Project Plans Summary

This is a project plans document prepared by IMEG Corp. for the Illinois Department of Natural Resources (IDNR) for a campground electrical panel replacement project at Delabar State Park in Henderson County, Illinois (IDNR File #1-25-034). The project scope includes demolition of existing electrical equipment and installation of a new NEMA 3R electrical panel rated at 400 amps with a 22,000 amp short circuit current rating (SCCR). The work encompasses removal of six existing fused disconnects, existing wireway, and the existing grounding system, along with disconnection and removal of the existing meter cabinet. New work includes installation of a new meter and current transformer (CT) cabinet per Ameren utility company requirements, extension of the existing secondary utility feeder from the meter cabinet to the new panel using 3#500KCM conductors in 3.5-inch rigid metal conduit, provision of new service ground at the panel, installation of new conduit sections and wiring to reconnect existing circuits from new handholes to the new panel, and construction of an equipment support structure suitable for exterior installation using metal poles and unistrut.

The electrical design must comply with the 2020 National Electrical Code (NFPA 70), 2015 International Building Code (IBC), and local amendments. The project includes provisions for minimum two handholes (11 feet long by 17 feet wide by 24 feet deep) with long-radius sweeps, gravel drainage beds, and stainless steel mesh for rodent control. The contractor is responsible for all field verification of existing conditions, coordination of utility shutdowns with Ameren, coordination of access hours with the owner, damage caused by contractor actions, and compliance with accessibility standards. The plans include electrical symbol lists, equipment schedules, and general notes addressing branch circuits, equipment feeders, controls, wet and damp location installations, and conduit installation requirements specifying use of rigid metallic conduit (RMC), electrical metallic tubing (EMT), or polyvinyl chloride (PVC) based on installation location and application.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ARGYLE LAKE STATE PARK

BIG OAK CAMPGROUND WELL REPLACEMENT

640 ARGYLE PARK ROAD, COLCHESTER, MCDONOUGH COUNTY, ILLINOIS

IDNR FILE #1-23-034

VICINITY MAP

NOT TO SCALE

IMEG CORP. HAS ADOPTED SAFETY PROCEDURES FOR ITS EMPLOYEES WHO PROVIDE

PROFESSIONAL ENGINEERING AND SURVEYING SERVICES. A COPY OF THESE PROCEDURES IS

AVAILABLE FROM THE SAFETY OFFICER. IMEG CORP. PERSONNEL ARE NOT TRAINED IN

CONTRACTOR (CONSTRUCTION) SAFETY AND COMPLIANCE PROCEDURES. THE METHODS AND

MEANS TO COMPLY WITH CONSTRUCTION SITE SAFETY ARE THE SOLE RESPONSIBILITY OF THE

CONTRACTOR.

PREPARED BY

UTILITY NOTE

THE LOCATIONS OF THOSE BURIED AND ABOVE GROUND UTILITIES SHOWN ARE APPROXIMATE,

THEY ARE SHOWN FOR CONTRACTOR INFORMATIONAL USE ONLY, AND ARE NOT TO BE

REFERENCED FOR CONSTRUCTION PURPOSES. THE IMPLIED PRESENCE OR ABSENCE OF

UTILITIES IS NOT TO BE CONSTRUED BY THE OWNER, ENGINEER, CONTRACTOR, OR

SUBCONTRACTORS TO BE AN ACCURATE AND COMPLETE REPRESENTATION OF UTILITIES THAT

MAY OR MAY NOT EXIST ON THE CONSTRUCTION SITE. BURIED AND ABOVE GROUND UTILITY

LOCATION, IDENTIFICATION, AND MARKING ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.

REROUTING, DISCONNECTION, PROTECTION, ETC. OF ANY UTILITY MUST BE COORDINATED

BETWEEN THE CONTRACTOR, UTILITY COMPANY AND OWNER. SITE SAFETY, INCLUDING THE

AVOIDANCE OF HAZARDS ASSOCIATED WITH BURIED AND ABOVEGROUND UTILITIES, REMAINS

THE SOLE RESPONSIBILITY OF THE CONTRACTOR.

