Attachment 2 - Building 1318 Roofdeck and Wood Arch Waterproofing Final Specifications.pdf
PDF 6 MB Posted
- Attached to
- NUWC Building 1318 Roof Deck & Wood Arch Waterproofing (Naval Station Newport, Rhode Island)
- Solicitation number
- 5999917
About this file
This document is a hazardous materials inspection report for the roof deck and wood arch waterproofing project at Building 1318 on Naval Station Newport in Rhode Island. The report details asbestos, PCB, and RCRA 8 metals testing conducted on materials that may be impacted by the planned renovations. No asbestos was detected in any samples. All samples tested were found to have PCB levels below 50 ppm. RCRA 8 metals testing of coatings on the concrete roof and timber sealant showed results below Rhode Island regulatory thresholds for direct exposure. The report provides recommendations for any additional testing needed and regulatory compliance for removal of identified hazardous materials as part of the roof deck and wood arch waterproofing project.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B1318 ROOFDECK AND
WOOD ARCH WATERPROOFING
NAVAL UNDERSEA WARFARE CENTER
NEWPORT, RI
JULY 2023
NUWC Division Newport Attn: Mr. Stephen Regan 1176 Howell Street Newport, RI 02841
RE: ECM Project # 220435 Naval Station Newport – Pier 2 – Building 1318 Newport, RI Limited Hazardous Materials Inspection Report.
Dear Mr. Regan:
Enclosed are the analytical results, observations, and recommendations associated with the limited hazardous materials inspection performed by Environmental Consulting & Management Inc. (ECM) of the roof and timber array located on Building 1318 at Pier 2 of Naval Station Newport in Newport, Rhode Island.
Methodology and Scope
On July 15th, 2022 a limited asbestos, Poly Chlorinated Biphynel (PCB), and Resource Conservation and Recovery Act Metals (RCRA 8 metals) inspection was conducted by Mr. Andrew Perreault (AI00914) of ECM. During the course of the inspection ECM collected samples of accessible suspect asbestos containing building materials (ACBM); RCRA 8 metal containing paints, coatings and sealers; and PCB caulks, coatings, and sealers that may be impacted during the renovation to the roof and the timber array on Building 1318 at Pier 2. According to the onsite NUWC personnel the renovations to the building consisted of the remove of the gray/silver coating on the concrete roof of building 1318 and the removal of the rubber roofing membrane on the timber array of building 1318.
Samples of the gray/silver coating on the concrete roof and the pitch/sealer on the timber array were collected to be analyzed for Arsenic, Barium, Cadmium, Chromium, Lead, Mercury, Selenium, and Silver (commonly referred to as the RCRA 8 metals). A sample of the pitch/sealer on the timber array was also analyzed for flash point and total petroleum hydrocarbons (TPH). The asbestos portion of this inspection was conducted according to the Environmental Protection Agency (EPA) Asbestos Hazard Emergency Response Act (AHERA) asbestos bulk sampling protocols. Only accessible materials that are anticipated to be impacted by the renovations to building 1318 were surveyed as part of this inspection. No attempt was made to survey this building in it’s entirety.
181 Amaral Street O: 401.438.1360 Riverside, RI 02915 F: 401.438.1316 www.ecmne.com
Asbestos
The survey consisted of collecting accessible suspect ACBM associated with the painted concrete roof and timber array of building 1318. These materials are then sent to a Rhode Island licensed asbestos analytical laboratory to be analyzed for asbestos content utilizing Polarized Light Microscopy (PLM); in accordance with Environmental Protection Agency (EPA) method 600/R-93/116. The materials collected, results, location and quantity of ACBM have been denoted within this report. Please refer to Attachment #1 for the asbestos analytical results. Below is a chart of the samples collected
Table 1: NSN Pier 2 Building 1318 Roof and Timber Array Asbestos Bulk Sample Results
Sample #s
Material Description Material Location Results Quantity
SanAir ID# 22034973
01A-E Gray/Silver Rubberized
Coating / Paint Building 1318 Concrete Roof None Detected NA
02A-B Rubber Membrane Building 1318 Timber Array None Detected NA
03A-B Black Adhesive to Rubber
Memrbane Building 1318 Timber Array None Detected NA
NA – Not Applicable
Asbestos: Recommendations & Summary
Asbestos was not detected in any of the materials collected by ECM as part of this inspection.
Any materials that may be impacted by the renovation activities that were not identified and sampled should be tested prior to being impacted or assumed to be asbestos and removed and disposed of in accordance with all federal, state and local rules and regulations.
Polychlorinated Bi-Phynels (PCBs)
The chart below represents the PCB sample collected from the caulks, coatings, and sealers found on the concrete roof and timber array at Building 1318. Analytical results can be found in Attachment #2 of this report.
Table 2: NSN Pier 2 Building 1318 Roof and Timber Array PCB Bulk Sample Results
Sample
ID
Description Location Compound Result (ug/kg)
Result (ppm)
NETLAB Case # 2G18001
Gray/Silver
Coating on Roof Building 1318 Concrete
Roof All Aroclors ND ND
Black
Sealer/Pitch on Timbers
Building 1318 Timber Array
All Aroclors ND ND
Black Adhesive to Rubber Membrane
Building 1318 Timber Array
All Aroclors ND ND
ND – None Detected
PCB Conclusion:
All samples were found to be less than 50 ppm and is determined to be non-PCB waste in accordance with 40 CFR 761.3.
Only the materials listed in the table above were sampled for PCBs. Any suspect PCB containing materials (such as caulks and glazings) that were not accessible at the time of the inspection or suspect PCB containing materials that were not part of the scope of work should be sampled for PCBs prior to being impacted or assumed to be PCB containing and removed in accordance with all federal, state, and local rules and regulations.
When dealing with PCB waste, site preparation and controls should established and implemented within a work plan prior to removal activities. Removal activities will need to be conducted under a performance-based disposal plan in accordance with 40 CFR 761.62(a). Performance based PCB removal may not require EPA notification.
RCRA 8 Metals Testing
As part of the limited hazmat ECM collected samples of the materials anticipated to be impacted by this project for the RCRA 8 metals. ECM collected a total of threes samples (two samples of the gray/silver coating on the concrete roof and one sample of the black sealer/pitch on the timber array) to be analyzed for arsenic, barium, cadmium, chromium, lead, mercury, selenium, and silver by Rhode Island licensed analytical laboratory by EPA methods 6010C and 7471B. The analytical laboratory report for the RCRA 8 metals can be found in Attachment #3. Below is a table of the samples collected and the results.
