOR SHALL INSTALL THE TELECOMMUNICATIONS

EQUIPMENT IN ACCORDANCE TO UFC 3-580-01,

TELECOMMUNICATIONS INTERIOR INFRASTRUCTURE PLANNING

AND DESIGN.

TELECOMMUNICATION CABLE

C

9. NEW EQUIPMENT WILL BE BOLD ON THE SHEETS.

10. #10 AWG THHN WIRE WILL BE USED FOR ALL INTERIOR WORK, UNLESS

OTHERWISE NOTED #10 AWG XHHW WIRE WILL BE USED FOR ALL EXTERIOR

WORK UNLESS OTHERWISE NOTED.

11. ALL NEW CONDUIT INSTALLED SHALL BE CONCEALED IN THE WALLS OR

SURFACE MOUNTED ABOVE THE DROPPED CEILING.

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

P S

O

F

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S K

A

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

C T

N

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps of Engineers ® Alaska District

W

A I N

W R

I G

H T

A

L A

S K

A

C I D

R

E N

O V

A T

E

B

L D

G

35%

F

B

W

K B

R x x

F T

W

F

NOT FOR CONSTRUCTION

VERIFY SCALES: BAR IS ONE INCH

ON ORIGINAL DRAWING

0 1"

A B

B R

E V

I A

T I O

L

G E

N D

F T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

G E

N E

R A

L

E-001

AutoCAD SHX Text

PS

AutoCAD SHX Text

OC

AutoCAD SHX Text

WH

PANEL D

PANEL E

MTR

(DU36 240 861)

AND 200AMP

BRKR

(POD11898)

PANEL C

B-27

B-27

B-27

B-27

B-27

B-27

B-27

B-27

B-27

A-2A-4

A-8

A-6

A-5

A-7

A-15

A-11

A-12

A-10

A-30

A-16A-18

A-3

A-1

A-28

A-26

A-23

A-27

A-13

A-9

A-17

A-19

A-21

A-25

A-22

A-24

A-33

A-29

A-20

A-31

A-14

B-24

B-24

G

G

B-3

B-13

C-21 C-21

C-6A

C-6A

C-6A

C-6A D-3

D-3

D-3

D-3

15A TWIST

LOCK

(3)QUADPLEX

30A, 120V

RECEP

30A, 208V, L6-30R

7' AFF

10' AFF

10' AFF

10' AFF

10' AFF

10' AFF

10' AFF

10' AFF

STORAGE

ROOM

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

TRAINING AND

BRIEFING ROOM

STORAGE

ROOM

STORAGE

AND ELEC. ROOM

MEN'S

RESTROOM

WOMEN'S

RESTROOM

STORAGE ROOM

AND GARAGE

STORAGE

ROOM

MEN RESTROOM

WOMEN RESTROOM

UTILITY ROOM

CLOSET

CLOSET

MEETING ROOM

MECH. ROOM

BREAK

ROOM

WEIGHT

ROOM

WEIGHT

ROOM

OFFICE

OFFICE

OFFICE

MEETING

ROOM

STORAGE

ROOM

STORAGE

ROOM

OFFICE

OFFICE

OFFICE

E-9

E-9

E-3

E-3

E-9

E-9

E-3

E-3

E-13

E-11

E-7

E-5

E-13

E-11

E-7

E-5

E-13

E-11

E-7

E-5

E-9

E-9

E-3

E-3

E-9

E-9

E-3

E-3

E-9

E-9

E-3

E-3

E-9

E-9

E-3

E-3

E-4

E-1

E-1

E-1

E-10

E-10

E-10

E-10

E-10

PANEL B

MDP

PANEL A

M

A-1,3,9,13,16, 18,23,26,27,28

A-17,19,20,21,22, 24,25,29,31,33

A-2,4,5,6,7,8,10,11,12,15

A-14

B-21

B-21

B-27

B-27

B-24

B-24

D-4

D-4

B-24

B-24

B-24

B-21

B-21

B-21

B-21

B-21

B-21

B-27

B-27

B-27

B-27

A-14

A-14

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

D E

M O

L I T

I O

N

F T

W

E

D d w g

B

T

R Z

A S

K A

R

R

H O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

P L

A N

S

ED101

SHEET NOTES:

1. REMOVE ALL HATCHED RECEPTACLES TO THE CLOSEST

JUNCTION BOX. THE EXISTING CONDUIT AND CONDUCTORS

WILL BE USED TO SUPPORT THE NEW RECEPTACLES, AS SEEN

ON SHEET E-101.

N

SCALE: 1/8" = 1'

EXISTING AND DEMO SITE POWER PLAN

C2

0 16'4' 8'

G

G

STORAGE

ROOM

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

TRAINING AND

BRIEFING ROOM

STORAGE

ROOM

STORAGE

AND ELEC. ROOM

MEN'S

RESTROOM

WOMEN'S

RESTROOM

STORAGE ROOM

AND GARAGE

STORAGE

ROOM

RESTROOM

RESTROOM

UTILITY ROOM

CLOSET

CLOSET

MEETING ROOM

MECH. ROOM

BREAK

ROOM

WEIGHT

ROOM

WEIGHT

ROOM

OFFICE

OFFICE

OFFICE

MEETING

ROOM

STORAGE

ROOM

STORAGE

ROOM

OFFICE

OFFICE

OFFICE

B-28

B-24

B-24

B-28

B-28

B-28 B-28

B-28

B-28

B-24

B-24

B-24

E-6 E-6 E-6 E-6

E-6 E-6 E-6 E-6

E-2 E-2 E-2 E-2

E-2 E-2 E-2 E-2

B-24

B-24

B-24

B-24

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

L I G

H T

I N

G

D

E M

O

F T

W

E

D d w g

B

T

R Z

A S

K A

R

R

H O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

P L

A N

S

ED102

SHEET NOTES:

1. ALL GENERAL LIGHTING LIGHT FIXTURES IN THE HATCHED

ROOMS WILL BE REMOVED AND REPLACED WITH LED LIGHT

FIXTURES (TYP 2FT. BY 4FT.). SEE SHEET E-102 FOR NEW

INSTALL LOCATIONS.

2. LIGHT FIXTURE WILL NOT BE REMOVED OR REPLACED.

3. REMOVE LIGHT FIXTURE.

N

SCALE: 1/8" = 1'

EXISTING AND DEMO SITE LIGHTING PLAN

C2

0 16'4' 8'

3.

2.

2.

2.

2.

2.

2.

2.

2.

2.

2.

2.

2.

2.

2.

2.

VESTIBULE

TOILET

MECHANICAL

103A

UTILITY

103B

TOILET

WITNESS

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

PROCESSING

CORRIDOR

VESTIBULE

SUSPECT

INTERVIEW

POLYGRAPH

WAITING

ADMIN

INTELLIGENCE

ANALYSTS

DETACHMENT

SGT

SAC OFFICE

CORRIDOR

ASAC OFFICE

DIGITAL

MEDIA

STORAGE

CORRIDOR

BREAK

ROOM

MEETING

ROOM

VEHICLE

HOLDING

DRUG

SUPPRESSION

TEAM

ELECTRICAL

ROOM

TER

TV

STORAGE

EVIDENCE

CONTROL

EVIDENCE

PROCESSING

EVIDENCE

STORAGE

CORRIDOR

GENERAL

CRIMES

SHOWER

GENERAL

CRIMES

WOMEN'S

TOILET

MEN'S

TOILET

CORRIDOR

CLASSROOM

VESTIBULE

MECHANICAL

PANEL E

MTR

(DU36 240 861)

AND 200AMP

BRKR

(POD11898)

PANEL C

B-27

B-27

B-27

B-27

B-27

B-27

B-27

B-27

B-27

A-2A-4

A-8

A-6

A-5

A-7

A-15

A-11

A-12

A-10

A-30

A-16A-18

A-3

A-1

A-28

A-26

A-23

A-27

A-13

A-9

A-17

A-19

A-21

A-25

A-22

A-24

A-33

A-29

A-20

A-31

A-14

B-24

G

G

B-3

B-13

C-6A

C-6A

C-6A

C-6A

15A TWIST

LOCK

10' AFF

G

D-1

D-2

D-3

D-4

PANEL B

MDP

PANEL A

(N)MTS

L14-30P, 120/240V, 30AMP TWIST LOCK

PLUG

8' AFF

8' AFF

J

E E

E E

J

(N)

PANEL F

(N)

PANEL D

M

G G

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

F L O

A

N

F T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

P L

A N

S

E-101

1. NEW 15/20 AMP DUPLEX RECEPTACLES WILL BE INSTALLED AT

ALL THE BOLD RECEPTACLE LOCATIONS, CONTRACTOR WILL

USE THE SAME CIRCUITS THAT THE EXISTING RECEPTACLES

WERE POWERED FROM.

2. #10 AWG THHN WIRE WILL BE USED FOR ALL INTERIOR WORK,

UNLESS OTHERWISE NOTED. #10 AWG XHHW WIRE WILL BE

USED FOR ALL EXTERIOR WORK UNLESS OTHERWISE NOTED.

