Attachment 1 - AE Drawings.pdf
PDF 41 MB Posted
- Solicitation number
- 36C24825R0035
About this file
This file contains architectural and engineering drawings for a renovation project at the Bruce W. Carter VA Medical Center in Miami, FL. The drawings detail plans to renovate the Preventative Maintenance Shop and replace an aluminum canopy.
The drawings include detailed specifications for demolition, new construction, and modifications including: removal of an existing aluminum canopy and installation of a new 5,274 SF canopy structure; demolition of an existing 8'x8' equipment lift and installation of a new 3,000 lb capacity equipment lift with rail; removal and replacement of stainless steel sink and emergency shower/eyewash station; installation of new LED lighting, adjustable fans, and electrical systems; new chain link fencing with gates; pressure washing and painting of exterior surfaces; and various mechanical, electrical and plumbing modifications. The drawings provide comprehensive architectural, structural, civil, plumbing and electrical details including floor plans, elevations, sections, schedules and specifications necessary for construction. The project includes connections to existing building systems including sanitary waste, storm drainage, electrical and lighting.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXTERIOR ELEVATION
INTERIOR ELEVATION
SECTION/DETAIL NUMBER
DRAWING NUMBER
EQUIPMENT TAG
COLUMN GRID
NOTE
WINDOW OPENING
DOOR OPENING
ROOM NAME
ROOM NUMBER
WALL TYPE
CEILING HEIGHT
FINISH DESIGNATION
X
10'-8"
X
X
XX.X-X
XX
X
1/A101
X
A101
P-1X
TOILET ACCESSORY TAGX SIGNAGE TAG
A101
SIM
X
AREA OF
WORK
N W
T
H A
V E
N W
T
H A
V E
NW 16TH ST.
NW 17TH ST.
NW 19TH ST.
MIAMI VA
MEDICAL
CENTER
BLDG. 1
BLDG. 7
BLDG. 10
BLDG. 2
BLDG. 40
BLDG. 5
BLDG. 44
BLDG. 68
FISCHER
HOUSE
BLDG. 70
WATER
TOWER
S E Y B O
LD
C
A N
A L
BLDG. 8&9
S T A
T E
OF FLO
R
I D A
R E G
IS
TERED ARC
H
IT
E C T
J A S
ON
H. RO
S S
AR101907
VA Project No.
RDC/JPA Project No.
Bruce W. Carter VA Medical Center
ABOVE GROUP, INC.
305 EAST DRIVE, SUITE H
MELBOURNE, FL. 32904
321.345.9026 P
ARCHITECTURE PLANNING INTERIOR DESIGN
524 FERNWOOD AVENUE
ALTAMONTE SPRINGS, FLORIDA 32701
407.830.6522 P
3131 NEWMARK DRIVE, SUITE 200
MIAMISBURG, OHIO 45342
937.461.3290 P
RDC / JPA ARCHITECTURE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PENNONI ASSOCIATES, INC.
5755 RIO VISTA DR.
CLEARWATER, FL. 33760
727-536-8772
MECHANICAL | ELECTRICAL | PLUMBING
STRUCTURAL | CIVIL
10/13/2023Design Development Submittal50%
01/11/2024Construction Documents Submittal65%
/2
/2
:1
:4
P M
Renovate Preventative Maintenance Shop and Replace
Aluminum Canopy
01/26/2024
COVER SHEET
GI001
BRJR
546-22-106
MIAMI, FL
Renovate Preventative Maintenance Shop and Replace Aluminum Canopy 1201 NW 16th Street Miami, Florida 33125 PROJECT #: 546-22-106
Apolinar Vargas
100% Design Submittal 23082.00
GENERAL
GI001 COVER SHEET
GENERAL CONSTRUCTION NOTES
* PLEASE NOTE THAT THE TERM PROJECT ENGINEER REFERS TO THE
CONTRACTING OFFICER'S REPRESENTATIVE (C.O.R.).
1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE,
INTERNATIONAL BUILDING CODE, AND OTHER COES AS IDENTIFIED IN VHA
PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE
ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERAN AFFAIRS,
TECHNICAL INFORMATION LIBRRARY WEBSITE.
2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS) AND
DEPARTMENT OF VETERANS AFFAIRS BARRIER FREE DESIGN GUIDE PG-18-13
WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS AFFAIRS
TECHNICAL INFORMATION LIBRARY WEBSITE.
3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT
EXISTING CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED
WITH THE CONTRACTING OFFICER'S REPRESENTATIVE.
4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH
ADJACENT EXISTING SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT
ARE DAMAGED DURING THE COURSE OF DEMOLITION OR NEW WORK.
5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF
NEW WORK, CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO
REMAIN OR PROVIDE NEW CONSTRUCTION TO MATCH EXISTING ADJACENT
SURFACES TO REMAIN.
6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND
DIMENSIONS PRIOR TO ORDERING, FABRICATING OR INSTALLING NEW
MATERIALS.
DRAWING INDEXVICINITY MAP
7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO
BE INSTALLED AS PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE
SPECIAL PROVISIONS TO INSTALL EQUIPMENT THAT IS TOO LARGE TO FIT
THROUGH FINISHED OPENINGS.
8. CONTRACTOR SHALL PROVIDE WOOD BLOCKING AT TOILET ACCESSORIES,
HAND RAILS, BUMPER RAILS, SHELVING, CASEWORK, MOUNTING BRACKETS
AND OTHER WALL MOUNTED ITEMS, AS INDICATED IN THE CONTRACT
DOCUMENTS AND AS RECOMMENDED BY PRODUCT MANUFACTURERS. ALL
WOOD BLOCKING SHALL BE FIRE RETARDANT TREATED.
9. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS
SPECIFICALLY NOTED OTHERWISE. iF NO FINISH IS INDICATED AT A
PARTICULAR SURFACE, CONTRACTOR SHALL PROVIDE FINISH(S) AS
INDICATED AT SIMILAR CONDITIONS.
10. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL
SYSTEMS WHICH COMPLY WITH STATED CODES AND REGULATIONS. WHERE
THE OMISSION OF A PART OR ELEMENT OF A SYSTEM WOULD RESULT IN THE
NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM, CONTRACTOR
SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.
11. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED
WALLS SHALL BE SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF
THE WALL.
12. FIRE PROTECTION CONTRACTOR'S SPRINKLER DESIGN WILL BE SUBJECT TO
AN INDEPENDENT REVIEW BY A CERTIFIED FIRE PROTECTION ENGINEER
RETAINED BY THE OWNER. THE FIRE PROTECTION CONTRACTOR IS
RESPONSIBLE FOR MAKING ANY REQUIRED CHANGES TO THE DESIGN AS
IDENTIFIED BY THE OWNER'S FIRE PROTECTION ENGINEER AS NECESSARY
FOR COMPLIANCE WITH SPECIFIED NFPA REQUIREMENTS.
GRAPHIC SYMBOLS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
CIVIL
CS-021 EXISTING CONDITIONS
CS-051 DEMOLITION PLAN
CS-101 SITE PLAN
CS-171 UTILITY PLAN
CS-601 SITE DETAILS
ARCHITECTURAL
AD101 DEMOLITION PLAN
AE101 ARCHITECTURAL PLAN
AE102 ROOF PLANS
AE201 EXTERIOR ELEVATIONS
AE301 SECTIONS AND DETAILS
AF101 FINISH PLAN
STRUCTURAL
S-001 GENERAL NOTES
S-002 WIND TABLES & SCHEDULES
SB101 FOUNDATION PLAN
SF101 ROOF FRAMING PLAN
SJ101 DETAILS
SJ102 DETAILS
PLUMBING
P-001 PLUMBING NOTES, LEGENDS, & SYMBOLS
P-101 FLOOR PLAN - PLUMBING
P-801 PLUMBING SCHEDULES
ELECTRICAL
E-001 ELECTRICAL LEGENDS & SYMBOLS
E-002 ELECTRICAL GENERAL NOTES
ED101 FLOOR PLAN - ELECTRICAL - DEMO
EL101 FLOOR PLAN - LIGHTING - NEW WORK
EP101 FLOOR PLAN - ELECTRICAL EQUIPMENT - NEW WORK
E-601 ELECTRICAL DIAGRAMS
E-801 ELECTRICAL SCHEDULES
Revisions Date
SOIL BORING "B-3"
ELEVATION 5.03
CONC
STEPS
SANITARY
PUMP STATION
CONC PAD
WITH SIGN
POLES
S-01
S-02
S-04 S-05
S-10
±1
±7 7'
S-01 S-02
PARKING
AREA
CATCH BASIN
CATCH BASIN
CURB INLET
CURB INLET
STORM LINE
DEPTH 2'-4'
END OF
MARKINGS
PUMP STATION VAULT
LID EL 6.84
TOP OF 2" FM (2) EL 5.84
E 3" PVC 90° INV 5.44
BOTTOM EL -0.16
(FULL OF DEBRIS)
4" METAL FIRELINE
TOP 10.97
90° BEND
TOP 11.00
TOP 8.80
90° BEND
TOP 8.99
4" METAL FIRELINE
90° BEND TOP 8.98
90° BEND
TOP 9.66
TOP 9.68
3" PVC
TOP 8.52
3" 45° BEND
TOP 6.87
3"x4" REDUCER
TOP 6.98
3"x4" REDUCER
TOP 7.80
4" WYE
WITH CAP
TOP 7.03
4" WYE
WITH CAP
TOP 7.63
3" WYE WITH CAP
TOP 7.80
3" 45° BEND
TOP 8.50 3" 90° BEND
TOP 8.62
3" 90° BEND
TOP 8.35
3" PVC
TOP 8.87
3" WYE
TOP 8.28
3" WYE
WITH CAP
TOP 8.89
POST INDICATOR
VALVE
CONTROL
PANEL
MULTIPLE CONDUIT
LINES BETWEEN
WALL AND FENCE
SEWER LINE
ON SURFACESEWER LINE
ON SURFACE
FIRE LINE
ON SURFACE
CONC WALK
END OF
MARKINGS (DU)
NOTE:
ADDITIONAL
ALUMINUM POSTS
NOT LOCATED
6.833
2.0X2.0 VAULT
8.618 3" 90
8.499 3" 45
8.280
3" WYE
8.346 3" 90
8.887
3" WYE
8.874
3" PVC
DRAINAGE MANHOLE
RIM EL. 8.56'
SE INV. 3.56' (12" RCP)
W INV. 0.36' (12" CMP)
DRAINAGE MANHOLE
RIM EL. 4.29'
E INV. -0.11' (12" CMP)
S INV. -0.21' (12" RCP)
EMERGENCY CALL BOX
DRAINAGE MANHOLE
RIM EL. 4.19'
N INV. -0.21' (12" RCP)
S INV. -0.41 (12" RCP)
UNDERGROUND ELECTRIC
LINE (TYP)
AC PAD
S-11
GRATE EL 6.41
W 12" CMP INV 2.02
S-13
RIM EL 6.74
BOTTOM EL 0.66
S-12
RIM EL 6.83
BOTTOM EL 2.08
S-12
RIM EL 4.83
S-07
GRATE EL 4.89
NE 12" HDPE INV -0.01
W 24" HDPE INV -0.67
SOIL BORING "B-2A"
ELEVATION 5.52
SOIL BORING "B-2"
ELEVATION 6.5
SOIL BORING "B-3"
ELEVATION 5.03
CONC
STEPS
FENCE
MOTOR
FF EL 9.16
FF EL 9.28 FF EL 9.16
FF EL 8.62 FF EL 8.65 FF EL 8.65
COVERED CONC
AND ASPHALT
COVERED CONC
AND ASPHALT
COVERED
CONC AREA
COVERED
CONC AREA
FENCE
POST
CONC PAD
WITH SIGN
POLES
B U I L D I N G
B U I L D I N G
B U
I L
D I
N G
.2
115.1'
.2
3.1'
.0
2.9'
.3
.0
3.1'
.3
29.1'
7.