Table 3: NSN Pier 2 Building 1318 Roof and Timber Array RCRA 8 Metal Sample Results
Analyte M01A: Gray/Silver
Coating on Concrete Roof (mg/kg)
M01B: Gray/Silver Coating on Concrete
Roof (mg/kg)
M02A: Black Sealer/Pitch on Timbers (mg/kg)
RI DEM Direct Exposure Criteria Industrial/Comm ercial (mg/kg)
SanAir ID# 22034838
Arsenic <2.5 <2.8 <3.1 7.0
Barium 7,000 13,000 10 10,000
Cadmium <1.3 <1.4 <1.6 1,000
Chromium <6.2 <7.0 <7.7 10,000
Lead 12 <7.0 <7.7 500
Selenium <6.2 <7.0 <7.7 10,000
Silver <6.2 <7.0 <7.7 10,000
Mercury <0.27 <0.27 <0.33 610
Samples in bold were greater than RI DEM direct exposure criteria.
Samples in italics were above the detection limit but below the RI DEM direct exposure criteria.
RCRA 8 Metal Conclusion
The samples collected showed detectable concentrations of barium and lead. The levels of lead detected were below the Rhode Island Department of Environmental Management (RIDEM) direct disposal criteria. The level of barrium detected in the gray/silver coating on the concrete roof was greater than the RIDEM direct disposal criteria.
Any work that impacts the gray/silver coating on the concrete roof must comply with the OSHA rules and regulations for barium exposure. Any work that impacts this material should includes engineering controls and work practices that prevent the workers from exceeding the OSHA PEL for barium sulfate (most commonly used in paints and coatings) of 15 milligrams per cubic meter (mg/m3) of air for total dust and 5 mg/m3 of air for respirable dust for an eight hour time weighted average.
ECM recommends performing a barium TCLP test on the waste material generated by scraping the concrete roof or segregating the this waste and dispose of it as barium containing waste.
Lead Specific Conclusion:
The RCRA 8 metals samples collected as part of this inspection showed a lead concentration of 12 ppm (mg/kg) in the gray/silver coating on the concrete roof. No samples were above the HUD lead base paint standard of 5,000 PPM.
OSHA’s lead in construction standard applies to all construction, modification, or repair where workers may be exposed to lead. OSHA's Lead Standard for the Construction Industry, Title 29 Code of Federal Regulations 1926.62, establishes maximum limits of exposure to lead for all workers. The OSHA exposure limits are not determined by the lead concretion of the painted surface but instead uses air sampling to determine the exposure to a worker. The permissible exposure limit (PEL) sets the maximum worker exposure to lead at 50 micrograms per cubic meter (µg/m3) of air averaged over an eight-hour period. The action level (AL), regardless of respirator use, is an airborne concentration of 30 µg/m3 averaged over an eight-hour period. The AL is the level at which an employer must begin specific compliance activities.
Until an exposure assessment is performed, and documentation showing that workers are not exposed above the PEL, OSHA requires that personal protective equipment (PPE) must be utilized.
Prior to disposal, construction waste suspected to contain lead must undergo Toxic Characteristic Leaching Procedure (TCLP) sampling for lead. The Environmental Protection Agency (EPA) specifies that waste containing greater than 5 mg/l of lead be disposed of as lead waste. The material can be sent out with the normal construction debris, however if there is any concern that it could cause a TCLP of the waste container to fail, the paint chip waste could be segregated and disposed of as lead waste.
Additional Analysis
Additional bulk samples were collected from the black sealer/pitch that was present on the timber array on the roof of Building 1318, to determine in there were any additional hazards associated with impacting this material. One sample was collected for flash point and one sample was collected for total petroleum hydrocarbons (TPH). All bulk samples were sent to a Rhode Island license analytical laboratory to be analyzed by methods EPA 101A-Modified (flash point) and EPA 8100-Modified (TPH).
The laboratory analytical report can be found in Attachment #2. Below is a table of the results.
Table 4: NSN Pier 2 Building 1318 Roof and Timber Array Flash Point and TPH Sample Results
Sample Flash Point (Degrees Fahrenheit) Total Petroleum Hydrocarbons (TPH)
(mg/kg)
NETLAB Case #2G18001
Sealer/Pitch on Timber Array
>200 196,000
Conclusions
The flash point of the collected material was found to be greater than 200 degrees Fahrenheit. As such this material is not defined as a combustible liquid or flammable liquid as defined by the OSHA construction standard (1926.155(c)(h)).
The black sealer/pitch on the timber array was found to have a TPH of 196,000 milligrams per kilogram (mg/kg). Waste generated from the cleaning up of this material, either for general clean up or surface preparation, must be disposed of as hazardous waste in accordance with the Resource Conservation and Recovery Act (RCRA). Contractors should refer to 40 CFR Part 261-263 for specific regulations pertaining to hazardous waste classification, generation and transportation.
All waste materials must be removed/reclaimed, recycled/disposed of in a manner appropriate for each material (solvents/oils/petroleum products). Packing and disposal of some items may differ depending on chosen waste facilities requirements. Therefore, coordination should be made with appropriate waste facilities. It should be noted that in some cases failure to recycle a particular hazardous material (ex. select petroleum products) may incur a hazardous material disposal tax.
Recycling and disposal of all hazardous materials should be coordinated with the appropriate waste facility.
l Each hazard shall be treated separately and containerized in the appropriate DOT approved vessel.
l Contractor shall, at a minimum, lab pack materials as necessary to meet DOT transportation requirements.
l Contractor shall supply US DOT-approved shipping containers for all required lab packs and consolidation. All required packing materials shall also be included for the lab packs.
l Contractor shall supply US DOT-approved over pack drums, as needed and required by applicable regulations.
l Contractor shall supply US DOT-approved drum lids with rings and bolts, as needed.
The disposal of these wastes will be to a RCRA licensed facility. A copy of the operating permit of the facility and transportation firm is to be submitted to the property owner or their agent prior to any waste being shipped from the property. Packaging, storage, shipment, and disposal of the materials should be in accordance with all state and federal regulations.
Transportation of wastes:
l All vehicles used for the transportation of hazardous and special waste shall be properly placarded according to USDOT transporting requirements.
l All drums and containers leaving the property shall be appropriately labeled as hazardous waste (when applicable), as well as the quantity and type of waste, USDOT description, emergency phone numbers, name, address, and telephone number of the generator and date on which the drum was filled.
l Contractor shall supply a Uniform Hazardous Waste Manifest (EPA Form 8700-22) or alternate which contains substantially similar information to be signed by the generator, Contractor, transporter, and receiving facility.
