Attachment 1 - Project Plans~11.pdf
PDF 3 MB Posted
- Solicitation number
- 27-422DNR-REALT-B-53706
- Issued by
- Illinois
About this file
Project Plans Summary
This is a project plans document prepared by IMEG Corp. for the Illinois Department of Natural Resources (IDNR) for a campground electrical panel replacement project at Delabar State Park in Henderson County, Illinois (IDNR File #1-25-034). The project scope includes demolition of existing electrical equipment and installation of a new NEMA 3R electrical panel rated at 400 amps with a 22,000 amp short circuit current rating (SCCR). The work encompasses removal of six existing fused disconnects, existing wireway, and the existing grounding system, along with disconnection and removal of the existing meter cabinet. New work includes installation of a new meter and current transformer (CT) cabinet per Ameren utility company requirements, extension of the existing secondary utility feeder from the meter cabinet to the new panel using 3#500KCM conductors in 3.5-inch rigid metal conduit, provision of new service ground at the panel, installation of new conduit sections and wiring to reconnect existing circuits from new handholes to the new panel, and construction of an equipment support structure suitable for exterior installation using metal poles and unistrut.
The electrical design must comply with the 2020 National Electrical Code (NFPA 70), 2015 International Building Code (IBC), and local amendments. The project includes provisions for minimum two handholes (11 feet long by 17 feet wide by 24 feet deep) with long-radius sweeps, gravel drainage beds, and stainless steel mesh for rodent control. The contractor is responsible for all field verification of existing conditions, coordination of utility shutdowns with Ameren, coordination of access hours with the owner, damage caused by contractor actions, and compliance with accessibility standards. The plans include electrical symbol lists, equipment schedules, and general notes addressing branch circuits, equipment feeders, controls, wet and damp location installations, and conduit installation requirements specifying use of rigid metallic conduit (RMC), electrical metallic tubing (EMT), or polyvinyl chloride (PVC) based on installation location and application.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 2 - Project Manual~3.pdf | ||
| 0 standard terms and conditions V23.2~69.pdf | ||
| 0 standard-illinois-certifications-v-26-2~16.pdf | ||
| Attachment 3 - Ameren Meter Specifications.pdf | ||
| SCOPE DOCUMENT 5-18-2026 smalls.docx | DOCX document | |
| Attachment 4 - Contractor Schedule of Values~2.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARGYLE LAKE STATE PARK
BIG OAK CAMPGROUND WELL REPLACEMENT
640 ARGYLE PARK ROAD, COLCHESTER, MCDONOUGH COUNTY, ILLINOIS
IDNR FILE #1-23-034
VICINITY MAP
NOT TO SCALE
IMEG CORP. HAS ADOPTED SAFETY PROCEDURES FOR ITS EMPLOYEES WHO PROVIDE
PROFESSIONAL ENGINEERING AND SURVEYING SERVICES. A COPY OF THESE PROCEDURES IS
AVAILABLE FROM THE SAFETY OFFICER. IMEG CORP. PERSONNEL ARE NOT TRAINED IN
CONTRACTOR (CONSTRUCTION) SAFETY AND COMPLIANCE PROCEDURES. THE METHODS AND
MEANS TO COMPLY WITH CONSTRUCTION SITE SAFETY ARE THE SOLE RESPONSIBILITY OF THE
CONTRACTOR.
