Attachment 03_Drawing Set 1 USFS Site and Details - FY25.pdf
PDF 3 MB Posted
- Attached to
- Pagosa Ranger District Security Upgrade
- Solicitation number
- 1145939
- Issued by
-
Department of Agriculture Forest Service
About this file
The file is a detailed architectural drawing set for the Pagosa Ranger District (RD) Security Upgrade project, consisting of 16 technical sheets documenting proposed security improvements to the Forest Service office located at 180 Pagosa Street in Pagosa Springs, Colorado. The drawing set provides comprehensive plans for security enhancements, including architectural floor plans, elevations, electrical, HVAC, hydronic, and plumbing details.
Key proposed security upgrades include installing 1-hour rated walls in the existing lobby, two interior security doors with Lenel card readers, an electronic locking mechanism for the front door, optional security cameras, and integration with the existing building security system. The drawings specify technical details such as door dimensions (36" security doors with windows), card reader placements, and optional camera locations. The project aims to create a physical separation between the public lobby and staff areas, addressing safety concerns from increased visitor traffic. The drawings are dated October 4, 2023, with recent updates on May 16, 2024, and are prepared for the USDA Forest Service, Rocky Mountain Region, San Juan National Forest.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 02_SOW - Pagosa RD Security Ugrade.pdf | ||
| Attachment 01_Schedule of Items SOI - Pagosa RD Security Upgrade.xlsx | XLSX spreadsheet | |
| SF 1449 1282B125Q0015.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FOREST LOCATION MAP
PROJECT LOCATION MAP
TRAVEL DIRECTIONS:
SHEET OF
United States Department of Agriculture
Forest Service
PAGOSA RANGER DISTRICT (RD)
THE SITE IS LOCATED IN THE TOWN OF PAGOSA SPRINGS, CO. FROM THE CENTER OF MAIN STREET IN PAGOSA SPRINGS, GO EAST ON US-160 (MAIN STREET) FOR APPROXIMATELY 0.6 MILES. THE OFFICE BUILDING WILL BE ON THE LEFT-HAND SIDE OF THE ROAD. THE SITE COORDINATES ARE 37.269087303790556, -107.0048722195328. THE ADDRESS IS 180
PAGOSA ST. PAGOSA SPRINGS, CO, 81147.
SECURITY UPGRADE
RECOMMENDED BY:
APPROVED:
FOREST ENGINEER
DISTRICT RANGER
DATE
DATE
DIRECTOR OF ENGINEERING DATE
FOREST SUPERVISOR DATE
RO FACILITIES PROGRAM MANAGER DATE
/29
/23
:0 4 T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
CA
D\
PA
GO
S
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.29 .23
.D W
G;
COLORADO
ARCHULETA COUNTY
R02 - ROCKY MOUNTAIN REGION
SAN JUAN NATIONAL FOREST
PAGOSA RANGER DISTRICT
INDEX OF SHEETS
SHEET SHEET TITLE DATE
G-00 SITE OVERVIEW 11/29/2023
G-01 NORTH/SOUTH ELEVATIONS 11/29/2023
G-02 EAST/WEST ELEVATIONS 11/29/2023
G-03 EXISTING 1ST FLOOR PLAN VIEW 11/29/2023
G-04 PROPOSED 1ST FLOOR PLAN VIEW 11/29/2023
G-05 EXISTING LOBBY PLAN 11/29/2023
G-06 PROPOSED LOBBY PLAN 11/29/2023
G-07 PROPOSED LOBBY DIMENSIONS 11/29/2023
E-01 ELECTRICAL LEGEND 11/29/2023
E-02 EXISTING POWER PLAN VIEW 11/29/2023
E-03 LIGHTING PLAN VIEW 11/29/2023
M-01 MECHANICAL LEGEND 11/29/2023
M-02 HVAC PLAN VIEW 11/29/2023
M-03 HYDRONIC PLAN VIEW 11/29/2023
P-01 PLUMBING PLAN VIEW 11/29/2023
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
SITE OVERVIEW
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
G-00 02 16
· FIELD VERIFY ALL DIMENSIONS AND CONDITIONS. NOTIFY CONTRACTING
OFFICER REPRESENTATIVE (COR) IMMEDIATELY SHOULD CONDITIONS BE
FOUND CONTRADICTORY TO THESE DRAWINGS.
· BUILDING WILL BE OCCUPIED DURING CONSTRUCTION.
· EXISTING WALLS, ROOFS, FLASHING, ETC. THAT IS DAMAGED OR DISTURBED
DUE TO WORK SHALL BE REPAIRED, REPLACED SUCH THAT THEY CANNOT BE
DISTINGUISHED FROM THE NEW OR ADJACENT EXISTING SURFACES & FINISHES.
· OBTAIN COR APPROVAL OF ANY ELECTRICAL POWER OUTAGES NECESSITATED
BY CONSTRUCTION 48 HOURS PRIOR TO SHUT-DOWN.
· PATCH/REPAIR/REPLACE PAVED SURFACES AND LANDSCAPE MATERIALS THAT
ARE INDICATED TO REMAIN THAT ARE DAMAGED AS A RESULT OF
CONSTRUCTION ACTIVITIES.
· PROPERLY DISPOSE OF ALL CONSTRUCTION WASTE OFF SITE. RECYCLE ALL
RECYCLABLE ALL MATERIALS.
· THE CONTRACTOR WILL BE ABLE TO PARK, STORE MATERIALS, AND PLACE A
DUMPSTER IN THE AREA LABELED "VISITOR PARKING" IN THE ABOVE FIGURE
OUTLINED IN BLACK.
