Attachment 1b - Drawings - 9186_Madison Clerks Reno_BID DRAWINGS.pdf

PDF 5 MB Posted

Attached to
RFB 2026-12 Madison County Bldg. #4, Clerks Office Renovation
Solicitation number
2133343
Issued by
Madison County, New York

About this file

This document set contains architectural and engineering bid drawings for Madison County Building #4 Clerk's Office Renovation project located in Wampsville, New York. The drawings package, issued for bid on March 13, 2026, comprises architectural, HVAC, and electrical plans prepared by King + King Architects and Argus Engineering for project number 26-11-9186. The scope of work involves a Level 2 alteration to the first floor clerk's office suite totaling approximately 4,510 square feet, including partial demolition of existing metal prefabricated wall systems, installation of new gypsum drywall partitions with sound batt insulation, new casework with Corian solid surface countertops, carpet tile flooring, ceiling work, and coordination of mechanical, plumbing, and electrical systems. The project is classified as Building Use Group B (Business) occupancy with Construction Type II-B and requires compliance with the 2025 Building Code of New York State and applicable fire and energy conservation codes.

The bid drawings provide comprehensive details for general construction, HVAC work including ductwork modifications and diffuser relocation, and electrical work including lighting, power, low-voltage data cabling, fire alarm relocation, and access control systems. Specific construction details include partition types S3a and S3g specifications, door and window schedules with hollow metal frames, interior elevations for workstation counters with ADA-accessible stations, and reception desk configurations. HVAC work includes removal and relocation of existing diffusers, extension of ductwork connections balanced to specified CFM rates, and installation of a 24x24 return grille. Electrical demolition and construction drawings detail removal and relocation of lighting fixtures, disconnection of power to the Kardex filing system, installation of new convenience receptacles and data outlets with Cat 6A cabling throughout workstations, card reader and electric strike installation, and new low-voltage wiring from the basement telecom room. The project requires coordination among all trades, field verification of dimensions prior to construction, and compliance with cutting and patching responsibilities per specification section 017329.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAWING INDEX

COVERPAGE

ARCHITECTURAL

A0.01 LEGEND, SYMBOLS, DETAILS & CODE COMPLIANCE PLANS

A1.01 PARTIAL FIRST FLOOR DEMO PLAN

A1.11 PARTIAL FIRST FLOOR PLAN

A1.21 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN

A5.01 DOOR AND FINISH SCHEDULES AND DETAILS

HVAC

H0.01 LEGEND, DETAILS, SPECIFICATIONS AND GENERAL NOTES

H2.01 PARTIAL FIRST FLOOR PLAN - DUCTWORK

ELECTRICAL

E0.01 LEGEND AND SPECIFICATIONS

E1.01 PARTIAL FIRST FLOOR PLAN - DEMOLITION

E2.01 PARTIAL FIRST FLOOR PLAN - CONSTRUCTION

E2.02 PARTIAL BASEMENT FLOOR PLAN - CONSTRUCTION

358 West Jefferson Street Syracuse, NY 13202 p 315 | 671-2400 f 315 | 671-7891 www.kingarch.com

Argus Engineering 200 Boss Road Syracuse, NY 13211 p 315 | 475-6061 www.argusengineering.com

M A D

IS

O

N C

O U

N

TY

B U

IL

D

IN

G

C

LE

R K 'S

O

FF

IC

E

R

EN

O V

AT

IO

N

S

ISSUED FOR BID 03/13/2026

-1

1-

K

IN

G

+K

IN

G P

R O

JE

C

T N

U M

BE

R

138 NORTH COURT STREET

WAMPSVILLE, NY 13163

MADISON COUNTY

ARCHITECT'S CERTIFICATION

THE UNDERSIGNED CERTIFIES THAT TO THE BEST OF THEIR KNOWLEDGE, INFORMATION, AND

BELIEF, THE PLANS AND SPECIFICATIONS ARE IN ACCORDANCE WITH APPLICABLE

REQUIREMENTS OF THE NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING CODE,

THE NEW YORK STATE ENERGY CONSERVATION CONSTRUCTION CODE, AND THE

CONSTRUCTION STANDARDS OF THE EDUCATION DEPARTMENT. LOCATION MAP

crogers New Stamp

THE DRAWING COORDINATE SYSTEM IS USED TO STANDARDIZE NUMBERING FROM

DRAWING TO DRAWING AND FROM PROJECT TO PROJECT.

EACH SHEET SIZE IS BROKEN INTO COLUMNS AND ROWS STARTING AT THE BOTTOM

LEFT CORNER OF THE SHEET. EACH QUADRANT IS NUMBERED ACCORTING TO ITS

LOCATION ON THE GRID. THE ROW IS THE FIRST CHARACTER, AND IS ALWAYS A

LETTER. THE COLUMN IS THE SECOND CHARACTER, AND IS ALWAYS A NUMBER.

E1 E2 E3 E4 E5

D1 D2 D3 D4 D5

C1 C2 C3 C4 C5

D6

C6

B1 B2 B3 B4 B5 B6

A6A5A4A3A2A1

COLUMNS

R O W S

DRAWING COORDINATE SYSTEM:

E

D

C

B

A

E6

1 2 3 4 5 6

GRAPHIC SYMBOLS

W1

(HANDICAPPED

ICON)

(ROOM AREA)

101-1 V1

W1

S6

(INTERIOR

WINDOW ID)

(PARTITION

TYPE ID)

(DOOR ID)

(EXISTING

DOOR)

(EXISTING

WALL)

(DEMO WALL) (DEMO DOOR)

(DEMO OBJECT)

REFERENCE #

SHEET #

(REFERENCE MARKER)

DRAWING TITLE

Scale: 1/8" = 1'-0"

A5 (18point)

(9point)

(EXTERIOR

ELEVATIONS)

(BUILDING AND WALL

SECTIONS)

(DETAILS)

B1

A3.01

(INTERIOR

ELEVATIONS)

C1

A9.01

(EXTERIOR

WINDOW ID)

(LOUVER ID)

L1

A2 A3.02

0 10 20 FT

(NORTH ARROW)

(GRAPHIC SCALE)

D.1

(REVISIONS NOTE)

(DEMO NOTE)

(CONSTRUCTION

NOTE)

A

B

A

B

(CASEWORK OUTLINE

& BACKSPLASH

SOLID LINE )

(CABINET ABOVE

COUNTER LONG

DASHED LINE )

(CABINET BELOW

COUNTER SHORT

DASHED LINE )

(MATCH LINE)

MB

(MARKERBOARD)

ALIGN

A

B

C

D

A4.01

CLASSROOM

AREA : 782SF

(ROOM NUMBER)

(ROOM NAME)

(USE SPACE OBJECT

FOR ROOM NAMES)

A1

A3.01

D1

A9.01

ABBREVIATIONS

PAR parallel PC piece PCC precast concrete PCT porcelain tile PREFAB prefabricated PFN prefinished PLAM plastic laminate PLAS plaster PLMB plumbing(er) PL plate PNL panel PT paint PR pair PRES. TRT pressure treated PRF preformed PROVIDE furnish and install PSC prestressed concrete PSI pounds per square inch PTCLBD particle board PTN partition PWD, PLYWD plywood QT quarry tileRAD radius RAF resilient sports flooring RB rubber base RD roof drain RE reinforce(ed)(ing) REF reference REQ'D required REV revision(s) revised RFT rubber floor tile RFG roofing RM room RO rough opening RLT rubber landing tile RSL rubber stair landings RSR rubber stair risers RST rubber stair treads RT rubber tile RWC rainwater conductor S south SC stained concrete SCH, SCHED schedule SECT section SFCMU split face cmu SFPL sand float plaster SFT square foot SGT structural glazed facing tile SHT sheet SHTG sheathing SIM similar SIN square inch SK sink SPEC specification SQ square SSK service sink SST stainless steel ST steel STA station STD standard STF stiffener STN Stain STOR storage STRUCT structural SUSP suspend(ed) SVF sheet vinyl flooring SWC special wall coating SYD square yard

< angle @ at AB anchor bolt ACCESS accessory ACM asbestos containing material ACT acoustical ceiling tile AD access door ADJ adjustable AFF above finish floor AGG aggregate AL aluminum ALT alternate AP access panel APX or APPROX approximate ARCH architect(ural) ASB asbestos ASPH asphalt ASSY assembly AVG average AWP acoustic wall panel BAR barrier BD board BFBD bio-fiber board BLDG building BLK block BLKG blocking BM bench mark BOT bottom BO bottom of BR bumper rail BRK brick BS backsplash/both sides BSMT basement BUR built-up roof C courses CABT cabinet C/L center line CB catch basin CEM cement CC cubical curtain PCPL cement plaster (Portland) CFMF cold form metal framing CFT cubic foot CG corner guard CHB chalkboard CHR chair rail CI cast iron CJ control joint CL closet CLG ceiling CLR clear CMT ceramic mosaic tile CMU concrete masonry unit COL column CONC concrete COND conductive CONST construction CONT continue or continuous CONTR contractor CONV convector COORD coordinate CPT carpet CS countersunk CSWK casework CSWS countersunk wood screw CT ceramic tile CTR counter CW curtainwall CWT ceramic wall tile CYD cubic yard CX connection

DF drinking fountain DHW domestic hot water DIAM diameter DIM dimension DN down DIV division DPCO deck plate clean out DR door DTA dovetail anchor DTL or DET detail DTS dovetail anchor slot DWG drawing E east EA each EB expansion bolt EF each face EIFS exterior insulation finish system EL elevation ELEC electric ELEV elevator ENGR engineer EP epoxy paint EPDM ethylene propylene dienemonomer EQ equal EQP, EQUIP equipment ETC etcetera EWC electric watercooler EJ expansion joint EXCA excavation EXG existing EXP expansion EXT exterior FAB fabric FD floor drain FE fire extinguisher FEC fire extinguisher cabinet FF finish floor FG fiberglass FH fire hose FHMS flat head machine screw FHWS flat head wood screw FIN finish FIN FLR finished floor FLG flashing FLR floor FND foundation FO face of FP fireproof FR frame FRG fire rated glass FRP fiber reinforced panel FSTN fasten FTG footing FUR furred FUT future FWC fabric wall covering GA gauge GB grab bar GCT glazed ceramic tile GD grade GL glass GP gypsum GPDW gypsum drywall GV or GALV galvanized GMT glass wall tile GWT glazed wall tile

H RD half-round HDWR hardware HM hollow metal HOR horizontal HPC high performance coating HR hour HT or HGT height HVAC heating, ventilating & air conditioning HWD hardwoodID inside diameter IG insulating glass INS, INSUL insulation INSC insulating concrete INT interior INV invert ITFG insulated temp. float glass INFO information IWB interactive white board JST joist JC, JAN janitor's closet JT joint KCPL keene cement plaster KPL kickplate LIN linolium LKR locker LOC location LLH long leg horizontal LLV long leg vertical LWINSC light weight insulating concrete MAS masonry MAX maximum MB markerboard MECH mechanical MEMB membrane MEJ masonry expansion joint MET metal MFR manufacture(er)(ed)

MIL 1/1000"

MIN minimum MISC miscellaneous MO masonry opening MS machine screw MSP multi-spec paint MTD mounted MTG mounting MTL material MVEJ masonry veneer EJ # or NO number N north NAT naturals NEC necessary NIC not in contract NOM nominal NTS not to scale OC on center OD outside diameter OFCI owner furnished,contractor installed OH overhead door/opposite hand OPG opening OPP opposite

T tread TB tackboard T&B top and bottom TBD tackboard T&G tongue and groove T/C, TOC top of concrete T/F, TOF top of footing TOM top of masonry TOS top of steel TEMP temperature TERR, TZ terrazzo THD threshold THK thick(ness) TO top of TOIL toilet TP translucent panel TPO thermoplastic polyolefin TRANS transom TSL top of slab TW top of wall TYP typical UL Underwriter's Laboratories, Inc.