PREPARED BY
UTILITY NOTE
THE LOCATIONS OF THOSE BURIED AND ABOVE GROUND UTILITIES SHOWN ARE APPROXIMATE,
THEY ARE SHOWN FOR CONTRACTOR INFORMATIONAL USE ONLY, AND ARE NOT TO BE
REFERENCED FOR CONSTRUCTION PURPOSES. THE IMPLIED PRESENCE OR ABSENCE OF
UTILITIES IS NOT TO BE CONSTRUED BY THE OWNER, ENGINEER, CONTRACTOR, OR
SUBCONTRACTORS TO BE AN ACCURATE AND COMPLETE REPRESENTATION OF UTILITIES THAT
MAY OR MAY NOT EXIST ON THE CONSTRUCTION SITE. BURIED AND ABOVE GROUND UTILITY
LOCATION, IDENTIFICATION, AND MARKING ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
REROUTING, DISCONNECTION, PROTECTION, ETC. OF ANY UTILITY MUST BE COORDINATED
BETWEEN THE CONTRACTOR, UTILITY COMPANY AND OWNER. SITE SAFETY, INCLUDING THE
AVOIDANCE OF HAZARDS ASSOCIATED WITH BURIED AND ABOVEGROUND UTILITIES, REMAINS
THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
CONTACTS
ILLINOIS DEPARTMENT OF NATURAL RESOURCES
OFFICE OF REALITY AND CAPITAL PLANNING
Know what's below.
before you dig.Call
R
PROJECT
LOCATION
G-1 COVER SHEET
G-2 GENERAL NOTES, SUMMARY OF QUANTITIES & DETAILS
C-1 SITE PLAN
C-2 NEW WELL DETAILS
C-3 WELL HOUSE DETAILS
E-1 ELECTRICAL PLAN & DETAILS
INDEX OF SHEETS
1138 COLUMBUS ST.
OTTAWA, IL 61350
G :\2
9\
.4 6\
D es ig n\
C iv il\ C
3D \P lo t\C
O
VE
R .d w g
REGIONAL MAPREGIONAL MAP
HENNEPIN CANAL STATE PARK
ELECTRICAL UPGRADES FOR FISHERIES BUILDING AND WELL
#1-23-035
623 26TH AVENUE
ROCK ISLAND, ILLINOIS 61201
MCDONOUGH
SON
G000
E000
E001
E100
E500
COVER SHEET
ELECTRICAL COVERSHEET
ELECTRICAL SITE PLAN
ELECTRICAL FLOOR PLAN
ELECTRICAL SCHEDULES
CONTACTS
ILLINOIS DEPARTMENT OF NATURAL RESOURCES
OFFICE OF REALITY AND CAPITAL PLANNING
G-1 COVER SHEET
G-2 GENERAL NOTES, SUMMARY OF QUANTITIES & DETAILS
C-1 SITE PLAN
C-2 NEW WELL DETAILS
C-3 WELL HOUSE DETAILS
E-1 ELECTRICAL PLAN & DETAILS
INDEX OF SHEETS
G000
E000
E001
E100
E500
COVER SHEET
ELECTRICAL COVERSHEET
ELECTRICAL SITE PLAN
ELECTRICAL FLOOR PLAN
ELECTRICAL SCHEDULES
LA SALLE
LA SALLE
HENNEPIN CANAL
STATE PARK
STARVED ROCK
STATE PARK
OGLESBY, LASALLE COUNTY, ILLINOIS
STARVED ROCK STATE PARK
CONSTRUCT EV CHARGING STATIONS
IDNR FILE #1-24-010
G000 COVER SHEET
E000 ELECTRICAL COVERSHEET
E001 SITE - ELECTRICAL DEMOLITION
E002 SITE - ELECTRICAL
DELABAR STATE PARK
CAMPGROUND ELECTRICAL PANEL REPLACEMENT
HENDERSON COUNTY, ILLINOIS
1-25-034
DELABAR STATE
PARK
APPLICABLE CODES
VIEW NAME
VIEW KEY
ABBREVIATION KEY
ABBR: DESCRIPTION:
ELECTRICAL GENERAL NOTES:
1.