7'
21.4'
7.
6'
37.5'
.3
.0
G
AT
E
6' PLASTIC FENCE
6' CHAIN LINK FENCE
6' C
H
AI
N L
IN
K
FE
N
C E
G
AT
E
6' PLASTIC FENCE
COVERED CONC
6' PLASTIC FENCE
CONC STEPS (TYP)
TBM #101
COVERED
CONC AREA
HEAVY EQUIPMENT
AREA
HEAVY EQUIPMENT
AREA
PARKING
AREA
BOLLARD
(TYP)
BOLLARD
(TYP)
R
AM
P
R
AM
P
ST
O
P
BA
R
ST
O
P
BA
R
CONC SIDEWALK
8" CURB
(TYP)
SOIL BORING "B-4"
ELEVATION 4.6
I-BEAM (TYP)
ALUMINUM POST (TYP)
10" RETAINING
WALL
B U I L D I N G
FF EL 6.90
GATE
B U I L D I N G
LOCKED
WALL
COVERED
CONC AREA
COVERED CONC
AND ASPHALT
HYDRAULIC
LIFT
6' PLASTIC FENCE
CONC
EYE WASH
STATION
220.3'
CONC WALK
FF EL 8.60
6.7 66.8
6.9 0 6.7
6.8
6.8
6.8
6.7
6.7
6.7 8 7.5
7.4
7.1
6.9
6.9 9 6.9
6.9
6.5
6.5 65.9
5.9 65.5
5.5 24.9
4.9
4.9
4.9
4.7
4.5
4.4
4.5
4.5
4.5
4.8
4.2
4.1
4.1
4.0
4.0
4.1
4.2
4.4
4.5
4.6 1 4.8 5 5.0
4 5.3 1 5.5
4 5.9
6.0
6.1
12" 12"12"
14"
6.6
5.9
5.3
4.7
4.6
4.5
4.7
4.6
4.8 5.1
12"
12"
5.4
5.4
4.2
4.1
4.9
5.1
5.0
5.2 4.9
4.9
4.8
4.7
4.7
4.7
4.6
4.7
4.8
4.9
5.0
5.1
5.2
4.4
4.4
4.3
4.2
4.3
4.3
4.3
4.4
4.6
4.6
4.6
4.6
4.7
5.1 65.1
5.1
4.9
4.9
4.8
5.0
4.8
5.9
5.4
5.1
5.3
5.4
6.0
5.6
5.0
4.9
5.3
5.4
5.5
5.8
5.6
6.0
6.1
6.4
6.8
6.1
9.2
9.2
9.1
9.1
9.1
9.1
8.0
8.0
8.8
8.3
8.1
6.3
8.9 8.8
8.9 8.4
8.2
8.0
8.5 8.96.55.3
6.1
7.0
6.2 6.5
12"
12" 12"
10"
9"
4.7
5.1
5.4
6.8
6.8
6.9
7.4
7.5
7.4
7.4
7.5
8.8 3 8.8
8.9
8.9
8.9
8.8
8.3
7.2
6.7
6.7
6.7
6.7
6.8
6.8
6.8
6.8
7.1 7.8
6.9
7.0 46.7
6.8
6.6
6.7
6.6
6.3
6.8 5 6.7
6.5
6.8
6.8
6.8
6.8
6.6
6.6
6.3
6.6
6.4
6.4
6.1 3 6.2
6.2
6.2
6.8 26.8
6.7
6.2
6.1
8.6
7.8
8.9
9.2
6.4
6.4
6.9
6.9
6.8
12" 6.5
86.5
6.3
5.9
5.6
5.1 44.6
4.9
4.9
4.5
4.5 6 5.3
4 6.3
6.0
5.9
5.9
5.8
5.8
5.8
5.2
5.2
5.0
4.5 9 4.7
5.8
5.9
5.9
6.0
5.5
4.6
4.6
6.9
8.4
8.4
6.9
7.1
7.3
7.2
7.6
7.8
.2
.43
.59
.2
.47
.60
.56
.4810
.2
.46
.4410
.42
.54
9.8
9.2
8.4
7.9
8.6 9.0
9.1
9.1
6.9 6.9
6.8
7.0
7.5
7.3 67.3
7.2
7.3
.0
9.3 8.4
7.2
7.7
7.4
9.8 9.8
.2
.0
9.8
7.8
.0
9.8 8.0
8.1 88.1
8 9.8
9.8
.23
.27
9.9
.14 10
.16
8.6
8.0
8.5
9.9
12" 12" 10" 10"
12" 10" 12" 10" 8"
12"
8"
12" 16"
GATE
BUILDING
CONC
RAMP
CONC
WALK
HANDICAPPED PARKING
ONLY SIGN (TYP)
TBM #101
FND PK&D STAMPED
"TRAVERSE LB 8126"
N: 530948.19 E: 913634.49
ELEVATION 4.97'
GRASS
6" CONC CURB
(5) 2" PVC
PIPES
TWIN 2X12"
PAVER
WALK(TYP)
6" CONC BOLLARD
CONC PAD
WITH HANDRAIL
6' CHAIN LINK
FENCE
(5) METAL SUPPORT
PARKING STRIPING
(TYP)
6" CONC CURB
6" CONC CURB
6" CONC CURB
6" CONC CURB
STRIPING (TYP)
(WALKWAY)
FF=8.59'
FF=8.60'
CONC
RAMP
ASPHALT
PAVEMENT
CURB CUT
CURB CUT
CURB CUT
CURB CUT
CURB CUT
CURB CUT
9.4
7.3
7.5
5.7
5.9
5.5
5.4
5.4
5.4 3 5.8
5 6.2 6 6.8
9.3
8.9 6 9.2
7.6
7.0
6.8
6.2 6.5
5.9
5.5
6.2
6.1
9.5
9.0
8.6 8.6
8.4
8.1 8.1
8.3
7.8
7.2
6.8
7.0
6.4
6.5
6.1
6.1
6.3
6.1
6.0
5.2
5.8
8.9
7.6
7.4
6.4
6.3
5.7
6.2
6.7
7.2
7.6
8.4
8.2
8.2
7.9
7.5
6.6
7.0
6.2
8.5 26.5
6.5
6.4
6.2
6.3 0 6.6
6.8
8.1
7.9
7.8
7.8
8.1
7.2
7.3
7.3 3 7.3
7.7
7.9
8.4
8.4 4 7.7
8.5
9.0
8.6
8.1
8.1
8.3
8.3
8.2
8.4
8.6 0 8.7
9.0 29.5
9.3
9.3
8.8
9.3 9.1 9.4
9.5
9.4
9.3
9.2
9.5
9.4
9.5
9.6
9.3
9.8
9.6
9.6
9.5
9.5 9.5
9.9
9.2
8.2
9.3
8.8
8.3
8.1
5.1
9.8
9.8
9.7
8.9
7.7
7.8
9.0
7.2
9.7
8.2
8.8
6.9
7.4
9.1
6.0
5.8
6.5 4 7.3
9 7.2
9.3
9.5
7.3
5.8
9.3
8.9
9.0
7.8
8.9
8.0
6.1
6.2
6.5
6.1
7.4
7.0
8.8
8.9
9.5
8.4
7.9
7.9
8.3
8.5
8.6
6.2
5.4
5.0
EXISTING LEGEND
EXISTING MANHOLES
EXISTING COMMUNICATION, UNDERGROUND
EXISTING NATURAL GAS, UNDERGROUND
EXISTING POWER, UNDERGROUND
EXISTING SANITARY SEWER, UNDERGROUND
EXISTING STORM SEWER, UNDERGROUND
EXISTING STORM SEWER, ROOF DRAIN
EXISTING BUILDING OVERHANG
EXISTING WATER, UNDERGROUND
EXISTING CURB
EXISTING EDGE OF PAVEMENT
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
EXISTING EXISTING TREES
EXISTING BOLLARD
BORING LOCATION
EXISTING SIGN
EXISTING UTILITY POLE
EXISTING FENCE
EXISTING BUILDING
EXISTING SPOT ELEVATION100.55
EXISTING STORM SEWER, INLET
EXISTING SANITARY SEWER, CLEAN-OUT
EXISTING JUNCTION BOX
EXISTING WATER STRUCTURES
EXISTING VALVES
EXISTING SIDEWALK
EXISTING PAVERS
EXISTING UNIDENTIFIED UTILITY
EXISTING FORCE MAIN
EXISTING FIRE LINE
Revisions DateRevisions Date
VA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
APOLINAR VARGAS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
RENOVATE PREVENTATIVE
MAINTENANCE SHOP AND
01/26/2024 CRHJS
546-22-106
MIAMI, FL
100% DESIGN SUBMITTAL
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
50% DESIGN DEVELOPMENT SUBMITTAL 10/13/2023
REPLACE ALUMINUM CANOPY
RDC/JPA Project No. 23082.00
NOT FOR CONSTRUCTION
65% CONSTRUCTION DOCUMENTS SUBMITTAL 12/08/2023
100% CONSTRUCTION DOCUMENTS SUBMITTAL 01/11/2024
100% CONSTRUCTION DOCUMENTS SUBMITTAL 01/26/2024
CS - 021
EXISTING CONDITIONS
1. TOPOGRAPHIC INFORMATION OBTAINED FROM FIELD SURVEY PERFORMED
BY PENNONI ASSOCIATES.
2. ELEVATIONS BASED ON MIAMI DADE SURVEY CONTROL POINT "N-3004-A",
ELEVATION 8.86 FEET, AND "N-3005", ELEVATION 5.46 FEET, NORTH AMERICAN
VERTICAL DATUM OF 1988 (NAVD88).