UNO unless noted otherwise VAT vinyl asbestos tile VB vapor barrier VCT vinyl composition tile VERT vertical VEST vestibule VIF verify in field VWF vinyl wall fabric VIN vinyl VWC vinyl wall covering W wide, width W/ with W/O without WCV wall covering WD wood WDV wood veneer finish WB white board WI wrought iron WIN window WS waterstop or weatherstripping WP wall protection WSCT wainscot WT weight WWM welded wire mesh

MATERIAL INDICATION

ACOUSTIC TILE

ALUMINUM

BRICK

CERAMIC TILE

CONCRETE

CONCRETE BLOCK

DRYWALL CEILING

EARTH UNDISTURBED

GLASS

GLAZED STRUCTURAL TILE

GRAVEL

GYPSUM DRYWALL

LIGHT WEIGHT CONCRETE

METAL STUD PARTITION

PLASTER

PLYWOOD

RIGID INSULATION

STEEL

WOOD BLOCKING

WOOD SHIM

WOOD FINISHED

PATCHING

EARTH DISTURBED

EXISTING CONSTRUCTION

REFLECTED CEILING SYMBOLS

ACOUSTIC CEILING

SYSTEM, 2X4 OR

2X2 AS SHOWN

ON DWG

DRYWALL/PLASTER

FLUO. DOWNLIGHT

2X2 FLUORESCENT

2X4 FLUORESCENT

1X4 FLUORESCENT

2X4 FLUO./EMERGENCY

2X2 FLUO./EMERGENCY

FLUO. DOWNLIGHT/EMERGENCY

EXIT LIGHT/CEILING MT.

EXIT LIGHT/WALL MT.

SPEAKER

TV OUTLET

OCCUPANCY SENSOR

FIRE DETECTOR

HVAC SUPPLY DIFFUSER

HVAC RETURN GRILLE

CURTAIN TRACK

EGGRATE GRILLE

S

TV

F

OS

FLUORESCENT STRIP

WALL SCONCE

LIGHT PENDANT BOWL

TYPICAL DIMENSIONS AT DOORS

TYPICAL DIMENSIONS

101-1

101-2

4"

1'-6"

3' -0

MARK DESCRIPTION DATE

ISSUED FOR BID

03/13/2026DRAWING DATE:

DIGITAL REPRODUCTIONS OF THESE

DRAWINGS SHALL NOT BE POSTED TO WEB

SITES WITHOUT THE DIRECT WRITTEN

PERMISSION OF THE ARCHITECT.

IT IS A VIOLATION OF THE STATE EDUCATION

LAW FOR ANY PERSON, UNLESS UNDER THE

DIRECTION OF A LICENSED ARCHITECT TO

ALTER THIS DOCUMENT IN ANY WAY.

ALTERATIONS MUST HAVE THE SEAL AFFIXED

ALONG WITH THE DESCRIPTION OF THE

ALTERATION AND SIGNATURE AND DATE.

COPYRIGHT ©.

M A

D

IS

O N

C O

U N

TY

B

U

IL

D

IN

G

C

LE

R

K 'S

O

FF

IC

E

R E

N O

VA

TI

O N

S

N O

R

TH

C O

U R

T

ST

R E

ET

W

AM

PS

VI

LL

E , N

Y

26-11-9186KING + KING PROJ. NO.:

A0.01

SCALE:

DRAWING TITLE:

Sheet Scale

LEGEND, SYMBOLS,

DETAILS & CODE

COMPLIANCE

A

B

C

D

E

1 2 3 4 5 6

WOMEN

119A

ELEC.

MEN

CHASE

CHASE

OFFICE

OFFICE

OFFICE

WORK RM.

CORRIDOR

OFFICE

OFFICE

CONFERENCE

OFFICE

STORAGE

OFFICE

SUPPLIES

OFFICE

STORAGE

OFFICE

111B

OFFICE

111C

OFFICE

111D

OFFICE

ELEV.

113A

ADA TOILET

JAN.

ADA TOILET

CHASES2-1

STAIR 2

130A

VEST.

CONFERENCE

130B

OFFICE

130A

OFFICE

CHASE

DMV LOBBY

LOBBY

S1-1

STAIR

RECEPTION

111A

OFFICE

PUBLIC WORK AREA

A

C

D

E

H

B

F

1 HR. FIRE RATED PARTITION

SMOKE PARTITION

2 HR. FIRE BARRIER

RATED PARTITION LEGEND:

EMERGENCY EGRESS LEGEND:

ALTERATION L1

MINIMAL / NO WORK

CONSTRUCTION TYPE DESIGNATIONS:

ALTERATION L2

EXIT WIDTH PER OPENING36" E.W.

36" E.W.

EACH

72" E.W.

72" E.W.

FIRST FLOOR CODE COMPLIANCE PLAN

Scale: 3/32" = 1'-0"

C1 A0.01

CODE REVIEW SUMMARY

2025 EXISTING BUILDING CODE OF NEW YORK STATE

Chapter 8 - Alterations Level 2: All new work shall comply with NYS Bldg. Code.

2025 BUILDING CODE OF NEW YORK STATE

Building Use & Occupancy Classification:

304.1 Business, Group B

Table 601 “Fire-Resistance Rating For Building Elements” = 0 hours for all structural elements.

602.2: Construction Type: Type II-B, Sprinkler System Not Required or Provided.

Occupancy and Egress Summary

1004.1 No change to existing space usage or occupant load.

County Clerk Suite: Level 1 Business Area = 4,510 SF/150 = 31 occupants (2,370 SF in work area = 16 occupants in work area)

1005.3.2 Egress components: 31 occupants x .2" = 6.2". Use 36" min. for new doors.

T1006.2.1 Maximum common path of travel distance = 75'-0".

1 exit allowed from space where < 50 occupants and < 75'-0" common path of travel distance.

Only 1 exit required from Public Work Area Rm.123: 890 SF / 150 = 6 Occupants

T1017.2 Exit Access Travel Distance:

200’-0” for B occupants without automatic sprinkler system

T1020.2 Corridors: 1 hour fire resistance rated.

COMMON PATH OF

TRAVEL = 54'-0" (COMPLIES)

EXIT ACCESS TRAVEL

DISTANCE = 117'-0" (COMPLIES)

EXIT ACCESS TRAVEL

DISTANCE = 100'-0" (COMPLIES)

S2-B

STAIR 2

S1-B

STAIR 1

B-6

WOMEN

B-7

MEN

B-10

JANITOR

B-8

ELEV. MACH. RM.B-15

CORRIDOR

B-11

CORRIDOR

B-13

OFFICE

B-14

OFFICE

TEL/ELEC.

REMOTE STORAGE

B-3

MAINTENANCE

B-1

MECHANCAL

B-2-1

IT SERVER RM.

B-2-2

IT OFFICE

B-2-8

CONFERENCE RM.

B-2-7

WAITING RM.

B-2-6

OFFICE #3

B-2-5

OFFICE #2

B-2-4

OFFICE #1

B-2-3

STORAGE

MECH. RM.

STORAGE

CONFERENCE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CONFERENCE

CHASE

B-28A

OFFICE

B-36

BREAK RM.

B-35

OFFICE

B-31

STORAGE

B-32

STOR.

B-33

STOR.

B-34

OFFICE

B-28B

OFFICE

B-29A

CORRIDOR

B-6A

BREAK RM.

IT RACK

LIEBERT UNIT

SERVICE BYPASS LEIT-2 LEIT-1

D

IS

C . S

W

D

AY

A U

TO

IT

IT

S H

E

LF

TEMP.

COOLING

UNIT

IT

RACKS

SHELF

B

MAINTENANCE

A

MAINTENANCE

B-4

CORRIDOR

A

C

D

E

H

B

F

BASEMENT CODE COMPLIANCE PLAN

Scale: 3/32" = 1'-0"

A1 A0.01

" E

.W

36" E.W.

MARK DESCRIPTION DATE

ISSUED FOR BID

03/13/2026DRAWING DATE:

DIGITAL REPRODUCTIONS OF THESE

DRAWINGS SHALL NOT BE POSTED TO WEB

SITES WITHOUT THE DIRECT WRITTEN

PERMISSION OF THE ARCHITECT.

IT IS A VIOLATION OF THE STATE EDUCATION

LAW FOR ANY PERSON, UNLESS UNDER THE

DIRECTION OF A LICENSED ARCHITECT TO

ALTER THIS DOCUMENT IN ANY WAY.

ALTERATIONS MUST HAVE THE SEAL AFFIXED

ALONG WITH THE DESCRIPTION OF THE

ALTERATION AND SIGNATURE AND DATE.

COPYRIGHT ©.

M A

D

IS

O N

C O

U N

TY

B

U

IL

D

IN

G

C

LE

R

K 'S

O

FF

IC

E

R E

N O

VA

TI

O N

S

N O

R

TH

C O

U R

T

ST

R E

ET

W

AM

PS

VI

LL

E , N

Y

26-11-9186KING + KING PROJ. NO.:

A1.01

SCALE:

DRAWING TITLE:

Sheet Scale

PARTIAL FIRST FLOOR

DEMO PLAN

A

B

C

D

E

1 2 3 4 5 6

CHASECHASE

PR INTER

( N.I .C. )

PR INTER

( N.I .C. )

WO RK STAT IO N

( N.I .C. )

5 7 9 15 17 19

A

C

D

E

H

6 8321 16 1812

B

F

FIRST FLOOR KEY PLAN

Scale: 1/32" = 1'-0"

A5 A1.01

B4

A1.01

119A

ELEC.

MEN

CHASE

CHASE

OFFICE

OFFICE

OFFICE

WORK RM.

CORRIDOR

OFFICE

CONFERENCE

113A

ADA TOILET

JAN.

ADA TOILET

130B

OFFICE

PUBLIC WORK AREA

PARTIAL FIRST FLOOR DEMO PLAN

Scale: 1/4" = 1'-0"

B4 A1.01

NORTH

M.1

M.1

L.1

L.1

M.2

L.1

L.1

L.1L.1

K.2

K.1

(UNDER

MACHINE)

K.1

(UNDER

MACHINE)

D.1 K.4

D.1

K.3

K.3K.3 K.5

K.5

K.5

M.3

(2) 4" CONDUIT

(HATCH)

(HATCH)

K.3

15 17 1916 18

GENERAL DEMOLITION NOTES DEMOLITION NOTES

D. INTERIOR WALL AND FINISH DEMOLITION

GN-1

THE GENERAL CONTRACTOR SHALL REFER TO SPECIFICATION SECTION 011100

"SUMMARY OF WORK" FOR A GENERAL DESCRIPTION OF THE SCOPE OF WORK

ASSOCIATED WITH DEMOLITION.