ELECTRICAL INSTALLATION NOTES:
ELECTRICAL RENOVATION NOTES:
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
MECHANICAL GENERAL NOTES:
MECHANICAL RENOVATION NOTES:
MECHANICAL AND ELECTRICAL SHEET INDEX
N o
D
E S
C R
I P
T I O
N D
A T
E
COPYRIGHT
ALL RIGHTS RESERVED
C
ME000.dwg
R E
V I S
I O
N S
File Name:
Date:
Drawn By:
Checked By:
P H
F A
X w w w i m e g c o r p c o m
T
H
A
V E
N U
E
R O
C K
I S
L A
N D
I L
I l l i n o i s
D e s i g n
F i r m
R e g i s t r a t i o n
P U
M P
T A
T I O
N
E
L E
C T
R I C
A L
C
O N
T R
O L
U
G
R A
D E
B A
N N
E
A R
H
A
R
K
19000789.03
06.22.2020
MATSNY
SEJCHI
ME000
M E
C H
A N
I C
N D
E
C T
R I C
A L
C O
V E
R
S
H E
E T
ELECTRICAL ABBREVIATION KEY
AFF ABOVE FINISHED FLOOR
ABBR: DESCRIPTION:
C CONDUIT
GFI GROUND FAULT INTERRUPTER
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON
THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH
PHASE.
3. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE
IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
4. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR
COLOR/LABEL REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.
ELECTRICAL INSTALLATION NOTES:
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT AND CONDUIT ARE SHOWN. VERIFY EXISTING CONDITIONS
AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CONDUITS BEFORE FABRICATION. RISES
AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND
SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF
ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.
CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.
6. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
CIVIL CONTRACTORC.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
CONTACT PERSONS:
PROJECT MANAGER
MECHANICAL
ELECTRICAL
MATT SNYDER
PETE COURTNEY
ADAM BROCKMAN
DESCRIPTION: PERSON:
BUILDING CODE: IBC 2015 EDITION
PLUMBING CODE: UPC 2021 EDITION
MECHANICAL CODE: IMC 2021 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
ELECTRICAL GENERAL NOTES:
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
DEVICE KEY:
1. COORDINATE HOURS OF ACCESS WITH OWNER.
2. EXISTING EMERGENCY LIGHTING AND EXIT SIGNAGE SHALL REMAIN.
3. EXPOSED 3/4" CONDUIT TO NEW OR EXISTING FIXTURES OR DEVICES IS ACCEPTABLE AS
LONG AS IT IS INSTALLED IN A NEAT AND ORDERLY METHOD AND MEETS ADOPTED CODES.
COORDINATE NEW RUNS WITH OWNER PRIOR TO INSTALLATIONS.
BRANCH CIRCUITS: LIGHTING, RECEPTACLES,
CONTROLS, ETC.
MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,
AIR HANDLING UNITS, ETC.
FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.
(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)
CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)
WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,
INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)
FINISHED SPACES / CONCEALED
CONDUIT INSTALLATION SCHEDULE
THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF
APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF RMC
CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE. REFER TO
CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL INFORMATION.