3. UNLESS SPECIFICALLY STATED OR SHOWN HEREON TO THE CONTRARY, THIS
SURVEY IS MADE SUBJECT TO AND DOES NOT LOCATE OR DELINEATE:
A. RIGHTS OR INTERESTS OF THE UNITED STATES OF AMERICA OR THE
CITY OF MIAMI, OVER LANDS NOW OR FORMERLY FLOWED BY
TIDEWATER, BUT NO LONGER VISIBLE OR PHYSICALLY EVIDENT, OR
LANDS CONTAINING ANY ANIMAL, MARINE, OR BOTANICAL SPECIES
REGULATED BY OR UNDER THE JURISDICTION OF ANY FEDERAL, STATE,
OR LOCAL AGENCY.
B. BUILDING SETBACK LINES, ZONING REGULATIONS OR LINES
ESTABLISHED BY ANY FEDERAL, STATE OR LOCAL AGENCY WHICH MAY
AFFECT THE BUILDING OR DEVELOPMENT POTENTIAL OF THE SUBJECT
PROPERTY.
C. ANY SUBSURFACE OR SUBTERRANEAN CONDITION, EASEMENTS OR
RIGHTS, INCLUDING, BUT NOT LIMITED TO MINERAL OR MINING RIGHTS,
OR THE LOCATION OF OR RIGHTS TO ANY SUBSURFACE STRUCTURES,
CONTAINERS OR FACILITIES OR ANY OTHER NATURAL OR MAN-MADE
SUBSURFACE CONDITION WHICH MAY OR MAY NOT AFFECT THE USE OR
DEVELOPMENT POTENTIAL OF THE SUBJECT PROPERTY.
3. LOCATIONS OF ON AND OFF SITE UTILITIES AS SHOWN ARE APPROXIMATE
AND MAY OR MAY NOT BE COMPLETE. THE NATURE AND EXACT LOCATION OF
EXISTING UTILITIES SHOULD BE VERIFIED PRIOR TO INITIATING ANY ACTIVITY
THAT MAY AFFECT THEIR USE OR LOCATION.
4. A. THE LOCATION OF THE EXISTING UNDERGROUND UTILITIES SHOWN ON
THIS PLAN HAVE BEEN TAKEN FROM EXISTING UTILITY RECORDS
AVAILABLE AT THE TIME THESE PLANS WERE PREPARED AND FROM
SURFACE OBSERVATION OF THE SITE.
B. COMPLETENESS OR ACCURACY OF LOCATION AND DEPTH OF
UNDERGROUND UTILITIES AND STRUCTURES IS NOT GUARANTEED.
C. IN ACCORDANCE WITH "UNDERGROUND FACILITY DAMAGE PREVENTION
AND SAFETY ACT" FLORIDA STATUTES, CHAPTER 556. THE CONTRACTOR
SHALL NOTIFY ALL UTILITIES WITHIN THE WORK AREA VIA THE SUNSHINE
ONE CALL SYSTEM, INC. (800-432-4770) A MINIMUM OF 2 WORKING DAYS
BEFORE THE START OF EXCAVATION
D. THE CONTRACTOR SHALL VERIFY LOCATIONS AND DEPTHS OF ALL
UNDERGROUND UTILITIES AND STRUCTURES BEFORE THE START OF
WORK.
GENERAL NOTES:
00 10' 20'
N O
R
TH
SITE INFORMATION:
ADDRESS: 1201 NW 16TH ST
MIAMI, FL 33125
OWNER: U.S. DEPT. OF VETERANS AFFAIRS
1201 NW 16TH ST
MIAMI, FL 33125
ENGINEER: PENNONI
JASON SHERIDAN, PE
5755 RIO VISTA DRIVE
CLEARWATER, FL 33760
SOIL BORING "B-3"
ELEVATION 5.03
CONC
STEPS
SANITARY
PUMP STATION
CONC PAD
WITH SIGN
POLES
S-02
S-04 S-05
S-10
±1
±7 7'
S-01 S-02
SET PK&D STAMPED
"TRAVERSE LB 8126"
PARKING
AREA
CATCH BASIN
CATCH BASIN
CURB INLET
CURB INLET
STORM LINE
DEPTH 2'-4'
END OF
MARKINGS
PUMP STATION VAULT
LID EL 6.84
TOP OF 2" FM (2) EL 5.84
E 3" PVC 90° INV 5.44
BOTTOM EL -0.16
(FULL OF DEBRIS)
4" METAL FIRELINE
TOP 10.97
90° BEND
TOP 11.00
TOP 8.80
90° BEND
TOP 8.99
4" METAL FIRELINE
90° BEND TOP 8.98
90° BEND
TOP 9.66
TOP 9.68
3" PVC
TOP 8.52
3" 45° BEND
TOP 6.87
3"x4" REDUCER
TOP 6.98
3"x4" REDUCER
TOP 7.80
4" WYE
WITH CAP
TOP 7.03
4" WYE
WITH CAP
TOP 7.63
3" WYE WITH CAP
TOP 7.80
3" 45° BEND
TOP 8.50 3" 90° BEND
TOP 8.62
3" 90° BEND
TOP 8.35
3" PVC
TOP 8.87
3" WYE
TOP 8.28
3" WYE
WITH CAP
TOP 8.89
UGS
DEPTH 3'-5'
POST INDICATOR
VALVE
CONTROL
PANEL
MULTIPLE CONDUIT
LINES BETWEEN
WALL AND FENCE
SEWER LINE
ON SURFACESEWER LINE
ON SURFACE
FIRE LINE
ON SURFACE
CONC WALK
END OF
MARKINGS (DU)
NOTE:
ADDITIONAL
ALUMINUM POSTS
NOT LOCATED
6.833
2.0X2.0 VAULT
8.618 3" 90
8.499 3" 45
8.280
3" WYE
8.346 3" 90
8.887
3" WYE
8.874
3" PVC
DRAINAGE MANHOLE
RIM EL. 4.19'
N INV. -0.21' (12" RCP)
S INV. -0.41 (12" RCP)
UNDERGROUND ELECTRIC
LINE (TYP)
AC PAD
S-11
GRATE EL 6.41
W 12" CMP INV 2.02
S-13
RIM EL 6.74
BOTTOM EL 0.66
S-12
RIM EL 6.83
BOTTOM EL 2.08
S-12
RIM EL 4.83
S-07
GRATE EL 4.89
NE 12" HDPE INV -0.01
W 24" HDPE INV -0.67
SOIL BORING "B-2A"
ELEVATION 5.52
SOIL BORING "B-2"
ELEVATION 6.5
SOIL BORING "B-3"
ELEVATION 5.03
CONC
STEPS
FENCE
MOTOR
FF EL 9.21
FF EL 9.16
FF EL 9.28 FF EL 9.16
FF EL 8.62 FF EL 8.65 FF EL 8.65
COVERED CONC
AND ASPHALT
COVERED CONC
AND ASPHALT
COVERED
CONC AREA
COVERED
CONC AREA
FENCE
POST
CONC PAD
WITH SIGN
POLES
B U I L D I N G
B U I L D I N G
B U
I L
D I
N G
.2
115.1'
.2
3.1'
.0
2.9'
.3
.0
3.1'
.3
29.1'
7.
7'
21.4'
7.
6'
37.5'
.3
.0
G
AT
E
6' PLASTIC FENCE
6' CHAIN LINK FENCE
6' C
H
AI
N L
IN
K
FE
N
C E
G
AT
E
6' PLASTIC FENCE
COVERED CONC
6' PLASTIC FENCE
CONC STEPS (TYP)
TBM #101
SET PK&D
STAMPED "TRAVERSE LB 8126"
N: 530948.19 E: 913634.49
ELEVATION 4.97
GATE
GATE
6' METAL
FENCE
6' CHAIN
LINK FENCE
COVERED
CONC AREA
HEAVY EQUIPMENT
AREA
HEAVY EQUIPMENT
AREA
PARKING
AREA
ASPHALT
DRIVE
BOLLARD
(TYP)
BOLLARD
(TYP)
R
AM
P
R
AM
P
ST
O
P
BA
R
ST
O
P
BA
R
CONC SIDEWALK
8" CURB
(TYP)
8" CURB
(TYP)
SOIL BORING "B-4"
ELEVATION 4.6
I-BEAM (TYP)
ALUMINUM POST (TYP)
10" RETAINING
WALL
FF EL 11.58
B U I L D I N G
CONC DOCK
FF EL 6.90
G
AT
E
GATE
B U I L D I N G
LOCKED
WALL
COVERED
CONC AREA
COVERED CONC
AND ASPHALT
HYDRAULIC
LIFT
6' PLASTIC FENCE
CONC
EYE WASH
STATION
220.3'
UGS
DEPTH 3'-5'
CONC WALK
FF EL 8.60
B U I L D I N G
6.7
6.7
6.7 66.8
6.9
0 6.7
6.8
6.8
6.8
6.7
6.7
6.7 8 7.5
7.4
7.1
6.9
6.9 9 6.9
6.9
6.5
6.5 65.9
5.9 65.5
5.5 24.9
4.9
4.9
4.9
4.7
4.5
4.4
4.5
4.5
4.5
4.8
4.2
4.1
4.1
4.0
4.0
4.1
4.2
4.4
4.5
4.6 1 4.8 5 5.0
4 5.3 1 5.5
4 5.9
6.0
6.1
12" 12"12"
14"
6.6
5.9
5.3
4.7
4.6
4.5
4.7
4.6
4.8 5.1
12"
12"
5.4
5.4
4.2
4.7
4.1
4.9
5.1
5.0
5.2 4.9
4.9
4.8
4.7
4.7
4.7
4.6
4.7
4.8
4.9
5.0
5.1
5.2
4.4
4.4
4.3
4.2
4.3
4.3
4.3
4.4
4.6
4.6
4.6
4.6
4.7
5.1 65.1
5.1
4.9
4.9
4.8
5.0
4.8
5.9
5.4
5.1
5.3
5.4
6.0
5.6
5.0
4.9
5.3
5.4
5.5
5.8
5.6
6.0
6.1
6.5
8.1
7.2
6.4
6.8
6.1
9.2
9.2
9.1
9.1
9.1
9.1
8.0
8.0
9.1
9.1
8.98.8 8.8
8.3 8.1
7.8
6.7
6.3
8.9
8.8
8.9 8.4
8.2
8.0
8.5 8.96.55.3
6.1
7.0
6.2 6.5
12"
12" 12"
10"
9"
4.7
5.1
5.4
6.7
6.8
6.8
6.9
7.4
7.5
7.4
7.4
7.5
8.8 3 8.8
8.9
8.9
8.9
8.8
8.3
7.2
6.7 6.7
6.7
6.7
6.8
6.8
6.8
6.8
7.1
7.8
6.9
7.0 46.7
6.8
6.6
6.7
6.6
6.3
6.8 5 6.7
6.5
6.8
6.8
6.8
6.8
6.6
6.6
6.3
6.6
6.4
6.4
6.1 3 6.2
6.2
6.2
6.8 26.8
6.7
6.2
6.1
8.6
7.8
8.9
9.2
6.4
6.4
6.9
6.9
6.8
12"
6.5 86.5
6.3
5.9
5.6
5.1 44.6
4.9
4.9
4.5
4.5 6 5.3
4 6.3
6.0
5.9
5.9
5.8
5.8
5.8
5.2
5.2
5.0
4.5 9 4.7
5.8
5.9
5.9
6.0
5.5
4.6
5.1
5.2
5.6
4.6
5.4
6.9
8.4
8.4
6.9
7.1
7.3
7.2
7.6
7.8
.2
.43
.59
.2
