This product data portfolio describes the Eaton BladeUPS uninterruptible power system. The BladeUPS delivers 5, 8, or 12 kW of efficient, reliable power protection in only 6U of standard rack space. It offers high power density, scalability to 60 kW, flexible deployment options, easy serviceability, and industry-leading efficiency of up to 98 percent. Standard internal batteries provide ride-through power until an external source takes over. Optional extended battery modules extend runtime up to 94 minutes at full load. The modular design allows capacity additions without power interruption. Intelligent power and thermal management features maximize uptime and efficiency. This document provides detailed specifications, configuration diagrams, cost savings analyses, and order codes for the BladeUPS UPS system and accessories.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

2.165 55.00

71.88 1825.7

INPUT PLUG DETAIL

NEMA L21-20

20A / 4P5W

DISPLAY

2.265 57.52

MOUNTING BUTTON

61.250 1555.75

61.250 1555.75

64.750 1644.65

64.159 1629.65

1.091 27.70

4.92 125.0

1.94 49.2

1.45 36.9

AUX 1AUX 2

RESET BUTTON

POWER LED

DISPLAY

SELECTOR BUTTONS

USB PORT

SECURE

ARRAY OUT

SECURE

ARRAY IN

ETHERNET

CONSOLE 1

DISPLAY DETAIL

CONSOLE 2

.081 2.05

.570 14.48

.435 11.05

.066 1.67

MOUNTING BUTTON

DETAIL

Notes:

1 All Dimension are in inches [millimeters] unless otherwise specified 2 Installation must conform with all related national and local codes 3 All Bracket kits are sold separately. Toolless mounting buttons are included for installation in CPI cabinets.

4 For more information, please contact Tech Support at techsupport@chatsworth.com

EA-3013-X

SHEET 1 OF 1THIRD ANGLE

É2019 Chatsworth Products, Inc.

All rights reserved.

All products quoted are subject to availability based on manufacturing capacity and shipping dates should be considered estimates only.

While every effort has been made to ensure the accuracy of all information, CPI does not accept liability for any errors or omissions and reserves the right to change information and descriptions of listed services and products.

ISS

eConnect Vertical PDU, Monitored, L21-20, 10ft (3m), 120/208V Three Phase Input, 20A,

(30) C13 (6) C19 (6)5-20 Outlets, 120/208V Output

EA-3013-X

SHEET 1 OF 1THIRD ANGLE

É2019 Chatsworth Products, Inc.

All rights reserved.

All products quoted are subject to availability based on manufacturing capacity and shipping dates should be considered estimates only.

While every effort has been made to ensure the accuracy of all information, CPI does not accept liability for any errors or omissions and reserves the right to change information and descriptions of listed services and products. 1

ISS

eConnect Vertical PDU, Monitored, L21-20, 10ft (3m), 120/208V Three Phase Input, 20A,

(30) C13 (6) C19 (6)5-20 Outlets, 120/208V Output

Sheet1

Drawing View1

Drawing View2

Drawing View3

Drawing View4

Detail View MOUNTING BUTTON (1 : 1)

G1-315 – Lumen/AT&T fiber path from street to Row 3 data center

Ground and ceiling penetrations illustration

Lumen to

Street

AT&T to

Street

AT&T

Bridge

Lumen

Bridge

Lumen to Data Center

See illustration 2 below

AT&T to Data Center

See illustration 2 below

Ground and ceiling penetrations illustration #2

AT&T to

Data Center

R4 R1

Ceiling Riser

Lumen to

Data Center

R4 R1

Celing Riser

4th from right

GP-102 HER Duct Pathway illustration

Lower Row

4 From Right

Upper Row

5 From Right

AT&T to G1-315

Lumen to G1-315

GP-102 HER Duct Pathway illustration #2

AT&T LUMEN

GP-103 Data Center Illustration

All cable from street is Prysmian optical cable 48f sm PC-5B12LT048

Appears to be 48 strand (24 pair) on both

Lower Row

9 From Left

Upper Row

8 From Left

Protecting your technology investment.PRODUCT DATA SHEET

United States Agoura Hills, CA 800-834-4969 Canada Toronto, Ontario, Canada +905-850-7770 chatsworth.com • techsupport@chatsworth.com

Latin America Mexico City +52-55-5203-7525 Toll Free within Mexico 800-201-7592 chatsworth.com.co

Europe Buckinghamshire, UK +441628524834

Middle East & Africa Dubai, UAE +971-4-2602125

Doha, Qatar +974-4-267422

Asia Pacific Shanghai +86 21 6880-0266 chatsworth.com.cn

Global Availability

Monitored eConnect® PDUs

• Input and branch circuit monitoring with billing-grade +/-1% accuracy

• Field-replaceable controller for easy serviceability and upgradeability while maintaining power to critical loads; SD-card transfers PDU configuration

• Onboard GUI, RESTful API, SNMP v1/v2/v3, Command Line Interface (CLI), and native Power IQ® DCIM software integration allows users to easily manage PDUs

• Zero Touch Provisioning (ZTP) automates configuration and provisioning of large deployments of PDUs.

• HTTPs support, RADIUS and LDAP integration for enhanced authentication and security

• Customization capabilities: outlet configurations, color options, power cord length, input connection types and more

• Made in the United States, TAA-compliant

Additional Features:

Monitored eConnect® PDUs provide remote power monitoring to the input and branch circuit level, making it possible to obtain and manage power consumption at the cabinet level.

Reduced Networking Costs and

Complexity – Secure Array® allows the use of a single IP address for up to 48 connected PDUs (32 when electronic locks are integrated). Second IP address for the entire array provides failover capability

Resistance to High Temperature –

Market-leading temperature ratings of up to 149°F (65°C) ensures reliability when mounted toward hot aisles

Simplified Load Balancing – Phase-balance outlets on three-phase models ensure equal loading across all phases; allows use of shorter equipment power cords for better cable and airflow management

No Accidental Disconnections –

Patent-pending, low-profile locking outlets prevent accidental disconnections without requiring special cords

Easy Identification of Failover Unit –

Redundancy Pack includes 2 PDUs (one in Black and one in Glacier White) for easy identification of the primary and secondary unit

Electronic Lock Integration – Patented technology seamlessly integrates PDU, environmental sensors and electronic locks into a single hardware and software solution

Gigabit Ethernet – Ensures compatibility with enterprise routers and switches

Latest UL Compliance – Meets UL and IEC

62368 for compliance with new listing requirements for

North America and the European Union

Cabinet Preinstallation – Complete ecosystem ships ready for IT equipment integration, and saves deployment time and reduces packaging waste

Vertical and Horizontal Options Available https://www.chatsworth.com/

PRODUCT DATA SHEET

2 Chatsworth Products

SPECIFICATIONS

Description: Single-input, vertical and horizontal rack-mount PDUs Use: For indoor use in environmentally controlled areas or within environmental enclosures that maintain Operating Conditions (listed below)

Power Input:

