Attachment 1 - Specifications Eng 23-1024.pdf
PDF 5 MB Posted
- Attached to
- RPR School HVAC B314 Federal contract opportunity
- Solicitation number
- FA557525B0014
About this file
This document is a detailed specification for a construction project to upgrade the HVAC system at Building 314 on Moron Air Base in Spain. The project, designated QUUG 23-1024, involves replacing the existing heating, ventilation, and air conditioning system to address current deficiencies, including lack of external ventilation and issues with noise and temperature control. Key work includes minor demolition and selective renovation, installing a new Dedicated Outside Air (DOAS) unit, replacing the fire alarm control panel, implementing a new VRF (Variable Refrigerant Flow) system, and performing necessary electrical and control system upgrades.
The solicitation is specifically for local sources in Spain, with a project value between $500,000 and $1,000,000. A pre-proposal conference and site visit is scheduled for 25 July 2025, and bids must be received by 10:00 hours local time on 18 August 2025. The project requires compliance with Spanish and U.S. regulations, and contractors must be authorized to perform government works in Spain. The government notes that funds are not currently available, and the bid acceptance period should remain valid through 31 December 2025, with the potential for the solicitation to be canceled at any time.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 5 - AF66 Schedule of Material Submittals 23-1024.xlsx | XLSX spreadsheet | |
| Solicitation - FA557525B0014.pdf | ||
| Attachment 2 - Especificaciones Sp 23-1024.pdf | ||
| Attachment 4 - Blank Cost Estimate 23-1024.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT DESIGN
QUUG 23-1024, RPR SCHOOL HVAC SYSTEM, B #314
AT MORÓN AIR BASE, SPAIN
SPECIFICATIONS
Prepared by: Cayetano Gómez Herrero
Ingeniero Industrial – Colegiado Nº 4784
Colegio Oficial de Ingenieros Industriales de Andalucía Occidental
Reviewed by: _________________________________________________________________
Approved by: _________________________________________________________________
January 2025
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK
LIST OF SPECIFICATIONS
DIVISION 01 GENERAL REQUIREMENTS
01 11 00 SCOPE OF WORK AND DRAWINGS 01
01 11 01 GENERAL CONDITIONS 06
01 11 02 SPECIAL CONDITIONS 38
DIVISION 02 EXISTING CONDITIONS
02 41 00 DEMOLITION 41
DIVISION 04 MASONRY
04 20 00 MASONRY 48
DIVISON 05 METALS
05 12 00 STRUCTURAL STEEL 54
05 50 13 MISCELLANEOUS METAL FABRICATIONS 59
DIVISION 07 THERMAL AND MOISTURE PROTECTION
07 22 00 ROOF AND DECK INSULATION 65
07 84 00 FIRESTOPPING 71
07 92 00 JOINT SEALANTS 74
DIVISION 09 FINISHES
09 29 00 GYPSUM BOARD 79
09 51 00 ACOUSTICAL CEILINGS 85
09 90 00 PAINT AND COATINGS 92
DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST
SYSTEMS
23 03 00.00 20 BASIC MECHANICAL MATERIALS AND METHODS 121
23 05 48.19 SEISMIC BRACING FOR HVAC 126
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS 134
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHERS
BUILDING CONTROL SYSTEM
23 31 13.00 40 METAL DUCTS 166
DIVISION 25 INTEGRATED AUTOMATION
25 05 11 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS 179
DIVISION 26 ELECTRICAL
26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS 215
26 20 00 INTERIOR DISTRIBUTION SYSTEM 221
DIVISION 28
ELECTRONIC SAFETY AND SECURITY
28 31 76 INTERIOR FIRE ALARM SYSTEM 234
QUUG 23-1024
01 11 00
SECTION 01 11 00
SCOPE OF WORK AND DRAWINGS
SCOPE OF WORK: This project is intended to upgrade the existing heating, ventilation and air conditioning (HVAC) system in building #314. The main deficiencies of the system are the lack of external ventilation and some problems related to noise and difficulties in achieving comfort cooling and heating conditions in the different spaces. The construction works consist of, but are not limited to, the items indicated below, including the testing to be performed by independent laboratories for quality control. All items do not limit or reduce the Contractor’s responsibility to design and build all works as required by the project in order to provide a complete, operational and low-maintenance facility.
1. Architectural works:
1.1 Minor selective demolitions: false ceiling, metal roof panel, structural courtyard etc
1.2 Close minor gaps in façade and interior partitions
1.3 Minor selective works: new false ceiling, new metal roof panel, structural courtyard, new tramex, etc
2. Fire Alarm:
2.1 Replace existing FACP with a new FACP.
2.2 Provide new smokes detector in the supply duct of the new DOAS and FACP.
2.3 Existing FA devices in building 314 will be left as they are today, by connecting these devices to the new FACP by using addressable interface devices (from four analog loop circuits to four addressable circuits).
3. Mechanical works:
3.1 Removed existing HVAC equipment
3.2 The existing duct system is to be reused and and selective demolition shall be performed in the duct system and accessories according to the drawings
3.3 Install HVAC system to cover all areas. Provide a Dedicated Outside Air
(DOAR) unit for ventilation of the whole area.
3.4 Provide Control system and TAB.
3.5 Provide Cybersecurity
3.6 Existing duct cleaning
3.7 Duct disinfection
4. Electrical works:
3.1 Provide electrical interior distribution system for new HVAC equipment
DRAWINGS:
PLANOS DW G. No HOJA No.
DRAW ING PLANO No. SHEET No.
HOJA TÍTULO
TITLE SHEET
GC1 01 R-826-03 3 OF 61
RUTAS DE ACCESO Y ZONAS DE ACOPIO
GI002 R-826-02 2 OF 61
ACCESS ROUTES AND STOCKPILING AREAS
RELAC IÓN DE PLANOS
RELACIÓN DE PLANOS / DRAW ING SCHEDULE
TÍTULO DE HOJA / TITLE SHEET
GENERAL / GENERAL
GI001 R-826-01 1 OF 61
DRAW INGS SCHEDULE
GC1 02 R-826-04 4 OF 61
FASES DE CONSTRUCC IÓN - PLANTA BAJA Y PLANTA ÁTICO DE CUBIERTA
CONSTRUCTION PHASING - GROUND FLOOR AND ROOF ATTIC FLOOR PLAN
PLANOS DW G. No HOJA No.