.47
.60
.56
.4810
.2
.46
.4410 .42
.54
9.8 9.2
8.4
7.9
8.6 9.0
9.1
9.1
6.9 6.9
6.8
7.0
7.5
7.3 67.3
7.2
7.3
.0
9.3
8.4
7.2
7.7
7.4
9.8
9.8
.2
.0
9.8 7.8
.0
9.8
8.0
8.1 88.1
8 9.8
9.8
.23
.27
9.9
.14 10 .16
8.6
8.0
8.5
9.9
7.7
.66
7.8
8.5
168.2'
GATE
12" 12" 10" 10"
12" 10" 12" 10" 8"
12"
8"
12"
GATE
BUILDING
CONC
RAMP
CONC
WALK
TBM #101
FND PK&D STAMPED
"TRAVERSE LB 8126"
N: 530948.19 E: 913634.49
ELEVATION 4.97'
GRASS
6" CONC CURB
(5) 2" PVC
PIPES
TWIN 2X12"
PAVER
WALK(TYP)
6" CONC BOLLARD
CONC PAD
WITH HANDRAIL
(5) METAL SUPPORT
PARKING STRIPING
(TYP)
6" CONC CURB
6" CONC CURB
6" CONC CURB
FF=8.59'
FF=8.60'
CONC
RAMP
ASPHALT
PAVEMENT
CURB CUT
CURB CUT
CURB CUT
CURB CUT
CURB CUT
PROPOSED
SILT FENCE
LIMITS OF
DEMOLITION
PUMP STATION TO BE REPLACED
EXISTING CANOPY
& SUPPORT STRUCTURES
TO BE REMOVED
EXISTING LEGEND
EXISTING MANHOLES
EXISTING COMMUNICATION, UNDERGROUND
EXISTING NATURAL GAS, UNDERGROUND
EXISTING POWER, UNDERGROUND
EXISTING SANITARY SEWER, UNDERGROUND
EXISTING STORM SEWER, UNDERGROUND
EXISTING STORM SEWER, ROOF DRAIN
EXISTING BUILDING OVERHANG
EXISTING WATER, UNDERGROUND
EXISTING CURB
EXISTING EDGE OF PAVEMENT
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
EXISTING EXISTING TREES
EXISTING BOLLARD
BORING LOCATION
EXISTING SIGN
EXISTING LIGHT
EXISTING UTILITY POLE
EXISTING FENCE
EXISTING BUILDING
EXISTING SPOT ELEVATION100.55
EXISTING STORM SEWER, INLET
EXISTING SANITARY SEWER, CLEAN-OUT
EXISTING JUNCTION BOX
EXISTING WATER STRUCTURES
EXISTING VALVES
EXISTING FEATURE TO BE DEMOLISHED
EXISTING SIDEWALK
EXISTING PAVERS
EXISTING UNIDENTIFIED UTILITY
EXISTING FORCE MAIN
EXISTING FIRE LINE
Revisions DateRevisions Date
VA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
APOLINAR VARGAS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
RENOVATE PREVENTATIVE
MAINTENANCE SHOP AND
01/26/2024 CRHJS
546-22-106
MIAMI, FL
100% DESIGN SUBMITTAL
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
50% DESIGN DEVELOPMENT SUBMITTAL 10/13/2023
REPLACE ALUMINUM CANOPY
RDC/JPA Project No. 23082.00
NOT FOR CONSTRUCTION
65% CONSTRUCTION DOCUMENTS SUBMITTAL 12/08/2023
100% CONSTRUCTION DOCUMENTS SUBMITTAL 01/11/2024
100% CONSTRUCTION DOCUMENTS SUBMITTAL 01/26/2024
CS - 051
DEMOLITION PLAN
00 10' 20'
N O
R
TH
1. SITE CONTRACTOR SHALL BE RESPONSIBLE FOR
DISCONNECTION OF ALL UTILITIES ON SITE TO BE REMOVED.
2. ALL DEMOLITION TO BE PERFORMED BY A QUALIFIED,
LICENSED CONTRACTOR IN ACCORDANCE WITH ALL
APPLICABLE LOCAL, STATE, AND FEDERAL CODES AND
REGULATIONS. ALL DEBRIS TO BE REMOVED FROM THE SITE
AND DISPOSED OF IN ACCORDANCE WITH ALL APPLICABLE
LOCAL, STATE, AND FEDERAL REGULATIONS.
3. ALL UTILITIES SHALL BE DISCONNECTED AND REMOVED IN
ACCORDANCE WITH ALL APPLICABLE LOCAL, STATE, AND
FEDERAL REGULATIONS.
4. ANY UTILITIES DAMAGED DURING DEMOLITION AND
CONSTRUCTION SHALL BE REPAIRED AND/OR REPLACED IN
KIND BY THE CONTRACTOR AT HIS OWN EXPENSE. UTILITY
REMOVAL SHALL BE IN ACCORDANCE WITH THE
REQUIREMENTS OF THE UTILITY COMPANY.
5. ALL OPENINGS IN STORM SEWER STRUCTURES RESULTING
FROM PIPE REMOVAL SHALL BE FILLED WITH SEWER BRICK
AND MORTAR OR REPLACED, AS DIRECTED BY THE CITY
ENGINEER.
6. STORMWATER AND SANITARY LINES, STRUCTURES AND
APPURTENANCES SHALL BE REMOVED IN THEIR ENTIRETY.
7. ALL EXISTING BUILDING CONCRETE FOUNDATIONS AND
FOOTINGS ARE TO BE REMOVED IN THEIR ENTIRETY. ALL SITE
STRUCTURES AND IMPROVEMENTS WITHIN THE LIMIT OF
DEMOLITION SHALL BE REMOVED IN THEIR ENTIRETY,
INCLUDING FOUNDATIONS UNLESS NOTED OTHERWISE.
8. TREES TO BE REMOVED SHALL INCLUDE REMOVAL AND
DISPOSAL OF TREES AND STUMPS.
9. DUST CONTROL - DEMOLITION CONTRACTOR IS RESPONSIBLE
FOR WETTING DUST GENERATING DEBRIS FROM TIME OF
FIRST CONTACT UNTIL PLACING INTO APPROPRIATE WASTE
OR HAULING CONTAINERS OR TRUCKS. DEBRIS SHALL NOT BE
ALLOWED TO DRY BEFORE REMOVAL FROM SITE.
10.WATER FOR DUST CONTROL - DEMOLITION CONTRACTOR IS
RESPONSIBLE FOR PROVIDING WATER TANK / PUMP TRUCKS
IF ON-SITE WATER FLOW OR PRESSURE IS NOT SUFFICIENT
FOR OPERATIONS.
11.CONTAMINATED SOIL - IF UNUSUAL STAINS OR ODORS ARE
DETECTED IN SOILS, CEASE OPERATIONS AND NOTIFY THE
EHS IMMEDIATELY.
DEMOLITION NOTES:
SOIL BORING "B-2A"
ELEVATION 5.52
SOIL BORING "B-2"
ELEVATION 6.5
SOIL BORING "B-3"
ELEVATION 5.03
CONC
STEPS
FENCE
MOTOR
FF EL 9.21
FF EL 9.16
FF EL 9.28 FF EL 9.16
FF EL 8.62 FF EL 8.65 FF EL 8.65
COVERED CONC
AND ASPHALT
COVERED CONC
AND ASPHALT
COVERED
CONC AREA
COVERED
CONC AREA
FENCE
POST
CONC PAD
WITH SIGN
POLES
B U I L D I N G
B U I L D I N G
B U
I L
D I
N G
.2
115.1'
.2
3.1'
.0
2.9'
.3
.0
3.1'
.3
29.1'
7.
7'
21.4'
7.
6'
37.5'
.3
.0
G
AT
E
6' PLASTIC FENCE
6' CHAIN LINK FENCE
6' C
H
AI
N L
IN
K
FE
N
C E
G
AT
E
6' PLASTIC FENCE
COVERED CONC
6' PLASTIC FENCE
CONC STEPS (TYP)
TBM #101
SET PK&D
STAMPED "TRAVERSE LB 8126"
N: 530948.19
GATE
6' CHAIN
LINK FENCE
COVERED
CONC AREA
HEAVY EQUIPMENT
AREA
HEAVY EQUIPMENT
AREA
PARKING
AREA
ASPHALT
BOLLARD
(TYP)
BOLLARD
(TYP)
R
AM
P
R
AM
P
ST
O
P
BA
R
ST
O
P
BA
R
CONC SIDEWALK
8" CURB
(TYP)
8" CURB
(TYP)
SOIL BORING "B-4"
ELEVATION 4.6
I-BEAM (TYP)
ALUMINUM POST (TYP)
10" RETAINING
WALL
B U I L D I N G
FF EL 6.90
G
AT
E
GATE
B U I L D I N G
LOCKED
WALL
COVERED
CONC AREA
COVERED CONC
AND ASPHALT
HYDRAULIC
LIFT
6' PLASTIC FENCE
CONC
EYE WASH
STATION
220.3'
CONC WALK
FF EL 8.60
12" 12"12"
14"
12"
12"
12"
12" 12"
10"
9"
12"
.47
.60
.56
.48
.46
12" 12" 10" 10"
12" 10" 12" 10" 8"
12"
8"
12"
GATE
BUILDING
CONC
RAMP
CONC
WALK
HANDICAPPED PARKING
ONLY SIGN (TYP)
TBM #101
FND PK&D STAMPED
"TRAVERSE LB 8126"
N: 530948.19 E: 913634.49
ELEVATION 4.97'
GRASS
6" CONC CURB
(5) 2" PVC
PIPES
TWIN 2X12"
PAVER
WALK(TYP)
6" CONC BOLLARD
CONC PAD
WITH HANDRAIL
6' CHAIN LINK
FENCE
(5) METAL SUPPORT
PARKING STRIPING
(TYP)
6" CONC CURB
6" CONC CURB
6" CONC CURB
6" CONC CURB
STRIPING (TYP)
(WALKWAY)
FF=8.59'
FF=8.60'
CONC
RAMP
ASPHALT
PAVEMENT
CURB CUT
CURB CUT
CURB CUT
CURB CUT
CURB CUT
EXISTING VINYL FENCE
TO BE CLEANED AND REPAIRED
PROPOSED CANOPY
EXISTING VINYL FENCE
TO BE CLEANED AND REPAIRED
EXISTING
MAINTENANCE SHOP
TO BE PAINTED
PROPOSED POST (TYP.)