3. PANEL D WILL BE RELOCATED AND REINSTALLED IN THE

ELECTRICAL ROOM. ADDITIONALLY A NEW MANUAL TRANSFER

SWITCH (MTS) WILL BE INSTALLED AND PROVIDE POWER TO

PANEL D. THE MTS WILL ALLOW PANEL D TO RECIEVE POWER

FROM THE MAIN DISTRIBUTION PANEL (MDP), NORMALLY, OR

FROM A GFGI PORTABLE GENERATOR, THROUGH THE NEW

L14-30P TWIST LOCK PLUG.

4. PANEL F WILL BE A NEW 3-PHASE, 30 SPACE, 100 AMP

ELECTRICAL PANEL, TO SUPPLY POWER TO THE

TELECOMMUNICATIONS ROOM AND CATV ROOM ONLY.

5. RECEPTACLES IN THE INTERVIEW ROOMS WILL BE TYPICAL

TAMPERPROOF DUPLEX RECEPTACLES.

6. CONNECT NEW RECEPTACLES TO THE NEAREST EXISTING OR

REMOVED RECEPTACLE CIRCUIT.

N

SHEET NOTES:

SCALE: 1/8" = 1'

SITE POWER PLAN

C2

0 16'4' 8'

INSTALL A NEMA 3R 6X6X4 INCH JUNCTION BOX TO THE EXTERIOR WALL, 6FT. AGL

INSTALL A NEMA 1 6X6X4 INCH JUNCTION BOX, 7FT. AFF.

INSTALL (1) 1-1/4" EMT CONDUIT W/PULL STRING,

ABOVE DROPPED CEILING.

TYP. CEILING MOUNTED DUPLEX RECEPTACLE

FOR PROJECTOR

INSTALL (1) MOTOR STARTERS FOR SHOWER ROOM EXHAUST FAN

HV

UH

F-2

F-3

F-1

INSTALL (1) MS FOR UH

INSTALL (1) MS FOR HV

SEE SHEET E-401, FOR

ENLARGED POWER PLAN.

E-10

E-10

A

E-2

AE

E-6

A

E-6

E-10

A

E-2

AE

E-2

AE

E-2

A

E-2

A

E-2

AE

E-2

AE

E-2

AE

E-6

A

E-6

AE

E-6

A

E-6

AE

E-6

A

E-6

C

CE

CE

CE

CE C

GE GE

GE

GE

G G

G

CE

CE

CE

CE

C

CC

C

FE F

F

F

F

F

F

F

F

F

F

FE

FE

FE

FE FE

FE

FE FE

FE

FE FE FE

FE

FEFE

BE

BE

E

DED

A

AE

G

BE BE

B B

B

B

B

BE

BE

BE

CE

C

F

F F

F

F

FE

FE

FE

FE

FE

FE

FE

F

F F

F

DE

DE

DE

D

D

D

GE

G

GE

GE

GE

GE

GE

GE

GE

G

G

G

GG

GE

GE

F

F

F

F

FE

FE

FE

FE

BE

B-28

BE

B-24

B

B-28

B

B-24

GE G

GE

GE

FE

FE

FE

FE FE

FE

F

F

F

F

F

F

F

AE

AE

F

VESTIBULE

TOILET

MECHANICAL

103A

UTILITY

103B

TOILET

WITNESS

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

PROCESSING

CORRIDOR

VESTIBULE

SUSPECT

INTERVIEW

POLYGRAPH

WAITING

ADMIN

INTELLIGENCE

ANALYSTS

DETACHMENT

SGT

SAC OFFICE

CORRIDOR

ASAC OFFICE

DIGITAL

MEDIA

STORAGE

CORRIDOR

BREAK

ROOM

MEETING

ROOM

VEHICLE

HOLDING

DRUG

SUPPRESSION

TEAM

ELECTRICAL

ROOM

TER

TV

STORAGE

EVIDENCE

CONTROL

EVIDENCE

PROCESSING

EVIDENCE

STORAGE

CORRIDOR

GENERAL

CRIMES

SHOWER

GENERAL

CRIMES

WOMEN'S

TOILET

MEN'S

TOILET

CORRIDOR

CLASSROOM

VESTIBULE

MECHANICAL

aaaa a a aaaa aaaa aaaa f g f g f h

BE

B-28

B

B-28

BE

B-24

B

B-24

BE

B-24

B

B-24

BE

B-24

B

B-24

BE

B-24

B

B-24

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

L I G

H T

I N

G

P

L A

N

F T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

P L

A N

S

E-102

SHEET NOTES:

1. ALL LIGHT FIXTURES WILL BE REPLACED WITH TYPICAL LED

OFFICE LIGHT FIXTURES, WITH THE EXCEPTION OF MECHANICAL

ROOM 103A AND THE EXIT AND EMERGENCY LIGHTS. THE

EXISTING CIRCUITS AND BREAKERS WILL BE USED FOR THE

NEW LED LIGHT FIXTURES. LIGHT FIXTURE MOUNTING

LOCATIONS WILL BE RELOCATED FROM THEIR EXISTING

INSTALLATION LOCATION.

2. NEW LIGHT SWITCHES WILL BE INSTALLED, TO CONTROL THE

LIGHTS IN THEIR RESPECTIVE ROOMS.

3. OCCUPANCY SENSOR WILL BE INSTALLED ON THE CEILINGS OF

THE CORRIDORS AND RESTROOMS ONLY.

4. EMERGENCY LIGHT INSTALLATION LOCATIONS WILL BE

PERFORMED IN THE 65% DESIGN.

N

SCALE: 1/8" = 1'

LIGHTING PLAN

C2

VESTIBULE

TOILET

MECHANICAL

103A

UTILITY

103B

TOILET

WITNESS

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

PROCESSING

CORRIDOR

VESTIBULE

SUSPECT

INTERVIEW

POLYGRAPH

WAITING

ADMIN

INTELLIGENCE

ANALYSTS

DETACHMENT

SGT

SAC OFFICE

CORRIDOR

ASAC OFFICE

DIGITAL

MEDIA

STORAGE

CORRIDOR

BREAK

ROOM

MEETING

ROOM

VEHICLE

HOLDING

DRUG

SUPPRESSION

TEAM

ELECTRICAL

ROOM

TER

TV

STORAGE

EVIDENCE

CONTROL

EVIDENCE

PROCESSING

EVIDENCE

STORAGE

CORRIDOR

GENERAL

CRIMES

SHOWER

GENERAL

CRIMES

WOMEN'S

TOILET

MEN'S

TOILET

CORRIDOR

CLASSROOM

VESTIBULE

MECHANICAL

PANEL E

MTR

(DU36 240 861)

AND 200AMP

BRKR

(POD11898)

PANEL C

PANEL B

MDP

PANEL A

(N)MTS

L14-30P, 120/240V, 30AMP TWIST LOCK

PLUG

J

J

J

J

(N) A-30

J

J

J

E E E

E E

E

E E E

E E E E E

E E

E

C C C C C

C C

C C

C C C C C

C

C C C C C C

C C

C C

C

C C

J

(N)

PANEL F

(N)

PANEL D

M

J

C C

C

J

J

J

J

J

J

J

JJ

J

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

S E

C U

R I T

Y

P

L A

N

F T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

P L

A N

S

E-103

1. A JUNCTION BOX AND 4 FT BY 8FT PLYWOOD BACKBOARD (IN

ACCORDANCE TO TIA-569-C) WILL BE INSTALLED IN THE

EVIDENCE STORAGE ROOM. 120V, 20A POWER WILL BE

PROVIDED FROM PANEL A CIRCUIT 30. THIS BREAKER AND

JUNCTION BOX WILL BE USED TO FOR PROVIDING POWER TO

THE EVIDENCE STORAGE ROOM IDS SYSTEM.

2. JUNCTION BOX WILL BE INSTALLED IN EACH OF THE VESTIBULES

TO SUPPORT THE IDS AND CAMERAS THAT WILL BE INSTALLED

BY OTHERS. SEE SHEET E-501 FOR ADDITIONAL DETAILS

3. ONE OF THE TWO JUNCTION BOXES IN EACH VESTBULE AND THE

WAITING ROOM WILL PROVIDE 12VOLT AC POWER FROM PANEL

A CIRCUIT 30 FOR THE IDS CCTV CAMERAS. THE OTHER

JUNCTION BOXES WILL EACH HAVE A 3/4 INCH EMT CONDUIT

AND PULL STRING ROUTED THROUGH BULDING 1579 TO A

JUNCTION BOX IN ADMIN ROOM 115.

4. CONDUIT ROUTES ARE FOR INFORMATIONAL PURPOSES ONLY

AND THE ACTUAL ROUTES MAY BE CHANGED DUE TO SITE

CONDITIONS.

5. CONDUIT AND J-BOXES SHALL BE INSTALLED ABOVE THE

DROPPED CEILING.