• Alternating current, 50/60 Hz, 10’ (3m) input power cord

• Voltage, maximum current, and inlet/plug type varies per model (see ordering table)

Power Capacity: Specific to PDU, limited by circuit breakers or power input (see ordering table) Power Output: NEMA 5-20R, Locking IEC C13 and/or IEC C19 Outlets, specific to PDU with up to 54 outlets (see order table)

Circuit Protection:

• UL 489 listed, single- or two-pole, 100%-rated hydraulic-magnetic breakers available on single- and three-phase models with 30A and above input

• 10kAIC breakers on 220-240/380-415 VAC models; 5kAIC for all other models

• Low-profile design prevents accidental discharge

Metering:

• Input line currents

• Voltage, current, power, energy and power factor at branch circuits

• +/- 1% billing-grade

Local Display:

(Vertical PDUs only)

• Liquid Crystal Display (LCD) with power-on autotext orientation, color

• Provides PDU information; allows initial IP setup, restore defaults and upgrade firmware

• Displays voltage, current, power for input lines and breakers

• Displays temperature and humidity when optional environmental sensor (P/N 14665-001) is attached to the PDU

• Displays alarm notifications – separate LED flashes red on alarm

Networking:

• 10/100/1000MB Ethernet Port

• Secure Array IP Consolidation for up to 48 PDUs without integrated electronic locks or 32 PDUs with integrated electronic locks

• Secure Array IP Consolidation supports alternate/failover network connection through a second PDU

• Static IP and Dynamic Host Configuration Protocol (DHCP) Support, Zero Touch Provisioning (ZTP)

Remote Management:

HTTP/HTTPs compatible onboard Web GUI, SNMP v1/v2/v3; RESTful API, CLI Native Software Integration:

- Sunbird Power IQ® DCIM and dcTrack DCIM

- ZPE Systems Nodegrid Manager™

- RF Code Centerscape Software

- Nlyte DCIM

Console Access: Through serial console port connection and Command Line Interface (CLI)

Security:

• LDAP and Radius Authentication

• Password protection

• Separate user- and admin-level permissions

• Ability to upload custom HTTPs certificate

• Secure Shell (SSH)

Controller: Field-replaceable module; SD-card transfers PDU configuration Firmware: Flash upgradeable through USB port, Web interface, CLI, API or Power IQ.

Environmental Sensor Integration:

• Supports 2 temperature and humidity sensors

• USB Type A port

Electronic Lock Integration:

• Front and rear cabinet door locks (ordered separately) connected to AUX ports on the PDU

• Door locks are powered from and remotely accessed through the PDU

Mounting:

Vertical PDUs:

• 2 preinstalled tool-less mounting buttons; adjustable positions

• Top or bottom power cord entry orientation Horizontal PDUs: Include rack-mount brackets for 19"EIA (482.6 mm) racks

Grounding/Bonding:

• Bonded power inlet/plug and external bond connection with a threaded M5 attachment point

• Includes a bonding kit for CPI cabinets

Color Options:

• Black or Glacier White

• Redundancy Pack includes (1) Black PDU and (1) Glacier White PDU

Operating Conditions:

• Temperature: 32°F – 149°F (0°C – 65°C) at Input Power Rating (kW)

• Relative Humidity: 5% – 95%, noncondensing

• Elevation: 0 – 10,000’ (0 – 3,000 m)

Storage/Non-operating Conditions:

• Temperature: -13°F – 149°F (-25°C – 65°C)

• Relative Humidity: 5% – 95%, noncondensing

• Elevation: 0 – 50,000’ (0 – 15,000 m)

Shipping Weight:

Vertical PDUs: 27 lb (12 kg) single unit; 54 lb (24 kg) Redundancy Pack Horizontal PDUs:

• 1U is 18 lb (8.2 kg) single unit; 35 lb (15.9 kg) Redundancy Pack

• 2U is 23 lb (10.4 kg) single unit; 45 lb (20.4 kg) Redundancy Pack

Certifications: UL/cUL/IEC62368, CE (EU), FCC Part 15, Class A, EN 55022, RoHS Compliant Warranty: 3 years standard with advanced replacement; 2 additional years optional

3 Chatsworth Products

100%-Rated Hydraulic-Magnetic Breakers

Field-Replaceable Module

Color-Coded Labels Printed on Metal

Proprietary Auxiliary Ports for Lock Kits

Serial Console Port - USB Mini Type B

Status LED

Ethernet Port - RJ45

Serial Console Port - RJ45

USB Type A Ports for Firmware and Temperature/Humidity Sensors

Secure Array Ports - RJ45 - for linking of up to 48 PDUs

LCD Local Display

Locking Outlets

VERTICAL CONFIGURATION

Use Vertical eConnect PDUs in data centers and equipment rooms with 42U or higher racks, cabinets and enclosures to provide power connections alongside equipment for higher-density applications. Use Redundancy Pack to support redundant power circuits.

4 Chatsworth Products

Monitored eConnect PDU, Vertical - North America

Part Number Input

Amperage Input Plug Outlets kW Capacity

(UL)

Cabinet CompatibilityBlack* Glacier White* Redundancy

Pack**

120 Volt, Single-Phase Input

EA-3001-C EA-3001-E EA-3001-CE 20A C20 Inlet to L5-20 (24) 5-20 1.9 kW 42U & higher

EA-3002-C EA-3002-E EA-3002-CE 30A L5-30 (24) 5-20 2.9 kW 42U & higher

208 Volt, Single-Phase Input

EA-3003-C EA-3003-E EA-3003-CE 20A C20 Inlet to L6-20 (24) C13 3.3 kW 42U & higher

EA-3004-C EA-3004-E EA-3004-CE 30A L6-30 (24) C13 5 kW 42U & higher

EA-3015-C EA-3015-E EA-3015-CE 30A L6-30 (36) C13 + (6) C19 5 kW 42U & higher

120/208 Volt, Single-Phase Input

EA-3087-C EA-3087-E EA-3087-CE 30A L14-30 (30) C13 + (6) C19 + (6) 5-20 5 kW 42U & higher

120/208 Volt, Three-Phase Input

EA-3013-C EA-3013-E EA-3013-CE 20A L21-20 (30) C13 + (6) C19 + (6) 5-20 5.7 kW 42U & higher

EA-3017-C EA-3017-E EA-3017-CE 20A L21-20 (36) C13 + (6) C19 5.7 kW 42U & higher

EA-3014-C EA-3014-E EA-3014-CE 30A L21-30 (30) C13 + (6) C19 + (6) 5-20 8.6 kW 42U & higher

EA-3018-C EA-3018-E EA-3018-CE 30A L21-30 (36) C13 + (6) C19 8.6 kW 42U & higher

208 Volt, Three-Phase Input

EA-3016-C EA-3016-E EA-3016-CE 30A L15-30 (36) C13 + (6) C19 8.6 kW 42U & higher

EA-3007-C EA-3007-E EA-3007-CE 50A CS8365 (30) C13 + (12) C19 14.4 kW 42U & higher