D.1

REMOVE ENTIRE METAL PREFABRICATED WALL SYSTEM FULL HEIGHT,

INCLUDING ALL WALL MOUNTED ITEMS, DOORS, AND WINDOWS

COMPLETE. EXISTING COLUMNS AND BEAMS TO REMAIN. PATCH &

MATCH ADJACENT SURFACES.

G. CEILING DEMOLITION

GN-2

THE GENERAL CONTRACTOR SHALL REFER TO SPECIFICATION SECTION 017329

"CUTTING & PATCHING" FOR DETERMINING RESPONSIBILITY OF CUTTING AND

PATCHING OF EXISTING AND/OR NEW WALLS, FLOORS, ROOFS, ETC. THE GENERAL

CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING AND COORDINATING WITH

ELECTRICAL DRAWINGS FOR ANY ADDITIONAL DEMOLITION WORK ASSOCIATED

WITH CUTTING & PATCHING.

(REFER TO REFLECTED CEILING PLAN FOR CEILING NOTES)

K. FLOOR DEMOLITION

GN-3

PENETRATIONS, OPENINGS, CHASES, ETC. FOR MECHANICAL, PLUMBING,

ELECTRICAL, AND ROOFING WORK ARE SHOWN FOR COORDINATION PURPOSES

ONLY. DIMENSIONS AND LOCATIONS MUST BE VERIFIED AND COORDINATED WITH

OTHER TRADES PRIOR TO CONSTRUCTION.

K.1

REMOVE CARPET, BASE, AND PAD COMPLETE INCLUDING ANY

TRANSITION STRIPS OR OTHER EDGING MATERIALS BACK TO

NEAREST FULL EXPOSED CARPET TILE. REMOVE REMAINING

ADHESIVE WITH SOLVENT ACCEPTABLE TO ARCHITECT AND NEW

FLOORING MANUFACTURER. PREPARE SLAB FOR NEW FINISH AS

SCHEDULED AND IN MANNER REQUIRED BY NEW FINISH

MANUFACTURER. INSTALL NEW CARPET TILE (CPT-1) USING FULL

CARPET TILES.

GN-4

ALL EXISTING STRUCTURE, FINISHES, AND EQUIPMENT TO REMAIN SHALL BE

PROTECTED FROM DAMAGE. EXISTING STRUCTURE, FINISHES, AND EQUIPMENT

DAMAGED OR REMOVED DUE TO DEMOLITION OR NEW WORK SHALL BE REPAIRED

AND/OR PATCHED WITH MATCHING CONSTRUCTION AND FINISHES.

K.2

REMOVE CERAMIC TILE FLOOR, BASE, BOND COAT, AND MORTAR BED

COMPLETE TO CONCRETE SLAB. PROTECT AND PREPARE SLAB FOR

NEW FINISH AS SCHEDULED AND IN MANNER REQUIRED BY NEW

FINISH MANUFACTURER. INSTALL SELF-LEVELING UNDERLAYMENT

FLUSH WITH ADJACENT CONCRETE SLAB.

GN-5 REFER TO DRAWING A0.01 FOR SYMBOLS THAT APPLY TO THIS SHEET AS WELL AS

DEMOLITION DRAWINGS. K.3

REMOVE CARPET AND BASE COMPLETE IN LOCATION OF NEW WALLS,

AND INSIDE WORK RM., BACK TO NEAREST FULL CARPET TILE JOINT.

RE-LAY CARPET USING FULL CARPET TILES IN BREAK RM.

K.4

REMOVE CARPET TILES COMPLETE IN LOCATION OF EXISTING WALLS,

BACK TO NEAREST FULL CARPET TILE JOINT. RE-LAY CARPET USING

FULL CARPET TILES ALIGNING WITH ADJACENT CARPET TILE JOINTS.

K.5

REMOVE CARPET TILES COMPLETE IN LOCATION OF EXISTING AND

NEW CASEWORK, BACK TO NEAREST FULL CARPET TILE JOINT.

RE-LAY CARPET USING FULL CARPET TILES ALIGNING WITH

ADJACENT CARPET TILES JOINTS AND CUT AROUND NEW CASEWORK

AS REQUIRED.

L. MILLWORK DEMOLITION

L.1 REMOVE BASE CABINETS, COUNTERTOPS AND ALL ASSOCIATED

CONSTRUCTION COMPLETE.

M. MISCELLANEOUS DEMOLITION

M.1

REMOVE KARDEX MACHINE AND ALL ATTACHMENTS COMPLETE.

DISPOSE OF PROPERLY AS PER SPECIFICATIONS. THE MACHINE'S

FOOTPRINT IS APPROX. AS SHOWN, AND EACH MACHINE IS APPROX.

12'-0" TALL.

M.2 COUNTY FORCES WILL REMOVE EXISTING SYSTEM FURNITURE

(CUBICLES) AS SHOWN .

M.3

CORE DRILL HOLES FOR NEW DATA CONDUIT. COORDINATE WITH

ITEMS IN SPACE BELOW AND NEW WALL ENCLOSURE LAYOUT. PRIOR

TO CORE DRILLING, COORDINATE WITH OWNER'S SPECIAL TESTING

AGENCY TO PREFORM A SCAN OF THE CONCRETE SLAB TO LOCATE

EXISTING REINFORCING BARS (REBAR) IN SLAB. COORDINATE CORE

DRILL LOCATIONS TO AVOID ANY EXISTING REBAR IN TOP HALF OF

THE SLAB. IF UNAVOIDABLE, CONTACT ARCHITECT TO ALLOW UP TO 1

REBAR IN EACH DIRECTION (EAST-WEST OR NORTH-SOUTH) TO BE IN

CORE LOCATION. AVOID CORING THROUGH THE CONCRETE 'DROP

PANEL' AT TOP OF COLUMN. NOTIFY ARCHITECT IF ANY

DISCREPANCIES ARE FOUND.

A

C

D

E

H

B

F

03/13/2026DRAWING DATE:

DIGITAL REPRODUCTIONS OF THESE

DRAWINGS SHALL NOT BE POSTED TO WEB

SITES WITHOUT THE DIRECT WRITTEN

PERMISSION OF THE ARCHITECT.

IT IS A VIOLATION OF THE STATE EDUCATION

LAW FOR ANY PERSON, UNLESS UNDER THE

DIRECTION OF A LICENSED ARCHITECT TO

ALTER THIS DOCUMENT IN ANY WAY.

ALTERATIONS MUST HAVE THE SEAL AFFIXED

ALONG WITH THE DESCRIPTION OF THE

ALTERATION AND SIGNATURE AND DATE.

COPYRIGHT ©.

M A

D

IS

O N

C O

U N

TY

B

U

IL

D

IN

G

C

LE

R

K 'S

O

FF

IC

E

R E

N O

VA

TI

O N

S

N O

R

TH

C O

U R

T

ST

R E

ET

W

AM

PS

VI

LL

E , N

Y

26-11-9186KING + KING PROJ. NO.:

A1.11

SCALE:

DRAWING TITLE:

Sheet Scale

PARTIAL FIRST FLOOR

PLAN

A

B

C

D

E

1 2 3 4 5 6

119A

ELEC.

MEN

CHASE

CHASE

OFFICE

OFFICE

OFFICE

WORK RM.

CORRIDOR

OFFICE

CONFERENCE

113A

ADA TOILET

JAN.

W-1

W-1

W-1

117 119W-1

PUBLIC WORK AREA

PRINTER

(N.I.C.)

PRINTER

(N.I.C.)

WORK STATION

(N.I.C.)

PARTIAL FIRST FLOOR PLAN

Scale: 1/4" = 1'-0"

B4 A1.11

NORTH

KEYED CONSTRUCTION NOTES

INSTALL (2) 4" GALV. STEEL DATA CONDUITS FROM BASEMENT CEILING SPACE, EXTENDING THROUGH LEVEL 1 FLOOR AND UP TO CEILING CAVITY OF LEVEL 1 SPACE. REFER TO DEMOLITION NOTE M.3 ON A1.01 FOR ADDITIONAL CORE DRILL NOTES.

3" DIA. COUNTER GROMMET. CONFIRM FINAL LOCATIONS WITH OWNER.

PATCH & MATCH HOLE IN EXISTING WALL W/ 5/8" GPDW & BLOCKING AS REQUIRED. PAINT TO MATCH ADJACENT WALL.

REMOVE PARTIAL EXISTING CARPET TILES BACK TO NEAREST FULL CARPET TILE JOINT. INSTALL NEW CARPET TILE (CPT-1) WHERE CERAMIC TILE WAS REMOVED. REFER TO DEMO NOTES FOR ADDITIONAL NEW CARPET TILE INFILLS RELATED TO

NEW WALL AND CASEWORK LOCATIONS.

PATCH & MATCH DRYWALL 5/8" GPDW WHERE ELECTRICAL EQUIPMENT IS REMOVED. REFER TO DRAWING E1.01.

14'-912" +/-

1"

'-8

1 4"

15'-014"

1' -8

C A

B

3' -4

K N

E E

S

PA

C E

3' -2

3 4"

A D

A

TR

A N

S

3' -4

K N

E E

S

PA

C E

1' -8

C A

B

2"

5' -0

W O

R K

S

PA

C E

1' -8

C A

B

4' -0

3 4"

K N

E E

S

PA

C E

4' -0

3 4"

K N

E E

S

PA

C E

2"

1' -8

C A

B

2" 1' -8

C A

B

5' -3

3 4"

K N

E E

S

PA

C E

1' -8

C A

B

R E

S E

A R

C H

D E

S K

S (N

.I.

C

P

R

IN

TE

R

(N .I.

C

5' -0

W O

R K

S

PA

C E

5' -8

3 4"

W O

R K

S

PA

C E

5' -8

3 4"

W O

R K

S

PA

C E

5' -0

W O

R K

S

PA

C E

3' -8

3 4"

PA

S

S P

O R

T

CENTER NEW WALL

ON WINDOW

MULLION

CENTER NEW WALL ON

WINDOW MULLION

CENTER NEW DOOR ON

EXISTING DOOR

A

LI

G N

CENTER NEW WALL

ON WINDOW

MULLION

1' -1

1"

4' -0

1'

-0

4' -0

1'

-0

4' -0

1'

-1

4" 1'

-0

S3a

S3a

S3a

S3a

S3a

S3g

S3g

S3g

7'-1114"8'-0"4'-9"

E5 A5.01

@ WORKSTATION

CABINET

E3 A5.01

@ COUNTER

E1 A5.01

@ ADA TRANS.

C1 A5.01

D5 A5.01

C5 A5.01

C2 A5.01

A2 A5.01

3'-0"2'-112"8'-10" 4'-0"

ALIGN NEW WALLS WITH

FACE OF EXISTING

COLUMN ENCLOSURE,

TYP.