DRAW ING PLANO No. SHEET No.
EXTER IOR UTILITIES SITE PLAN
GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
CU1 01 R-826-06 6 OF 61
PLANTA DE INSTALAC IONES EXTER IORES
RELACIÓN DE PLANOS / DRAW ING SCHEDULE
CIV IL / CIVIL
TÍTULO DE HOJA / TITLE SHEET
C-001 R-826-05 5 OF 61
NOTAS GENERALES, SIMBOLOS Y ABREV IATURAS
PLANOS DWG. No HOJA No.
DRAWING PLANO No. SHEET No.
RELACIÓN DE PLANOS / DRAWING SCHEDULE
FIRE ALARM SYSTEM. GROUND FLOOR
TÍTULO DE HOJA / TITLE SHEET
PROTECCIÓN CONTRA INCENDIOS / FIRE PROTECTION
FA101 18 OF 60
SISTEMA DE ALARMA DE INCENDIOS. PLANTA BAJA
AE503 R-826-1 7 1 7 OF 61
DETALLES 3 DE 3
AE502 1 6 OF 61
DETALLES 2 DE 3
AE501 1 5 OF 61
DETALLES 1 DE 3
R-826-1 5
EQU IPMENT COURTYARD FLOOR PLAN AND SECTIONS
DETAILS 2 OF 3
DETAILS 1 OF 3
AE402 1 4 OF 61
PLANTA Y SECC IONES DE PATIO DE INSTALAC IONES
R-826-1 4
AE1 01 R-826-1 2 1 2 OF 61
PLANTA DE FALSO TECHO REFLEJADO
ROOF ATTIC FLOOR PLAN. ROOF MODIFIC ATIONS. ENLARGED PLANS
R-826-1 3
EXISTING CONDITIONS AND DEMOLITION. EQU IPMENT COURTYARD FLOOR PLAN
AND SECTIONS
AE401 1 3 OF 61
PLANTA ÁTICO DE CUBIERTA . MODIFIC AC IONES DE CUBIERTA . PLANTAS
AMPLIADAS
EXISTING CONDITIONS AND DEMOLITION. ROOF ATTIC FLOOR PLAN. ENLARGED
PLANS
REFLECTED FALSE CEILING PLAN
AD402 R-826-1 1 1 1 OF 61
ESTADO ACTUAL Y DEMOLIC IÓN. PLANTA Y SECC IONES DE PATIO DE
INSTALAC IONES
AD401 R-826-1 0 1 0 OF 61
ESTADO ACTUAL Y DEMOLIC IÓN. PLANTA ÁTICO DE CUBIERTA . PLANTAS
AMPLIADAS
AD1 02 R-826-09 9 OF 61
ESTADO ACTUAL Y DEMOLIC IÓN. PLANTA ÁTICO DE CUBIERTA
EXISTING CONDITIONS AND DEMOLITION. ROOF ATTIC FLOOR PLAN
ARQUITECTURA / ARCHITECTURAL
A-001 R-826-07 7 OF 61
NOTAS GENERALES, LEYENDA Y ABREV IATURAS
R-826-08 8 OF 61
RELACIÓN DE PLANOS / DRAW ING SCHEDULE
GENERAL NOTES, LEGEND AND ABBREVIATIONS
TÍTULO DE HOJA / TITLE SHEET
ESTADO ACTUAL Y DEMOLIC IÓN. PLANTA BAJA
EXISTING CONDITIONS AND DEMOLITION. GROUND FLOOR .
AD1 01
R-826-1 6
DETAILS 3 OF 3
PLANOS DWG. No HOJA No.
DRAW ING PLANO No. SHEET No.
PROTECC IÓN CONTRA INCENDIOS / FIRE PROTECTION
FA1 01 R-826-1 8 1 8 OF 61
SISTEMA DE ALARMA DE INCENDIOS. PLANTA BAJA
FIRE ALARM SINGLE DIAGRAM SYSTEM CONTROL PANEL
FA701 R-826-1 9 1 9 OF 61
RELAC IÓN DE PLANOS / DRAW ING SCHEDULE
FIRE ALARM SYSTEM. GROUND FLOOR
TÍTULO DE HOJA / TITLE SHEET
ESQUEMA UNIFILAR DEL PANEL DE ALARMAS CONTRA INCENDIOS
TÍTULO DE HOJA / TITLE SHEET
RELACIÓN DE PLANOS / DRAW ING SCHEDULE
CLIMA TIZA CIÓN / HVAC
GENERAL NOTES, LEGEND AND ABBREVIATIONS. 1 OF 2
M-002
M-001 R-826-20 20 OF 61
NOTAS GENERALES, LEYENDA Y ABREV IATURAS. 1 DE 2
M-003
GENERAL NOTES, LEGEND AND ABBREVIATIONS. 2 OF 2
R-826-21 21 OF 61
NOTAS GENERALES, LEYENDA Y ABREV IATURAS. 2 DE 2
MD1 01
HVAC SYSTEM DESCR IPTION
R-826-22 22 OF 61
DESCR IPC IÓN DEL SISTEMA DE HVAC
MD1 02
HVAC EXISTING CONDITIONS AND DEMOLITIONS. GROUND FLOOR
R-826-23 23 OF 61
ESTADO ACTUAL Y DEMOLIC IÓN DE CLIMATIZAC IÓN. PLANTA BAJA
MH001
HVAC EXISTING CONDITIONS AND DEMOLITIONS. ROOF ATTIC FLOOR PLAN
R-826-24 24 OF 61
ESTADO ACTUAL Y DEMOLIC IÓN DE CLIMATIZAC IÓN. PLANTA ÁTICO DE
CUBIERTA
MH002
HVAC SYSTEM GENERAL FLOOR PLAN. GROUND FLOOR
R-826-25 25 OF 61
PLANTA GENERAL DEL SISTEMA DE HVAC . PLANTA BAJA
MH1 01