CONTACTS

ILLINOIS DEPARTMENT OF NATURAL RESOURCES

OFFICE OF REALITY AND CAPITAL PLANNING

Know what's below.

before you dig.Call

R

PROJECT

LOCATION

G-1 COVER SHEET

G-2 GENERAL NOTES, SUMMARY OF QUANTITIES & DETAILS

C-1 SITE PLAN

C-2 NEW WELL DETAILS

C-3 WELL HOUSE DETAILS

E-1 ELECTRICAL PLAN & DETAILS

INDEX OF SHEETS

1138 COLUMBUS ST.

OTTAWA, IL 61350

G :\2

9\

.4 6\

D es ig n\

C iv il\ C

3D \P lo t\C

O

VE

R .d w g

REGIONAL MAPREGIONAL MAP

HENNEPIN CANAL STATE PARK

ELECTRICAL UPGRADES FOR FISHERIES BUILDING AND WELL

#1-23-035

623 26TH AVENUE

ROCK ISLAND, ILLINOIS 61201

MCDONOUGH

SON

G000

E000

E001

E100

E500

COVER SHEET

ELECTRICAL COVERSHEET

ELECTRICAL SITE PLAN

ELECTRICAL FLOOR PLAN

ELECTRICAL SCHEDULES

CONTACTS

ILLINOIS DEPARTMENT OF NATURAL RESOURCES

OFFICE OF REALITY AND CAPITAL PLANNING

G-1 COVER SHEET

G-2 GENERAL NOTES, SUMMARY OF QUANTITIES & DETAILS

C-1 SITE PLAN

C-2 NEW WELL DETAILS

C-3 WELL HOUSE DETAILS

E-1 ELECTRICAL PLAN & DETAILS

INDEX OF SHEETS

G000

E000

E001

E100

E500

COVER SHEET

ELECTRICAL COVERSHEET

ELECTRICAL SITE PLAN

ELECTRICAL FLOOR PLAN

ELECTRICAL SCHEDULES

LA SALLE

LA SALLE

HENNEPIN CANAL

STATE PARK

STARVED ROCK

STATE PARK

OGLESBY, LASALLE COUNTY, ILLINOIS

STARVED ROCK STATE PARK

CONSTRUCT EV CHARGING STATIONS

IDNR FILE #1-24-010

G000 COVER SHEET

E000 ELECTRICAL COVERSHEET

E001 SITE - ELECTRICAL DEMOLITION

E002 SITE - ELECTRICAL

DELABAR STATE PARK

CAMPGROUND ELECTRICAL PANEL REPLACEMENT

HENDERSON COUNTY, ILLINOIS

1-25-034

DELABAR STATE

PARK

APPLICABLE CODES

VIEW NAME

VIEW KEY

ABBREVIATION KEY

ABBR: DESCRIPTION:

ELECTRICAL GENERAL NOTES:

1.

ELECTRICAL INSTALLATION NOTES:

ELECTRICAL RENOVATION NOTES:

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

MECHANICAL GENERAL NOTES:

MECHANICAL RENOVATION NOTES:

MECHANICAL AND ELECTRICAL SHEET INDEX

N o

D

E S

C R

I P

T I O

N D

A T

E

COPYRIGHT

ALL RIGHTS RESERVED

C

ME000.dwg

R E

V I S

I O

N S

File Name:

Date:

Drawn By:

Checked By:

P H

F A

X w w w i m e g c o r p c o m

T

H

A

V E

N U

E

R O

C K

I S

L A

N D

I L

I l l i n o i s

D e s i g n

F i r m

R e g i s t r a t i o n

P U

M P

T A

T I O

N

E

L E

C T

R I C

A L

C

O N

T R

O L

U

G

R A

D E

B A

N N

E

A R

H

A

R

K

19000789.03

06.22.2020

MATSNY

SEJCHI

ME000

M E

C H

A N

I C

N D

E

C T

R I C

A L

C O

V E

R

S

H E

E T

ELECTRICAL ABBREVIATION KEY

AFF ABOVE FINISHED FLOOR

ABBR: DESCRIPTION:

C CONDUIT

GFI GROUND FAULT INTERRUPTER

1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR

ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON

THIS PAGE FOR ADDITIONAL INFORMATION.

