31 MAY 2022/ Rev 02

V6-CONS-1/14/22 Page 1 of 1

SOW APPENDIX A

GOVERNMENT FURNISHED AHU-1N and AHU-2S MFR SUBMITTAL

EQUIPMENT SUBMITTAL FOR APPROVAL

PROJECT: Keesler AFB AHUs

York Solution Indoor Air Handling Unit

EQUIPMENT Solution XTI

UNIT TAGS AHU-2; AHU-1

QUANTITY 2

SOLD TO:

PREPARED BY:

DATE:

Wednesday, May 25, 2022

REVISION:

TABLE OF CONTENTS

(Solution XTI)

BOM Data

Performance Report

Fan Curves

Unit And Wiring Drawings

Warranties

Submittal Approval Page

Project: Keesler AFB AHUs 1 Submittal Bid: A

Bill Of Material (BOM) Data Section

Product Type: Solution XTI

Unit Tags: AHU-2; AHU-1

BILL OF MATERIAL DATA

EQUIPMENT Solution XTI

UNIT TAGS AHU-2; AHU-1

QTY 2

Items Included Unit Options:

o Standard Warranty is 18 months parts and labor from date of shipment or 12 months from startup, whichever occurs first.

LED Light will be provided in Supply Fan segments, all wired to a single switch located on the supply fan segment.

Supply Fan Segment o STD Ga. G-90 Galvanized Interior Liner, STD Ga. G-90 Galvanized Floor Liner o Single DDPG2 Fan o Left Outward Swing Access Door provided (AHU-2) o Right Outward Swing Access Door provided (AHU-1) o 460 Volt ODP Premium Efficiency Motor o Factory Mounted ABB VFD Fused in NEMA 1 Enclosure

Mixing Box Segment o Left Outward Swing Access Door provided (AHU-2) o Right Outward Swing Access Door provided (AHU-1) o Dampers

Cooling Coil Segment o Left Outward Swing Access Door provided (AHU-2) o Right Outward Swing Access Door provided (AHU-1) o IAQ Drain Pan with Stainless Steel Liner and No additional length

Flat Filter Segment o Left Outward Swing Access Door provided (AHU-2) o Right Outward Swing Access Door provided (AHU-1)

Items NOT Included Humidifier Segment has not been selected.

Unit Startup is not included.

Hauling/Rigging of Equipment is not included.

Performance Ratings Section

YORK® Solution™ Air Handling Unit Performance Report

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:50:01 AM Unit Folder:AHU-2 Report Version: 2022.1.4.743 Unit Tag(s): AHU-2 Software Version: 21.4.6395.9682

Job Summary

Project Name: Keesler AFB AHUs Unit Tag(s): AHU-2 Quantity: 1 Environment: Indoor

Unit Overview

Model Airflow (CFM) Altitude (ft) Operating Weight (lbs) XTI-75x81 16,035 10 3,912

Segment Sequence

(FS CC FF MB)

Unit Construction

Casing Details

Segment(s) Thickness (in) Exterior Paint Exterior Gauge and Material

Interior Gauge and Material

Insulation Thickness and

Material

Bulkhead Material

MB , FF , CC , FS 2 None STD Ga. G-90 Galvanized

STD Ga. G-90 Galvanized 2" Foam Galvanized

Base Details

Segment(s) Base Floor

Material Paint Gauge and Material Paint Insulation Attachment Tread

Plate

MB , FF , CC , FS Standard Formed Steel None STD Ga. G-90

Galvanized None N/A - None

Unit Electrical

Circuit Details Circuit # Component(s) V/Ph/Hz Full Load Amps (FLA) Minimum Current

Ampacity (MCA) Maximum Overcurrent

Protection (MOP) 1 Supply Fan Motor Control 460/3/60 24.0 30.0 50.0 2 Lights and Outlets 120/1/60 - - 15.0

Electrical Details Minimum Unit SCCR 5 kA rms Symmetrical ETL Label (UL1995/NEC-2002) Yes

Unit Light Type Unit Light Switch Standard LED External

Supply Fan(s)

Performance Details Fan

Manufacturer Model Class Size % Wheel Width

% Wheel Diameter Quantity Total Airflow

(CFM) Altitude (ft) TSP (in w.g)

ESP

(in w.g)

Fan Speed

(RPM)

Fan Power

(BHP)

Lau DDPG2 II 270-9 100 100 1 16,035 10 4.96 2.50 1,955 19.93

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:50:01 AM Unit Folder:AHU-2 Report Version: 2022.1.4.743 Unit Tag(s): AHU-2 Software Version: 21.4.6395.9682

Drive Type Wheel Type Blade Type Wheel Material Base Material Fan Flow

Isolation Isolation

Type Total

Eficiency (%) Outlet

Velocity (ft/s) Max Speed

(RPM) FEP (kW)

Direct Drive SWSI Airfoil Aluminum Galvanized Steel None 2" Spring 62.71 1,551 2,035 16.50 Motor Details

Type Manufacturer Motor Power (HP) V/Ph/Hz Quantity Insulation Class

Motor Speed

(RPM)

Frame Size Full Load Amps (Amps) Efficiency Location

ODP Baldor 20.0 460/3/60 1 H 1,800 256 24.00 Premium Direct Drive

At Motor Synchronous Details TSP (in w.g.) Total Air Flow (CMF) Fan Speed (RPM) Motor Correction Factor(%) Fan Power (BHP)

3.98 14,356 1,750 93.0 14.31 Notes

Certified by the AHRI Central Station Air-Handling Unit (AHU) Certification Program, which is based on AHRI Standard 430/431. AHRI certified units are subject to rigorous and continuous testing, have performance ratings independently measured and are third-party verified. Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Water Coil(s)

Performance1 Details

Coil Fluid Type Rows

Fin Spacing

(FPI)

TPC TMBH SMBH

EAT (°F) LAT (°F) Airflow

(CFM)

FV

(ft/min) APD Flow

(GPM)

EWT

(°F)

LWT

(°F)

Fluid Vel.

(ft/s) WPD Alt.