HVAC SYSTEM GENERAL FLOOR PLAN. ROOF ATTIC FLOOR PLAN
R-826-26 26 OF 61
PLANTA GENERAL DEL SISTEMA DE HVAC . PLANTA ÁTICO DE CUBIERTA
MH1 02
HVAC FLOOR PLAN. GROUND FLOOR . 1 OF 3
R-826-27 27 OF 61
PLANTA DE VENTILAC IÓN Y CLIMATIZAC IÓN. PLANTA BAJA . 1 DE 3
MH1 03
HVAC FLOOR PLAN. GROUND FLOOR . 2 OF 3
R-826-28 28 OF 61
PLANTA DE VENTILAC IÓN Y CLIMATIZAC IÓN. PLANTA BAJA . 2 DE 3
MH1 04
HVAC FLOOR PLAN. GROUND FLOOR . 3 OF 3
R-826-29 29 OF 61
PLANTA DE VENTILAC IÓN Y CLIMATIZAC IÓN. PLANTA BAJA . 3 DE 3
R-826-30
MH1 05
HVAC FLOOR PLAN. ROOF ATTIC FLOOR PLAN. 1 OF 2
PLANTA DE VENTILAC IÓN Y CLIMATIZAC IÓN. PLANTA ÁTICO DE CUBIERTA . 1 DE 2
MH301
HVAC FLOOR PLAN. ROOF ATTIC FLOOR PLAN. 2 OF 2
R-826-31 31 OF 61
PLANTA DE VENTILAC IÓN Y CLIMATIZAC IÓN. PLANTA ÁTICO DE CUBIERTA . 2 DE 2
SECC IONES. 1 DE 2
SECTIONS. 1 OF 2
MH302
R-826-32 32 OF 61
MP1 01
R-826-33 33 OF 61
SECC IONES. 2 DE 2
SECTIONS. 2 OF 2
PLANTA DE TUBER ÍAS DE DRENAJE Y REFR IGERANTE. PLANTA BAJA . 1 DE 3
DRAINAGE AND REFR IGERANT PIPES FLOOR PLAN. GROUND FLOOR . 1 OF 3
MP1 02
R-826-34 34 OF 61
MP1 03
R-826-35 35 OF 61
PLANTA DE TUBER ÍAS DE DRENAJE Y REFR IGERANTE. PLANTA BAJA . 2 DE 3
DRAINAGE AND REFR IGERANT PIPES FLOOR PLAN. GROUND FLOOR . 2 OF 3
PLANTA DE TUBER ÍAS DE DRENAJE Y REFR IGERANTE. PLANTA BAJA . 3 DE 3
DRAINAGE AND REFR IGERANT PIPES FLOOR PLAN. GROUND FLOOR . 3 OF 3
MP1 04
R-826-36 36 OF 61
MP1 05
DRAINAGE AND REFR IGERANT PIPES FLOOR PLAN. ROOF ATTIC FLOOR PLAN. 1 OF
R-826-37 37 OF 61
PLANTA DE TUBER ÍAS DE DRENAJE Y REFR IGERANTE. PLANTA
ÁTICO DE CUBIERTA . 1 DE 2
M-501
DRAINAGE AND REFR IGERANT PIPES FLOOR PLAN. ROOF ATTIC FLOOR PLAN. 2 OF
R-826-38 38 OF 61
PLANTA DE TUBER ÍAS DE DRENAJE Y REFR IGERANTE. PLANTA
ÁTICO DE CUBIERTA . 2 DE 2
M-502
DETAILS 1 OF 2
R-826-39 39 OF 61
DETALLES. 1 DE 2
DETALLES 2 DE 2
DETAILS 2 OF 2
R-826-40 40 OF 61
*** END OF SECTION ***
M-605
M-606
MI801
MI802
MI803
MI804
MI805
DIAGRAMA DE CABLEADO DEL EQU IPO DEL SISTEMA HVAC
HVAC SYSTEM EQU IPMENT W IR ING DIAGRAM
CUADROS DE DIFUSORES Y REJILLAS
DIFFUSERS AND GR ILLES SCHEDULE
ESQUEMA DE PR INC IPIO DE CLIMATIZAC IÓN
HVAC SYSTEM CONCEPT DIAGRAM
SECUENC IA DE CONTROL 1 DE 2
CONTROL SEQUENCE 1 OF 2
SECUENC IA DE CONTROL 2 DE 2
CONTROL SEQUENCE 2 OF 2
LISTA DE PUNTOS DE CONTROL DEL SISTEMA DDC
DDC SYSTEM CONTROL POINT LIST
DIAGRAMA DE LA ARQU ITECTURA DE CONTROL
NETWORK ARCHITECTURE DIAGRAM
R-826-45
R-826-49
M-601
M-602
R-826-41 41 OF 61
CUADROS DE EQU IPOS DE CLIMATIZAC IÓN 1 DE 3
HVAC EQU IPMENT SCHEDULES 1 OF 3
HVAC EQU IPMENT SCHEDULES 2 OF 3
CUADROS DE EQU IPOS DE CLIMATIZAC IÓN 2 DE 3
R-826-42 42 OF 61
HVAC EQU IPMENT SCHEDULES 3 OF 3
CUADROS DE EQU IPOS DE CLIMATIZAC IÓN 3 DE 3
43 OF 61R-826-43M-603
ESQUEMAS DE EQU IPOS DE CLIMATIZAC IÓN
HVAC SYSTEM EQU IPMENT DIAGRAM
M-604 R-826-44
R-826-46
R-826-47
R-826-48
R-826-50
M-901
R-826-51
M-902
3D VIEW . 1 OF 4
V ISTAS 3D 1 DE 4
R-826-52
M-903
3D VIEW . 2 OF 4
V ISTAS 3D. 2 DE 4
R-826-53
M-904
3D VIEW . 3 OF 4
R-826-54 54 OF 61
V ISTAS 3D. 3 DE 4
M-905
3D VIEW . 4 OF 4
R-826-55 55 OF 61
V ISTAS 3D. 4 DE 4
V ISTAS 3D AMPLIADAS
ENLARGED 3D VIEW
R-826-56 56 OF 61
PLANOS DW G. No HOJA No.
DRAW ING PLANO No. SHEET No.
