About this file

This solicitation is for the Install Car Charging Stations Project #539-21-203 at the Cincinnati VAMC in Cincinnati, Ohio. The contractor shall furnish all labor and materials to prepare sites, including demolition, site preparation, electrical work, and installation of new equipment at the Cincinnati VAMC campus and Fort Thomas Division campus. The period of performance is 180 calendar days from receipt of the notice to proceed. The project value is estimated between $5-10 million. Bids are due virtually on the date specified in block 13A at the Network Contracting Office in Cincinnati, Ohio. A pre-bid site visit is scheduled for February 24, 2021. This solicitation is 100% set aside for Service-Disabled Veteran Owned Small Businesses verified in the VA Vendor Information Pages database. Temperature checks and masks are required for the site visit.

View the file

Other files

File Type Posted
36C25021B0013 0005.docx DOCX document
36C25021B0013 0004.docx DOCX document
SD321216-02.pdf PDF
SD321216-01.pdf PDF
36C25021B0013 0003.docx DOCX document
36C25021B0013 0002.docx DOCX document
539-21-203_ ADDENDUM_1-write up -2021.0304.pdf PDF
539-21-203 drawings -addendum1 2021.03.pdf PDF
36C25021B0013 0001.docx DOCX document
Site Visit 2.24.2021.pdf PDF
36C25021B0013_1.docx DOCX document
Attachment 2- SPECIFICATONS.pdf PDF
Attachment 3 -Contractor EMR Certification Form.pdf PDF
Attachment 5-DBA-WD-OH020210082.pdf PDF
Attachmetn 4- RFI Form.pdf PDF
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

T A T

E OF OH

IO

R E G

IST ERED A RC

HI

T

E C T

MARK

C.

WISEMAN

13215

Mark C. Wiseman, License #13215 Expiration Date 12/31/2021

P ro je ct

N o.

F

E

D

C

B

A

Department of Veterans Affairs Medical Center

LEVIN PORTER ASSOCIATES

ARCHITECTURE PLANNING INTERIOR DESIGN

3011 NEWMARK DRIVE

MIAMISBURG, OH 45342

937.224.1931 P

937.224.3091 F

HEAPY ENGINEERING

MECHANICAL ELECTRICAL COMMISSIONING TECHNOLOGY

1400 WEST DOROTHY LANE

DAYTON, OH 45409

937.224.0861 P

937.224.5777 F

1 2 3 4 5 6 7 8 9 10

E

D

C

B

A

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

F

Phase

ARCHITECT/ENGINEER OF RECORDCONSULTANT

32 4 5 6 7 8 9 10

CONSTRUCTION

DOCUMENTS

SCHEMATIC DESIGN 5/29/20201

REVISED SCHEMATIC DESIGN 6/23/20202

DESIGN DEVELOPMENT (DD1) 8/18/20203

DESIGN DEVELOPMENT (DD2) 10/09/20204

JASON REEVES

CONSTRUCTION DOCUMENTS 11/06/20205

/8

/2

:1 :4

P

M

3200 VINE STREET CINCINNATI, OHIO 45342

INSTALL CAR CHARGING STATIONS

P ro je c t

N u m b e r

TITLE SHEET

11/06/2020 VP SS

INSTALL CAR CHARGING STATIONS

G001

539-21-203

CINCINNATI AND FT THOMAS

N/A

VICINITY MAP

CINCINNATY CAMPUS

VICINITY MAP

FT THOMAS CAMPUS

SHEET INDEX

Sheet Number Sheet Name

1. GENERAL

G001 TITLE SHEET

8. ARCHITECTURE

A101 SIGNAGE SITE PLANS AND DETAILS

26.ELECTRICAL

E001 INDEX LEGEND AND SCHEDULES

E101 SITE PLAN - CINCINNATI CAMPUS

E102 SITE PLAN - FT THOMAS CAMPUS

E103 ENLARGED FLOOR PLANS

E201 ELECTRIC SINGLE LINE DIAGRAMS

VA PROJECT # 539-21-203

# DESCRIPTION DATE

L2

GP6

U P

U P

H V A C

H V A C

H V A C

H V A C H V A C

H V A C

H V A C

H V A C

H V A C

H V A C

H V A C

H V A C

H V A C

L2A

DC FAST

P

P

P

P

P

P

P

P

P

BUILDING

BUILDING 117

TRAILER

FUTURE WELL FIELD

PB

SOUTH FT THOMAS AVENUE

COCHRAN AVENUE

D R

IN

K

IN

G

F O U N T A

IN

P K

P K

P K

P K

P K

DN

BUILDING 2

BUILDING 13

GARAGE

BUILDING 1

BUILDING 14

BUILDING 3

32.01

26.01

10.02

32.01

26.01

32.01

26.01

10.02

10.02

26.01

10.03

26.01

10.03

26.01

26.01

10.02

10.01

26.01

26.01

10.02

10.02

10.02

32.01

26.0126.01

32.01

10.02

32.01

32.01

A101

BUILDING 64

BUILDING 17

TRAILER

COCHRAN AVENUE

SOUTH FT THOMAS AVENUE

26.01

26.0126.01

26.01

26.01

26.01

26.01

26.01

10.01

32.02

26.02

32.01

1. EXISTING STRUCTURE WILL BE OCCUPIED DURING

ENTIRE CONSTRUCTION PERIOD. CONTRACTOR TO

PROTECT EXISTING STRUCTURE DURING ALL PHASES

OF CONSTRUCTION.

2. COORDINATE ALL PHASING WITH COR.

3. EXISTING PUBLIC MEANS OF EGRESS TO BE

MAINTAINED THROUGHOUT PROJECT AT ALL TIMES.

4. CONTRACTOR TO PROVIDE PROTECTIVE MASKS TO BE

WORN BY ALL CONSTRUCTION STAFF IN ALL COMMON

AREAS WITHIN THE HOSPITAL.