Contractor shall provide all Certificates of Reclamation/Destruction for all materials that are transported off the site.
Limitations:
This inspection was limited by scope of work, visibility and accessibility. Components that could affect building operation and endanger the safety of the inspector such as active mechanical or electrical systems were not scrutinized during this inspection unless otherwise noted.
Sampling was performed for a specific scope of work and directed by onsite personnel. Should the scope of work change additional sampling may be required.
This report was prepared under the request of the Naval Undersea Warfare Center. This report should not be represented, reproduced, or disseminated without the written approval of Environmental Consulting and Management or Naval Undersea Warfare Center. No warranties other than those expressed in the contract for this project are expressed or implied.
A hard copy of this report can be provided for your records via mail upon request. If you have any further questions feel free to contact myself at 401-304-6615.
Sincerely, Environmental Consulting & Management, Inc.
Andrew Perreault Project Manager RI Inspector License: AI00914
Attachment 1 Asbestos Bulk Samples
Laboratory Reports
SanAir ID#: 22034973
Project #: 220435 Project Name: NSN Building 1318 Report Date: 7/19/2022
Analysis Report prepared for Environmental Consulting & Management Inc
Dear Andrew Perreault, We at SanAir would like to thank you for the work you recently submitted. The 9 sample(s) were received on Monday, July 18, 2022 via UPS. The final report(s) is enclosed for the following sample(s): 01A, 01B, 01C, 01D, 01E, 02A, 02B, 03A, 03B.
These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.
Sincerely, Sandra Sobrino Asbestos & Materials Laboratory Manager SanAir Technologies Laboratory
Final Report Includes:
- Cover Letter
- Analysis Pages
- Disclaimers and Additional Information
Sample conditions:
- 9 samples in Good condition.
10501 Trade Ct., N. Chesterfield, VA 23236 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
220435Project Number:
P.O. Number:
Project Name: NSN Building 1318
7/15/2022Collected Date:
7/18/2022 10:45:00 AMReceived Date:
7/19/2022 10:44:17 AM
22034973 SanAir ID Number
FINAL REPORT
Environmental Consulting & Management IncName:
Address: 50 Kickemuit Ave
Bristol, RI 02809
401-438-1360Phone:
Analyst: Hogrefe, Sarah
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers 01A / 22034973-001 Paint / Coating / Roof Edge Bldg
Silver Non-Fibrous
Homogeneous
100% Other None Detected
01B / 22034973-002 Paint / Coating / Roof Edge Bldg
Silver Non-Fibrous
Homogeneous
100% Other None Detected
01C / 22034973-003 Paint / Coating / Roof Edge Bldg
Silver Non-Fibrous
Homogeneous
100% Other None Detected
01D / 22034973-004 Paint / Coating / Roof Edge Bldg
Silver Non-Fibrous
Homogeneous
100% Other None Detected
01E / 22034973-005 Paint / Coating / Roof Edge Bldg
Silver Non-Fibrous
Homogeneous
100% Other None Detected
02A / 22034973-006 Membrane / Timbers Bldg 1318
Black Non-Fibrous
Homogeneous
100% Other None Detected
02B / 22034973-007 Membrane / Timbers Bldg 1318
Black Non-Fibrous
Homogeneous
100% Other None Detected
03A / 22034973-008 Adhesive To 02A
Black Non-Fibrous
Homogeneous
100% Other None Detected
03B / 22034973-009 Adhesive To 02B
Black Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 7/19/2022 Date: 7/19/2022
Approved Signatory:
220435Project Number:
P.O. Number:
Project Name: NSN Building 1318
7/15/2022Collected Date:
7/18/2022 10:45:00 AMReceived Date:
7/19/2022 10:44:17 AM
22034973 SanAir ID Number
FINAL REPORT
Environmental Consulting & Management IncName:
Address: 50 Kickemuit Ave
Bristol, RI 02809
401-438-1360Phone:
Disclaimer
This report is the sole property of the client named on the SanAir Technologies Laboratory chain-of-custody (COC). Results in the report are confidential information intended only for the use by the customer listed on the COC. Neither results nor reports will be discussed with or released to any third party without our client's written permission. The final report shall not be reproduced except in full without written approval of the laboratory to assure that parts of the report are not taken out of context. The information provided in this report applies only to the samples submitted and is relevant only for the date, time, and location of sampling. The accuracy of the results is dependent upon the client’s sampling procedure and information provided to the laboratory by the client. SanAir assumes no responsibility for the sampling procedure and will provide evaluation reports based solely on the sample(s) in the condition in which they arrived at the laboratory and information provided by the client on the COC, such as: project number, project name, collection dates, po number, special instructions, samples collected by, sample numbers, sample identifications, sample type, selected analysis type, flow rate, total volume or area, and start stop times that may affect the validity of the results in this report. Samples were received in good condition unless otherwise noted on the report. SanAir assumes no responsibility or liability for the manner in which the results are used or interpreted. This report does not constitute and shall not be used to claim product certification, approval, or endorsement by NVLAP, NIST, or any other U.S. governmental agencies and may not be certified by every local, state, and federal regulatory agencies.
Samples are held for a period of 60 days. Fibers smaller than 5 microns cannot be seen with this method due to scope limitations.
For NY state samples, method EPA 600/M4-82-020 is performed.
NYELAP Disclaimer:
Polarized- light microscopy is not consistently reliable in detecting asbestos in floor covering and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing.
Asbestos Certifications NVLAP lab code 200870-0 City of Philadelphia: ALL-460 PA Department of Environmental Protection Number: 68-05397 California License Number: 2915 Colorado License Number: AL-23143 Connecticut License Number: PH-0105 Massachusetts License Number: AA000222 Maine License Number: LB-0075, LA-0084 New York ELAP lab ID: 11983 Rhode Island License Number: PCM00126, PLM00126, TEM00126 Texas Department of State Health Services License Number: 300440 Commonwealth of Virginia 3333000323 Washington State License Number: C989 West Virginia License Number: LT000616 Vermont License: AL166318 Louisiana Department of Environmental Quality: 212253, Cert 05088
Revision Date: 8/14/2020
Page 1 of 1Page 4 of 5
Attachment 2 PCB, Flash Point, and TPH Laboratory Analysis Report
[TOC_1]Cover Letter[
New England Testing Laboratory, Inc.
(401) 353-3420
REPORT OF ANALYTICAL RESULTS
NETLAB Work Order Number: 2G18001
Client Project: 220405 - NSN
Report Date: 19-July-2022
Richard Warila, Laboratory Director
New England Testing Laboratory, Inc.