2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE

WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR

BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH

PHASE.

3. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE

WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE

IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND

FINISH.

4. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR

COLOR/LABEL REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.

ELECTRICAL INSTALLATION NOTES:

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD

SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND

REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING EQUIPMENT AND CONDUIT ARE SHOWN. VERIFY EXISTING CONDITIONS

AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CONDUITS BEFORE FABRICATION. RISES

AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND

SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHER UTILITIES ARE

REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.

5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF

ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.

CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.

6. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW

EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER

ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES

NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO

ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

ELECTRICAL RENOVATION NOTES:

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

DETAIL REFERRED TO BY SECTION CUT

SHEET DETAIL IS LOCATED ON

NAME

VIEW NAME

1/8" = 1'-0"

M101

SIMSIM

INDICATES SIMILAR DETAIL REFERENCED

IN MULTIPLE LOCATIONS

LEVEL NAME

10'-0" HEIGHT ABOVE

PROJECT 0'-0"

1 INDICATES NOTE USED TO DESCRIBE

ADDITIONAL INFORMATION ABOUT

WORK REQUIRED, SPECIFIC TO THE

SHEET AND/OR DETAIL

N

O R HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

LINE TYPE AND TAG KEY:

NEW WORK BY THIS CONTRACTOR (WIDE LINE)

NEW

EXISTING TO BE REMOVED (SHORT DASHED PATTERN)

NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)

EXISTING

EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)

EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

HALFTONING DOES NOT MODIFY SCOPE.

'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING

TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL

INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST

INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL

T101

CIVIL CONTRACTORC.C.

PLUMBING CONTRACTORP.C.

GENERAL CONTRACTORG.C.

ELECTRICAL CONTRACTORE.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

CONTACT PERSONS:

PROJECT MANAGER

MECHANICAL

ELECTRICAL

MATT SNYDER

PETE COURTNEY

ADAM BROCKMAN

DESCRIPTION: PERSON:

BUILDING CODE: IBC 2015 EDITION

PLUMBING CODE: UPC 2021 EDITION

MECHANICAL CODE: IMC 2021 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION

LOCAL BUILDING CODE: CURRENT EDITION

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.

ELECTRICAL GENERAL NOTES:

DEVICE

A = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

DEVICE KEY:

1. COORDINATE HOURS OF ACCESS WITH OWNER.

2. EXISTING EMERGENCY LIGHTING AND EXIT SIGNAGE SHALL REMAIN.

3. EXPOSED 3/4" CONDUIT TO NEW OR EXISTING FIXTURES OR DEVICES IS ACCEPTABLE AS

LONG AS IT IS INSTALLED IN A NEAT AND ORDERLY METHOD AND MEETS ADOPTED CODES.

COORDINATE NEW RUNS WITH OWNER PRIOR TO INSTALLATIONS.

BRANCH CIRCUITS: LIGHTING, RECEPTACLES,

CONTROLS, ETC.

MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,

AIR HANDLING UNITS, ETC.

FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.

(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)

CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)

WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,

INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)

FINISHED SPACES / CONCEALED

CONDUIT INSTALLATION SCHEDULE

THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF

APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF RMC

CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE. REFER TO

CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL INFORMATION.

INSTALLATION TYPE RMC EMT PVC

X

X

X

X

X

X

INTERIOR LOCATIONS: CONCEALED

INTERIOR LOCATIONS: EXPOSED

WITHIN 5’ FROM THE PERIMETER OF THE BUILDING

WHEN PASSING THROUGH THE PERIMETER OF THE

BUILDING FOUNDATION:

UNDERGROUND SITE CONDUITS:

INTERIOR LOCATIONS: EXISTING WALLS AND EXPOSED

INSTALLATION (FINISHED SPACES)