5. A MINIMUM OF 3 WEEKS NOTICE ( 21 CALENDAR DAYS)

IS REQUIRED FOR ANY UTILITY SHUTDOWN OR MAJOR

INTERRUPTION . CONTRACTOR TO COORDINATE

APPROVAL WITH COR.

1' - 0"

1' - 0"

8' - 0"

4" PAINTED

PARKING

STALL LINE

GOVERNMENT

EV SYMBOL

WHEEL STOP

CL CL

8' - 0"

WALL OR CURB

EV CHARGER SEE ELECTRICAL

DRAWINGS

EQ EQ

BOLLARD

ONE SIDED STUDP2

0' - 0 5/8"

20 GA. TRACK &

STUDS 24" O.C.

ACOUSTIC SEALANT

ACOUSTIC

SEALANT

STUD

GYPSUM

WALLBOARD-

PAINT WALL TO

MATCH EXISTING

3 5/8" METAL STUDS @ 24" O.C. WITH 5/8"

TYPE "X" GWB

ON ONE SIDE EXTEND TO UNDERSIDE OF

STRUCTURE

SOUND ATTENUATION

BATT INSULATION

STRUCTURE ABOVE

FINISH CEILING

FINISH FLOOR

RUBBER BASE TO

MATCH EXISTING

A101

Office

Off.

2A

10"

9.01

S

T A T

E OF OH

IO

R E G

IST ERED A RC

HI

T

E C T

MARK

C.

WISEMAN

13215

Mark C. Wiseman, License #13215 Expiration Date 12/31/2021

P ro je ct

N o.

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 10

E

D

C

B

A

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

F

Phase

ARCHITECT/ENGINEER OF RECORDCONSULTANT

32 4 5 6 7 8 9 10

SCHEMATIC DESIGN 5/29/20201

REVISED SCHEMATIC DESIGN 6/23/20202

DESIGN DEVELOPMENT (DD1) 8/18/20203

DESIGN DEVELOPMENT (DD2) 10/09/20204

CONSTRUCTION DOCUMENTS 11/06/20205

/8

/2

:3 :1

P

M P ro je c t

N u m b e r

SIGNAGE SITE PLANS AND

DETAILS

11/06/2020 MW VP

INSTALL CAR CHARGING STATIONS

A101

539-21-203

CINCINNATI AND FT THOMAS

N/A

SCALE | 1" = 50'-0"

SITE SIGNAGE CINCINNATI26 SCALE | 1" = 50'-0"

FT. THOMAS SITE SIGNAGE16

GENERAL NOTESKEYNOTES#

9.01 ELECTRICAL CHASE - GYPSUM WALLBOARD CHASE TO BE WALL

TYPE P2, SEE ELECTRICAL DRAWINGS FOR CONDUIT PATH.

10.01 TYPE 1 NON-ILLUMINATED SINGLE POST PARKING ELECTRIC

VEHICLE SIGNAGE PROVIDED AT EACH PARKING SPOT. PROVIDE

TWO SIGNAGE PER LEVEL 2 CHARGER.

10.02 TYPE 2 NON-ILLUMINATED WALL MOUNTED PARKING ELECTRIC

VEHICLE SIGNAGE. PROVIDE AT EACH PARKING SPOT PER LEVEL 2

CHARGER

10.03 TYPE 2 NON-ILLLUMINATED WALL MOUNTED PARKING ELECTRIC

VEHICLE SIGNAGE. GOVERNMENT PARKING ONLY

26.01 LEVEL 2 CAR CHARGER. SEE ELECTRICAL DRAWINGS.

26.02 DEDUCT ALTERNATE-DC FAST CHARGER. SEE ELECTRICAL

DRAWINGS.

32.01 CONCRETE FILLED BOLLARD AT EACH CAR CHARGER

32.02 PROVIDE WHEEL STOP AT EACH PARKING SPOT

SCALE | 1/2" = 1'-0"

TYPE 2 SIGNAGE2

SCALE | 1/2" = 1'-0"

TYPE 1 SIGNAGE1

NORTHNORTH

SCALE | 1/8" = 1'-0"

PARKING STALL LAYOUT3

SCALE | 1 1/2" = 1'-0"

WALL TYPE

SCALE | 1/16" = 1'-0"

BUILDING 3 - BASEMENT PLAN4

SCALE | 1/8" = 1'-0"

ENLARGED PLAN5

3' -0

DETAIL NOTES

15"DIA

GENERAL NOTES

6"

1 4" DIA GALVANIZED STEEL BOLLARD, CONCRETE FILLED

WITH DOMED CONCRETE TOP. PRIMED AND PAINTED,

COLOR SELECTED BY COR.

2 COMPACTED GRAVEL SUBGRADE.

3 CONCRETE FOUNDATION WITH SLIGHTLY DOMED TOP.

4 EXISTING FINISHED GRADE.

5 1/4"W x 1/4"D REVEAL WITH FLEXIBLE CONCRETE

SEALER TO PREVENT WATER INFILTRATION.

A INCLUDE TWO ADDITIONAL INSTALLED BOLLARDS IN

BASE BID. LOCATION TO BE DETERMINED BY COR.

4"DIA

ELECTRICAL SYMBOLS

EXISTING OUTLET OR DEVICE TO REMAIN . MAINTAIN EXISTING C IRCUITING.

DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS W HERE

REQUIRED.

ELECTRICAL CONNECTION.

DISCONNECT SW ITCH.

ELECTRICAL PANEL OR SW ITCHBOARD PER DRAW INGS.