59 Greenhill Street
West Warwick, RI 02893 rich.warila@newenglandtesting.com
Dan Simas
Environmental Consulting & Management
81 Amaral Street
Riverside, RI 02915
Prepared for:
NETLAB Case Number: 2G18001
Sample Lab ID Matrix Date Sampled Date Received
Samples Submitted :
The samples listed below were submitted to New England Testing Laboratory on 07/18/22. The group of samples appearing in this report was assigned an internal identification number (case number) for laboratory information management purposes. The client�s designations for the individual samples, along with our case numbers, are used to identify the samples in this report. This report of analytical results pertains only to the sample(s) provided to us by the client which are indicated on the custody record. The case number for this sample submission is 2G18001. Custody records are included in this report.
01: Silver Coating on Roof Solid (Misc)2G18001-01 07/18/202207/15/2022
02: Sealer/Pitch on Timbers Solid (Misc)2G18001-02 07/18/202207/15/2022
03: Adh to Rubber Membrane Solid (Misc)2G18001-03 07/18/202207/15/2022
Request for Analysis
At the client's request, the analyses presented in the following table were performed on the samples submitted.
Analysis Method
01: Silver Coating on Roof (Lab Number: 2G18001-01)
EPA 8082APCBs (Soxhlet)
Analysis Method
02: Sealer/Pitch on Timbers (Lab Number: 2G18001-02)
EPA 1010A-ModFlashpoint
EPA 8082APCBs (Soxhlet)
EPA-8100-modTotal Petroleum Hydrocarbons
Analysis Method
03: Adh to Rubber Membrane (Lab Number: 2G18001-03)
EPA 8082APCBs (Soxhlet)
Method References
Test Methods for Evaluating Solid Waste, Physical/Chemical Methods, SW846, USEPA
Case Narrative
Sample Receipt:
The samples associated with this work order were received in appropriately cooled and preserved containers. The chain of custody was adequately completed and corresponded to the samples submitted.
Exceptions: None
Analysis:
All samples were prepared and analyzed within method specified holding times and according to NETLAB�s documented standard operating procedures. The results for the associated calibration, method blank and laboratory control sample (LCS) were within method specified quality control requirements and allowances. Results for all soil samples, unless otherwise indicated, are reported on a dry weight basis.
PCB 8082: Samples "02: Sealer/Pitch on Timber" and "03: Adh to Rubber Membrane" were reported without surrogate compound "Decachlorobiphenyl (DCBP)" due to chromatogram pattern interference caused by the sample matrix during analysis. These samples were also reported at an elevated detection level due to chromatogram pattern interference caused by the sample matrix during analysis.
Results: General Chemistry
ResultAnalyte
Reporting
Limit Date AnalyzedQual Units
Lab Number: 2G18001-02 (Non-soil solid, as received basis)
Sample: 02: Sealer/Pitch on Timbers
Date Prepared
Flashpoint degrees F 07/19/2207/19/22> 200 70
Results: Polychlorinated Biphenyls (PCBs)
ResultAnalyte
Reporting
Limit Date AnalyzedQual Units
Lab Number: 2G18001-01 (Non-soil solid, as received basis)
Sample: 01: Silver Coating on Roof
Date Prepared
Aroclor-1016 ug/kg 07/19/2207/18/22ND 1250
Aroclor-1221 ug/kg 07/19/2207/18/22ND 1250
Aroclor-1232 ug/kg 07/19/2207/18/22ND 1250
Aroclor-1242 ug/kg 07/19/2207/18/22ND 1250
Aroclor-1248 ug/kg 07/19/2207/18/22ND 1250
Aroclor-1254 ug/kg 07/19/2207/18/22ND 1250
Aroclor-1260 ug/kg 07/19/2207/18/22ND 1250
Aroclor-1262 ug/kg 07/19/2207/18/22ND 1250
Aroclor-1268 ug/kg 07/19/2207/18/22ND 1250
PCBs (Total) ug/kg 07/19/2207/18/22ND 1250
Surrogate(s) Recovery% Limits
2,4,5,6-Tetrachloro-m-xylene (TCMX ) 30-10075.1% 07/19/2207/18/22
Decachlorobiphenyl (DCBP) 30-105101% 07/19/2207/18/22
ResultAnalyte
Reporting
Limit Date AnalyzedQual Units
Lab Number: 2G18001-02 (Non-soil solid, as received basis)
Sample: 02: Sealer/Pitch on Timbers
Date Prepared
Aroclor-1016 ug/kg 07/19/2207/18/22ND 12800
Aroclor-1221 ug/kg 07/19/2207/18/22ND 12800
Aroclor-1232 ug/kg 07/19/2207/18/22ND 12800
Aroclor-1242 ug/kg 07/19/2207/18/22ND 12800
Aroclor-1248 ug/kg 07/19/2207/18/22ND 12800
Aroclor-1254 ug/kg 07/19/2207/18/22ND 12800
Aroclor-1260 ug/kg 07/19/2207/18/22ND 12800
Aroclor-1262 ug/kg 07/19/2207/18/22ND 12800
Aroclor-1268 ug/kg 07/19/2207/18/22ND 12800
PCBs (Total) ug/kg 07/19/2207/18/22ND 12800
Surrogate(s) Recovery% Limits
2,4,5,6-Tetrachloro-m-xylene (TCMX ) 30-10088.4% 07/19/2207/18/22
Decachlorobiphenyl (DCBP) 30-105% 07/19/2207/18/22
ResultAnalyte
Reporting
Limit Date AnalyzedQual Units
Lab Number: 2G18001-03 (Non-soil solid, as received basis)
Sample: 03: Adh to Rubber Membrane
Date Prepared
Aroclor-1016 ug/kg 07/19/2207/18/22ND 3600