(ft)DB WB DB WB

CC Water 2 8 2 364 364 35.0 - 54.6 - 16,035 535 0.23 17.8 140.0 98.3 .5 .2 10 CC Water 3 11 6 557 391 80.0 67.1 57.5 55.7 16,035 535 0.61 108.0 44.0 54.3 5.7 13.4 10

Coil # of Coils High

Face Type

Total Fin Height (in)

Fin Length (in)

Coil Face Area (ft2) Fin Material Fin Thickness

(in) Fin Type Tube Diameter (in) Tube Material Tube Wall

Thickness (in)

CC 2 Full 63.50 68 30.0 AL .006 Sine 5/8 Copper .020 CC 2 Full 63.50 68 30.0 AL .010 Sine 5/8 Copper .020

Coil Coil Coating Dry Weight (lbs) Fluid Weight (lbs) Fluid Volume (ft³) Header Material Casing Material Intermediate Drain

Pan Material Fouling Factor (hr.ft².°F/BTU)

CC - 231 73 1.2 Copper 304 Stainless Steel

304 Stainless Steel -

CC - 400 119 1.9 Copper 304 Stainless Steel

304 Stainless Steel -

Construction Details

Coil Location

Offset (in) Connection Material3

Connection Rotation (degrees) Connection Type

Supply Connection (Per Coil) Coil Stack Rack

Coil Index2 Connection Qty Size (in) CC 0 Left 0 Steel 0 MPT 2 1-1/2 - CC 2 Left 0 Steel 0 MPT 2 2-1/2 -

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:50:01 AM Unit Folder:AHU-2 Report Version: 2022.1.4.743 Unit Tag(s): AHU-2 Software Version: 21.4.6395.9682

Coil # of Coils High

Face Type

Total Fin Height (in)

Fin Length (in)

Coil Face Area (ft2) Fin Material Fin Thickness

(in) Fin Type Tube Diameter (in) Tube Material Tube Wall

Thickness (in)

Notes

● ¹Performance is shown for the entire coil bank. Performance is not per coil.

● ²Coil index indicates position in segment. Example: CC-1, index 0; Spacer, index 1; CC-2, index 2

● ³Johnson Controls suggests using red brass or copper connectors when the coil is to be attached to a copper or brass piping system.

● All coils are rated with a fouling factor of 0.00000 hr.ft².°F/BTU unless otherwise noted

● Ratings are for coils manufactured by Johnson Controls, Inc., 507 E. Michigan St., Milwaukee WI 53202.

● Coil DLL Version: 7.7L

● CDW Tube Spacing: 1.50 x 1.30

● CDW Tube Spacing: 1.50 x 1.30

● CC[1][0]: This coil is certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the range of Standard rating conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.

● CC[1][2]: This coil is certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the range of Standard rating conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Drain(s)

Details

Segment Drain Pan

Liner Material Connection Location Liner Coating

CC Stainless Steel Left None

Coil Spacer(s)

Details Segment Location Length (in) Material

CC 1 4 Galvanized

Filter(s)

Details

Segment Type Depth Filter Loading Media/MERV # of Spares Spare Filter Media Frame Material

FF Primary Filter 2" Side Pleated 30% (MERV 8) 1 Pleated 30% (MERV 8) Galvanized

Sizes Filter Gauge Details Segment Filter 1st Filter Size H x W

(in) 1st Qty 2nd Filter Size H x W

(in) 2nd Qty Location Type Range (in w.g) FF Primary Filter 20x24 6 24x24 3 - - -

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:50:01 AM Unit Folder:AHU-2 Report Version: 2022.1.4.743 Unit Tag(s): AHU-2 Software Version: 21.4.6395.9682

Damper(s) Details

Segment Air Path H x W (in) Qty Total Face Velocity (ft/min)

Face Area CFM Minimum Allowable

OA CFM

Damper Type

Damper Config Model Material Blade

Orientation Actuator

Type Fail

Position

MB Outside Air

38.25 x

40.00 1,509 16,035 Control 100% CD60 Galvanized Parallel - -

MB Return Air

21.00 x

62.00 1,773 16,035 - Control 100% CD60 Galvanized Parallel - -

Door(s)

Details

Segment(s) Location Swing Hinge Location H x W x T (in) View Port Test Port

Spare Gasket

Thermal Break

Safety Latch

Noncontact Safety Interlock

MB Left Outward Upstream Side 69 x 29 x 2 None - - Yes - - FF Left Outward Upstream Side 69 x 10 x 2 None - - Yes - - CC Left Outward Downstream Side 69 x 18 x 2 None - - Yes - - FS Left Outward Upstream Side 69 x 18 x 2 None - - Yes Yes -

Motor Control(s)

Details Segment Type MMP V/Ph/Hz Input/Output

Amps* Efficiency Heat Loss (at 100% load) Enclosure Bypass Disconnect

Type

RFI/EMI EMC

Filter

FS ABB VFD ABB

AYK580 - 460/3/60 27.0/27.0 93 % 430 NEMA 1 - Fused Yes

Notes *Drives are rated for use below 3,000 ft and 104°F. Use Derating Charts in Air-Mod Engineering Guide Form 100.42-EGI (212) for use above these limits.

Storage Temperature: -40°F to 158°F Humidity: MAX 95% RH non-condensing Altitude: 3,300 ft. without derate (1% derate for each additional 330 ft.)

Overload Current Rating: 100% for 1 minute every 10 minutes.

The Class 10 trip rating of the MMP device will not withstand an across-the-line start of a fan and should not be used with VFDs with bypass circuits.

The customer must provide a platform or catwalk for accessing the power-disconnect.

Copper Conductors Only.

FS: Contains the following option: Swinging DC Line Choke (Equivalent to 5% Input Line Reactor)

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:50:01 AM Unit Folder:AHU-2 Report Version: 2022.1.4.743 Unit Tag(s): AHU-2 Software Version: 21.4.6395.9682

Face Velocity and Static Pressure

Summary

Segment Description Face Area (sq. ft) Airflow

(CFM)

Face Velocity (ft/min)

Supply Fan Static Pressure

(in w.g.)

Exhaust/Return Fan Static Pressure (in w.g.)

MB Opening 9.0 16,035 1,773.00 0.53 0.00 MB Control Galvanized (CD60) 0.0 16,035 0.00 0.07 0.00 FF 2" Pleated 30% (MERV 8) 32.0 16,035 501.00 0.27 0.00 FF Dirty Filter Allowance 0.0 16,035 0.00 0.50 0.00 CC Heating 2 rows 8 fins 30.0 16,035 535.00 0.23 0.00 CC Cooling 3 rows 11 fins 30.0 16,035 535.00 0.61 0.00 FS Opening 10.3 16,035 1,551.00 0.25 0.00 FS External Static - User Entered 0.0 16,035 0.00 2.50 0.00

Total 4.96 0.00

Dimensions and Weight

Details Segment Description Length1 (in) Width2 (in) Height (in) Weight (lbs)

MB Mixing Box 35 81 75 668 FF Flat Filter 10 81 75 202 CC Variable Length Cooling Coil 42 81 75 1,369 FS Supply Fan 48 81 75 1,673

Overall3 135 3,912

Notes ¹The length includes bottom tier segments only ²The width does not include coil connection extensions or door latches that extend beyond the unit casing. The width does not include the depth of any pipe chases.

³Unit level and other loose components may be excluded from segment weights and overall segment weights. For total unit weight reference Unit Overview.