GENERAL NOTES
HOW TO READ AND USE GENERAL SYMBOLS IN THIS SHEET SET
GENERAL SYMBOLOGY
IMAGE NUMBER
IMAGE NUMBER
SHEET WHERE IMAGE IS LOCATED
SHEET WHERE IMAGE IS LOCATED
COMMENT DETAIL NUMBER
ARROW POINTING NORTHNORTH ARROW
DETAIL MARKER
IMAGE/ITEM TITLE
IMAGE/ITEM
DIRECTION MARKER
VIEWING DIRECTION
N
PAGOSA RANGER DISTRICT OFFICE - SITE OVERVIEW
SUMMARY OF WORK
EMPLOYEE
PARKING
VISITOR
PARKING
MAIN BUILDING
AND LOBBY
HWY 160
COURTYARD
· INSTALL VARIOUS 1-HR RATED WALLS IN EXISTING LOBBY ACCORDING TO THIS SHEET SET.
SECURE SILL PLATE TO THE SUB-FLOOR AND THE TOP PLATE TO CEILING TRUSSES.
DEMOLITION OF THE CEILING AND FLOOR TILE WILL OCCUR AS REQUIRED. ALL WALLS WILL BE
BUILT TO MATCH THE EXISTING WALLS OF THE BUILDING.
· INSTALL TWO (2) CONTRACTOR SUPPLIED INTERIOR SECURITY DOORS. DIMENSIONS OF DOORS
ARE OUTLINED IN THIS SHEET SET AND THE STATEMENT OF WORK (SOW). ALL DOORS WILL
HAVE A 20-MIN RATING, UTILIZE ACCESSIBLE LEVER-STYLE DOOR HANDLES, PUSH BARS, AND
HYDRAULIC DOOR CLOSERS TO MATCH THROUGHOUT BUILDING, AND WILL SWING AS SHOWN
IN THIS SHEET SET.
INSTALL LENEL CARD READERS FOR TWO OF THE CONTRACTOR SUPPLIED INTERIOR DOORS
AND ONE EXISTING EXTERIOR DOOR (BASE). INTEGRATE ALL NEW READERS WITH EXISTING
SYSTEM OF THE BUILDING. LENEL CARD READER LOCATIONS ARE SPECIFIED IN THIS SHEET
SET.
INSTALL FOUR (4) SECURITY CAMERAS AT THE LOCATIONS OUTLINED IN THIS SHEET SET
(OPTIONAL). SECURITY CAMERAS MUST COME EQUIPPED WITH MONITORING SOFTWARE THAT
IS COMPATIBLE WITH EXISTING USFS COMPUTERS OR OTHER USFS ELECTRONIC DEVICES
(PHONES/TABLETS). THE CONTRACTOR MUST WORK WITH COR IF INTEGRATION IS NOT
FEASIBLE. A MONITORING SYSTEM WILL BE INSTALLED IN THE FRONT DESK AREA WHILE THE
CONTROLS WILL BE INSTALLED IN THE SERVER ROOM.
· LENEL CABLES FOR DOOR CARD READERS WILL BE RUN TO THE SERVER ROOM TO CONNECT
TO THE EXISTING SYSTEM.
· INSTALL ONE (1) ELECTRONIC LOCKING MECHANISM FOR THE FRONT DOOR THAT CAN BE
REMOTELY TRIGGERED FROM THE FRONT DESK (BASE).
· PROVIDE ANY NECESSARY DEMOLITION FOR THE PROJECT.
· SUPPLY AND INSTALL ALL NECESSARY WIRING, BREAKERS, AND CONNECTIONS FOR CARD
READERS, SECURITY CAMERAS (OPTIONAL), AND REMOTE LOCK (BASE).
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text
XXX
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
XXX
SOUTH ELEVATION
NORTH ELEVATION
NEW WIDE ANGLE
SECURITY CAMERA (OPTIONAL)
NEW WIDE ANGLE
SECURITY CAMERA
(OPTIONAL)
NEW WIDE ANGLE
SECURITY CAMERA (OPTIONAL)
NEW LENEL CARD READER
FOR MAIN ENTRANCE (BASE)
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
NORTH/SOUTH
ELEVATIONS
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
G-01 03 16
Feet
0 10 20
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
E
EAST ELEVATION
WEST ELEVATION
NEW WIDE ANGLE
SECURITY CAMERA (OPTIONAL)
COMPOSITE CORNER
TRIM & FASCIA (TYP)
COMPOSITE LAP SIDING (TYP.)
STONE VENEER (TYP.)
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
EAST/WEST
ELEVATIONS
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
G-02 04 16
Feet
0 10 20
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
DN
UP
1 1 1
2 2 2
3" DIAMETER STEEL COLUMN
GLU-LAM BEAM ABOVE.
DN
DN
UP
TOP LEVEL BOTTOM LEVEL
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
EXISTING
1ST FLOOR PLAN VIEW
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
G-03 05 16
N
Feet
0 15 30
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
UP
TOP LEVEL BOTTOM LEVEL
DN
UP
1 1 1
2 2 2
3" DIAMETER STEEL COLUMN
GLU-LAM BEAM ABOVE.
36" SECURITY DOOR -
W/ WINDOW
1-HR RATED WALL
WIDE ANGLE
SECURITY
CAMERAS
(OPTIONAL)
SECURITY CAMERA
RANGE OF VIEW
(OPTIONAL)
LENEL CARD
READERS
REMOTE LOCK FOR
FRONT DOOR
(BASE)
WIDE ANGLE
SECURITY CAMERAS
(OPTIONAL)
SECURITY CAMERA
RANGE OF VIEW
(OPTIONAL)
EXTERIOR LENEL
CARD READER
(BASE)
SERVER ROOM WITH
SECURITY CONTROLS
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
PROPOSED
1ST FLOOR PLAN VIEW
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
G-04 06 16
N
Feet
0 15 30
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
3" DIAMETER STEEL COLUMN
GLU-LAM BEAM ABOVE.
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
EXISTING
LOBBY PLAN VIEW
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
G-05 07 16
N
Feet
0 5 10
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
3" DIAMETER STEEL COLUMN
GLU-LAM BEAM ABOVE.
