Attachment 1 - Minimum Saliant Characteristics.pdf
PDF 69 KB Posted
- Attached to
- 70 Ton Chiller Rental B3206
- Solicitation number
- FA303025Q0028
About this file
This document is a Minimum Salient Characteristics specification for a temporary 70 Ton, Air-Cooled Chiller Unit rental. The rental requires a unit with specific technical requirements, including:
- Power cables and supply/return hoses up to 100' long
- Ability to connect to 6" - 8 bolt flanges
- Power supply of 480V / 3PH, 225A breaker
- Compatibility with an external water pump on-site
The chiller unit is part of a solicitation (FA303025Q0028) for Goodfellow Air Force Base in Texas, which is a 100% Small Business Set-Aside with a performance period from 18 April 2025 to 17 October 2025. Quotes are due by 14 April 2025 at 1:00 PM CST and must be submitted via email to specified Air Force personnel, with requirements including a price quotation, technical documentation, product data sheet, and capabilities statement.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Minimum Saliant Characteristics
Rental: one temporary 70 Ton, Air-Cooled, Chiller Unit
- Rental unit will be delivered, connected to be fully operational, disconnected after use, and removed by contractor.
- Power cables and supply and return hoses for rental unit must be up to 100’ in length to reach existing tie-in.
- Rental Unit supply and return hoses must tie-in to 6” - 8 bolt flanges.
- Chiller unit’s power supply must be able to operate on 480V / 3PH, 225A breaker.
- Chiller unit will use external water pump on-site.