6. CCTV AND IDS SYSTEM WILL BE INSTALLED BY OTHERS.

N

SHEET NOTES:

SCALE: 1/8" = 1'

SECURITY PLAN

C1

3/4" EMT CONDUIT

WITH PULL STRING

(1) 12"X12"X6" J-BOX,

WITH (1) 3/4" EMT CONDUIT AND

PULL STRING TO TV ROOM

(1) 12"X12" X6"IN J-BOX,

WITH 3/4" EMT CONDUIT

AND A 120VAC TO 12VDC

CONVERTER

0 16'4' 8'

(1) 12"X12"X6" J-BOX WITH PULL STRING FROM ADMIN RM

NOTE 2.

(1) 12"X12"X6" J-BOX,

WITH (2) #10 THHN AWG,

(1) #12 THHN AWG GROUND

AND (1) 3/4" EMT CONDUIT

(1) 12"X12"X6" J-BOX,

WITH (1) 3/4" EMT CONDUIT AND

PULL STRING BETWEEN

TV AND TER ROOM

NOTE 2.

NOTE 2.

NOTE 2.

VESTIBULE

TOILET

MECHANICAL

103A

UTILITY

103B

TOILET

WITNESS

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

PROCESSING

CORRIDOR

VESTIBULE

SUSPECT

INTERVIEW

POLYGRAPH

WAITING

ADMIN

INTELLIGENCE

ANALYSTS

DETACHMENT

SGT

SAC OFFICE

CORRIDOR

ASAC OFFICE

DIGITAL

MEDIA

STORAGE

CORRIDOR

BREAK

ROOM

MEETING

ROOM

VEHICLE

HOLDING

DRUG

SUPPRESSION

TEAM

ELECTRICAL

ROOM

STORAGE

EVIDENCE

CONTROL

EVIDENCE

PROCESSING

CORRIDOR

VESTIBULE

MECHANICAL

MTR

(DU36 240 861)

AND 200AMP

BRKR

(POD11898)

PANEL C

PANEL B

MDP

PANEL A

(N)MTS

L14-30P, 120/240V, 30AMP TWIST LOCK

E

E E E E E E

E

E E E E E E E E

J

J

J

J

J

J

J

J

J

J

E E

E E

E

C

C C

C C

C C

C C

CCCCCC

J

(N)

PANEL D

M

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

C C

V

A

N

F T

W E d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

P L A

N S

E-104 xx

1. A 6"X6"X4" J-BOX, THAT HAS 3/4" EMT CONDUIT WITH PULL

STRING RAN FROM DIGITAL MEDIA ROOM 117, ABOVE THE

DROPPED CEILING.

2. A 6"X6"X4" J-BOX, THAT HAS 3/4" EMT CONDUIT WITH THREE #10

THHN WIRE (HOT, NEUTRAL, GROUND) RAN FROM PANEL A

CIRCUIT 36, ABOVE THE DROPPED CEILING.CONDUIT ROUTES

ARE FOR INFORMATIONAL PURPOSES ONLY AND THE ACTUAL

ROUTES MAY BE CHANGED DUE TO SITE CONDITIONS.

3. CCTV SYSTEM WILL BE INSTALLED BY OTHERS.

N

SHEET NOTES:

0 10'5'

SEE SHEET NOTE 1.

(1) 12"X12"X4" J-BOX

SCALE: 1" = 5'

INTERVIEW ROOM CCTV PLAN

C1

SEE SHEET NOTE 2.

SEE SHEET NOTE 1.

SEE SHEET NOTE 2.

SEE SHEET NOTE 1.

SEE SHEET NOTE 2.

SEE SHEET NOTE 1.

SEE SHEET NOTE 2.

SEE SHEET NOTE 1.

SEE SHEET NOTE 2.

morgan.m.pohlman.civ Highlight morgan.m.pohlman.civ Sticky Note

1. If this is for RG-11, should be RMC

F-8

PANEL F

F-8 F-8

F-8

F-4

F-4

F-4

F-6

F-6

F-6

F-1,3

F-5,7,9,11

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

E N

L A

R G

R

F T

W E d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

L A

R G

E S

C A

V

E

W S

E-401 xx

1. NEW 15/20 AMP DUPLEX RECEPTACLES WILL BE INSTALLED AT

ALL THE BOLD RECEPTACLE LOCATIONS, CONTRACTOR WILL

USE THE SAME CIRCUITS THAT THE EXISTING RECEPTACLES

WERE POWERED FROM.

2. #10 AWG THHN WIRE WILL BE USED FOR ALL INTERIOR WORK,

UNLESS OTHERWISE NOTED. #10 AWG XHHW WIRE WILL BE

USED FOR ALL EXTERIOR WORK UNLESS OTHERWISE NOTED.

3. NEW PANEL F, 3-PHASE, 30 SPACE, 100 AMP ELECTRICAL PANEL,

TO SUPPLY POWER TO THE TELECOMMUNICATIONS ROOM AND

CATV ROOM ONLY.

4.

N

SHEET NOTES:

0 16'4' 8'

INSTALL (1) MS FOR TV ROOM FAN F-2

F-13

INSTALL (1) MS FOR TER FAN F-3

F-13

F-2

F-3

SEE NOTE 3.

TER

TV

CORRIDOR

INSTALL (2) L6-20R RECEPTACLES, MINIMUM 18" AFF, FOR

THE CATV AND CCTV RACK.

INSTALL (4) L6-20R RECEPTACLES, MINIMUM 18" AFF, FOR

THE TELECOMMUNICATION RACKS.

SCALE: 1/2" = 1'

ENLARGED POWER PLAN - TER RM136 AND TV RM137

C4

INTERIOR FRONT VIEW ELEVATION

TYPICAL SINGLE ENTRY/EXIT

DOORWAY WITH SECURITY DEVICES

ELECTRIC

DOOR LOCK

EMT CONDUIT WITH WIRE ROUTED

FROM PANEL A CIRCUIT 30.

J-BOX TO PROVIDE POWER FOR

CAMERA.

HINGES (TYP)

UNSECURE SIDE

FINISHED FLOOR

DOOR TYPE AND

HARDWARE

EMT CONDUIT WITH PULL STRING ROUTED

TO ADMIN RM 115.

J-BOX TO PROVIDE COMMUNICATION

CONNECTION FOR CAMERAS.

EL

INTERIOR FRONT VIEW ELEVATION

TYPICAL SINGLE ENTRY/EXIT

DOORWAY WITH SECURITY DEVICES

ELECTRIC

DOOR LOCK

SST ARMORED FLEX CABLE

EMT CONDUIT WITH CABLES ROUTED

FROM PANEL A CIRCUIT 30.

J-BOX TO PROVIDE POWER

FOR IDS SYSTEM, TO INCLUDE

CAMERA AND BMS.

ELECTRICAL POWER

TRANSFER HINGE

(GFGI) BALANCED

MAGNETIC SWITCH (BMS*)

HINGES (TYP)

SECURE SIDE

FINISHED FLOOR

DOOR TYPE AND

HARDWARE

1 2 3 5

EL

SHEET NOTES:

ALL EXPOSED SECURITY DEVICES, ARMORED

CABLES, AND CONDUITS SHALL BE

INSTALLED WITH REQUIRED SUPPORT

HARDWARE PER NEC.

WIRE TERMINATIONS FOR SECURITY

DEVICES SHALL ONLY BE MADE INSIDE THE

DEVICE ENCLOSURE OR ASSIGNED BOX

ENCLOSURE.

ARMORED FLEX CABLES AND RGS CONDUITS

SHALL BE CONCEALED BEHIND FINISHED

WALLS AND CEILINGS WHERE APPLICABLE.

SEE DRAWING E-103 FOR LOCATION OF

DEVICES.

CABLES WITH SHIELDS SHALL HAVE SHIELDS

GROUNDED AT EACH INTENDED ENCLOSURE.

SHIELDS SHALL NOT BE TERMINATED AT

DEVICE. WRAP SHIELD AND TAPE TO CABLE

AT DEVICE END.

J-BOX (12"HX12"WX6"D) ENCLOSURES SHALL BE

LOCATED IN PROXIMITY OF DOOR LOCATION, TO

ALLOW AN UNSPLICED CONNECTION FROM (BMS*) TO

J-BOX.

POWER J-BOXES SHALL HAVE A 120VAC TO

12VDC INVERTER TO SUPPORT THE

CAMERA AND BMS.

ELECTRIC DOOR LOCK WITH ASSOCIATED DC

POWER SUPPLY REQUIREMENTS SHALL BE

PER SECURITY PLAN DRAWINGS, RISERS,

ARCHITECTURAL SPECIFICATIONS AND DOOR

SCHEDULES.

INSTALL TAMPER SWITCHES OR SECURITY

LOCKING SCREWS OR J-BOXES INSTALLED ON

THE NON-SECURE SIDE.

VERIFY DOOR HARDWARE PRIOR TO

LOCATING SWITCH NEAR THE DOOR EDGE.