1-HR RATED WALL
36" SECURITY DOOR -
W/ WINDOW
SECURITY CAMERA
RANGE OF VIEW
(OPTIONAL)
LENEL CARD
READERS
REMOTE LOCK FOR
FRONT DOOR
(BASE)
WIDE ANGLE
SECURITY CAMERAS
(OPTIONAL)
EXTERIOR LENEL
CARD READER
(BASE)
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
PROPOSED
LOBBY PLAN VIEW
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
G-06 08 16
N
Feet
0 5 10
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
GLU-LAM BEAM ABOVE.
0.71'
2.33'
0.59'0.66'
0.81'
1 3" DIAMETER STEEL COLUMN
NEW WALL - 1 HR RATED
EXISTING WALL
NEW SECURITY CAMERA
(OPTIONAL)
LEGEND
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
PROPOSED LOBBY
DIMENSIONS
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
G-07 09 16
N
Feet
0 5 10
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
ELECTRICAL LEGEND (NOTE: NOT ALL SYMBOLS SHOWN ARE USED ON THESE DRAWINGS)
SYMBOL - ABBREVIATIONS - - ABBREVIATIONS -
(E) EXISTING IG ISOLATED GROUND
JB JUNCTION BOX(N) NEW
(PART) PARTIAL CIRCUIT
+XX MOUNTING HEIGHT IN INCHES, AFF UNO
A AMP
AB AMPS BRACING
AC ABOVE COUNTER TOP
AF AMP FRAME
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPS INTERRUPTING CAPACITY
AS AMPS SENSOR
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
BFC BELOW FINISHED CEILING
C CONDUIT
CAM CONTROL ADDRESSABLE MODULE
CB MOLDED CASE CIRCUIT BREAKER
CCTV CLOSED CIRCUIT T.V.
CKT CIRCUIT
CLG CEILING
CO CONDUIT ONLY
CUH CABINET UNIT HEATER
DMC DUAL MODE CONTROLLER
DTB DATA TERMINAL BOARD
DTC DATA TERMINAL CABINET
E/G ENGINE/GENERATOR
EC EMPTY CONDUIT
EF EXHAUST FAN
K THOUSAND
LTG LIGHTING
LTS LIGHTS
LV LOW VOLTAGE
MAM MONITOR ADDRESSABLE MODULE
MATV MASTER ANTENNA TV
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCSW MOLDED CASE SWITCH
MDF MAIN DISTRIBUTION FRAME
MDP MAIN DISTRIBUTION PANEL
MH MANHOLE
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG MOUNTING HEIGHT
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NF NON FUSED
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
P POLE
PA PUBLIC ADDRESS
PB PULL BOX
PIV POST INDICATOR VALVE
PNL PANEL
PWR POWER
RCPT(S) RECEPTACLE(S)
ELEC ELECTRIC
ELEV ELEVATION
EM EMERGENCY
EMERG EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EP EXPLOSION PROOF
EWC ELECTRIC WATER COOLER
EX EXISTING
F FUSE
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
FACP FIRE ALARM CONTROL PANEL
FAP FIRE ALARM PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FTU FAN TERMINAL UNIT
G GROUND (EQUIPMENT)
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT CIRCUIT INTERRUPTER
GF GROUND FAULT INTERRUPTER
GND GROUND (EQUIPMENT)
HC HANDICAPPED
HG HOSPITAL GRADE
HP HORSEPOWER
HT HEAT TRACE
HV HIGH VOLTAGE
IC INTERRUPTING CAPACITY
INC INCANDESCENT
IDF INTERMEDIATE DISTRIBUTION FRAME
RF RETURN AIR FAN
SBC STRANDED BARE COPPER
SF SUPPLY AIR FAN
SO SPACE ONLY
SP SPARE
SPD SURGE PROTECTIVE DEVICE
ST SHUNT TRIP
SW SWITCH
T TRANSFORMER
TEL TELEPHONE
TF TRANSFER FAN
TTB
TV
UF UNDERFLOOR
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTAGE
VFD VARIABLE FREQUENCY DRIVE
VP VAPOR PROOF
VV VARIABLE VOLUME UNIT
W WIRE
WG WIRE GUARD
WP WEATHERPROOF
WT WATERTIGHT
XFMR TRANSFORMER
XP EXPLOSION PROOF
TELEPHONE TERMINAL BOARD
TELEVISION
COPYRIGHT OF THE RMHGROUP, INC. 2016
DESCRIPTIONSYMBOL
CIRCUIT BREAKER
DRAW-OUT CIRCUIT BREAKER (MOLDED INSULATED CASE)
DRAW-OUT POWER CIRCUIT BREAKER
CONTROL FUSE
FUSE WITH SWITCH
SWITCH
PANELBOARD
SPD OR MISC EQUIPMENT
AUTOMATIC TRANSFER SWITCH
FEEDER DESIGNATION, SEE FEEDER SCHEDULE
AUTOMATIC TRANSFER SWITCH WITH BY-PASS
ENGINE GENERATOR
TRANSFORMER
ENCLOSED BUSWAY
GROUND BUS
WEATHERHEAD
MOTOR
DELTA CONNECTION
WYE CONNECTION
GROUNDED WYE CONNECTION
GROUNDED WYE CONNECTION W/RESISTOR GROUND
GROUNDED WYE CONNECTION W/REACTOR GROUND
METERING DEVICE
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
LOAD-BREAK CONNECTOR
CONTACT NORMALLY OPEN
CONTACT NORMALLY CLOSED
SINGLE BATTERY
MULTIPLE BATTERIES
LIGHTNING ARRESTOR
THERMAL ELEMENT, OVERLOAD RELAY
BRANCH CIRCUIT HOME RUN TO PANELBOARD, DESIGNATION
INDICATES PANEL AND CIRCUIT NUMBERS.