PULL BOX.P/B

ABBREVIATIONS

AAP - AREA ALARM PANEL - MEDICAL GAS

ACC - ACCESS

ADJ - ADJUSTABLE

AF - ARC FAULT CIRCUIT INTERRUPTER

AFCI - ARC FAULT CIRCUIT INTERRUPTER

AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM

AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATS - AUTOMATIC TRANSFER SW ITCH

BLDG - BUILD ING

BOE - BOTTOM OF EQUIPMENT

BOT - BOTTOM

BTW N - BETW EEN

CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CKT - C IRCUIT

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

COR - CONTRACTING OFFICER'S REPRESENTATIVE

CORR - CORRIDOR

CTR - CENTER

D - DEPTH

DET - DETAIL

DIA - D IAMETER

DIM - D IMENSION

DIV - D IVISION

DN - DOW N

DW G - DRAW ING

EA - EACH

EC - ELECTRICAL (D IVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATION OR ELEVATOR

EM - EMERGENCY

EQ - EQUAL

EQS - EQUIPMENT SUPPLIER

EQUIP - EQUIPMENT

ETR - EXISTING TO REMAIN

EX - EXISTING

EXP - EXPANSION

EXT - EXTERIOR

FCE - FIRE CONTROL EQUIPMENT

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FSC - FIRE SUPPRESSION (D IVISION 21)

FT - FEET

FTG - FOOTING

GC - GENERAL (DIV 01)

GF - GROUND FAULT CIRCUIT INTERRUPTER

GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT

FURNISHED CONTRACTOR INSTALLED

GFFT - GROUND FAULT FEED THRU

HC - HVAC (DIVISION 23)

HP - HORSE POW ER OR HIGH POINT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

IN - INCHES

KEC - KITCHEN EQUIPMENT

L - LENGTH

LBS - POUNDS

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM

MIN - MIN IMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

NIC - NOT IN CONTRACT

NOM - NOMINAL

NTS - NOT TO SCALE

OD - OUTSIDE DIAMETER

OFCI - OW NER FURNISHED CONTRACTOR INSTALLED

OFOI - OW NER FURNISHED OW NER INSTALLED

P - PEDESTAL MOUNTED CHARGER

PC - PLUMBING (DIVISION 22)

PLBG - PLUMBING

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RI - ROUGH-IN

S - SURFACE MOUNTED/W ALL SURFACE MOUNTED CHARGER

SC - SECURITY (DIV 28)

SCH - SCHEDULE

SHT - SHEET

SMS - SECURITY MANAGEMENT SYSTEM

SPEC - SPECIFICATIONS

SQ - SQUARE

SS - STAINLESS STEEL

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY

TC - TECHNOLOGY

TEMP - TEMPERATURE

TOE - TOP OF EQUIPMENT

TYP - TYPICAL

UNO - UNLESS NOTED OTHERW ISE

VFD - VARIABLE FREQUENCY DRIVE

VOL - VOLUME

W / - W ITH

W /O - W ITHOUT

W P - W EATHERPROOF

ZVC - ZONE VALVE CABINET

E2

B

E2

NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT

TO MODIFICATIONS ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT

NECESSARILY BE USED ON THIS PROJECT.

DETAIL: B = DETAIL DESIGNATION

E2 = SHEET W HERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

E2 = SHEET W HERE SECTION IS LOCATED

PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

GENERAL FLOOR PLAN NOTES

EACH ARROW HEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES

CIRCUIT(S).

X - 1,2

T2 1 ELEVATION: 1 = ELEVATION DESIGNATION

T2 = SHEET W HERE ELEVATION IS LOCATED

P

PEDESTAL/PAD MOUNTED CHARGING STATION.

S

W ALL SURFACE MOUNTED CHARGING STATIO N.

1 3000 LB. CONCRETE ENCASEMENT. 3" M IN. FROM

OUTSIDE OF DUCT.

2 SCHEDULE 40 PVC DUCT. SIZE AS NOTED ON PLANS.

3 RED DYE, RED DUST OR YELLOW MARKER TAPE ON

COMPACTED FILL.

DETAIL NOTES

1' -6

TAMPED

BACKFILL

FIN ISH GRADE

2' -6

C

O V

E R .

1 3000 LB. CONCRETE.

2 CHEDULE 40 PVC DUCT. S IZE AS NOTED ON PLANS.

3 MIN. 3" SPACING BETW EEN CONDUITS AND MIN. 3"

ENCASEMENT (TYPICAL). PROVIDE CONDUIT SPACERS

6'-0" O.C.

4 RED DYE, RED DUST OR YELLOW MARKER TAPE ON

COMPACTED FILL.

DETAIL NOTES

1' -6

TAMPED

BACKFILL

FIN ISH GRADE

2' -3

C

O V

E R

1 3000 LB. CONCRETE.

2 CHEDULE 40 PVC DUCT. S IZE AS NOTED ON PLANS.

3 MIN. 3" SPACING BETW EEN CONDUITS AND MIN. 3"

ENCASEMENT (TYPICAL). PROVIDE CONDUIT SPACERS

6'-0" O.C.

4 RED DYE, RED DUST OR YELLOW MARKER TAPE ON

COMPACTED FILL.

DETAIL NOTES

2' -3

C

O V

E R

1' -6

TAMPED

BACKFILL

FIN ISH GRADE

1 3000 LB. CONCRETE.

2 CHEDULE 40 PVC DUCT. S IZE AS NOTED ON PLANS.

3 MIN. 3" SPACING BETW EEN CONDUITS AND MIN. 3"

ENCASEMENT (TYPICAL). PROVIDE CONDUIT SPACERS

6'-0" O.C.

4 RED DYE, RED DUST OR YELLOW MARKER TAPE ON

COMPACTED FILL.

DETAIL NOTES

FIN ISH GRADE

TAMPED

BACKFILL

2' -3

C

O V

E R

1' -6

1 5" CONCRETE W ALLS, FOUR SIDES.

2 1/2" DIA. REINFORCED STEEL-10"CC BOTH W AYS.

3 1/4" CHECKERED STEEL PLATE COVER.

4 2"X2"X1/4" L W ELDED TO PLATE. TW O SIDES ONLY 1/4"

CLEARANCE FIT.

5 UNDERGROUND DUCT-TURN UP @ 45 DEG.

6 CONDUCTORS-LOOP/PULL OR SPLICE.

7 CROSSW ISE FOR SUPPORT.

DETAIL NOTES

5"

.3'-10" SQUARE

2C

DIA.

2' -4

6C DIA.

2' -6

1 REFER TO MANUFACTURER DETAILS FOR PEDESTAL

INFORMATION.

2 ANCHOR BOLTS BY EQUIPMENT SUPPLIER.

3 CHAMFERED EDGE.

4 FINISH GRADE, COMPACT TO 95%.

5 SIX #4 REINFORCING BARS VERTICALLY ON #3 STIRRUPS

AT 18" O.C.

6 PVC CONDUIT, SCHEDULE 40.

7 RIGID GALVANIZED STEEL CONDUIT.

8 BASE PLATE, PAD, ETC BY PEDESTAL MANUFACTURER.

REFER TO MANUFACTURER INSTALLATION INSTRUCTIONS.

DETAIL NOTES

18" SQ.

4' -0

2' -6

" 1' -6

2"

A EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED

EQUIPMENT GROUNDING CONDUCTOR.

B FOR EXISTING EQUIPMENT, SUCH AS W IRING DEVICES, CONDUITS, ETC., SHOW N ON

PLANS TO BE REMOVED, COMPLETELY CUT/CAP CO NDUITS AT THE AREA OF W ORK

PERIMETER AND REMOVE CONDUIT W ITHIN THE W ORK AREA, DISCONNECT W IRING AT

THE OVERCURRENT PROTECTIVE DEVICE AND REMOVE W ITING COMPLETELY FROM

THE ABANDONED CONDUITS.

GENERAL NOTES

P ro je ct

N o.

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 10

E

D

C

B

A

VA FO RM 08 - 6231

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project D irector

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

F

Phase

ARCHITECT/ENGINEER OF RECORDCONSULTANT

32 4 5 6 7 8 9 10

CONSTRUCTION

DOCUMENTS

SCHEMATIC DESIGN 5/29/20201

REVISED SCHEMATIC DESIGN 6/23/20202

DESIGN DEVELOPMENT (DD1) 8/18/20203

DESIGN DEVELOPMENT (DD2) 10/09/20204

JASON REEVES

CONSTRUCTION DOCUMENTS 11/06/20205

539-21-203

N/A

CINCINNATI AND FT THOMAS

FULLY SPRINKLERED

/4

/2

:0

:5

P

M P ro je c t

N u m b e r

INDEX LEGEND AND SCHEDULES

11/06/2020 MSG NES

INSTALL CAR CHARGING STATIONS

E001

INDEX

SHEET NUMBER SHEET NAME

E001 INDEX LEGEND AND SCHEDULES

E101 SITE PLAN - CINCINNATI CAMPUS

E102 SITE PLAN - FT THOMAS CAMPUS

E103 ENLARGED FLOOR PLANS

E201 ELECTRIC SINGLE LINE DIAGRAMS

56 kVA 56 kVA (155 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Load: 21.00 kVA 21.00 kVA 14.00 kVA

41 Space -- -- 0 kVA 0 kVA -- -- Space 42

39 Space -- -- 0 kVA 0 kVA -- -- Space 40

37 Space -- -- 0 kVA 0 kVA -- -- Space 38

35 Space -- -- 0 kVA 0 kVA -- -- Space 36

33 Space -- -- 0 kVA 0 kVA -- -- Space 34

31 Space -- -- 0 kVA 0 kVA -- -- Space 32

29 Space -- -- 0 kVA 0 kVA -- -- Space 30

27 Space -- -- 0 kVA 0 kVA -- -- Space 28

25 Space -- -- 0 kVA 0 kVA -- -- Space 26

23 Space -- -- 0 kVA 0 kVA -- -- Space 24

21 Space -- -- 0 kVA 0 kVA -- -- Space 22

19 Space -- -- 0 kVA 0 kVA -- -- Space 20

17 Space -- -- 0 kVA 0 kVA -- -- Space 18

15 -- -- -- 4 kVA 4 kVA -- -- -- 16

13 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 14

11 -- -- -- 4 kVA 4 kVA -- -- -- 12

9 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 10

7 -- -- -- 4 kVA 4 kVA -- -- -- 8

5 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 6

3 -- -- -- 4 kVA 4 kVA -- -- -- 4

1 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W 1 A Mains Rating: 400 A Supply From: Enclosure: Type 1 Mains Type: M.L.O.

Location: Mounting: Surface A.I.C. Rating: 42,000

Panel: L2

112 kVA 112 kVA (311 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Load: 42.00 kVA 35.00 kVA 35.00 kVA

41 Space -- -- 0 kVA 0 kVA -- -- Space 42

39 Space -- -- 0 kVA 0 kVA -- -- Space 40

37 Space -- -- 0 kVA 0 kVA -- -- Space 38

35 -- -- -- 0 kVA 0 kVA -- -- -- 36

33 Spare 40 A 2 0 kVA 0 kVA 2 40 A Spare 34

31 -- -- -- 4 kVA 4 kVA -- -- -- 32

29 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 30

27 -- -- -- 4 kVA 4 kVA -- -- -- 28

25 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 26

23 -- -- -- 4 kVA 4 kVA -- -- -- 24

21 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 22

19 -- -- -- 4 kVA 4 kVA -- -- -- 20

17 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 18

15 -- -- -- 4 kVA 4 kVA -- -- -- 16

13 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 14

11 -- -- -- 4 kVA 4 kVA -- -- -- 12

9 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 10

7 -- -- -- 4 kVA 4 kVA -- -- -- 8

5 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 6

3 -- -- -- 4 kVA 4 kVA -- -- -- 4

1 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W 1 A Mains Rating: 400 A Supply From: Enclosure: Type 3R Mains Type: M.L.O.

Location: Mounting: Surface A.I.C. Rating: 10,000

Panel: L2A

63 kVA 63 kVA (175 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Load: 24.50 kVA 21.00 kVA 17.50 kVA

29 Space -- -- 0 kVA 0 kVA -- -- Space 30

27 Space -- -- 0 kVA 0 kVA -- -- Space 28

25 Space -- -- 0 kVA 0 kVA -- -- Space 26

23 Space -- -- 0 kVA 0 kVA -- -- Space 24

21 Space -- -- 0 kVA 0 kVA -- -- Space 22

19 -- -- -- 4 kVA 0 kVA -- -- -- 20

17 L2 CHARGER 40 A 2 4 kVA 0 kVA 2 40 A Spare 18

15 -- -- -- 4 kVA 4 kVA -- -- -- 16

13 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 14

11 -- -- -- 4 kVA 4 kVA -- -- -- 12

9 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 10

7 -- -- -- 4 kVA 4 kVA -- -- -- 8

5 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 6

3 -- -- -- 4 kVA 4 kVA -- -- -- 4

1 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W MCB Rating: 225 A Mains Rating: 400 A Supply From: Enclosure: Type 1 Mains Type: M.L.O.

Location: Mounting: Surface A.I.C. Rating: 22,000

Panel: GP6

50 kVA 50 kVA (60 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Load: 16.67 kVA 16.67 kVA 16.67 kVA

29 Space -- -- 0 kVA 0 kVA -- -- Space 30

27 Space -- -- 0 kVA 0 kVA -- -- Space 28

25 Space -- -- 0 kVA 0 kVA -- -- Space 26

23 Space -- -- 0 kVA 0 kVA -- -- Space 24

21 Space -- -- 0 kVA 0 kVA -- -- Space 22

19 Space -- -- 0 kVA 0 kVA -- -- Space 20

17 Space -- -- 0 kVA 0 kVA -- -- Space 18

15 Space -- -- 0 kVA 0 kVA -- -- Space 16

13 Space -- -- 0 kVA 0 kVA -- -- Space 14

11 Space -- -- 0 kVA 0 kVA -- -- Space 12

9 Space -- -- 0 kVA 0 kVA -- -- Space 10

7 Space -- -- 0 kVA 0 kVA -- -- Space 8

5 -- -- -- 17 kVA 0 kVA -- -- -- 6

3 -- -- -- 17 kVA 0 kVA -- -- -- 4

1 DC FAST CHARGER 80 A 3 17 kVA 0 kVA 3 80 A FUTURE 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W 1 A Mains Rating: 200 A Supply From: Enclosure: Type 3R Mains Type: M.L.O.

Location: Mounting: Surface A.I.C. Rating: 10,000

Panel: DC FAST

SCALE: NONE

CONCRETE ENCASED UNDERGROUND DUCT - 1

SCALE: NONE

UNDERGROUND DUCTS - 2

SCALE: NONE

UNDERGROUND DUCTS - 3

SCALE: NONE

UNDERGROUND DUCTS - 4

SCALE: NONE

LARGE IN-GROUND PULLBOX

21 kVA 21 kVA (58 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: * PROVIDE NEW BREAKER

Total Load: 3.50 kVA 7.00 kVA 10.50 kVA

41 -- -- -- 4 kVA 4 kVA -- -- -- 42

39 L2 CHARGER* 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER* 40

37 EXIST 20 A 1 0 kVA 4 kVA -- -- -- 38

35 EXIST 20 A 1 0 kVA 4 kVA 2 40 A L2 CHARGER* 36

33 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 34

31 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 32

29 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 30

27 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 28

25 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 26

23 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 24

21 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 22

19 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 20

17 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 18

15 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 16

13 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 14

11 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 12

9 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 10

7 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 8

5 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 6

3 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 4

1 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W 1 A Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: M.L.O.

Location: Mounting: Surface A.I.C. Rating: 10,000

Panel: PB (EXIST)

BUILDING 1 (BASEMENT)

US-1D

BUILDING 3 (BASEMENT)

BUILDING 3 MAIN D IST. BOARD

GARAGE ELEC ROOM (LEVEL 1)

MDP

BUILDING 117

MS (BUILD ING 64 LOW ER LEVEL)

BUILDING 117

MS (BUILD ING 64 LOW ER LEVEL)

SCALE: NONE

L2 CHARGER BASE

# DESCRIPTION DATE

SCALE: NONE

PROTECTIVE BOLLARD

D N

D N

O ff.

B

O ff.

B

O ff.

B

O ff.

B

O ff.

B

O c c

T h e ra p y

B

K it.

M u lti-P u rp o s e

B

O ff.

B

O ff.

B

G ro u p R m

B

G ro u p

R o o m B

132B

A d m . A s s t.

B

O ffic e B

125A

S to r.

B

127A

S to r.

B

137A S to r.

B 137B

A u d io lo g y

C lin ic B

T lt.

B

T e le

B

124A

R N

In ta k e

B

O x y g e n

B

P h y s ic a l

T h e ra p y /O c c u p a tio n a l

T h e ra p y

B

S p e e c h

P a th o lo g y

B

S p e e c h

P a th o lo g y

B

E le c tric a l

C lo s e t

B

N a v e

B

C h a n c e l B

163A

C h a p . C lin

P a s to ra l

E d u c a tio n

B 163G

C h a p la in A s s is ta n t

B 163H

C h ie f B

163J C h a p la in B

163K

C o rrid o r

C *1*8

C o rrid o r

C *1*6

S ta ir 3 S

*1*3

S ig

B 124B

S to ra g e

B 132A

O ffic e B

125B

C o n fe re n c e

B 163D

B le s s e d

S a c ra m e n t

B 163E

C lo s e t

B 163F

C le ric a l

D N

U P

D N

U P

2S

P S

P

S

S

S

S S

US-1D

MDP

PARKING

GARAGE

BUILDING 2

BUILDING 1

BUILDING

BUILDING

L2

GP6

BUILDING 2

BUILDING 3

TRAILER

TRAILER

T R

A

IL

E R

FISHER

HOUSE

E101

E101

E101

PB

PB - 36,38

PB - 39,41 PB - 40,42EX

L2 - 1,3 L2 - 2,4

L2 - 5,7

L2 - 6,8

L2 - 10,12

L2 - 9,11

L2 - 14,16

L2 - 13,15

GP6 - 9,11

GP6 - 6,8

GP6 - 5,7

GP6 - 2,4

GP6 - 1,3

P GP6 - 13,15

GP6 - 10,12

P GP6 - 17,19

GP6 - 14,16

1 7

E103

E101

E101

BUILDING

BUILDING

T R

A

IL

E R

DUAL L2 CHARGER

(SURFACE)

BOLLARD

DUAL L2 CHARGER

(SURFACE)

BOLLARD

DUAL L2 CHARGER

(SURFACE)

BOLLARD

DUAL L2 CHARGER

(PEDESTAL)

BOLLARD

DUAL L2 CHARGER SURFACE MOUNT

(TYPICAL)

BOLLARD

DUAL L2 CHARGER

PEDESTAL MOUNT

(TYPICAL)

DUAL L2 CHARGER (SURFACE)

L2 CHARGER

(SURFACE)

BOLLARD

BOLLARD

GP6

MDP

GP

ATSEM

GPEMFACP

EX

EX

EX

EXEX

P

S

S

S

P ro je ct

N o.

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 10

E

D

C

B

A

VA FO RM 08 - 6231

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project D irector

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

F

Phase

ARCHITECT/ENGINEER OF RECORDCONSULTANT

32 4 5 6 7 8 9 10

CONSTRUCTION

DOCUMENTS

SCHEMATIC DESIGN 5/29/20201

REVISED SCHEMATIC DESIGN 6/23/20202

DESIGN DEVELOPMENT (DD1) 8/18/20203

DESIGN DEVELOPMENT (DD2) 10/09/20204

JASON REEVES

CONSTRUCTION DOCUMENTS 11/06/20205

539-21-203

N/A

CINCINNATI AND FT THOMAS

FULLY SPRINKLERED

/4

/2

:0

:5

P

M P ro je c t

N u m b e r

SITE PLAN - CINCINNATI CAMPUS

11/06/2020 MSG NES

INSTALL CAR CHARGING STATIONS

E101

SCALE: 1" = 50'-0"

SITE PLAN - CINCINNATI

NOTES

1 NEW DUAL LEVEL 2 CHARGER.

2 NEW SINGLE LEVEL 2 CHARGER.

3 PROVIDE ALL REQUIRED FLOOR PENETRATIONS FOR NEW CAR

CHARGER CIRCUITS TO RISE FROM FLOOR BELOW.

4 APPROXIMATE LOCATION OF NEW PANELBOARD. FIELD VERIFY EXACT

LOCATION WITH ENGINEER.

5 PROVIDE PROTECTIVE BOLLARD. REFER TO DETAIL SHEET E001.

6 RUN 2-#8, 1-#10 GRD. IN 1" C. TO EACH CAR CHARGING STATION. DUAL

STATIONS SHALL SHARE SINGLE CONDUIT. CIRCUIT TO 40A/2P

BREAKER(S) IN PANEL INDICATED.

7 RUN 2-#8, 1-#10 GRD. IN 1" C. TO EACH CAR CHARGING STATION. DUAL

STATIONS SHALL SHARE SINGLE CONDUIT. CIRCUIT TO NEW PANEL

GP6.

8 RUN 2-#8, 1-#10 GRD. IN 1" C. TO EACH CAR CHARGING STATION. DUAL

STATIONS SHALL SHARE SINGLE CONDUIT. CIRCUIT TO NEW PANEL L2.

9 PROVIDE TRENCHING/SAW CUTTING AND PATCHING AS REQUIRED TO

INSTALL CONDUIT(S) SERVING NEW L2 CHARGER(S). RISE AT BUILDING

AS SHOWN.

10 REMOVE EXISTING LEVEL 2 CHARGER INCLUDING CIRCUIRTY BACK TO

SOURCE.

11 NEW CIRCUITS TO RISE TO ELECTRIC ROOM ABOVE. NEW CIRCUITS TO

FOLLOW PATH OF EXISTING CAR CHARGER CIRCUITS TO BE REMOVED

TO NEW CHARGER LOCATION.

12 EXPOSED CONDUIT SHALL BE RUN IN IMC FOR PHYSICAL PROTECTION

OF CIRCUITS.

NSCALE: NONE

BUILDING 1 SITE PHOTO

SCALE: NONE

GARAGE SITE PHOTO

SCALE: NONE

BUILDING 3 SITE PHOTO

SCALE: 1/8" = 1'-0"

GARAGE ELECTRIC ROOM

SCALE: 1/16" = 1'-0"

BUILDING 1 ENLARGED

P K

P K

P K

P K

P K

SOUTH FT THOMAS AVENUE

COCHRAN AVENUE

D R

IN

K

IN

G

F O U N T A

IN

EMERGENCY

GENERATOR

ROOM

MAIN

ELECTRIC

ROOM

MAIN

SWITCHBOARD

"MS"

EMERGENCY SWITCHBOARD "MEDP"

ATS-1

EDP-E

EDP-E1

EDP-E2

EDP-L

ATS-2

EDP-L

EDP-C

ATS-3

EDP-C

ECB.1

EL1.4

EX

EX

EX

EXEX

EX

EX

EX

EX

EDP-E2

ATS-EQ2

EX

EX

EX

EX

P

P

P

P

P

P

P

P

2P

BUILDING

BUILDING 117

TRAILER

FUTURE GEOTHERMAL

W ELL FIELD

PB

L2A

DC FAST

E001

E001

E001

E102

E102

L2A - 1,3

L2A - 2,4 L2A - 5,7

L2A - 6,8

L2A - 9,11

L2A - 10,12 L2A - 13,15

L2A - 14,16 L2A - 17,19

L2A - 18,20 L2A - 21,23

L2A - 22,24

L2A - 25,27

L2A - 26,28

L2A - 29,31

L2A - 30,32

E102

E102

(TYPICAL OF 8)

(TYP)

(TYP)

(TYP)

DC FAST CHARGER

BOLLARD

BOLLARD

PANEL L2A

STRUCTURAL SUPPORT

P

P

P

P

P

P

P

P

L2A

P ro je ct

N o.

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 10

E

D

C

B

A

VA FO RM 08 - 6231

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project D irector

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

F

Phase

ARCHITECT/ENGINEER OF RECORDCONSULTANT

32 4 5 6 7 8 9 10

CONSTRUCTION

DOCUMENTS

SCHEMATIC DESIGN 5/29/20201

REVISED SCHEMATIC DESIGN 6/23/20202

DESIGN DEVELOPMENT (DD1) 8/18/20203

DESIGN DEVELOPMENT (DD2) 10/09/20204

JASON REEVES

CONSTRUCTION DOCUMENTS 11/06/20205

539-21-203

N/A

CINCINNATI AND FT THOMAS

FULLY SPRINKLERED

/4

/2

:0

:5

P

M P ro je c t

N u m b e r

SITE PLAN - FT THOMAS CAMPUS

11/06/2020 MSG NES

INSTALL CAR CHARGING STATIONS

E102

SCALE: 1" = 30'-0"

SITE PLAN - FT THOMAS

N

NOTES

1 LOCATION OF NEW DUAL LEVEL 2 CHARGER.

2 LOCATION OF NEW FREESTANDING 50KW DC FAST CHARGER. PROVIDE

CONCRETE BASE PER MANUFACTURER REQUIREMENTS.

3 LOCATION OF NEW 208V TO 480Y/277V TRANSFORMER AND NEMA 1

BREAKER SERVING DC FAST CHARGER.

4 APPROXIMATE LOCATION OF NEW PANEL.

5 RUN 2-#8, 1-#10 GRD. IN 1" C. TO EACH CAR CHARGING STATION. DUAL

STATIONS SHALL SHARE SINGLE CONDUIT. REFER TO DUCTBANK

DETAILS SHEET E000.

6 RUN 3-#3, 1-#8 GRD. IN 1.25" C. TO TO NEW DC FAST. CHARGER

STATION FROM NEW PANEL "DC FAST"

7 SAWCUT AND PATCH EXISTING CONCRETE/ASPHALT AS REQUIRED

FOR NEW DUCTBANK INSTALLATION. PATCH TO MATCH EXISTING.

8 UNDER DEDUCT ALTERNATE #1 WORK ASSOCIATED WITH DC FAST

CHARGER TO BE REMOVED FROM PROJECT. THIS INCLUDES THE DC

FAST CHARGER, NEW BREAKER IN THE SWITCHBOARD,

TRANSFORMER, BREAKER ON SECONDARY OF TRANSFORMER,

FEEDER, CONDUIT, DUCTBANK, PANELBOARD AND CONNECTION TO DC

FAST CHARGER.

9 PROVIDE CONCRETE HOUSEKEEPING PAD FOR TRANSFORMER AND

ASSOCIATED BREAKER.

10 PROVIDE PROTECTIVE BOLLARD. REFER TO DETAIL SHEET E001.

11 PROVIDE STRUCTURAL SUPPORT FOR PANELBOARD MOUNTING. TWO

(2) GALVANIZED STEEL SUPPORTS TO GO TO A DEPTH NO LESS THAN

4'-0" IN CONCRETE PIERS.

SCALE: NONE

BUILDING 117 SITE PHOTO

SCALE: 1 1/2" = 1'-0"

LOT SITE PHOTO

SCALE: 1" = 30'-0"

PARTIAL SITE PLAN

SCALE: 1/8" = 1'-0"

BUILDING 64 ELECTRIC ROOM

DN

Supply Storage

SUB 1

Equip. Room

SUB 2

Medical Records Storage

SUB 4

Stairs

S-SB-1

Electrical

Conference Room

Break Room

1A

Corridor

C*B *2

Elev. Equip.

Vestibule

Lobby

010A

Pipe Basement

1B

Off.

2A

Office

HR Off

3A

HR Off.

HR Off.

HR Off.

Stairs

S*B*2

HR Off.

HR Off.

Corridor

C*B *1

Lobby

Bathroom

10B

HR Office

Clos.

10D

H.A.C.

Stairs

S*B*1

BASEMENT PLANSUB-BASEMENT PLAN

UP

UP

UP

UP

UP

UP

UP

UP

UPUP

Fire Alarm Control B019A

UP

Transformer Room A023

PP1LPB

XFMR

MCCD

CDP

LSDP

MCC2

US-1PUS-1X

LC

DISTRIBUTION

SWITCHGEAR

DISTRIBUTION

SWITCHGEAR

MV SWGR

PS1

TGDE

ATS-14

ATS-16

ATS

CDP

B1

GDE

VFD

US-1C

US-1D

HONEYWELL

FACPEF3

PLC

CABINET

JCI

JCI

PB

ATS -

ESWB-F-3

JCI

CAB

METER

FUSE

CABINET

XFMR

KVA

UNIT

SUBSTATION

KVA

UNIT

SUBSTATION

ATS-17

HONEYWELL

PB 1

PB

(ABOVE)

NEW PANEL

L2

P ro je ct

N o.

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 10

E

D

C

B

A

VA FO RM 08 - 6231

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project D irector

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

F

Phase

ARCHITECT/ENGINEER OF RECORDCONSULTANT

32 4 5 6 7 8 9 10

CONSTRUCTION

DOCUMENTS

SCHEMATIC DESIGN 5/29/20201

REVISED SCHEMATIC DESIGN 6/23/20202

DESIGN DEVELOPMENT (DD1) 8/18/20203

DESIGN DEVELOPMENT (DD2) 10/09/20204

JASON REEVES

CONSTRUCTION DOCUMENTS 11/06/20205

539-21-203

N/A

CINCINNATI AND FT THOMAS

FULLY SPRINKLERED

/4

/2

:0

:5

P

M P ro je c t

N u m b e r

ENLARGED FLOOR PLANS

11/06/2020 MSG NES

INSTALL CAR CHARGING STATIONS

E103

SCALE: 1/16" = 1'-0"

BUILDING 3 ENLARGED PLANS

NOTES

1 NEW CHASE TO SUB-BASEMENT LEVEL BELOW.

2 CONDUIT TO BE RUN DOWN INTERIOR WALL AND PENETRATE OUT TO

SERVE LEVEL 2 CHARGING STATION(S).

3 EXPOSED CONDUIT SHALL BE RUN AS IMC FOR PHYSICAL PROTECTION

OF CIRCUITS.

SCALE: 1/8" = 1'-0"

ELECTRIC ROOM A23

U.L.H.&P. CO.

12.47KV PRIMARY

1000 KVA DRY- TYPE

PADMOUNTED XFMR.

12.47 KV DELTA TO

208Y/120V. 3PH-4W

Z=5.5% MIN.

EXIST. V.A. OWNED

FEEDER

3000A/3P

I=2776A.

A

/3 P

A

/3 P

DC FAST

208V-3PH

112.5 KVA

480Y/277V

3PH-4W

200A

D C

F A

S T

208Y/120V-3PH-4W

/3

A

GP6

PAD-MOUNT TRANSFORMER "TPG"

SWBD

METERING

TVSS

40HP

ELEV

GP GP2

40HP

ELEV

GP1 GP3

LCP2

LCP3

LCP1

GP5 GPEM2

GPEM

ATSEM

400A/4P

400/3

100KW/125KVA

208Y/120V-3PH-4W

/3

A

/3

A

/3

A

/3

A

/3

A

TVSS

L2A PANEL

L2 CHARGER

(TYP)

L2 CHARGER

(TYP)

DC FAST

CHARGER

3000A, 208Y/120V-3PH-4W

P A

N E

L

SWBD

METERING

2000A

12,470V, 750KVA

208Y/120V

3PH-4W

SWBD

METERING

SPD

3000A, 208Y/120V-3PH-4W

TO PS1

L2 PANEL

L2 CHARGER

(TYP)

A

/3 P

EXISTING MAIN DIST SWBD "MDP" (GARAGE)

EXISTING MAIN DIST SWBD "MS" (FT THOMAS)

EXISTING UNIT SUBSTATION "US-1D" (BUILDING 1)

L.A.

AREA OF W ORK

AREA OF W ORK

AREA OF W ORK

P ro je ct

N o.

F

E

D

C

B

A

1 2 3 4 5 6 7 8 9 10

E

D

C

B

A

VA FO RM 08 - 6231

321 4 5 6 7 8 9 10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project D irector

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

F

Phase

ARCHITECT/ENGINEER OF RECORDCONSULTANT

32 4 5 6 7 8 9 10

CONSTRUCTION

DOCUMENTS

SCHEMATIC DESIGN 5/29/20201

REVISED SCHEMATIC DESIGN 6/23/20202

DESIGN DEVELOPMENT (DD1) 8/18/20203

DESIGN DEVELOPMENT (DD2) 10/09/20204

JASON REEVES

CONSTRUCTION DOCUMENTS 11/06/20205

539-21-203

N/A

CINCINNATI AND FT THOMAS

FULLY SPRINKLERED

/4

/2

:0

:5

P

M P ro je c t

N u m b e r

ELECTRIC SINGLE LINE DIAGRAMS

11/06/2020 MSG NES

INSTALL CAR CHARGING STATIONS

E201

NOTES

1 UTILIZE EXISTING 400A/3P BREAKER IN EXISTING UNIT SUBSTATION.

2 3-500 KCMIL, 1-#3 GRD. IN 4" C.

3 UNDER DEDUCT ALTERNATE #1 WORK ASSOCIATED WITH DC FAST

CHARGER TO BE REMOVED FROM PROJECT.

4 REFER TO SITE PLAN FOR CIRCUIT SIZING.

5 PROVIDE NEW 400A/3P BREAKER IN EXISTING DISTRIBUTION PANEL.

6 4-500 KCMIL, 1-#3 GRD. IN 4" C.

7 4-#3/0, 1-#4 GRD. IN 2" C.

8 PROVIDE NEW 400A/3P SWITCH FUSED AT 400A IN EXISTING

DISTRIBUTION PANEL.

G001
A101
2020-05073 - Sheet - E001 - INDEX LEGEND AND SCHEDULES
2020-05073 - Sheet - E101 - SITE PLAN - CINCINNATI CAMPUS
2020-05073 - Sheet - E102 - SITE PLAN - FT THOMAS CAMPUS
2020-05073 - Sheet - E103 - ENLARGED FLOOR PLANS
2020-05073 - Sheet - E201 - ELECTRIC SINGLE LINE DIAGRAMS

File details come from the government source that posted it. Updated .