EA-3019-C EA-3019-E EA-3019-CE 50A CS8365 (36) C13 + (6) C19 14.4 kW 42U & higher

EA-3125-C EA-3125-E EA-3125-CE 50A CS8365 (54) C13 14.4 kW 45U & higher

EA-3126-C EA-3126-E EA-3126-CE 60A IEC 60309 60A 3P+E (54) C13 17.2 kW 45U & higher

EA-3008-C EA-3008-E EA-3008-CE 60A IEC 60309 60A 3P+E (30) C13 + (12) C19 17.2 kW 42U & higher

EA-3020-C EA-3020-E EA-3020-CE 60A IEC 60309 60A 3P+E (36) C13 + (6) C19 17.2 kW 42U & higher

EA-3033-C EA-3033-E EA-3033-CE 60A IEC 60309 60A 3P+E (12) C13 + (18) C19 17.2 kW 42U & higher

240/415 Volt, Three-Phase Input

EA-3021-C EA-3021-E EA-3021-CE 30A L22-30 (36) C13 + (6) C19 17.2 kW 42U & higher

EA-3127-C EA-3127-E EA-3127-CE 30A L22-30 (54) C13 17.2 kW 45U & higher

Notes: *Shipping weight for each unit is 27 lb (12 kg).

**Redundancy Pack includes 2 PDUs in Black and Glacier White for easy identification of the primary and secondary unit; shipping weight is 54 lb (24 kg).

ORDERING INFORMATION

Notes: * Shipping weight for each unit is 27 lb (12 kg).

**Redundancy Pack includes 2 PDUs (one in Black and one in Glacier White) for easy identification of the primary and secondary unit; shipping weight is 54 lb (24 kg).

Monitored eConnect PDU, Vertical - Worldwide

Amperage Input Plug Outlets kW Capacity

Worldwide

(CE)

North

America (UL)

Cabinet CompatibilityBlack* Glacier White* Redundancy

220 - 240 Volt, Single-Phase Input

EA-3005-C EA-3005-E EA-3005-CE 16A C20 Inlet to IEC 60309 16A 1P+N+E (24) C13 3.8 kW 3.8 kW 42U & higher

EA-3006-C EA-3006-E EA-3006-CE 32A IEC 60309 32A 1P+N+E (24) C13 7.7 kW 6.1 kW 42U & higher

EA-3022-C EA-3022-E EA-3022-CE 32A IEC 60309 32A 1P+N+E (36) C13 + (6) C19 7.7 kW 6.1 kW 42U & higher

220 - 240/380-415 Volt, Three-Phase Input

EA-3023-C EA-3023-E EA-3023-CE 16/20A IEC 60309 16/20A 3P+N+E (36) C13 + (6) C19 11.5 kW 11.5 kW 42U & higher

EA-3009-C EA-3009-E EA-3009-CE 32A IEC 60309 32A 3P+N+E (30) C13 + (12) C19 23 kW 18.4 kW 42U & higher

EA-3024-C EA-3024-E EA-3024-CE 32A IEC 60309 32A 3P+N+E (36) C13 + (6) C19 23 kW 18.4 kW 42U & higher

EA-3128-C EA-3128-E EA-3128-CE 32A IEC 60309 20A 3P+N+E (54) C13 23 kW 18.4 kW 45U & higher

5 Chatsworth Products

HORIZONTAL CONFIGURATION

Use Horizontal eConnect PDUs in applications that require outlets at the top or bottom of cabinets for quick access, low- to medium-density applications that require fewer connections and in distributed infrastructure for edge applications. Horizontal PDUs are available in 1U and 2U heights with up to 24 outlets.

Monitored eConnect PDU, 1U Front/Back

Proprietary Auxiliary Ports

Console 2 Port - USB

Ethernet Port - RJ45

Console 1 Port - RJ45

USB Type A Ports for Firmware and Temperature/Humidity Sensors

Secure Array/PDU Linking/Serial Port (link-in)

Secure Array/PDU Linking/Serial Port (link-out)

7 8

Field-Replaceable Main Control Module

100%-Rated Hydraulic-Magnetic Breakers

Locking Outlets

Field-Replaceable Controller Module

Preinstalled Adjustable Depth MountingBrackets

Monitored eConnect PDU, 2U Front/Back

Note: Horizontal eConnect PDUs do not have a LCD Local Display.

6 Chatsworth Products

Monitored eConnect PDU, Horizontal - North America

Form Factor

(U) HeightBlack* Glacier White* Redundancy

EA-3243-C EA-3243-E EA-3243-CE 20A C20 Inlet to L5-20 (12) 5-20 1.9 kW 1U

EA-3244-C EA-3244-E EA-3244-CE 30A NEMA L5-30P (12) 5-20 2.9 kW 1U

EA-3245-C EA-3245-E EA-3245-CE 20A C20 Inlet to L6-20 (12) C13 3.3 kW 1U

EA-3270-C EA-3270-E EA-3270-CE 20A C20 Inlet to L6-20 (8) C13 + (4) C19 3.3 kW 1U

EA-3246-C EA-3246-E EA-3246-CE 30A NEMA L6-30P (12) C13 5 kW 1U

EA-3253-C EA-3253-E EA-3253-CE 30A NEMA L6-30P (9) C19 5 kW 1U

EA-3271-C EA-3271-E EA-3271-CE 30A NEMA L6-30P (8) C13 + (4) C19 5 kW 1U

EA-3248-C EA-3248-E EA-3248-CE 20A NEMA L21-20P (12) C13 5.7 kW 1U

EA-3255-C EA-3255-E EA-3255-CE 20A NEMA L21-20P (9) C19 5.7 kW 1U

EA-3273-C EA-3273-E EA-3273-CE 20A NEMA L21-20P (8) C13 + (4) C19 5.7 kW 1U

EA-3249-C EA-3249-E EA-3249-CE 30A NEMA L21-30P (12) C13 8.6 kW 1U

EA-3256-C EA-3256-E EA-3256-CE 30A NEMA L21-30P (9) C19 8.6 kW 1U

EA-3274-C EA-3274-E EA-3274-CE 30A NEMA L21-30P (8) C13 + (4) C19 8.6 kW 1U

EA-3247-C EA-3247-E EA-3247-CE 30A NEMA L15-30P (12) C13 8.6 kW 1U

EA-3254-C EA-3254-E EA-3254-CE 30A NEMA L15-30P (9) C19 8.6 kW 1U

EA-3272-C EA-3272-E EA-3272-CE 30A NEMA L15-30P (8) C13 + (4) C19 8.6 kW 1U

Notes: * Shipping weight for each unit is 18 lb (8.2 kg) **Redundancy Pack includes 2 PDUs in Black and Glacier White for easy identification of the primary and secondary unit; shipping weight is 35 lb (15.9 kg)

Monitored eConnect PDU, Horizontal - Worldwide

EA-3250-C EA-3250-E EA-3250-CE 16A C20 Inlet to IEC 60309 16A 1P+N+E (12) C13 3.8 kW 3.8 kW 1U