X

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

4"

1" MAX FROM DOOR EDGE

(TYP)

BALANCED MAGNETIC SWITCH (BMS*)

NON-HINGED

SIDE OF DOOR

(TYPICAL FOR

RIGHT OR LEFT

HANDED DOORS)

J-BOX, SURFACE MOUNTED

WITH MOUNTING

HARDWARE PER NEC

MAGNET

DOOR STOP

HEAD FRAME

MAGNET

BALANCED MAGNETIC

SWITCH (BMS*) AND

MOUNTING HARDWARE

STAINLESS STEEL

ARMORED FLEX CABLE

AND CONNECTORS

SECURE

SIDE (TYP)

USE ADDITIONAL

SPACERS OR

BRACKETS FOR

MOUNTING (BMS*)

SWITCH

ADJUST GAP

AS REQUIRED

FOR OPTIMUM

OPERATIONS

(TYP)

SWITCH

DOOR EDGE

DOOR FRAME

SECURE SIDE

TAMPER

ALARM

SWITCH

(TAS*)

DOOR

SIDE VIEW FRONT VIEW

2 3 4 5

1 3

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

E E

T

A L

A S

S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L

E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

R E

N O

V A

D

G

C

I D

35%

O C

T

W K

B R x x x x x x x x

F T

W

F x x x x x x x

XXX

0 1"

S E

C U

R I T

Y

D

E T

A I L

F T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z

S

A M

Z

S

A M

E L

E C

T R

I C

A L

D E

T A

I L

S

E-501 xx

EMER NORM

(N) MTS-01

240V, 3-POLE,

50 AMP

100A BRKR

(CKT 14,16,18)

GENERATOR

240/120V, 1PH, 4W,

9.7KW

S

P

POLE MOUNTED XFMR

ID#:1229, 1230, & 1231

150KVA

UTIL- Pole 1109

METER ID: DU 36 240 861

POD UTILITY BRKR

200A

MDP - 225A Main Breaker

MDP 208/120V, 3PH, 4W, 225 AMP, 18K AIC

100A BRKR

(CKT 2,4,6)

70A BRKR

(CKT 38,40,42)

50A BRKR

(CKT 13,15)

#3/0 AWG AERIAL CABLE

(3) #3/0 AWG IN 2" CONDUIT

100A BRKR

(CKT 31,33,35)

CBL-0003

MDP Panel Loads

Panel A 208/120V, 3PH, 4W, 200 AMP, 10K AIC

Panel B 208/120V, 3PH, 4W, 100 AMP, 10K AIC

Panel E 208/120V, 3PH, 4W, 70 AMP, 10K AIC

Panel C 208/120V, 3PH, 4W, 100 AMP, 10K AIC

CBL-0004CBL-0005(3) #8 THHN AWG,

(1) #10 THHN AWG

GROUND, IN 3/4" EMT

CBL-0007

200A BRKR

(CKT 37,39,41)

(N) Panel F 208/120V, 3PH, 4W, 100 AMP, 10K AIC

(3) #2 THHN AWG,

(1) #8 THHN AWG

GROUND, IN 1-1/2" EMT

EXTERIOR

INTERIOR

(N) Panel D 240/120V, 1PH, 3W, 50 AMP, 10K AIC

(3) #8 THHN AWG,

(1) #10 THHN AWG

GROUND, IN 3/4" EMT

(3) #8 THHN AWG,

(1) #10 THHN AWG

GROUND, IN 3/4" EMT

S

P

POLE MOUNTED XFMR

ID#:1229, 1230, & 1231

150KVA

UTIL- Pole 1109

METER ID: DU 36 240 861

POD UTILITY BRKR

200A

MDP - 225A Main Breaker

100A BRKR

(CKT 2,4,6)

70A BRKR

(CKT 38,40,42)

50A BRKR

(CKT 13,15)

#3/0 AWG AERIAL CABLE

(3) #3/0 AWG, (1) #2 AWG XHHW GROUND IN 2" CONDUIT

100A BRKR

(CKT 31,33,35)

CBL-0003

MDP Panel Loads

CBL-0004CBL-0005CBL-0006

CBL-0007

200A BRKR

(CKT 37,39,41)

EXTERIOR

INTERIOR

MDP 208/120V, 3PH, 4W, 225 AMP, 18K AIC

Panel A 208/120V, 3PH, 4W, 200 AMP, 10K AIC

Panel B 208/120V, 3PH, 4W, 100 AMP, 10K AIC

Panel E 208/120V, 3PH, 4W, 70 AMP, 10K AIC

Panel C 208/120V, 3PH, 4W, 100 AMP, 10K AIC

Panel D 240/120V, 1PH, 3W, 50 AMP, 10K AIC

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

O N

E L I N

E

D

I A

G R

A M

F T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z

S

A M

Z

S

A M

E L

E C

T R

I C

A L

S C

H E

D U

L E

S

A

A

G R

A M

S

E-601

SCALE: NTS

EXISTING ONE-LINE

C1

SCALE: NTS

NEW ONE-LINE

C6

SHEET NOTES:

1. THE GENERATOR WILL REQUIRE SOMEONE TO MANUALLY PLUG

THE GENERATOR INTO THE L14-30P PLUG, THAT WILL BE

INSTALLED ON THE BUILDING AND TRANSFER THE MANUAL

TRANSFER SWITCH (MTS-01) TO EMERGENCY, FOR PANEL D TO

RECEIVE POWER FROM THE GENERATOR.

G

MDP, 208/129V, 3PH, 4W, 225 AMP

G

POD UTILITY

BRKR

, 208/120V, 3PH,

4W, 200 AMP

N

INTERIOREXTERIOR

GND

#2

G

N

GND

#2

PANEL A,

208/120V, 3PH,

4W, 200 AMP

PANEL B,

208/120V, 3PH,

4W, 100 AMP

PANEL C,

208/120V, 3PH,

4W, 100 AMP

PANEL D,

208/120V, 2PH,

4W, 50 AMP

PANEL E,

208/120V, 3PH,

4W, 70 AMP

G

N

GND

#4

G

N

GND

#4

G

N

GND

#10

G

N

GND

#10

G

N

EMER-OFF-NORM

(N)MTS-01

240V, 3-POLE,

50 AMP

GENERATOR

, 240/120V, 1PH,

4W, AMP

N

G

MDP, 208/129V, 3PH, 4W, 225 AMP

G

POD UTILITY

BRKR

, 208/120V, 3PH,

4W, 200 AMP

N

INTERIOREXTERIOR

GND

#2

PANEL A,

208/120V, 3PH,

4W, 200 AMP

(N) PANEL D,

208/120V, 2PH,

4W, 50 AMP

G

N

GND

#10

G

N

GND

#4

(N)GND

#8

G

N

GND

#4

G

N

(N)GND

#2

PANEL B,

208/120V, 3PH,

4W, 100 AMP

GND

#2

G

N

PANEL C,

208/120V, 3PH,

4W, 100 AMP

PANEL E,

208/120V, 3PH,

4W, 70 AMP

(N) PANEL F,

208/120V, 3PH,

4W, 100 AMP

G

N

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

G R

O U

N D

I N

G

D

I A

G R

A M

F T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z

S

A M

Z

S

A M

E L

E C

T R

I C

A L

S C

H E

D U

L E

S

A

A

G R

A M

S

E-602

SCALE: NTS

EXISITING GROUNDING DIAGRAM

E2

SCALE: NTS

NEW GROUNDING DIAGRAM

A2

SHEET NOTES:

1. THE POD UTILITY BREAKER IS ASSUMED TO BE CONNECTED TO

A GROUND ROD.

2. TWO NEW TELECOMMUNICATIONS MAIN GROUND BUSBAR

(TMGB) WILL BE INSTALLED, ONE EACH IN THE CATV AND

TELECOMMUNICATION ROOMS.

LIGHT FIXTURE SCHEDULE

FIXT.

FIXTURE DESCRIPTION

FIXTURE FIXTURE LAMP FIXTURE

FIXTURE DETAIL REMARKS

ID. VOLTAGE WATTS TYPE MOUNTING

A LOW PROFILE LED HIGH EFFICACY LUMINAIRE, 2-3/8"D X 24"W X 48"H , WITH SELF-DIAGNOSTIC TESTING

BATTERYPACK OPTION; FIXTURE IS CEILING MOUNTED. INDOOR RATED. MVOLT

DRIVER

120-277V

59W 7,200 LUMEN ARRAY LED, 4000K, 80 CRI,

L80@60,000 HOUR, 123 LPW CEILING MOUNTED CEILING MOUNT, ABOUT 13 FT. AFF. SHALL BE CONTROLLED BY NON-DIMMING LIGHTING CONTROLS, TYPICAL

LIGHT SWITCH.

NOTES:

1. THE LIGHT FIXTURES MUST PROVIDE 3 FC OF LIGHT MEASURED AT FINISHED FLOOR FOR THE FOLLOWING ROOMS: RM113, RM123, RM130, RM144.