CONTROL WIRING
LIGHTING, ONE-LINE, AND POWER CIRCUITING
LIGHTING, ONE-LINE, AND POWER CIRCUITING
(UNDERGROUND)
JUNCTION BOX
WALL MOUNTED JUNCTION BOX
FLOOR MOUNTED JUNCTION BOX
PUSH BUTTON
A = ABORT
DA = DURESS ALARM
EPO = EMERGENCY POWER OFF
IC = INTERCOM
ST = SHUNT TRIP
DUAL SWITCH
INTERCOM SWITCH
SPECIAL SYSTEMS SYMBOLS:
B = BUZZER
CH = CHIME
CK = CARD READER/KEYPAD
CR = CARD READER
DA = DURESS ALARM PUSH-BUTTON
DC = DOOR CONTACT
DO = DOOR OPERATOR
DS = DOOR STRIKE
EL = ELECTRIC LOCK
ES = ELECTRIC STRIKE
F = MANUAL PULL STATION
FS = FLOW SWITCH
GB = GLASSBREAK DETECTOR
HC = HANDICAP PUSH-BUTTON
IC = INTERCOM CALL STATION
KP = KEYPAD
MH = MANHOLE
MD = MOTORIZED DAMPER
MS = MOTION SENSOR
ML = MAGNETIC LOCK
OS = OCCUPANCY SENSOR
PA = PUBLIC ADDRESS
PB = PULLBOX
PM = POWER QUALITY METER
PS = PRESSURE SWITCH
R = REMOTE INDICATING LIGHT
RT = REMOTE TEST STATION
RX = REQUEST TO EXIT PUSH-BUTTON
S = WALL MOUNTED SPEAKER
TC = TIME CLOCK
TS = TAMPER SWITCH
VM = VIDEO MONITOR
VS = VACANCY SENSOR
DUPLEX RECEPTACLE
D = DEDICATED DUPLEX GROUNDED RECEPTACLE
IG = ISOLATED GROUND
GFI = GROUND FAULT CIRCUIT INTERRUPTER
FLOOR MOUNTED DUPLEX RECEPTACLE
FLOOR MOUNTED FOURPLEX RECEPTACLE
LUMINAIRES
# = BRANCH CIRCUIT NUMBER
* = SWITCH LEG IDENTIFIER
-LIGHTING (REFER TO LUMINAIRE SCHEDULE)-
SYMBOL DESCRIPTION
-GENERAL--ONE LINE SYMBOLS-
DESCRIPTION DESCRIPTION DESCRIPTION
-POWER- -GROUNDING SYMBOLS-
DESCRIPTION
DESCRIPTION
SHADING INDICATES LUMINAIRE ON LIFE SAFETY
SHADING INDICATES PORTION OF LUMINAIRE ON LIFE SAFETY
WALL MOUNTED LUMINAIRE
STRIP LIGHT
POLE MOUNTED LUMINAIRE
DOWNLIGHT LUMINAIRE
WALL WASHER LUMINAIRE
ADJUSTABLE LUMINAIRE
PENDANT LUMINAIRE
TRACK LIGHTING
PHOTOCELL
EXIT LIGHT (WITH FACES & DIRECTION ARROWS INDICATED)
WALL MOUNTED EXIT LIGHT (WITH FACES & DIRECTION
ARROWS INDICATED)
WALL MOUNTED BATTERY PACK EMERGENCY LIGHT
-FIRE ALARM DEVICES-
GROUND ROD WITH INSPECTION TEST WELL
PIGTAIL
-SPECIAL SYSTEMS DEVICES-
TELEPHONE TERMINAL BOARD
WALL MOUNTED VOLUME CONTROL
CLOCK RECEPTACLE OUTLET
SECURITY CAMERA
THERMOSTAT
ABORT BUTTON
SPD
PANEL
XXX
ATS
XXX
X
J
J
J
GFI
SYMBOL SYMBOL
SYMBOL
P
CEILING MOUNTED DUPLEX RECEPTACLE
CEILING MOUNTED FOURPLEX RECEPTACLE
CEILING MOUNTED SPECIAL PURPOSE RECEPTACLE
FOURPLEX RECEPTACLE
RANGE RECEPTACLE
SINGLE RECEPTACLE
SPECIAL PURPOSE RECEPTACLE
SWITCHED RECEPTACLE
DUPLEX EMERGENCY / CRITICAL
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
MOTOR STARTER
COMBINATION MOTOR STARTER
DISTRIBUTION PANEL
EXISTING DISTRIBUTION PANEL
NEW PANEL, FLUSH MOUNTED
EXISTING PANEL, FLUSH MOUNTED
NEW PANEL, SURFACE MOUNTED
EXISTING PANEL, SURFACE MOUNTED
COMBINATION SWITCH AND RECEPTACLE
CONDUIT SEAL OFF
FIRE RATED POKE-THRU
PARTITION CIRCUIT SPLIT
POWER POLE
SURFACE RACEWAY
METER
TRANSFORMER
W
M
T
FLOOR MOUNTED SPECIAL PURPOSE RECEPTACLE
E
100A4G
M
TX-XXXX
M
RESISTOR
2400V,100A
10SEC.
RESISTOR
CAPACITOR
SYMBOL
TTB
T
GROUND TEST WELL
GROUNDING CONDUCTOR
LIGHTNING PROTECTION AIR TERMINAL
BONDING POINT
GROUND BAR
ELECTRICAL GROUND
G
A
S
H
H
B
D
D
D
X
STRIP LIGHT WITH LIFE SAFETY
S
DELUGE VALVE
BELL
DUCT SMOKE DETECTOR
FIRE FIGHTER'S TELEPHONE JACK
COMBINATION FIRE HORN/STROBE LIGHT
COMBINATION FIRE SPEAKER/STROBE LIGHT
FIRE ALARM STROBE LIGHT
FIRE HORN
FIRE ALARM STROBE, CEILING MOUNT
DUAL PROJECTION FIRE HORN
ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH LOCAL BUILDING CODES AND THE
NATIONAL ELECTRICAL CODE (NEC).
