539-21-203 drawings -addendum1 2021.03.pdf
PDF 8 MB Posted
- Attached to
- Install Car Charging Stations Project #539-21-203 at the Cincinnati VAMC, Cincinnati, OH
- Solicitation number
- 36C25021B0013
About this file
This solicitation is for the Install Car Charging Stations Project #539-21-203 at the Cincinnati VAMC in Cincinnati, Ohio. The contractor shall furnish all labor and materials for site preparation, building construction including demolition, carpentry, finishes, electrical work and installation of new equipment at two locations - the Cincinnati VAMC and Fort Thomas Division campus. The period of performance is 180 calendar days from receipt of the notice to proceed. The project value is estimated between $5-10 million. The NAICS code is 236220 with a size standard of $39.5 million. The bid opening will be virtual through the Network Contracting Office on the date specified in block 13A. A pre-bid site visit is scheduled for February 24, 2021. This solicitation is 100% set aside for service-disabled veteran-owned small businesses that are verified in the VA VIP database prior to award. Temperature checks and masks are required for the site visit.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25021B0013 0005.docx | DOCX document | |
| 36C25021B0013 0004.docx | DOCX document | |
| SD321216-02.pdf | ||
| SD321216-01.pdf | ||
| 36C25021B0013 0003.docx | DOCX document | |
| 36C25021B0013 0002.docx | DOCX document | |
| 539-21-203_ ADDENDUM_1-write up -2021.0304.pdf | ||
| 36C25021B0013 0001.docx | DOCX document | |
| Site Visit 2.24.2021.pdf | ||
| 36C25021B0013_1.docx | DOCX document | |
| Attachment 2- SPECIFICATONS.pdf | ||
| Attachment 3 -Contractor EMR Certification Form.pdf | ||
| Attachment 1 - DRAWINGS.pdf | ||
| Attachment 5-DBA-WD-OH020210082.pdf | ||
| Attachmetn 4- RFI Form.pdf |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
T A T
E OF OH
IO
R E G
IST ERED A RC
HI
T
E C T
MARK
C.
WISEMAN
13215
Mark C. Wiseman, License #13215 Expiration Date 12/31/2021
P ro je ct
N o.
F
E
D
C
B
A
Department of Veterans Affairs Medical Center
LEVIN PORTER ASSOCIATES
ARCHITECTURE PLANNING INTERIOR DESIGN
3011 NEWMARK DRIVE
MIAMISBURG, OH 45342
937.224.1931 P
937.224.3091 F
HEAPY ENGINEERING
MECHANICAL ELECTRICAL COMMISSIONING TECHNOLOGY
1400 WEST DOROTHY LANE
DAYTON, OH 45409
937.224.0861 P
937.224.5777 F
1 2 3 4 5 6 7 8 9 10
E
D
C
B
A
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
F
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
32 4 5 6 7 8 9 10
CONSTRUCTION
DOCUMENTS
SCHEMATIC DESIGN 5/29/20201
REVISED SCHEMATIC DESIGN 6/23/20202
DESIGN DEVELOPMENT (DD1) 8/18/20203
DESIGN DEVELOPMENT (DD2) 10/09/20204
JASON REEVES
CONSTRUCTION DOCUMENTS 11/06/20205
/8
/2
:1 :4
P
M
3200 VINE STREET CINCINNATI, OHIO 45342
INSTALL CAR CHARGING STATIONS
P ro je c t
N u m b e r
TITLE SHEET
11/06/2020 VP SS
INSTALL CAR CHARGING STATIONS
G001
539-21-203
CINCINNATI AND FT THOMAS
N/A
VICINITY MAP
CINCINNATY CAMPUS
VICINITY MAP
FT THOMAS CAMPUS
SHEET INDEX
Sheet Number Sheet Name
1. GENERAL
G001 TITLE SHEET
8. ARCHITECTURE
A101 SIGNAGE SITE PLANS AND DETAILS
26.ELECTRICAL
E001 INDEX LEGEND AND SCHEDULES
E101 SITE PLAN - CINCINNATI CAMPUS
E102 SITE PLAN - FT THOMAS CAMPUS
E103 ENLARGED FLOOR PLANS
E201 ELECTRIC SINGLE LINE DIAGRAMS
VA PROJECT # 539-21-203
# DESCRIPTION DATE
L2
GP6
U P
U P
H V A C
H V A C
H V A C
H V A C H V A C
H V A C
H V A C
H V A C
H V A C
H V A C
H V A C
H V A C
H V A C
L2A
DC FAST
P
P
P
P
P
P
P
P
P
BUILDING
BUILDING 117
TRAILER
FUTURE WELL FIELD
PB
SOUTH FT THOMAS AVENUE
COCHRAN AVENUE
D R
IN
K
IN
G
F O U N T A
IN
P K
P K
P K
P K
P K
DN
BUILDING 2
BUILDING 13
GARAGE
BUILDING 1
BUILDING 14
BUILDING 3
32.01
26.01
10.02
32.01
26.01
32.01
26.01
10.02
10.02
26.01
10.03
26.01
10.03
26.01
26.01
10.02
10.01
26.01
26.01
10.02
10.02
10.02
32.01
26.0126.01
32.01
10.02
32.01
32.01
10.01 26.01
32.0132.01
32.01
BUILDING 64
BUILDING 17
TRAILER
COCHRAN AVENUE
SOUTH FT THOMAS AVENUE
26.01
26.0126.01
26.01
26.01
26.01
26.01
26.01
10.01
32.02
26.02
32.01
1. EXISTING STRUCTURE WILL BE OCCUPIED DURING
ENTIRE CONSTRUCTION PERIOD. CONTRACTOR TO
PROTECT EXISTING STRUCTURE DURING ALL PHASES
OF CONSTRUCTION.
2. COORDINATE ALL PHASING WITH COR.
3. EXISTING PUBLIC MEANS OF EGRESS TO BE
MAINTAINED THROUGHOUT PROJECT AT ALL TIMES.
4. CONTRACTOR TO PROVIDE PROTECTIVE MASKS TO BE
WORN BY ALL CONSTRUCTION STAFF IN ALL COMMON
AREAS WITHIN THE HOSPITAL.
5. A MINIMUM OF 3 WEEKS NOTICE ( 21 CALENDAR DAYS)
IS REQUIRED FOR ANY UTILITY SHUTDOWN OR MAJOR
INTERRUPTION . CONTRACTOR TO COORDINATE
APPROVAL WITH COR.
1' - 0"
1' - 0"
8' - 0"
4" PAINTED
PARKING
STALL LINE
GOVERNMENT
EV SYMBOL
WHEEL STOP
CL CL
8' - 0"
WALL OR CURB
EV CHARGER SEE ELECTRICAL
DRAWINGS
EQ EQ
BOLLARD
ONE SIDED STUDP2
0' - 0 5/8"
20 GA. TRACK &
STUDS 24" O.C.
ACOUSTIC SEALANT
ACOUSTIC
SEALANT
STUD
GYPSUM
WALLBOARD-
PAINT WALL TO
MATCH EXISTING
3 5/8" METAL STUDS @ 24" O.C. WITH 5/8"
TYPE "X" GWB
ON ONE SIDE EXTEND TO UNDERSIDE OF
STRUCTURE
SOUND ATTENUATION
BATT INSULATION
STRUCTURE ABOVE
FINISH CEILING
FINISH FLOOR
RUBBER BASE TO
MATCH EXISTING
A101
Office
Off.
2A
10"
9.01
S
T A T E
OF O
H
IO
R E G
IST ERED A RC
HI
T
E C T
MARK
C.
WISEMAN
13215
Mark C. Wiseman, License #13215 Expiration Date 12/31/2021
P ro je ct
N o.
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
E
D
C
B
A
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
F
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
32 4 5 6 7 8 9 10
/3
/2
:4
:2 P
M P ro je c t
N u m b e r
SIGNAGE SITE PLANS AND
DETAILS
11/06/2020 MW VP
INSTALL CAR CHARGING STATIONS
A101
539-21-203
CINCINNATI AND FT THOMAS
N/A
SCALE | 1" = 50'-0"
SITE SIGNAGE CINCINNATI26 SCALE | 1" = 50'-0"
FT. THOMAS SITE SIGNAGE16
GENERAL NOTESKEYNOTES#
9.01 ELECTRICAL CHASE - GYPSUM WALLBOARD CHASE TO BE WALL
TYPE P2, SEE ELECTRICAL DRAWINGS FOR CONDUIT PATH.
10.01 TYPE 1 NON-ILLUMINATED SINGLE POST PARKING ELECTRIC
VEHICLE SIGNAGE PROVIDED AT EACH PARKING SPOT. PROVIDE
TWO SIGNAGE PER LEVEL 2 CHARGER.
10.02 TYPE 2 NON-ILLUMINATED WALL MOUNTED PARKING ELECTRIC
VEHICLE SIGNAGE. PROVIDE AT EACH PARKING SPOT PER LEVEL 2
CHARGER
10.03 TYPE 2 NON-ILLLUMINATED WALL MOUNTED PARKING ELECTRIC
VEHICLE SIGNAGE. GOVERNMENT PARKING ONLY
26.01 LEVEL 2 CAR CHARGER. SEE ELECTRICAL DRAWINGS.
26.02 DEDUCT ALTERNATE-DC FAST CHARGER. SEE ELECTRICAL
DRAWINGS.
32.01 CONCRETE FILLED BOLLARD AT EACH CAR CHARGER
32.02 PROVIDE WHEEL STOP AT EACH PARKING SPOT
SCALE | 1/2" = 1'-0"
TYPE 2 SIGNAGE2
SCALE | 1/2" = 1'-0"
TYPE 1 SIGNAGE1
NORTHNORTH
SCALE | 1/8" = 1'-0"
PARKING STALL LAYOUT3
SCALE | 1 1/2" = 1'-0"
WALL TYPE
SCALE | 1/16" = 1'-0"
BUILDING 3 - BASEMENT PLAN4
SCALE | 1/8" = 1'-0"
ENLARGED PLAN5
# DESCRIPTION DATE
1 SCHEMATIC DESIGN 5/29/2020
2 REVISED SCHEMATIC DESIGN 6/23/2020
3 DESIGN DEVELOPMENT (DD1) 8/18/2020
4 DESIGN DEVELOPMENT (DD2) 10/09/2020
5 CONSTRUCTION DOCUMENTS 11/06/2020
6 ADDENDUM #1 03/04/2021
JASON REEVES
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
BUILDING 3
26.01
10.03
26.01
10.03
A101
3' -0
DETAIL NOTES
15"DIA
GENERAL NOTES
6"
1 4" DIA GALVANIZED STEEL BOLLARD, CONCRETE FILLED
WITH DOMED CONCRETE TOP. PRIMED AND PAINTED,
COLOR SELECTED BY COR.
2 COMPACTED GRAVEL SUBGRADE.
3 CONCRETE FOUNDATION WITH SLIGHTLY DOMED TOP.
4 EXISTING FINISHED GRADE.
5 1/4"W x 1/4"D REVEAL WITH FLEXIBLE CONCRETE
SEALER TO PREVENT WATER INFILTRATION.
A INCLUDE TWO ADDITIONAL INSTALLED BOLLARDS IN
BASE BID. LOCATION TO BE DETERMINED BY COR.
4"DIA
ELECTRICAL SYMBOLS
EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.
DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS WHERE
REQUIRED.
ELECTRICAL CONNECTION.
DISCONNECT SWITCH.
ELECTRICAL PANEL OR SWITCHBOARD PER DRAWINGS.
PULL BOX.P/B
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SWITCH
BLDG - BUILDING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTWN - BETWEEN
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - CIRCUIT
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
COR - CONTRACTING OFFICER'S REPRESENTATIVE
CORR - CORRIDOR
CTR - CENTER
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DIV - DIVISION
DN - DOWN
DWG - DRAWING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EX - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
GC - GENERAL (DIV 01)
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT
FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC (DIVISION 23)
HP - HORSE POWER OR HIGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
IN - INCHES
KEC - KITCHEN EQUIPMENT
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
P - PEDESTAL MOUNTED CHARGER
PC - PLUMBING (DIVISION 22)
PLBG - PLUMBING
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH-IN
S - SURFACE MOUNTED/WALL SURFACE MOUNTED CHARGER
SC - SECURITY (DIV 28)
SCH - SCHEDULE
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY
TC - TECHNOLOGY
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W/ - WITH
W/O - WITHOUT
WP - WEATHERPROOF
ZVC - ZONE VALVE CABINET
E2
B
E2
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
DETAIL: B = DETAIL DESIGNATION
E2 = SHEET WHERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
E2 = SHEET WHERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES
CIRCUIT(S).
X - 1,2
T2 1 ELEVATION: 1 = ELEVATION DESIGNATION
T2 = SHEET WHERE ELEVATION IS LOCATED
P
PEDESTAL/PAD MOUNTED CHARGING STATION.
S
WALL SURFACE MOUNTED CHARGING STATION.
1 3000 LB. CONCRETE ENCASEMENT. 3" MIN. FROM
OUTSIDE OF DUCT.
2 SCHEDULE 40 PVC DUCT. SIZE AS NOTED ON PLANS.
3 RED DYE, RED DUST OR YELLOW MARKER TAPE ON
COMPACTED FILL.
DETAIL NOTES
1' -6
TAMPED
BACKFILL
FINISH GRADE
2' -6
C
O V
E R .
1 3000 LB. CONCRETE.
2 CHEDULE 40 PVC DUCT. SIZE AS NOTED ON PLANS.
3 MIN. 3" SPACING BETWEEN CONDUITS AND MIN. 3"
ENCASEMENT (TYPICAL). PROVIDE CONDUIT SPACERS
6'-0" O.C.
4 RED DYE, RED DUST OR YELLOW MARKER TAPE ON
COMPACTED FILL.
DETAIL NOTES
1' -6
TAMPED
BACKFILL
FINISH GRADE
2' -3
C
O V
E R
1 3000 LB. CONCRETE.
2 CHEDULE 40 PVC DUCT. SIZE AS NOTED ON PLANS.
3 MIN. 3" SPACING BETWEEN CONDUITS AND MIN. 3"
ENCASEMENT (TYPICAL). PROVIDE CONDUIT SPACERS
6'-0" O.C.
4 RED DYE, RED DUST OR YELLOW MARKER TAPE ON
COMPACTED FILL.
DETAIL NOTES
2' -3
C
O V
E R
1' -6
TAMPED
BACKFILL
FINISH GRADE
1 3000 LB. CONCRETE.
2 CHEDULE 40 PVC DUCT. SIZE AS NOTED ON PLANS.
3 MIN. 3" SPACING BETWEEN CONDUITS AND MIN. 3"
ENCASEMENT (TYPICAL). PROVIDE CONDUIT SPACERS
6'-0" O.C.
4 RED DYE, RED DUST OR YELLOW MARKER TAPE ON
COMPACTED FILL.
DETAIL NOTES
FINISH GRADE
TAMPED
BACKFILL
2' -3
C
O V
E R
1' -6
1 5" CONCRETE WALLS, FOUR SIDES.
2 1/2" DIA. REINFORCED STEEL-10"CC BOTH WAYS.
3 1/4" CHECKERED STEEL PLATE COVER.
4 2"X2"X1/4" L WELDED TO PLATE. TWO SIDES ONLY 1/4"
CLEARANCE FIT.
5 UNDERGROUND DUCT-TURN UP @ 45 DEG.
6 CONDUCTORS-LOOP/PULL OR SPLICE.
7 CROSSWISE FOR SUPPORT.
DETAIL NOTES
5"
.3'-10" SQUARE
2C
DIA.
2' -4
6C DIA.
2' -6
1 REFER TO MANUFACTURER DETAILS FOR PEDESTAL
INFORMATION.
2 ANCHOR BOLTS BY EQUIPMENT SUPPLIER.
3 CHAMFERED EDGE.
4 FINISH GRADE, COMPACT TO 95%.
5 SIX #4 REINFORCING BARS VERTICALLY ON #3 STIRRUPS
AT 18" O.C.
6 PVC CONDUIT, SCHEDULE 40.
7 RIGID GALVANIZED STEEL CONDUIT.
8 BASE PLATE, PAD, ETC BY PEDESTAL MANUFACTURER.
REFER TO MANUFACTURER INSTALLATION INSTRUCTIONS.
DETAIL NOTES
18" SQ.
4' -0
2' -6
" 1' -6
2"
A EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.
EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED
EQUIPMENT GROUNDING CONDUCTOR.
B FOR EXISTING EQUIPMENT, SUCH AS WIRING DEVICES, CONDUITS, ETC., SHOWN ON
PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK
PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT
THE OVERCURRENT PROTECTIVE DEVICE AND REMOVE WITING COMPLETELY FROM
THE ABANDONED CONDUITS.
GENERAL NOTES
P ro je ct
N o.
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
E
D
C
B
A
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
F
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
32 4 5 6 7 8 9 10
CONSTRUCTION
DOCUMENTS
JASON REEVES
539-21-203
N/A
CINCINNATI AND FT THOMAS
FULLY SPRINKLERED
/3
/2
:4 :5
P
M P ro je c t
N u m b e r
INDEX LEGEND AND SCHEDULES
11/06/2020 MSG NES
INSTALL CAR CHARGING STATIONS
E001
INDEX
SHEET NUMBER SHEET NAME
E001 INDEX LEGEND AND SCHEDULES
E101 SITE PLAN - CINCINNATI CAMPUS
E102 SITE PLAN - FT THOMAS CAMPUS
E103 ENLARGED FLOOR PLANS
E201 ELECTRIC SINGLE LINE DIAGRAMS
70 kVA 70 kVA (194 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load: 28.00 kVA 21.00 kVA 21.00 kVA
41 Space -- -- 0 kVA 0 kVA -- -- Space 42
39 Space -- -- 0 kVA 0 kVA -- -- Space 40
37 Space -- -- 0 kVA 0 kVA -- -- Space 38
35 Space -- -- 0 kVA 0 kVA -- -- Space 36
33 Space -- -- 0 kVA 0 kVA -- -- Space 34
31 Space -- -- 0 kVA 0 kVA -- -- Space 32
29 Space -- -- 0 kVA 0 kVA -- -- Space 30
27 Space -- -- 0 kVA 0 kVA -- -- Space 28
25 Space -- -- 0 kVA 0 kVA -- -- Space 26
23 Space -- -- 0 kVA 0 kVA -- -- Space 24
21 Space -- -- 0 kVA 0 kVA -- -- Space 22
19 -- -- -- 4 kVA 4 kVA -- -- -- 20
17 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 18
15 -- -- -- 4 kVA 4 kVA -- -- -- 16
13 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 14
11 -- -- -- 4 kVA 4 kVA -- -- -- 12
9 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 10
7 -- -- -- 4 kVA 4 kVA -- -- -- 8
5 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 6
3 -- -- -- 4 kVA 4 kVA -- -- -- 4
1 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W 1 A Mains Rating: 400 A Supply From: Enclosure: Type 1 Mains Type: M.L.O.
Location: Mounting: Surface A.I.C. Rating: 42,000
Panel: L2
112 kVA 112 kVA (311 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load: 42.00 kVA 35.00 kVA 35.00 kVA
41 Space -- -- 0 kVA 0 kVA -- -- Space 42
39 Space -- -- 0 kVA 0 kVA -- -- Space 40
37 Space -- -- 0 kVA 0 kVA -- -- Space 38
35 -- -- -- 0 kVA 0 kVA -- -- -- 36
33 Spare 40 A 2 0 kVA 0 kVA 2 40 A Spare 34
31 -- -- -- 4 kVA 4 kVA -- -- -- 32
29 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 30
27 -- -- -- 4 kVA 4 kVA -- -- -- 28
25 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 26
23 -- -- -- 4 kVA 4 kVA -- -- -- 24
21 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 22
19 -- -- -- 4 kVA 4 kVA -- -- -- 20
17 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 18
15 -- -- -- 4 kVA 4 kVA -- -- -- 16
13 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 14
11 -- -- -- 4 kVA 4 kVA -- -- -- 12
9 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 10
7 -- -- -- 4 kVA 4 kVA -- -- -- 8
5 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 6
3 -- -- -- 4 kVA 4 kVA -- -- -- 4
1 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W 1 A Mains Rating: 400 A Supply From: Enclosure: Type 3R Mains Type: M.L.O.
Location: Mounting: Surface A.I.C. Rating: 10,000
Panel: L2A
63 kVA 63 kVA (175 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load: 24.50 kVA 21.00 kVA 17.50 kVA
29 Space -- -- 0 kVA 0 kVA -- -- Space 30
27 Space -- -- 0 kVA 0 kVA -- -- Space 28
25 Space -- -- 0 kVA 0 kVA -- -- Space 26
23 Space -- -- 0 kVA 0 kVA -- -- Space 24
21 Space -- -- 0 kVA 0 kVA -- -- Space 22
19 -- -- -- 4 kVA 0 kVA -- -- -- 20
17 L2 CHARGER 40 A 2 4 kVA 0 kVA 2 40 A Spare 18
15 -- -- -- 4 kVA 4 kVA -- -- -- 16
13 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 14
11 -- -- -- 4 kVA 4 kVA -- -- -- 12
9 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 10
7 -- -- -- 4 kVA 4 kVA -- -- -- 8
5 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 6
3 -- -- -- 4 kVA 4 kVA -- -- -- 4
1 L2 CHARGER 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W MCB Rating: 225 A Mains Rating: 400 A Supply From: Enclosure: Type 1 Mains Type: M.L.O.
Location: Mounting: Surface A.I.C. Rating: 22,000
Panel: GP6
50 kVA 50 kVA (60 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load: 16.67 kVA 16.67 kVA 16.67 kVA
29 Space -- -- 0 kVA 0 kVA -- -- Space 30
27 Space -- -- 0 kVA 0 kVA -- -- Space 28
25 Space -- -- 0 kVA 0 kVA -- -- Space 26
23 Space -- -- 0 kVA 0 kVA -- -- Space 24
21 Space -- -- 0 kVA 0 kVA -- -- Space 22
19 Space -- -- 0 kVA 0 kVA -- -- Space 20
17 Space -- -- 0 kVA 0 kVA -- -- Space 18
15 Space -- -- 0 kVA 0 kVA -- -- Space 16
13 Space -- -- 0 kVA 0 kVA -- -- Space 14
11 Space -- -- 0 kVA 0 kVA -- -- Space 12
9 Space -- -- 0 kVA 0 kVA -- -- Space 10
7 Space -- -- 0 kVA 0 kVA -- -- Space 8
5 -- -- -- 17 kVA 0 kVA -- -- -- 6
3 -- -- -- 17 kVA 0 kVA -- -- -- 4
1 DC FAST CHARGER 80 A 3 17 kVA 0 kVA 3 80 A FUTURE 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 480/277 Wye-3PH-4W 1 A Mains Rating: 200 A Supply From: Enclosure: Type 3R Mains Type: M.L.O.
Location: Mounting: Surface A.I.C. Rating: 10,000
Panel: DC FAST
SCALE: NONE
CONCRETE ENCASED UNDERGROUND DUCT - 1
SCALE: NONE
UNDERGROUND DUCTS - 2
SCALE: NONE
UNDERGROUND DUCTS - 3
SCALE: NONE
UNDERGROUND DUCTS - 4
SCALE: NONE
LARGE IN-GROUND PULLBOX
21 kVA 21 kVA (58 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: * PROVIDE NEW BREAKER
Total Load: 3.50 kVA 7.00 kVA 10.50 kVA
41 -- -- -- 4 kVA 4 kVA -- -- -- 42
39 L2 CHARGER* 40 A 2 4 kVA 4 kVA 2 40 A L2 CHARGER* 40
37 EXIST 20 A 1 0 kVA 4 kVA -- -- -- 38
35 EXIST 20 A 1 0 kVA 4 kVA 2 40 A L2 CHARGER* 36
33 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 34
31 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 32
29 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 30
27 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 28
25 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 26
23 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 24
21 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 22
19 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 20
17 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 18
15 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 16
13 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 14
11 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 12
9 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 10
7 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 8
5 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 6
3 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 4
1 EXIST 20 A 1 0 kVA 0 kVA 1 20 A EXIST 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W 1 A Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: M.L.O.
Location: Mounting: Surface A.I.C. Rating: 10,000
Panel: PB (EXIST)
BUILDING 1 (BASEMENT)
US-1D
BUILDING 3 (BASEMENT)
BUILDING 3 MAIN DIST. BOARD
GARAGE ELEC ROOM (LEVEL 1)
MDP
BUILDING 117
MS (BUILDING 64 LOWER LEVEL)
BUILDING 117
MS (BUILDING 64 LOWER LEVEL)
SCALE: NONE
L2 CHARGER BASE
SCALE: NONE
PROTECTIVE BOLLARD
# DESCRIPTION DATE
1 SCHEMATIC DESIGN 5/29/2020
2 REVISED SCHEMATIC DESIGN 6/23/2020
3 DESIGN DEVELOPMENT (DD1) 8/18/2020
4 DESIGN DEVELOPMENT (DD1) 10/09/2020
5 CONSTRUCTION DOCUMENTS 11/06/2020
6 ADDENDUM #1 3/04/2021
D N
D N
O ff.
B
O ff.
B
O ff.
B
O ff.
B
O ff.
B
O c c
T h e ra p y
B
K it.
M u lti-P u rp o s e
B
O ff.
B
O ff.
B
G ro u p R m
B
G ro u p
R o o m B
132B
A d m . A s s t.
B
O ffic e B
125A
S to r.
B
127A
S to r.
B
137A S to r.
B 137B
A u d io lo g y
C lin ic B
T lt.
B
T e le
B
124A
R N
In ta k e
B
O x y g e n
B
P h y s ic a l
T h e ra p y /O c c u p a tio n a l
T h e ra p y
B
S p e e c h
P a th o lo g y
B
S p e e c h
P a th o lo g y
B
E le c tric a l
C lo s e t
B
N a v e
B
C h a n c e l B
163A
C h a p . C lin
P a s to ra l
E d u c a tio n
B 163G
C h a p la in A s s is ta n t
B 163H
C h ie f B
163J C h a p la in B
163K
C o rrid o r
C *1*8
C o rrid o r
C *1*6
S ta ir 3 S
*1*3
S ig
B 124B
S to ra g e
B 132A
O ffic e B
125B
C o n fe re n c e
B 163D
B le s s e d
S a c ra m e n t
B 163E
C lo s e t
B 163F
C le ric a l
D N
U P
D N
U P
2S
P S
P
S
S
S
S S
US-1D
MDP
PARKING
GARAGE
BUILDING 2
BUILDING 1
BUILDING
BUILDING
L2
GP6
BUILDING 2
BUILDING 3
TRAILER
TRAILER
T R
A
IL
E R
FISHER
HOUSE
E101
E101
E101
PB
PB - 36,38
PB - 39,41 PB - 40,42EX
L2 - 1,3
L2 - 2,4
L2 - 5,7
L2 - 6,8
L2 - 10,12
L2 - 9,11
L2 - 14,16
L2 - 13,15
GP6 - 9,11
GP6 - 6,8
GP6 - 5,7
GP6 - 2,4
GP6 - 1,3
P GP6 - 13,15
GP6 - 10,12
P GP6 - 17,19
GP6 - 14,16
1 7
E103
E101
E101
BUILDING
BUILDING
T R
A
IL
E R
PL2 - 17,19
L2 - 18,206
DUAL L2 CHARGER
(SURFACE)
BOLLARD
DUAL L2 CHARGER
(SURFACE)
BOLLARD
DUAL L2 CHARGER
(SURFACE)
BOLLARD
DUAL L2 CHARGER
(PEDESTAL)
BOLLARD
DUAL L2 CHARGER SURFACE MOUNT
(TYPICAL)
BOLLARD
DUAL L2 CHARGER
PEDESTAL MOUNT
(TYPICAL)
DUAL L2 CHARGER (SURFACE)
L2 CHARGER
(SURFACE)
BOLLARD
BOLLARD
GP6
MDP
GP
ATSEM
GPEMFACP
EX
EX
EX
EXEX
P
S
S
S
P
9 5
P ro je ct
N o.
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
E
D
C
B
A
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
F
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
32 4 5 6 7 8 9 10
CONSTRUCTION
DOCUMENTS
JASON REEVES
539-21-203
N/A
CINCINNATI AND FT THOMAS
FULLY SPRINKLERED
/3
/2
:4 :1
P
M P ro je c t
N u m b e r
SITE PLAN - CINCINNATI CAMPUS
11/06/2020 MSG NES
INSTALL CAR CHARGING STATIONS
E101
SCALE: 1" = 50'-0"
SITE PLAN - CINCINNATI
NOTES
1 NEW DUAL LEVEL 2 CHARGER.
2 NEW SINGLE LEVEL 2 CHARGER.
3 PROVIDE ALL REQUIRED FLOOR PENETRATIONS FOR NEW CAR
CHARGER CIRCUITS TO RISE FROM FLOOR BELOW.
4 APPROXIMATE LOCATION OF NEW PANELBOARD. FIELD VERIFY EXACT
LOCATION WITH ENGINEER.
5 PROVIDE PROTECTIVE BOLLARD. REFER TO DETAIL SHEET E001.
6 RUN 2-#8, 1-#10 GRD. IN 1" C. TO EACH CAR CHARGING STATION. DUAL
STATIONS SHALL SHARE SINGLE CONDUIT. CIRCUIT TO 40A/2P
BREAKER(S) IN PANEL INDICATED.
7 RUN 2-#8, 1-#10 GRD. IN 1" C. TO EACH CAR CHARGING STATION. DUAL
STATIONS SHALL SHARE SINGLE CONDUIT. CIRCUIT TO NEW PANEL
GP6.
8 RUN 2-#8, 1-#10 GRD. IN 1" C. TO EACH CAR CHARGING STATION. DUAL
STATIONS SHALL SHARE SINGLE CONDUIT. CIRCUIT TO NEW PANEL L2.
9 PROVIDE TRENCHING/SAW CUTTING AND PATCHING AS REQUIRED TO
INSTALL CONDUIT(S) SERVING NEW L2 CHARGER(S). RISE AT BUILDING
AS SHOWN.
10 REMOVE EXISTING LEVEL 2 CHARGER INCLUDING CIRCUIRTY BACK TO
SOURCE.
11 NEW CIRCUITS TO RISE TO ELECTRIC ROOM ABOVE. NEW CIRCUITS TO
FOLLOW PATH OF EXISTING CAR CHARGER CIRCUITS TO BE REMOVED
TO NEW CHARGER LOCATION.
12 EXPOSED CONDUIT SHALL BE RUN IN IMC FOR PHYSICAL PROTECTION
OF CIRCUITS.
NSCALE: NONE
BUILDING 1 SITE PHOTO
SCALE: NONE
GARAGE SITE PHOTO
SCALE: NONE
BUILDING 3 SITE PHOTO
SCALE: 1/8" = 1'-0"
GARAGE ELECTRIC ROOM
SCALE: 1/16" = 1'-0"
BUILDING 1 ENLARGED
# DESCRIPTION DATE
1 SCHEMATIC DESIGN 5/29/2020
2 REVISED SCHEMATIC DESIGN 6/23/2020
3 DESIGN DEVELOPMENT (DD1) 8/18/2020
4 DESIGN DEVELOPMENT (DD1) 10/09/2020
6 ADDENDUM #1 3/04/2021
P K
P K
P K
P K
P K
SOUTH FT THOMAS AVENUE
COCHRAN AVENUE
D R
IN
K
IN
G
F O U N T A
IN
EMERGENCY
GENERATOR
ROOM
MAIN
ELECTRIC
ROOM
MAIN
SWITCHBOARD
"MS"
EMERGENCY SWITCHBOARD "MEDP"
ATS-1
EDP-E
EDP-E1
EDP-E2
EDP-L
ATS-2
EDP-L
EDP-C
ATS-3
EDP-C
ECB.1
EL1.4
EX
EX
EX
EXEX
EX
EX
EX
EX
EDP-E2
ATS-EQ2
EX
EX
EX
EX
P
P
P
P
P
P
P
P
2P
BUILDING
BUILDING 117
TRAILER
FUTURE GEOTHERMAL
WELL FIELD
PB
L2A
DC FAST
E001
E001
E001
E102
E102
L2A - 1,3
L2A - 2,4 L2A - 5,7
L2A - 6,8
L2A - 9,11
L2A - 10,12 L2A - 13,15 L2A - 14,16
L2A - 17,19
L2A - 18,20 L2A - 21,23
L2A - 22,24
L2A - 25,27
L2A - 26,28
L2A - 29,31
L2A - 30,32
E102
E102
(TYPICAL OF 8)
(TYP)
(TYP)
(TYP)
DC FAST CHARGER
BOLLARD
BOLLARD
PANEL L2A
STRUCTURAL SUPPORT
P
P
P
P
P
P
P
P
L2A
P ro je ct
N o.
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
E
D
C
B
A
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
F
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
32 4 5 6 7 8 9 10
CONSTRUCTION
DOCUMENTS
JASON REEVES
539-21-203
N/A
CINCINNATI AND FT THOMAS
FULLY SPRINKLERED
/3
/2
:4 :1
P
M P ro je c t
N u m b e r
SITE PLAN - FT THOMAS CAMPUS
11/06/2020 MSG NES
INSTALL CAR CHARGING STATIONS
E102
SCALE: 1" = 30'-0"
SITE PLAN - FT THOMAS
N
NOTES
1 LOCATION OF NEW DUAL LEVEL 2 CHARGER.
2 LOCATION OF NEW FREESTANDING 50KW DC FAST CHARGER. PROVIDE
CONCRETE BASE PER MANUFACTURER REQUIREMENTS.
3 LOCATION OF NEW 208V TO 480Y/277V TRANSFORMER AND NEMA 1
BREAKER SERVING DC FAST CHARGER.
4 APPROXIMATE LOCATION OF NEW PANEL.
5 RUN 2-#8, 1-#10 GRD. IN 1" C. TO EACH CAR CHARGING STATION. DUAL
STATIONS SHALL SHARE SINGLE CONDUIT. REFER TO DUCTBANK
DETAILS SHEET E000.
6 RUN 3-#3, 1-#8 GRD. IN 1.25" C. TO TO NEW DC FAST. CHARGER
STATION FROM NEW PANEL "DC FAST"
7 SAWCUT AND PATCH EXISTING CONCRETE/ASPHALT AS REQUIRED
FOR NEW DUCTBANK INSTALLATION. PATCH TO MATCH EXISTING.
8 UNDER DEDUCT ALTERNATE #1 WORK ASSOCIATED WITH DC FAST
CHARGER TO BE REMOVED FROM PROJECT. THIS INCLUDES THE DC
FAST CHARGER, NEW BREAKER IN THE SWITCHBOARD,
TRANSFORMER, BREAKER ON SECONDARY OF TRANSFORMER,
FEEDER, CONDUIT, DUCTBANK, PANELBOARD AND CONNECTION TO DC
FAST CHARGER.
9 PROVIDE CONCRETE HOUSEKEEPING PAD FOR TRANSFORMER AND
ASSOCIATED BREAKER.
10 PROVIDE PROTECTIVE BOLLARD. REFER TO DETAIL SHEET E001.
11 PROVIDE STRUCTURAL SUPPORT FOR PANELBOARD MOUNTING. TWO
(2) GALVANIZED STEEL SUPPORTS TO GO TO A DEPTH NO LESS THAN
4'-0" IN CONCRETE PIERS.
SCALE: NONE
BUILDING 117 SITE PHOTO
SCALE: 1 1/2" = 1'-0"
LOT SITE PHOTO
SCALE: 1" = 30'-0"
PARTIAL SITE PLAN
SCALE: 1/8" = 1'-0"
BUILDING 64 ELECTRIC ROOM
# DESCRIPTION DATE
1 SCHEMATIC DESIGN 5/29/2020
2 REVISED SCHEMATIC DESIGN 6/23/2020
3 DESIGN DEVELOPMENT (DD1) 8/18/2020
4 DESIGN DEVELOPMENT (DD1) 10/09/2020
DN
Supply Storage
SUB 1
Equip. Room
SUB 2
Medical Records Storage
SUB 4
Stairs
S-SB-1
Electrical
Conference Room
Break Room
1A
Corridor
C*B *2
Elev. Equip.
Vestibule
Lobby
010A
Pipe Basement
1B
Off.
2A
Office
HR Off
3A
HR Off.
HR Off.
HR Off.
Stairs
S*B*2
HR Off.
HR Off.
Corridor
C*B *1
Lobby
Bathroom
10B
HR Office
Clos.
10D
H.A.C.
Stairs
S*B*1
BASEMENT PLANSUB-BASEMENT PLAN
UP
UP
UP
UP
UP
UP
UP
UP
UPUP
Fire Alarm Control B019A
UP
Transformer Room A023
PP1LPB
XFMR
MCCD
CDP
LSDP
MCC2
US-1PUS-1X
LC
DISTRIBUTION
SWITCHGEAR
DISTRIBUTION
SWITCHGEAR
MV SWGR
PS1
TGDE
ATS-14
ATS-16
ATS
CDP
B1
GDE
VFD
US-1C
US-1D
HONEYWELL
FACPEF3
PLC
CABINET
JCI
JCI
PB
ATS -
ESWB-F-3
JCI
CAB
METER
FUSE
CABINET
XFMR
KVA
UNIT
SUBSTATION
KVA
UNIT
SUBSTATION
ATS-17
HONEYWELL
PB 1
PB
(ABOVE)
NEW PANEL
L2
P ro je ct
N o.
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
E
D
C
B
A
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
F
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
32 4 5 6 7 8 9 10
CONSTRUCTION
DOCUMENTS
JASON REEVES
539-21-203
N/A
CINCINNATI AND FT THOMAS
FULLY SPRINKLERED
/3
/2
:4 :1
P
M P ro je c t
N u m b e r
ENLARGED FLOOR PLANS
11/06/2020 MSG NES
INSTALL CAR CHARGING STATIONS
E103
SCALE: 1/16" = 1'-0"
BUILDING 3 ENLARGED PLANS
NOTES
1 NEW CHASE TO SUB-BASEMENT LEVEL BELOW.
2 CONDUIT TO BE RUN DOWN INTERIOR WALL AND PENETRATE OUT TO
SERVE LEVEL 2 CHARGING STATION(S).
3 EXPOSED CONDUIT SHALL BE RUN AS IMC FOR PHYSICAL PROTECTION
OF CIRCUITS.
SCALE: 1/8" = 1'-0"
ELECTRIC ROOM A23
# DESCRIPTION DATE
1 SCHEMATIC DESIGN 5/29/2020
2 REVISED SCHEMATIC DESIGN 6/23/2020
3 DESIGN DEVELOPMENT (DD1) 8/18/2020
U.L.H.&P. CO.
12.47KV PRIMARY
1000 KVA DRY- TYPE
PADMOUNTED XFMR.
12.47 KV DELTA TO
208Y/120V. 3PH-4W
Z=5.5% MIN.
EXIST. V.A. OWNED
FEEDER
3000A/3P
I=2776A.
A
/3 P
A
/3 P
DC FAST
208V-3PH
112.5 KVA
480Y/277V
3PH-4W
200A
D C
F A
S T
208Y/120V-3PH-4W
/3
A
GP6
PAD-MOUNT TRANSFORMER "TPG"
SWBD
METERING
TVSS
40HP
ELEV
GP GP2
40HP
ELEV
GP1 GP3
LCP2
LCP3
LCP1
GP5 GPEM2
GPEM
ATSEM
400A/4P
400/3
100KW/125KVA
208Y/120V-3PH-4W
/3
A
/3
A
/3
A
/3
A
/3
A
TVSS
L2A PANEL
L2 CHARGER
(TYP)
L2 CHARGER
(TYP)
DC FAST
CHARGER
3000A, 208Y/120V-3PH-4W
P A
N E
L
SWBD
METERING
2000A
12,470V, 750KVA
208Y/120V
3PH-4W
SWBD
METERING
SPD
3000A, 208Y/120V-3PH-4W
TO PS1
L2 PANEL
L2 CHARGER
(TYP)
A
/3 P
EXISTING MAIN DIST SWBD "MDP" (GARAGE)
EXISTING MAIN DIST SWBD "MS" (FT THOMAS)
EXISTING UNIT SUBSTATION "US-1D" (BUILDING 1)
L.A.
AREA OF WORK
AREA OF WORK
AREA OF WORK
P ro je ct
N o.
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
E
D
C
B
A
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
F
Phase
ARCHITECT/ENGINEER OF RECORDCONSULTANT
32 4 5 6 7 8 9 10
CONSTRUCTION
DOCUMENTS
JASON REEVES
539-21-203
N/A
CINCINNATI AND FT THOMAS
FULLY SPRINKLERED
/3
/2
:4 :2
P
M P ro je c t
N u m b e r
ELECTRIC SINGLE LINE DIAGRAMS
11/06/2020 MSG NES
INSTALL CAR CHARGING STATIONS
E201
NOTES
1 UTILIZE EXISTING 400A/3P BREAKER IN EXISTING UNIT SUBSTATION.
2 3-500 KCMIL, 1-#3 GRD. IN 4" C.
3 UNDER DEDUCT ALTERNATE #1 WORK ASSOCIATED WITH DC FAST
CHARGER TO BE REMOVED FROM PROJECT.
4 REFER TO SITE PLAN FOR CIRCUIT SIZING.
5 PROVIDE NEW 400A/3P BREAKER IN EXISTING DISTRIBUTION PANEL.
6 4-500 KCMIL, 1-#3 GRD. IN 4" C.
7 4-#3/0, 1-#4 GRD. IN 2" C.
8 PROVIDE NEW 400A/3P SWITCH FUSED AT 400A IN EXISTING
DISTRIBUTION PANEL.
# DESCRIPTION DATE
1 SCHEMATIC DESIGN 5/29/2020
2 REVISED SCHEMATIC DESIGN 6/23/2020
3 DESIGN DEVELOPMENT (DD1) 8/18/2020
| G001 |
| A101 |
| 2020-05073 - Sheet - E001 - INDEX LEGEND AND SCHEDULES |
| 2020-05073 - Sheet - E101 - SITE PLAN - CINCINNATI CAMPUS |
| 2020-05073 - Sheet - E102 - SITE PLAN - FT THOMAS CAMPUS |
| 2020-05073 - Sheet - E103 - ENLARGED FLOOR PLANS |
| 2020-05073 - Sheet - E201 - ELECTRIC SINGLE LINE DIAGRAMS |