2. THE LIGHT FIXTURES MUST PROVIDE 5 FC OF LIGHT MEASURED AT 3 FT. AFF FOR THE FOLLOWING ROOMS: RM102, RM104, RM142, RM143.

3. THE LIGHT FIXTURES MUST PROVIDE 10 FC OF LIGHT MEASURED AT 2.5 FT. AFF FOR THE FOLLOWING ROOMS: RM101, RM110, RM116, RM131.

4. THE LIGHT FIXTURES MUST PROVIDE 10 FC OF LIGHT MEASURED AT 3 FT. AFF FOR THE FOLLOWING ROOMS: RM139.

5. THE LIGHT FIXTURES MUST PROVIDE 10 FC OF LIGHT MEASURED AT FINISHED FLOOR FOR THE FOLLOWING ROOMS: RM119, RM138, RM134.

6. THE LIGHT FIXTURES MUST PROVIDE 15 FC OF LIGHT MEASURED AT 2.5 FT. AFF FOR THE FOLLOWING ROOMS: RM120.

7. THE LIGHT FIXTURES MUST PROVIDE 20 FC OF LIGHT MEASURED AT 3.5 FT. AFF FOR THE FOLLOWING ROOMS: RM103B, RM118, RM135, RM139 MECHANICAL CLOSET.

8. THE LIGHT FIXTURES MUST PROVIDE 30 FC OF LIGHT MEASURED AT 2.5 FT. AFF FOR THE FOLLOWING ROOMS: RM105, RM106, RM107, RM108, RM111, RM112, RM114, RM117, RM122, RM124, RM125, RM128, RM133, RM140, RM141.

9. THE LIGHT FIXTURES MUST PROVIDE 30 FC OF LIGHT MEASURED AT FINISHED FLOOR FOR THE FOLLOWING ROOMS: .

10. THE LIGHT FIXTURES MUST PROVIDE 40 FC OF LIGHT MEASURED AT 2.5 FT. AFF FOR THE FOLLOWING ROOMS: RM115, RM145.

5. THE LIGHT FIXTURES MUST PROVIDE 50 FC OF LIGHT MEASURED AT 2.5 FT. AFF FOR THE FOLLOWING ROOMS: RM129, RM132.

5. THE LIGHT FIXTURES MUST PROVIDE 50 FC OF LIGHT MEASURED AT 3 FT. AFF FOR THE FOLLOWING ROOMS: RM136, RM137.

6. CONTRACTOR SHALL SUBMIT LIGHT CALCULATIONS (IN ACCORDANCE WITH IES LIGHTING HANDBOOK AND UFC 3-535-01) VERIFYING THAT THE SELECTED LIGHT FIXTURES CONFORM WITH THE PROJECT LIGHTING REQUIREMENTS .

B

38W

C HIGH EFFICACY LUMINAIRE, 3.5" D X 5.5" W X 48" H, WITH SELF-DIAGNOSTIC TESTING BATTERY PACK

OPTION; FIXTURE IS CEILING MOUNTED. INDOOR RATED.

11W

D

MVOLT

DRIVER

120-277V 74W

G

MVOLT

DRIVER

120-277V

11W 1,500 LUMEN ARRAY LED, 4000K, 80 CRI,

L90@100,000 HOUR, 136 LPW CEILING MOUNTED

E SURFACE MOUNT OR RECESSED 8" LED DOWN LIGHT LUMINAIRE RATED FOR WET OR DAMP LOCATIONS.

20W

1,600 LUMEN ARRAY LED, 4000K, 80 CRI,

L70@50,000 HOUR, 83 LPW CEILING MOUNTED

F MVOLT

DRIVER

120-277V

31W CEILING MOUNTED

MVOLT

DRIVER

120-277V

CEILING MOUNTED

CEILING MOUNTED

CEILING MOUNTED

H LED EMERGENCY EGRESS EXIT SIGN , WITH INTEGRATED TWIN LED LAMPS. 3W LED WALL MOUNTED WALL MOUNT, ABOUT 8 FT. AFF.

LOW PROFILE LED HIGH EFFICACY LUMINAIRE, 2-3/8"D X 24"W X 48"H , WITH SELF-DIAGNOSTIC TESTING

BATTERYPACK OPTION; FIXTURE IS CEILING MOUNTED. INDOOR RATED.

LOW PROFILE LED HIGH EFFICACY LUMINAIRE, 2-3/8"D X 24"W X 48"H , WITH SELF-DIAGNOSTIC TESTING

BATTERYPACK OPTION; FIXTURE IS CEILING MOUNTED. INDOOR RATED.

LOW PROFILE LED HIGH EFFICACY LUMINAIRE, 2-3/8"D X 24"W X 48"H , WITH SELF-DIAGNOSTIC TESTING

BATTERYPACK OPTION; FIXTURE IS CEILING MOUNTED. INDOOR RATED.

LOW PROFILE LED HIGH EFFICACY LUMINAIRE, 2-3/8"D X 12"W X 48"H , WITH SELF-DIAGNOSTIC TESTING

BATTERYPACK OPTION; FIXTURE IS CEILING MOUNTED. INDOOR RATED.

4,800 LUMEN ARRAY LED, 4000K, 80 CRI,

L80@60,000 HOUR, 126 LPW

8,500 LUMEN ARRAY LED, 4000K, 80 CRI,

L80@60,000 HOUR, 115 LPW

4,000 LUMEN ARRAY LED, 4000K, 80 CRI,

L80@60,000 HOUR, 129 LPW

CEILING MOUNT. SHALL BE CONTROLLED BY NON-DIMMING LIGHTING CONTROLS, TYPICAL LIGHT SWITCH.

CEILING MOUNT. SHALL BE CONTROLLED BY NON-DIMMING LIGHTING CONTROLS, TYPICAL LIGHT SWITCH.

CEILING MOUNT. SHALL BE CONTROLLED BY NON-DIMMING LIGHTING CONTROLS, TYPICAL LIGHT SWITCH.

MVOLT

DRIVER

120-277V

1,500 LUMEN ARRAY LED, 4000K, 80 CRI,

L80@60,000 HOUR, 136 LPW

CEILING MOUNT. SHALL BE CONTROLLED BY NON-DIMMING LIGHTING CONTROLS, TYPICAL LIGHT SWITCH.

SHALL HAVE INTEGRATED OCCUPANCY CONTROLS FOR THE LIGHTS FIXTURES INSTALLED IN THE CORRIDORS

AND RESTROOMS.

CEILING MOUNT. SHALL BE CONTROLLED BY NON-DIMMING LIGHTING CONTROLS, TYPICAL LIGHT SWITCH.

120V

MVOLT

DRIVER

120-277V

LOW PROFILE LED HIGH EFFICACY LUMINAIRE, 2-3/8"D X 24"W X 48"H , WITH SELF-DIAGNOSTIC TESTING

BATTERYPACK OPTION; FIXTURE IS CEILING MOUNTED. INDOOR RATED.AE

BE LOW PROFILE LED HIGH EFFICACY LUMINAIRE, 2-3/8"D X 24"W X 48"H , WITH SELF-DIAGNOSTIC TESTING

BATTERYPACK OPTION; FIXTURE IS CEILING MOUNTED. INDOOR RATED.

CE HIGH EFFICACY LUMINAIRE, 3.5" D X 5.5" W X 48" H, WITH SELF-DIAGNOSTIC TESTING BATTERY PACK

OPTION; FIXTURE IS CEILING MOUNTED. INDOOR RATED.

DE LOW PROFILE LED HIGH EFFICACY LUMINAIRE, 2-3/8"D X 24"W X 48"H , WITH SELF-DIAGNOSTIC TESTING

BATTERYPACK OPTION; FIXTURE IS CEILING MOUNTED. INDOOR RATED.

EE SURFACE MOUNT OR RECESSED 8" LED DOWN LIGHT LUMINAIRE RATED FOR WET OR DAMP LOCATIONS.

FE LOW PROFILE LED HIGH EFFICACY LUMINAIRE, 2-3/8"D X 24"W X 48"H , WITH SELF-DIAGNOSTIC TESTING

BATTERYPACK OPTION; FIXTURE IS CEILING MOUNTED. INDOOR RATED.

GE LOW PROFILE LED HIGH EFFICACY LUMINAIRE, 2-3/8"D X 12"W X 48"H , WITH SELF-DIAGNOSTIC TESTING

BATTERYPACK OPTION; FIXTURE IS CEILING MOUNTED. INDOOR RATED.

CEILING MOUNT. SHALL BE CONTROLLED BY NON-DIMMING LIGHTING CONTROLS, TYPICAL LIGHT SWITCH.

SHALL HAVE INTEGRATED OCCUPANCY CONTROLS FOR THE LIGHTS FIXTURES INSTALLED IN THE CORRIDORS

AND RESTROOMS.