EXISTING LEGEND
EXISTING MANHOLES
EXISTING COMMUNICATION, UNDERGROUND
EXISTING NATURAL GAS, UNDERGROUND
EXISTING POWER, UNDERGROUND
EXISTING SANITARY SEWER, UNDERGROUND
EXISTING STORM SEWER, UNDERGROUND
EXISTING STORM SEWER, ROOF DRAIN
EXISTING BUILDING OVERHANG
EXISTING WATER, UNDERGROUND
EXISTING CURB
EXISTING EDGE OF PAVEMENT
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
EXISTING EXISTING TREES
EXISTING BOLLARD
BORING LOCATION
EXISTING SIGN
EXISTING LIGHT
EXISTING UTILITY POLE
EXISTING FENCE
EXISTING BUILDING
EXISTING SPOT ELEVATION100.55
EXISTING STORM SEWER, INLET
EXISTING SANITARY SEWER, CLEAN-OUT
EXISTING JUNCTION BOX
EXISTING WATER STRUCTURES
EXISTING VALVES
EXISTING FEATURE TO BE DEMOLISHED
EXISTING SIDEWALK
EXISTING PAVERS
EXISTING UNIDENTIFIED UTILITY
EXISTING FORCE MAIN
EXISTING FIRE LINE
PROPOSED LEGEND
PROPOSED CURB LINE
PROPERTY LINE
PROPOSED WALL
PROPOSED CANOPY
PROPOSED SIDEWALK
PROPOSED WATER MAIN
PROPOSED STORM SEWER
PROPOSED SANITARY SEWER
PROPOSED UNDERGROUND ELECTRIC
PROPOSED UNDERGROUND GAS
PROPOSED AREA DRAIN
PROPOSED DRAINAGE INLET
PROPOSED DRAINAGE MANHOLE
PROPOSED SANITARY MANHOLE
PROPOSED MAJOR CONTOUR
PROPOSED MINOR CONTOUR30
PROPOSED FENCE
PROPOSED VEGETATION
5.7
4% PROPOSED SLOPE
PROPOSED SPOT ELEVATION
Revisions DateRevisions Date
VA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
APOLINAR VARGAS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
RENOVATE PREVENTATIVE
MAINTENANCE SHOP AND
01/26/2024 CRHJS
546-22-106
MIAMI, FL
100% DESIGN SUBMITTAL
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
50% DESIGN DEVELOPMENT SUBMITTAL 10/13/2023
REPLACE ALUMINUM CANOPY
RDC/JPA Project No. 23082.00
NOT FOR CONSTRUCTION
65% CONSTRUCTION DOCUMENTS SUBMITTAL 12/08/2023
100% CONSTRUCTION DOCUMENTS SUBMITTAL 01/11/2024
100% CONSTRUCTION DOCUMENTS SUBMITTAL 01/26/2024
CS - 101
SITE PLAN
00 10' 20'
N O
R
TH
SITE INFORMATION:
ADDRESS: 1201 NW 16TH ST
MIAMI, FL 33125
OWNER: U.S. DEPT. OF VETERANS AFFAIRS
1201 NW 16TH ST
MIAMI, FL 33125
ENGINEER: PENNONI
JASON SHERIDAN, PE
5755 RIO VISTA DRIVE
CLEARWATER, FL 33760
9.4
7.3
7.5
8.9
7.6
7.0
6.8
6.2
6.5
5.9
5.5
6.2
6.1
9.5
8.6
8.1
7.2
6.86.4
6.1
5.2
5.8 6.2
6.7
7.2
7.6
6.6
7.0
6.2
8.5
6.2
7.3
7.3 3 7.3
7.7
7.9
8.4
8.4 4 7.7
8.5
9.3
8.8
9.3
9.5
8.8
8.3
5.1
9.8
9.7
9.7
7.4
9.1
7.3
5.8
8.9
7.8
6.1
6.2
6.5
6.1
9.5
8.6
6.2
SOIL BORING "B-3"
ELEVATION 5.03
.2
115.1'
.2
3.1'
.0
2.9' 3.1'
.3
29.1'
7.
7'
21.4'
7.
6'
37.5'
.0
SOIL BORING "B-4"
ELEVATION 4.6
220.3'
12" 12"12"
14"
12"
12"
4.2
4.4
4.3
4.5
4.1
12"
6.8
12"
4.5 6 5.3
4 6.3
4.6
.47
.60
.56
.48
.46
12" 12" 10" 10"
12" 10" 12" 10" 8"
12"
8"
12"
CONC
WALK
6" CONC CURB
SOIL BORING "B-3"
ELEVATION 5.03
S-02
S-04 S-05
S-08
±1
±7 7'
S-01 S-02
SET PK&D STAMPED
"TRAVERSE LB 8126"
N: 531091.24 E: 913585.68
ELEVATION 4.14 CATCH BASIN
CATCH BASIN
CURB INLET
CURB INLET
END OF
MARKINGS
4" METAL FIRELINE
TOP 10.97
90° BEND
TOP 11.00
TOP 8.80
90° BEND
TOP 8.99
4" METAL FIRELINE
90° BEND TOP 8.98
90° BEND
TOP 9.66
TOP 9.68
POST INDICATOR
VALVE
CONTROL
PANEL
MULTIPLE CONDUIT
LINES BETWEEN
WALL AND FENCE
FIRE LINE
ON SURFACE
END OF
MARKINGS (DU)
6.833
2.0X2.0 VAULT
8.618 3" 90
8.499 3" 45
8.280
3" WYE
8.346 3" 90
8.887
3" WYE
8.874
3" PVC
DRAINAGE MANHOLE
RIM EL. 8.56'
SE INV. 3.56' (12" RCP)
W INV. 0.36' (12" CMP)
DRAINAGE MANHOLE
RIM EL. 4.29'
E INV. -0.11' (12" CMP)
S INV. -0.21' (12" RCP)
DRAINAGE MANHOLE
RIM EL. 4.19'
N INV. -0.21' (12" RCP)
S INV. -0.41 (12" RCP)
UNDERGROUND ELECTRIC
LINE (TYP)
S-11
GRATE EL 6.41
W 12" CMP INV 2.02
S-13
RIM EL 6.74
BOTTOM EL 0.66
S-12
RIM EL 6.83
BOTTOM EL 2.08
S-12
RIM EL 4.83
S-07
GRATE EL 4.89
NE 12" HDPE INV -0.01
W 24" HDPE INV -0.67
EXISTING VINYL FENCE
TO BE CLEANED AND REPAIRED
PROPOSED CANOPY
EXISTING VINYL FENCE
TO BE CLEANED AND REPAIRED
EXISTING
MAINTENANCE SHOP
TO BE PAINTED
PROPOSED
5,274 SF
CANOPY
PROPOSED POST (TYP.)
PROPOSED
ROOF DRAIN (TYP)
CONNECT TO
EXISTING 12"
DRAINAGE PIPE
INV IN: 2.02
PROPOSED 12"
PERFORATED
HDPE
DMH-01
(DOGHOUSE)
RIM: 5.97
INV: 2.00
VIF
CO-04
RIM: 6.35
INV: 2.23
VIF
CO-05
RIM: 7.97
INV: 2.95
VIF
CO-03
RIM: 8.05
INV: 3.52
VIF
CO-02
RIM: 7.14
INV: 3.00
VIF
FD-02
GRATE: 7.02
INV: 2.88
VIF
CO-01
RIM: 6.23
INV: 2.28
VIF
23 LF 12" HDPE @ 1%
93 LF 12" HDPE @ 1%
35 LF 12" HDPE @ 1%
12 LF 12" HDPE @ 1%
45 LF 12" HDPE @ 1%
28 LF 12" HDPE @ 1%
PROPOSED
LIFT STATION
LID 8.0
PROPOSED LIFT
STATION
CONTROL PANEL
PROPOSED 2" FORCE MAIN
(CONNECT TO EXISTING)
DIVERT EXISTING
SANITARY SEWER TO
PROPOSED FORCE MAIN
INV 4.0
10 LF 2" SANITARY
LATERAL @ 1.5%
INV IN 3.85
11 LF 2" FORCE MAIN
INV OUT 4.5
15 LF 12" HDPE @ 1%
FD-01
GRATE: 6.32
INV: 2.43
VIF
FD-03
GRATE: 7.58
INV: 3.35
VIF 17 LF 12" HDPE @ 1%
EXISTING LEGEND
EXISTING MANHOLES
EXISTING COMMUNICATION, UNDERGROUND
EXISTING NATURAL GAS, UNDERGROUND
EXISTING POWER, UNDERGROUND
EXISTING SANITARY SEWER, UNDERGROUND
EXISTING STORM SEWER, UNDERGROUND
EXISTING STORM SEWER, ROOF DRAIN
EXISTING BUILDING OVERHANG
EXISTING WATER, UNDERGROUND
EXISTING CURB
EXISTING EDGE OF PAVEMENT
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
EXISTING EXISTING TREES
EXISTING BOLLARD
EXISTING SIGN
EXISTING FENCE
EXISTING BUILDING
EXISTING SPOT ELEVATION100.55
EXISTING STORM SEWER, INLET
EXISTING SANITARY SEWER, CLEAN-OUT
EXISTING JUNCTION BOX
EXISTING WATER STRUCTURES
EXISTING VALVES
EXISTING SIDEWALK
EXISTING PAVERS
EXISTING UNIDENTIFIED UTILITY
EXISTING FORCE MAIN
EXISTING FIRE LINE
PROPOSED LEGEND
PROPOSED CURB LINE
PROPERTY LINE
PROPOSED WALL
PROPOSED CANOPY
PROPOSED WATER MAIN
PROPOSED STORM SEWER
PROPOSED SANITARY SEWER
PROPOSED UNDERGROUND ELECTRIC
PROPOSED UNDERGROUND GAS
PROPOSED AREA DRAIN
PROPOSED DRAINAGE INLET
PROPOSED DRAINAGE MANHOLE
PROPOSED SANITARY MANHOLE
PROPOSED FENCE
Revisions DateRevisions Date
VA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
APOLINAR VARGAS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
RENOVATE PREVENTATIVE
MAINTENANCE SHOP AND
01/26/2024 CRHJS
546-22-106
MIAMI, FL
100% DESIGN SUBMITTAL
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
50% DESIGN DEVELOPMENT SUBMITTAL 10/13/2023
REPLACE ALUMINUM CANOPY
RDC/JPA Project No. 23082.00
NOT FOR CONSTRUCTION
65% CONSTRUCTION DOCUMENTS SUBMITTAL 12/08/2023
100% CONSTRUCTION DOCUMENTS SUBMITTAL 01/11/2024
100% CONSTRUCTION DOCUMENTS SUBMITTAL 01/26/2024
CS - 171
UTILITY PLAN
00 10' 20'
N O
R
TH
SITE INFORMATION:
ADDRESS: 1201 NW 16TH ST
MIAMI, FL 33125
OWNER: U.S. DEPT. OF VETERANS AFFAIRS
1201 NW 16TH ST
MIAMI, FL 33125
ENGINEER: PENNONI
JASON SHERIDAN, PE
5755 RIO VISTA DRIVE
CLEARWATER, FL 33760
1. ALL PIPE LENGTHS AND DISTANCES BETWEEN STRUCTURES ARE MEASURED FROM CENTER OF STRUCTURE
TO CENTER OF STRUCTURE ALONG A HORIZONTAL PLANE.