Aroclor-1221 ug/kg 07/19/2207/18/22ND 3600
Aroclor-1232 ug/kg 07/19/2207/18/22ND 3600
Aroclor-1242 ug/kg 07/19/2207/18/22ND 3600
Aroclor-1248 ug/kg 07/19/2207/18/22ND 3600
Aroclor-1254 ug/kg 07/19/2207/18/22ND 3600
Aroclor-1260 ug/kg 07/19/2207/18/22ND 3600
Aroclor-1262 ug/kg 07/19/2207/18/22ND 3600
Aroclor-1268 ug/kg 07/19/2207/18/22ND 3600
PCBs (Total) ug/kg 07/19/2207/18/22ND 3600
Surrogate(s) Recovery% Limits
2,4,5,6-Tetrachloro-m-xylene (TCMX ) 30-10053.4% 07/19/2207/18/22
Decachlorobiphenyl (DCBP) 30-105% 07/19/2207/18/22
Results: Total Petroleum Hydrocarbons
ResultAnalyte
Reporting
Limit Date AnalyzedQual Units
Lab Number: 2G18001-02 (Non-soil solid, as received basis)
Sample: 02: Sealer/Pitch on Timbers
Date Prepared
Total Petroleum Hydrocarbons mg/kg 07/19/2207/19/22196000 1440
Surrogate(s) Recovery% Limits
Chlorooctadecane 40-13084.0% 07/19/2207/19/22
Result
Reporting
Limit Units
Spike
Level
Source
Result %REC
%REC
Limits RPD
RPD
LimitQual Analyte
Quality Control
General Chemistry
Batch: B2G0850 - Flashpoint-EPA 1010A-Mod Prepared & Analyzed: 07/19/22 LCS (B2G0850-BS1)
Flashpoint 85 70 80.0 90-110107degrees F
Prepared & Analyzed: 07/19/22 Source: 2G18001-02Duplicate (B2G0850-DUP1)
Flashpoint > 200 70 > 200 20degrees F
Limit Units
Spike
Level
Source
Result %REC
%REC
Limits RPD
RPD
LimitQual Analyte
Quality Control (Continued)
Polychlorinated Biphenyls (PCBs)
Batch: B2G0745 - EPA 3540C Prepared: 07/18/22 Analyzed: 07/19/22 Blank (B2G0745-BLK1)
Aroclor-1016 ND 200 ug/kg
Aroclor-1221 ND 200 ug/kg
Aroclor-1232 ND 200 ug/kg
Aroclor-1242 ND 200 ug/kg
Aroclor-1248 ND 200 ug/kg
Aroclor-1254 ND 200 ug/kg
Aroclor-1260 ND 200 ug/kg
Aroclor-1262 ND 200 ug/kg
Aroclor-1268 ND 200 ug/kg
PCBs (Total) ND 200 ug/kg
80.0 30-100Surrogate: 2,4,5,6-Tetrachloro-m-xylene
(TCMX )
81.965.5 ug/kg
80.0 30-105Surrogate: Decachlorobiphenyl (DCBP) 87.169.7 ug/kg
Prepared: 07/18/22 Analyzed: 07/19/22 LCS (B2G0745-BS1)
Aroclor-1016 758 200 1000 64-11275.8ug/kg
Aroclor-1260 834 200 1000 59.4-12483.4ug/kg
80.0 30-100Surrogate: 2,4,5,6-Tetrachloro-m-xylene
(TCMX )
74.959.9 ug/kg
80.0 30-105Surrogate: Decachlorobiphenyl (DCBP) 90.472.3 ug/kg
Prepared: 07/18/22 Analyzed: 07/19/22 LCS Dup (B2G0745-BSD1)
Aroclor-1016 735 200 1000 2064-11273.5 3.16ug/kg
Aroclor-1260 796 200 1000 2059.4-12479.6 4.69ug/kg
80.0 30-100Surrogate: 2,4,5,6-Tetrachloro-m-xylene
(TCMX )
82.465.9 ug/kg
80.0 30-105Surrogate: Decachlorobiphenyl (DCBP) 98.879.1 ug/kg
Limit Units
Spike
Level
Source
Result %REC
%REC
Limits RPD
RPD
LimitQual Analyte
Quality Control (Continued)
Total Petroleum Hydrocarbons
Batch: B2G0775 - EPA 3550C Prepared & Analyzed: 07/19/22 Blank (B2G0775-BLK1)
Total Petroleum Hydrocarbons ND 27 mg/kg
8.33 40-130Surrogate: Chlorooctadecane 92.27.69 mg/kg
Prepared & Analyzed: 07/19/22 LCS (B2G0775-BS1)
Total Petroleum Hydrocarbons 525 27 667 40-13078.8mg/kg
8.33 40-130Surrogate: Chlorooctadecane 95.77.98 mg/kg
Prepared & Analyzed: 07/19/22 LCS Dup (B2G0775-BSD1)
Total Petroleum Hydrocarbons 543 27 667 20040-13081.5 3.40mg/kg
8.33 40-130Surrogate: Chlorooctadecane 1038.60 mg/kg
Notes and Definitions
Item Definition
Wet Sample results reported on a wet weight basis.
ND Analyte NOT DETECTED at or above the reporting limit.
[TOC_1]Qualifiers and
Definitions[TOC]
Attachment 3 RCRA 8 Metals
Laboratory Reports
SanAir Technologies LaboratorySanAir Technologies Laboratory
Analysis Report prepared for
Environmental Consulting & Management Inc
Report Date: 7/20/2022 Project Name: NSN Building 1318 Project #: 220435 SanAir ID#: 22034838
804.897.1177 www.sanair.com804.897.1177 www.sanair.com
SanAir Technologies Laboratory, Inc.
10501 Trade Ct., N. Chesterfield, VA 23236
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
Environmental Consulting & Management Inc 50 Kickemuit Ave Bristol, RI 02809
July 20, 2022
SanAir ID # 22034838 Project Name: NSN Building 1318 Project Number: 220435
Dear Andrew Perreault, We at SanAir would like to thank you for the work you recently submitted. The 3 sample(s) were received on Monday, July 18, 2022 via UPS. The final report(s) is enclosed for the following sample (s): M01A, M01B, M02A.
These results only pertain to this job and should not be used in the interpretation of any other job.
This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.
Sincerely, Abisola Kasali Metals Laboratory Director SanAir Technologies Laboratory
Final Report Includes:
- Cover Letter
- Analysis Pages
- Disclaimers and Additional Information
Sample Conditions:
3 sample(s) in Good condition
Analysis Report
Client:
Project/Test Address:
San Air Technologies
7469 Whitepine Rd
Telephone: 800.347.4010
Richmond, VA 23237
Environmental Hazards Services, L.L.C.