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

F I X

T U

H

E D

U L E

F T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

S C

H E

D U

L E

S

A

A

G R

A M

S

E-603

NOTES:

1. IF ALTERNATE EQUIPMENT IS PROVIDED, CONTRACTOR SHALL REVISE BREAKER AND FEEDER AS REQUIRED TO SUPPORT.

MECHANICAL EQUIPMENT SCHEDULE

TYPE MARK DESCRIPTION AMPERAGE LOAD HP VOLTAGE

NUMBER

OF POLES

CONNECTION

TYPE NOTES

HARDWIRED

HARDWIRED

HARDWIRED

HARDWIRED

HARDWIRED

CIRCUIT

NUMBER

CONDUCTOR

SIZE

C:20,22,24 #10HV HEATING & VENTILATING 6.6 A 1-1/2 HP 208 V 3

SHOWER FAN - 120 V 1F-1

TV FAN - 120 V 1F-2

TER FAN - 120 V 1F-3

UNIT HEATER 1/12 HP 120 V 1UH

0.6 A

0.2 A

0.2 A

2.2 A 264 VA

27 W

27 W

77 W

2378 VA

COMBINATION MOTOR STARTER

COMBINATION MOTOR STARTER

COMBINATION MOTOR STARTER

COMBINATION MOTOR STARTER

COMBINATION MOTOR STARTERA: 32

F: 13

F: 13

A: 34

#12

#12

#12

#10

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

M E

C H

A N

I C

A L

E

Q U

I P

M E

H

E D

U L E

F T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

S C

H E

D U

L E

S

A

A

G R

A M

S

E-604 xx

SHEET NOTES:

1.

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

E X

I S

T I N

G

P

A N

E L

S

C H

E D

U

T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

S C

H E

D U

L E

S

A

A

G R

A M

S

E-605

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

E X

I S

T I N

G

P

A N

E L

S

C H

E D

U

T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

S C

H E

D U

L E

S

A

A

G R

A M

S

E-606

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

N E

W

P

A N

E L

S

C H

E D

U

T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

S C

H E

D U

L E

S

A

A

G R

A M

S

E-607

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

N E

W

P

A N

E L

S

C H

E D

U

T

W

E d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

S C

H E

D U

L E

S

A

A

G R

A M

S

E-608

TELECOMMUNICATION INSTALLATION SHALL COMPLY WITH THE MOST CURRENT VERSION OF THE FOLLOWING STANDARDS:

· TECHNICAL CRITERIA FOR INSTALLATION INFORMATION INFRASTRUCTURE ARCHITECTURE (I3A) FEBRUARY 2010

· UFC 3-580-01 TELECOMMUNICATIONS INTERIOR INFRASTRUCTURE PLANNING AND DESIGN

· UFC 4-021-02 ELECTRONIC SECURITY SYSTEMS

· TIA/EIA-568 COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD SET

· TIA/EIA-569 TELECOMMUNICATIONS PATHWAYS AND SPACES

· TIA/EIA-606-B ADMINISTRATIVE STANDARD FOR TELECOMMUNICATIONS INFRASTRUCTURE

· TIA/EIA-607 GENERIC TELECOMMUNICATIONS BONDING AND GROUNDING (EARTHING) FOR CUSTOMER PREMISES

TELECOMMUNICATION STANDARDS

GENERAL NOTES

T-501

ELEVATION OR SECTION INDICATOR: 1 INDICATES

ELEVATION OR SECTION NUMBER, T-401 INDICATES

DRAWING SHEET WHERE ELEVATION OR SECTION IS

SHOWN.

KEYED NOTE INDICATOR. # INDICATES NOTE NUMBER.

DETAIL INDICATOR: 1 INDICATES DETAIL NUMBER,

T-501 INDICATES DRAWING SHEET WHERE DETAIL IS

SHOWN.

SYMBOL LEGEND

T-401

REVISION 1 INDICATOR. #INDICATES NOTE NUMBER.#

EQUIPMENT INDICATOR

BREAK LINE: TO BREAK PARTS OF DRAWING.

LINE BREAK.

PULL BOX SIZE PER NEC UNO.

CABLE TRAY, SIZE AS INDICATED ON PLANS. WELDED

WIRE TYPE FOR DISTRIBUTION OF CABLING OUTSIDE

AND WITHIN TELECOMMUNICATION ROOMS, UNO.

WIRING METHODS

PB

TELECOMMUNICATIONS

REFERENCE AND LINE SYMBOLS

EF-1

TELECOM OUTLET, 8 PIN, RJ45 TYPE,

VOICE/DATA JACKS MOUNT 18" AFF UNO.

+ DENOTES ABOVE FINISHED FLOOR HEIGHT.

1 DENOTES TYPE 1 OUTLET

2 DENOTES TYPE 2 OUTLET

3 DENOTES TYPE 3 OUTLET

4 DENOTES TYPE 4 OUTLET

W DENOTES WALL MOUNT 54" AFF WITH SINGLE

GANG FACEPLATE.

PBB OR SBB AS INDICATED ON PLANS.

TELECOMMUNICATIONS CABINET, LOCKABLE, WALL

MOUNTED

J TELECOM JUNCTION BOX

C DENOTES CEILING MOUNTED

1. REFER TO DIVISION 26, 27, 28 AND 33 SPECIFICATIONS FOR TELECOMMUNICATION SYSTEM ITEMS.

2. MOUNTING HEIGHTS, UNLESS OTHERWISE NOTED, ARE TO CENTER LINE OF DEVICE.

3. THE CONTRACTOR SHALL DETERMINE THE EXACT ROUTING OF RACEWAYS.

4. THE CONTRACTOR SHALL COORDINATE ALL CONDUIT PENETRATIONS AND PROVIDE FIREPROOFING AND HAZARDOUS AREA

CONDUIT SEALS AS APPLICABLE.

5. THE MAXIMUM PERMANENT HORIZONTAL LINK DISTANCE SHALL BE 295 FEET AND THE MAXIMUM HORIZONTAL CHANNEL (LINK

PLUS WORKSTATION CABLES AND PATCH CORDS) SHALL BE 328 FEET.

6. ALL HORIZONTAL VOICE AND DATA CABLING SHALL BE CAT6 INSTALLED IN A MINIMUM 1 INCH CONDUIT FROM TELECOMM

OUTLET LOCATIONS TO THE CABLE TRAY.

7. CAT6 CABLING SHALL BE TERMINATED ON 8-PIN, 8-CONDUCTOR (RJ-45) CONNECTORS USING PIN/PAR ASSIGNMENTS IN

ACCORDANCE WITH T568B PIN-OUT SEQUENCE.

8. ALL HORIZONTAL AND BACKBONE CABLING SHALL BE PLENUM RATED WITH THE EXCEPTION OF CABLING INSTALLED IN

UNDERGROUND CONDUITS. SEE NOTE 9 FOR CABLES INSTALLED IN UNDERGROUND CONDUITS.

9. PROVIDE CABLE INSTALLED IN UNDERGROUND CONDUITS LISTED FOR USE IN WET LOCATIONS WITH A WATER BLOCKING

COMPOUND. PLENUM RATED CABLE SHALL NOT BE INSTALLED IN ANY UNDERGROUND CONDUIT.

10. PROVIDE PULL CORD IN ALL SPARE DUCTS AND INNER-DUCTS.

11. THE USE OF J-HOOKS SHALL BE LIMITED AND NOT USED IN PLACE OF THE CABLE TRAY SYSTEM. WHEN USED J-HOOKS SHALL

BE CAT 6 RATED AND SPACED AT INTERVALS NOT TO EXCEED 60 INCHES. J-HOOKS SHALL NOT EXCEED 20 CABLES OR 50% FILL, WHICHEVER IS LESS. WHEN J-HOOKS ARE USED TO SPAN FROM CONDUIT STUB UPS TO CABLE TRAY A BONDING BUSHING SHALL BE INSTALLED ON THE CONDUIT STUB UPS AND A MINIMUM #6 AWG GROUND CONDUCTOR SHALL BE INSTALLED FROM THE BONDING BUSHING TO THE CABLE TRAY EFFECTIVELY BONDING THE METALLIC RACEWAYS TOGETHER.

LINEAR DISTANCE FROM CONDUITS TO CABLE TRAY SHALL NOT EXCEED 40 FEET.

12. CABLE TRAY SHALL BE WALL MOUNTED (PREFERABLE) OR TRAPEZE MOUNTED.

13. PROVIDE ACCESS PANELS IN NON LAY-IN CEILINGS SUCH THAT NO POINT IN THE CABLE TRAY SYSTEM IS MORE THAN 20 FEET

FROM AN ACCESS POINT.

14. PROVIDE A MINIMUM OF 12 INCHES OF CLEARANCE ABOVE THE TOP OF CABLE TRAYS AND A MINIMUM OF 3 INCHES

CLEARANCE BELOW CABLE TRAYS.

