Attachment 07 - Hydrant Report Repair - July 2024.pdf

PDF 134 KB Posted

Attached to
Repair Fire Hydrants
Solicitation number
FA480326B0005
Issued by

About this file

This document is a Hydrant Report Repair for July 2024, detailing the inspection and maintenance status of multiple fire hydrants across different locations. The comprehensive report catalogs 72 individual hydrants, categorizing their conditions into statuses such as "Repaired", "Needs Replaced", "In-Progress", "Not Found", and "Remove From Records". Key issues identified include seized operating nuts, damaged safety couplings, low water pressure, leaking from bonnets and bases, stiff stems, and hydrants struck by vehicles. The inspections were conducted between March and August 2023, with most assessments occurring in April 2023. Manufacturers noted include Mueller, Kennedy, American Darling, and M&H, with hydrant ages ranging from 1953 to 2018. Recommended actions vary from lubricating and minor repairs to complete hydrant replacement and investigating potential buried isolation valves.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Test Hydrant Remarks Date_Flown Flowing_Hydrant 1-3 Stem is too tight, unable to remove lube nut - Disasembled Operating Nut, funtion checked, oiled, verified…Repaired 3/21/2023 Repaired

1-49 OUT of SERVICE, Free Spinning - Right turn open; Disasembled bonnet, stem is damaged, safety coupling broken. Contacted vendor for replacment hold down nut which is damaged, need new safety coupling. Repair In progress 4/13/2023 In-Progress

2-10 OUT OF SERVICE - Needs Replaced,--Kennedy 5 K10 1968: Operating nut seized, Isolation valve not found, need to find isolation valve and/or repair or install. 3/23/2023 Needs Replaced

2-15 Abandoned, Tested multiple hydrants, no drop - Kennedy 4 1/2, 1969…Operational checked/flowed, 100% funtional; no issues, just needs greasing 4/13/2023 Repaired 2-21 No Pressure Drop - American Darling 5 1/4, B84B-5, 2017, Operationally checked, 100% functional 4/14/2023 Repaired

2-24

OUT OF COMMISSION - Hydrant appears to be funtioning fine, however there is no water to it. Appears to be shut off or decomissioned possibly due to the previous demolotion of facilities within the area---because no buildings within close proximity of the fire hydrant itself. Also, no isolation valve found; needs to be found or installed if found. Repaired

2-25 Stem is too tight, Cannot open - Mueller 4 1/2 1956: Operating nut seized, Isolation valve not found, need to find isolation valve and/or repair or install. 3/23/2023 Needs Replaced 2-27D No Pressure Drop - Mueller 5 1/4 2012, Operationall check, 100% funtional 4/12/2023 Repaired 2-30 No Drop, Discovered closed valves - American Darling 4 1/2, MK73-5, Operationally checked, 100% funtional 4/14/2023 Repaired

2-31 Very low pressure, gauge didn't move from OPSi - American Darling 5 1/4, B84B-5, Operational chedked/ flowed, 100% functioning, however it has low pressure….need to find / troublshoot area for closed valve(s) down and/or upstream within the system 4/14/2023 Repaired

3-1 BROKEN, FREE SPINING, POSSIBLE TO REMOVE - M&H: Operating nut free spinnin…older fire hydrant, need to find isolation valve and/or repair or install as appropriate. 3/17/2023 Needs Replaced

3-17 OUT OF SERVICE - Mueller 5 1/4 1989: Operating nut is free spining….disasembled needs new safety coupling and operating nut to attempt repair. Will have to troubleshoot after first repair to see what needs to be done next if applicable. Has isolation valve 4/27/2023 In-Progress

3-33 Too stiff, Couldn't be opened - Operating nut is very stiff, can be troubleshot, however the nozzles are out of code (only 7" off ground f/ lowest outlet) and extention needs installing. Recommend replacing and adding proper berrel hight. Isolation valve found. 4/3/2023 Needs Replaced

3-37 ONLY FOUND YARD HYDRANT - Surveyed area and did not find a fire hydrant, only a yard hydrant for a water spigot 3/17/2023 Not Found 3-5 OUT OF SERVICE 4/17/2023 Not Found