CONTRACTOR SHALL REFERENCE SPECIFICATIONS FOR CONSTRUCTION MATERIALS AND
INSTALLATION PROCEDURES. SPECIFICATIONS ARE A PART OF THE CONSTRUCTION
DOCUMENTS. SHOULD ANY CONFLICT ARISE BETWEEN THE DRAWINGS AND SPECIFICATIONS,
SUCH CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER FOR
RESOLUTION.
THESE DRAWINGS ARE DIAGRAMMATIC IN CHARACTER AND DO NOT SHOW MATERIALS FOR A
COMPLETE INSTALLATION.
CONTRACTOR SHALL PLAN THE INSTALLATION AND LAYOUT THE WORK AS DIAGRAMMED IN THESE
DOCUMENTS. REFER TO THE FLOOR PLANS, SCHEMATICS AND DIAGRAMS OF OTHER TRADES FOR
ELECTRICAL REQUIREMENTS, BRANCH CIRCUITS AND ELECTRICAL CONNECTIONS NOT
INDICATED ON THESE DOCUMENTS.
ALL PENETRATIONS THROUGH FIRE SEPARATION WALLS ARE TO BE SEALED TO MAINTAIN
SEPARATION RATING.
JUNCTION BOXES FOR LUMINAIRES ARE NOT INDICATED. ELECTRICAL CONTRACTOR IS
RESPONSIBLE FOR PROVIDING THE PROPER NUMBER OF J-BOXES TO MEET LOCAL CODE AND
NATIONAL ELECTRICAL CODE.
DETECTOR
F = FLAME
I = IONIZATION TYPE
P = PHOTOELECTRIC
TYPE
T = THERMAL TYPE
DETECTOR UNDER FLOOR
F = FLAME
I = IONIZATION TYPE
P = PHOTOELECTRIC
TYPE
T = THERMAL TYPE
PULL STATION/TELEPHONE JACK
MAGNETIC DOOR HOLD OPEN
BEAM DETECTOR
H
X
B
XX
COMBINATION TELEPHONE/DATA OUTLET
DATA OUTLET
TELEPHONE OUTLET
TELEVISION JACK
CEILING MOUNTED DATA OUTLET
CEILING MOUNTED TELE/DATA OUTLET
CEILING MOUNTED TELEPHONE OUTLET
FLOOR MOUNTED DATA OUTLET
FLOOR MOUNTED TELEPHONE/DATA OUTLET
FLOOR MOUNTED TELEPHONE OUTLET
DATA TERMINAL BOARDDTB
M MICROPHONR OUTLET
SPEAKER
V = WITH INTEGRAL VOLUME CONTROL
S
X
R
V
S WALL MOUNTED SPEAKER
SS
MISC. SYSTEM COMPONENT
AMP = AMPLIFIER
ANN = ANNUNCIATOR
ASD = ADJUSTABLE SPEED DRIVE
ATS = AUTOMATIC TRANSFER SWITCH
BMS = BALANCED MAGNETIC STRIP
CAM = CONTROL ADDRESSABLE MODULE
DE = DELAYED EGRESS
DMA = DOOR MANAGEMENT ALARM
DTC = DATA TERMINAL CABINET
DVR = DIGITAL VIDEO RECORDER
EC = ELECTRICAL CONTACTOR
FAA = FIRE ALARM ANNUNCIATOR
FACP = FIRE ALARM CONTROL PANEL
FSD = FIRE SMOKE DAMPER
MAM = MONITOR ADDRESSABLE MODULE
N = NURSE CALL STATION
NCS = NURSE'S CALL MASTER STATION
NCT = NURSE CALL TERMINAL CABINET
PIR = PASSIVE INFRARED DETECTOR
SAP = SECURITY ALARM PANEL
SPD = SURGE PROTECTIVE DEVICE
VFD = VARIABLE FREQUENCY DRIVE
XXX
X = FIXTURE DESIGNATION
X,*
LOCATIONS AND INFORMATION FOR EXISTING ELECTRICAL DEVICES AND EQUIPMENT SHOWN ON THESE PLANS ARE APPROXIMATE. THIS INFORMATION IS DERIVED FROM FIELD OBSERVATIONS AND RECORD DRAWINGS THAT WERE AVAILABLE AT THE TIME THESE DRAWINGS WERE ISSUED FOR PUBLICATION. THE CONTRACTOR IS TO
VERIFY ACTUAL FIELD CONDITIONS PRIOR TO STARTING WORK.
UP-TO-DATE AS-BUILT ELECTRICAL PLANS ARE NOT AVAILABLE FOR THIS BUILDING. INFORMATION FOR EXISTING CIRCUITRY IS BASED ON EXISTING PANEL DIRECTORIES, AVAILABLE DRAWINGS, AND ASSUMPTIONS. IF SIGNIFICANT DISCREPANCIES ARE FOUND THAT CANNOT BE EASILY DEALT WITH, CONTACT THE ARCHITECT OR
ENGINEER.