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:50:01 AM Unit Folder:AHU-2 Report Version: 2022.1.4.743 Unit Tag(s): AHU-2 Software Version: 21.4.6395.9682

Recommended Trap Height

Details

Segment Applicable Fan Fan TSP (in w.g.) Positive or Negative

Calculated Dimensions (in) Recommended Dimensions (in) Base Rail Height (in)

H X H + X H H + X CC Supply Fan 4.96 Negative 5.96 2.98 8.94 6.00 9.00 6"

Notes Formulas and calculations are recommendations only. Contractor shall determine actual dimensions required for each trap based on jobsite conditions, and application requirements.

Refer to the Installation Manual of the IOM for more information.

Statement of Compliance

Details YORK® Solution XT AHU's meet IBC seismic requirements for non-critical equipment (Ip = 1.0) for locations with design spectral response Sds <=

0.43. Units must be rigid mounted.

The anchorage of the unit to the ground or building structure needs to be evaluated by and is the responsibility of the engineer of record.

Specification of seismic requirements is the responsibility of the project design engineer. If formal certification is required, please contact your sales representative and/or application engineer for review. Certain application and site requirements may require additional cost and/or lead time.

Component locations are listed as Segment Hand (Unit Hand): ex. Left (Right). See SubmittalDrawing for additional details Air handling unit parameters vary depending on conditions. Parameters such as airflows, air pressure drops, and coil capacities are shown for design conditions.

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:50:01 AM Unit Folder:AHU-2 Report Version: 2022.1.4.743 Unit Tag(s): AHU-2 Software Version: 21.4.6395.9682

Shipping Summary

Details

Skid Skid Length (in) Skid Height (in) Skid Width (in) Skid Weight (lbs)

(FS CC FF MB) 135 85 95 3,911

Notes Skid Width: Total width of the shipping skid, including any items that may extend beyond the cabinet (this includes any door handles, coil connections, drain connections, lifting lugs, mounted pipe-chases, electrical/control components, tie-down brackets, side dampers).

Skid Height: Total height of the shipping skid, including any items that may extend beyond the cabinet (this includes any base-rails, shipping wood-blocks, roof peak, discharge flanges, mounted gas-furnace flue pipes).

Skid Length: Total length of the shipping skid, including any items that may extend beyond the cabinet (this includes any mounted rain-hoods, discharge flanges,tie-down brackets, shipping wood-blocks, front dampers, split connectors, electrical/control components, outrigging extensions, isolation dampers, inlet baskets).

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:48:53 AM Unit Folder:AHU-1 Report Version: 2022.1.4.743 Unit Tag(s): AHU-1 Software Version: 21.4.6395.9682

Job Summary

Project Name: Keesler AFB AHUs Unit Tag(s): AHU-1 Quantity: 1 Environment: Indoor

Unit Overview

Model Airflow (CFM) Altitude (ft) Operating Weight (lbs) XTI-75x81 15,705 10 3,920

Segment Sequence

(FS CC FF MB)

Unit Construction

Casing Details

Segment(s) Thickness (in) Exterior Paint Exterior Gauge and Material

Interior Gauge and Material

Insulation Thickness and

Material

Bulkhead Material

MB , FF , CC , FS 2 None STD Ga. G-90 Galvanized

STD Ga. G-90 Galvanized 2" Foam Galvanized

Base Details

Segment(s) Base Floor

Material Paint Gauge and Material Paint Insulation Attachment Tread

Plate

MB , FF , CC , FS Standard Formed Steel None STD Ga. G-90

Galvanized None N/A - None

Unit Electrical

Circuit Details Circuit # Component(s) V/Ph/Hz Full Load Amps (FLA) Minimum Current

Ampacity (MCA) Maximum Overcurrent

Protection (MOP) 1 Supply Fan Motor Control 460/3/60 24.0 30.0 50.0 2 Lights and Outlets 120/1/60 - - 15.0

Electrical Details Minimum Unit SCCR 5 kA rms Symmetrical ETL Label (UL1995/NEC-2002) Yes

Unit Light Type Unit Light Switch Standard LED External

Supply Fan(s)

Performance Details Fan

Manufacturer Model Class Size % Wheel Width

% Wheel Diameter Quantity Total Airflow

(CFM) Altitude (ft) TSP (in w.g)

ESP

(in w.g)

Fan Speed

(RPM)

Fan Power

(BHP)

Lau DDPG2 II 270-12 120 100 1 15,705 10 5.12 2.50 1,743 19.10

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:48:53 AM Unit Folder:AHU-1 Report Version: 2022.1.4.743 Unit Tag(s): AHU-1 Software Version: 21.4.6395.9682

Drive Type Wheel Type Blade Type Wheel Material Base Material Fan Flow

Isolation Isolation

Type Total

Eficiency (%) Outlet

Velocity (ft/s) Max Speed

(RPM) FEP (kW)

Direct Drive SWSI Airfoil Aluminum Galvanized Steel None 2" Spring 66.17 1,519 2,035 15.80 Motor Details

Type Manufacturer Motor Power (HP) V/Ph/Hz Quantity Insulation Class

Motor Speed

(RPM)

Frame Size Full Load Amps (Amps) Efficiency Location

ODP Baldor 20.0 460/3/60 1 H 1,800 256 24.00 Premium Direct Drive

At Motor Synchronous Details TSP (in w.g.) Total Air Flow (CMF) Fan Speed (RPM) Motor Correction Factor(%) Fan Power (BHP)

5.16 15,764 1,750 93.0 19.32 Notes

Certified by the AHRI Central Station Air-Handling Unit (AHU) Certification Program, which is based on AHRI Standard 430/431. AHRI certified units are subject to rigorous and continuous testing, have performance ratings independently measured and are third-party verified. Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Water Coil(s)

Performance1 Details

Coil Fluid Type Rows

Fin Spacing

(FPI)

TPC TMBH SMBH

EAT (°F) LAT (°F) Airflow

(CFM)

FV

(ft/min) APD Flow

(GPM)

EWT

(°F)

LWT

(°F)

Fluid Vel.

(ft/s) WPD Alt.

(ft)DB WB DB WB

CC Water 2 8 2 363 363 35.0 - 55.0 - 15,705 524 0.22 17.8 140.0 98.5 .5 .2 10 CC Water 4 11 8 545 386 79.7 66.8 57.0 55.4 15,705 524 0.80 106.0 44.0 54.2 5.6 16.8 10

Coil # of Coils High

Face Type

Total Fin Height (in)

Fin Length (in)

Coil Face Area (ft2) Fin Material Fin Thickness

(in) Fin Type Tube Diameter (in) Tube Material Tube Wall

Thickness (in)

CC 2 Full 63.50 68 30.0 AL .006 Sine 5/8 Copper .020 CC 2 Full 63.50 68 30.0 AL .006 Sine 5/8 Copper .020

Coil Coil Coating Dry Weight (lbs) Fluid Weight (lbs) Fluid Volume (ft³) Header Material Casing Material Intermediate Drain

Pan Material Fouling Factor (hr.ft².°F/BTU)

CC - 231 73 1.2 Copper 304 Stainless Steel

304 Stainless Steel -

CC - 408 151 2.4 Copper 304 Stainless Steel

304 Stainless Steel -

Construction Details

Coil Location

Offset (in) Connection Material3

Connection Rotation (degrees) Connection Type

Supply Connection (Per Coil) Coil Stack Rack

Coil Index2 Connection Qty Size (in) CC 0 Right 0 Steel 0 MPT 2 1-1/2 - CC 2 Right 0 Steel 0 MPT 2 2-1/2 -

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:48:53 AM Unit Folder:AHU-1 Report Version: 2022.1.4.743 Unit Tag(s): AHU-1 Software Version: 21.4.6395.9682

Coil # of Coils High

Face Type

Total Fin Height (in)

Fin Length (in)

Coil Face Area (ft2) Fin Material Fin Thickness

(in) Fin Type Tube Diameter (in) Tube Material Tube Wall

Thickness (in)

Notes

● ¹Performance is shown for the entire coil bank. Performance is not per coil.