15. PROVIDE RECTANGULAR, MODULAR, FIRE RATED WALL PENETRATION ASSEMBLIES WHEN PENETRATING WALLS.

16. ENCLOSURES TO BE NEMA 1 UNLESS OTHERWISE NOTED.3R = NEMA 3R, 4X = NEMA 4X, WP = WEATHERPROOF, XP = EXPLOSION PROOF.

17. COMPLY WITH TIA/EIA-569-D ENVIRONMENTAL STANDARDS IN TELECOMMUNICATION SPACES.

18. USE ONLY COPPER CONDUCTORS FOR GROUND CONNECTIONS. THE USE OF ALUMINUM CONDUCTORS IS NOT ALLOWED.

19. LABEL ALL CABLE TERMINATIONS AND BOTH ENDS OF ALL CABLES IN ACCORDANCE WITH THE I3A AND TIA/EIA-606-B-1.

20. PROVIDE AS-BUILT DOCUMENTATION INCLUDING COMPLETE TEST RESULT REPORTS, FLOOR PLANS SHOWING USER

WORKSTATIONS WITH CABLING LABELING, AND BACKBONE CABLE SCHEMATIC AND LABELING IN AN ELECTRONIC FORMAT (PDF) OR OTHER APPROVED FORMAT AND A PRINTED HARDCOPY. TEST RESULTS SHALL BE SUPPLIED ELECTRONICALLY TO THE PROJECT RCDD AND CORPS PROJECT ENGINEER/ARCHITECT IN THE TEST PROGRAM NATIVE FORMAT. LAMINATED

DIAGRAMS SHALL BE INSTALLED ON WALLS OF THE TER AND ALL TR ’S.

21. PROVIDE ALL REQUIRED AMPLIFIERS, MULTIPORT TAPS, SPLITTERS, OUTLETS AND F TYPE CONNECTORS FOR A COMPLETE

AND USABLE CATV SYSTEM.

22. MAINTAIN A MINIMUM OF 6’-8" CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS, ELECTRICAL BOXES AND FITTINGS, SUSPENDED EQUIPMENT, ETC. THROUGHOUT ACCESS ROUTES IN ELECTRICAL ROOMS, TELECOM ROOMS, AND MECHANICAL

ROOMS.

23. THE FOLLOWING SHALL BE PROVIDED AND INSTALLED BY THE GOVERNMENT (GFGI):

· FACILITY DATA EQUIPMENT (SERVERS, ROUTERS, SWITCHES, MODEMS)

· FACILITY TELEPHONE SWITCH EQUIPMENT

· UPS SYSTEMS

· RADIO TRANSMITTING EQUIPMENT AND ASSOCIATED ANTENNA AND WIRING (RACEWAY TO BE PROVIDED BY

CONTRACTOR)

· CCTV AND INTRUSION DETECTION SYSTEM END DEVICES (RADC ’S, MOTION AND INFRARED SENSORS, CAMERAS, MONITORS, ALARMS AND BALANCED MAGNETIC SWITCHES).

· FRONT END EQUIPMENT AND EQUIPMENT RACKS ASSOCIATED WITH CATV/CCTV/SATELITE TV, AND SEPARATE FRONT

END AUDIO EQUIPMENT NOT ASSOCIATED WITH A COMBINED MASS NOTIFICATION AND PAGING SYSTEM

· A/V EQUIPMENT (PROJECTORS, VIDEO CONFERENCE DISPLAYS, MONITORS/TV

’S)24. CONTRACTOR SHALL COORDINATE WITH GOVERNMENT ON GFGI ITEM REQUIREMENTS AND PROVIDE SUITABLE STRUCTURAL SUPPORT, BRACKETS FOR PROJECTORS/VCR’S/TV’S, ALL UTILITY CONNECTIONS AND SPACE WITH REQUIRED CLEARANCES

FOR GFGI ITEMS.

25. ALL WORK AREA TELECOMMUNICATION OUTLETS REQUIRE A QUADRUPLEX ELECTRICAL OUTLET WITHIN 18 INCHES TO SERVE

TELECOMMUNICATIONS LOADS ASSOCIATED WITH THAT OUTLET.

26. THIS IS A STANDARD LEGEND SHEET. NOT ALL SYMBOLS OR ABBREVIATIONS MAY APPEAR ON DRAWINGS.

27. CONSTRUCTION FOR SECURE AREA MATERIALS AND COMPONENTS SHALL COMPLY WITH UFC 4-010-05 AND IC TECH SPECS

FOR ICD/ICS 705. SECURE AREAS ARE REQUIRED TO OBTAIN ACCREDIDATION.

CONDUIT PENETRATION

ABBRV DESCRIPTION

MGB MAIN GROUNDING BUSBAR LOCATED IN

MAIN ELECTRICAL ROOM

MH MANHOLE

MIN MINIMUM

MM MULTI-MODE FIBER OPTIC

MTD MOUNTED

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NIPR NON-CLASSIFIED INTERNET PROTOCOL

ROUTER NETWORK

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED/CONTRACTOR

INSTALLED

OFOI OWNER FURNISHED/OWNER INSTALLED

OH OVERHEAD

OSP OUTSIDE PLANT

PB PUSHBUTTON

PBB PRIMARY BONDING BUSBAR

PET PROTECTED ENTRANCE TERMINALS

PNL PANEL

PTZ PAN-TILT-ZOOM

PVC POLYVINYL CHLORIDE

QTY QUANTITY

QUAD QUADRUPLE RECEPTACLE

RADC REMOTE AREA DATA COLLECTOR

RCDD REGISTERED COMMUNICATIONS

DISTRIBUTION DESIGNER

RGS RIGID GALVANIZED STEEL

RM ROOM

RMC RIGID METAL CONDUIT

RUS RURAL UTILITIES SERVICE

SAS SECURE ACCESS SYSTEM

SBB SECONDARY BONDING BUSBAR

SCH SCHEDULE

SF SQUARE FOOT (FEET)

SIPR SECRET INTERNET PROTOCOL ROUTER

NETWORK

SM SINGLE-MODE FIBER OPTIC

SPEC SPECIFICATION

TBB TELECOMMUNICATIONS BONDING

BACKBONE

TBC TELECOMUNICATIONS BONDING

CONDUCTOR

TELECOM TELECOMMUNICATION

TIA TELECOMMUNICATIONS INDUSTRY

ASSOCIATION

TP TWISTED PAIR

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UCL UNCLASSIFIED

UCLP UNCLASSIFIED PRINTER

UF UNDERFLOOR

UG UNDERGROUND

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTP UNSHIELDED TWISTED PAIR

W/ WITH

W/O WITHOUT

WP WEATHERPROOF

ABBRV DESCRIPTION

110 110 PUNCHDOWN BLOCKS, RACK, OR

WALL MOUNTED AS INDICATED.

ACS ACCESS CONTROL SYSTEM.

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GROUND

ANSI AMERICAN NATIONAL STANDARD

INSTITUTE

AV AUDIO VISUAL

AWG AMERICAN WIRE GAGE

Hz HERTZ

BAS BUILDING AUTOMATION SYSTEM

BBC BACKBONE BONDING CONDUCTOR

BBS BLUE BEACON SYSTEM

BFC BELOW FINISHED CEILING

C CONDUIT

CATV COMMUNITY ANTENNA TELEVISION

(CABLE)

CCTV CLOSED CIRCUIT TELEVISION

CFCI CONTRACTOR FURNISHED/ CONTRACTOR

INSTALLED

CFOI CONTRACTOR FURNISHED/OWNER

INSTALLED

CL CLASSIFIED

CLG CEILING

CLP CLASSIFIED PRINTER

COMM COMMUNICATION

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CP CONTROL PANEL

CU COPPER

CV2 COMPUTER VISION 2

DB DIRECT BURIED

dBA UNIT OF SOUND LEVEL

DDC DIRECT DIGITAL CONTROL

E EXISTING

EA EACH

EIA ELECTRONIC INDUSTRIES ALLIANCE

ELEC ELECTRICAL

EMT ELECTRICAL METALLIC TUBING

ENT ELECTRICAL NONMETALLIC TUBING

EQUIP EQUIPMENT

EXIST EXISTING

FA FIRE ALARM

FMC FLEXIBLE METAL CONDUIT

FO FIBER OPTIC

G, GND GROUND

GE GROUND EQUALIZER

GFGI GOVERNMENT FURNISHED/GOVERNMENT

INSTALLED

GRC GALVANIZED RIGID CONDUIT

HDPE HIGH-DENSITY POLYETHYLENE

I3A INSTALLATION INFORMATION

INFRASTRUCTURE ARCHITECTURE

I/O INPUT/OUTPUT

IAW IN ACCORDANCE WITH

ICIDS INTEGRATED COMMERCIAL INTRUSION

DETECTION SYSTEM

IDS INTRUSION DETECTION SYSTEM

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

JWICS JOINT WORLDWIDE INTELLIGENCE

COMMUNICATIONS SYSTEMS

LOS LINE-OF-SIGHT

LV LOW VOLTAGE

MC METAL CLAD

NOTE: NOT ALL ABBREVIATIONS MAY BE USED.