EA-3275-C EA-3275-E EA-3275-CE 16A C20 Inlet to IEC 60309 16A 1P+N+E (8) C13 + (4) C19 3.8 kW 3.8 kW 1U

EA-3252-C EA-3252-E EA-3252-CE 32A IEC 60309 32A 1P+N+E (12) C13 7.7 kW 6.1 kW 1U

EA-3257-C EA-3257-E EA-3257-CE 32A IEC 60309 32A 1P+N+E (9) C19 7.7 kW 6.1 kW 1U

EA-3277-C EA-3277-E EA-3277-CE 32A IEC 60309 32A 1P+N+E (8) C13 + (4) C19 7.7 kW 6.1 kW 1U

220 - 240/380 - 415 Volt, Three-Phase Input

EA-3251-C EA-3251-E EA-3251-CE 16/20A IEC 60309 16/20A 3P+N+E (12) C13 11.5 kW 11.5 kW 1U

EA-3258-C EA-3258-E EA-3258-CE 16/20A IEC 60309 16/20A 3P+N+E (9) C19 11.5 kW 11.5 kW 1U

EA-3276-C EA-3276-E EA-3276-CE 16/20A IEC 60309 16/20A 3P+N+E (8) C13 + (4) C19 11.5 kW 11.5 kW 1U

Notes: * Shipping weight for each unit is 18 lb (8.2 kg) **Redundancy Pack includes 2 PDUs in Black and Glacier White for easy identification of the primary and secondary unit; shipping weight is 35 lb (15.9 kg)

7 Chatsworth Products

Monitored eConnect PDU, Horizontal - North America

EA-3401-C EA-3401-E EA-3401-CE 20A C20 Inlet to L5-20 (24) 5-20 1.9 kW 2U

EA-3402-C EA-3402-E EA-3402-CE 30A NEMA L5-30P (24) 5-20 2.9 kW 2U

EA-3403-C EA-3403-E EA-3403-CE 20A C20 Inlet to L6-20 (24) C13 3.3 kW 2U

EA-3459-C EA-3459-E EA-3459-CE 20A C20 Inlet to L6-20 (18) C13 + (6) C19 3.3 kW 2U

EA-3404-C EA-3404-E EA-3404-CE 30A NEMA L6-30P (24) C13 5 kW 2U

EA-3461-C EA-3461-E EA-3461-CE 30A NEMA L6-30P (18) C13 + (6) C19 5 kW 2U

EA-3478-C EA-3478-E EA-3478-CE 30A NEMA L6-30P (6) C13 + (12) C19 5 kW 2U

120/208 Volt, Single-Phase Input

EA-3469-C EA-3469-E EA-3469-CE 30A NEMA L14-30P (12) C13 + (6) C19 + (4) 5-20 5 kW 2U

EA-3439-C EA-3439-E EA-3439-CE 20A NEMA L21-20P (24) C13 5.7 kW 2U

EA-3463-C EA-3463-E EA-3463-CE 20A NEMA L21-20P (18) C13 + (6) C19 5.7 kW 2U

EA-3480-C EA-3480-E EA-3480-CE 20A NEMA L21-20P (6) C13 + (12) C19 5.7 kW 2U

EA-3467-C EA-3467-E EA-3467-CE 20A NEMA L21-20P (12) C13 + (6) C19 + (4) 5-20 5.7 kW 2U

EA-3440-C EA-3440-E EA-3440-CE 30A NEMA L21-30P (24) C13 8.6 kW 2U

EA-3464-C EA-3464-E EA-3464-CE 30A NEMA L21-30P (18) C13 + (6) C19 8.6 kW 2U

EA-3482-C EA-3482-E EA-3482-CE 30A NEMA L21-30P (6) C13 + (12) C19 8.6 kW 2U

EA-3468-C EA-3468-E EA-3468-CE 30A NEMA L21-30P (12) C13 + (6) C19 + (4) 5-20 8.6 kW 2U

EA-3441-C EA-3441-E EA-3441-CE 30A NEMA L15-30P (24) C13 8.6 kW 2U

EA-3465-C EA-3465-E EA-3465-CE 30A NEMA L15-30P (18) C13 + (6) C19 8.6 kW 2U

EA-3483-C EA-3483-E EA-3483-CE 30A NEMA L15-30P (6) C13 + (12) C19 8.6 kW 2U

EA-3484-C EA-3484-E EA-3484-CE 50A CS8365 (6) C13 + (12) C19 14.4 kW 2U

EA-3485-C EA-3485-E EA-3485-CE 60A IEC 60309 60A 3P+E (6) C13 + (12) C19 17.2 kW 2U

Monitored eConnect PDU, Horizontal - Worldwide

Form Factor

(U) Height

Black* Glacier White* Redundancy

EA-3405-C EA-3405-E EA-3405-CE 16A C20 Inlet to IEC 60309 16A 1P+N+E (24) C13 3.8 kW 3.8 kW 2U

EA-3460-C EA-3460-E EA-3460-CE 16A C20 Inlet to IEC 60309 16A 1P+N+E (18) C13 + (6) C19 3.8 kW 3.8 kW 2U

EA-3406-C EA-3406-E EA-3406-CE 32A IEC 60309 32A 1P+N+E (24) C13 7.7 kW 6.1 kW 2U

EA-3462-C EA-3462-E EA-3462-CE 32A IEC 60309 32A 1P+N+E (18) C13 + (6) C19 7.7 kW 6.1 kW 2U

EA-3479-C EA-3479-E EA-3479-CE 32A IEC 60309 32A 1P+N+E (6) C13 + (12) C19 7.7 kW 6.1 kW 2U

220 - 240/380 - 415 Volt, Three-Phase Input

EA-3442-C EA-3442-E EA-3442-CE 16/20A IEC 60309 16/20A 3P+N+E (24) C13 11.5 kW 11.5 kW 2U

EA-3466-C EA-3466-E EA-3466-CE 16/20A IEC 60309 16/20A 3P+N+E (18) C13 + (6) C19 11.5 kW 11.5 kW 2U

EA-3481-C EA-3481-E EA-3481-CE 16/20A IEC 60309 16/20A 3P+N+E (6) C13 + (12) C19 11.5 kW 11.5 kW 2U

EA-3486-C EA-3486-E EA-3486-CE 32A IEC 60309 32A 3P+N+E (6) C13 + (12) C19 23 kW 18.4 kW 2U

Notes: * Shipping weight for each unit is 23 lb (10.4 kg) **Redundancy Pack includes 2 PDUs in Black and Glacier White for easy identification of the primary and secondary unit; shipping weight is 45 lb (20.4 kg)