2. ALL STORM DRAINAGE PIPE SHALL BE LAID ON SMOOTH CONTINUOUS GRADES WITH NO VISIBLE BENDS AT
JOINTS.
3. BEDDING REQUIREMENTS SPECIFIED HEREIN ARE TO BE CONSIDERED AS MINIMUMS FOR RELATIVELY DRY, STABLE EARTH CONDITIONS. ADDITIONAL BEDDING SHALL BE REQUIRED FOR ROCK TRENCHES AND WET AREAS. CONTRACTOR SHALL HAVE THE RESPONSIBILITY TO PROVIDE SUCH ADDITIONAL BEDDING AS MAY BE
REQUIRED TO PROPERLY CONSTRUCT THE WORK.
4. COMPACTION OF THE BACKFILL OF ALL TRENCHES SHALL BE COMPACTED TO THE DENSITY OF 95% OF THEORETICAL MAXIMUM DRY DENSITY (ASTM D698). BACKFILL MATERIAL SHALL BE FREE FROM ROOTS, STUMPS, OR OTHER FOREIGN DEBRIS AND SHALL BE PLACED IN LIFTS NOT TO EXCEED 6 INCHES IN COMPACTED FILL THICKNESS. A REPORT FROM A GEOTECHNICAL ENGINEER MAY BE REQUIRED BY THE PUBLIC WORKS INSPECTOR. CORRECTION OF ANY TRENCH SETTLEMENT WITHIN A YEAR FROM THE DATE OF
APPROVAL WILL BE THE RESPONSIBILITY OF THE CONTRACTOR.
5. CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY CONNECTION FEES.
6. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE THE LOCATION OF ALL EXISTING
UNDERGROUND UTILITIES AND TO TAKE WHATEVER STEPS NECESSARY TO PROVIDE FOR THEIR PROTECTION.
THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THE LOCATIONS OF UTILITIES SHOWN OR NOT SHOWN.
THE CONTRACTOR SHALL CONTACT THE UTILITY COMPANIES FOR EXACT LOCATION OF THEIR UTILITIES PRIOR TO STARTING CONSTRUCTION. IT SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO
REPAIR AND REPLACE ANY AND ALL DAMAGE MADE TO UTILITIES BY THE CONTRACTOR.
7. THE CONTRACTOR SHALL COORDINATE LOCATION AND INSTALLATION OF ALL UNDERGROUND UTILITIES AND APPURTENANCES TO MINIMIZE DISTURBANCE TO CURBING, PAVING, AND COMPACTED SUBGRADE.
8. CONTRACTOR SHALL EXCAVATE ONLY AS MUCH TRENCH WHICH PIPE CAN BE INSTALLED AND TRENCH
BACKFILLED BY THE END OF EACH WORK DAY.
9. ALL UNDERGROUND UTILITY TRENCHES SHALL BE BACKFILLED WITH SAFE CLEAN FILL.
10. ALL TRENCHES SHALL BE PROPERLY SECURED AND BRACED.
11. ALL EXISTING CASTING AND INLET TOPS OR GRATES MUST BE ADJUSTED TO THE PROPOSED GRADE, UNLESS
OTHERWISE INDICATED.
12. ALL PROPOSED UTILITIES, INCLUDING ELECTRIC SERVICE, SHALL BE PLACED UNDERGROUND.
13. ALL CONNECTIONS TO EXISTING UTILITIES AND TESTING SHALL BE PERFORMED IN THE PRESENCE OF UTILITY
OWNERS AND PENNONI. CONNECTION LOCATIONS MUST BE APPROVED IN FIELD AFTER PIPE IS EXPOSED.
CONTRACTOR SHALL PROVIDE WRITTEN REQUEST TO PENNONI WITH PROPOSED TIME AND DATE OF CONNECTION AT LEAST 5 WORKING DAYS IN ADVANCE OF PLANNED CONNECTION. COORDINATE WITH LOCAL
JURISDICTION ON THE CAPPING AND DISCONNECTING REQUIREMENTS FOR
14. ANY EXISTING SERVICES.ALL BUILDINGS CONTAINING KITCHENS / RESTAURANTS REQUIRE GREASE TRAPS
SIZED IN ACCORDANCE WITH THE EPA REGULATIONS WITHIN SANITARY LATERALS.
15. ON SITE SANITARY SEWER IS PRIVATELY OWNED.
UTILITY NOTES:
ENCLOSURE AND DEADFRONT LAYOUT (TYPICAL)
ELECTRICAL DATA
GENERAL NOTES
INLET INVERT
TOP OF WET WELL
HIGH WATER ALARM
PUMP OFF
BOTTOM OF WET WELL
ELEVATIONS*
LAG PUMP ON
LEAD PUMP ON
WET WELL/VALVE BOX LAYOUT
PO BOX 3529, LAKELAND, FL 33802
PHONE: (863) 665-8500 FAX: (863) 666-3858
LISTED
U L
PUMP DESIGN CAPACITY
IMPELLER DIAMETER
PUMP DESIGN TDH
SECONDARY TDH
HORSEPOWER
VOLTAGE
PUMP DATA TABLE
PHASE
DISCHARGE SIZE
NOTES:
SECONDARY CAPACITY
C
B
A
D
E
F
G
A
B
C
D
E
F
G
SECTION VIEW
PLAN VIEW
PUMP MODEL
GPM
FT
GPM
FT
HP
V
PH
PUMP PERFORMANCE CURVE
3- W
IR
E
0v
,1
Ø MCB __A
L1 L2
N
CCB
15A
V M
MECHANICAL
INTERLOCK
R G
ECB __A
F1-2 1A
600V
VM
GFICB
15A
GFI
VMR
SFM2
R IL
SFM1
ILR
TB9
TB10
TB13
TB14
PDB
N
G
AH
M1
PCB1
MS1
__A
S
T1 T2 T3
M2
PCB2
MS2
__A
S
T1 T2 T3
VMR
AR
I0.4 (HIGH_LEVEL)
I0.5 (VOLTAGE_MONITOR)
PLC DIGITAL INPUTS
PLC
UPS
SR
L N
PSU
PSUCB
1A
ETHERNET
SWITCH
SWITCH
COMMUNICATIONS TOPOLOGY
PLC
ETHERNET
CAT5E
SCADA
CAT5E
(BY
OTHERS)
NETWORK
ALT
6 83
2 7
H O A
TB11 TB12THERMAL#1
ETM
G RL
MS1
OL1
VMR
H O A
TB15 TB16THERMAL#2
ETM
G RL
MS2
OL2
FS1TB1 TB2
OFF
FS2TB3 TB4
LEAD
FS3TB5 TB6
LAG
MS1 AUX
MS2 AUX
ASR
ASR AH
ASB
ASR
R
AL
F
FS4TB7 TB8
HIGH
120V
CONTINUED ON PAGE 2
N
AR
OL1 OL2
S S
SC
RC
SC
RC
120V
CONTINUED FROM PAGE 1
N
PLCCB
1A L1 L1 G
L1 G
N
+24 -24
COM
+24 -24
G
1 42 3 5 6 16117 8 109 12 13 1514
FIELD TERMINAL BLOCK
FS2
LEAD
OFF
FS1
FS3
LAG
FS4
ALARM
M1 M2
PUMP SENSOR CORDS
M O
IS
TU
R E
SE
N
SO
R
M O
IS
TU
R E
SE
N
SO
R
M O
IS
TU
R E
SE
N
SO
R
M O
IS
TU
R E
SE
N
SO
R
TH
ER
M
AL
S
EN
SO
R
TH
ER
M
AL
S
EN
SO
R
TH
ER
M
AL
S
EN
SO
R
TH
ER
M
AL
S
EN
SO
R
RESET
OL RESET
GFI
ASB
AL
SUN
SHIELD
PL
C
C B
UPS
SWITCH
SR PLC
GR
TERMINALS
CAPACITORS
HOA
HOURS
ETM
RL
IL
PUMP1
HOA
HOURS
ETM
RL
IL
PUMP2
M C
B
EC
B
PC
B2
PC
B1
G
FI
C B
C C
B
MS2MS1
N F1 -2
3O
0/
H Z
0-
VA
C
LO
SS
M O
N
IT
O R
PH
AS
E
SE
Q U
EN
C
E
AN
D
M
IN
M
AX
VM
3-POINT
LATCH
ASR AR VMR
POS. 1
POS. 2
ALT
4.7TO100K OHMS
SFM1
4.7TO100K OHMS
SFM2
PSU
PS
U
C B
PDB
RESET
BREAKERS
ENCLOSURE, 304SS, NEMA 3R/12
SQ.D, QOU - SIZE AS REQUIRED
SQ.D, QOU - SIZE AS REQUIRED
SQ.D, QOU - SIZE AS REQUIRED
SQ.D, 8536 - SIZE AS REQUIRED
MANUFACTURER, PART#
UNITRON CONTROLS, VM180-300
SQ.D, 9001-SKR1BH5
SQ.D, 9001-SKS43BH13
SQ.D, 9001-SKP38-LG
SQ.D, 9001-SKP38-LR
CUSTOM EQUIP., 36X36X12-SS
RUSSELL STOLL, JRSB1044FR
FEDERAL, 350-120-30 + TR
SYRELEC, PNRU-110A
ABBR.