● ²Coil index indicates position in segment. Example: CC-1, index 0; Spacer, index 1; CC-2, index 2

● ³Johnson Controls suggests using red brass or copper connectors when the coil is to be attached to a copper or brass piping system.

● All coils are rated with a fouling factor of 0.00000 hr.ft².°F/BTU unless otherwise noted

● Ratings are for coils manufactured by Johnson Controls, Inc., 507 E. Michigan St., Milwaukee WI 53202.

● Coil DLL Version: 7.7L

● CDW Tube Spacing: 1.50 x 1.30

● CDW Tube Spacing: 1.50 x 1.30

● CC[1][0]: This coil is certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the range of Standard rating conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.

● CC[1][2]: This coil is certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the range of Standard rating conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Drain(s)

Details

Segment Drain Pan

Liner Material Connection Location Liner Coating

CC Stainless Steel Right None

Coil Spacer(s)

Details Segment Location Length (in) Material

CC 1 4 Galvanized

Filter(s)

Details

Segment Type Depth Filter Loading Media/MERV # of Spares Spare Filter Media Frame Material

FF Primary Filter 2" Side Pleated 30% (MERV 8) 1 Pleated 30% (MERV 8) Galvanized

Sizes Filter Gauge Details Segment Filter 1st Filter Size H x W

(in) 1st Qty 2nd Filter Size H x W

(in) 2nd Qty Location Type Range (in w.g) FF Primary Filter 20x24 6 24x24 3 - - -

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:48:53 AM Unit Folder:AHU-1 Report Version: 2022.1.4.743 Unit Tag(s): AHU-1 Software Version: 21.4.6395.9682

Damper(s) Details

Segment Air Path H x W (in) Qty Total Face Velocity (ft/min)

Face Area CFM Minimum Allowable

OA CFM

Damper Type

Damper Config Model Material Blade

Orientation Actuator

Type Fail

Position

MB Outside Air

38.00 x

54.00 1,102 15,705 Control 100% CD60 Galvanized Parallel - -

MB Return Air

20.00 x

64.00 1,767 15,705 - Control 100% CD60 Galvanized Parallel - -

Door(s)

Details

Segment(s) Location Swing Hinge Location H x W x T (in) View Port Test Port

Spare Gasket

Thermal Break

Safety Latch

Noncontact Safety Interlock

MB Right Outward Upstream Side 69 x 29 x 2 None - - Yes - - FF Right Outward Upstream Side 69 x 10 x 2 None - - Yes - - CC Right Outward Downstream Side 69 x 18 x 2 None - - Yes - - FS Right Outward Upstream Side 69 x 18 x 2 None - - Yes Yes -

Motor Control(s)

Details Segment Type MMP V/Ph/Hz Input/Output

Amps* Efficiency Heat Loss (at 100% load) Enclosure Bypass Disconnect

Type

RFI/EMI EMC

Filter

FS ABB VFD ABB

AYK580 - 460/3/60 27.0/27.0 93 % 430 NEMA 1 - Fused Yes

Notes *Drives are rated for use below 3,000 ft and 104°F. Use Derating Charts in Air-Mod Engineering Guide Form 100.42-EGI (212) for use above these limits.

Storage Temperature: -40°F to 158°F Humidity: MAX 95% RH non-condensing Altitude: 3,300 ft. without derate (1% derate for each additional 330 ft.)

Overload Current Rating: 100% for 1 minute every 10 minutes.

The Class 10 trip rating of the MMP device will not withstand an across-the-line start of a fan and should not be used with VFDs with bypass circuits.

The customer must provide a platform or catwalk for accessing the power-disconnect.

Copper Conductors Only.

FS: Contains the following option: Swinging DC Line Choke (Equivalent to 5% Input Line Reactor)

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:48:53 AM Unit Folder:AHU-1 Report Version: 2022.1.4.743 Unit Tag(s): AHU-1 Software Version: 21.4.6395.9682

Face Velocity and Static Pressure

Summary

Segment Description Face Area (sq. ft) Airflow

(CFM)

Face Velocity (ft/min)

Supply Fan Static Pressure

(in w.g.)

Exhaust/Return Fan Static Pressure (in w.g.)

MB Opening 8.9 15,705 1,767.00 0.53 0.00 MB Control Galvanized (CD60) 0.0 15,705 0.00 0.07 0.00 FF 2" Pleated 30% (MERV 8) 32.0 15,705 491.00 0.26 0.00 FF Dirty Filter Allowance 0.0 15,705 0.00 0.50 0.00 CC Heating 2 rows 8 fins 30.0 15,705 524.00 0.22 0.00 CC Cooling 4 rows 11 fins 30.0 15,705 524.00 0.80 0.00 FS Opening 10.3 15,705 1,519.00 0.24 0.00 FS External Static - User Entered 0.0 15,705 0.00 2.50 0.00

Total 5.12 0.00

Dimensions and Weight

Details Segment Description Length1 (in) Width2 (in) Height (in) Weight (lbs)

MB Mixing Box 35 81 75 668 FF Flat Filter 10 81 75 202 CC Variable Length Cooling Coil 42 81 75 1,377 FS Supply Fan 48 81 75 1,673

Overall3 135 3,920

Notes ¹The length includes bottom tier segments only ²The width does not include coil connection extensions or door latches that extend beyond the unit casing. The width does not include the depth of any pipe chases.

³Unit level and other loose components may be excluded from segment weights and overall segment weights. For total unit weight reference Unit Overview.

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:48:53 AM Unit Folder:AHU-1 Report Version: 2022.1.4.743 Unit Tag(s): AHU-1 Software Version: 21.4.6395.9682

Recommended Trap Height

Details

Segment Applicable Fan Fan TSP (in w.g.) Positive or Negative

Calculated Dimensions (in) Recommended Dimensions (in) Base Rail Height (in)

H X H + X H H + X CC Supply Fan 5.12 Negative 6.12 3.06 9.18 6.25 9.50 6"

Notes Formulas and calculations are recommendations only. Contractor shall determine actual dimensions required for each trap based on jobsite conditions, and application requirements.