8 Chatsworth Products

PLUG/INLET TABLE

NEMA L5-20P

110-125 VAC/20A

NEMA L6-30P

200-240 VAC/30A

Single-Phase/ Locking

Three-Phase/

NEMA L5-30P

110-125 VAC/30A

NEMA L6-20P

200-240 VAC/20A

NEMA 5-20R

120 VAC/20A

IEC C13

UL: 120/208VAC/15A

CE: 208VAC/10A

IEC C19

UL: 120/208VAC/20A

CE: 208VAC/16A

POWER RECEPTACLE/OUTLET TABLE

Receptacles/ Outlets

NEMA L15-20P

208 VAC/20A

NEMA L15-30P

208 VAC/30A

NEMA L21-20P

120/208 VAC/20A

NEMA L21-30P

120/208 VAC/30A

NEMA L22-20P

380/415 VAC/20A

NEMA L22-30P

380/415 VAC/30A

50A CS8365

208 VAC/50A*

Power Inlet Universal/

IEC C20

110/125 VAC/20A

IEC C20

200/240 VAC/20A

IEC 16A 1P+N+E

200/240 VAC/16A

IEC 32A 1P+N+E

200/240 VAC/32A

IEC 16A 3P+N+E

230/400 VAC/16A

IEC 32A 3P+N+E

230/400 VAC/32A

* Note: 50A CS8365 is rated for 50A, but maximum input is 35A on three-breaker PDUs.

60A CS8365

208 VAC/60A*

ACCESSORIES

Extended Limited Warranties Extended Limited Warranties on CPI-Branded Electronic products, available for two additional years beyond the expiration of the Original Warranty Period (3 years).

Contact CPI Customer Service, or visit chatsworth.com/warranty for more information.

Part Number

Description

L1-2YEXTWAR-ELECTRONICS-C 2-Year Warranty Extension for PDUs with MSRP up to $1700

L2-2YEXTWAR-ELECTRONICS-C 2-Year Warranty Extension for PDUs with MSRP $1701 - $3400

L3-2YEXTWAR-ELECTRONICS-C 2-Year Warranty Extension for PDUs with MSRP > $3400

For a complete list of eConnect PDU models, visit chatsworth.com/power

While every effort has been made to ensure the accuracy of all information, CPI does not accept liability for any errors or omissions and reserves the right to change information and descriptions of listed services and products.

©2021 Chatsworth Products, Inc. All rights reserved. Chatsworth Products, Clik-Nut, CPI, CPI Passive Cooling, CUBE-iT, Secure Array, eConnect, Evolution, GlobalFrame, MegaFrame, QuadraRack, RMR, Saf-T-Grip, SeismicFrame, SlimFrame, TeraFrame, Motive and Velocity are federally registered trademarks of Chatsworth Products. EuroFrame, Simply Efficient and ZetaFrame are trademarks of

Chatsworth Products. All other trademarks belong to their respective companies. Rev4/0421 MKT-60020-726

Simplify ordering, shipping and installation by requesting eConnect PDUs to be installed in CPI's ZetaFrame Cabinets before they leave the factory. Request Redundancy Pack for easy identification of primary and secondary units.

ACCESSORIES

Additional Accessories

Shipping Weight lb (kg)

14665-001 USB Temperature and Humidity Sensor 3 (1.4)

POWER MANAGEMENT, ENVIRONMENTAL MONITORING

AND PHYSICAL SECURITY INTEGRATION

eConnect® RFID Electronic Lock Kit Integrate cabinet access control along with power management and environmental monitoring under a single network connection, one user interface and one user database for dramatically reduced deployment savings. Fully compatible with DCIM software. Available on vertical Monitored, Monitored Pro, Switched and Switched Pro eConnect PDUs.

Shipping Weight lb (kg)

14666-001 eConnect® RFID Electronic Lock Kit For GlobalFrame and TeraFrame cabinet systems 3 (1.4)

USB Temperature and Humidity Sensor Attaches to the USB port in the PDUs.

Power IQ® (PIQ) for eConnect Power IQ® is a data center energy, power, environmental and access control monitoring software that provides out-of-the-box support for eConnect PDUs, Networked Control Module as well as devices from many other manufacturers.

Power IQ for eConnect Software and License, With 1-Year Maintenance Plan

Number Number of Licenses Part

Number Number of Licenses

36603-001 Up to 10 Devices 36603-020 Up to 200 Devices 36603-002 Up to 20 Devices 36603-030 Up to 300 Devices 36603-005 Up to 50 Devices 36603-040 Up to 400 Devices 36603-010 Up to 100 Devices 36603-050 Up to 500 Devices power Order locks and PDUs preinstalled into your cabinet.

Add power. Make it easy.

http://chatsworth.com/power

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 1

User Manual for eConnect®

PDU and

Electronic

Lock Kit

Reference Sales Model EA-XXXX

Regulatory Model K-XXXX

Version 4

May 2021

While every effort has been made to ensure the accuracy of all information, CPI does not accept liability for any errors or omissions and reserves the right to change information and descriptions of listed services and products.

©2021 Chatsworth Products, Inc. All rights reserved. Chatsworth Products, Clik-Nut, CPI, CPI Passive Cooling, eConnect, Evolution, GlobalFrame, MegaFrame, Motive, QuadraRack, RMR, Saf-T-Grip, Secure Array, SeismicFrame, SlimFrame, TeraFrame and Velocity are federally registered trademarks of Chatsworth Products.

CUBE-iT, EuroFrame, Simply Efficient and ZetaFrame are trademarks of Chatsworth Products.

All other trademarks belong to their respective companies. Rev4. 04/21 MKT-60020-720 800-834-4969 chatsworth.com techsupport@chatsworth.com http://www.chatsworth.com/

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 2

TABLE OF CONTENTS

INTRODUCTION

PRODUCT FEATURES

PRODUCT LABELING AND CERTIFICATIONS

PDU MODELS

INSTALLATION CHECKLIST

INSTALLATION GUIDE

USING THE LOCAL DISPLAY

MONITORING PDU CONDITIONS

NETWORK CONFIGURATION

DISPLAY SETUP

PDU SETTINGS

UPDATE FIRMWARE

PDU MODEL INFORMATION

USING THE BUILT-IN WEB SERVER (GUI) APPLICATION

OUTLETS – GROUPS

CABINET ACCESS – OVERVIEW

CABINET ACCESS – SETTINGS

CABINET ACCESS – RADIUS CARD SETTINGS

LOGGING – OVERVIEW

LOGGING – EXPORT LOGS

LOGGING – SETTINGS

NOTIFICATIONS - THRESHOLDS

NOTIFICATIONS - ROUNTING

SETTINGS – PDU

SETTINGS – PDU - CLONE

SETTINGS - ENVIRONMENTAL

SETTINGS – NETWORK

SETTINGS – SNMP

SETTINGS – EMAILS

ADMINISTRATION – USER MANAGEMENT

ADMINISTRATION – RADIUS AUTHENTICATION

ADMINISTRATION – LDAP AUTHENTICATION

ADMINISTRATION – ADVANCED

ADMINISTRATION – UPGRADE FIRMWARE

CONFIGURE IP ADDRESS USING SERIAL CONNECTION

AND CLI

BUILT-IN SOFTWARE FEATURES

TROUBLESHOOTING GUIDE

REPLACING THE CONTROLLER MODULE

APPENDIX

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 3

INTRODUCTION

User Manual for eConnect PDU and Electronic Lock Kit This document is the User Manual for CPI eConnect Power Distribution Units (PDUs)

(Sales Models EA-XXXX, Regulatory Model K-XXXX) and Electronic Lock Kit.