1" 1" 4"

1" 1" 4"

1"

FACE OF COUNTER ANGLES

TO MEET 'WATERFALL

EDGE', TYP. EA. SIDE OF ADA

TRANS. COUNTER

1'-4"

4' -0

A D

A W

O R

K C

O U

N T.

'-0

W O

R K

C O

U N

TE

R

1"

TYP. 3 LOCATIONS

TA

B

LE

(N

.I.

C

D2 A5.01

GENERAL CONSTRUCTION NOTES

1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION.

2.

GENERAL CONTRACTOR TO CUT OPENINGS IN WALLS, FLOORS, AND CEILINGS FOR

INSTALLATION OF M/E/P WORK WHERE NECESSARY. REFER TO M/E/P DRAWINGS FOR

QUANTITY AND LOCATIONS. COORDINATE WITH M/E/P CONTRACTORS FOR SIZE OF

OPENINGS.

3.

GC TO PATCH WALLS, FLOORS AND CEILINGS WHERE M/E/P EQUIPMENT IS BEING

REMOVED. REFER TO M/E/P DRAWINGS FOR QUANTITY AND LOCATIONS. PATCH AS

REQUIRED TO RECEIVE NEW FINISHES AND FIRE RATINGS AS APPLICABLE.

CHASECHASE

5 7 9 15 17 19

A

C

D

E

H

6 8321 16 1812

B

F

FIRST FLOOR KEY PLAN

Scale: 1/32" = 1'-0"

A5 A1.11

B4

A1.11

15 1716 18

A

C

D

E

H

B

F

GENERAL NOTES:

1. ALL PARTITIONS ARE DIMENSIONED FROM FACE OF STEEL STUD OR FACE OF BLOCK, UNLESS OTHERWISE NOTED.

2. ALL STEEL STUDS SHALL HAVE 1 LAYER GPDW EACH SIDE, UNLESS NOTED OTHERWISE.

3. EXTEND ALL PARTITIONS, STUDS, AND GPDW TO DECK ABOVE, UNLESS NOTED OTHERWISE.

4. ALL DRYWALL TO BE 5/8” THICK, UNLESS NOTED OTHERWISE.

5. WHERE UNBALANCED DRYWALL SYSTEM IS USED, ADDITIONAL LAYER IS ON SYMBOL SIDE.

6. SEE SPECIFICATIONS FOR THICKNESS OF SOUND BATT AND INSULATION.

7. SEE FINISH SCHEDULE FOR FINISHES INCLUDING PAINT, VENEER PLASTER, TILE, VINYL WALL COVERINGS, ETC.

8. REFER TO CODE COMPLIANCE DRAWINGS FOR LOCATION OF RATED WALLS.

9. WHERE GPDW DOES NOT EXTEND FROM FLOOR TO DECK ON BOTH SIDES OF METAL STUD WALLS, PROVIDE STEEL

CHANNEL AND CLIP ANGLE BRIDGING AS SPECIFIED AT 4'-0” MAXIMUM ON CENTER, FULL HEIGHT OF ASSEMBLY. WHERE STUD KNOCKOUTS DON'T ALIGN OR ARE BLOCKED BY OTHER CONSTRUCTION, PROVIDE METAL STRAPPING AS

SPECIFIED ON BOTH FACES OF STUDS AT SAME SPACING.

10. AT DEFLECTION TRACK LOCATIONS OF RATED WALLS, PROVIDE CHANNEL AND CLIP BRIDGING OR STRAPPING 1'-0”

MAXIMUM BELOW STRUCTURE ABOVE.

PARTITION TYPES

PARTITION TYPES

4 7/8" 3 5/8" METAL STUDS

1 LAYER 5/8" GPDW TYPE 'X' ON BOTH SIDES

SOUND BATT INSULATION BETWEEN STUDS

STC: 49

EXTEND ALL GPDW TO 6" ABOVE CEILING, EXTEND

FRAMING TO STRUCTURE ABOVE

S3a

414" 3 5/8" METAL STUDS

1 LAYER 5/8" GPDW TYPE 'X' ON ONE SIDE

EXTEND ALL WALLS TO 6" ABOVE CEILING

S3g

03/13/2026DRAWING DATE:

DIGITAL REPRODUCTIONS OF THESE

DRAWINGS SHALL NOT BE POSTED TO WEB

SITES WITHOUT THE DIRECT WRITTEN

PERMISSION OF THE ARCHITECT.

IT IS A VIOLATION OF THE STATE EDUCATION

LAW FOR ANY PERSON, UNLESS UNDER THE

DIRECTION OF A LICENSED ARCHITECT TO

ALTER THIS DOCUMENT IN ANY WAY.

ALTERATIONS MUST HAVE THE SEAL AFFIXED

ALONG WITH THE DESCRIPTION OF THE

ALTERATION AND SIGNATURE AND DATE.

COPYRIGHT ©.

M A

D

IS

O N

C O

U N

TY

B

U

IL

D

IN

G

C

LE

R

K 'S

O

FF

IC

E

R E

N O

VA

TI

O N

S

N O

R

TH

C O

U R

T

ST

R E

ET

W

AM

PS

VI

LL

E , N

Y

26-11-9186KING + KING PROJ. NO.:

A1.21

SCALE:

DRAWING TITLE:

Sheet Scale

PARTIAL FIRST FLOOR

REFLECTED CEILING

PLAN

A

B

C

D

E

1 2 3 4 5 6

WOMEN

119A

ELEC.

MEN

CHASE

CHASE

OFFICE

OFFICE

OFFICE

WORK RM.

CORRIDOR

OFFICE

OFFICE

CONFERENCE

ELEV.

113A

ADA TOILET

JAN.

ADA TOILET

130B

OFFICE

130A

OFFICE

S1-1

STAIR

PUBLIC WORK AREA

NORTH

PARTIAL FIRST FLOOR REFLECTED CEILING PLAN

Scale: 1/4" = 1'-0"

B4 A1.21

CAREFULLY REMOVE ACOUSTIC CEILING TILE (ACT) SYSTEM (INCLUDING GRID) ONLY AS NEEDED TO ALLOW FOR NEW MEP OR NEW WALL INSTALLATION. REINSTALL ACT SYSTEM, PATCH AND MATCH, WHEN WORK IS COMPLETE AND INSPECTED. TEMPORARILY SUSPEND LIGHTING, DIFFUSERS, AND OTHER DEVICES IF REQUIRED.

KEY NOTES

10'-0"

(MATCH

EXIST.)

12'-0"

(MATCH

EXIST.)

10'-0"

12'-0"

(MATCH

EXIST.)

12'-0"

(MATCH

EXIST.)

CHASECHASE

5 7 9 15 17 19

A

C

D

E

H

6 8321 16 1812

B

F

FIRST FLOOR KEY PLAN

Scale: 1/32" = 1'-0"

A5 A1.21

B4

A1.21

GENERAL RCP NOTES

1. REFER TO SHEET A0.00 FOR REFLECTED CEILING PLAN SYMBOLS.

2. REFER TO FINISH LEGEND AND SPECIFICATIONS FOR CEILING FINISHES AND SYSTEMS.

3. INSTALL ALL CEILING MOUNTED EQUIPMENT IN THE CENTER OF CEILING TILE.

4. COORDINATE CEILING MOUNTED EQUIPMENT, FIXTURE SIZES AND LOCATION WITH

HVAC/ELECTRICAL/PLUMBING DRAWINGS.

5. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES BETWEEN REFLECTED CEILING

PLAN AND HVAC/ELECTRICAL/FIRE PROTECTION/PLUMBING DRAWINGS.

6. CENTER GRID IN THE N,S,E &W DIRECTIONS OF ALL SPACES UNLESS OTHERWISE NOTED.

7.

DAMAGE TO ANY CEILING TILE OR GRID THAT IS SCHEDULED TO BE REMOVED AND

REINSTALLED SHALL BE REPLACED WITH THE SAME PRODUCT BY THE G.C. PRIOR TO

REINSTALLATION.

8. NEW CEILINGS TO BE INSTALLED AT EXISTING CEILING HEIGHT UNLESS OTHERWISE

NOTED.

15 17 1916 18

A

C

D

E

B

F

03/13/2026DRAWING DATE:

DIGITAL REPRODUCTIONS OF THESE

DRAWINGS SHALL NOT BE POSTED TO WEB

SITES WITHOUT THE DIRECT WRITTEN

PERMISSION OF THE ARCHITECT.

IT IS A VIOLATION OF THE STATE EDUCATION

LAW FOR ANY PERSON, UNLESS UNDER THE

DIRECTION OF A LICENSED ARCHITECT TO

ALTER THIS DOCUMENT IN ANY WAY.

ALTERATIONS MUST HAVE THE SEAL AFFIXED

ALONG WITH THE DESCRIPTION OF THE

ALTERATION AND SIGNATURE AND DATE.

COPYRIGHT ©.

M A

D

IS

O N

C O

U N

TY

B

U

IL

D

IN

G

C

LE

R

K 'S

O

FF

IC

E

R E

N O

VA

TI

O N

S

N O

R

TH

C O

U R

T

ST

R E

ET

W

AM

PS

VI

LL

E , N

Y

26-11-9186KING + KING PROJ. NO.:

A5.01

SCALE:

DRAWING TITLE:

Sheet Scale

DOOR AND FINISH

SCHEDULES AND

DETAILS

A

B

C

D

E

1 2 3 4 5 6

FINISH LEGEND

FINISH MANUFACTURER STYLE COLOR NOTES

ACOUSTIC CEILING TILE

ACT-1 USG MARS ACOUSTICAL PANELS, 2' X 2' WHITE SLT EDGE PROFILE (ANGLED TEGULAR) w/ CLIMAPLUS PERFORMANCE 15/16" GRID, WHITE.

CARPET

CPT-1 MILLIKEN NORDIC STORIES - AMERICAS, TECTONIC TTC124-94 SANDPIPER COLOR/PATTERN TO MATCH EXISTING CARPET TILE

PAINT

PT-1 (FIELD) SHERWIN WILLIAMS MATCH EXISTING MATCH EXISTING

PT-2 (DOOR FRAMES) SHERWIN WILLIAMS MATCH EXISTING MATCH EXISTING

PLASTIC LAMINATE

PL-1 WILSONART LAMINATE 7928-38 'CASTLE OAK'

PL-2 WILSONART LAMINATE D25-60 'ATLANTIS'

RUBBER BASE

RB-1 ROPPE PINNACLE SERIES, 4" COVE BASE 100 BLACK

SEE SPECIFICATION 096513

SOLID SURFACING

SS-1 CORIAN SOLID SURFACE, 2 CM CARRARA LINO

--- NO FINISHES

EXG EXISTING FINISH TO REMAIN

EXPOSED

GENERAL FINISH NOTES

1. PAINT ALL NEW WALLS PT-1 TO MATCH EXISTING. INSTALL RB-1 TO MATCH EXISTING.

2. PATCH & MATCH ALL EXISTING CEILING ACT-1 SYSTEM AS NOTED ON REFLECTED CEILING PLAN.

3. PATCH & MATCH ALL EXISTING CARPET CPT-1 SYSTEM AS NOTED ON DEMO AND FLOOR PLANS.

4. PAINT ALL NEW DOOR FRAMES PT-2 TO MATCH EXISTING.

DOOR SCHEDULE

DOOR FRAME ASSEMBLY HDWR

DOOR NO. TYPE WIDTH HEIGHT THICK. MTL TYPE HEAD DETAIL JAMB DETAIL MTL LABEL SET # NOTES

FIRST FLOOR

117 P-F 6'0" 8'8" 1 3/4" WD A B3 / A5.01 A3 / A5.01 HM - 01 1

119 F 3'0" 8'8" 1 3/4" WD A B3 / A5.01 A3 / A5.01 HM - 02 1

120 F 3'0" 8'8" 1 3/4" WD A B3 / A5.01 A3 / A5.01 HM - 03 1

123 P-F 6'0" 8'8" 1 3/4" WD A B3 / A5.01 A3 / A5.01 HM - 04 1

NOTES

1. PAINT DOOR FRAMES PT-2 TO MATCH EXISTING.

A

2" AS SCHD. 2"

A S

S C

H D

2"

DOOR FRAMES

1/4" = 1'-0"

A4 A5.01

F

AS SCHD.