22034838
Client Number:
201219
Fax Number:
Laboratory Results
Analyzed Date:
Client Sample Number
Lab Sample Number
Analyte: Concentration ppm (mg/kg)
RCRA8 Metals
07/19/2022
07/19/2022
22-07-02757
Reported Date:
Received Date:
Report Number:
10501 Trade Court Richmond, VA 23236
Narrative ID
Paint
Arsenic (As) <2.5M01A 07/19/202222-07-02757-001
Barium (Ba) 7000
Cadmium (Cd) <1.3
Chromium (Cr) <6.2
Lead (Pb) 12
Selenium (Se) <6.2
Silver (Ag) <6.2
Mercury (Hg) <0.27
Arsenic (As) <2.8M01B 07/19/202222-07-02757-002
Barium (Ba) 13000
Cadmium (Cd) <1.4
Chromium (Cr) <7.0
Lead (Pb) <7.0
Selenium (Se) <7.0
Silver (Ag) <7.0
Mercury (Hg) <0.27
Arsenic (As) <3.1M02A 07/19/202222-07-02757-003
Page 2of1
Barium (Ba) 10
Cadmium (Cd) <1.6
Chromium (Cr) <7.7
Lead (Pb) <7.7
Selenium (Se) <7.7
Silver (Ag) <7.7
Mercury (Hg) <0.33
Tasha Eaddy
QA/QC Clerk
Analyst: Anthony Dee
Method:
Sample Results denoted with a “less than” (<) sign contains less than the reporting limit for each particular metal, based on a 50mL volume.
The reporting limit is 0.10 ug for Mercury, 0.5ug for Cadmium and Beryllium, 1ug for Arsenic and Thallium and 2.5ug for all other metals. To convert metals concentration (ppm) to % by weight, divide the above concentration by 10,000.
LEGEND ug = microgram ppm = parts per million mL = milliliter mg/kg = milligrams per kilogram
Reviewed By Authorized Signatory:
Mercury (Hg): EPA SW846 7471B
All other metals: EPA SW846 3050B/6010D
The condition of the samples analyzed was acceptable upon receipt per laboratory protocol unless otherwise noted on this report. Results represent the analysis of samples submitted by the client. Unless otherwise noted, samples are reported without a dry weight correction.
Sample location, description, area, volume, etc., was provided by the client. If the report does not contain the result for a field blank, it is due to the fact that the client did not include a field blank with their samples. These sample results do not reflect blank correction. This report shall not be reproduced except in full, without the written consent of Environmental Hazards Services, L.L.C. NY ELAP #11714.
Report Number:
Environmental Hazards Services, L.L.C
Project/Test Address:
Client Number: 22-07-02757
22034838
201219
Analyzed Date:
Client Sample Number
Lab Sample Number
Concentration ppm (mg/kg)
Narrative IDAnalyte:
Page 2of2
(401) 353-3420
REPORT OF ANALYTICAL RESULTS
NETLAB Work Order Number: 3F07011
Client Project: NUWCDIVNPT
Report Date: 16-June-2023
Richard Warila, Laboratory Director
New England Testing Laboratory, Inc.
59 Greenhill Street
West Warwick, RI 02893 rich.warila@newenglandtesting.com
Stacie Paquette
NUWC Newport
1176 Howell Street
Newport, RI 02841
Work Order: 3F07011
Date: 6/16/2023 10:24:30AM
Samples Submitted:
Sample Lab ID Matrix Date Sampled
The samples listed below were submitted to New England Testing Laboratory on
06/07/23. The group of samples appearing in this report was assigned an internal identification number (case number) for laboratory information management purposes.
The client�s designations for the individual samples, along with our case numbers, are used to identify the samples in this report. This report of analytical results pertains only to the sample(s) provided to us by the client which are indicated on the custody record.
The case number for this sample submission is 3F07011. Custody records are included in this report.
3F07011-01 06/06/2023Solid (Misc)B1318 Roof Deck Surface Material
Request for Analysis
At the client's request, the analyses presented in the following table were performed on the samples submitted.
B1318 Roof Deck Surface Material
EPA 6010CTCLP Barium
The analytical methods provided are documented in the following references:
Manual of Methods for Chemical Analysis of Water and Water Wastes, EPA-600/4-79-020 (Revised
1983), USEPA/EMSL.
Standard Methods for the Examination of Water and Wastewater , 20th Edition, 1998, APHA, AWWA-WPCF.
40 CFR 136, Guidelines Establishing Test Procedures for the Analysis of Pollutants Under the Clean
Water Act, Office of Federal Register National Archives and Records Administration.
Results:
3F07011-01 (Solid (Misc))
Sample: B1318 Roof Deck Surface Material
TCLP Metals
Result Date
Analyzed
UnitsReporting
Limit
0.025Barium mg/L2.85 06/13/23
The samples were all appropriately cooled and preserved upon receipt. The samples were received in the appropriate containers. The chain of custody was adequately completed and corresponded to the samples submitted.
All samples were analyzed in accordance with 40 CFR 136 approved methodologies when applicable.
Result
Reporting
Limit Units
Spike
Level
Source
Result %REC
%REC
Limits RPD
RPD
LimitQual Analyte
Quality Control
TCLP Metals
Batch: B3F0429 - Metals Digestion Waters Date Analyzed: 06/13/23 LCS (B3F0429-BS1)
Barium 0.939 0.005 1.00 85-11593.9mg/L
(401) 353-3420
REPORT OF ANALYTICAL RESULTS
NETLAB Work Order Number: 3F21007
Client Project: NUWCDIVNPT
Report Date: 29-June-2023
Richard Warila, Laboratory Director
New England Testing Laboratory, Inc.
59 Greenhill Street
West Warwick, RI 02893 rich.warila@newenglandtesting.com
Stacie Paquette
NUWC Newport
1176 Howell Street
Newport, RI 02841
Work Order: 3F21007
Date: 6/29/2023 9:54:54AM
Samples Submitted:
Sample Lab ID Matrix Date Sampled
The samples listed below were submitted to New England Testing Laboratory on
06/21/23. The group of samples appearing in this report was assigned an internal identification number (case number) for laboratory information management purposes.
The client�s designations for the individual samples, along with our case numbers, are used to identify the samples in this report. This report of analytical results pertains only to the sample(s) provided to us by the client which are indicated on the custody record.
The case number for this sample submission is 3F21007. Custody records are included in this report.
3F21007-01 06/21/2023Solid (Misc)Sample 1 Southeast gray/blue tar material
3F21007-02 06/20/2023Solid (Misc)Sample 2 Southwest gray/blue tar material
Request for Analysis
At the client's request, the analyses presented in the following table were performed on the samples submitted.
Sample 1 Southeast gray/blue tar material
EPA 6010CTCLP Barium
EPA 6010CBarium
Sample 2 Southwest gray/blue tar material
EPA 6010CTCLP Barium
EPA 6010CBarium
The analytical methods provided are documented in the following references:
Manual of Methods for Chemical Analysis of Water and Water Wastes, EPA-600/4-79-020 (Revised
1983), USEPA/EMSL.
Standard Methods for the Examination of Water and Wastewater , 20th Edition, 1998, APHA, AWWA-WPCF.