DUPLEX-2PORT USB
4PORT USB
BJ BONDING JUMPER
GENERAL NOTES
GROUND ROD
FOURPLEX EMERGENCY / CRITICAL
ENCLOSED CIRCUIT BREAKER
SWITCH SYMBOL (#)
SINGLE POLE (IF BLANK)
2 = DOUBLE POLE
3 = THREE-WAY
4 = FOUR-WAY
AS = ADJUSTABLE SPEED
D = DIMMER
K = KEY OPERATED
LV = LOW VOLTAGE
M = MANUAL MOTOR SWITCH
OS = OCCUPANCY SENSOR
P = WITH PILOT LIGHT
T = TIMER
TO = THERMAL OVERLOAD
VS = VACANCY SENSOR
WP = WEATHERPROOF
x = SMALL LETTER INDICATES LUMINAIRES CONTROLLED
XP = EXPLOSION PROOF
FLEXIBLE CONDUIT
CONDUIT BREAK SYMBOL
CONDUIT CAP
CONDUIT CHANGE IN ELEVATION
CONDUIT STUB DOWN (OUT OF DRAWING LIMITS)
CONDUIT STUB UP (OUT OF DRAWING LIMITS)
NORTH ARROW
SYMBOL DESCRIPTION
KEY NOTE
REVISION NUMBER
DETAIL NOTE
X = DENOTES ALL LUMINAIRES IN THE RESPECTIVE AREA
ARE THE TYPE INDICATED UNLESS NOTED OTHERWISE,
REFER TO LUMINAIRE SCHEDULE
MECHANICAL EQUIPMENT TAG
SHADING INDICATES EQUIPMENT
ROOM NUMBER
DETAIL BUBBLE
HATCHING INDICATES ITEM(S) TO BE REMOVED
SECTION CUT
E2.1
DETAIL NUMBER
SHEET NUMBER - WHERE DETAIL IS SHOWN
TAG
A100
SECTION NUMBER/LETTER
SHEET NUMBER - WHERE DETAIL IS SHOWN
- GRAPHIC SYMBOLS -
XXX
X
X
REV: 2/23/2016
S# # LIGHTING CONTROL SEQUENCE NUMBER
DAYLIGHT DIMMING MAXIMUM ILLUMINATION SET-POINT
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
ELECTRICAL LEGEND
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
E-01 10 16
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
J
M
J
J
J
S
GFI, WP
GFI
GFI
42"
GFI
42"
R
R
R
R
RR
R
R
R
S
+96"
+46"
+46"
+46"
+50"
M
+46"
+42"
PANEL
A
PANEL
B
PANEL
C
GFI, WP
24"
INSTALL (2) LENEL CARD
READERS
EXISTING SECURITY
WIRE FOR LENEL
SYSTEM
LENEL SECURITY
SYSTEM PANEL
BOTTOM LEVEL
TOP LEVEL
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
EXISTING POWER
PLAN VIEW
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
E-02 11 16
N
Feet
0 15 30
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
D
SS
S
D
S
S
D
S
S
SSS3
S S
S
S
S
S S
S
S S
S
S3
S S
S
D
S
S
S
S
S S
SSS3
S
BOTTOM LEVEL
TOP LEVEL
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
LIGHTING PLAN VIEW
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
E-03 12 16
N
Feet
0 15 30
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
2-WAY MOTOR CONTROL VALVE
M
3-WAY MOTOR CONTROL VALVE
CHECK VALVE
BALANCE VALVE
FLOW MEASURING STATION
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
NORTH ARROW
- GRAPHIC SYMBOLS -
- ABBREVIATIONS -
AFF ABOVE FINISHED FLOOR
BDD BACK DRAFT DAMPER
BFF BELOW FINISHED FLOOR
CL CENTERLINE
CO CLEANOUT
(E) EXISTING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ELEV ELEVATION
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
FFE FINISHED FLOOR ELEVATION
IE INVERT ELEVATION
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMP.
MA MIXED AIR
(N) NEW
NC NORMALLY CLOSED
NO NORMALLY OPEN
OA OUTSIDE AIR
OTCS OPEN TO CEILING SPACE
RA RETURN AIR
SA SUPPLY AIR
TSP TOTAL STATIC PRESSURE
VTR VENT THROUGH ROOF
SHADING INDICATES MECHANICAL EQUIPMENT
MECHANICAL EQUIPMENT TAG
KEY NOTE
HATCHING INDICATES ITEM(S) TO BE REMOVED
GENERAL NOTES:
CONTRACTOR SHALL REFERENCE SPECIFICATIONS FOR CONSTRUCTION MATERIALS
AND INSTALLATION PROCEDURES. SPECIFICATIONS ARE A PART OF THE
CONSTRUCTION DOCUMENTS. SHOULD ANY CONFLICT ARISE BETWEEN THE DRAWINGS
AND SPECIFICATIONS, SUCH CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER FOR RESOLUTION.
ALL PENETRATIONS THROUGH FIRE RATED WALLS OR FLOORS SHALL BE SEALED TO
MAINTAIN SEPARATION RATING.
THESE DRAWINGS ARE DIAGRAMMATIC IN CHARACTER AND DO NOT NECESSARILY
INDICATE EVERY REQUIRED OFFSET, FITTING, ETC.
ALL DUCTWORK DIMENSIONS SHOWN ARE INTERIOR CLEAR DIMENSIONS. ALLOWANCES
FOR DUCT LINER OR INSULATION ARE NOT INCLUDED.