DOOR TYPES

1/4" = 1'-0"

A5 A5.01

A S

S C

H D

PARTITION AS SCHEDULED

DOUBLE METAL

STUDS @ JAMB

METAL STUD ANCHOR,

3 PER JAMB

HM DOOR FRAME

SEALANT TYP. ALL SIDES

58"

VA

R

IE

S

2"

1 2" T

Y P

AT

B

O

TH

S

ID

E S

V.

I.F

TYP. HM FRAME JAMB DETAIL

Scale: 1 1/2" = 1'-0"

A3 A5.01

5 8"

METAL STUD

VARIES

HM DOOR FRAME

PARTITION AS SCHEDULED

SEALANT TYP. ALL SIDES

1 15/16"1 15/16"

2"

TYP. HM FRAME HEAD DETAIL

Scale: 1 1/2" = 1'-0"

B3 A5.01

INTERIOR WINDOW TYPES

1/4" = 1'-0"

A6 A5.01

W-1

2" 3'-8" 2"

2" 3'

-0

2"

3' -4

4'-0"

4' -6

HOLLOW METAL FRAME. PAINT

PT-2 BOTH SIDES, TYP.

1/4" CLEAR TEMPERED SAFETY

GLASS

BASE RB-1, TYP.

414"

2' -6

SOLID SS-1 EDGES, TYP.

2" X 3" X 1/4" ALUMINUM ANGLE

SUPPORT MAX. 4'-0" O.C. BASIS OF

DESIGN “RAKKS EH-1824” (FINISH:

MATTE SILVER POWDER COAT)

214"

PUBLIC WORK

RM. SIDE

OFFICE

SIDE

3/4" PLYWOOD WITH

3/4” (2 CM) SS-1

COUNTERTOP WITH

EASED EDGES, ALSO

RETURN AT EACH

END BACK TO

ADJACENT

CASEWORK (SEE

ELEVATIONS)

1'-2"2'-6"

2' -2

SS-1 RETURN BEYOND, TYP. EA.

SIDE

RETURN SS-1 AT

BASE

PLANE OF BASE ALIGNS

WITH ADJACENT

COUNTERTOP SECTIONS

3'-1014"

3/4" PLYWOOD WITH 3/4” (2

CM) SS-1 COUNTERTOP

WITH EASED EDGES

4"

2X4 WD. BLOCKING, TYP.

CABLE CHASES IN ALL FRAMING, TYP.

3/4" PLYWOOD W/ HARDWOOD EDGE

BAND AND PL-1 FINISH ON ALL

SURFACES ON OFFICE SIDE, TYP.

SS-1 COUNTER EXTENSION

BEYOND W/ SS-1 EDGES, TYP.

WORKSTATION COUNTER DETAIL (ADA)

Scale: 1 1/2" = 1'-0"

E1

A5.01 NOTE: REFER TO DETAIL E3/A5.01 FOR ADDITIONAL NOTES.

BASE RB-1, TYP.

2"

2' -6

2" X 3" X 1/4" ALUMINUM ANGLE SUPPORT MAX.

4'-0" O.C. BASIS OF DESIGN “RAKKS EH-1824”

(FINISH: MATTE SILVER POWDER COAT). REFER

TO INTERIOR ELEVATION FOR LOCATION.

2X4 WD. BLOCKING, TYP.

4"

8"

PUBLIC WORK

RM. SIDE

OFFICE

SIDE

5'-4" PRIVACY SCREEN BEYOND

3/4" PLYWOOD W/

PL-1 FINISH, TYP.

1'-2"2'-6"

CABLE CHASES IN ALL FRAMING, TYP.

2"

1' -2

2"

3/4" PLYWOOD VERT. PANEL

W/ PL-2 FINISH

1'-0"

5' -0

P

R

IV

A C

Y S

C R

E E

N B

E Y

O N

D

PRIVACY SCREEN BEYOND: 3

LAYERS OF PLYWOOD (TOTAL

2" THICKNESS) VERT. PANEL

W/ HARDWOOD EDGE BAND

AND PL-1 FINISH ON ALL

EDGES AND SURFACES, TYP.

SOLID SS-1 EDGES, TYP.

SS-1 RETURN BEYOND, TYP. EA.

SIDE

REFER TO INT. ELEV. FOR REMOVEABLE

PANEL LOCATIONS, TYP.

3/4" PLYWOOD W/ HARDWOOD EDGE

BAND AND PL-1 FINISH ON ALL SURFACES

ON OFFICE SIDE, TYP.

1/2" X 1-1/2" SOLID OAK TRIM,

w/ 1/4" CHAMFER, TYP. @

PERIMETER OF PANEL

2"

3/4" PLYWOOD WITH 3/4” (2 CM)

SS-1 COUNTERTOP WITH EASED

EDGES, TYP.

3/4" PLYWOOD W/ HARDWOOD EDGE

BAND AND PL-1 FINISH ON ALL

SURFACES ON OFFICE SIDE, TYP.

3/4" X 2-1/2" SOLID OAK TRIM,

w/ 1/4" CHAMFER, TYP. @

PERIMETER OF PANEL

3/4" PLYWOOD W/

PL-2 FINISH, TYP.

3/4" PLYWOOD W/

PL-2 FINISH, TYP.

3/4" X 3/4" SOLID OAK TRIM, w/

1/4" CHAMFER, TYP. @

PERIMETER OF PANEL

134"

2"

SS-1 COUNTER EXTENSION

BEYOND W/ SS-1 EDGES, TYP.

WORKSTATION COUNTER DETAIL

Scale: 1 1/2" = 1'-0"

E3 A5.01

BASE RB-1, TYP.

2"

2' -6

4"

6"

PUBLIC WORK

RM. SIDE

OFFICE

SIDE

4'-2"

1'-2"2'-6"

2"

1' -2

2 x WD.BLK

DRAWER SLIDES, TYP.

2'-0" 214"

2'-5"

2"

8"

8"

1' -2

4"

2"

3/4" PLYWOOD DRAWER FRONT

W/ HARDWOOD EDGE BAND AND

PL-1 FINISH, TYP.

HARDWOOD DRAWER STOP, TYP.

1/2" PARTICLE BOARD W/

PL-1 FINISH

3/4" PLYWOOD W/

HARDWOOD EDGE BAND

AND PL-1 FINISH ON ALL

SURFACES ON OFFICE

SIDE, TYP.

2X4 CLEAT SECURED TO

CASEWORK FRAMING, TYP.

SATIN NICKEL BAR DOOR PULLS

(BASIS OF DESIGN: LIBERTY

96MM/3.75" WIRE PULL), TYP.

DRAWERS, SEE SPEC.

FOR DETAILS, TYP.

2"

3/4" PLYWOOD W/

PL-1 FINISH, TYP.

3/4" X 2-1/2" SOLID OAK TRIM,

w/ 1/4" CHAMFER, TYP. @

PERIMETER OF PANEL

LINE OF TRIM

BEYOND

WORKSTATION DRAWER DETAIL

Scale: 1 1/2" = 1'-0"

E5

A5.01 NOTE: REFER TO DETAIL E3/A5.01 FOR ADDITIONAL NOTES.

FASTEN .040" PREFINISHED

ALUM. BENT METAL TRIM

('U-SHAPED') w/ COMPATIBLE

CONSTRUCTION ADHESIVE.

COLOR AND FINISH TO MATCH

WINDOW MULLION (DARK

BRONZE)

1"

EXISTING ALUM. & GLASS

WINDOW SYSTEM

EXISTING 4" HIGH +/- STONE

SILL BELOW, STEP WALL TO

FOLLOW SILL, CAULK

PERIMETER, TYP.

PARTITION, REFER TO

SCHEDULE

WOOD JAMB PLAN DETAIL

Scale: 1 1/2" = 1'-0"

A2 A5.01

RECEPTION DESK ELEVATION

Scale: 1/4" = 1'-0"D5

E1 A5.01

E5 A5.01

E3 A5.01

PL-2 PANEL w/ HARDWOOD EDGE/TRIM

(HATCHED AREAS), REFER TO DETAILS, TYP.

PL-1 PANEL w/ HARDWOOD EDGE/TRIM, REFER TO DETAILS, TYP.

1'-1112"3'-0"3'-534"3'-0"1'-1112"1'-1112"3'-914"3'-914"1'-1112"1'-1112"1'-1112" 4'-1034"

SS-1

OAK HARDWOOD TRIM, REFER TO

DETAILS, TYP.

RB-1

2"2"2"

RETURN SS-1 @ EACH END, TYP.

34'-2" +/-

RECEPTION DESK ELEVATION

Scale: 1/4" = 1'-0"C5

3' -8

2' -6

1'

-2

5"

16" X 16" REMOVEABLE PANEL,

CHROME FINISH SCREWS, TYP.

1" FILLER PANEL, TYP. EACH CABINET

COUNTER SUPPORT BRACKET, TYP.

6" TYP.

EXISTING COLUMN ENCLOSURE

DASHED FOR CLARITY

NEW PARTITION

5'-0" TALL PRIVACY SCREEN, SEE

SECTION DETAIL, TYP.

WORKSTATION CABINET, TYP.

REFER TO FLOOR PLAN FOR HORIZ. DIMENSIONS NOT SHOWN

E1 A5.01

E5 A5.01

E3 A5.01

RECESSED RECEPTACLE OR DATA

OUTLET, REFER TO ELECT. DWGS., TYP.

RB-1

RECEPTION DESK ELEVATION

Scale: 1/4" = 1'-0"C2

C1 A5.01

SS-1 COUNTER, TYP.

3'-2"

3' -8

3' -0

4'-10"

7' -1

0"

7' -1

0"

B1 A5.01

PAINT WALLS PT-1 (TO MATCH EXIST.), TYP.

PAINT DOOR FRAME PT-2 (TO MATCH

EXISTING), TYP.

OPEN TO BEYOND

4' -6

3'

-4

W-1

TYP.

8"

PARTITION, REFER TO

SCHEDULE

2"

3/4" PLYWOOD WITH 3/4” (2

CM) SS-1 COUNTERTOP WITH

EASED EDGES, TYP.