40 CFR 136, Guidelines Establishing Test Procedures for the Analysis of Pollutants Under the Clean
Water Act, Office of Federal Register National Archives and Records Administration.
Results:
3F21007-01 (Solid (Misc))
Sample: Sample 1 Southeast gray/blue tar material
Total Metals
Result Date
Analyzed
UnitsReporting
Limit
0.34Barium mg/kg7440 06/28/23
TCLP Metals
Result Date
Analyzed
UnitsReporting
Limit
0.025Barium mg/L2.90 06/26/23
3F21007-02 (Solid (Misc))
Sample: Sample 2 Southwest gray/blue tar material
Total Metals
Result Date
Analyzed
UnitsReporting
Limit
0.39Barium mg/kg9430 06/28/23
TCLP Metals
Result Date
Analyzed
UnitsReporting
Limit
0.025Barium mg/L2.33 06/26/23
The samples were all appropriately cooled and preserved upon receipt. The samples were received in the appropriate containers. The chain of custody was adequately completed and corresponded to the samples submitted.
All samples were analyzed in accordance with 40 CFR 136 approved methodologies when applicable.
Result
Reporting
Limit Units
Spike
Level
Source
Result %REC
%REC
Limits RPD
RPD
LimitQual Analyte
Quality Control
Total Metals
Batch: B3F1024 - Metals Digestion Soils Date Analyzed: 06/28/23 Blank (B3F1024-BLK1)
Barium ND 0.33 mg/kg
Date Analyzed: 06/28/23 LCS (B3F1024-BS1)
Barium 87.5 0.33 100 85-11587.5mg/kg
Result
Reporting
Limit Units
Spike
Level
Source
Result %REC
%REC
Limits RPD
RPD
LimitQual Analyte
Quality Control (Continued)
TCLP Metals
Batch: B3F1071 - Metals Digestion Waters Date Analyzed: 06/26/23 LCS (B3F1071-BS1)
Barium 5.63 0.025 5.00 85-115113mg/L
Date Analyzed: 06/26/23 LCS Dup (B3F1071-BSD1)
Barium 5.30 0.025 5.00 2085-115106 5.91mg/L
Date Analyzed: 06/26/23 Leach Fluid Blank (B3F1071-LBK1)
Barium ND 0.025 mg/L
B1318 ROOFDECK AND WOOD ARCH WATERPROOFING B1318ARCH
PROJECT TABLE OF CONTENTS
DI VI SI ON 01 - GENERAL REQUI REMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRICTIONS
01 20 00 PRICE AND PAYMENT PROCEDURES
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 31 23.13 20 ELECTRONIC CONSTRUCTION AND FACILITY SUPPORT CONTRACT
MANAGEMENT SYSTEM
01 32 16.00 20 SMALL PROJECT CONSTRUCTION PROGRESS SCHEDULES
01 33 00 SUBMITTAL PROCEDURES
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.10 20 QUALITY CONTROL FOR MINOR CONSTRUCTION
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS
01 78 00 CLOSEOUT SUBMITTALS
DI VI SI ON 09 - FI NI SHES
09 90 00 PAINTS AND COATINGS
09 96 00 HIGH-PERFORMANCE COATINGS
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 1
SECTION TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
SECTION 01 11 00
SUMMARY OF WORK
08/ 15, CHG 2: 08/ 21
PART 1 GENERAL
1.1 WORK COVERED BY CONTRACT DOCUMENTS
1.1.1 Project Description
1.1.2 Location
1.2 OCCUPANCY OF PREMISES
1.3 EXISTING WORK
PART 2 PRODUCTS
PART 3 EXECUTION
-- End of Section Table of Contents --
SECTION 01 11 00 Page 1
SECTION 01 11 00
SUMMARY OF WORK
08/ 15, CHG 2: 08/ 21
PART 1 GENERAL
1.1 WORK COVERED BY CONTRACT DOCUMENTS
1.1.1 Project Description
The work shall consist of existing concrete rooftop coating removal, concrete rooftop substrate preparation and repair, and the furnishing and application of a spray applied, 100% solids, fast cure, high build polymer system that prevents the passage of water and complies with the physical property requirements specified herein, along with incidental related work. Compliance shall be demonstrated by third party testing meeting the requirements of this specification. The waterproofing system (excluding primer) shall have a minimum finished nominal thickness of 132 mils.Additionally, the three (3) laminated wood arches shall be cleaned with a wood cleaner and stained with a penetrating semi-transparent, premium modified oil formula wood stain, all in accordance with the plans and these specifications.
1.1.2 Location
The work is located at the Naval Undersea Warfare Center, Pier 2, Building 1318, approximately as indicated. The exact location will be shown by the Contracting Officer.
1.2 OCCUPANCY OF PREMISES
Building will be occupied during performance of work under this Contract.
Before work is started, arrange with the Contracting Officer a sequence of procedure, means of access, space for storage of materials and equipment, and use of approaches, corridors, and stairways.
1.3 EXISTING WORK
In addition to FAR 52.236-9 Protection of Existing Vegetation, Structures, Equipment, Utilities, and Improvements:
a. Remove or alter existing work in such a manner as to prevent injury or damage to any portions of the existing work which remain.
b. Repair or replace portions of existing work which have been altered during construction operations to match existing or adjoining work, as approved by the Contracting Officer. At the completion of operations, existing work must be in a condition equal to or better than that which existed before new work started.
SECTION 01 11 00 Page 2
PART 2 PRODUCTS
Not used.
PART 3 EXECUTION
Not used.
-- End of Section --
SECTION 01 11 00 Page 3
DIVISION 01 - GENERAL REQUIREMENTS
SECTION 01 14 00
WORK RESTRICTIONS
11/ 11, CHG 13: 08/ 21
PART 1 GENERAL
1.1 SUBMITTALS
1.2 SPECIAL SCHEDULING REQUIREMENTS
1.3 CONTRACTOR ACCESS AND USE OF PREMISES
1.3.1 Activity Regulations
1.3.1.1 Subcontractors and Personnel Contacts
1.3.1.2 Installation Access
1.3.1.2.1 DBIDS Eligibility Requirements
1.3.1.2.2 DBIDS Notification Requirements
1.3.1.2.3 One-Day Passes
1.3.1.2.4 Activity Regulations
1.3.1.3 No Smoking Policy
1.3.2 Working Hours
1.3.3 Work Outside Regular Hours
PART 2 PRODUCTS
PART 3 EXECUTION
SECTION 01 14 00 Page 1
SECTION 01 14 00
WORK RESTRICTIONS
11/ 11, CHG 13: 08/ 21
PART 1 GENERAL
1.1 SUBMITTALS
Government approval is required for submittals with a "G" classification.