INSTALLATION TYPE RMC EMT PVC
X
X
X
X
X
X
INTERIOR LOCATIONS: CONCEALED
INTERIOR LOCATIONS: EXPOSED
WITHIN 5’ FROM THE PERIMETER OF THE BUILDING
WHEN PASSING THROUGH THE PERIMETER OF THE
BUILDING FOUNDATION:
UNDERGROUND SITE CONDUITS:
INTERIOR LOCATIONS: EXISTING WALLS AND EXPOSED
INSTALLATION (FINISHED SPACES)
WITHIN 5’ FROM THE PERIMETER OF THE BUILDING
UNDERGROUND / SLABS ON GRADE
(IN OR UNDER SLABS ON GRADE)
5' OR GREATER FROM THE PERIMETER OF A BUILDING
FOUNDATION
WITHIN 5' FROM THE PERIMETER OF A BUILDING
FOUNDATION
HAZARDOUS (CLASSIFIED LOCATIONS AS DEFIED BY THE
NATIONAL ELECTRICAL CODE:
COMPLETE WITH SCREWED FITTINGS AND CONDUIT SEALS
X
X
X
X
X
X
XX
X
JB 26 05 33 JUNCTION BOX
J
J
ECONN 26 05 33 ELECTRICAL CONNECTION
E
E
PANEL '###' EXISTING PANELBOARD - SURFACE MOUNT
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC
SECTION:
DESCRIPTION:
MX-# 26 24 19 MANUAL SWITCH
ELECTRICAL SHEET INDEX
E000 ELECTRICAL COVERSHEET
E001 SITE - ELECTRICAL
E600 ELECTRICAL SCHEDULES
GRAND TOTAL: 3
MATT SNYDER
BBR: DESCRIPTION:
ELECTRICAL ADAM BROCKMANMATT SNYDER
REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V
REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V
REC-DUP-WP 26 27 26 DUPLEX GFI WEATHERPROOF RECEPTACLE 125VW
REC-QUAD 26 27 26 QUAD RECEPTACLE, 125V
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC
SECTION:
DESCRIPTION:
REC-TAMP 26 27 26 DUPLEX RECEPTACLE, TAMPER RESISTANT 125V
MECHANICAL RENOVATION NOTES:
BRANCH CIRCUITS: LIGHTING, RECEPTACLES,
CONTROLS, ETC.
MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,
AIR HANDLING UNITS, ETC.
FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.
(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)
CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)
WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,
INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)
FINISHED SPACES / CONCEALED
CONDUIT INSTALLATION SCHEDULE
THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF
APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF RMC
CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE. REFER TO
CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL INFORMATION.
INSTALLATION TYPE RMC EMT PVC
X
X
X
X
X
X
INTERIOR LOCATIONS: CONCEALED
INTERIOR LOCATIONS: EXPOSED
WITHIN 5’ FROM THE PERIMETER OF THE BUILDING
WHEN PASSING THROUGH THE PERIMETER OF THE
BUILDING FOUNDATION:
UNDERGROUND SITE CONDUITS:
INTERIOR LOCATIONS: EXISTING WALLS AND EXPOSED
INSTALLATION (FINISHED SPACES)
WITHIN 5’ FROM THE PERIMETER OF THE BUILDING
UNDERGROUND / SLABS ON GRADE
(IN OR UNDER SLABS ON GRADE)
5' OR GREATER FROM THE PERIMETER OF A BUILDING
FOUNDATION
WITHIN 5' FROM THE PERIMETER OF A BUILDING
FOUNDATION
HAZARDOUS (CLASSIFIED LOCATIONS AS DEFIED BY THE
NATIONAL ELECTRICAL CODE:
COMPLETE WITH SCREWED FITTINGS AND CONDUIT SEALS
X
X
X
X
X
X
XX
X
26 24 16
SW-1P
SW-3W
26 09 33
26 09 33
SWITCH - SINGLE POLE
SWITCH - THREE WAY
RANCH CI
STALLAT
ITS: LIGHTING, RREC-DUP-GFI
X
DUPLEX GFI RECEPTACLE, 125V
REC-SIM-630R RECEPTACLE, 6-30R, 250V
EPTACLES, 26 27 26
EPTACLES, 26 27 26
MECHANICAL AND ELECTRICAL SHEET INDEX
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON
THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH
PHASE.
3. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE
IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
4. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR
COLOR/LABEL REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.
ELECTRICAL INSTALLATION NOTES:
MECHANICAL RENOVATION NOTES:
FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.