SS-1 COUNTER w/

'WATERFALL EDGE' BEYOND

SOLID OAK CASING/TRIM

BEYOND

2X WOOD BLOCKING

CAULK JOINT, TYP. BOTH

SIDES

COUNTER DETAIL

Scale: 1 1/2" = 1'-0"

C1 A5.01

3/4" X 2-1/2" SOLID OAK TRIM

w/ EASED EDGES, TYP.

3/4" SOLID OAK CASING w/

EASED EDGES, TYP.212"

8"

SS-1 COUNTERTOP BELOW

1/2" FILLET RADIUS, TYP. AT ENDS

COUNTER JAMB DETAIL (HEAD SIMILAR)

Scale: 1 1/2" = 1'-0"

B1 A5.01

WORK COUNTER ELEVATION

Scale: 1/4" = 1'-0"D2

D1

A5.01 SS-1 COUNTER, TYP.

3' -8

2' -1

0"

D1 A5.01

COUNTER SUPPORT BRACKET, REFER TO

SECTION DETAIL. PROVIDE BLOCKING IN

WALL, PATCH AND MATCH WALL SURFACE,

TYP.

SOLID SS-1 EDGES, TYP.

2"

3/4" PLYWOOD WITH 3/4” (2 CM)

SS-1 COUNTERTOP WITH EASED

EDGES, TYP.

1'-4"

REFER TO ELEVATION

FOR HEIGHT ABOVE

FINISH FLOOR

2" X 2" X 1/4" ALUMINUM ANGLE SUPPORT MAX.

4'-0" O.C. BASIS OF DESIGN “RAKKS EH-1212”

(FINISH: MATTE SILVER POWDER COAT). REFER

TO INTERIOR ELEVATION FOR LOCATION.

INSTALL F.T. PLYWOOD OR STEEL BLOCKING IN

WALL TO SUPPORT BRACKETS, PATCH AND

MATCH WALL, TYP.

COUNTER JAMB DETAIL (HEAD SIMILAR)

Scale: 1 1/2" = 1'-0"

D1 A5.01

MARK DESCRIPTIONDATE

03/13/2026DRAWING DATE:

DIGITAL REPRODUCTIONS OF THESE

DRAWINGS SHALL NOT BE POSTED TO WEB

SITES WITHOUT THE DIRECT WRITTEN

PERMISSION OF THE ENGINEER.

IT IS A VIOLATION OF THE STATE EDUCATION

LAW FOR ANY PERSON, UNLESS UNDER THE

DIRECTION OF A LICENSED ENGINEER TO

ALTER THIS DOCUMENT IN ANY WAY.

ALTERATIONS MUST HAVE THE SEAL AFFIXED

ALONG WITH THE DESCRIPTION OF THE

ALTERATION AND SIGNATURE AND DATE.

COPYRIGHT ©.

M

AD

IS

O

N C

O U

N

TY

B U

IL

D

IN

G

C

LE

R K'

S O

FF

IC

E R

EN

O

VA

TI

O N

S

N O

R

TH

C O

U R

T

ST

R

EE

T W

AM

PS

VI

LL

E, N

Y

26-11-9186KING + KING PROJ. NO.:

SCALE:

DRAWING TITLE:

Sheet Scale

A

B

C

D

E

1 2 3 4 5 6 H0.01

LEGEND, DETAILS,

SPECIFICATIONS

& GENERAL NOTES

(10")

(10x8)(10x8)

HU-#

EQUIP-#

T

H

XXX

CFM

AAD

FD

LPS

PC

PD

CD

MV

AV

LEGEND

SYMBOL DESCRIPTION ABBR.

S

VD

14X10

LPC

SYMBOL DESCRIPTION ABBR.

POINT OF CONNECTION - NEW TO EXISTING -

POINT BETWEEN EXISTING TO REMAIN AND

EXISTING TO BE REMOVED -

DEDICATED SERVICE AREA CLEARANCE -

KEYED NOTE REFERENCE:

REFERS TO CORRESPONDING NUMBER

ON RESPECTIVE DRAWING OR DETAIL

SOUND LINED DUCTWORK (DOUBLE LINE / SINGLE LINE) -

FLEXIBLE DUCTWORK FLEX

FIRE DAMPER FD

SMOKE DAMPER SD

VOLUME DAMPER VD

AUTOMATIC AIR DAMPER AAD

FLEXIBLE DUCT CONNECTION FC

ACCESS DOOR / ACCESS PANEL AD / AP

RECTANGULAR DUCT (SIZE IN INCHES) 14x10

ROUND DUCT (SIZE IN INCHES) 14Ø

EXISTING ELEMENT TO BE REMOVED -

EXISTING FLEXIBLE DUCTWORK -

SUPPLY AIR DIFFUSER (RECT. / ROUND NECK) SAD

RETURN / EXHAUST AIR REGISTER (RECT. / ROUND NECK) RAR / XAR

START / STOP S/S

STATUS ST

VALVE V

TEMPERATURE T

DAMPER MOTOR DM

DIFFERENTIAL PRESSURE DP

HUMIDITY SENSOR H

SPEED CONTROL SPD

ANALOG INPUT AI

ANALOG OUTPUT AO

DIGITAL INPUT DI

DIGITAL OUTPUT DO

END SWITCH ES

DEGREES FAHRENHEIT (°F)

BRAKE HORSEPOWER BHP

MINIMUM CIRCUIT AMPACITY MCA

HERTZ Hz

DECIBEL POWER dBA

HORSEPOWER HP

REVOLUTIONS PER MINUTE RPM

POUNDS PER SQUARE INCH PSI

EXTERNAL STATIC PRESSURE ESP

INCHES IN

FEET PER MINUTE FPM

GALLONS PER MINUTE GPM

POUNDS PER HOUR PPH

MAKE-UP AIR TAP WITH VOLUME DAMPER

BALANCE TO CFM INDICATED (XXX) -

WALL MOUNTED TEMPERATURE SENSOR -

WALL MOUNTED HUMIDITY SENSOR -

EXISTING DUCTWORK TO REMAIN

(SINGLE LINE / DOUBLE LINE)

APPROXIMATE SIZES SHOWN IN PARENTHESIS

EXISTING PIPING TO REMAIN

APPROXIMATE SIZES SHOWN IN PARENTHESIS -

EXISTING DUCTWORK TO BE CAPPED -

EXISTING GRILLE / REGISTER / DIFFUSER TO REMAIN -

REFRIGERANT-410A R-410A

GATE VALVE GV

CHECK VALVE CV

BUTTERFLY VALVE BFV

BALL VALVE BV

BALANCING VALVE -

FLOAT AND THERMOSTATIC TRAP F&T

BUCKET TRAP BT

UNION U

MANUAL AIR VENT MV

AUTOMATIC AIR VENT AV

PIPE UP / PIPE DOWN -

TEE UP / TEE DOWN -

PIPING (ARROW INDICATES DIRECTION OF FLOW) -

CONDENSATE DRAIN CD

LOW PRESSURE CONDENSATE LPC

LOW PRESSURE STEAM LPS

PUMP DISCHARGE PD

PUMPED CONDENSATE PC

ABOVE FINISHED FLOOR / ABOVE FINISHED GRADE AFF / AFG

BELOW FINISHED FLOOR / BELOW FINISHED GRADE BFF / BFG

UNLESS NOTED OTHERWISE UNO

NOT IN CONTRACT NIC

NOT TO SCALE NTS

NORMALLY OPEN / NORMALLY CLOSED NO / NC

CONTRACTOR FOR GENERAL CONSTRUCTION DIVISION GC

CONTRACTOR FOR ELECTRICAL DIVISION ELEC

CONTRACTOR FOR HEATING, VENTILATING & AIR COND. DIV. HVAC

CONTRACTOR FOR PLUMBING DIVISION PC

CONTRACTOR FOR FIRE PROTECTION DIVISION FP

BUILDING AUTOMATIC SYSTEM BAS

TWO-WAY CONTROL VALVE -

STRAINER w/ BLOWOFF -

OWNER FURNISHED & OWNER INSTALLED OFOI

OWNER FURNISHED & CONTRACTOR INSTALLED OFCI

AIR COOLED CONDENSING UNIT ACCU

UNIT HEATER UH

REHEAT COIL RHC

AIR COOLED CONDENSING UNIT ACCU

HUMIDIFIER HU

FAN F

SUPPLY AIR SA

RETURN AIR RA

OUTSIDE AIR OA

EXHAUST AIR XA

EXTERNAL STATIC PRESSURE ESP

TOTAL STATIC PRESSURE TSP

DISPERSION MANIFOLD DM

CABINET UNIT HEATER CUH

WALL HEATER WH

PRESSURE GAUGE (PROVIDE w/ PETCOCK OR NEEDLE VALVE) -

THERMOMETER -

HS

HR

HEAT PUMP SUPPLY HS

HEAT PUMP RETURN HR

THESE ARE STANDARD SYMBOLS AND ABBREVIATIONS AND MAY NOT APPEAR ON THE

PROJECT DRAWINGS. HOWEVER, WHEREVER THE SYMBOL OR ABBREVIATION APPEARS

ON THE PROJECT DRAWINGS, THE ITEM SHALL BE FURNISHED AND INSTALLED.

NOTE:

SA-#

PLAN SYMBOL EXPLANATION:

GRILLE-REGISTER-DIFFUSER

NECK SIZE

DESIGN FLOW RATE (CFM)

TYPE

RA = RETURN AIR

XA = EXHAUST AIR

SA = SUPPLY AIR

TEST PLUG -

BRITISH THERMAL UNITS (1000'S) MBH

GENERAL NOTES

1. PROVIDE ALL MATERIALS, EQUIPMENT, AND LABOR REQUIRED TO INSTALL

COMPLETE AND OPERABLE SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED, AND AS REQUIRED BY ALL APPLICABLE CODES AND REGULATIONS.

2. CONTRACT DOCUMENT DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO

CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY.

3. INSTALL ALL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH

MANUFACTURER'S RECOMMENDATIONS, CONTRACT DOCUMENTS, AND ALL

APPLICABLE CODES AND REGULATIONS.

4. COORDINATE CONSTRUCTION OF ALL HVAC WORK WITH ARCHITECTURAL,

ELECTRICAL, AND PLUMBING WORK, SHOWN ON OTHER CONTRACT DRAWINGS.

5. ALL PRESSURE TESTS SHALL BE COMPLETED BEFORE ANY PIPE INSULATION IS

APPLIED.

6. WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED,

THE PRODUCT OF ONE MANUFACTURER SHALL BE USED.

7. PROVIDE ALL REQUIRED CONTROL WIRING AND CONDUIT, INSTALL IN

ACCORDANCE WITH NATIONAL ELECTRIC CODE, ELECTRICAL CODE OF NEW

YORK STATE, AND ALL APPLICABLE CODES AND REGULATIONS.

8. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER'S CERTIFIED

DRAWINGS. COORDINATE AND PROVIDE ALL PIPING TRANSITIONS REQUIRED FOR

FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND

COORDINATE ALL PIPING DIMENSIONS BEFORE FABRICATION.

9. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE

SPECIFICATIONS, THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS, ARE

APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST

CONDITIONS AND RESULTS SHALL BE DETERMINED BY THE PROJECT SITE

CONDITIONS AND SHALL BE VERIFIED BY THE PLUMBING CONTRACTOR BEFORE

BEING INSTALLED. DO NOT SCALE DRAWINGS.

10. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION, AND AS

SHOWN IN DETAILS FOR PIPING AND EQUIPMENT (UNLESS OTHERWISE NOTED),

SHALL BE FURNISHED AND INSTALLED.

11. ALL DUCTWORK AND PIPING SHALL BE SUPPORTED AS SPECIFIED, AND AS

REQUIRED TO PROVIDE A VIBRATION FREE INSTALLATION.

12. ALL DUCTWORK AND PIPING SUPPORTED FROM STRUCTURE SHALL BE

COORDINATED WITH GENERAL CONTRACTOR.

13. ALL DUCTWORK AND PIPING WORK SHALL BE COORDINATED WITH ALL OTHER

TRADES INVOLVED. OFFSETS IN DUCTWORK AND PIPING AROUND OBSTRUCTIONS

SHALL BE PROVIDED AT NO ADDITIONAL COST.

14. LOCATIONS AND SIZES OF ALL FLOOR, AND WALL OPENINGS SHALL BE

COORDINATED WITH ALL OTHER TRADES.

15. ALL OPENINGS IN FIRE WALLS FOR PIPING SHALL BE FIRESTOPPED.

16. INSTALL PIPING SO THAT ALL VALVES, AND OTHER APPURTENANCES REQUIRING

SERVICE, ARE ACCESSIBLE.

17. INSTALL ALL PIPING WITHOUT FORCING OR SPRINGING.

18. ALL PIPING SHALL BE INSTALLED TO CLEAR DOORS AND WINDOWS.

19. ALL WORK SHALL CONFORM TO ALL APPLICABLE RULES, REGULATIONS, CODES

AND STANDARDS, INCLUDING, BUT NOT LIMITED TO BUILDING CODE OF NEW

YORK STATE, NFPA, FEDERAL, STATE, COUNTY, AND CITY ORDINANCES, CODES,

LAWS AND REGULATIONS.

20. ALL TRADES SHALL APPLY AND PAY FOR ALL NECESSARY PERMITS AND

INSPECTIONS REQUIRED AND SUBMIT COPIES OF PERMITS TO THE ENGINEER BEFORE

ANY WORK BEGINS.

21. ALL UNUSED HOLES THROUGH EXISTING WALLS, AND EXISTING FLOORS SHALL BE

PATCHED AND FINISHED TO MATCH EXISTING CONDITIONS.

22. PROTECT ALL EXISTING EQUIPMENT, FINISHES, ETC. FROM DAMAGE DURING

CONSTRUCTION.

23. CONTRACTOR SHALL VISIT SITE AND VERIFY ALL DIMENSIONS AND EXISTING

CONDITIONS PRIOR TO STARTING ANY WORK. NOTIFY THE ENGINEER IN WRITING

OF ANY DISCREPANCIES. STARTING WORK INDICATES ACCEPTANCE OF EXISTING

CONDITIONS.

LONG RADIUS 90° ELBOW

DOUBLE LINE

SINGLE LINE

TURNING VANES

OR ELBOW WITH

VD

DOUBLE LINE

VD

VOLUME DAMPER

ROUND SIDE TAP WITH

SINGLE LINE

OR

(UNO)

DOUBLE LINE

AS SHOWN

DOUBLE LINE

LOW VELOCITY DUCTWORK LEGEND

VD

AxB

(45° ENTRY TYPE)

TRANSFER AIR DUCT

ABOVE CEILING

WITH SOUND LINING

SINGLE LINE

DOUBLE LINE

(MIN)

45°

1-1/4A)XB

VD

VD

VD

90° BRANCH

SINGLE LINE

TAKE OFF

DOUBLE LINE

4"

(MIN)

SINGLE LINE

VD

VD VD

VD

VD VD

TAKE OFF

SINGLE LINE

DUAL 90° BRANCH

(45° ENTRY TYPE)

DOUBLE LINE

IN BOTTOM OF DUCT

OR DIFFUSER

SINGLE LINE

GRILLE REGISTER

DROPRISE

DOUBLE LINE

R

RISE

R

D

D

DROP

ARROW INDICATES FLOW DIRECTION

DOUBLE LINE

DUCT RISE / DROP TO AVOID

OBSTRUCTION

SINGLE LINE

TURN DOWN

TURN UP

12x6

DUCT ELBOW UP OR DOWN

TURN DOWN

SINGLE LINE

12x6 TURN UP

TRANSITION

CONTRACTOR OPTION

3 DIFFUSER AND FLEXIBLE DUCT DETAIL

NO SCALE

2 DUCT DETAILS

NO SCALE

SQUARE ELBOW RADIUS ELBOW

BRANCH DUCT

AIR FLOW (RA / XA)

AIR FLOW (SA / OA)

45° ANGLE

VOLUME DAMPER

R = W

90° ELBOW w/

TURNING VANES

CONTRACTOR

OPTION

AIR FLOW (SA / OA)

1 RETURN AIR DUCTWORK DETAIL

NO SCALE

18x18

CEILING PLENUM

ELEVATION CEILING

RA GRILLE

ACOUSTICAL

LAY-IN CEILING

DUCT HANGER

STRUCTURE

SUPPLY DUCT

SUPPLY

DUCT

3" HARDCAST "FOIL-GRIP" OVER

INNER MEMBRANE AND

EXTENSION COLLAR (TYP.)

NYLON WRAP-LOC CLAMP

HOLDS OUTER MEMBRANE

AND INSULATION IN PLACE

DUCT

HANGER

STARTING COLLAR

w/ VOLUME DAMPER EXTENSION COLLAR (6"

MIN.) SCREWED ONTO

STARTING COLLAR

HARDCAST

"IRON-GRIP" 601

ON METAL TO

METAL AND 3

SCREWS MIN.

HARDCAST

"IRON-GRIP"

601 ON

METAL TO

METAL

ACOUSTICAL

LAY-IN CEILING

FULL RADIUS ELBOW

TO PREVENT "KINKING"

AT DIFFUSER

CONNECTION. USE

HARDCAST

"IRON-GRIP" 601 ON

EACH JOINT.

SCREW TO DIFFUSER

CEILING DIFFUSER

CEILING

DIFFUSER

INSULATED FLEXIBLE

DUCTWORK, MAX

LENGTH 2'- 0"

END OF INNER

MEMBRANE

END OF INNER MEMBRANE

FLEX DUCT

HANGER (TYP.)

STEEL WORM-GEAR CLAMP OVER

HARDCAST "FOIL-GRIP" SEALANT

AND INNER MEMBRANE OF FLEX

DUCT (TYP.)

STARTING COLLAR

W/ VOLUME DAMPER

AND EXTENSION COLLAR

ACOUSTICAL

LAY-IN CEILING

FULL RADIUS

ELBOW

NYLON

WRAP-LOC

CLAMP

OUTER

MEMBRANE

INSULATION

OVER

ELBOW AND

ONTO

DIFFUSER

EXTENSION COLLAR (6"

MIN.) SCREWED ONTO

METAL ELBOW

3" 3"

MANUAL VOLUME

DAMPERS

FACTORY FABRICATED WITH REQUIRED HARDWARE AND ACCESSORIES. STIFFEN DAMPER BLADES FOR STABILITY. INCLUDE LOCKING DEVICE TO HOLD SINGLE-BLADE DAMPERS IN A FIXED POSITION WITHOUT VIBRATION. CLOSE DUCT PENETRATIONS FOR DAMPER COMPONENTS TO SEAL DUCT CONSISTENT WITH

PRESSURE CLASS.

FRAMES: 20-GAGE GALVANIZED STEEL.

STEEL BLADES: 20-GAGE GALVANIZED STEEL.

AXLES: 3/8" SQUARE STEEL.

BEARINGS: MOLDED SYNTHETIC.

CONTROL SHAFT: 3/8" SQUARE STEEL.

BASIS OF DESIGN: RUSKIN MDRS25.

TURNING VANES TWO PIECE TURNING VANES SHALL BE SHOP FABRICATED IN ACCORDANCE WITH THE CURRENT EDITION OF

SMACNA HVAC DUCT CONSTRUCTION STANDARDS.

DIFFUSERS VERIFICATION OF PERFORMANCE: RATE DIFFUSERS ACCORDING TO ASHRAE 70, "METHOD OF TESTING FOR

RATING THE PERFORMANCE OF AIR OUTLETS AND INLETS."

COMMON WORK

RESULTS FOR HVAC

COORDINATION:

EQUIPMENT

INSTALLATION -

COMMON

REQUIREMENTS:

PAINTING:

COORDINATION

DRAWINGS

ARRANGE FOR CHASES, SLOTS, AND OPENINGS IN BUILDING STRUCTURE DURING PROGRESS OF

CONSTRUCTION TO ALLOW FOR HVAC INSTALLATIONS. COORDINATE REQUIREMENTS FOR ACCESS PANELS AND DOORS FOR HVAC ITEMS REQUIRING ACCESS THAT ARE CONCEALED BEHIND FINISHED SURFACES.

1. INSTALL EQUIPMENT TO ALLOW MAXIMUM POSSIBLE HEADROOM UNLESS SPECIFIC MOUNTING

HEIGHTS ARE NOT INDICATED.

2. INSTALL EQUIPMENT LEVEL AND PLUMB, PARALLEL AND PERPENDICULAR TO OTHER BUILDING

SYSTEMS AND COMPONENTS IN EXPOSED INTERIOR SPACES, UNLESS OTHERWISE INDICATED.

3. INSTALL HVAC EQUIPMENT TO FACILITATE SERVICE, MAINTENANCE AND REPAIR OR REPLACEMENT

OF COMPONENTS. CONNECT FOR EASE OF DISCONNECTING, WITH MINIMUM INTERFERENCE TO

OTHER INSTALLATIONS. EXTEND GREASE FITTINGS TO ACCESSIBLE LOCATIONS.

1. DAMAGE AND TOUCHUP: REPAIR MARRED AND DAMAGED FACTORY-PAINTED FINISHES WITH

MATERIALS AND PROCEDURES TO MATCH ORIGINAL FACTORY FINISH.

CONTRACTOR SHALL PROVIDE COMPLETE COORDINATION DRAWINGS WITH STRUCTURE AND ALL

OTHER TRADES.

SUBMITTALS ARE REQUIRED FOR ALL MATERIALS AND EQUIPMENT.SUBMITTALS

TESTING,

ADJUSTING

AND

BALANCING

TESTING, ADJUSTING AND BALANCING AGENCY SHALL BE A MEMBER OF THE

ASSOCIATED AIR BALANCE COUNCIL (AABC) OR THE NATIONAL ENVIRONMENTAL

BALANCING BUREAU (NEBB) OR THE TESTING, ADJUSTING, AND BALANCING BUREAU

(TABB). TESTING, ADJUSTING AND BALANCING SHALL BE PERFORMED IN

ACCORDANCE WITH THE APPROPRIATE AGENCY'S STANDARDS AND PROCEDURES.

