Attachment 1 Salient Characteristics Worksheet .docx

DOCX document 31 KB Posted

Attached to
N059--VA Southern Nevada Health Care System (VASNHCS) Cellular Distributive Antenna System Equipment & Install
Solicitation number
36C26126Q0569
Issued by

About this file

This is a Salient Characteristics Worksheet that defines the brand-name equipment and minimal infrastructure requirements for a Cellular Distributive Antenna System (DAS) to be installed at the VA Southern Nevada Health Care System in Las Vegas under solicitation 36C26126Q0569. The worksheet specifies equipment from multiple manufacturers including CommScope, Corning, Microlab, Telect, Chatsworth, Southwire, and Solid, with detailed model numbers and quantities for each component. The system encompasses RF infrastructure (antennas, coaxial cables, and RF jumpers), fiber optic connectivity (armored cables, cassettes, and jumper cords), rack and cable management equipment (seismic racks, cable runways, and wire managers), grounding components, and the core DAS equipment (management system, optical modules, input modules, amplifier modules, and remote optical units). Notably, the worksheet indicates that a Guldmann GH3+ motor system and associated B rail room covering infrastructure are to be provided by VASNHS from existing stored inventory and include design, installation, and clinical training.

The specification provides essential physical and functional characteristics for "or equal" alternatives, allowing vendors to propose equivalent equipment meeting the stated performance standards rather than limiting responses to the exact brand-name items listed. The equipment list represents a complete neutral-host DAS solution designed to support multiple cellular bands (700 MHz, 800/850 MHz, 1900 MHz, and AWS bands) with 20-watt amplification capability and hybrid power options to ensure in-building wireless coverage throughout the facility.

View the file

Other files

File Type Posted
S06 36C26126Q0569 Amendment 1 Q and A.pdf PDF
36C26126Q0569 DAS Project VASNHCS RFQ.pdf PDF
WD 2015-5593.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

36C26126Q0569 Cellular Distributive Antenna System Salient Characteristics (Brand Name or Equal Worksheet)

Cellular Distributive Antenna System shall consist of the below equipment as a minimal infrastructure Brand Name Item: Essential/significant physical, functional, or performance characteristics.

1. CommScopeCMAX-O-43-UW-I53SISO Low PIM Omni In-building Antenna, 617–6000 MHz 4.3-10F
1. CommScopeHL4RPV-50Coaxial Cable, 1/2", Plenum Copper White
1. CommScopePTS1P-HMHM-1MRF Jumper 3ft PTS1-50-P, 4.3-10M to 4.3-10M
1. Corning012EC8-14101-A3 12Strand Ribbon Interlocking Armored Cable, Plenum, Single-mode (OS2)
1. Corning020202G5120003FLC/UPC to LC/UPC Duplex Jumper, 3ft
1. CorningCCH-04UCloset Connector Housing, 4RU, Holds 12 Cassettes/Panels
1. CorningWCH-02PWall Mount - Supports 2 Panels or Cassettes
1. CorningCCH-CS12-B3-P00RJCassette - 12 Port LC/APC Ribbon Pigtails
1. CorningCCH-CS24-B3-P00RJCassette - 24 Port LC/APC Ribbon Pigtails
1. CorningFDC-Cable-GRNDArmored Fiber Grounding Kit
1. MicrolabFXR DN-34FE3dB Tapper, 350-5850MHz 500W; Low PIM 4.3-10
1. Telect 12545-300-1 2Post - 19"x7' (43RU)Seismic Rack, UEF Base (Gray)
1. Telect 02100-113BTelectSeismic Rack Anchor Kit
1. Telect 01464-01Telect ISOMaterial 19" for FS EQ Rack
1. Chatsworth11275-712Cable Runway, UL Listed, 1.5"x 12"x 10' (Black)
1. Chatsworth111421-712Cable Runway, 12" Wall Angle Brackets
1. Chatsworth12121-712Cable Runway, Channel to Runway Mounting Plates (1 Per Rack)
1. Chatsworth642-001Cable Runway, Rubber Endcaps
1. TelectACCE-6DX-DSBLKVertical Wire Manager - 6" Wide Double Sided for Zone 4 19" Rack (Black) 1
1. Southwire57192501Ground Wire - KS24194 L4 2 AWG, Telcoflex Class B (Braided) Green
1. Southwire57150401Ground Wire - KS24194 L4 6 AWG, Telcoflex Class B (Braided) Green
1. Solid #0056DMS_1200_R2_ACDAS Management System (DMS) for ALLIANCE
1. SolidIOM_4_27004 Port optical module, use with iBIU, iODU, iOEU, supports 2500TDD Full Band
1. SolidiBIU_ACiBIU Chassis, Includes:iMCPU, iMPSU_AC
1. SolidiMCDUMain Combiner/Divider Unit
1. SolidiMDBU_8085_700LTE_FInput module, 800/850MHz, 700LTE + FirstNet
1. Solid #0061iMDBU_1900P_EInput module, 1900 MHz with extension for Band 70
1. SolidiMDBU_AWS13_B66B7Input module, 2100MHz (AWS 1+3) with extension for Band 70 and AWS-4 4,865.25
1. SolidHLPOI_8085_700LTE_FNHybrid POI, 700LTE+FN: 20W & 100mW, 800/850: 20W & 100mW
1. SolidHLPOI_1900P HybridPOI1900MHz, 2 Ports 20W, 2 Ports 100mW 3 $ 2 ,041.00 $ 6,123.00
1. SolidHLPOI_AWS13 HybridPOI AWS(1+3), 2 Ports 20W, 2 Ports 100mW 3 $ 2 ,041.00 $ 6,123.00
1. Solid #0066HROU_C_AC 20 WATTRemote Optical Unit Chassis - AC Power 19 $ 7 ,386.60 $ 1 40,345.40
1. SolidHRDU_700LTE_FN20 WATT 700MHz Amplifier Module (Includes FirstNet) 19 $ 3 ,808.35 $7 2,358.65
1. SolidHRDU_800I_850C20 WATT 800MHz (Sprint Only) and 850MHz Module 19 $ 3 ,528.85 $ 6 7,048.15
1. SolidHRDU_1900P20 WATT 1900MHz Amplifier Module
1. Solid #0070HRDU_AWS1320 WATT 2100MHz Amplifier Module (AWS1+3)
1. Solid #0071HROU_CU4_AWS1320 WATT Combiner Unit: 1 Antenna port. 700LTE or 850IC /1900 /AWS13/2500

1) Complete generic identification – x2 4x4 meter B rail room covering system installed for 770# hoist including design, installation, and clinical training. [Guldmann GH3+ motors to be provided by VASNHS from stored stock).

3) Applicable model/make/catalog number – Catalog number NA:

File details come from the government source that posted it. Updated .