TÍTULO DE HOJA / TITLE SHEET
RELACIÓN DE PLANOS / DRAW ING SCHEDULE
ELECTRICIDAD / ELECTRICA L
GENERAL NOTES, LEGEND AND ABBREVIATIONS
EP1 01
E-001 R-826-57 57 OF 61
NOTAS GENERALES, LEYENDA Y ABREV IATURAS
EP1 02
POWER SYSTEM FLOOR PLAN. GROUND FLOOR
R-826-58 58 OF 61
PLANTA DE FUERZA . PLANTA BAJA
E-601
POWER SYSTEM FLOOR PLAN. ROOF ATTIC FLOOR PLAN
R-826-59 59 OF 61
PLANTA DE FUERZA . PLANTA ÁTICO DE CUBIERTA
E-701
ELECTR ICAL PANELBOARD SCHEDULE
PANEL ELÉCTR ICO
R-826-60
R-826-61
ONE LINE DIAGRAM
ESQUEMA UNIFILAR
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK
PROJECT QUUG 23-1024
01 11 01
Page - 1 of 34
SECTION 01 11 01
GENERAL CONDITIONS
1. GENERAL: The work consists of furnishing all labor, materials, utilities, transportation, equipment, and services to execute the project. In accordance with the drawings and specifications, complete and ready for use. Measurements shown on the drawings and specifications are given for reference use only. They are not conclusive and may be erroneous.
It is the Contractor’s responsibility to verify any and all of measurements. The Government will not be held responsible for measurements shown or measurements and estimations made by the Contractor.
2. GENERAL DESCRIPTION: The work consists in, but is not limited to, executing the line items indicated in the scope of work. All line items indicated in the scope of work do not limit nor reduce the Contractor’s responsibility to perform all work as required by the project in order to provide a complete and usable facility.
3. LOCATION: The work is located in Morón Air Base, Spain, as shown on the contract drawings.
4. DRAWINGS ACCOMPANYING SPECIFICATIONS: Drawings are the property of the
Government and shall not be used for any purpose other than that contemplated by the specifications. The drawings indicated in the specifications are in A1 size.
5. WARRANTY: For this contract the Contractor shall provide a two-year standard commercial warranty for with all line items of the scope of work, including materials and workmanship. The warranty shall cover all defects noticed and reported to the Contractor within two years after acceptance of the work. The Contractor shall repair or replace defective materials at their expense within a reasonable time and as approved by the Contracting Officer.
The Contractor must comply with any additional warranty periods established by Spanish codes and regulations. The Contractor shall submit the warranty letter within 15 calendar days after to the acceptance of the work by the Contracting Officer.
6. BASE ACCESS:
6.1. Permits or Authorizations: The Contractor shall obtain all permits or authorizations required to access Morón Air Base. All the communications in relation to the Base Access request must be directed to Construction Management Section for PASS&ID Office processing. Once the works have finalized, the Contractor will return the permits or authorizations. Contractor is responsible to provide the required escorts as required to execute the works.
6.2. Delays and Interruptions: The Contractor is advised that delays are liable to occur, due to security reasons, during the access/egress process of personnel and materials from Morón
Air Base. Additionally, the Contractor shall immediately interrupt the work when it is required
Page - 2 of 34 if security warning/risk situations occur. The contractor shall submit in writing, excess delays
(90 minutes or more) experienced due to base access.
7. WORK CLEARANCE REQUEST:
7.1. 15 calendar days in advance, as minimum, before the commencement of the works, the
Contractor shall request AF Form 103 “BCE Work Clearance Request” to Construction
Management in order to obtain all the information pertaining to the current status of Base utilities. Additional requests shall be submitted to Construction Management 15 calendar days in advance, at minimum. The Contractor shall not perform any work under any circumstances without having the approved Work Clearance at the construction site (hard copy) and not before having marked at the site with stakes and/or pins the location of the utilities. Work Clearance
Request shall only be processed once all materials and documentation necessary to commence work have been submitted and approved. The Contractor shall be responsible for any damage caused to Base utilities shown on the AF Form 103 and project drawings and shall be responsible for the repairs without additional cost to the Government.
7.2. Return entire permit to Geobase Office after completion of digging excavating activities. If additional utilities are located or encounters (or marked utilities are not found in their expected locations) then the requester shall provide a sketch to Geobase office precisely detailing the location(s) of all utilities that were found to not be in the location expected within the 10 workdays after the discovery of the discrepancy.
8. BASE UTILITIES:
8.1. The Contractor, at its expense and in coordination with the Contracting Officer or CE personnel, shall install and maintain all necessary temporary connections and distribution lines.
Before final acceptance of the work by the Government, the Contractor shall remove all the temporary connections, distribution lines, and associated accessories.
8.2. Use of Base Utilities: Water, sewage and electrical utilities may be available to the
Contractor for supply to the following buildings: Offices, latrines, break rooms and laboratories. If the contractor wants any of these available utilities, the contractor must provide the material for the temporary utility connection and he must perform the work for the temporary utility installation. If the contractor does not want any of these available utilities, the contractor is responsible for providing their own utilities at no additional cost to the government. Contractor must request officially the connection points needed in the Mobility
Plan for CE review/approval.
Other utilities, apart from the listed below, shall be supplied by the Contractor at no cost to the
Government.
The following utilities are available from the existing Base utilities:
1. Electricity: 120/208 volts, 60 Hz.
2. Non-potable water.
Page - 3 of 34
8.3. Base utility connection and/or disconnection: 15 calendar days before the connection/disconnection date, the Contractor shall request the connection and/or disconnection and shall indicate:
1. Type of utility required
2. Type of connection and/or disconnection to be performed
3. Utility use
4. Required consumption
5. Maximum duration
All connection and/or disconnection works of Base utilities shall be programmed between
08:30 and 16:00 hours (between 08:30 to 15:00 during the period from 15 June to 15
September) from Monday to Friday, except holidays. The utility connections and/or disconnections can be considered critical by the Government, in which case they shall be performed on the date and time most convenient to the Government, i.e. weekends and/or during nighttime hours, without additional cost to the Government. The Contractor shall be responsible for making connections and/or disconnections, conversion, transportation of Base utility to the work site, including the furnishing and installation of the mechanisms that prevent the backflow of water to the Base service (backflow preventers) and the furnishing and installation of the transformers, if required. The Contractor shall not activate or alter any control device of the Base utilities including water, sewage and electricity. The Government shall operate said control devices. The Contractor shall submit additional requests to
Construction Management with a minimum of 15 calendar days in advance of the estimated date for the required connection, disconnection or control maneuver of the corresponding utility. The temporary overhead connections to utility are prohibited. All utilities shall be restored to their original condition prior to satisfying final contractual payments.