3-6 OUT OF SERVICE, free spinning - No water to hydrant, recommend replace, investigate etc to see if any more issues present…believe isolation valve may be burried under the road. 4/17/2023 Needs Replaced

4-12 Behind locked fence, No POC number, Bldg 1619 - Mueller 4 1/2 1980; Inspected hydrant and it is 100% operational. 4/24/2023 Repaired

4-14D Unable to do 4-17, outlet threads are damaged - Mueller 5 1/4; Hydrant functions and is 100 % funtional. It is lower than it should be to the ground;

outlets are out of code, but funtionality is in tact…apears the dirt has washed around and/or construction for asthetic reasons 4/25/2023 Repaired

4-16

OUT OF SERVICE Low pressure, Valve closed somewhere, Hydrant leaning and dug up from ground - Hydrant has been struck by vehicle (or something) and leaning. Has an isolation valve in closed position but Iso valve can get a 96% shutoff (stiff). Hydrant flows water but needs to be replaced, pipe inspected, etc. 4/20/2023 Repaired/Replaced

4-17 Unable to do 4-17, outlet threads are damaged - Replace, hydrant has damaged threads, but is also out of code 4/25/2023 Needs Replaced 4-26 4-27 Leaking from bonnet and outlets, stem is ceased up 4/25/2023 Needs Replaced 4-29 Stem Seized 8/10/2023 Needs Replaced

5--11 BOTH DIDN'T DROP ON STATIC PRESSURE - 100% functional checked, flow was good, no lead valve found…may be burried and/or need to search. 100% functional 4/3/2023 Repaired

5-26 Static pressure didn't drop, Valve closed between hydrants, retest with diff. static hydrant 4/4/2023 Repaired 5-27 OUT OF SERVICE - Mueller 5 1/4 2003; Flowed, noticed the pressure is lower in area, flowed, hydrant, function checked and it is operational 4/4/2023 Repaired

5-32 Too stiff, can't open, needs lubricant - Mueller, 5 1/4, 1953; Stem / operating nut extreemly stiff…older hydrand (1953), has isolation valve. Needs Replaced 4/4/2023 Needs Replaced

5-35 STEM SEIZED 8/14/2023 Needs Replaced

5-9D TOO STIFF, NEEDS LUBRICANT - Operating nut very stiff. "The hydrant is old(er) but could not read the date Recommend replace due to the age, and the unknown of troubleshooting…ie, fix one problem, find another, fix that one, find another, and so on. Isolation valve located. 4/3/2023 Needs Replaced

6-21 OUT OF SERVICE - Hydrant is older, out of service and does not have water supply. Previous buildings in area have been demolished…Needs to be reomoved from the records 4/10/2023 Remove From Records

6-22 OUT OF SERVICE - Hydrant is older, out of service and does not have water supply. Previous buildings in area have been demolished…Needs to be reomoved from the records 4/10/2023 Remove From Records

09 - Hydrant Report Repair - July 2024

6-23 In service but has orange cone next to it - Operationally checked, function is 100% functioning 4/10/2023 Repaired

6-24

OUT OF SERVICE - Hydrant has been hit, leaning and is leaking from bonnet. Suspect main valve is leaking by but operating nut is spinning as if the safety coupling is broken we think. Cannot get a positive shut off, but was able to slow leak down some by snugging up bonnet bolts.....cannot find an isolation valve. 4/10/2023 Needs Replaced

6-28 NO DROP IN STATIC PRESSURE - Function checked and 100% Operational, troubleshot and zero issues 4/10/2023 Repaired 6-29 No Static pressure drop - Mueller 5 1/2 2013, Operational, checked….hydrant functions w/ zero issues 4/10/2023 Repaired

6-30 TOO STIFF, can't fully open, needs lubricant - Mueller 5 1/4 PATD style….Operating nut very stiff, will not open completely. Hydrant has been struck/hit by something it apears. Has isolation valve, recommend replace. 4/10/2023 Needs Replaced

7-1 Stiff can't open needs lubricant 4/11/2023 Needs Replaced

7-11 Leaks heavy from top of hydrany - Mueller 5 1/4 2014; Leaking on the bottom side of the bonnet; need to try and tighten the bonnet and/or disasemble.