MS1,2
PCB1,2
SFM1,2
IL
HOA
RL
ASB
AL
ETM
AH
VM
GR
4,2
CCB
OL
ECB
QTY.
MCB
ENC
GENERATOR RECEPTACLE, 100A
ALARM SILENCE BUTTON
HAND OFF AUTO SWITCH
INDICATING LIGHT, RED
SEAL FAIL MODULE
VOLTAGE MONITOR
ALARM HORN
ALARM LIGHT
RUN LIGHT, GREEN
ELAPSED TIME METER EATON, 6-T-3H-508RPM-406
AC/DC EQUIPMENT, R40-XLS-25
BILL OF MATERIALS
EMERGENCY CIRCUIT BREAKER
CONTROL CIRCUIT BREAKER
MAIN CIRCUIT BREAKER
PUMP CIRCUIT BREAKER
MOTOR STARTER
OVERLOAD HEATER
DESCRIPTION
SQ.D, QOU115
SQ.D, SIZE AS REQUIRED
FERRAZ, ATQR-12 F1-2 FUSE, 1A 600V
1 GFICB GFI CIRCUIT BREAKER SQ.D, QOU115
P&S, 1595I1 GFI GFI RECEPTACLE, 15A
1 F FLASHER INGRAM, SSF-150W
EATON, D5PR3A3 VMR,AR,ASR CONTROL RELAY
SIZE AS REQUIRED
SIZE AS REQUIRED
SC
RC RUN CAPACITOR
START CAPACITOR
SIZE AS REQUIRED2 S START RELAY
DIVERSIFIED, ARA-120-ACA1 ALT ALTERNATING RELAY
1 SR SIMPLEX RECEPTACLE PHOENIX, 2963860
1 PLC PROGRAMMABLE LOGIC CONTROLLER SCHNEIDER ELEC., TM221CE16R
1 PLCCB PLC CIRCUIT BREAKER A-B, 1489-M1C010
1 ENET ETHERNET SWITCH (4)RJ-45 + (1)ST F/O PORT PHOENIX, SFN-4TX/FX-ST
1 UPS UNITERRUPTABLE POWER SUPPLY APC
Revisions DateRevisions Date
VA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
APOLINAR VARGAS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
RENOVATE PREVENTATIVE
MAINTENANCE SHOP AND
01/26/2024 CRHJS
546-22-106
MIAMI, FL
100% DESIGN SUBMITTAL
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
50% DESIGN DEVELOPMENT SUBMITTAL 10/13/2023
REPLACE ALUMINUM CANOPY
RDC/JPA Project No. 23082.00
NOT FOR CONSTRUCTION
65% CONSTRUCTION DOCUMENTS SUBMITTAL 12/08/2023
100% CONSTRUCTION DOCUMENTS SUBMITTAL 01/11/2024
100% CONSTRUCTION DOCUMENTS SUBMITTAL 01/26/2024
CS - 601
SITE DETAILS
EROSION AND SEDIMENTATION CONTROL NOTES
1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO CONTROL AND PREVENT EROSION AND THE TRANSPORTATION OF SEDIMENT TO SURFACE DRAINS AND
OUTFALLS. REFER TO CONSTRUCTION PLANS, DETAILS, SPECIFICATIONS AND APPROVED PERMITS FOR DETAILS. SEDIMENT DEPOSITS SHALL BE REMOVED WHEN
THEY REACH SIX INCHES ON AN EROSION DEVICE.
2. DURING THE CONSTRUCTION OF DRAINAGE STRUCTURES, AND OTHER STRUCTURES REQUIRING EXCAVATION, THE CONTRACTOR SHALL PLACE APPROVED BARRIERS OR OTHER APPROVED DEVICES AROUND SUCH STRUCTURES TO PREVENT EROSION AND THE MIGRATION OF SEDIMENT TO POINTS OUTSIDE THE CONSTRUCTION AREA. THE APPROVED BARRIERS OR OTHER APPROVED DEVICES SHALL BE PLACED IN ACCORDANCE WITH REQUIREMENTS OF F.D.O.T. INDEX NO.
102, FDEP, OR AS DIRECTED BY THE ENGINEER.
3. REQUIRED EROSION CONTROL MEASURES MUST REMAIN INTACT THROUGHOUT CONSTRUCTION. FAILURE TO INSTALL OR PROPERLY MAINTAIN REQUIRED EROSION CONTROL WILL RESULT IN ENFORCEMENT. ALL EROSION CONTROL MEASURES, SAND, SILT, AND DEBRIS SHALL BE REMOVED FROM ALL DRAINAGE PIPES AND STRUCTURES AFTER CONSTRUCTION HAS BEEN COMPLETED AND PRIOR TO COUNTY FINAL WALK-THROUGH.
4. OUTFALL PROTECTION - PROJECT PIPE OR DITCH DISCHARGES INTO OFF-SITE OUTFALLS SHALL BE INSPECTED DAILY FOR POSSIBLE SEDIMENT BUILDUP OR TRANSPORT. OUTFALLS SHALL BE PROTECTED THROUGH USE OF EROSION CONTROL FEATURES AS NECESSARY TO CONTAIN ANY SEDIMENT LOSS TO THE IMMEDIATE AREA OF THE PROJECT. ANY SEDIMENT BUILDUP OR TRANSPORT OFF-SITE SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REMEDY. THE CONTRACTOR SHALL USE APPROPRIATE MEASURES AS DIRECTED BY THE PROJECT ENGINEER FOR OUTFALL PROTECTION.
5. APPROVED BARRIERS (OR OTHER APPROVED SEDIMENT CONTROL DEVICES): THESE SHALL BE PLACED AT THE BASE OF ANY SLOPE WHERE A RAINFALL EVENT COULD ERODE A SLOPE AND TRANSPORT SEDIMENTS OFF-SITE. APPROVED BARRIERS SHALL BE DOUBLE STAKED IN ACCORDANCE WITH F.D.O.T. INDEX NO. 102 OR FDEP. IF EROSION DEPOSITS REACH THE TOP ELEVATION OF EXISTING APPROVED BARRIERS, THEN SEDIMENTS SHOULD BE REMOVED. ANY DAMAGED OR INEFFECTIVE APPROVED BARRIERS ARE TO BE REPLACED WITH NEW ONES. THE LOCATION AND INSTALLATION OF APPROVED BARRIERS SHALL BE AS DIRECTED
BY THE PROJECT ENGINEER.
6. BACK OF SIDEWALK INLETS OR MEDIAN INLETS: THESE SHALL BE PROTECTED FROM SEDIMENT INTAKE UNTIL PROJECT IS COMPLETE. ELEVATION OF GROUND OUTSIDE INLET TOP SHALL NOT BE HIGHER THAN INLET TOP. APPROVED BARRIERS OR OTHER APPROVED SEDIMENT CONTROL DEVICES SHALL BE INSTALLED AROUND INLET TOP. A SECOND ROW OF APPROVED BARRIERS OR OTHER APPROVED SEDIMENT CONTROL DEVICES SHALL BE PLACED AROUND INLET APPROXIMATELY 4" OUTSIDE FIRST ROW. BETWEEN ROWS THERE SHALL BE A DEPRESSION TO ACT AS A SEDIMENT BASIN. COMPLETED INLETS IN PAVED AREAS SHALL ALSO BE PROTECTED WITH A SINGLE LINE OF APPROVED BARRIERS OR OTHER APPROVED SEDIMENT CONTROL DEVICES TO PREVENT SEDIMENT INTAKE
FROM OTHER AREAS.
7. STOCKPILED MATERIALS SHALL BE PROTECTED BY COVER, APPROVED BARRIERS OR OTHER APPROVED SEDIMENT CONTROL DEVICES.
8. ALL DISTURBED AREAS SHALL BE STABILIZED WITHIN 3 DAYS AFTER 1/2" RAIN EVENT DISTURBANCE.
9. CONTRACTOR IS RESPONSIBLE FOR OBTAINING THE NECESSARY DEWATERING PERMITS FROM THE LOCAL WATER MANAGEMENT DISTRICT OR OTHER
REGULATORY AGENCY.
10. A DEWATERING PLAN MUST BE SUBMITTED AND APPROVED BY THE ENGINEER PRIOR TO DISCHARGE.
11. IF WIND EROSION BECOMES SIGNIFICANT DURING CONSTRUCTION, THE CONTRACTOR SHALL STABILIZE THE AFFECTED AREA USING SPRINKLING, IRRIGATION, OR
OTHER ACCEPTABLE METHODS.
12. THERE IS TO BE NO DISCHARGE (I.E. PUMPING, SHEET FLOW, SWALE, DITCH, ETC.) INTO EXISTING DITCHES OR CANALS WITHOUT THE USE OF SETTLING PONDS OR DEVICES. IF THE CONTRACTOR DESIRES TO DISCHARGE INTO EXISTING DITCHES OR CANALS A SETTLING PLAN PREPARED BY THE CONTRACTOR MUST BE SUBMITTED TO AND APPROVED BY THE ENGINEER OF RECORD AND LOCAL REGULATORY AGENCY PRIOR TO CONSTRUCTION.
13. WHERE APPLICABLE, SOIL TRACKING PREVENTION DEVICES SHALL BE PROVIDED AND MAINTAINED PER F.D.O.T. INDEX NO. 106 OR FDEP.
14. ALL EROSION CONTROL FENCES, BARRIERS, AND SILTATION DEVICES SHALL BE ERECTED PRIOR TO ANY LAND ALTERATIONS, SHALL BE MAINTAINED IN GOOD WORKING ORDER DURING CONSTRUCTION, AND REMOVED FOLLOWING SOIL STABILIZATION AND FINAL DRESSING. BUILT-UP SEDIMENT WILL BE REMOVED FROM SILT FENCES AND STAKED TURBIDITY BARRIERS WHEN IT HAS REACHED ONE THIRD THE HEIGHT OF THE FENCE/BARRIER. STOCKPILE AREAS SHALL INCLUDE SILT
FENCE AROUND THE PERIMETER.
15. THE CONTRACTOR SHALL NOT RESTRICT OR BLOCK THE EXISTING DRAINAGE FLOW OVERLAND OR WITHIN RESHAPED SWALES. FLOW WITHIN EXISTING DRAINAGE PIPES SHALL BE MAINTAINED AT ALL TIMES. STORMWATER WILL BE CONVEYED VIA EXISTING SWALES, DITCHES, OR PROPOSED DITCHES, EXISTING AND
PROPOSED STORM SEWERS.