WITHIN 5’ FROM THE PERIMETER OF THE BUILDING

UNDERGROUND / SLABS ON GRADE

(IN OR UNDER SLABS ON GRADE)

5' OR GREATER FROM THE PERIMETER OF A BUILDING

FOUNDATION

WITHIN 5' FROM THE PERIMETER OF A BUILDING

FOUNDATION

HAZARDOUS (CLASSIFIED LOCATIONS AS DEFIED BY THE

NATIONAL ELECTRICAL CODE:

COMPLETE WITH SCREWED FITTINGS AND CONDUIT SEALS

X

X

X

X

X

X

XX

X

JB 26 05 33 JUNCTION BOX

J

J

ECONN 26 05 33 ELECTRICAL CONNECTION

E

E

PANEL '###' EXISTING PANELBOARD - SURFACE MOUNT

ELECTRICAL SYMBOL LIST

SYMBOL: TAG: SPEC

SECTION:

DESCRIPTION:

MX-# 26 24 19 MANUAL SWITCH

ELECTRICAL SHEET INDEX

E000 ELECTRICAL COVERSHEET

E001 SITE - ELECTRICAL

E600 ELECTRICAL SCHEDULES

GRAND TOTAL: 3

MATT SNYDER

BBR: DESCRIPTION:

ELECTRICAL ADAM BROCKMANMATT SNYDER

REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V

REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V

REC-DUP-WP 26 27 26 DUPLEX GFI WEATHERPROOF RECEPTACLE 125VW

REC-QUAD 26 27 26 QUAD RECEPTACLE, 125V

ELECTRICAL SYMBOL LIST

SYMBOL: TAG: SPEC

SECTION:

DESCRIPTION:

REC-TAMP 26 27 26 DUPLEX RECEPTACLE, TAMPER RESISTANT 125V

MECHANICAL RENOVATION NOTES:

BRANCH CIRCUITS: LIGHTING, RECEPTACLES,

CONTROLS, ETC.

MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,

AIR HANDLING UNITS, ETC.

FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.

(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)

CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)

WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,

INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)

FINISHED SPACES / CONCEALED

CONDUIT INSTALLATION SCHEDULE

THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF

APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF RMC

CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE. REFER TO

CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL INFORMATION.

INSTALLATION TYPE RMC EMT PVC

X

X

X

X

X

X

INTERIOR LOCATIONS: CONCEALED

INTERIOR LOCATIONS: EXPOSED

WITHIN 5’ FROM THE PERIMETER OF THE BUILDING

WHEN PASSING THROUGH THE PERIMETER OF THE

BUILDING FOUNDATION:

UNDERGROUND SITE CONDUITS:

INTERIOR LOCATIONS: EXISTING WALLS AND EXPOSED

INSTALLATION (FINISHED SPACES)

WITHIN 5’ FROM THE PERIMETER OF THE BUILDING

UNDERGROUND / SLABS ON GRADE

(IN OR UNDER SLABS ON GRADE)

5' OR GREATER FROM THE PERIMETER OF A BUILDING

FOUNDATION

WITHIN 5' FROM THE PERIMETER OF A BUILDING

FOUNDATION

HAZARDOUS (CLASSIFIED LOCATIONS AS DEFIED BY THE

NATIONAL ELECTRICAL CODE:

COMPLETE WITH SCREWED FITTINGS AND CONDUIT SEALS

X

X

X

X

X

X

XX

X

26 24 16

SW-1P

SW-3W

26 09 33

26 09 33

SWITCH - SINGLE POLE

SWITCH - THREE WAY

RANCH CI

STALLAT

ITS: LIGHTING, RREC-DUP-GFI

X

DUPLEX GFI RECEPTACLE, 125V

REC-SIM-630R RECEPTACLE, 6-30R, 250V

EPTACLES, 26 27 26

EPTACLES, 26 27 26

MECHANICAL AND ELECTRICAL SHEET INDEX

1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR

ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON

THIS PAGE FOR ADDITIONAL INFORMATION.

2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE

WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR

BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH

PHASE.

3. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE

WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE

IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND

FINISH.

4. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR

COLOR/LABEL REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.

ELECTRICAL INSTALLATION NOTES:

MECHANICAL RENOVATION NOTES:

FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.

(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)

CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)

WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,

INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)

FINISHED SPACES / CONCEALED

X

X

X

X

INTERIOR LOCATIONS: CONCEALED

INTERIOR LOCATIONS: EXPOSED

WITHIN 5’ FROM THE PERIMETER OF THE BUILDING

WHEN PASSING THROUGH THE PERIMETER OF THE

BUILDING FOUNDATION:

UNDERGROUND SITE CONDUITS:

INTERIOR LOCATIONS: EXISTING WALLS AND EXPOSED

INSTALLATION (FINISHED SPACES)

WITHIN 5’ FROM THE PERIMETER OF THE BUILDING

UNDERGROUND / SLABS ON GRADE

(IN OR UNDER SLABS ON GRADE)

5' OR GREATER FROM THE PERIMETER OF A BUILDING

FOUNDATION

WITHIN 5' FROM THE PERIMETER OF A BUILDING

FOUNDATION

HAZARDOUS (CLASSIFIED LOCATIONS AS DEFIED BY THE

NATIONAL ELECTRICAL CODE:

COMPLETE WITH SCREWED FITTINGS AND CONDUIT SEALS

X

X

X

X

X

X

XX

X

MECHANICAL RENOVATION NOTES:

BRANCH CIRCUITS: LIGHTING, RECEPTACLES,

CONTROLS, ETC.

MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,

AIR HANDLING UNITS, ETC.

FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.

(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)

CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)

WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,

INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)

FINISHED SPACES / CONCEALED

CONDUIT INSTALLATION SCHEDULE

THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF

APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF RMC

CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE. REFER TO

CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL INFORMATION.

INSTALLATION TYPE RMC EMT PVC

X

X

X

X

X

X

INTERIOR LOCATIONS: CONCEALED

INTERIOR LOCATIONS: EXPOSED

WITHIN 5’ FROM THE PERIMETER OF THE BUILDING

WHEN PASSING THROUGH THE PERIMETER OF THE

BUILDING FOUNDATION:

UNDERGROUND SITE CONDUITS:

INTERIOR LOCATIONS: EXISTING WALLS AND EXPOSED

INSTALLATION (FINISHED SPACES)

WITHIN 5’ FROM THE PERIMETER OF THE BUILDING

UNDERGROUND / SLABS ON GRADE

(IN OR UNDER SLABS ON GRADE)

5' OR GREATER FROM THE PERIMETER OF A BUILDING

FOUNDATION

WITHIN 5' FROM THE PERIMETER OF A BUILDING

FOUNDATION

HAZARDOUS (CLASSIFIED LOCATIONS AS DEFIED BY THE

NATIONAL ELECTRICAL CODE:

COMPLETE WITH SCREWED FITTINGS AND CONDUIT SEALS

X

X

X

X

X

X

XX

X

23006751.76

ME000

MATSNY

06.30.2025

P H

F A

X w w w i m e g c o r p c o m

T

H

A

V E

N U

E

R O

L A

N D

I L

I l l i n o i s

D e s i g n

F i g i s t r a t i o n

E000

CA

M

PG

RO

U N

D

EL

EC

TR

IC

AL

P

AN

EL

R

EP

LA

CE

M

EN

T

DE

LA

BA

R

ST

AT

E

PA

RK

EL

EC

TR

IC

AL

C

O

VE

RS

HE

ET

EMT

RMC

PVC

ELECTRICAL METALLIC TUBING

RIGID METALLIC CONDUIT

POLYVINYL CHLORIDE CONDUIT

GAUSHA

PANEL NAME: A

TYPE: BOLT-ON MAIN: 400A MCB

MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 240/120

FED FROM: EXISTING UTILITY TRANSFORMER GROUND BUS PHASE: 1

K SCCR: 22,000 WIRE: 3 K

E NOTES: NEMA 3R, SERVICE ENTRANCE RATED E

Y CKT WIRE LOAD BREAKER BREAKER LOAD WIRE CKT Y

* NO. LOAD DESCRIPTION SIZE KVA AMP P AMP P KVA SIZE LOAD DESCRIPTION NO. *

*W 1 EXISTING LOAD (LIGHTING) 10 -- 30 2 100 2 -- 3 EXISTING LOAD (RV SITES) 2 *W

3 ------ -- -- -- -- -- -- -- -- ------ 4

*W 5 EXISTING LOAD (RV SITES) 3 -- 100 2 100 2 -- 3 EXISTING LOAD (RV SITES) 6 *W

7 ------ -- -- -- -- -- -- -- -- ------ 8

*W 9 EXISTING LOAD (RV SITES) 3 -- 100 2 100 2 -- 3 EXISTING LOAD (RV SITES) 10 *W

11 ------ -- -- -- -- -- -- -- -- ------ 12

13 SPACE SPACE 14

15 SPACE SPACE 16

17 SPACE SPACE 18

19 SPACE SPACE 20

21 SPACE SPACE 22

23 SPACE SPACE 24

25 SPACE SPACE 26

27 SPACE SPACE 28

29 SPACE SPACE 30

31 SPACE SPACE 32

33 SPACE SPACE 34

35 SPACE SPACE 36

37 SPACE SPACE 38

39 SPACE SPACE 40

41 SPACE SPACE 42

43 SPACE SPACE 44

45 SPACE SPACE 46

47 SPACE SPACE 48

49 SPACE SPACE 50

51 SPACE SPACE 52

53 SPACE SPACE 54

KEY: *W=WIRE SIZE NOTED IS THE MINIMUM, HOWEVER MATCH EXISTING WHEN EXTENDING AND UPSIZE IF REQUIRED

PUMP HOUSE

GENERAL NOTES

KEYNOTES

N o

D

E S

C R

I P

T I O

N D

A T

E

COPYRIGHT

ALL RIGHTS RESERVED

C

ME100.dwg

R E

V I S

I O

N S

File Name:

Date:

Drawn By:

Checked By:

P H

F A

X w w w i m e g c o r p c o m

T

H

A

V E

N U

E

R O

L A

N D

I L

I l l i n o i s

D e s i g n

F i g i s t r a t i o n

P U

A

T I O

N

E

L E

C T

R I C

A L

C

O N

T R

O

G

R A

D E

B A

N N

R

A

R

K

19000789.03

06.22.2020

FIRST FLOOR PLAN - MECHANICAL AND ELECTRICAL DEMOLITION

SCALE: 1/4"=1'-0"

R

T

H

N

O

MATSNY

SEJCHI

ME100

F I R

F

O

O

A

N

M

E C

H A

N I C

A L

A N

D

E

L E

C T

R I C

M

O L

I T

I O

N

P H

F A

X w w w i m e g c o r p c o m

T

H

A

V E

N U

E

R O

L A

N D

I L

I l l i n o i s

D e s i g n

F i g i s t r a t i o n

N O R

HT

3/32" = 1'-0"

SITE - ELECTRICAL

1 1" = 30'-0"

N O

R H

T

N

HOUSE

PUMP HOUSE

FIRST FLOOR PLAN - MECHANICAL AND ELECTRICAL DEMOLITION

SCALE: 1/4"=1'-0"

R

T

H

N

O

N O R

HT

3/32" = 1'-0"

SITE - ELECTRICAL

1 1" = 30'-0"

N O

R H

T

N

MATSNY

ME000E001

SI

TE

EL

EC

TR

IC

AL

D

EM

O

LI

TI

O

N

23006751.76

06.30.2025

CA

M

PG

RO

U N

D

EL

EC

TR

IC

AL

P

AN

EL

R

EP

LA

CE

M

EN

T

DE

LA

BA

R

ST

AT

E

PA

RK

N O R

HT

3/32" = 1'-0"

SITE - ELECTRICAL

1 1" = 30'-0"

N O

R H

T

N

NH T

N H

DEMOLITIONN

50'-0"

N O R

HT

3/32" = 1'-0"