©2021 Chatsworth Products, Inc. All rights reserved.

UL Listed for use in U.S. and Canada.

Legal Information The information contained in this guide is subject to change without notice.

Chatsworth Products, Inc. (CPI) shall not be liable for technical or editorial errors or omissions contained herein; nor is it liable for any injury, loss, or incidental or consequential damages resulting from the furnishing, performance or use of this material and equipment.

Warranty CPI warrants all CPI-branded hardware products to be free from defects in material and/or workmanship (CPI’s Standard Limited Warranty) for a period of three (3) years following the date of purchase (the Original Warranty Period).

The customer must contact CPI in writing or by oral communication confirmed in writing within the Original Warranty Period to report a product that the customer claims is defective. CPI reserves the sole and absolute right to determine whether or not the product or any part thereof is defective. In the event a product (or any part thereof) is determined by CPI to be defective (an Accepted Claim), CPI will provide a re-manufactured or replacement product or part (the Replacement Product) at no cost to the customer and issue a Return Material Authorization (RMA) number.

Extended Limited Warranty CPI Extended limited warranties on CPI-Branded Electronic and Non-Electronic hardware products are available for two additional years beyond the expiration of the Original

Warranty Period (3 years). CPI’s Extended Limited Warranty can be purchased concurrently with, or separately from, the initial purchase of the product until the expiration of the Original Warranty Period for that product.

For more information on CPI Warranties, visit the website.

Nomenclature

PDU: eConnect Power Distribution Unit product

Socket/Receptacle/Outlet: Electrical output port

Secure Array®: Connects up to 48 PDUs (or 32 PDUs, if integrated with RFID electronic locks) under one IP address. A second connection provides failover capability, allowing linked PDUs to stay connected when one loses functionality.

Locking Outlet: PDUs with locking IEC C13 and C19 outlets that secure equipment power cords to vertical PDUs to prevent accidental disconnections.

Primary Role: The role that is assigned to the PDU that is attached to the network and serves as the beginning of the Secure Array. This PDU should have a level of functionality that is equal to or higher than that of all the remaining

PDUs within the array. In an array with several PDUs with the highest level of http://www.chatsworth.com/warranty/

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 4 functionality, the PDU with the most outlets among this group should be assigned the Primary Role.

Secondary Role: The role assigned to a PDU that is 1) linked to the primary PDU, or

2) a standalone PDU.

Alternate Role: The role assigned to the PDU that is connected to the network to provide a backup network connection if the Primary Role PDU loses power. This

PDU must be equivalent to the Primary PDU in functionality and number of outlets.

PRODUCT FEATURES

Vertically Mounted PDUs:

Physical Dimensions: refer to product cut sheet at www.chatsworth.com

Input Voltage:

100 – 415 Volts, varies by part number Output Voltage:

100 – 240 Volts, varies by part number

Input/Output Configurations: Please refer to the cut sheet for the specific model available at chatsworth.com

Power Input Cable:

Length: Standard: 10 ft (3 m) Gauge: 6 – 12 AWG, varies by part number Plug type: Current, Voltage and Configuration dependent, varies by part number. Some PDUs have an IEC C20 Input.

Circuit Breakers:

Type: Single or Double Pole Electro-hydraulic UL489 listed Breakers Quantity: One, two, three or six, varies by part number Rating: 20 Amp

Receptacles:

Types: NEMA, IEC, varies by part number Quantity: Varies by part number Rating: C13: 10 Amp, C19: 16 Amp; 5-20R: 16 Amp, varies by part number

Mounting style: 2 x Tool-less Buttons on the PDU rear cover Distances: 61.25” (1556 mm) and 64.75” (1645 mm) apart Positions: 4 mounting positions (A1, A2, B1, B2)

Single-phase unit. Actual information displayed may vary depending on whether the unit is single- or three-phase.

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 5

Field-replaceable Main Control Module

The Main Control Module can be replaced at the customer site without having to return the entire PDU

LCD local display with push button control:

(currently not available on horizontal models)

Dimension: 1.5” x 2.0” (38 mm x 51 mm)

Resolution: 240 x 320

Proprietary Auxiliary ports:

For Electronic Lock Kit or other peripherals Connector type: (2) RJ45 Aux1: For rear door Aux 2: For front door

Console 2 port:

Console 2 is a Micro USB connection.

Same functions as Console 1.

Note: This is the port used for CLI connection. For CLI connection you must use a standard YOST cable. Refer to Appendix

Ethernet port:

Connector type: (1) RJ45 Speed:

10/100/1000 Megabit/sec

Support: IPv6; IPv4; SNMP v1, v2, v3 Note: If using the 10/100/1000MB Ethernet port at a 1000MB (Gigabit) speed, please use shielded Ethernet cables only.

Console 1 port:

RJ45 YOST serial connection.

The Console1 is typically connected via a Cable – RJ45 YOST connector (PDU) to a DB-9 connector (PC)

Note: This is the port used for CLI connection. For CLI connection you must use a standard YOST cable. Refer to Appendix

USB ports Quantity: 2 USB-A

Function: CPI Firmware upgrades

Temp/Humidity sensor will be plugged into either standard USB1 or

USB2 port

Secure Array/PDU Linking/Serial Port:

Connector type: (2) RJ45

(1) link-in/serial port

(1) link-out port for Secure Array PDU linking using a Cat 5/6 cable

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 6

Horizontally Mounted PDUs:

Physical Dimensions: refer to product data sheet at chatsworth.com

Input Voltage:

100 – 415 Volts, varies by part number Output Voltage:

100 – 240 Volts, varies by part number

Input/Output Configurations: Please refer to the cut sheet for the specific model available at chatsworth.com

Power Input Cable:

Length: Standard: 10’ (3 m) Gauge: 6 – 12 AWG, varies by part number Plug type: Current, Voltage and Configuration dependent, varies by part number.

Some PDUs have an IEC C20 Input.

Circuit Breakers:

Type: Single or Double Pole Electro-hydraulic UL489 listed Breakers Quantity:

One, two, three or six, varies by part number Rating: 20 Amp

Receptacles:

Types: NEMA, IEC, varies by part number Quantity: Varies by part number Rating: C13: 10 Amp, C19: 16 Amp; 5-20R: 16 Amp, varies by part number

Mounting style: 19” EIA mounting brackets attach to cabinet or rack equipment mounting rails.

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 7

Field-Replaceable Main Control Module

The field-replaceable controller module can be replaced at the customer site without having to return the entire PDU

Proprietary Auxiliary ports: For Electronic Lock Kit or other peripherals

Aux1: For rear door Aux 2: For front door

Console 2 port: Console 2 is a Micro USB connection.