(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)
CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)
WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,
INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)
FINISHED SPACES / CONCEALED
X
X
X
X
INTERIOR LOCATIONS: CONCEALED
INTERIOR LOCATIONS: EXPOSED
WITHIN 5’ FROM THE PERIMETER OF THE BUILDING
WHEN PASSING THROUGH THE PERIMETER OF THE
BUILDING FOUNDATION:
UNDERGROUND SITE CONDUITS:
INTERIOR LOCATIONS: EXISTING WALLS AND EXPOSED
INSTALLATION (FINISHED SPACES)
WITHIN 5’ FROM THE PERIMETER OF THE BUILDING
UNDERGROUND / SLABS ON GRADE
(IN OR UNDER SLABS ON GRADE)
5' OR GREATER FROM THE PERIMETER OF A BUILDING
FOUNDATION
WITHIN 5' FROM THE PERIMETER OF A BUILDING
FOUNDATION
HAZARDOUS (CLASSIFIED LOCATIONS AS DEFIED BY THE
NATIONAL ELECTRICAL CODE:
COMPLETE WITH SCREWED FITTINGS AND CONDUIT SEALS
X
X
X
X
X
X
XX
X
MECHANICAL RENOVATION NOTES:
BRANCH CIRCUITS: LIGHTING, RECEPTACLES,
CONTROLS, ETC.
MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,
AIR HANDLING UNITS, ETC.
FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.
(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)
CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)
WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,
INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)
FINISHED SPACES / CONCEALED
CONDUIT INSTALLATION SCHEDULE
THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF
APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF RMC
CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE. REFER TO
CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL INFORMATION.
INSTALLATION TYPE RMC EMT PVC
X
X
X
X
X
X
INTERIOR LOCATIONS: CONCEALED
INTERIOR LOCATIONS: EXPOSED
WITHIN 5’ FROM THE PERIMETER OF THE BUILDING
WHEN PASSING THROUGH THE PERIMETER OF THE
BUILDING FOUNDATION:
UNDERGROUND SITE CONDUITS:
INTERIOR LOCATIONS: EXISTING WALLS AND EXPOSED
INSTALLATION (FINISHED SPACES)
WITHIN 5’ FROM THE PERIMETER OF THE BUILDING
UNDERGROUND / SLABS ON GRADE
(IN OR UNDER SLABS ON GRADE)
5' OR GREATER FROM THE PERIMETER OF A BUILDING
FOUNDATION
WITHIN 5' FROM THE PERIMETER OF A BUILDING
FOUNDATION
HAZARDOUS (CLASSIFIED LOCATIONS AS DEFIED BY THE
NATIONAL ELECTRICAL CODE:
COMPLETE WITH SCREWED FITTINGS AND CONDUIT SEALS
X
X
X
X
X
X
XX
X
23006751.76
ME000
MATSNY
06.30.2025
P H
F A
X w w w i m e g c o r p c o m
T
H
A
V E
N U
E
R O
L A
N D
I L
I l l i n o i s
D e s i g n
F i g i s t r a t i o n
E000
CA
M
PG
RO
U N
D
EL
EC
TR
IC
AL
P
AN
EL
R
EP
LA
CE
M
EN
T
DE
LA
BA
R
ST
AT
E
PA
RK
EL
EC
TR
IC
AL
C
O
VE
RS
HE
ET
EMT
RMC
PVC
ELECTRICAL METALLIC TUBING
RIGID METALLIC CONDUIT
POLYVINYL CHLORIDE CONDUIT
GAUSHA
PANEL NAME: A
TYPE: BOLT-ON MAIN: 400A MCB