Refer to the Installation Manual of the IOM for more information.

Statement of Compliance

Details YORK® Solution XT AHU's meet IBC seismic requirements for non-critical equipment (Ip = 1.0) for locations with design spectral response Sds <=

0.43. Units must be rigid mounted.

The anchorage of the unit to the ground or building structure needs to be evaluated by and is the responsibility of the engineer of record.

Specification of seismic requirements is the responsibility of the project design engineer. If formal certification is required, please contact your sales representative and/or application engineer for review. Certain application and site requirements may require additional cost and/or lead time.

Component locations are listed as Segment Hand (Unit Hand): ex. Left (Right). See SubmittalDrawing for additional details Air handling unit parameters vary depending on conditions. Parameters such as airflows, air pressure drops, and coil capacities are shown for design conditions.

Project Name:Keesler AFB AHUs Last Saved: 5/25/2022 9:48:53 AM Unit Folder:AHU-1 Report Version: 2022.1.4.743 Unit Tag(s): AHU-1 Software Version: 21.4.6395.9682

Shipping Summary

Details

Skid Skid Length (in) Skid Height (in) Skid Width (in) Skid Weight (lbs)

(FS CC FF MB) 135 85 95 3,919

Notes Skid Width: Total width of the shipping skid, including any items that may extend beyond the cabinet (this includes any door handles, coil connections, drain connections, lifting lugs, mounted pipe-chases, electrical/control components, tie-down brackets, side dampers).

Skid Height: Total height of the shipping skid, including any items that may extend beyond the cabinet (this includes any base-rails, shipping wood-blocks, roof peak, discharge flanges, mounted gas-furnace flue pipes).

Skid Length: Total length of the shipping skid, including any items that may extend beyond the cabinet (this includes any mounted rain-hoods, discharge flanges,tie-down brackets, shipping wood-blocks, front dampers, split connectors, electrical/control components, outrigging extensions, isolation dampers, inlet baskets).

Fan Curves Section

Unit and Wiring Drawings Section

Warranties Section

OPTIONAL 5 YEAR PARTS & LABOR LIMITED WARRANTY

YORK® SOLUTION™ XTO/XTI

JOHNSON CONTROLS

PRODUCT TYPE: YORK® SOLUTION™ XTO/XTI STARTUP DATE:

YORK CONTRACT NO.: SHIPPING DATE:

UNIT MODEL NUMBER:

UNIT SERIAL NUMBER:

UNIT TAG ID:

UNIT LOCATION:

PROJECT NAME:

INSTALLATION

ADDRESS:

LIMITED WARRANTY

Subject to the terms, conditions, exclusions, and other limitations set forth in the Standard Limited Warranty for Engineered Systems Equipment (50.05-NM2), when properly endorsed, this protection plan between Johnson Controls, Inc. (“Seller”) and the undersigned Customer (“Buyer”) warrants that that each new Engineered Systems Equipment manufactured by Seller and materials, or installation or start-up services performed by Johnson Controls in connection therewith, are free from defects in material and workmanship for sixty-six (66) months from the date of shipment from Seller’s facility or sixty (60) months from startup, whichever occurs first. When properly endorsed, this protection plan between the Seller and Buyer, warrants, to the customer named herein, labor for the entire air handling unit. Labor repairs must be performed in accordance with instructions issued by Johnson Controls.

THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, EXPRESS OR IMPLIED IN LAW OR IN FACT, INCLUDING, WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. THE WARRANTIES CONTAINED HEREIN SET FORTH BUYER’S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A DEFECT IN WORKMANSHIP OR MATERIALS. IN NO EVENT SHALL JOHNSON CONTROLS’ LIABILITY FOR DIRECT OR COMPENSATORY DAMAGES EXCEED THE

PAYMENTS RECEIVED BY JOHNSON CONTROLS FROM BUYER FOR THE MATERIALS OR EQUIPMENT

INVOLVED. NOR SHALL JOHNSON CONTROLS BE LIABLE FOR ANY SPECIAL, INCIDENTAL, OR

CONSEQUENTIAL DAMAGES. THESE LIMITATIONS ON LIABILITY AND DAMAGES SHALL APPLY UNDER ALL THEORIES OF LIABILITY OR CAUSES OF ACTION, INCLUDING, BUT NOT LIMITED TO, CONTRACT, WARRANTY, TORT (INCLUDING NEGLIGENCE) OR STRICT LIABILITY. THE ABOVE LIMITATIONS SHALL INURE TO THE

BENEFIT OF JOHNSON CONTROLS’ SUPPLIERS AND SUBCONTRACTORS.

Notification of defect and any warranty claim must be made in writing, postage paid, with a brief written description of the problem to Buyer’s local Johnson Controls’ sales/service office. Nothing herein us intended to provide warranty coverage to lessees or anyone other than Buyer and no third-parties are intended to be beneficiaries of this warranty.

BRANCH SERVICE OFFICE:

OFFERED BY: __________________________________________________________ _______________ Johnson Controls Selling Representative Print/Sign Date

APPROVED BY: __________________________________________________________ _______________ Johnson Controls Branch Manager or other authorized individual Print/Sign Date

ACCEPTED BY: __________________________________________________________ _______________ Customer Signature Date

6. Rental Chillers.

Reference: BOS 03-23.105.BEGTM Replaces: 50.05-NM2 (812)

Copyright © 2012 Johnson Controls, Inc. Printed in USA 50.05-NM2 (1212) www.johnsoncontrols.com

P.O. Box 423, Milwaukee, WI 53203

POLICY STATEMENT

Johnson Controls (JCI) warrants all equipment and associated factory supplied materials or start-up services performed by

Johnson Controls in connection therewith, against defects in workmanship and material for a period of eighteen (18) months from date of shipment, or twelve (12) months from date of start up, whichever occurs first. Subject to the exclusions listed below, Johnson Controls, at its option, will repair or replace, FOB point of shipment, such products or components as it finds defective.

Except for reciprocating replacement compressors, which

Johnson Controls warrants for a period of twelve (12) months from date of shipment, Johnson Controls warrants Johnson

Controls reconditioned or replacement materials, or installation or start-up services performed by Johnson Controls in connection therewith, against defects in workmanship and material for a period of (90) days from date of shipment.

The above represents the minimum warranty policy Johnson

Controls will extend to customers. Additional product specific coverage is provided as outlined in related warranty policies. No warranty repairs or replacements will be made until payment for all equipment, materials, or components has been received by

Johnson Controls.

EXCLUSIONS:

Unless specifically agreed to in the contract documents, this warranty does not include the following costs and expenses:

1. Labor to remove or reinstall any equipment, materials or components.

2. Shipping, handling or transportation charges, including cranes, safety walks or other safety requirements specific to jobsites.