16. DURING DEWATERING OPERATIONS, THE CONTRACTOR SHALL NOT DISCHARGE DIRECTLY TO RECEIVING WATERS, EXISTING CONVEYANCES TO RECEIVING WATERS, OR WETLAND SYSTEMS. TEMPORARY SEDIMENT BASINS, TRAPS, OR SILTATION REDUCTION DEVICES SHALL BE UTILIZED TO COLLECT THE DISCHARGE FROM DEWATERING ACTIVITIES TO ELIMINATE THE POTENTIAL FOR OFF-SITE SEDIMENT TRANSPORT AND TO INSURE THAT DIRECT DISCHARGE DOES NOT OCCUR.
17. BANKS SHALL BE PROTECTED FROM EROSION OR COLLAPSE DURING CONSTRUCTION. BANK PROTECTION MATERIAL SHALL BE CAREFULLY PLACED FROM THE BANK AND NOT DUMPED FROM ABOVE IN AN UNCONTROLLED MANNER. EROSION CONTROL FABRIC SHALL BE USED FOR EROSION PROTECTION WHERE SOD WILL NOT HOLD OR BECOME ESTABLISHED IN TIME TO PROTECT THE BANKS. UNLESS OTHERWISE SPECIFIED IN THE PLANS, UPON COMPLETION OF CONSTRUCTION, ALL BANKS AND WATERWAYS SHALL BE RESTORED TO THEIR PRE- CONSTRUCTION CONFIGURATION AND PROTECTION FROM EROSION.
UP UP UP UP
2.04
2.05
2.51
2.06
2.07
2.08
TYP.
PIPE SHOP
STORAGE
PM SHOP
RESTROOM
PM OFFICE
PM SHOP
WORK AREA
PIPE SHOP
2.10
2.152.152.152.15
2.152.152.152.15 2.152.152.152.15
2.152.152.152.15
2.08
2.52
2.542.54
2.532.532.532.53
2.11
2.09
2.082.082.082.08
S T A
T E
OF FLO
R
I D A
R E G
IS
TERED ARC
H
IT
E C T
J A S
ON
H. RO
S S
AR101907
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
10/13/2023Design Development Submittal50%
01/11/2024Construction Documents Submittal65%
/2
/2
:1
:2
P M
Renovate Preventative Maintenance Shop and Replace
Aluminum Canopy
01/26/2024
DEMOLITION PLAN
AD101
BRJR
546-22-106
MIAMI, FL
Apolinar Vargas
100% Design Submittal 23082.00
A. See Plumbing, HVAC and Electrical Drawings for removal work associated with those trades.
B. Computer and communication cables and/or other wiring, piping, tubing, etc. serving other areas and functions located above ceiling or in walls of area to be remodeled shall be maintained during demolition/construction process. Coordinate any required changes to these systems with the C.O.R.
C. Repair existing walls to match adjacent undisturbed wall where canopy shown to be removed.
D. Prepare walls and floor slabs as required to receive new fininsh materials where shown on Architectural and Finish plans.
2.04 Removed existing chainlink fence and gate.
2.05 Remove existing emergency shower and eye wash. See
Plumbing Drawings.
2.06 Remove existing 8' x 8' equipment lift. See Electrical
Drawings.
2.07 Remove existing stainless steel utility sink. See Plumbing Drawings.
2.08 Remove existing aluminum canopy, integrated gutter, downspouts, columns, and footings. Fill all grade holes with asphalt and prepar to receive new finish.
2.09 Patch all Bldg. 40 holes created by existing canopy with concrete and prepar building Bldg. 40 exterior to receive new paint finish.
2.10 Saw cut and remove existing damaged concrete retaining
wall. Exact extents TBD on site with COR. Approx. 20' long x 3' tall.
2.11 Remove existing break metal baffle.
2.15 Existing Shipping Container to be moved by VA.
2.51 Existing Air Compressor to remain
2.52 Existing membrane on concrete deck to remain.
2.53 Existing Metal Panel on Structural Steel canopy to
remain.
2.54 Existing aluminum canopy to remain
PLAN NOTES
GENERAL DEMOLITION NOTES
N Scale: 1/8" = 1'-0"1
DEMOLITION PLAN
N Scale: 1/8" = 1'-0"2
DEMOLITION PLAN - ROOF
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
UP UP UP UP
A A
B B
4.8 4.4
2.7 2.3
A.5 A.5
PIPE SHOP
STORAGE
PM SHOP
RESTROOM
PM OFFICE
108 PM SHOP
WORK AREA
PIPE SHOP
23'-0"
6'-0"
8'-0" 11'-0" 25'-0" 9'-0" 7'-9" 8'-3" 24'-0"
122'-0" to f a c e o f w a ll a t g ra d e
10.15
4'-11 7/8" 8'-0" 18'-2"11'-0 1/8" 9'-0" 8'-0" 14'-11 1/8"
22.08
Fenced Secure Storage
2.14
2.12
TYP.
2.12TYP.
3.09
26.02
2.51
P it
Pit:
8'-0"
3.103.103.103.10
11.18
7.05 7.05 7.05
5.10
Fenced Secure Storage
5.10
5.11 5.11
7.05 7.05 7.05 7.05 7.05 7.05
2.14
AE301
AE301
AE301
AE301
S.1/AE201
W .1
/A E
S.2/AE201
E .2
/A E
W .2
/A E
N.1/AE201
W .1
/A E
E .1
/A E
2 0
C C
3"9' - 10"
7.05
7.05
7.05
7.057.05
A A
B B
4.8 4.4
2.7 2.3
A.5 A.5
26.03 26.03 26.03
P-3
Typical for all Structural Steel, Structural Perlins, and Steel Decking.
C C
REFLECTED CEILING PLAN LEGEND
Recessed downlight fixture
Supply Air Diffuser
Return Air Grille2' x 4' light fixture
2' x 2' acoustical tile ceiling
Gypsum board / portland cement plaster ceiling / soffit - painted
Pendant light fixture
Chain-hung light fixture
Access panel
Recessed wall-wash fixture
Surface-mounted strip light fixture
S T A
T E
OF FLO
R
I D A
R E G
IS
TERED ARC
H
IT
E C T
J A S
ON
H. RO
S S
AR101907
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
10/13/2023Design Development Submittal50%
01/11/2024Construction Documents Submittal65%
/2
/2
:1
:3
P M
Renovate Preventative Maintenance Shop and Replace
Aluminum Canopy
01/26/2024
ARCHITECTURAL PLAN
AE101
BRJR
546-22-106
MIAMI, FL
Apolinar Vargas
100% Design Submittal 23082.00
N Scale: 1/8" = 1'-0"1
ARCHITECTURAL PLAN
2.12 Pressure wash existing white vinyl fence. Both sides.
2.14 Pressure wash exterior of existing Maintenance building, including exterior walls, doors, stairs, and handrails, preparation to receive new paint finish.
2.51 Existing Air Compressor to remain
3.09 6" wide concrete retaining wall. Dow #4 rebar every 6" vertically into adjacent concrete wall. Backfill with loose aggregate and layer of soil.
Locate weeps at lower grade level every 48" O.C.
3.10 Line existing 1' deep equipment lift pit with 1/4" expansion foam, fill with concrete, and level.
5.10 10'-0" tall chainlink fence with horizontal and vertical rails 5'-0" O.C.
5.11 Full height chainlink fence gate.
7.05 Connect aluminum gutter and downspout system to Storm Drainage.
See Civil Drawings
10.15 Flammable Storage Cabinet. Final location TBD.
11.18 New Ground Level Scissor Lift Table.
22.08 New Emergency Shower and Eye Wash. See Plumbing Drawings.
26.02 Relocate electrical junction box, as necessary, to complete concrete retaining wall. Coordinate with COR.
26.03 Ceiling-Mounted, adjustable fan. See Electrical Drawings.
PLAN NOTES
N Scale: 1/8" = 1'-0"2
REFLECTED CEILING PLAN
A. See P, M, E and FP drawings for additional information regarding final information and quantites of fixtures/devices to be installed in ceiling.
B See Structural and Architectural Section Drawings for canopy elevations
C. Existing Shop Floor Elevation 100'-0" equals Civil elevation 8.65'.
See Civil Drawings
D. See Electrical Drawings for lighting and fan specifications.
E. All Structural steel to be shop primed and field painted. Final color
TBD.
GENERAL NOTES
A
B
123456
4.8 4.4 2.7 2.3
A.5
AE301
AE301
AE301
AE301
/1
/1
130' - 11 1/4"
7.087.08
/4
/4
/4
5' - 3 3/8" 23' - 0" 25' - 0" 25' - 0" 25' - 0" 24' - 0" 3' - 8"
7.087.08
7.06
7.06
AE301
C
AE301
Sim
AE301
Sim
AE301
Sim
A A
123456 7.07
7.07
AE301
AE301
AE301
2.522.522.522.52
2.542.542.542.54
S T A
T E
OF FLO
R
I D A
R E G
IS
TERED ARC
H
IT
E C T
J A S
ON
H. RO
S S
AR101907
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
10/13/2023Design Development Submittal50%
01/11/2024Construction Documents Submittal65%
/2
/2
:1
:3
P M
Renovate Preventative Maintenance Shop and Replace
Aluminum Canopy
01/26/2024
ROOF PLANS
AE102
BRJR
546-22-106
MIAMI, FL
Apolinar Vargas
100% Design Submittal 23082.00
2.52 Existing membrane on concrete deck to remain.
2.54 Existing aluminum canopy to remain
7.06 5" x 7" Aluminum Gutter with leaf guard. 1/4" Slope Min.
7.07 4" x 3" Aluminum Gutter with leaf guard. 1/4" Slope min.
7.08 TPO single-ply roof membrane fully adhered to Cement Roof Board. Mechanically fasten Cement Roof Board to 3" deep structural decking. Add through and through mechanical fasteners near canopy edges, as required by roofing manufacturer.
PLAN NOTES
N Scale: 1/8" = 1'-0"1
ROOF PLAN - CANOPY
N Scale: 1/8" = 1'-0"2
ROOF PLAN - BUILDING 40
Maint. Shop Floor 100' - 0"
Maint. Shop Ceiling 109' - 0"
123456
Top of Concrete 101' - 4 1/4"
4.8 4.4 2.7 2.3
/2
3' - 8"24' - 0"8' - 3"7' - 9"9' - 0"25' - 0"11' - 0"8' - 0"6' - 0"23' - 0"5' - 3 3/8"
32.037.053.05 7.05 3.053.05 3.053.05 7.05 3.05
7.05
3.05 7.05
3.05
7.05
2.12
Maint. Shop Floor 100' - 0"
Maint. Shop Ceiling 109' - 0"
A B
Top of Concrete 101' - 4 1/4"
A.5
2.142.142.142.14
2.122.12
7.07
AE301
Sim
AE301
Sim
/4
3.0532.033.053.05
5.17
1 5/16" / 12"
1 5/16" / 12"
P-1
Maint. Shop Floor 100' -…