PROVIDE FINAL REPORT FOR ENGINEER REVIEW IN THE RESPECTIVE AGENCY'S

STANDARD FORMAT.

SUBMISSION OF O & M MANUALS ARE REQUIRED FOR ALL MATERIALS AND

PRODUCTS PRIOR TO COMPLETION OF WORK.

CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS IN AUTOCAD FORMAT, AT END

OF OF PROJECT.

O&M

MANUALS

AS-BUILT

DRAWINGS

MULTILAYER, MULTICOLOR, PLASTIC LABELS FOR MECHANICAL ENGRAVING, 1/16 INCH THICK, AND HAVING

PRE-DRILLED HOLES FOR ATTACHMENT HARDWARE.

WHITE.

BLACK.

ABLE TO WITHSTAND TEMPERATURES UP TO 160°F.

LENGTH AND WIDTH VARY FOR REQUIRED LABEL CONTENT, BUT NOT LESS THAN 2-1/2" BY 3/4".

1/4" FOR NAME OF UNITS IF VIEWING DISTANCE IS LESS THAN 24", FOR VIEWING DISTANCES UP TO 72", AND PROPORTIONATELY LARGER LETTERING FOR GREATER VIEWING DISTANCES. INCLUDE SECONDARY LETTERING

2/3 TO 3/4 THE SIZE OF PRINCIPAL LETTERING.

STAINLESS-STEEL RIVETS.

CONTACT-TYPE PERMANENT ADHESIVE, COMPATIBLE WITH LABEL AND WITH SUBSTRATE.

INCLUDE EQUIPMENT'S DRAWING DESIGNATION OR UNIQUE EQUIPMENT NUMBER.

EQUIPMENT LABELS

MATERIAL AND

THICKNESS:

LETTER COLOR:

BACKGROUND

COLOR:

MAXIMUM

TEMPERATURE:

MINIMUM LABEL

SIZE:

MINIMUM LETTER

SIZE:

FASTENERS:

ADHESIVE:

LABEL CONTENT:

FIRE-STOP SEALANT PROVIDE FIRE-STOPPING AT ALL PIPING AND ELECTRICAL CONDUIT PENETRATIONS THROUGH FIRE RATED PARTITIONS AND AT ALL PIPING PENETRATIONS THROUGH FLOORS, WALLS, AND CEILINGS. FIRE STOPPING

PUTTY SHALL BE ASBESTOS FREE.

BASIS OF DESIGN: HILTI, INC.

COMPLY WITH ASTM C 553. PROVIDE FOR NEW SUPPLY DUCTWORK, NEW RETURN DUCTWORK, AND NEW EXHAUST DUCTWORK: 1.5# / CUBIC FOOT DENSITY FIBERGLASS DUCT WRAP, WITH FACING COMPOSED OF ALUMINUM FOIL REINFORCED WITH FIBERGLASS YARN AND LAMINATED TO FIRE RESISTANT KRAFT PAPER.

K-VALUE AT 75° F, (MEAN TEMPERATURE) SHALL BE .25 OR LESS. MOISTURE ABSORPTION LESS THAN 1% BY VOLUME, MOISTURE VAPOR TRANSMISSION 0.02 PERMS. FLAME SPREAD 25 OR LESS, SMOKE DEVELOPED 50 OR

LESS. BASIS OF DESIGN: MANVILLE 800 SERIES SPIN GLASS.

NEW SUPPLY DUCTWORK SHALL HAVE A MINIMUM "AS INSTALLED" R-VALUE OF 8.

DUCTWORK

INSULATION

GALVANIZED, SHEET STEEL: LOCK-FORMING QUALITY; ASTM A 653/A 653M.

1. SMACNA HVAC DUCT CONSTRUCTION STANDARDS FOR 2" W.G. DUCT PRESSURES.

2. GENERAL FABRICATION REQUIREMENTS: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION

STANDARDS - METAL AND FLEXIBLE" BASED ON INDICATED STATIC-PRESSURE CLASS UNLESS OTHERWISE

INDICATED.

3. TRANSVERSE JOINTS: SELECT JOINT TYPES AND FABRICATE ACCORDING TO SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 1-4, "TRANSVERSE (GIRTH) JOINTS," FOR STATIC-PRESSURE CLASS, APPLICABLE SEALING REQUIREMENTS, MATERIALS INVOLVED, DUCT-SUPPORT INTERVALS, AND OTHER PROVISIONS IN SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL

AND FLEXIBLE."

4. LONGITUDINAL SEAMS: SELECT SEAM TYPES AND FABRICATE ACCORDING TO SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 1-5, "LONGITUDINAL SEAMS -

RECTANGULAR DUCTS," FOR STATIC-PRESSURE CLASS, APPLICABLE SEALING REQUIREMENTS,

MATERIALS INVOLVED, DUCT-SUPPORT INTERVALS, AND OTHER PROVISIONS IN SMACNA'S "HVAC

DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE."

5. ELBOWS, TRANSITIONS, OFFSETS, BRANCH CONNECTIONS, AND OTHER DUCT CONSTRUCTION: SELECT

TYPES AND FABRICATE ACCORDING TO SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS -

METAL AND FLEXIBLE," CHAPTER 2, "FITTINGS AND OTHER CONSTRUCTION," FOR STATIC-PRESSURE CLASS, APPLICABLE SEALING REQUIREMENTS, MATERIALS INVOLVED, DUCT-SUPPORT INTERVALS, AND OTHER PROVISIONS IN SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE."

1. GENERAL FABRICATION REQUIREMENTS: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," CHAPTER 3, "ROUND, OVAL, AND FLEXIBLE DUCT," BASED ON

INDICATED STATIC-PRESSURE CLASS UNLESS OTHERWISE INDICATED.

2. TRANSVERSE JOINTS: SELECT JOINT TYPES AND FABRICATE ACCORDING TO SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 3-2, "TRANSVERSE JOINTS - ROUND DUCT," FOR STATIC-PRESSURE CLASS, APPLICABLE SEALING REQUIREMENTS, MATERIALS INVOLVED, DUCT-SUPPORT INTERVALS, AND OTHER PROVISIONS IN SMACNA'S "HVAC DUCT CONSTRUCTION

STANDARDS - METAL AND FLEXIBLE."

3. LONGITUDINAL SEAMS: SELECT SEAM TYPES AND FABRICATE ACCORDING TO SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 3-1, "SEAMS - ROUND DUCT AND FITTINGS," FOR STATIC-PRESSURE CLASS, APPLICABLE SEALING REQUIREMENTS, MATERIALS INVOLVED, DUCT-SUPPORT INTERVALS, AND OTHER PROVISIONS IN SMACNA'S "HVAC DUCT CONSTRUCTION

STANDARDS - METAL AND FLEXIBLE."

1. GENERAL MATERIAL REQUIREMENTS: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION

STANDARDS - METAL AND FLEXIBLE" FOR ACCEPTABLE MATERIALS, MATERIAL THICKNESSES, AND DUCT CONSTRUCTION METHODS UNLESS OTHERWISE INDICATED. SHEET METAL MATERIALS SHALL BE FREE OF PITTING, SEAM MARKS, ROLLER MARKS, STAINS, DISCOLORATIONS, AND OTHER IMPERFECTIONS.

2. GALVANIZED SHEET STEEL: COMPLY WITH ASTM A 653/A 653M.

a. GALVANIZED COATING DESIGNATION: G90.

b. FINISHES FOR SURFACES EXPOSED TO VIEW: MILL PHOSPHATIZED.

3. TIE RODS: GALVANIZED STEEL, 1/4-INCH MINIMUM DIAMETER FOR LENGTHS 36 INCHES OR LESS;

3/8-INCH MINIMUM DIAMETER FOR LENGTHS LONGER THAN 36 INCHES.

1. GENERAL SEALANT AND GASKET REQUIREMENTS: SURFACE-BURNING CHARACTERISTICS FOR

SEALANTS AND GASKETS SHALL BE A MAXIMUM FLAME-SPREAD INDEX OF 25 AND A MAXIMUM

SMOKE-DEVELOPED INDEX OF 50 WHEN TESTED ACCORDING TO UL 723; CERTIFIED BY AN NRTL.

2. TWO-PART TAPE SEALING SYSTEM:

a. TAPE: WOVEN COTTON FIBER IMPREGNATED WITH MINERAL GYPSUM AND MODIFIED

ACRYLIC/SILICONE ACTIVATOR TO REACT EXOTHERMICALLY WITH TAPE TO FORM HARD,

DURABLE, AIRTIGHT SEAL.

b. TAPE WIDTH: 4 INCHES.

c. SEALANT: MODIFIED STYRENE ACRYLIC.

d. WATER RESISTANT.

e. MOLD AND MILDEW RESISTANT.

f. MAXIMUM STATIC-PRESSURE CLASS: 10-INCH W.G. POSITIVE AND NEGATIVE.

g. SERVICE: INDOOR AND OUTDOOR.

h. SERVICE TEMPERATURE: MINUS 40 TO PLUS 200 DEG F.

i. SUBSTRATE: COMPATIBLE WITH GALVANIZED SHEET STEEL (BOTH PVC COATED AND BARE), STAINLESS STEEL, OR ALUMINUM.

j. FOR INDOOR APPLICATIONS, USE SEALANT THAT HAS A VOC CONTENT OF 250 G/L OR LESS

WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA METHOD 24).

3. WATER-BASED JOINT AND SEAM SEALANT:

a. APPLICATION METHOD: BRUSH ON.

b. SOLIDS CONTENT: MINIMUM 65 PERCENT.

c. SHORE A HARDNESS: MINIMUM 20.

d. WATER RESISTANT.

e. MOLD AND MILDEW RESISTANT.

f. VOC: MAXIMUM 75 G/L (LESS WATER).

g. MAXIMUM STATIC-PRESSURE CLASS: 10-INCH WG, POSITIVE AND NEGATIVE.

h. SERVICE: INDOOR OR OUTDOOR.

i. SUBSTRATE: COMPATIBLE WITH GALVANIZED SHEET STEEL (BOTH PVC COATED AND BARE), STAINLESS STEEL, OR ALUMINUM SHEETS.

1. HANGER RODS FOR NONCORROSIVE ENVIRONMENTS: CADMIUM-PLATED STEEL RODS AND NUTS.

2. STRAP AND ROD SIZES: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL

AND FLEXIBLE," TABLE 4-1, "RECTANGULAR DUCT HANGERS MINIMUM SIZE," AND TABLE 4-2, "MINIMUM

HANGER SIZES FOR ROUND DUCT."

3. TRAPEZE SUPPORTS:

a. SUPPORTS FOR GALVANIZED-STEEL DUCTS: GALVANIZED-STEEL SHAPES AND PLATES.

SINGLE-WALL

RECTANGULAR DUCTS

AND FITTINGS:

SINGLE-WALL ROUND

DUCTS AND FITTINGS:

SHEET METAL

MATERIALS:

SEALANT:

HANGERS AND

SUPPORTS:

METAL DUCTWORK

UL 181 (CLASS I) COMPLIANCE, POLYETHYLENE INNER JACKET, 1-1/2" THICK FIBERGLASS INSULATION, POLYETHYLENE…