8.4. Base Utility Outages: When a utility outage is necessary, the Contractor shall request the utility outage, at least 15 calendar days in advance of the work, and shall indicate:
1. Type of affected utility
2. Type of cut to be performed
3. Maximum duration
All utility outages shall be scheduled from 08:30 and 16:00 hours (from 08:30 to 15:00 during the period from 15 June to 15 September) from Monday to Friday, except holidays. The utility outages can be considered critical by the Government, in which case they shall be performed on the date and time most convenient to the Government, i.e. weekends and/or during nighttime hours, without Government cost. The Contractor shall be responsible for making the outage, including the provision and installation of devices and materials. The Contractor shall not
Page - 4 of 34 activate or alter any control device of the Base utilities, including water, sewage and electricity.
The Government shall operate said control devices. Temporary overhead connections to utility are prohibited. All systems shall be restored to their original condition prior to satisfying final contractual payments.
9. HOT WORK: The Contractor shall submit for approval a written request to Construction
Management 15 calendar days prior to any welding, as oxyacetylene or plasma cutting work.
Said request shall indicate welding procedures and fire prevention measures. All welding work performed during the project execution shall be carried out by qualified welders only. The copies of the welder certificates, issued by an approved agency, shall be kept in the construction inspector’s files. Contractor will be responsible to keeping in effect the Hot Work Permit along the project execution period with the frequency established by the Fire Prevention Department.
10. VEHICULAR, MACHINERY AND EQUIPMENT TRAFFIC:
10.1. Transit Control Plan: All works requiring vehicular or pedestrian traffic disruptions on the Base shall require an approved transit control plan. Said plan shall be approved at least 15 calendar days prior to carrying out said disruption. Said plan shall include:
1. Start date of the traffic disruption
2. Duration of the traffic disruption
3. Proposed alternative routes
4. Signs, barriers, cones, flags and/or flagmen to be implemented
The Contractor shall establish alternate procedures if unforeseen circumstances take place. The responsibility of the provision, erecting, keeping and removing all signs, barriers, cones and flags shall be solely the Contractor. Once the work is completed, the Contractor shall remove the signaling elements such as signs, barriers, cones and/or flags.
10.2. Access Route Plan: 10 calendar days after the contract commencement date, the
Contractor shall submit an access route plan to Construction Management for its approval by
Contracting Officer or authorized representative.
10.3. Trucks: Trucks loaded with loose material (volatile dust, construction debris or other objects that could fall from them) shall be duly covered. Said covers (tarpaulins, etc.) shall be securely secured and placed on the load before accessing the Base roads.
11. STOCKPILING:
11.1. Stockpiling area of demolished/removed material: The Contractor shall transport the demolished or excavated materials to an authorized dump. Should any of the Morón Air Base shops need all or part of any of the materials from the demolition operations (concrete, aggregate and natural ground), the Contracting Office representative shall coordinate with the base
Construction Management office on the exact location to stockpile said material.
Page - 5 of 34
11.2. Stockpiling area for Contractor material and Contractor offices: The C.O. representative shall coordinate with the base Construction Management office the exact location for Contractor offices and stockpiling.
12. CONSTRUCTION SCHEDULE:
12.1. It shall be the sole responsibility of the Contractor to ensure all required submittals are submitted for approval in a timely manner, which shall not incur any delay in completion of the project. For materials or equipment requiring a long term of procurement and delivery, said term shall be included in the period of performance. Delay in delivery/procurement will not justify an extension of the period of performance.
12.2. The Contractor shall submit an updated Construction Schedule within 7 calendar days after the Construction Phase starting date and when requested by the Contracting Officer or his authorized representative. In no case is the Contractor required to submit an updated more frequently than 20 working days. For Design-Build contracts, the updated Construction Schedule shall be submitted prior the actual construction starts.
12.3. The Construction Schedule shall include a Gantt chart showing each task, including task description, identification number, duration in calendar days, earliest start and finish dates, predecessor and successor task identification numbers, critical path and float that a task in the project network can be delayed without causing a delay to the subsequent task/s (free float) and to the project completion date (total float). The critical path shall be shown by means of a red color line and the float by means of black line after the predecessor task bar.
12.4. The Construction Schedule shall show the whole week, from Monday through Sunday.
The labor days shall be from Monday through Friday. Saturday and Sunday shall be non-labor days. The holidays shall not be considered on the Construction Schedule and, therefore, they shall be considered labor days for Construction Schedule development purpose only.
12.5. The Construction Schedule shall be developed assuming 8-working hours for each labor days.
12.6. The Construction Schedule must include the following tasks if required:
12.6.1. Preconstruction tasks:
1. Preparation and transmittal of the bond and insurance submittals.
2. Preparation, transmittal, and approval of the submittals shown on document Schedule of Material Submittals (progress schedule, mobility plan, project sign, quality control plan, key staff, health and safety plan, environmental protection plan, AF Form 103 BCE Work Clearance Request, utility connection request, utility outage requests, welding work request, transit control plan, access routes, materials and equipment).
Page - 6 of 34
3. Procurement, fabrication and delivery on construction site of long lead time materials, equipment and fabricated assemblies.
4. The installation of the portable/modular buildings (rest room, dressing room, dining room, first aid, office, if required).
5. The installation of temporary connections from the portable/modular buildings to the utilities of the base.
6. The installation of the temporary fence and fabric plastic mesh along the perimeter of the area assigned for the Contractor (equipment and material storage, personnel vehicle parking area, portable/modular buildings, off-construction site disposal and waste area, if required).
7. The installation of the project sign.
8. The installation of the temporary plastic Jersey barriers filled with water, fence, fabric plastic mesh, cones and lights along the perimeter of the construction site.
9. The installation of the temporary signs, barriers, cones and flags along the transit routes.
10. The installation of the temporary occupational safety and health signs
(prohibition, mandatory, warning, help, fire prevention, danger, directional board) at the area assigned for the Contractor.
11. The installation of the temporary occupational safety and health signs at the construction site.
12.6.2. Construction tasks:
1. The construction tasks shown on the AF Form 3052, Construction Cost
Estimate Breakdown, including testing, curing time and the submission of the delivery tickets of the waste and construction debris and the approval of the field test result data.
