This is a Scope of Work (SOW) for RFQ 140P8326Q0038 issued by Nez Perce National Historical Park for the replacement of fire-rated collection storage vault doors. The project is located at 39063 US Hwy 95, Lapwai, ID 83540-9715.
The primary requirement is to replace existing hollow metal doors with UL-listed fire-rated hollow metal doors and frames equipped with automatic door closers and fire-rated hardware. The scope includes two doors: B3 (Archive Vault Door), a double door measuring 86" H × 76.25" W, and Option A—B2 (Collections Storage Vault Door), a single door with dimensions to be determined, contingent on funding acquisition. Required tasks encompass removal of existing doors and frames, installation of new fire-rated assemblies, installation of fire-rated hardware including Grade 1 mortise locksets with ADA levers, deadbolts, continuous geared hinges, flush bolts for the inactive leaf, security astragals, perimeter smoke/draft control gasketing (UL 1784 compliant), ADA-compliant thresholds, and NFPA 80-compliant automatic door closers. Additional deliverables include paint finishing to match existing walls, provision of UL fire labels and compliance documentation, and commissioning activities comprising keying, closer adjustment, ADA force checks, and punchlist completion.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_3_Forms_to_Return_with_Quote.pdf | ||
| Sol_140P8326Q0038.pdf | ||
| Attachment_A_Wage_Determination.pdf | ||
| Attachment_2_Quote_Instructions.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFQ 140P8326Q0038 Nez Perce National Park
Replace Fire Rated Collections Vault Doors
Scope of Work (SOW)
Project: Fire-Rated Door Replacement for Collection Storage
Location: Nez Perce National Historical Park, 39063 US Hwy 95, Lapwai, ID 83540-9715
Project Overview & Fire Protection Narrative
The doors serving the collection storage were made of hollow metal without fire door labels and automatic door closers. Concrete walls provide at least a 1-hour fire resistance rating. Gypsum walls separating the work prep area from mechanical equipment. The walls have unknown fire ratings but offer some smoke resistance.
NPS Museum Fire Protection requires compartmentation for dedicated storage collection with appropriate fire resistance rating. Replacing existing walls to achieve proper fire rating is not recommended. Instead, replacing existing hollow metal doors with fire-rated hardware and automatic door closers is recommended to meet compartmentation requirements.
Scope of Work
Replace existing hollow metal doors with UL-listed fire-rated hollow metal doors and frames equipped with automatic door closers and fire-rated hardware.
This includes:
• B3: Archive Vault Door (Double Door, 86" H × 76.25" W)
• Option A (if funding is acquired) B2: Collections Storage Vault Door (Single Door, dimensions
TBD)
Tasks:
• Remove existing doors and frames.
• Install new fire-rated assemblies and frames.
• Install fire-rated hardware: mortise lock, deadbolt, flush bolts (inactive leaf), continuous hinges, security astragal, perimeter smoke seals, ADA-compliant threshold.
• Install automatic door closers (NFPA 80 compliant).
• Apply paint finish to match existing walls and doors.
• Provide UL fire labels and compliance documentation.
• Commissioning: keying, closer adjustment, ADA force checks, punchlist.
Hardware Schedule
RFQ 140P8326Q0038 Nez Perce National Park
Replace Fire Rated Collections Vault Doors
For each door:
• Fire-rated hollow metal door and frame (UL 10C/NFPA 80)
• Automatic door closer (fire-rated)
• Mortise lockset (Grade 1, ADA lever)
• Deadbolt (Grade 1)
• Continuous geared hinges
• Flush bolts (inactive leaf for B3)
• Security astragal
• Perimeter smoke/draft control gasketing (UL 1784)
• ADA-compliant threshold
• UL fire labels and compliance documentation
Dimensioned Diagram
• B3 (Archive Vault Door): 86" H × 76.25" W (double door)
• Option A (if funding is acquired) B2: Dimensions TBD
File details come from the government source that posted it. Updated .