COPYRIGHT, THE RMH GROUP, INC 2016
TS
ZONE #
T
ZONE #
HS
ZONE #
CO
ZONE #
CO
GLOBE VALVE
PRESSURE REDUCING VALVE
PLUG VALVE
PRESSURE RELIEF VALVE
HOSE END DRAIN VALVE
STRAINER
STRAINER WITH BLOW OFF VALVE
GAS COCK
SOLENOID VALVE
PRESSURE REGULATING VALVE
VENTURI
THERMOWELL
THERMOMETER WITH THERMOWELL
UNION
DIELECTRIC COUPLING
AUTOMATIC AIR VENT
MANUAL AIR VENT
VACUUM BREAKER
DIFFERENTIAL PRESSURE GAUGE
THERMOMETER
GAUGE
GAUGE WITH BALL VALVE
PRESSURE TEMPERATURE/TEST POINT
PIPE ANCHOR
PIPE GUIDE
STEAM TRAP (INVERTED BUCKET TRAP)
FLEX CONNECTION
PIPE CAP
STEAM TRAP (THERMOSTATIC TRAP)
STEAM TRAP (FLOAT AND THERMOSTATIC TRAP)
FIRE HOSE CABINET
DOWNSPOUT NOZZLE
PIPE DOWN
THERMOSTAT W/ZONE CALLOUT
HUMIDITY SENSOR W/ZONE CALLOUT
ANALOG INPUT
TEMP SENSOR W/ZONE CALLOUT
CARBON MONOXIDE DETECTOR
CARBON DIOXIDE SENSOR
DIGITAL INPUT
DIGITAL OUTPUT
ANALOG OUTPUT
BI-DIRECTIONAL NETWORK CONNECTION
WELL MOUNTED TEMPERATURE SENSOR
FLOW ARROW
FLOW SWITCH
DUCT MOUNTED TEMPERATURE SENSOR
DUCT AVERAGING TEMPERATURE SENSOR
MOTORIZED CONTROL DAMPER
TEMPERATURE LOW LIMIT THERMOSTAT
DUCT SMOKE DETECTOR
AQUASTAT
DAMPER/VALVE END SWITCH
DIFFERENTIAL PRESSURE SWITCH
HIGH PRESSURE SWITCH
PRESSURE SWITCH MANUAL RESET
MOTOR STARTER
ELECTRIC MOTOR
FLOW TRANSMITTER
ANNUNCIATOR
AIR FLOW SWITCH
ROOF DRAIN
OVERFLOW DRAIN
WALL CLEANOUT
FLOOR SINK
FLOOR DRAIN
FLOOR CLEANOUT
GRADE CLEANOUT
WALL HYDRANT
DIFFUSER REGISTER, GRILLE CFM CALLOUT
DIFFUSER, REGISTER, GRILLE CFM CALLOUT W/
QUANTITY
BASEBOARD/FINTUBE RADIATION HEATING
DETAIL BUBBLE
DETAIL NUMBER
SHEET NUMBER - WHERE DETAIL IS SHOWN
SECTION CUT
VAV TERMINAL BOX CALLOUT
PRV
RD
OD
FS
FD
FCO
GCO
WCO
HB
NECK
CFM
M2.1
XXX
REVISION NUMBER
PIPE BREAK
CONNECT TO EXISTING
SECTION LETTER
SHEET NUMBER
DE
FS
WATER METER
M
M
TYPE
TYPE
TYPE
TYPE
LENGT
H
TAG
MD
S
FIRE DEPARTMENT CONNECTION
DESCRIPTIONSYMBOLABBR.
MECHANICAL LEGEND
(NOTE: NOT ALL SYMBOLS SHOWN ARE USED ON THESE DRAWINGS)
POSITIVE PRESSURE DUCT UP
CONICAL FITTING WITH DAMPER
ELBOW WITH TURNING VANES
ECCENTRIC FITTING WITH DAMPER
CONICAL FITTING WITHOUT DAMPER
ECCENTRIC FITTING WITHOUT DAMPER
LONG RADIUS ELBOW
SHORT RADIUS ELBOW
SUPPLY DIFFUSER
SUPPLY DIFFUSER ROUND NECK
SUPPLY DIFFUSER SQUARE NECK
EXHAUST/ RETURN GRILLE SQUARE NECK
EXHAUST/ RETURN GRILLE ROUND NECK
RETURN AIR GRILLE
DUCTWORK
ROUND DIFFUSER
SLOT DIFFUSER
FLEXDUCT
MANUAL VOLUME DAMPER
FIRE DAMPER 1-1/2 HOUR UNLESS NOTED
FIRE SMOKE DAMPER 1-1/2 HOUR UNLESS NOTED
ACCESS PANEL (SIZE)
SMOKE DAMPER
MOTORIZED DAMPER
SECURITY BARRIER
PUMP
DUCT BREAK
REDUCED PRESSURE BACKFLOW PREVENTER
DOUBLE CHECK VALVE ASSEMBLY
ELBOW WITHOUT TURNING VANES
SA
MVD
RPBP
DCVA
MD
POSITIVE PRESSURE DUCT DOWNSA
NEGATIVE PRESSURE DUCT UPEA/RA
NEGATIVE PRESSURE DUCT DOWNEA/RA
OUTSIDE AIR PRESSURE DUCT UPOA
OUTSIDE AIR PRESSURE DUCT DOWNOA
ROUND DUCT UP
ROUND DUCT DOWN
RPBP
DCVA
DESCRIPTIONSYMBOLABBR.
M
GAS METER
FLOW ARROW
IBT
T
TT
T
FTT
T
FIRE SPRINKLER PENDANT HEAD
FIRE SPRINKLER UPRIGHT HEAD
FIRE SPRINKLER SIDEWALL HEAD
PIPE UP
TEE OUTLET UP
TEE OUTLET DOWN
HEATING HOT WATER SUPPLY
HEATING HOT WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
COOLING TOWER SUPPLY
COOLING TOWER RETURN
LOW PRESSURE STEAM SUPPLY
LOW PRESSURE STEAM RETURN
HWSHWS
DESCRIPTIONSYMBOLABBR. DESCRIPTIONSYMBOLABBR. DESCRIPTIONSYMBOLABBR.
HWRHWR
CWSCWS
CWRCWR
CTSCTS
CTRCTR
LPS
LPR
LPS
LPR
MEDIUM PRESSURE STEAM SUPPLYMPS
MPR
MPS
MPR
HIGH PRESSURE STEAM SUPPLYHPS
HPR
HPS
HPR
CONDENSER WATER SUPPLYCDS
CDR
CDS
CDR
REFRIGERANT LIQUIDRL
RS
RL
RS
REFRIGERANT HOT GASRHG
FOS
RHG
FOS
FUEL OIL RETURNFOR
FOV
FOR
FOV
COMPRESSED AIRCA
PC
CA
PC
CONDENSATE OR EQUIPMENT DRAIND
GHXS
D
GHXS
GEOTHERMAL HX RETURNGHXR GHXR
DOMESTIC HOT WATER
DOMESTIC TEMPERED WATERLPS
LPR
T
DI
DOMESTIC VENT PIPINGLPS
AV
V
AV
SUSPENDED WASTEW
W
W
W
ACID WASTEAW
OST
AW
OST
SUSPENDED STORM DRAINST
ST
ST
ST
MEDIUM PRESSURE STEAM RETURN
HIGH PRESSURE STEAM RETURN
CONDENSER WATER RETURN
REFRIGERANT SUCTION
FUEL OIL SUPPLY
FUEL OIL VENT
PUMPED CONDENSATE
GEOTHERMAL HX SUPPLY
DOMESTIC COLD WATER
DOMESTIC HOT WATER CIRCULATING
DEIONIZED WATER
ACID VENT PIPING
BURIED WASTE
OVERFLOW STORM DRAIN
BURIED STORM DRAIN
DCW
DHW
D
G G NATURAL GAS
FL FL FIRE LINE
FHC
- PIPING - - CONTROLS -
HORIZONTAL CLEANOUT
LOCATIONS AND INFORMATION FOR EXISTING MECHANICAL DEVICES AND EQUIPMENT
SHOWN ON THESE PLANS ARE APPROXIMATE. THIS INFORMATION IS DERIVED FROM
FIELD OBSERVATIONS AND RECORD DRAWINGS THAT WERE AVAILABLE AT THE TIME
THESE DRAWINGS WERE ISSUED FOR PUBLICATION.