12.6.3. Finish tasks:
1. Required testing.
2. Commissioning.
3. Pre-final inspection, including the request.
4. Correction of deficiencies.
Page - 7 of 34
5. Final inspection, including the request.
6. The removal of the temporary occupational safety and health signs at the
7. The removal of the temporary plastic Jersey barriers filled with water, fence, fabric plastic mesh, cones and lights along the perimeter of the
8. Final cleaning.
9. The removal of the temporary signs, barriers, cones and flags along the transit routes.
10. The removal of the project sign.
11. The removal of the temporary occupational safety and health signs at the area assigned for the Contractor.
12. The removal of temporary connections to the utilities of the base, including the preparation and transmittal of the utility disconnection request, the utility outage request and the approval of the Government.
13. The removal of the portable/modular buildings.
14. The removal of the temporary fence and fabric plastic mesh along the perimeter of the area assigned for the Contractor.
15. Restoration of the area assigned for the Contractor. To include restoration of all grass by means of hydro seeding. Final project acceptance and progress report will not be approved until grass is established and accepted by
Contracting Officer.
16. Preparation and transmittal of the letter submittal about the inventory of all excess supplies, materials and equipment imported duty free for use under this contract.
17. Preparation and transmittal of the As-Built drawing submittal.
18. Preparation and transmittal of the spatial data submittal.
19. Preparation and transmittal of the warranty letter submittal.
20. Preparation and transmittal of the submittal of a certificate from the authorized dump about the estimated amounts or waste and construction debris managed during the execution of the project.
Page - 8 of 34
21. Approval of the submittals.
22. Project closeout.
13. PROGRESS SCHEDULE (AF Form 3064): Within the 10 calendar days after the contract commencement date or another period determined by the Contracting Officer, the Contractor shall develop and submit a practicable schedule to Construction Management for its approval by Contracting Officer or authorized representative. The plan shall show:
1. Activity sequence that the Contractor proposes to perform the work.
2. Dates proposed by the Contractor for the start and completion of the salient features of the work (including the acquiring of materials, plant and equipment).
The progress schedule of the work shall be delivered in the line graphic format at an adequate scale indicating the percentage of work scheduled every 30 calendar days for its execution during the performance period. The programmed works shall correspond to the line items of the cost estimate of the contract. If the Contractor fails to submit a progress schedule of the works within the established period, the Contracting Officer may withhold the approval of the progress payments until the Contractor submits the required progress schedule.
14. PROGRESS REPORT (AF Form 3065): Every 30 calendar days progress report to be submitted to Construction Management Office in accordance with previously submitted
Progress Schedule AF Form 3064. If the Contractor fails to submit a progress report of the works within the established period, the Contracting Officer may withhold the approval of the progress payments until the Contractor submits the required progress schedule. No work items will be considered 100% complete until approval of preconstruction and final submittals required. For each individual project Contracting Officer will determine the maximum percentage of work complete without preconstruction and final submittals required.
15. WORK PLAN
15.1 The Contractor shall submit a Work Plan within 7 calendar days after the Construction
Phase starting date. The Work Plan shall present the construction activities planned to take place.
The Work Plan shall be prepared in coordination with the Health and Safety Plan and the Quality
Control Plan and shall contain the following:
1. The summary of the proposed methodology for the execution of each task required for the project completion.
2. The resources to be used for the execution of each task required for the project completion describing the equipment and personnel to be used.
3. Daily production for each task required for the project completion.
Page - 9 of 34
16. MOBILITY PLAN: The Contractor shall submit a mobility plan to Construction
Management for its approval by Contracting Officer or authorized representative. Said plan shall show:
1. Location and area of the work site.
2. Location and area of the offices.
3. Location and area of the parking area.
4. Location and area of the material storage areas.
The Contractor shall include in the mobility plan the proposed system to supply the utilities required at each site.
16.1. Construction Site Fencing: The construction site, offices, parking area, latrines, and material storage areas shall be fenced in by means of a two-meter high fence with gates and locks, unless otherwise approved the Government. The Contracting Officer or authorized representative shall specify the type of fencing, height and color. Fences shall be screened with a green opaque mesh to prevent the view of the inside of the fenced area from the outside. Fencing shall be completely secured at top and bottom to prevent the access to the fenced area. The fence and mesh shall be adequately anchored to prevent their failing during high wind gusts. The Contractor shall include in the Mobilization Plan:
1. Photos, catalogs or samples of the fence to be used
2. Photos, catalog or samples of the mesh to be used
The Contractor shall not start the installation of the fencing and mesh until the plan is approved in writing by the Contracting Officer or authorized representative. The responsibility of providing, erecting, keeping and removing all the fences and meshes shall be solely the
Contractor. The Contractor shall replace or repair, within the following 24 hours or as determined by the Contracting Officer or authorized representative, all fence or mesh sections that have been damaged or deteriorated. Once the works have been finalized, the Contractor shall remove the fences and meshes.
16.2. Offices: Temporary prefabricated buildings required for administrative reasons (office space, conference room and break room) shall be in good conditions. Temporary prefabricated buildings requiring paint, repairs or are in bad conditions shall not be allowed at the site. Said temporary prefabricated buildings shall show on the outside a plaque of 0.5 x 0.5 meters maximum dimensions, indicating the name of the company and telephone number (s) of the person (s) designated as POC for the Contractor. Once the works are finalized, the Contractor shall remove the temporary prefabricated buildings.
16.3. Latrines: Prefabricated temporary buildings required for personnel latrines shall be in good conditions. The prefabricated temporary buildings requiring paint, repairs or are in bad conditions shall not be allowed on the work site. These buildings shall be kept in perfect use conditions and
Page - 10 of 34 sanitized, shall be treated for insects and shall be emptied and cleaned with a detergent for sanitary use once a week. The frequency of emptying and cleaning shall be adjusted according to needs.
The prefabricated temporary buildings shall be located at no less than 50 meters from the existing buildings of Base if they cannot be located near a sewage manhole. Once the works have been completed, the Contractor shall remove the temporary facilities and shall leave the area clean and sanitized.
16.4. Parking: The Contractor, their employees and subcontractors shall park all vehicles, including heavy machinery, equipment and vehicles, in areas where they do not pose an obstruction in the corresponding work site.