SITE - ELECTRICAL

1 1" = 30'-0"

N O

R H

T

N

NO SCALE3 ELECTRICAL EQUIPMENT BOARD DEMOLITION

DEMOLISH EXISTING FUSED

DISCONNECT, TYP. OF 6

DEMOLISH EXISTING WIREWAY

DEMOLISH EXISTING GROUNDING

SYSTEM

DISCONNECT EXISTING

UNDERGROUND CONDUIT AND SAVE

FOR RECONNECTION TO NEW

ELECTRICAL PANEL. CUT BACK TO

GRADE LEVEL AND TERMINATE INTO

NEW HANDHOLES. TYP. OF 6.

HANDHOLES TO BE MINIMUM

11Lx17Wx24D. PROVIDE AT LEAST

TWO HANDHOLES, OR MORE AS

REQUIRED BASED ON CONDUIT

ROUTING OR FIELD CONDITIONS.

REFER TO 3/E002 FOR DETAIL.

DEMOLISH EXISTING WOOD

MOUNTING BOARD AND

SUPPORTS

DISCONNECT AND REMOVE EXISTING

METER CABINET. SAVE EXISTING

UNDERGROUND FEEDER TO BE

REUSED IN SAME LOCATION.

N O R

HT

3/32" = 1'-0"

SITE - ELECTRICAL

1 1" = 30'-0"

N O

R H

T

N

NO SCALE2 EXISTING ELECTRICAL EQUIPMENT BOARD

NOTES:

1. DETAIL FROM EXISTING DRAWINGS PROVIDED FOR REFERENCE.

REFER TO 3/E001 FOR ELECTRICAL

DEMOLITION SCOPE OF WORK AT

EXISTING DISTRIBUTION CENTER

GAUSHA

PUMP HOUSE

GENERAL NOTES

KEYNOTES

N o

D

E S

C R

I P

T I O

N D

A T

E

COPYRIGHT

ALL RIGHTS RESERVED

C

ME100.dwg

R E

V I S

I O

N S

File Name:

Date:

Drawn By:

Checked By:

P H

F A

X w w w i m e g c o r p c o m

T

H

A

V E

N U

E

R O

L A

N D

I L

I l l i n o i s

D e s i g n

F i g i s t r a t i o n

P U

A

T I O

N

E

L E

C T

R I C

A L

C

O N

T R

O

G

R A

D E

B A

N N

R

A

R

K

19000789.03

06.22.2020

FIRST FLOOR PLAN - MECHANICAL AND ELECTRICAL DEMOLITION

SCALE: 1/4"=1'-0"

R

T

H

N

O

MATSNY

SEJCHI

ME100

F I R

F

O

O

A

N

M

E C

H A

N I C

A L

A N

D

E

L E

C T

R I C

M

O L

I T

I O

N

P H

F A

X w w w i m e g c o r p c o m

T

H

A

V E

N U

E

R O

L A

N D

I L

I l l i n o i s

D e s i g n

F i g i s t r a t i o n

N O R

HT

3/32" = 1'-0"

SITE - ELECTRICAL

1 1" = 30'-0"

N O

R H

T

N

HOUSE

PUMP HOUSE

FIRST FLOOR PLAN - MECHANICAL AND ELECTRICAL DEMOLITION

SCALE: 1/4"=1'-0"

R

T

H

N

O

N O R

HT

3/32" = 1'-0"

SITE - ELECTRICAL

1 1" = 30'-0"

N O

R H

T

N

MATSNY

ME000E002

SI

TE

EL

EC

TR

IC

AL

23006751.76

06.30.2025

CA

M

PG

RO

U N

D

EL

EC

TR

IC

AL

P

AN

EL

R

EP

LA

CE

M

EN

T

DE

LA

BA

R

ST

AT

E

PA

RK

N O R

HT

3/32" = 1'-0"

SITE - ELECTRICAL

1 1" = 30'-0"

N O

R H

T

N

NH T

N H

NEW WORKN

50'-0"

N O R

HT

3/32" = 1'-0"

SITE - ELECTRICAL

1 1" = 30'-0"

N O

R H

T

N

NO SCALE2 ELECTRICAL EQUIPMENT STRUCTURE - NEW WORK

REFER TO 2/E002 FOR ELECTRICAL

SCOPE OF WORK AT RECONFIGURED

DISTRIBUTION CENTER

NO SCALE

PROVIDE NEW METER AND C.T.