Same functions as Console 1.

Note: This is the port used for CLI connection. For CLI connection you must use a standard YOST cable. Refer to Appendix

Ethernet port: Connector type: (1) RJ45 Speed: 10/100/1000 Megabit/sec Support: IPv6; IPv4; SNMP v1, v2, v3 Note: If using the 10/100/1000MB Ethernet port at a 1000MB (Gigabit) speed, please use shielded Ethernet cables only.

Before connecting the PDU to the network, view the Network Configuration Page for instructions.

Console 1 port: RJ45 YOST serial connection.

The Console1 is typically connected via a Cable – RJ45 YOST connector (PDU) to a DB-9 connector (PC)

Note: This is the port used for CLI connection. For CLI connection you must use a standard YOST cable. Refer to Appendix

USB ports Quantity: 2 USB-A

Function: CPI Firmware upgrades

Temp/Humidity sensor will be plugged into either standard USB1 or USB2 port

Secure Array/PDU Linking/Serial Port:

(1) link-in/serial port

(1) link-out port for Secure Array PDU linking using a Cat 5/6 cable

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 8

PRODUCT LABELING AND CERTIFICATIONS

The presence of the CE Mark on equipment means that it has been designed, tested and certified as complying with all applicable

European Union (CE) regulations and recommendations.

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Samples of this product met UL's safety requirements for US and

Canada.

Do not dispose this product as unsorted municipal waste.

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 9

PDU MODELS

Tip: See how much savings you can obtain by taking advantage of the https://www.chatsworth.com/en-us/resources/configurators-and-estimators/estimator-page

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 10

INSTALLATION CHECKLIST

Safety Warnings and Cautions

• DO NOT OPEN THE CHASSIS of an eConnect PDU. There are no user serviceable parts within an eConnect PDU, except for eConnect Controller Module. Opening or removing covers, receptacle plates, or other access points may expose you to dangerous shock hazards or other risks. Refer all servicing to qualified service personnel.

• Do not spill any liquids on the chassis.

• Do not insert objects of any kind into the eConnect chassis via vent holes or any openings as they may contact dangerous voltage points, which can be fatal or cause harmful electric shock, fire or equipment failure.

• Do not place any heavy objects on the power cord. Damage to the cord may cause shock or fire.

• PDU must be installed VERTICALLY in a RESTRICTED ACCESS LOCATION.

• RESTRICTED ACCESS LOCATION: location for equipment where both of the following apply:

• Access can only be gained by SERVICE PERSONS or by USERS who have been instructed about the reasons for the restrictions applied to the location and about any precautions that shall be taken

• Access is using a TOOL or lock and key, or other means of security, and is controlled by the authority responsible for the location.

• Hot surface warning label: The equipment may be hot under full load.

• If using the 10/100/1000MB Ethernet port at a 1000MB (Gigabit) speed, please use shielded Ethernet cables only.

Checklist for Electronic Lock Kit:

• Connect wires between latch and CAN bus module

• Connect wires between sensors and CAN bus module

• Connect wires between CAN bus and PDU. Aux 1 should be connected to the rear door’s CAN module. Aux 2 should be connected to the front door’s CAN module.

• Login to the web GUI using the default login information of “admin/admin”, and navigate to the “Cabinet Access – Settings” page.

• Select the checkbox for the appropriate lock you wish to enable, and click “Save”

• The lock is powered when you see a continuous blue light on the lock. At this point you should be able to refresh the web page and see the status update appropriately.

• Program the Card Reader and Smart Card ID (Go to APPENDIX for Electronic

Lock Kit for eConnect for detailed information).

• Use the web GUI to change cabinet access and logging settings (Cabinet

Access and Logging tabs respectively)

• The light will flash magenta/blue when the latch opens

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 11

INSTALLATION GUIDE

Preparation:

• Prepare a plan identifying where each rack device is to be connected to the

PDU receptacle. For ease of power cord management, if you are installing a vertically mounted PDU, it is recommended to connect the rack device to the receptacle that is approximately at the same height.

• When using in North America, regulatory rating of input is de-rated to 80% of input plug. Please use a breaker with corresponding rating upstream of the

PDU.

o 20 A for PDU Input current rated 16 A o 30 A for PDU Input current rated 24 A o 40 A for PDU input current rated 32 A o 60 A for PDU input current rated 48 A o 80 A for PDU input current rated 64 A o 100 A for PDU input current rated 80 A

• It is recommended to retain the PDU Ethernet Hardware Address (MAC address) available through the LCD display under PDU Info. It’s recommended to record the PDU name, rack/cabinet name, location and MAC address for future reference.

• If the rack device has more than 1 input for power for purpose of redundancy, the power cables should be connected to different PDUs.

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 12

Locking Outlets:

The locking receptacles feature a locking lever that engages with IEC corded plugs.

To engage, insert the IEC plug into the receptacle until you hear a click. Ensure the locking lever is engaged by squeezing the lever and IEC plug together.

To disengage, pull the locking lever away from the IEC plug until it holds in the open position. Then, disengage the IEC plug from the receptacle. If the locking lever does not hold open, use one of your fingers to hold it open as you disengage the IEC plug.

External Connections:

1. Install the PDU into the cabinet and secure the PDU external ground wire to the cabinet ground stud.

2. Optional: Ethernet Port: Before connecting to LAN, go to the Network

Configuration page for instructions. Use CAT5/6 cable. Note: If using the 10/100/1000MB Ethernet port at a 1000MB (Gigabit) speed, please use shielded Ethernet cables only.

3. Optional: Environmental Probe Port.

a. Use USB Temperature and Humidity Sensor (P/N 14665-001) and attach to any of the USB ports.

4. Optional: Out Port: For Secure Array when linking PDUs.

a. Use a standard CAT5/6 cable.

5. Optional: USB Port: For firmware upgrades use USB Flash Drive.

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 13

Energizing the PDU

• Attach the input power cord to a matching power source.

• The PDU status light will blink Green for about 90 seconds as the PDU is booting up.

• A solid Green status light will follow with the LCD display coming on and displaying all zeroes.

• Once the PDU is energized, connect cabinet devices to their respective outlets.

USING THE LOCAL DISPLAY

Vertical eConnect PDUs include a multifunctional LCD display has a 240 x 320 pixel resolution and can be navigated by three soft buttons located immediately above the display.

The local interface can display the following information:

• Sum of current, voltage and power values for single-phase PDUs

• Line input current and sum of voltage and power values on three-phase PDUs

• Current, voltage, power and power factor values per branch breaker

• Temperature and humidity values when optional environmental sensors are attached

• Per outlet current on Monitored Pro and Switched Pro models

• Alarm notification when predefined warning or critical thresholds are reached

The local interface can also be used to set up many functions of an eConnect PDU as following:

• Network IP setup (v4 and v6)

• Display settings – brightness, timeout, orientation

• PDU role (primary or secondary)

• PDU info

Actual Informatin displayed may vary depending on whether the unit is single- or three-phase.