16.5. Material Storage: Material storage containers shall be in good conditions. The storage of materials, in containers or not, at the work site shall be at the Contractor’s risk. The use of private security guards at the work site shall require the previous Spanish Air Force Security Forces approval. The Contractor shall not use the work site to store material. Once the works have finished, the Contractor shall remove the excess stored material.
17. PROJECT SIGN: Within 15 calendar days after the Construction Phase starting date, the
Contractor shall install an identifying work/project sign in accordance with Figure 1 no later than one day after the work site fencing is completed. The sign shall be mounted on two wooden posts of 10 cm x 10 cm, as minimum, fastened to the ground and adequately anchored. The location of said sign shall be determined by the Contracting Officer or his representative. During final cleanup of the work site, the sign, posts, fasteners and anchoring elements shall be removed. Unless otherwise specified, the sign shall have white background and the lettering shall be dark blue.
When the performance period and completion date are contractually modified, the contractor shall replace the project sign within 15 calendar days after the contract modification at no cost to the
Government.
Page - 11 of 34
FIGURE 2: PROJECT SIGN
18. QUALITY CONTROL PLAN: Within 15 calendar days after the Construction Phase starting date and after the approval of the Work Plan, the Contractor shall submit for its approval a complete Quality Control Plan in English and Spanish which may be consulted by the workers at the Contractor's offices at the site.
18.1. Content: The plan shall contain at minimum the following:
1. Names and qualifications of the proposed quality control chief and inspectors.
2. Organization Chart: Include the teaming partners/key subcontractors, and the works required for the project. The team partners/key subcontractors indicated shall be those that participate in the project and the same as those submitted in the contract bid. The lack of this information or variation with previously submitted teaming partners/key subcontractors is cause for the disapproval of the QC Plan.
3. Responsibility of the Quality Control Inspectors, Quality Control
Manager and the Project Manager.
4. Inspection types to be performed. The Contractor shall fully develop a
Program of Points Inspection (PPI) covering all types of works involved in the project. Development of the PPI shall be based in any and all of the following documents:
Page - 12 of 34
a. Project drawings and specifications.
b. Applicable regulations, standards and industry codes.
c. Specific regulations for certain products, installations or facilities.
d. Manufacturer’s recommendations.
The type and number of Inspection Points (IP) shall be the required to obtain an acceptable level of inspection for achieving the best quality results. The
Contracting Officer or authorized representative shall evaluate if the type and number of Inspection Points are sufficient to obtain the acceptable quality level.
5. Inspection procedures and actions to be taken for failed or unsatisfactory inspections.
6. Inspection Reporting Forms. Submit all reporting forms for any type of inspection to be performed under this project. As a minimum, a specific form shall be developed for each section of the specifications, covering all necessary inspection points for such work. Minimum information required for each IP shall be:
a. Description of the IP
b. Applicable documents
c. Type and frequency of inspection
d. Lot applied for the inspection
e. Responsible of the performed inspection
f. Inspection result
g. Date of inspection
h. Reference to non-compliance document/register, if not in compliance
i. Information about pass/rejection criteria for the IP
j. Other.
7. List of planned "Hold Inspection Points" with the estimated dates from the construction schedule.
Page - 13 of 34
8. "Schedule of Material Submittals" form of the project with column titled
"Required Submission Date" filled in by the Contractor with the dates estimated by the Contractor for the submission of the corresponding item. Said estimated dates shall be based on the period for the delivery and review of the submissions and re-submissions, the period for the purchase orders, acquisitions and receptions at the work site of the items, the approved Work Plan of the
Contractor and the completion date of the contract. If the Work Plan is modified, the Contractor shall update the "Schedule of Material Submittals" form.
9. Material Testing: Submit the name and qualifications of the testing agency or laboratory planned for testing. All test reports shall be submitted in time for review and approval. The work activity related to these tests can only be continued when the test report has been approved. If any test report fails, the following work activities shall not be executed until after the fault has been corrected. The Contractor shall be responsible for checking that all reports are reviewed by him and taking the necessary actions to resolve any failed test.
10. Perform daily reports of all activities carried out during the contract term. These daily reports shall be kept at the work site and shall be available for review at all times. A copy of the daily reports performed from Monday to
Friday (or Sunday if the Contractor works during the weekend) shall be submitted weekly to Construction Management. The daily report shall include, at least, the following:
a. Inspection date
b. Weather conditions
c. Inspection of the equipment and materials delivered at the work site and their delivery date
d. Names of people who have visited the work site during the day and visit date
e. Inspection of the deficiencies found during the day and the taken corrective actions
f. Inspection and acceptance of the materials and workmanship.
g. Work performed during the day, including the used personnel and equipment
h. Any field change or modification approved by the
Contracting Officer.
Page - 14 of 34
18.2. Daily Report electronic file naming. Each Daily Report shall be named as indicated on this paragraph, failure in doing so will result in rejection of the daily report and the Contractor has to resubmit it. Daily Report file names shall have the following format: XXXXXXX, YYYYYY, Daily Report, from ZZZZ WW VV to SSSS UU TT, where:
1. XXXXXXX stands for the contract number last seven digits, after removing the first “FA5575“digits.
2. YYYYYY stands for the project number
3. ZZZZ stands for the year in which the inspection is made on Monday
4. WW stands for the month in which the inspection is made on Monday
5. VV stands for the month in which the inspection is made on Monday
6. SSSS stands for the year in which the inspection is made on the last day of the weekly period (Friday or Sunday)
7. UU stands for the month in which the inspection is made on the last day
8. TT stands for the month in which the inspection is made on the last day
18.3. Acceptance of the Construction Quality Control (QC) Plan: Acceptance of the QC Plan is required before the start of the work. The Contracting Officer reserves the right to require changes in the QC Plan, operations and key personnel, including the dismissal of personnel, to ensure the specified work quality.
18.4. The Contractor shall be responsible for keeping the records.
19. LABORATORY TESTING:
19.1. Laboratory: All sampling and testing shall be performed by an approved laboratory, independent from the Contractor, that is accredited in accordance with a current UNE-EN
9001:2000 and registered by Junta de Andalucía for the following tests. The laboratory shall be the responsible to perform the entire quality control of the project, shall be as a consultant and shall provide the technical assistance that can be required.
19.2. Laboratory Tests: Laboratory tests performed more than 6 months before the submission date shall not be accepted.
20. PRE-FINAL AND FINAL INSPECTIONS: The pre-final and final inspections shall be conducted jointly with the Contractor, the Government inspector and a representative of the
Contracting Office. The Contractor shall request a pre-final inspection once the works are completed in accordance with the inspector's judgement. After the solving of all the
Page - 15 of 34 discrepancies found during the pre-final inspection, if any, the Contractor shall request a final inspection. All punch list items must have been completely fixed before final acceptance of the project works. The Contractor shall request to Construction Management the pre-final or final inspection at least 15 calendar days in advance of the desired date.
21. WORKDAY:
21.1. Normal Workday: Normal workday shall be from 08:00 to 17:00, from Monday to
Friday, except holidays. The Contractor shall perform all work during normal workday unless the Contracting Officer or authorized representative issues a special authorization to deviate from said work schedule.
21.2. Special Working Hours: If the Contractor wishes to work outside the normal working hours, on Saturdays, Sundays or holidays, he shall submit a request to the Contracting Officer with at least 10 calendar days in advanced for evaluation (approval/disapproval).
22. CONSERVATION AND MAINTENANCE OF THE EXISTING FACILITIES:
Before the start of any work activity, the Contractor will carry out an inspection of the existing facilities at the work site (or adjacent to it), as well as the pavements proposed by the Contractor on the Transit Control Plan and on the Access Route Plan. The Contractor shall submit a report in writing, attaching photographs, to Construction Management of all the defects found during said inspection. The Contractor shall conserve and protect all existing facilities at the work site and adjacent to the work site. The Contractor shall repair all the defects that were not documented in the original report or have been further damaged by the Contractor's construction activities or negligence. These repairs will be completed without additional cost to the Government and before the final acceptance of the project.
23. ENVIRONMENTAL PROTECTION PLAN: Within 15 calendar days after the
Construction Phase starting date, the Contractor shall submit to Construction Management for its approval by Contracting Officer or authorized representative an Environmental Protection
Plan, in English and Spanish versions, which may be consulted by the workers at the
Contractor's offices at the site. The contractors are responsible for the entire process of requesting environmental permits (where necessary) to conduct work after the approval from
Spanish Air Force (SpAF) Base Commander. The contractor must submit the request for the
SpAF Base Commander’s approval to Civil Engineering. The program shall comply with applicable Spanish regulations and the below standards.
23.1. Integrated Natural Resources Management Plan for Morón Air Base (2015 - 2020)
23.2. Final Environmental Governing Standards for Spain, May 2014
23.3. Conservation and Maintenance of the Existing Vegetation: The Contractor shall conserve and protect the existing vegetation (trees, shrubs, grass) on the work site or adjacent to it that has not to be removed or has not to be affected by the works required by this contract.
The Contractor shall only remove the trees and/or shrubs when specifically indicated on the specifications and drawings and shall avoid damaging the remaining vegetation. If any tree
Page - 16 of 34 branch is split during the execution of the works due to the handling of the equipment or due to some carelessness of the workers, the Contractor shall prune those affected branches with a clean cut and apply a pruning paste to said cut. The Contractor shall cut the vegetal cover and/or turf at the work site to include a minimum of 1 meter outside of fencing so that it does not exceed 10 cm in height. The Contractor shall restore, at no additional cost to the Government, to its original condition the area affected during the execution of the project works before the final acceptance of project works.
23.4. Site Cleaning: The Contractor shall remove debris, waste materials and garbage and shall keep the site always tidy. All waste materials and garbage shall be placed in containers provided by the Contractor, which shall be removed daily outside of the Base to an authorized dump during the progress of the work. The Contractor shall ensure that all volatile wastes are placed in suitable containers to prevent that the wind blows them to adjacent areas and/or the aerodrome. Once the works are completed, the Contractor shall remove the containers.
23.5. Access Route Cleaning: The Contractor shall be solely responsible for any material dumped/spilled by trucks, vehicles, machinery or equipment on the access routes. Said material deposited on the access routes shall be removed by the Contractor immediately. The Contractor shall be responsible for ensuring that all access routes are kept clean at all times. No amount of material deposited on the access routes shall be tolerated.
23.6. Waste and Debris: The Contractor, 15 calendar days prior to the final inspection date, shall submit a certificate from the authorized dump or waste management plant to the
Construction Management for its approval by Contracting Officer or authorized representative with the quantities of waste and debris managed during the period of the execution of the works.
The delivery tickets shall be previously delivered to Construction Management for their review during the work execution. A report detailing the types and quantities of construction debris removed will be provided to the environmental section upon completion of the works.
23.7. Hazardous Material: The contractor shall provide SDSs to the environmental section for review for each chemical they will be using to execute the project. Estimated quantities of each chemical to be used will also be provided. Before transporting any hazardous material, the Contractor shall contact the Chief of Construction Management to coordinate its handling, transportation and storage. The Contractor shall be responsible for complying with all applicable environmental regulations related to handling, transportation and storage of hazardous materials and/or waste.
23.8. Noise Control and Prevention: The Contractor shall comply with all applicable state, autonomous community, municipality and Base regulations related to the control and prevention of the noise. The Contractor shall take the measures required to prevent and control the noise in the vicinity of the construction area.
23.9. Dust Control and Prevention: The Contractor shall comply with all applicable state, autonomous community, municipality and Base regulations related to the control and prevention of the dust. The Contractor shall take the measures required to prevent and control the dust in the vicinity of the construction area.
Page - 17 of 34
23.10. Storm Water Pollution Control and Prevention: The Contractor shall comply with all applicable state, autonomous community, municipality and Base regulations related to the control and prevention of the pollution of the storm water. The Contractor shall take the measures required to prevent and control the pollution of the surface and ground storm waters.
24. SPECIFICATIONS AND DRAWINGS FOR THE CONSTRUCTION: (See
Solicitation/Contract FAR clause 52.236-21, Specifications and Drawings for Construction, Feb 1997).
24.1. Maintenance and Updating of Specifications and As-Built Drawings: During the work execution, the Contractor shall keep 2 sets of specifications and drawings at A1 size. All the variations between the work as it has been built and the one indicated or specified on the original documents of the contract shall be shown in red. The As-Built drawings shall be kept updated at the work site at all times during the contract. All the revisions of the drawings shall be shown as follows:
1. The revisions shall be numbered
2. The revisions shall be marked in red accompanied with the revision number
3. The revision number…