CABINET PER AMEREN

REQUIREMENTS. EXTEND AND

CONNECT EXISTING

SECONDARY UTILITY FEEDER.

COORDINATE SHUTDOWNS

WITH UTILITY COMPANY.

NEW NEMA 3R ELECTRICAL PANEL 'A'.

FEED FROM METER CABINET WITH

3#500KCM IN 3 1/2" RIGID METAL

CONDUIT. PROVIDE NEW SERVICE

GROUND AT PANEL PER DETAIL 4/E002.

NEW CONDUIT SECTIONS AND

WIRING TO EXTEND FEEDERS FROM

NEW HANDHOLES UP TO NEW PANEL

AS REQUIRED TO RECONNECT

EXISTING CIRCUITS, REFER TO E000

FOR PANEL SCHEDULE

PROVIDE EQUIPMENT SUPPORT

STRUCTURE, SIZED AS REQUIRED

FOR THE METER, C.T. CABINET, AND

ELECTRICAL PANEL. STRUCTURE TO

BE WIDE ENOUGH TO ACCOMMODATE

FUTURE PANEL EXPANSION SPACE

SHOWN. STRUCTURE TO BE METAL

POLES AND UNISTRUT SUITABLE FOR

EXTERIOR INSTALLATION.

FINISHED GRADE LINE

STAINLESS STEEL HEX

HEAD BOLT W/WASHER

PULL SLOT

SKID RESISTANT SURFACE

EXTENSIONS AS REQUIRED

BY CONDUIT DEPTH

KNOCKOUTS - (8)

SLOPE GRADE AWAY

FROM COVER 1" IN 3'

MOUSEHOLES - (2)

CONDUITS LARGER THAN

MOUSEHOLES CAN

ACCOMMODATE, SHALL ENTER

BOTTOM OF HANDHOLE WITH

LONG RADIUS SWEEPS

GRAVEL DRAINAGE BED

MINIMUM 12" DEPTH EXTENDING

6" BEYOND ALL EDGES. MINIMUM

SIZE GRAVEL 1". (CA5 OR CA7)

8" E

XTENSIO

N

LOGO

LENGTH

W

IDTH

DEPTH

STAINLESS STEEL 304

1/2"X1/2"X.063 WOVEN METAL

MESH ABOVE GRAVEL FOR

RODENT CONTROL

NOTES:

1. ALL DIMENSIONS ARE NOMINAL INSIDE CLEARANCES.

2. ANY SPLICES OR DEVICES IN HANDHOLE SHALL BE SUBMERGIBLE.

NO SCALE

EXTERIOR HANDHOLE DETAIL

PROVIDE SPACE FOR FUTURE

PANEL EXPANSION

GROUND

#2 GROUNDING ELECTRODE

CONDUCTOR PER NEC 250.66

REMOVABLE LINK

#4 GROUNDING

ELECTRODE CONDUCTOR,

NEC 250.66

CONCRETE-ENCASED

GROUNDING ELECTRODE

(UFER). NEC 250.52

ELECTRICAL GROUND

FIELD. 3/4" DIA. x 10'-0"

COPPER GROUND ROD.

TOP OF ROD SHALL BE 12"

BELOW GRADE. (TYP)

20'-0"

NEUTRAL

SERVICE ENTRANCE

EQUIPMENT

NOTES.

1. 1. REFER TO SPECIFICATION SECTION 26 05 26 GROUNDING

AND BONDING

NO SCALE3

SERVICE ENTRANCE

GROUNDING ELECTRODE

SYSTEM DETAIL

#1/0 GROUNDING ELECTRODE

CONDUCTOR PER NEC 250.66

GAUSHA

.66GROUNDING ELECTRODE GROUNDING ELECTRODE