ABBREVIATIONS

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

E E

T

A L

A S

S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L

E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

W

K B

R x x

F T

W

F

0 1"

A B

B R

E V

I A

T I O

G

E N

D

A

G

N

E R

T

E S

F T

W T d w g

B

T

R Z

A S

K A

R

R

H O

Z S

A M

Z S

A M

E L E

C T

R I C

A L

G E

N E

R A

L

T-001

VESTIBULE

TOILET

MECHANICAL

103A

UTILITY

103B

TOILET

WITNESS

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

INTERVIEW

SUSPECT

PROCESSING

CORRIDOR

VESTIBULE

SUSPECT

INTERVIEW

POLYGRAPH

WAITING

ADMIN

INTELLIGENCE

ANALYSTS

DETACHMENT

SGT

SAC OFFICE

CORRIDOR

ASAC OFFICE

DIGITAL

MEDIA

STORAGE

CORRIDOR

BREAK

ROOM

MEETING

ROOM

VEHICLE

HOLDING

DRUG

SUPPRESSION

TEAM

ELECTRICAL

ROOM

TER

TV

STORAGE

EVIDENCE

CONTROL

EVIDENCE

PROCESSING

EVIDENCE

STORAGE

CORRIDOR

GENERAL

CRIMES

SHOWER

GENERAL

CRIMES

WOMEN'S

TOILET

MEN'S

TOILET

CORRIDOR

CLASSROOM

VESTIBULE

MECHANICAL

106A

106B

106E

106C 106D105H

105G

105A

105B

105C

105D

105E

105F

107C

107B

107A

107E

107D

108C 108A

108B

106A

106A

117A

119B

117C

116A

124C

108E

117D

108G 108H

108I

110C 110D 120C

109B

113B

111A111C 113A

114A

114E

110E

112A

119C

120B

PANEL E

MTR

(DU36 240 861)

AND 200AMP

BRKR

(POD11898)

PANEL B

MDP

PANEL A

PANEL C

(N)

PANEL D

(N)MTS

(N)

PANEL F

C

C C C

C C C C C

C C C C C C

C

C C C

J

J

J

J

J

T

T

T

M

J J

D E

S C

R I P

T I O

N

D E

S I G

N E

D

B

Y

U S

A

R M

Y

C

O R

E

N G

I N

E E

R S

R

D

S

T R

E E

T

A L A

S K

A

D

I S

T R

I C

T

REFERENCE

NUMBER:

SHEET OF

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

J B

E R

A

L A

S

D R

A W

N

B

Y

C H

E C

K E

D

B

Y

S U

B M

I T

T E

D

B

Y

A N

S I

D

S I Z

E

F I L E

I S

S U

E

D

A T

E

S O

L I C

I T

A T

I O

N

N

O

C O

N T

R A

D R

A W

I N

G

A C

T I O

N D

A T

E M

A R

K

US Army Corps

W

A I N

W R

I G

H T

A

L A

S K

A

C

N

O V

A T

E

B

L D

G

35%

F

W

K B

R x x

F T

W

F

0 1"

S I T

E

P

L A

N

F T

W

T d w g

B

T

R Z

A S

K A

R

R

O

Z S

A M

Z S

A M

E L

E C

T R

I C

A L

P L

A N

S

T-101

SHEET NOTES:

SCALE: 1/8" = 1'

TELECOMMUNICATION SITE PLAN

B2

N

INSTALL A NEW 24" (L) X24" (W)X12" (D) SPLICE BOX

FOR THE INCOMING TELECOMMUNICATIONS.

SEE SHEET NOTE 7.

INSTALL THREE NEW 2" RMC CONDUITS.

TWO WILL BE FOR TELECOMMUNICATIONS AND ONE WILL BE FOR CATV COAX

CABLE. THE CONDUIT WILL HAVE A #6 THHN GROUND WIRE CONNECTED TO

THE CONDUIT AND THE TELECOMMUNICATION MAIN GROUND BUSBAR.

INSTALL NEW 6" CABLE TRAY.

TO ROUTE NEW CAT6 CABLES FOR

TELECOMMUNICATION OUTLETS

1. THE TELECOMMUNICATION ROOM WILL HAVE PLYWOOD BACKING, ON ALL OF THE WALLS, THAT WILL BE USED TO MOUNT THE TELECOMMUNICATIONS MAIN

GROUND BUSBAR/PRIMARY BONDING BUSBAR (TMGB/PBB), PROTECTION TERMINAL (ENTRANCE) W/SPLICE CHAMBER, TWO 110 TYPE BLOCK (FOR THE

CROSS CONNECT SYSTEM), AND 10' WIRE MAINTENANCE LOOPS.

2. THE CATV ROOM WILL HAVE A PLYWOOD BACKING, ON ALL OF THE WALLS, THAT WILL BE USED TO SECURE A TMGB/PBB AND A 36" (L) X 24" (W) X 12" (D)

DISTRIBUTION BOX FOR THE CATV SYSTEM.

3. PLYWOOD BACKBOARDS WILL A/C GRADE AND FINISHED WITH TWO COATS OF FIRE-RETARDANT PAINT. THE FIRE-RATED STAMP WILL REMAIN VISIBLE.

4. PANEL F WILL PROVIDE POWER FOR BOTH THE TELECOMMUNICATION ROOM AND THE CATV ROOM.

5. RG-11 COAXIAL CABLE WILL BE PULLED FROM THE CATV ROOM TO THE INCOMING SPLICE BOX.

6. RG-6 COAXIAL CABLE AND SEPARATE CATV D-RINGS OR J-HOOKS WILL BE USED FOR DISTRIBUTING THE CABLE TV TO THE OFFICE ROOMS AND BREAK ROOM.

METAL DIVIDERS WILL BE INSTALLED IN THE CABLE TRAY AND LADDER TO SEPARATE DATA CABLES FROM THE CATV CABLES.

7. A OUTSIDE PLANT 50 PAIR COPPER LINE AND 12 STRAND SINGLE MODE FIBER WILL BE ROUTED THROUGH THE GROUNDED 2" CONDUIT FROM THE SPLICE

BOX TO THE TELECOMMUNICATION ROOM. THE FUSION SPLICING WILL BE THE MEANS FOR SPLICING THE FIBER OPTIC CABLE. A COMPACT 15" (L) X 9" (W)X 5"

(H) SPLICE ENCLOSURE WILL BE INSTALLED WITHIN THE J-BOX. COMPACT MULTI-PAIR SUPER MATE DRY PLUG SPLICING MODULES WILL BE INSTALLED AS

MEANS FOR SPLICING THE COPPER LINES. CASE, TRAY, AND CONSUMABLES REQUIRED TO ACCOMPLISH THE SPLICES ARE TO BE INCLUDED.

8. CAT6, WITH THE TIA/EIA T568A WIRE CONFIGURATION WILL BE USED FOR ALL THE RJ45 TELECOMMUNICATION OUTLETS. ALL WIRE AND OUTLET FACE PLATES

WILL BE REPLACED.

9. EXISTING CONDUIT, CABLE TRAYS, D-RINGS, AND J-HOOKS MAY BE REUSED WHEN INSTALLING CAT6 CABLES AND NEW OUTLET COVERS.

10. ALL TELECOMMUNICATION OUTLETS WILL BE 4 PORT OUTLETS, WITH TWO PORTS ACTIVE AND THE OTHER TWO LEFT OPEN AS SPARES, WITH THE

EXCEPTION OF THE ADMINISTRATIVE ROOM. THE (2) 4 PORT OUTLETS IN THE ADMINISTRATIVE ROOM WILL HAVE (3) CAT6 CABLES AND (3) RJ45 MODULES, WITH THREE PORTS ACTIVE IN EACH OUTLET.

11. 1 INCH EMT WILL BE INSTALLED FOR ALL TELECOMMUNICATION AND CATV OUTLETS WITHIN THIS PROJECT, EXCEPT WHEN EXISTING CONDUIT IS AVAILABLE

TO BE REUSED.

12. INSTALL NEW FACEPLATES ON ALL OF THE TELECOMMUNICATION AND CATV OUTLET.

13. INSTALL (2) NEW COMPLETE 84" BY 19" BY 3.5" FLOOR MOUNTED BLACK DATA RACKS (TYPICAL). A GROUND BASE ISOLATION KIT, FULL LENGTH GROUND

BUSBAR, GROUNDING CABLE, CABLE TRAY TO CABLE LADDER TRANSITION, HORIZONTAL BRACING, SINGLE VERTICAL CABLE MANAGEMENT (FRONT AND

BACK), AND HORIZONTAL CABLE MANAGEMENTS SHALL BE INSTALLED ON THE TELECOMMUNICATION RACKS.

14. (3) 4" X 4" FIRE RATED WALL PENETRATION PATHWAYS SHALL BE INSTALL IN THE WALL AND CONNECT TO THE LADDER TRAY.

REPAIR EXISTING 12" CABLE TRAY, BY

INSTALLING NEW CHANNELED STEEL

STRUT AND CONNECTING THE CABLE

TRAY TO THE…