Submittals not having a "G" for information only. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
List of Contact Personnel
1.2 SPECIAL SCHEDULING REQUIREMENTS
a. Have materials, equipment, and personnel required to perform the work at the site prior to the commencement of the work.
b. The building will remain occupied and in operation during the entire construction period. The Contractor must conduct his operations so as to cause the least possible interference with normal operations of the activity.
c. Permission to interrupt any Activity utility service must be requested in writing a minimum of 15 calendar days prior to the desired date of interruption. Schedule after hours building outages for demolition and installation of lighting and electrical devices.
1.3 CONTRACTOR ACCESS AND USE OF PREMISES
1.3.1 Activity Regulations
Ensure that Contractor personnel employed on the Activity become familiar with and obey Activity regulations including safety, fire, traffic and security regulations. Keep within the limits of the work and avenues of ingress and egress. Wear appropriate personal protective equipment (PPE) in designated areas. Do not enter any restricted areas unless required to do so and until cleared for such entry. Ensure all Contractor equipment, include delivery vehicles, are clearly identified with their company name.
1.3.1.1 Subcontractors and Personnel Contacts
Provide a list of contact personnel of the Contractor and subcontractors including addresses and telephone numbers for use in the event of an emergency. As changes occur and additional information becomes available, correct and change the information contained in previous lists.
1.3.1.2 Installation Access
Application for and use of badges will be as directed. Contractor shall be solely responsible for submitting all badging requests in a timely fashion throughout the duration of this contract. Monitor expiration dates and resubmit timely to prevent badge expiration and access denial.
SECTION 01 14 00 Page 2
Identification badges for the Contractor, his employees and subcontractors shall be furnished by the NUWC Security Division. Identification badges will be furnished without charge and are required to be worn and visible at all times while at NUWCDIVNPT. Immediately report instances of lost or stolen badges to the Security Division. Upon completion of the contract, or termination of the service of any employee, the Contractor shall return all badges to NUWC building 80. Compliance with this requirement is mandatory and failure to return badges will hold up the Contractor's final payment.
All deliveries and commercial vehicles must enter NAVSTANPT gate 17 for inspection before proceeding to the job site. The contractor shall fax a NUWC Visit Request for all personnel to be engaged in the work (including delivery drivers) to the NUWC Security Division and obtain necessary identification badges before access to the jobsite will be granted. The Security Division will either approve or disapprove the individuals on the request based on current security regulations. Foreign Nationals will not be allowed access under any circumstance. Failure to obtain an approved visit request will not affect the contract price or time of completion.
A NUWC visit request is mandatory for all visitors. Due to the number of visit requests received, a minimum of seven (7) working days processing time is required after submission of a completed visit request whether received by FAX, e-mail or JPAS. All incomplete visit requests will be denied. For questions regarding the NUWCDIVNPT visit request process, phone (401) 832-2252, or visit NUWCDIVNPT Visitor Control at building 80 located outside gate 23. Proper picture identification is required for station access; ID's that state "Not for federal use" will not be accepted and a US passport, Real ID or other acceptable picture ID will be required. Possession of a NUWC visit request alone will only grant escorted access to the station at all times. Escorting of individuals by the government will only be performed in emergency situations as determined by the government.
In addition to a NUWCDIVNPT visit request, possession of a Defense Biometrics Identification System (DBIDS) card is required for "unescorted grounds only" access. In order to be vetted for a DBIDS card, each visitor must complete and submit SECNAV form 5512-1. All SECNAV 5512-1 forms are to be included with the NUWCDIVNPT visit request submission.
Incomplete and incorrectly filled out forms will be returned and not processed. DBIDS cards are issued at the Naval Station Newport Pass & ID office located outside gate 1. Expect a minimum fifteen (15) business day waiting period for DBIDS vetting and availability of the DBIDS card after submission of the NUWCDIVNPT visit request. A NUWC badge in combination with a DBIDS card will grant unescorted access to NUWC grounds only. All individuals must be escorted while inside any NUWC building. For questions regarding the DBIDS card, contact NAVSTANPT Visitor Control at
(401) 841-3126.
1.3.1.2.1 DBIDS Eligibility Requirements
Throughout the length of the contract, the Contractor employee must continue to meet background screening standards. Periodic background screenings are conducted to verify continued DBIDS participation and installation access privileges. DBIDS access privileges will be immediately suspended or revoked if at any time a Contractor employee becomes ineligible.
SECTION 01 14 00 Page 3
An adjudication process may be initiated when a background screen failure results in disqualification from participation in the DBIDS, and Contractor employee does not agree with the reason for disqualification.
The Government is the final authority.
1.3.1.2.2 DBIDS Notification Requirements
a. Immediately report instances of lost or stolen badges to the Contracting Officer.
b. Immediately collect DBIDS credentials and notify the Contracting Officer in writing under the following circumstances:
(1) An employee has departed the company without having properly returned or surrendered their DBIDS credentials.
(2) There is a reasonable basis to conclude that an employee, or former employee, might pose a risk, compromise, or threat to the safety or security of the Installation or anyone therein.
1.3.1.2.3 One-Day Passes
Personnel applying for One-Day passes at the Base Visitor Control Office are subject to daily mandatory vehicle inspection, and will have limited access to the installation. The Government is not responsible for any cost or lost time associated with obtaining daily passes or added vehicle inspections incurred by non-participants in the DBIDS.
1.3.1.2.4 Activity Regulations
Ensure that Contractor personnel employed on the Activity become familiar with and obey Activity regulations including safety, fire, traffic and security regulations. Keep within the limits of the work and avenues of ingress and egress. Wear hard hats in designated areas. Do not enter any restricted areas unless required to do so and until cleared for such entry. Mark Contractor equipment for identification.
Contractor owned computers may be used for construction with government approval. Submit application for Non-NUWCDIVNPT Owned Computer Equipment for approval before bringing computers on government property. Computers shall be Standalone Only - No 802.11 Wireless - No web cameras, external or built-in. Full Disk Encryption required for processing and storing of FOUO/CUI government data and information.
The use of cell phones for photographic purposes is strictly forbidden.
Any cell phone used for photographic purposes will result in confiscation of the cell phone and may result in loss of station access for the user.
Digital cameras may be used for photographic purposes with prior approval. Submit a NUWC Division Newport Photography Permit Request form in advance of bringing digital cameras onto government property.
1.3.1.3 No Smoking Policy
Smoking is prohibited within and outside of all buildings on installation, except in designated smoking areas.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .