Attachment 1. B1631 Daikin Condenser Salient Characteristics 08 April 2025.pdf
PDF 124 KB Posted
- Solicitation number
- FA286025Q2025
About this file
This document is a Salient Characteristics Sheet for a Daikin VRV Condenser Replacement project at Building 1631 on Joint Base Andrews, Maryland, scheduled for Fiscal Year 2025. The project requires furnishing and installing a new Daikin condenser (Model: REYQ120PBYD) to replace the existing defective condensing unit, with specific installation requirements including refrigerant recovery, piping disconnection and flushing, equipment removal and replacement, system testing, and warranty documentation. The installation work will be subject to the Service Contract Act wage determination 2015-4281, Revision Number 32, and the work site is located at 1631 Brookley Ave., JBA, MD 20762. Base access must be coordinated with Joseph Osborne or SSgt Kimbridge Gaymon after contract award, and contractors will need to follow detailed technical specifications for equipment replacement and system commissioning.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics Sheet Building 1631 VRV Daikin Condenser Replacement and Flush - FY25
08 April 2025
Describe the requested item(s) in salient terms:
Furnish and install new Daikin condenser Model: REYQ120PBYD and remove and dispose of defective condensing unit. Installation work will be subject to the most recent wage determination under SCA WD: 2015-4281, Revision Number 32.
Current Chiller Description:
Manufacturer: Daikin Model: REYQ120PBYD Serial Numbers: A000195
Essential Characteristics for New Condensing Unit Replacement:
Manufacturer: Daikin Model Number: REYQ120PBYD.
Specific Installation Requirements:
• Power off and lock-out/tag-out Equip
• Recover Refrigerant following local, state, federal, and EPA regulations
• Remove and dispose defective condensing unit (1 each)
• Disconnect piping (18 Fan Coil Units)
• Using RX-11, flush piping and coils
• Purge coils and lines
• Provide rigging, transportation, and storage for new equipment
• Furnish and install new condensing unit matching the current unit’s manufacturer and model Manufacturer: Daikin; Model Number: REYQ120PBYD.
• Leak check circuit with dry nitrogen
• Pull a vacuum to min 500 micron
• Perform standing rise test
• Recharge to factory design (NTE 125lbs.)
• Re-apply insulation
• Remove lock-out/tag-out
• Restore power to equipment
• Perform operational test on system
• Provide warranty documentation to government representative
Delivery and Installation Address:
Dorm Residence: 1631 Brookley Ave. JBA, MD 20762
BASE ACCESS: Please contact Joseph Osborne (joseph.osborne.6@us.af.mil) or SSgt Kimbridge Gaymon (kimbridge.gaymon@us.af.mil), telephone number 301-981-7787 to coordinate forms required for base access after award.
File details come from the government source that posted it. Updated .