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 240/120
FED FROM: EXISTING UTILITY TRANSFORMER GROUND BUS PHASE: 1
K SCCR: 22,000 WIRE: 3 K
E NOTES: NEMA 3R, SERVICE ENTRANCE RATED E
Y CKT WIRE LOAD BREAKER BREAKER LOAD WIRE CKT Y
* NO. LOAD DESCRIPTION SIZE KVA AMP P AMP P KVA SIZE LOAD DESCRIPTION NO. *
*W 1 EXISTING LOAD (LIGHTING) 10 -- 30 2 100 2 -- 3 EXISTING LOAD (RV SITES) 2 *W
3 ------ -- -- -- -- -- -- -- -- ------ 4
*W 5 EXISTING LOAD (RV SITES) 3 -- 100 2 100 2 -- 3 EXISTING LOAD (RV SITES) 6 *W
7 ------ -- -- -- -- -- -- -- -- ------ 8
*W 9 EXISTING LOAD (RV SITES) 3 -- 100 2 100 2 -- 3 EXISTING LOAD (RV SITES) 10 *W
11 ------ -- -- -- -- -- -- -- -- ------ 12
13 SPACE SPACE 14
15 SPACE SPACE 16
17 SPACE SPACE 18
19 SPACE SPACE 20
21 SPACE SPACE 22
23 SPACE SPACE 24
25 SPACE SPACE 26
27 SPACE SPACE 28
29 SPACE SPACE 30
31 SPACE SPACE 32
33 SPACE SPACE 34
35 SPACE SPACE 36
37 SPACE SPACE 38
39 SPACE SPACE 40
41 SPACE SPACE 42
43 SPACE SPACE 44
45 SPACE SPACE 46
47 SPACE SPACE 48
49 SPACE SPACE 50
51 SPACE SPACE 52
53 SPACE SPACE 54
KEY: *W=WIRE SIZE NOTED IS THE MINIMUM, HOWEVER MATCH EXISTING WHEN EXTENDING AND UPSIZE IF REQUIRED
PUMP HOUSE
GENERAL NOTES
KEYNOTES
N o
D
E S
C R
I P
T I O
N D
A T
E
COPYRIGHT
ALL RIGHTS RESERVED
C
ME100.dwg
R E
V I S
I O
N S
File Name:
Date:
Drawn By:
Checked By:
P H
F A
X w w w i m e g c o r p c o m
T
H
A
V E
N U
E
R O
L A
N D
I L
I l l i n o i s
D e s i g n
F i g i s t r a t i o n
P U
A
T I O
N
E
L E
C T
R I C
A L
C
O N
T R
O
G
R A
D E
B A
N N
R
A
R
K
19000789.03
06.22.2020
FIRST FLOOR PLAN - MECHANICAL AND ELECTRICAL DEMOLITION
SCALE: 1/4"=1'-0"
R
T
H
N
O
MATSNY
SEJCHI
ME100
F I R
F
O
O
A
N
M
E C
H A
N I C
A L
A N
D
E
L E
C T
R I C
M
O L
I T
I O
N
P H
F A
X w w w i m e g c o r p c o m
T
H
A
V E
N U
E
R O
L A
N D
I L
I l l i n o i s
D e s i g n
F i g i s t r a t i o n
N O R
HT
3/32" = 1'-0"
SITE - ELECTRICAL
1 1" = 30'-0"
N O
R H
T
N
HOUSE
PUMP HOUSE
FIRST FLOOR PLAN - MECHANICAL AND ELECTRICAL DEMOLITION
SCALE: 1/4"=1'-0"
R
T
H
N
O
N O R
HT
3/32" = 1'-0"
SITE - ELECTRICAL
1 1" = 30'-0"
N O
R H
T
N
MATSNY
ME000E001
SI
TE
EL
EC
TR
IC
AL
D
EM
O
LI
TI
O
N
23006751.76
06.30.2025
CA
M
PG
RO
U N
D
EL
EC
TR
IC
AL
P
AN
EL
R
EP
LA
CE
M
EN
T
DE
LA
BA
R
ST
AT
E
PA
RK
N O R
HT
3/32" = 1'-0"
SITE - ELECTRICAL
1 1" = 30'-0"
N O
R H
T
N
NH T
N H
DEMOLITIONN
50'-0"
N O R
HT
3/32" = 1'-0"
SITE - ELECTRICAL
1 1" = 30'-0"
N O
R H
T
N
NO SCALE3 ELECTRICAL EQUIPMENT BOARD DEMOLITION
DEMOLISH EXISTING FUSED
DISCONNECT, TYP. OF 6
DEMOLISH EXISTING WIREWAY
DEMOLISH EXISTING GROUNDING
SYSTEM
DISCONNECT EXISTING
UNDERGROUND CONDUIT AND SAVE
FOR RECONNECTION TO NEW
ELECTRICAL PANEL. CUT BACK TO
GRADE LEVEL AND TERMINATE INTO
NEW HANDHOLES. TYP. OF 6.