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 14

Basic Menu Navigation

The legend below explains the meaning of each button on the PDU display:

Menu button/icon definitions and functions

Go to the Main Menu.

Note: In PDUs in the Secure Array, the blue icon — —turns green—

Note: The home icon turns purple during a firmware upgrade—

Select the highlighted menu item.

Go to Setup menu.

Move highlighted menu item down or to the right.

Move highlighted menu item up or to the left.

Actual Informatin displayed may vary depending on whether the unit is single- or three-phase.

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 15

MONITORING PDU CONDITIONS

The main screen on single-phase PDUs list total amperage, voltage and power usage by equipment attached to the PDU. The main screen on three phase PDUs lists total voltage and power usage by equipment attached to the PDU.

Single-phase PDU Three-phase PDU

From the Main menu press:

Left button to set up the PDU Middle button to view the next screen

Right button to go back to the Main Menu

The following screen(s) list branch circuit values (CB1, CB2 or XY, YZ, ZX). There is one screen per phase/branch.

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 16

Middle button to scroll through the remaining screens

After scrolling through the branch/phase screens, the PDU will display the Environment summary screen. USB Temperature and Humidity Sensor (P/N 14665-001) must be attached to the PDU for environmental values to display.

Middle button to view next data screen. This will return to the PDU Total screen

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 17

On Monitored Pro and Switched Pro PDUs, the following screen(s) list total current use for each outlet. Eight outlets are listed on each screen.

Middle button to go to the next data screen

Alarms When any alarm or warning threshold is hit, the Alarms summary will be displayed before the PDU Total values when the Home Icon is selected.

Color codes:

Text with Yellow background: Warning condition was reached.

Text with Red background: Critical condition was reached.

Left button to access the setup menu Middle button to view additional summary screens

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 18

Additionally, when there is an alarm, the out-of-range measurements are highlighted on the respective summary screen, and the LED next to the display will flash.

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 19

NETWORK CONFIGURATION

Using DHCP The default setting for the PDU is enabled for DHCP. The default address is 192.168.123.123.

Contact your network administrator to obtain the IP address assigned to the PDU by the DHCP server. To obtain the IP address for the PDU assigned by DHCP server, the PDU must be rebooted (go to PDU Settings to reset device).

To change network configuration using the LCD display, follow the instructions below. If the

PDU does not have an LCD display, change network configuration using Command Line

Interface (CLI).

Left button to traverse down the list of options Middle button to select the highlighted option Right button to traverse up the list of options

Select Exit to exit this screen

Click on middle button to set up

IPv4 Network

Middle button to select the highlighted option

Select Save or Cancel to exit this screen Save updates IP information immediately Cancel makes no changes to the setup

Return to the Setup Menu

The image above is an example of the address given to the PDU by the DCHP server.

To use Zero Touch Provisioning (ZTP) with DHCP, go here.

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 20

Using Static IP Address Make sure to switch the DHCP option to “NO”, then follow the instructions below.

Select the Left Button to access the PDU Setup Menu

Middle button to select the highlighted option

Select Exit to exit this screen

IPv4 Network

Middle button to select the highlighted option Right button to traverse up the list of options

Save updates IP information immediately Cancel makes no changes to the setup

Return to the Setup Menu

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 21

Use the Left Button to select IPv6 Network.

IPv6 Network Use the Left Button to select IPv6 Network

• Select Save or Cancel to exit this screen

• Save updates IP information immediately

• Cancel makes no changes to the setup

• Make sure the settings are “YES” for Enable and “NO” for DHCP, then enter the PDU

Address and Netmask

• Select Save or Cancel to exit this screen

• Save updates IP information immediately

• Cancel makes no changes to the setup

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 22

DISPLAY SETUP

Return to the Setup Menu.

Use the Left button to select Display.

Click on middle button to set up the Display

Click on:

Left button to traverse down the list of options Middle button to select the highlighted option Right button to traverse up the list of options

Timeout – Controls how long display remains on (minutes) Brightness – Controls display brightness (1-9) Input Cord – Controls display orientation (TOP or BOT input cord location). This rotates the display 180° so that it can be easily read regardless of whether the PDU is mounted with the cord toward the top or bottom of the cabinet. The display will automatically orient on power up.

Outlet – Controls whether individual outlet current measurements are displayed (Show or Hide) on Monitored Pro and Switched Pro models

Save updates IP information immediately Cancel makes no changes to the setup

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 23

PDU SETTINGS

Return to the Setup Menu.

Use the left button to select PDU Settings.

Click on middle button to set up advanced info for the PDU

Optional - Click on:

Role – There are three roles for the PDU: Secondary, Primary and Alternate. Secondary is the default role.

Choose PRIMARY if PDU is the FIRST PDU in a Secure Array. Only one PDU may be Primary, and this must be the PDU with the highest level of functionality and highest number of outlets within that functionality. Choose ALTERNATE if the PDU will be a backup to the Primary. Only one PDU may be ALTERNATE, and this PDU must match the functionality and outlet quantity of the Primary in order to fully support the array. Otherwise keep or choose SECONDARY. See Network Settings for additional details.

Temp – Choose Celsius or Fahrenheit Restore Defaults – Choose to select which fields will be restored (confirmation needed, see details on the next page) Update FW – Choose to update firmware locally through USB port

Save – Confirm all changes made in this session Cancel – Cancel all changes made in this session

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 24

Network Only – Will immediately reset the IP address back to the default address (192.168.123.123) with DCHP enabled, and reboot the main communications module.

Outlets will not lose power, but you will lose your network connection and monitoring during reboot.

Config Only – Will immediately reset PDU and outlet names, alarm thresholds, etc. back to defaults, and reboot the main communications module. Outlets will not lose power, but you will lose your network connection and

User Only – Will immediately delete all accounts except the default administrative user account:

User Name: “admin”, Password: “admin”, and reboot the main communications module.

Outlets will not lose power, but you will lose your network connection and monitoring during reboot.

Reset All – Resets Network, Config and User values to defaults, the main communications module.

Outlets will not lose power, but you will lose your network connection and monitoring during reboot.

Reset Device – Only reboots the main communications module. No values are reset to default. Outlets will not lose power, but you will lose your network connection and

Note: The physical reset pin under the screen will Reset Device and erase all local memory, including the date of the log file.

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 25

UPDATE FIRMWARE

Click on middle button to update firmware for the PDU.

Left button to traverse down the list of options

Sample of Updating screen Sample of Failed updating

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 26

PDU MODEL INFORMATION

Click on middle button to traverse back to the PDU Settings Menu.

Click on middle button to traverse back to the PDU Settings

Menu.

Note: The P/N shown is the Regulatory Model number found on the UL label in the back of the unit.

CPI User Manual for eConnect PDU and Electronic Lock Kit 05/21.v4 27

USING THE BUILT-IN WEB SERVER (GUI) APPLICATION

Login

To access the PDU using the web GUI, connect the Ethernet port to a network switch.

The default setting for the PDU is enabled for DHCP.