3. Cost of refrigerant.

4. Freight damage.

5. Field applied coatings added to any surface or heat ex-changer.

ALL WARRANTIES ARE VOID IF:

1. Equipment is used with refrigerants, oil, additives, or antifreeze agents other than those authorized by supplying factory.

2. Equipment is used with any material or any equipment such as evaporators, tubing, other low side equipment or refrigerant controls not approved by supplying factory.

3. Equipment has been damaged by freezing because it was not properly protected during cold weather or damaged by fire or any other conditions not ordinarily encountered.

4. Equipment is not installed, operated, maintained and serviced in accordance with instructions issued by Johnson

Controls.

5. Equipment is damaged due to dirt, air, moisture, or other foreign matter entering the refrigerant system.

6. Equipment is not properly stored, protected, or inspected by the customer during the period from date of shipment to date of initial start-up.

7. Field coating of coil has occurred.

8. Equipment is damaged due to acts of god, abuse, in-cluding shipping damage, neglect, sabotage, or acts of terrorists.

9. Equipment has modifications carried out that have an effect on the original design of the product without such work being authorized by the factory. Any on site design changes or unit modification/replacement shall be authorized in advance by the factory.

THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES AND

LIABILITIES, EXPRESS OR IMPLIED IN LAW OR IN FACT, INCLUDING THE

WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR

PURPOSE. THE WARRANTIES CONTAINED HEREIN SET FORTH BUYER’S

SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A DEFECT IN

WORKMANSHIP OR MATERIALS. IN NO EVENT SHALL JOHNSON

CONTROLS’ LIABILITY FOR DIRECT OR COMPENSATORY DAMAGES

EXCEED THE PAYMENTS RECEIVED BY JOHNSON CONTROLS FROM

BUYER FOR THE MATERIAL OR EQUIPMENT INVOLVED, NOR SHALL

JOHNSON CONTROLS BE LIABLE FOR ANY SPECIAL, INCIDENTAL, OR

CONSEQUENTIAL DAMAGES. THESE LIMITATIONS ON LIABILITY AND

DAMAGES SHALL APPLY UNDER ALL THEORIES OF LIABILITY OR

CAUSES OF ACTION, INCLUDING BUT NOT LIMITED TO, CONTRACT,

WARRANTY, TORT, (INCLUDING NEGLIGENCE) OR STRICT LIABILITY.

THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF JOHNSON

CONTROLS SUPPLIERS AND SUBCONTRACTORS.

STANDARD LIMITED WARRANTY

ENGINEERED SYSTEMS EQUIPMENT

SERVICE POLICY

Supersedes: 50.05-NM2 (812)

Form 50.05-NM2 (1212)

STANDARD LIMITED LABOR WARRANTY

SOLUTION XTO/XTI

JOHNSON CONTROLS

PRODUCT TYPE: SOLUTION XTO/XTI STARTUP DATE:

YORK CONTRACT NO.: SHIPPING DATE:

UNIT MODEL NUMBER:

UNIT SERIAL NUMBER:

UNIT TAG ID:

UNIT LOCATION:

PROJECT NAME:

INSTALLATION

ADDRESS:

LIMITED WARRANTY

Subject to the terms, conditions, exclusions, and other limitations set forth in the Standard Limited Warranty for Engineered Systems

Equipment (50.05-NM2), when properly endorsed, this protection plan between Johnson Controls, Inc. (“Seller”) and the undersigned Customer (“Buyer”) warrants that that each new Engineered Systems Equipment manufactured by Seller and materials, or installation or start-up services performed by Johnson Controls in connection therewith, are free from defects in material and workmanship for eighteen (18) months from the date of shipment from Seller’s facility or twelve (12) months from startup, whichever occurs first. When properly endorsed, this protection plan between the Seller and Buyer, warrants, to the customer named herein, labor for the entire air handling unit. Labor repairs must be performed in accordance with instructions issued by Johnson

Controls.

THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, EXPRESS OR

IMPLIED IN LAW OR IN FACT, INCLUDING, WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY

AND FITNESS FOR A PARTICULAR PURPOSE. THE WARRANTIES CONTAINED HEREIN SET FORTH BUYER’S SOLE

AND EXCLUSIVE REMEDY IN THE EVENT OF A DEFECT IN WORKMANSHIP OR MATERIALS. IN NO EVENT SHALL

JOHNSON CONTROLS’ LIABILITY FOR DIRECT OR COMPENSATORY DAMAGES EXCEED THE PAYMENTS

RECEIVED BY JOHNSON CONTROLS FROM BUYER FOR THE MATERIALS OR EQUIPMENT INVOLVED. NOR SHALL

JOHNSON CONTROLS BE LIABLE FOR ANY SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES. THESE

LIMITATIONS ON LIABILITY AND DAMAGES SHALL APPLY UNDER ALL THEORIES OF LIABILITY OR CAUSES OF

ACTION, INCLUDING, BUT NOT LIMITED TO, CONTRACT, WARRANTY, TORT (INCLUDING NEGLIGENCE) OR

STRICT LIABILITY. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF JOHNSON CONTROLS’

SUPPLIERS AND SUBCONTRACTORS.

Notification of defect and any warranty claim must be made in writing, postage paid, with a brief written description of the problem to Buyer’s local Johnson Controls’ sales/service office. Nothing herein us intended to provide warranty coverage to lessees or anyone other than Buyer and no third-parties are intended to be beneficiaries of this warranty.

BRANCH SERVICE OFFICE:

OFFERED BY: __________________________________________________________ _______________

Johnson Controls Selling Representative Print/Sign

Date

APPROVED BY: __________________________________________________________ _______________

Johnson Controls Branch Manager or other authorized individual Print/Sign

Customer Signature

(Product Code Ref: 8513

OPTIONAL 5 YEAR PARTS & LABOR LIMITED WARRANTY

YORK® SOLUTION™ XTO/XTI

JOHNSON CONTROLS

PRODUCT TYPE: YORK® SOLUTION™ XTO/XTI STARTUP DATE:

YORK CONTRACT NO.: SHIPPING DATE:

UNIT MODEL NUMBER:

UNIT SERIAL NUMBER:

UNIT TAG ID:

UNIT LOCATION:

PROJECT NAME:

INSTALLATION

ADDRESS:

LIMITED WARRANTY

Subject to the terms, conditions, exclusions, and other limitations set forth in the Standard Limited Warranty for Engineered Systems Equipment (50.05-NM2), when properly endorsed, this protection plan between Johnson Controls, Inc. (“Seller”) and the undersigned Customer (“Buyer”) warrants that that each new Engineered Systems Equipment manufactured by Seller and materials, or installation or start-up services performed by Johnson Controls in connection therewith, are free from defects in material and workmanship for sixty-six (66) months from the date of shipment from Seller’s facility or sixty (60) months from startup, whichever occurs first. When properly endorsed, this protection plan between the Seller and Buyer, warrants, to the customer named herein, labor for the entire air handling unit. Labor repairs must be performed in accordance with instructions issued by Johnson Controls.

THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, EXPRESS OR IMPLIED IN LAW OR IN FACT, INCLUDING, WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. THE WARRANTIES CONTAINED HEREIN SET FORTH BUYER’S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A DEFECT IN WORKMANSHIP OR MATERIALS. IN NO EVENT SHALL JOHNSON CONTROLS’ LIABILITY FOR DIRECT OR COMPENSATORY DAMAGES EXCEED THE

PAYMENTS RECEIVED BY JOHNSON CONTROLS FROM BUYER FOR THE MATERIALS OR EQUIPMENT

INVOLVED. NOR SHALL JOHNSON CONTROLS BE LIABLE FOR ANY SPECIAL, INCIDENTAL, OR

CONSEQUENTIAL DAMAGES. THESE LIMITATIONS ON LIABILITY AND DAMAGES SHALL APPLY UNDER ALL THEORIES OF LIABILITY OR CAUSES OF ACTION, INCLUDING, BUT NOT LIMITED TO, CONTRACT, WARRANTY, TORT (INCLUDING NEGLIGENCE) OR STRICT LIABILITY. THE ABOVE LIMITATIONS SHALL INURE TO THE

BENEFIT OF JOHNSON CONTROLS’ SUPPLIERS AND SUBCONTRACTORS.

Notification of defect and any warranty claim must be made in writing, postage paid, with a brief written description of the problem to Buyer’s local Johnson Controls’ sales/service office. Nothing herein us intended to provide warranty coverage to lessees or anyone other than Buyer and no third-parties are intended to be beneficiaries of this warranty.

BRANCH SERVICE OFFICE:

OFFERED BY: __________________________________________________________ _______________ Johnson Controls Selling Representative Print/Sign Date

APPROVED BY: __________________________________________________________ _______________ Johnson Controls Branch Manager or other authorized individual Print/Sign Date

Customer Signature Date

6. Rental Chillers.

Reference: BOS 03-23.105.BEGTM Replaces: 50.05-NM2 (812)

Copyright © 2012 Johnson Controls, Inc. Printed in USA 50.05-NM2 (1212) www.johnsoncontrols.com

P.O. Box 423, Milwaukee, WI 53203

POLICY STATEMENT

Johnson Controls (JCI) warrants all equipment and associated factory supplied materials or start-up services performed by

Johnson Controls in connection therewith, against defects in workmanship and material for a period of eighteen (18) months from date of shipment, or twelve (12) months from date of start up, whichever occurs first. Subject to the exclusions listed below, Johnson Controls, at its option, will repair or replace, FOB point of shipment, such products or components as it finds defective.

Except for reciprocating replacement compressors, which

Johnson Controls warrants for a period of twelve (12) months from date of shipment, Johnson Controls warrants Johnson

Controls reconditioned or replacement materials, or installation or start-up services performed by Johnson Controls in connection therewith, against defects in workmanship and material for a period of (90) days from date of shipment.

The above represents the minimum warranty policy Johnson

Controls will extend to customers. Additional product specific coverage is provided as outlined in related warranty policies. No warranty repairs or replacements will be made until payment for all equipment, materials, or components has been received by

Johnson Controls.

EXCLUSIONS:

Unless specifically agreed to in the contract documents, this warranty does not include the following costs and expenses:

1. Labor to remove or reinstall any equipment, materials or components.

2. Shipping, handling or transportation charges, including cranes, safety walks or other safety requirements specific to jobsites.

3. Cost of refrigerant.

4. Freight damage.

5. Field applied coatings added to any surface or heat ex-changer.

ALL WARRANTIES ARE VOID IF:

1. Equipment is used with refrigerants, oil, additives, or antifreeze agents other than those authorized by supplying factory.

2. Equipment is used with any material or any equipment such as evaporators, tubing, other low side equipment or refrigerant controls not approved by supplying factory.

3. Equipment has been damaged by freezing because it was not properly protected during cold weather or damaged by fire or any other conditions not ordinarily encountered.

4. Equipment is not installed, operated, maintained and serviced in accordance with instructions issued by Johnson

Controls.

5. Equipment is damaged due to dirt, air, moisture, or other foreign matter entering the refrigerant system.

6. Equipment is not properly stored, protected, or inspected by the customer during the period from date of shipment to date of initial start-up.

7. Field coating of coil has occurred.

8. Equipment is damaged due to acts of god, abuse, in-cluding shipping damage, neglect, sabotage, or acts of terrorists.

9. Equipment has modifications carried out that have an effect on the original design of the product without such work being authorized by the factory. Any on site design changes or unit modification/replacement shall be authorized in advance by the factory.

THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES AND

LIABILITIES, EXPRESS OR IMPLIED IN LAW OR IN FACT, INCLUDING THE

WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR

PURPOSE. THE WARRANTIES CONTAINED HEREIN SET FORTH BUYER’S

SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A DEFECT IN

WORKMANSHIP OR MATERIALS. IN NO EVENT SHALL JOHNSON

CONTROLS’ LIABILITY FOR DIRECT OR COMPENSATORY DAMAGES

EXCEED THE PAYMENTS RECEIVED BY JOHNSON CONTROLS FROM

BUYER FOR THE MATERIAL OR EQUIPMENT INVOLVED, NOR SHALL

JOHNSON CONTROLS BE LIABLE FOR ANY SPECIAL, INCIDENTAL, OR

CONSEQUENTIAL DAMAGES. THESE LIMITATIONS ON LIABILITY AND

DAMAGES SHALL APPLY UNDER ALL THEORIES OF LIABILITY OR

CAUSES OF ACTION, INCLUDING BUT NOT LIMITED TO, CONTRACT,

WARRANTY, TORT, (INCLUDING NEGLIGENCE) OR STRICT LIABILITY.

THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF JOHNSON

CONTROLS SUPPLIERS AND SUBCONTRACTORS.

STANDARD LIMITED WARRANTY

ENGINEERED SYSTEMS EQUIPMENT

SERVICE POLICY

Supersedes: 50.05-NM2 (812)

Form 50.05-NM2 (1212)

STANDARD LIMITED LABOR WARRANTY

SOLUTION XTO/XTI

JOHNSON CONTROLS

PRODUCT TYPE: SOLUTION XTO/XTI STARTUP DATE:

YORK CONTRACT NO.: SHIPPING DATE:

UNIT MODEL NUMBER:

UNIT SERIAL NUMBER:

UNIT TAG ID:

UNIT LOCATION:

PROJECT NAME:

INSTALLATION

ADDRESS:

LIMITED WARRANTY

Subject to the terms, conditions, exclusions, and other limitations set forth in the Standard Limited Warranty for Engineered Systems

Equipment (50.05-NM2), when properly endorsed, this protection plan between Johnson Controls, Inc. (“Seller”) and the undersigned Customer (“Buyer”) warrants that that each new Engineered Systems Equipment manufactured by Seller and materials, or installation or start-up services performed by Johnson Controls in connection therewith, are free from defects in material and workmanship for eighteen (18) months from the date of shipment from Seller’s facility or twelve (12) months from startup, whichever occurs first. When properly endorsed, this protection plan between the Seller and Buyer, warrants, to the customer named herein, labor for the entire air handling unit. Labor repairs must be performed in accordance with instructions issued by Johnson

Controls.

THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, EXPRESS OR

IMPLIED IN LAW OR IN FACT, INCLUDING, WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY

AND FITNESS FOR A PARTICULAR PURPOSE. THE WARRANTIES CONTAINED HEREIN SET FORTH BUYER’S SOLE

AND EXCLUSIVE REMEDY IN THE EVENT OF A DEFECT IN WORKMANSHIP OR MATERIALS. IN NO EVENT SHALL

JOHNSON CONTROLS’ LIABILITY FOR DIRECT OR COMPENSATORY DAMAGES EXCEED THE PAYMENTS

RECEIVED BY JOHNSON CONTROLS FROM BUYER FOR THE MATERIALS OR EQUIPMENT INVOLVED. NOR SHALL

JOHNSON CONTROLS BE LIABLE FOR ANY SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES. THESE

LIMITATIONS ON LIABILITY AND DAMAGES SHALL APPLY UNDER ALL THEORIES OF LIABILITY OR CAUSES OF

ACTION, INCLUDING, BUT NOT LIMITED TO, CONTRACT, WARRANTY, TORT (INCLUDING NEGLIGENCE) OR

STRICT LIABILITY. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF JOHNSON CONTROLS’

SUPPLIERS AND SUBCONTRACTORS.

Notification of defect and any warranty claim must be made in writing, postage paid, with a brief written description of the problem to Buyer’s local Johnson Controls’ sales/service office. Nothing herein us intended to provide warranty coverage to lessees or anyone other than Buyer and no third-parties are intended to be beneficiaries of this warranty.

BRANCH SERVICE OFFICE:

OFFERED BY: __________________________________________________________ _______________

Johnson Controls Selling Representative Print/Sign

APPROVED BY: __________________________________________________________ _______________

Johnson Controls Branch Manager or other authorized individual Print/Sign

Customer Signature

(Product Code Ref: 8513

Equipment Release Approval Form

SUBMITTAL NOTES

Product Type: Solution XTI

Unit Tags: AHU-2; AHU-1

The following table must be completed prior to releasing the equipment for fabrication. Please initial the column indicating the information contained in this submittal has been verified, or indicate to refer to a marked-up page.

SUBMITTAL VERIFICATION

Purchaser Initials

Electrical voltage and electrical connections are compatible with jobsite requirements.

Piping / Ductwork connections shown in this submittal are correct .

Unit tag designations are correct.

Equipment dimensions (length, width, and height) and weights have been verified to comply with jobsite conditions and rigging requirements. Please indicate approval by your initials on all included drawings.

Verify “Unit Hand” of any Air Handling Equipment per the definition provided on the “Equipment Release / Configuration Process” form.

Project: Keesler AFB AHUs 2 Submittal

SUBMITTAL VERIFICATION

Purchaser Initials

Indicate equipment configuration choices on the Equipment Release /Configuration Process form (if included on this Submittal package), and sign the form.

Important Notes:

1) Actual fabrication release cannot commence until this form is signed by the customer and returned to JCI along with a release notification want date and ship to address.

2) Equipment "lead-time" does not start until confirmed release documentation is received, and the order is actually released to the factory.

3) Modifications to equipment configurations after fabrication release may impact cost and lead-time

4) Attached configurations are as shown in the approved equipment submittals or as defined in superseding customer correspondence.

5) AHU "Side" / "Hand" orientation is relative to a person standing inside an AHU with air hitting the back of the head.

6) Note that once this document is confirmed, the equipment configurations defined by this document take precedence over all other documents.

7) "Want date" and/or "ship to address" changes made after this document is confirmed may impact cost and lead-time.

8) Air handler drawings also include shipping split explosions with corresponding weights and dimensions. If additional splits are required, there will be additional costs and the unit length will increase.

Project: Keesler AFB AHUs 3 Submittal

Please fill out the following table and refer to the receiving/rigging instructions in this submittal to help ensure a smooth delivery and installation of the equipment.

DELIVERY INFORMATION

Please fill out information below

Contact name for coordinating delivery of equipment with transportation company

Contact phone number

Advance notice required from transportation company prior to delivering equipment (typically 48 hours)

Ship to address:

Other special shipping instructions or requirements

Project: Keesler AFB AHUs 4 Submittal

CUSTOMER APPROVAL:

Customer Name:

Signature (*)

Date:

ALLERGENSMOLDVIRUSES BACTERIA

WWW.FRESHAIREUV.COM

FEATURES

• Easy to install

• Fits coils up to 144” x 144”

• High-output 2 year UV-C lamps

• Combine with application mounting kits

• Scalable design for multi-lamp configurations

• Lifetime warranty on all parts except lamp(s)

• Water-resistant heavy-duty power supply

• Optional door interlock switch (TUVC-INTLCK)

BENEFITS

• 99.9% surface disinfection GUARANTEED

• Sterilizes mold, bacteria, viruses

• Disinfects coil & drain pan

• Improves HVAC system efficiency

• Improves indoor air quality

FRESH-AIRE UV® CS

COMMERCIAL UV-C CORE SYSTEM

FRESH-AIRE UV

STERILIZES BIOLOGICAL PATHOGENS

This system is designed to improve indoor air quality by sterilizing airborne viruses, bacteria, and allergens. It also saves energy and maintenance costs associated with commercial HVAC. A biofilm of only 0.002” can reduce efficiency by 37%! Ultraviolet germicidal irradiation, (UVGI) is the most cost-effective and practical solution.

The Core System offers easy and flexible installation. It includes an advanced multi-voltage, water-resistant power supply. All parts (except lamps) are covered by a lifetime warranty. This system also improves indoor air quality by sterilizing airborne bacteria, viruses, and allergens.

Simple & Easy For coils up to 144” x 144”

Everything needed for most installations is included in the box.

Commercial Series Accessories View PDF Control Box

UV-C Radiometer

Safety Interlock Switch

UV-C Lamp Shield

LIFETIME

WARRANTY

http://freshaireuv.com

SALES@FRESHAIREUV.COM 800.741.1195

WWW.FRESHAIREUV.COM MADE IN USA

33” 40” 47” 56” 61” 72” 82” 98” 108” 120” 144” 24” 232S 232S 246S 246S 260S 260S 260S 246D 246D 260D 260D

32” 232S 232S 246S 246S 260S 260S 260S 246D 246D 260D 260D

40” 232S 232S 246S 246D 260S 260D 260D 246D (2) 246D (2) 260D 260D

56” 232D 232D 246D 246D 260D 260D 260D 246D (2) 246D…