No lead valve vissible…in-prog 5/1/2023 In-Progress

7-12D Unable to get static/residual (7-11 issues) - Mueller 5 1/4 (cant read date); 100% functional all components in tact and operational 5/1/2023 Repaired

7-13 leaks from base of hydrant - Mueller 5 1/4, 1997; Leaking at the base of the fire hydrant; need to excavate area around the base first, troubleshoot…no isolation valve visable 5/1/2023 In-Progress

7-17 Significant water leaking from ground when turned on 5/9/2023 Needs Replaced 7-2 Stiff can't open needs lubricant 4/11/2023 Needs Replaced

7-5 BROKEN - Mueller 5 1/4, N.D. (couldn’t see date) Weep hole appears to drain slowly, bonnet leaking when open & possibly main valve not shutting completely…No isolation valve visible (may need to search) Recommend Replace 8/8/2023 Needs Replaced

8-13 BROKEN - Mueller 5 1/4, N.D. (couldn’t see date) Bonnet leaking when open, no isolation valve identified…needs replaced 8/19/2023 Needs Replaced

8-9

Valve is OFF. Full of dirt - Mueller 5 1/4, 2000; Hydrant has an isolation valve that was turned off and locked in the closed position due to it leaking by…pumped out valve box, opened and locked in the open position to stop leakage and fire hydrant is 100% operational now. Still need to repair valve at a later date but hydrant is working and 100% operational now 5/11/2023 Repaired

9-11 Hydrant is seized shut 5/15/2023 Needs Replaced 10-11 No Pressure drop with any other hydrant in ammo - Mueller 5 1/4, 1997; Stem stiff, weep hole operational, valve in area f/ possible shutoff valve 7/19/2023 Repaired

10-14 No Pressure drop with any other hydrant in ammo - Mueller 5 1/4, 2006; Operating nut was stiff---repaired & functioned checked other components. No isolation valve found 7/19/2023 Repaired

10-38 Stem too tight, could not open - Mueller 5 1/4, 2009; Hydrant stem is extreemly tight and cannot opern…need to disasemble bonnet and inspect safety coupling, main valve, etc….in prog 6/14/2023 In-Progress

10-49 Hydrant Seized - Mueller 5 1/4, 2009; Hydrant stem was tight, but was able to work and free it up. Still a little stiff but hydrant and all components are 100% operational 6/26/2023 Repaired

10-52 Low GPM - Mueller 5 1/4, 1994; Funtion checked hydrant to include weep hole. Stem was stiff, but opened/closed and it works to functionality. 6/23/2023 Repaired 10-63 INOP - Mueler 4 1/2, 2018; free spinning, right turn open type hydrant 7/17/2023 Needs Replaced 4-23 4-16 doesn't work, covered in snow fence - Mueller 5 1/4, 1992; Verified Operation Repaired 4-16 4-16 doesn't work, covered in snow fence - Replaced with new fire hydrant Repaired 4-11 Mueller, 5 1/4, 1992; Operated fire hydrant, no issues found, weep hole drains….fully functional Repaired

3-8 Hydrant stuck closed - M & H, 1970; Hydrant seized shut/closed. Bolts missing out of bonnet recommend replace, investigate etc to see if any more issues present…believe isolation valve may be burried under the road. Needs Replaced

3-15 Unable to locate Not Found

1-43 American Darling, 5 1/4, B84B-5 - Operating nut stiff; troubleshot, adjusted then tested & operated and all components. No isolation valve visible. 100% operational now. Repaired

1--10 M & H, 5 1/4, 1974 - No water to hydrant. Recommend investigate and or install iso valve along with replacing the entire hydrant. Needs Replaced

09 - Hydrant Report Repair - July 2024

Hydrant Flow Test Report