TS
TL
SD
ES
DPT
HPS
PS
MS
CONTROL RELAY
CR
VARIABLE FREQUENCY DRIVEVFD
VARIABLE FREQUENCY DRIVE WITH BY-PASS
VFD
B
P
M
TEMPERATURE CONTROLLERTC
LEVEL TRANSMITTERLT
PRESSURE TRANSMITTERPT
DIFFERENTIAL PRESSURE TRANSMITTER
DPT
FT
ELECTRIC\PNEUMATIC TRANSDUCEREPT
CURRENT SWITCH\TRANSMITTER
ANN
FIRE ALARM CONTROL PANELFACP
CONTROL ADDRESSABLE MODULE
CAM
MONITOR ADDRESSABLE MODULE
MAM
EMERGENCY STOP RELAYESR
LEVEL CONTROLLERLC
EMERGENCY POWER OFFEPO
AFS
A
NECK
CFMB
TS
TS
D
Zone
CFM
C
Zone
CFM
REV. 5-18-2015
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
MECHANICAL LEGEND
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
M-01 13 16
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
T
26"x8"
26"x14"
(BELOW)
10"x6"
(TYP)
ø ø ø ø
22"ø
22"ø
22"ø
13"x4"
13"x4"
13"x4"
12"ø
24" x 8"
J
24" x 8"
J
18" x 6"
C
24" x 8"
J
A
9" x 9"
B2
6" x 6"
18" x 6"
F2
18" x 6"
F
18" x 6"
F
12" x 6"
E
18" x 6"
F
12" x 6"
E
12" x 6"
E
12" x 6"
H
12" x 4"
G
12" x 6"
H
26"x8" x
26"x14"
AC-1
AC-2
AC-3
WU-1
BOILER
EXPANSION
TANK
GAS
METER
6"ø
6"ø
6"ø6"ø
EXHAUST
FAN
EXHAUST
FAN
AC-3
24"x20"24"x20"
6" UP TO GRILLES
ON FLOOR ABOVE
(TYP OF 6)
4" EA UP THRU ROOF
DUCTWORK EXPOSED
BELOW CEILING
6"ø
6"ø
24"x24" RETURN AIR
24"x24" RETURN AIR
FLOOR GRILLES
DUCTED FROM BELOW
(TYP OF 6)
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
/29
/23
4:
T
UC
KE
RB
OW
MA
N C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
CA
D\
PA
GO
S
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.29
.23 .D
W G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
HVAC PLAN VIEW
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
M-02 14 16
N
Feet
0 15 30
BBR
BBR
BBR
BBR
1 1/4"
HWS
1 1/4"
HWR
H W
R
H W
S
H W
S
1"
HWS
H W
R
1"
HWR
1"
HWR
BOILER
EXPANSION
TANK
AC-1
AC-2
AC-3
WU-1
(TYP)
(TYP)
BBR
BBR
(TYP)
(TYP)
(TYP)
(TYP)
1" HWR DROP
IN WALL TO BBR
1" HWS DROP
IN WALL TO BBR
1" HWR DROP
IN WALL TO BBR
1" HWS DROP
IN WALL TO BBR
1" HWS DROP
IN WALL TO BBR
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
HYDRONIC PLAN VIEW
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
M-03 15 16
N
Feet
0 10 20
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
BOILER
EXPANSION
TANK
AC-1
AC-2
AC-3
1-1/4" WATER SERVICE
1"
4"
4"
2"
3/4"
1"
1"
2"
4"
WALL
HYDRANT
3/4"
WALL
HYDRANT
3/4"
1 1/4"
G
G
G
G G
G
1"
1 1/4"
1 1/4"
1 1/2"
GAS
METER
FD
FD
1/2"
1"
RPBP
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.
DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
5/1 6/2
4 1 5:
T
UC
KE
RB
OW
MA
N
C:
\U
SE
RS
\T
UC
KE
RB
OW
MA
N\
BO
X\
BU
IL
DI
NG
SS
TR
UC
TU
RE
S\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-2
PR
OJ
EC
TS
\20
_P
RO
JE
CT
S\
PA
GO
SA
S
EC
UR
IT
Y\
DE
SI
GN
\C
AD
\P
AG
OS
A
SE
CU
RI
TY
U
PG
RA
DE
P
RO
JE
CT
C
AD
UP
DA
TE
D
.16 .24
.D W
G;
R02
ROCKY MOUNTAIN REGION
PAGOSA RD
SECURITY
UPGRADE
SAN JUAN NATIONAL
FOREST
PAGOSA RANGER DISTRICT
PLUMBING PLAN VIEW
10/04/2023
USFS/RMH GROUP
T.BOWMAN
A.MCCAW
P-01 16 16
N
Feet
0 10 20
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
| Sheets and Views |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-G-00 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-G-01 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-G-02 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-G-03 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-G-04 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-G-05 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-G-06 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-G-07 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-E-01 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-E-02 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-E-03 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-M-01 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-M-02 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-M-03 |
| OLE1 |
| Pagosa Security Upgrade Project CAD - Updated 05.16.24-P-01 |
| OLE1 |
File details come from the government source that posted it. Updated .