HANDHOLES TO BE MINIMUM
11Lx17Wx24D. PROVIDE AT LEAST
TWO HANDHOLES, OR MORE AS
REQUIRED BASED ON CONDUIT
ROUTING OR FIELD CONDITIONS.
REFER TO 3/E002 FOR DETAIL.
DEMOLISH EXISTING WOOD
MOUNTING BOARD AND
SUPPORTS
DISCONNECT AND REMOVE EXISTING
METER CABINET. SAVE EXISTING
UNDERGROUND FEEDER TO BE
REUSED IN SAME LOCATION.
N O R
HT
3/32" = 1'-0"
SITE - ELECTRICAL
1 1" = 30'-0"
N O
R H
T
N
NO SCALE2 EXISTING ELECTRICAL EQUIPMENT BOARD
NOTES:
1. DETAIL FROM EXISTING DRAWINGS PROVIDED FOR REFERENCE.
REFER TO 3/E001 FOR ELECTRICAL
DEMOLITION SCOPE OF WORK AT
EXISTING DISTRIBUTION CENTER
GAUSHA
PUMP HOUSE
GENERAL NOTES
KEYNOTES
N o
D
E S
C R
I P
T I O
N D
A T
E
COPYRIGHT
ALL RIGHTS RESERVED
C
ME100.dwg
R E
V I S
I O
N S
File Name:
Date:
Drawn By:
Checked By:
P H
F A
X w w w i m e g c o r p c o m
T
H
A
V E
N U
E
R O
L A
N D
I L
I l l i n o i s
D e s i g n
F i g i s t r a t i o n
P U
A
T I O
N
E
L E
C T
R I C
A L
C
O N
T R
O
G
R A
D E
B A
N N
R
A
R
K
19000789.03
06.22.2020
FIRST FLOOR PLAN - MECHANICAL AND ELECTRICAL DEMOLITION
SCALE: 1/4"=1'-0"
R
T
H
N
O
MATSNY
SEJCHI
ME100
F I R
F
O
O
A
N
M
E C
H A
N I C
A L
A N
D
E
L E
C T
R I C
M
O L
I T
I O
N
P H
F A
X w w w i m e g c o r p c o m
T
H
A
V E
N U
E
R O
L A
N D
I L
I l l i n o i s
D e s i g n
F i g i s t r a t i o n
N O R
HT
3/32" = 1'-0"
SITE - ELECTRICAL
1 1" = 30'-0"
N O
R H
T
N
HOUSE
PUMP HOUSE
FIRST FLOOR PLAN - MECHANICAL AND ELECTRICAL DEMOLITION
SCALE: 1/4"=1'-0"
R
T
H
N
O
N O R
HT
3/32" = 1'-0"
SITE - ELECTRICAL
1 1" = 30'-0"
N O
R H
T
N
MATSNY
ME000E002
SI
TE
EL
EC
TR
IC
AL
23006751.76
06.30.2025
CA
M
PG
RO
U N
D
EL
EC
TR
IC
AL
P
AN
EL
R
EP
LA
CE
M
EN
T
DE
LA
BA
R
ST
AT
E
PA
RK
N O R
HT
3/32" = 1'-0"
SITE - ELECTRICAL
1 1" = 30'-0"
N O
R H
T
N
NH T
N H
NEW WORKN
50'-0"
N O R
HT
3/32" = 1'-0"
SITE - ELECTRICAL
1 1" = 30'-0"
N O
R H
T
N
NO SCALE2 ELECTRICAL EQUIPMENT STRUCTURE - NEW WORK
REFER TO 2/E002 FOR ELECTRICAL
SCOPE OF WORK AT RECONFIGURED
DISTRIBUTION CENTER
NO SCALE
PROVIDE NEW METER AND C.T.
CABINET PER AMEREN
REQUIREMENTS. EXTEND AND
CONNECT EXISTING
SECONDARY UTILITY FEEDER.
COORDINATE SHUTDOWNS
WITH UTILITY COMPANY.
NEW NEMA 3R ELECTRICAL PANEL 'A'.
FEED FROM METER CABINET WITH
3#500KCM IN 3 1/2" RIGID METAL
CONDUIT. PROVIDE NEW SERVICE
GROUND AT PANEL PER DETAIL 4/E002.
NEW CONDUIT SECTIONS AND
WIRING TO EXTEND FEEDERS FROM
NEW HANDHOLES UP TO NEW PANEL
AS REQUIRED TO RECONNECT
EXISTING CIRCUITS, REFER TO E000
FOR PANEL SCHEDULE
PROVIDE EQUIPMENT SUPPORT
STRUCTURE, SIZED AS REQUIRED
FOR THE METER, C.T. CABINET, AND
ELECTRICAL PANEL. STRUCTURE TO
BE WIDE ENOUGH TO ACCOMMODATE
FUTURE PANEL EXPANSION SPACE
SHOWN. STRUCTURE TO BE METAL
POLES AND UNISTRUT SUITABLE FOR
EXTERIOR INSTALLATION.
FINISHED GRADE LINE
STAINLESS STEEL HEX
HEAD BOLT W/WASHER
PULL SLOT
SKID RESISTANT SURFACE
EXTENSIONS AS REQUIRED
BY CONDUIT DEPTH
KNOCKOUTS - (8)
SLOPE GRADE AWAY
FROM COVER 1" IN 3'
MOUSEHOLES - (2)
CONDUITS LARGER THAN
MOUSEHOLES CAN
ACCOMMODATE, SHALL ENTER
BOTTOM OF HANDHOLE WITH
LONG RADIUS SWEEPS
GRAVEL DRAINAGE BED
MINIMUM 12" DEPTH EXTENDING
6" BEYOND ALL EDGES. MINIMUM
SIZE GRAVEL 1". (CA5 OR CA7)
8" E
XTENSIO
N
LOGO
LENGTH
W
IDTH
DEPTH
STAINLESS STEEL 304
1/2"X1/2"X.063 WOVEN METAL
MESH ABOVE GRAVEL FOR
RODENT CONTROL
NOTES:
1. ALL DIMENSIONS ARE NOMINAL INSIDE CLEARANCES.
2. ANY SPLICES OR DEVICES IN HANDHOLE SHALL BE SUBMERGIBLE.
NO SCALE
EXTERIOR HANDHOLE DETAIL
PROVIDE SPACE FOR FUTURE
PANEL EXPANSION
GROUND
#2 GROUNDING ELECTRODE
CONDUCTOR PER NEC 250.66
REMOVABLE LINK
#4 GROUNDING
ELECTRODE CONDUCTOR,
NEC 250.66
CONCRETE-ENCASED
GROUNDING ELECTRODE
(UFER). NEC 250.52
ELECTRICAL GROUND
FIELD. 3/4" DIA. x 10'-0"
COPPER GROUND ROD.
TOP OF ROD SHALL BE 12"
BELOW GRADE. (TYP)
20'-0"
NEUTRAL
SERVICE ENTRANCE
EQUIPMENT
NOTES.
1. 1. REFER TO SPECIFICATION SECTION 26 05 26 GROUNDING
AND BONDING
NO SCALE3
SERVICE ENTRANCE
GROUNDING ELECTRODE
SYSTEM DETAIL
#1/0 GROUNDING ELECTRODE
CONDUCTOR PER NEC 250.66
GAUSHA
.66GROUNDING ELECTRODE GROUNDING ELECTRODE
File details come from the government source that posted it. Updated .